X132_1683970_Design Revision 01_COVER SHEET_DWGS.pdf
PDF 1 MB Posted
- Solicitation number
- N4008524R2710
About this file
This document is a set of construction design drawings and specifications for the modification of a service center and IT customer service room at Building X-132 on the Naval Station Norfolk in Virginia. The drawings include demolition plans, renovation plans, and equipment schedules for HVAC, electrical, and telecommunications systems. The key details are:
The project involves modifying the existing Service Center (Room 179) and IT Customer Service (Room 186) spaces. The design revisions update the mechanical, electrical, and telecommunications plans, including updating unit tags, adding new diffusers/grilles, and revising power and communications raceway and outlet locations. The project has a construction contract number of N/A. The federal agency involved is the Department of the Navy Naval Facilities Engineering Command. No additional information about the solicitation, response dates, award, pricing, or set asides is provided in this document.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PWD Norfolk, Facilities Engineering and Acquisition Division Form Version 2023.11.07 Page 1 of 1
Design Revision 01 eProjects Work Order Number: 1683970
Construction Contract Number:
Building: X-132
Project Title: Modify Service Center (179) IT Customer Service (186)
Date: 22 July 2024
Design Revision Purpose
1. Update unit tags in mechanical plans and schedules.
2. Updated electrical and telecommunications plans.
Drawing Revisions
The following drawings are revised as of 7/22/2024, and accompany this Design Revision:
SHEET NO.
NAVFAC DRAWING NO. SHEET TITLE NO. SHEET
MECHANICAL
16 MD101 12,909,836 PARTIAL FIRST FLOOR MECHANICAL HVAC PLAN - DEMOLITION
17 MH101 12,909,837 PARTIAL FIRST FLOOR MECHANICAL PLAN
18 MI601 12,909,838 MECHANICAL SCHEDULES
ELECTRICAL
19 E-001 12,909,839 ELECTRICAL SYMBOLS, LEGEND, ABBREVIATIONS AND NOTES
22 ED102 12,909842 PARTIAL FIRST FLOOR POWER PLAN - DEMOLITION
24 EP101 12,909,844 PARTIAL FIRST FLOOR POWER PLAN
26 EP501 12,909,846 ELECTRICAL DETAILS
27 EP701 12,909,847 PANELBOARD SCHEDULES
TELECOMMUNICATIONS
28 T-001 12,909,848 TELECOMMUNICATIONS SYMBOLS, LEGEND, ABBREVIATIONS AND NOTES
29 TD101 12,909,849 PARTIAL FIRST FLOOR TELECOMMUNICATIONS PLAN - DEMOLITION
30 TN101 12,909,850 PARTAIL FIRST FLOOR PLAN - TELECOMMUNICATIONS
16 17 18 19
C
D
E
F
HALL
IT CUSTOMER SERVICE
SERVICE CENTER
OPEN OFFICE
OFFICE
TRAINING ROOM
CORRIDOR
CONFERENCE ROOM
181 1
(AHU-9) (AHU-8)
(AHU-10)
(AHU-7)
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K
V A
AS NOTED
MD101
BU
IL
DI
NG
X -1
PA
RT
IA
L
FI
RS
T
FL
O O
R M
EC
HA
NI
CA
L
HV
AC
P
LA
N
-D
EM
O
LI
TI
O
N
MRW
12,909,836
YG DAS
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
JMS
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL SHEET NOTES
KEYNOTES#
A. ALL DUCTWORK AND EQUIPMENT SHOWN ON THIS DRAWING IS
DIAGRAMMATIC. LOCATE ALL DUCTWORK AND EQUIPMENT SO AS TO CLEAR
ALL OBSTACLES.
B. ALL WORK MUST BE PREFORMED IN ACCORDANCE WITH APPLICABLE
FEDERAL, STATE, AND LOCAL CODES.
C. COORDINATE ALL HVAC INSTALLATIONS WITH ALL APPLICABLE TRADES.
D. VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF
INSTALLATION OF ALL MECHANICAL AND PLUMBING EQUIPMENT.
CONSTRUCTION DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTING OFFICER FOR A RESOLUTION.
E. COORDINATE ALL REQUIRED CONDUIT, PIPING, AND CHASES FOR
GOVERNMENT FURNISHED GOVERNMENT INSTALLED EQUIPMENT WITH THE
GOVERNMENT.
F. REFER TO SHEET M-001 FOR GENERAL REQUIREMENTS.
G. REFER TO ARCHITECTURAL, ELECTRICAL, AND TELECOMMUNICATION
DRAWINGS FOR ADDITIONAL INFORMATION.
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR MECHANICAL HVAC PLAN - DEMOLITIONA1
1 NO MECHANICAL WORK IN THIS AREA.
2 REMOVE EXISTING ABOVE CEILING AIR HANDLING UNIT. DISCONNECT
EXISTING ASSOCIATED DUCTWORK, WATER, ELECTRICAL, AND CONTROLS.
3 REMOVE EXISTING DIFFUSER AND REPLACE IN-KIND.
4 REMOVE EXISTING RETURN GRILLE AND REPLACE IN-KIND.
DCA B E
AREA OF WORK
KEY PLAN
(THIS SHEET ONLY)
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
D
ES
I G N
R
EV
IS
IO
N
/2 2/
16 17 18 19
C
D
E
F
HALL
IT CUSTOMER SERVICE
SERVICE CENTER
OPEN OFFICE
OFFICE
TRAINING ROOM
(WSHP-2) (WSHP-1)
(WSHP-4)
(WSHP-3)
CORRIDOR
CONFERENCE ROOM
181 1
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K
V A
AS NOTED
MH101
BU
IL
DI
NG
X -1
PA
RT
IA
L
FI
RS
T
FL
O O
R M
EC
HA
NI
CA
L
HV
AC
P
LA
N
MRW
12,909,837
YG DAS
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
JMS
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL SHEET NOTES
KEYNOTES#
A. ALL DUCTWORK AND EQUIPMENT SHOWN ON THIS DRAWING IS
DIAGRAMMATIC. LOCATE ALL DUCTWORK AND EQUIPMENT SO AS TO CLEAR
ALL OBSTACLES.
B. ALL WORK MUST BE PREFORMED IN ACCORDANCE WITH APPLICABLE
FEDERAL, STATE, AND LOCAL CODES.
C. COORDINATE ALL HVAC INSTALLATIONS WITH ALL APPLICABLE TRADES.
D. VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF
INSTALLATION OF ALL MECHANICAL AND PLUMBING EQUIPMENT.
CONSTRUCTION DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTING OFFICER FOR A RESOLUTION.
E. COORDINATE ALL REQUIRED CONDUIT, PIPING, AND CHASES FOR
GOVERNMENT FURNISHED GOVERNMENT INSTALLED EQUIPMENT WITH THE
GOVERNMENT.
F. REFER TO SHEET M-001 FOR GENERAL REQUIREMENTS.
G. REFER TO ARCHITECTURAL, ELECTRICAL, AND TELECOMMUNICATION
DRAWINGS FOR ADDITIONAL INFORMATION.
DCA B E
AREA OF WORK
KEY PLAN
(THIS SHEET ONLY)
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR MECHANICAL HVAC PLANA1
1 NO MECHANICAL WORK IN THIS AREA.
2 ABOVE CEILING WATER SOURCE HEAT PUMP. RECONNECT EXISTING
ASSOCIATED DUCTWORK, WATER, ELECTRICAL, AND CONTROLS. REFER TO
SCHEDULE ON SHEET MI601 FOR ADDITIONAL INFORMATION.
3 NEW DIFFUSER.
4 NEW RETURN GRILLE.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
D
ES
I G N
R
EV
IS
IO
N
/2 2/
WATER SOURCE HEAT PUMP SCHEDULE
UNIT
TAG
COMPRESSOR
STAGES
NOMINAL
CAPACITY
TONS
FLUID
FLOW
RATE GPM
FLUID
PD FT
H2O
UNIT
VOLTAGE
HZ
TOTAL
EXTERNAL
SP IN H2O
TOTAL
FLA
AMPS
MCA
AMPS
MOP
AMPS
SUPPLY
MOTOR HP
NET
CAPACITY
MBH
NET
SENSIBLE
MBH
EWT
DB
F
LWT
DB
F
AIR
EDB
F
AIR
LDB
F
AIR
LWB
F
BASIS OF DESIGN
103.5 TRANE MODEL GEHE006780.6 55.7 54.1
AIR
EWB
F
66.2865.57.30.08153.653.020.5560265
PHASE
11.72001/2
DESIGN
AIRFLOW
CFM
1.11WSHP-1
102.2 TRANE MODEL GEHE009780.6 58.3 56.866.2867.38.80.08154.023.320.2360265 11.83003/4 1.41WSHP-2
102.7 TRANE MODEL GEHE024780.6 60.4 57.266.28618.523.40.332013.5311.130.3060265 15.28352 3.61WSHP-3
101.4 TRANE MODEL GEHE030780.6 57.7 55.366.2865.527.90.331515.5312.730.3060265 15.98352-1/2 4.61WSHP-4
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K
V A
AS NOTED
MI601
BU
IL
DI
NG
X -1
M
EC
HA
NI
CA
L
SC
HE
DU
LE
S
MRW
12,909,838
YG DAS
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
JMS
M
ID
LA
N
T
P W
D N
O R
F O
L K
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
D
ES
I G N
R
EV
IS
IO
N
/2 2/
PANEL XXXXX
100A, 208Y/120V-30, 4W
FEEDS FROM PANEL MDP
INSTALLED 2019
DRAWING NO. ##,###,###
DEVICE ID
DEVICE RATING
POWER SOURCE
INSTALLATION DATE
NAVFAC DRAWING NUMBER
GENERAL
DEMOLITION AND NEW WORK KEYNOTE - REFER TO "KEYNOTES"
FOR EACH SHEET
# SPECIALTY NOTE - REFER TO "SPECIALTY NOTES" FOR EACH SHEET
X. GENERAL NOTE - REFER TO "GENERAL NOTES" FOR EACH SHEET
OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS
NEW OR PROPOSED FOR CONSTRUCTION, UON.
OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS
EXISTING TO BE REMOVED-DEMOLISHED, UON.
OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS
EXISTING TO REMAIN, UON.
NEW TO EXISTING CONNECTION
REMOVE TO THIS POINT
LIGHTING
LED EXIT LUMINAIRE. ARROW, WHEN USED, INDICATES DIRECTION.
( INDICATES BRACKET, WALL MOUNTED.) FILLED IN QUADRANT(s)
OF SYMBOL INDICATES NUMBER AND ORIENTATION OF ILLUMINATED
FACES.
EMERGENCY BATTERY POWERED LED LIGHTING UNIT.
LED LUMINAIRE. ( INDICATES BRACKET, WALL MOUNTED.)
LED EMERGENCY LUMINAIRE. ( INDICATES BRACKET, WALL
MOUNTED.)
TOGGLE SWITCH, 20A, 120/277V. MOUNT 48" AFF UON. SUBSCRIPT "2"
= 2 WAY, "3" = 3 WAY, "4" = 4 WAY.
DIMMER SWITCH. (WATTAGE AS REQUIRED TO CONTROL THE
LUMINAIRE(S) CONNECTED UON.) MOUNT 48" AFF UON.
OCCUPANCY SENSOR, DUAL TECHNOLOGY. CEILING MOUNTED UON.OS
D
TIME SWITCHTS
HIGH INTENSITY DISCHARGE (H.I.D.) OR COMPACT FLUORESCENT
LUMINAIRE. ( INDICATES BRACKET, WALL MOUNTED.)
XX LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE, SHEET ELXXX.
OCCUPANCY SENSOR CONTROLLER, DUAL TECHNOLOGY. WALL
MOUNTED 48" AFF UON.
OS
POWER
20A, 120V DUPLEX CONVENIENCE RECEPTACLE. MOUNT 18" AFF
UON. 'GFI' DENOTES INTERNAL GROUND FAULT INTERRUPTER, 'WP'
DENOTES WEATHER PROOF ENCLOSURE AND 'C' DENOTES FLUSH
MOUNTED IN CEILING
QUADRUPLEX CONVENIENCE RECEPTACLE MOUNTED IN TWO-GANG
OUTLET BOX - EACH RATED 20A, 125 VOLTS WITH SINGLE COVER
PLATE, MOUNT 18" AFF, UON.
30A, 120V SINGLE OUTLET NEMA 6-30 WITH MATCHING PLUG.
SPECIAL PURPOSE RECEPTACLE. NEMA 6-30R, RATED 30A, 250V
JUNCTION BOX. MINIMUM 4" SQUARE X 2 1/8" SIZE PER NEC.
CEILING FAN, THREE SPEED REVERSIBLE
J
20A, 120V DUPLEX CONVENIENCE RECEPTACLE UTILIZING GROUND
FAULT PROTECTION. MOUNT 6" ABOVE COUNTER UON. 'WP'
DENOTES WEATHER PROOF ENCLOSURE
20A, 120V FLUSH FLOOR DUPLEX RECEPTACLE
SYSTEMS FURNITURE CONNECTION.J
GROUND BAR
EQUIPMENT CONNECTIONS
MOTOR CONNECTION. HP AS INDICATED.
DISCONNECT SWITCH PROVIDED INTEGRAL WITH EQUIPMENT
MAGNETIC MOTOR STARTER
M
E EQUIPMENT CONNECTION
MOTOR RATED SWITCH OR MANUAL MOTOR STARTER WITH
OVERLOADS.
M
MANUAL MOTOR STARTER
DISCONNECT SWITCH. 3P = NO. OF POLES, 30 = SWITCH RATING, 20 =
FUSE RATING (NF = INDICATES NON-FUSED), 3R INDICATES NEMA
RATING.
VFD VARIABLE FREQUENCY DRIVE
3P 20 3R
WIRE, CONDUIT, AND RACEWAY
HOMERUN TO PANEL. PANEL & CIRCUIT DESIGNATIONS AS
INDICATED.
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICK MARKS
INDICATE 2-#12 CONDUCTORS & 1-#12 GND. IN 1/2" CONDUIT UON.
CONDUIT LARGER THAN 1/2" & WIRE LARGER THAN #12 MUST BE
INDICATED.
LADDER RACK CABLE TRAY, SIZE AND TYPE AS INDICATED.
WIRE BASKET CABLE TRAY, SIZE AND TYPE AS INDICATED.
CONDUIT TURNED DOWN
CONDUIT TURNED UP
L2A-1,3
DISTRIBUTION
480Y/277V PANELBOARD.
208Y/120V PANELBOARD.
DRY-TYPE TRANSFORMER. 'T' DENOTES TRANSFORMER
IDENTIFICATION
T
240Y/120V PANELBOARD.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
E-001
BU
IL
DI
NG
X -1
EL
EC
TR
IC
AL
S
YM
BO
LS
, L
EG
EN
D, A
BB
RE
VI
AT
IO
NS
, A
ND
N O
TE
S
CJM
12,909,839
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL ELECTRICAL NOTESELECTRICAL LEGEND
1/C ONE CONDUCTOR
A AMPERAGE OR AMPS
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARF ABOVE RAISED FLOOR
BFG BELOW FINISED GRADE
BH BASEBOARD HEATER
BKR BREAKER
BRF BELOW RAISED FLOOR
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
DWG DRAWING
EA EACH
EC EMPTY CONDUIT
ELEC ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
EXP EXPLOSION PROOF EQUIPMENT
FB FLOOR BOX
FCU FAN COIL UNIT
FT FEET
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFE GOVERNMENT FURNISHED EQUIPMENT
GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GFI GROUND FAULT INTERRUPTER
GND GROUND
HGT HEIGHT
HID HIGH INTENSITY DISCHARGE
HP HORSEPOWER
HUB COMPUTER DISTRIBUTION HUB
LED LIGHT EMITTING DIODE
LTS LUMINAIRE
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG HT MOUNTING HEIGHT
NEC NATIONAL ELECTRICAL CODE
NF NON FUSIBLE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OBI OUTLET BASE INFEED
OS OCCUPANCY SENSOR
PNL PANEL
PNLBD PANELBOARD
PVC POLYVINYL CHLORIDE CONDUIT
QU QUANTITY
REC RECEPTACLE
REQ'D REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
SHT SHEET
SUB SUBSTATION
SWBD SWITCHBOARD
T TELEPHONE
TELECOM TELECOMMUNICATIONS
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTAGE OR VOLTS
VRF VARIABLE REFRIGERANT FLOW UNIT
W WIRE
WP WEATHERPROOF
WSHP WATER SOURCE HEAT PUMP
WW WIREWAY (TROUGH)
X IN SCHEDULES, ITEM NOT APPLICABLE
XFMR TRANSFORMER
Ø PHASE
ELECTRICAL ABBREVIATIONS
A. ALL ELECTRICAL WORK AND MATERIAL IS NEW AND MUST BE PROVIDED BY
THE CONTRACTOR UON.
B. AN EQUIPMENT GROUND WIRE MUST BE RUN WITH FEEDERS AND BRANCH
CIRCUITS.
C. WIRING MUST BE AS PER NATIONAL ELECTRICAL CODE (NEC).
D. ELECTRICAL EQUIPMENT MUST BE IDENTIFIED AND LABELED.
E. FEEDERS/CIRCUITS MUST BE IDENTIFIED AT EACH END OF THE WIRE AND
AT EVERY SPLICE OR JUNCTION/PULL BOX.
F. PROVIDE NAMEPLATES ON THE EXTERIOR OF ELECTRICAL PANELS AND
ENCLOSURES AS FOLLOWS:
FOR DISCONNECT SWITCHES AND MOTOR STARTERS, THE TOP LINE SHALL
BE THE NAME/DESIGNATION OF EQUIPMENT BEING FED BY SAME.
G. PROVIDE NEW TYPED DIRECTORIES FOR PANELS (NEW OR EXISTING)
INCLUDED IN THIS PROJECT.
H. INTERIOR WIRING SYSTEMS MUST BE CONCEALED WITH FLUSH MOUNTED
BOXES/DEVICES, UON.
I. DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD
INVESTIGATIONS. CONTRACTOR MUST VISIT THE EXISTING BUILDING AND
ACQUAINT HIMSELF/HERSELF WITH THE EXISTING CONDITIONS.
CONTRACTOR MUST EXAMINE DRAWINGS TO AVOID CONFLICT.
J. COORDINATE LOCATION AND POWER REQUIREMENTS OF ELECTRICAL
DEVICES WITH MECHANICAL, PLUMBING, ARCHITECTURAL AND FIRE
PROTECTION DRAWINGS.
K. ELECTRICAL DEVICES SHOWN BUT NOT CIRCUITED MUST REMAIN ON
THEIR EXISTING CIRCUIT.
L. PROVIDE ARC-FLASH LABELS ON ALL PANELS/DISCONNECT SWITCHES AS
PER UFC 3-560-01 AND NFPA 70E. SEE DETAIL PLATE ON SHEET EP###.
M. SINGLE PHASE (120/208V) BRANCH CIRCUITS MUST CONSIST OF 2#12 & 1#1
GND. IN 1/2"C UON. THREE PHASE BRANCH CIRCUITS CONSIST OF 3#12 &
1#12 GND IN 1/2"C UON.
N. REFER TO PLANS FOR CONDUCTOR SIZING. COMPLY WITH THE FOLLOWING
GUIDELINES FOR CONDUCTOR RUN LENGTHS:
20A,120V CIRCUITS LONGER THAN 100' - USE #10 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 120V CIRCUITS LONGER THAN 150' - USE #8 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
20A, 277V CIRCUITS LONGER THAN 150' - USE #10 AWG TO LIMIT VOLTAGE
DROP ON BRANCH CIRCUITS TO 3%
O. COORDINATE ELECTRICAL WORK WITH ARCHITECTURAL, MECHANICAL AND
FIRE PROTECTION WORK PRIOR TO FABRICATION AND INSTALLATION TO
PREVENT CONFLICTS. NOTIFY CONTRACTING OFFICER WHERE CONFLICTS
ARE DISCOVERED PRIOR TO CONSTRUCTION AND BEFORE BEGINNING
WORK IN THOSE AREAS. ALL CONFLICTS THAT ARISE DUE TO LACK OF
COORDINATION MUST BE RECTIFIED BY THE CONTRACTOR AT NO COST TO
THE GOVERNMENT.
P. PROVIDE A MINIMUM OF 2 WEEKS NOTICE OF POWER OUTAGES TO
ACTIVITY AND CONTRACTING OFFICER.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
E
E E E
UPS-15
UPS-14
P8
1 1 1
P9
UPS-16
NIPR
CABINET
SIPR CABINETS
(TYP OF 3)
TYP
AHU-10
AHU-9 AHU-8
AHU-7
13 13
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
ED102
BU
IL
DI
NG
X -1
PA
RT
IA
L
FI
RS
T
FL
O O
R
PO
W
ER
P
LA
N -D
EM
O
LI
TI
O N
CJM
12,909,842
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL SHEET NOTES
KEYNOTES
DCA B E
AREA OF WORK
KEY PLAN
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR POWER PLAN - DEMOLITIONA1
1 NO ELECTRICAL WORK IN THIS AREA.
2 DEMOLISH SPECIAL PURPOSE RECEPTACLE, CONDUIT AND WIRING
COMPLETE.
3 DEMOLISH PDU AND FLOOR BOX#1 WITH1-QUAD RECEPTACLE, CONDUIT
AND WIRING BACK TO PANEL UPS16-1.
4 DEMOLISH FLOOR BOX#2 WITH 1-QUAD RECEPTACLE, CONDUIT AND WIRING
BACK TO PANEL UPS16-3.
5 DEMOLISH FLOOR BOX #3 WITH 1-QUAD RECEPTACLE, CONDUIT AND WIRING
BACK TO PANEL UPS16-5.
6 DEMOLISH FLOOR BOX #4 WITH 1-QUAD RECEPTACLE, CONDUIT AND WRING
BACK TO PANEL UPS16-7.
7 EXISTING 12"W X 4"H TELECOM CABLE TRAY MOUNTED BELOW RAISED
FLOOR TO REMAIN.
8 IN FLOOR BOX#1, DISCONNECT AND REMOVE 3-FIBER, 1 VOICE, 1-NIPR DATA
AND 1-SIPR DATA CABLING AND CONNECTORS/PORTS. PULL CABLES BACK
TO APPROPRIATE TELECOM CABINET IN ROOM 179.
9 IN FLOOR BOX#2, DISCONNECT AND REMOVE 3-FIBER PORTS AND CABLES.
PULL CABLES BACK TO APPROPRIATE TELECOM CABINET IN ROOM 179
10 IN FLOOR BOX#3, DISCONNECT AND REMOVE 3-NIPR PORTS AND CABLES.
PULL CABLES BACK TO NIPR CABINET IN ROOM 179.
11 IN FLOOR BOX#4, DISCONNECT AND REMOVE 3-FIBER AND 5-NIPR DATA
PORTS AND CABLES. PULL CABLES BACK TO APPROPRIATE TELECOM
CABINET IN ROOM 179.
12 EXISTING RECEPTACLES TO REMAIN. SHOWN ONLY FOR CLARITY.
13 DISCONNECT EXIST SWITCH AND CKT TO AHU. EXIST SWITCH AND CKT TO
REMAIN FOR REUSE. CKT INCLUDES CONDUIT AND WIRING.
A. REFER TO SHEET E-001 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND
GENERAL NOTES.
B. EQUIPMENT SHOWN WITH DASHED LINE MUST BE REMOVED, UON.
C. EXISTING ELECTRICAL EQUIPMENT NOT SHOWN ON DEMOLITION PLAN IS TO
REMAIN AND MUST REMAIN CONNECTED, UON.
D. RECONNECT EXISTING CIRCUIT(S) (INTERRUPTED BY REMOVAL OF
EXISTING DEVICE) TO THE REMAINING ELECTRICAL EQUIPMENT LOCATED
DOWNSTREAM FROM THE POINT OF INTERRUPTION.
(THIS SHEET ONLY)
TYP
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
E
E E E
UPS-15 UPS-14 P8
1 1 1
P8-29
P8-31 P8-26,28
UPS-16-1
UPS-16-3
FB#1
FB#2
FB#3
UPS-16-5
FB#4
UPS-16-7
FB#5
UPS-16-22
FB#6
UPS-16-24
FB#7UPS-16-29
P8-30 P8-32
5 6
UPS-16-27
SIPR WORKSTATION
NIPR WORKSTATION
SIPR SHELF
UPS-16-25
NIPR
SHELF #2
P9
UPS-16
UPS-16-23
NIPR
SHELF #1
FB#8UPS-16-31
UPS-16-26
LP-6
WSHP-4
LP-25
WSHP-1
LP-19WSHP-2
LP-21
WSHP-3
11 11
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
EP101
BU
IL
DI
NG
X -1
PA
RT
IA
L
FI
RS
T
FL
O O
R
PO
W
ER
P
LA
N
CJM
12,909,844
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL SHEET NOTES
KEYNOTES
DCA B E
AREA OF WORK
KEY PLAN
1 NO ELECTRICAL WORK IN THIS AREA.
2 PROVIDE DUPLEX RECEPTACLE FOR REFRIGERATOR AND SURFACE MOUNT
1'-5" ARF.
3 PROVIDE DUPLEX RECEPTACLE FOR MICROWAVE AND SURFACE MOUNT
3'-6" ARF.
4 PROVIDE NEMA 6-30R RECEPTACLE AND SURFACE MOUNT 3'-10" ARF.
PROVIDE 3/4" C WITH 2#10 THWN & 1#10 GND.
5 PROVIDE DIVIDED CHANNEL NONMETALLIC RACEWAY AND SURFACE MOUNT
MIDDLE OF CHANNEL 3'-2" ARF. IN TOP CHANNEL, PROVIDE (4) DUPLEX REC.
IN BOTTOM CHANNEL, PROVIDE (3) 2-PORT RED CAT6 STP COMM MODULES.
FOR POWER, PROVIDE 1/2"C W/2#12 THWN & 1#12 GND. FOR DATA, PROVIDE
2"C W/(6) RED CAT6 STP CABLES.
6 PROVIDE MULTI-CHANNEL NONMETALLIC RACEWAY AND SURFACE MOUNT
MIDDLE OF CHANNEL 3'-2" ARF. IN TOP CHANNEL, PROVIDE (4) DUPLEX REC.
IN MIDDLE CHANNEL, PROVIDE (4) GREEN 2-PORT CAT6 UTP COMM
MODULES. IN BOTTOM CHANNEL, PROVIDE (4) AQUA DUPLEX LC
CONNECTORS. FOR POWER, PROVIDE 1/2"C W/2#12 THWN & 1#12GND. FOR
COMM, PROVIDE 2"C W/(8) GREEN CAT6 UTP AND (8) AQUA OM3 CABLES.
7 PROVIDE RAISED FLOOR BOX FOR POWER AND TELECOMMUNICATIONS.
FLOOR BOX MUST BE PRE WIRED FOR (2) 20A, 120V DUPLEX REC IN SINGLE
GANG BOX. FLOOR BOX MUST (2) SINGLE GANG BOX, ON EACH SIDE OF REC
FOR COMMS WIRING. REFER TO FLOOR BOX LAYOUT, DETAIL C1 ON SHT
EP501.
8 PROVIDE DIVIDED CHANNEL NONMETALLIC RACEWAY AND SURFACE MOUNT
MIDDLE OF CHANNEL 3'-8" ARF. IN TOP CHANNEL, PROVIDE (5) DUPLEX REC.
IN BOTTOM CHANNEL, PROVIDE (5) 2-PORT RED CAT6 STP COMM MODULES.
FOR POWER PROVIDE 1/2"C W/2#12 THWN & 1#12 GND. FOR DATA PROVIDE
2-1/2"C W/(10) RED CAT6 STP CABLES.
9 PROVIDE MULTI CHANNEL NONMETALLIC RACEWAY AND SURFACE MOUNT
MIDDLE OF CHANNEL 3'-8" ARF. IN TOP CHANNEL, PROVIDE (5) DUPLEX REC.
IN MIDDLE CHANNEL, PROVIDE (5) 2-PORT GREEN CAT6 UTP COMM
MODULES. IN BOTTOM CHANNEL, PROVIDE (5) AQUA DUPLEX LC
CONNECTORS. FOR POWER, PROVIDE 1/2"C W/2#12 THWN & 1#12 GND. FOR
COMM, PROVIDE 2-1/2"C W/(10) GREEN CAT6 UTP AND (10) AQUA OM3
CABLES.
10 PROVIDE DUPLEX REC AND SURFACE MOUNT 6" ABOVE COUNTER ON
COLUMN. PROVIDE 1/2"C W/2#12 THWN 7 1#12 GND.
11 RECONNECT EXIST SWITCH AND CKT TO WATER SOURCE HEAT PUMP
(WSHP).
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR POWER PLANA1
A. REFER TO SHEET E-001 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND
GENERAL NOTES.
B. REFER TO SHEET EP701 FOR POWER RISER DIAGRAMS.
C. REFER TO SHEET EP702 FOR PANELBOARD SCHEDULE.
D. RUN ALL CONDUITS BELOW RAISED FLOOR. TRANSITION FROM CONDUIT TO
NONMETALLIC RACEWAY ABOVE RAISED FLOOR.
(THIS SHEET ONLY)
(TYP OF 8)
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
NIPRRECFIBER
BLANK SIPRREC
SIPR
FIBER NIPR
AF-1APRIL 2015
GENERAL ARC FLASH WARNING LABEL
SKETCH DATE STYLE
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC
FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING DESIGN GUIDE
WEBSITE (WWW.WDBG.ORG) FOR USE IN A LABEL MAKING MACHINE.
A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO NAVIGATE TO THIS LOCATION, FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY > NAVFAC CADD
RESOURCES > NAVFAC CADD DETAILS.
B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:
HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=23
WIDTH
HEIGHT
NOTES:
1. PROVIDE ACTIVATION COVER ASSEMBLY THAT COORDINATES WITH USE.
2. COORDINATE WITH POWER AND TELECOMMUNICATION
DRAWINGS FOR FLOOR BOX LOCATION.
3. ROUTE ALL CONDUITS TO FLOOR BOX UNDER EXISTING
RAISED FLOOR.
4. ROUTE COMMUNICATIONS CABLING IN EXISTING CABLE TRAY
LOCATED BELOW RAISED FLOOR. PROVIDE 1" FLEXIBLE CONDUIT
FROM CABLE TRAY TO FLOOR BOX.
5. PROVIDE KNOCKOUTS AS REQUIRED.
6. PROVIDE RECEPTACLES AND COMM OUTLETS AS REQUIRED
PER DETAIL C1 FLOOR BOX LAYOUT ON THIS SHEET.
FLUSH SURFACE COVER
WITH RAISED FLOOR
FINISH INSERT
PROVIDE 3-CAT6 UTP CABLES (2-GREEN DATA &
1-BLACK VOICE) FROM FLOOR BOX TO EXIST
TELECOM CABLE TRAY BELOW RAISED FLOOR TO
NIPR CABINET AND TELECOMMUNICATIONS
BACKBOARD IN ROOM 179
PROVIDE 2#12 THWN & 1#12 GND IN 1" C FROM FLOOR
BOX TO PANEL UPS-16
PROVIDE (2) 2-STRAND, 1-PAIR
AQUA OM3 CABLES FROM
FLOOR BOX TO EXIST
TELECOM CABLE TRAY BELOW
RAISED FLOOR TO NIPR
CABINET IN ROOM 179
PROVIDE 2#12 THWN &
1#12 GND IN 1" C FROM
FLOOR BOX TO
PANEL UPS-16
PROVIDE (2) RED CAT6 STP CABLES FROM FLOOR
BOX TO EXIST TELECOM CABLE TRAY BELOW
RAISED FLOOR TO SIPR CABINET IN ROOM 179
DUPLEX AQUA
LC CONNECTORS
(TYP OF 2)
BLANK ( TYP OF 2)
20A, 120V DUPLEX
REC (TYP OF 2)
GREEN 8-PIN MODULAR
CAT6 UTP DATA MODULES
(TYP OF 2)
BLACK 8-PIN MODULAR
CAT6 UTP DATA MODULE
BLANK
RED 8-PIN MODULAR
CAT6 STP COMM MODULE
(TYP OF 2)
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
EP501
BU
IL
DI
NG
X -1
EL
EC
TR
IC
AL
D
ET
AI
LS
CJM
12,909,846
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
NOT TO SCALE
A4
FLOOR BOX DETAIL
NOT TO SCALE
A1
FLOOR BOX CONFIGURATION
NOT TO SCALE
C1
FLOOR BOX LAYOUT
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
EP701
BU
IL
DI
NG
X -1
PA
NE
LB
O
AR
D
SC
HE
DU
LE
S
CJM
12,909,847
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
TOTAL CONNECTED AMPS: A: 35.8 B: 27.7 C: 13.4
41 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 42
39 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 40
37 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 38
35 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 36
33 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 34
31 MICROWAVE REC RM 179 1/2 12 20 8 A 6 A 20 12 1/2 SIPR WORKBENCH REC 32
29 FRIDGE REC RM 179 1/2 12 20 12 A 6 A 20 12 1/2 SIPR WORKBENCH REC 30
27 A/C UNIT BY FRONT DR -- -- 20 0 A 30 A 28
25 A/C UNIT BY FRONT DR -- -- 20 0 A 30 A
40 10 3/4 TEMP HVAC REC
23 UNKNOWN -- -- 20 0 A 0 A 20 -- -- RM 182 TRNG ROMM 24
21 UNKNOWN -- -- 20 0 A 0 A 20 -- -- RM 180 COMP REC 22
19 SHUNT TRIP -- -- 20 0 A 0 A 20 -- -- RIGHT SIDE FIBER CAB #12 20
17 UNKNOWN -- -- 20 0 A 0 A 20 -- -- RIGHT SIDE FIBER CAB #11 18
15 LEFT FIBER CAB #8 -- -- 20 0 A 0 A 20 -- -- UNKNOWN 16
13 LEFT FIBER CAB #7 -- -- 20 0 A 0 A 20 -- -- UNKNOWN 14
11 UNCLASS CAB #3 -- -- 20 0 A 0 A 20 -- -- CLASS RED CAB #6 12
9 UNCLASS CAB #2 -- -- 20 0 A 0 A 20 -- -- CLASS RED CAB #5 10
7 UNCLASS CAB #1 -- -- 20 0 A 0 A 20 -- -- UNKNOWN 8
5 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 6
3 RM 178 BK RM SWIPE -- -- 20 0 A 0 A 20 -- -- UNKNOWN 4
1 RM 79 WEST REC -- -- 20 0 A 0 A 20 -- -- LENEL SYSTEM 2
CKT
NO. LOAD DESCRIPTION
COND
SIZE
WIRE
SIZE
BKR
TRIP A B C A B C
BKR
TRIP
WIRE
SIZE
COND
SIZE LOAD DESCRIPTION
CKT
NO.
AMP BUS 225 A 208/120 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 10 KAIC SURFACE
PANEL P8 SCHEDULE 1
1 THE CONTRACT MUST TRACE CIRCUITS LABELED UNKNOWN AND UPDATE
PANEL SCHEDULE TO REFER ACTUAL LOAD. IF TRACE DETERMINES THAT
CIRCUIT IS A SPARE, INDICATE IN PANEL SCHEDULE. UPDATED PANEL
SCHEDULES SHALL BE TYPED.
2 PROVIDE 20A/1P CKT BKR IN EXISTING SPACE.
3 PROVIDE TYPED UPDATED PANEL SCHEDULE TO REFLECT CHANGE IN LOAD
DESCRIPTION FROM AHU-10 TO WSHP-4.
4 PROVIDE TYPED UPDATED PANEL SCHEDULE TO REFLECT CHANGE IN LOAD
DESCRIPTION FROM AHU-9 TO WSHP-2.
5 PROVIDE TYPED UPDATED PANEL SCHEDULE TO REFLECT CHANGE IN LOAD
DESCRIPTION FROM AHU-7 TO WSHP-3.
6 PROVIDE TYPED UPDATED PANEL SCHEDULE TO REFLECT CHANGE IN LOAD
DESCRIPTION FROM AHU-8 TO WSHP-1.
TOTAL CONNECTED AMPS: A: 12.5 B: 3.0 C: 6.5
29 SPACE -- -- -- -- -- -- -- -- SPACE 30
27 SPACE -- -- -- -- -- -- -- -- SPACE 28
25 SPACE -- -- -- -- -- -- -- -- SPACE 26
23 SPACE -- -- -- -- -- -- -- -- SPACE 24
21 SPACE -- -- -- -- -- -- -- -- SPACE 22
19 SPACE -- -- -- -- -- -- -- -- SPACE 20
17 SPACE -- -- -- -- 0 A 20 -- -- DAMPERS 18
15 0 A 0 A 20 -- -- UNKNOWN 16
UNKNOWN 30
0 A 6 A 20 REC EAST&SOUTH RM186 14
11 0 A 3 A 20 REC TV 12
UNKNOWN 30
0 A 2 A 20 REC NORTH WALL RM186 10
7 0 A 3 A 20 REC WEST WALL RM186 8
UNKNOWN 30
0 A 3 A 20 REC WEST WALL RM186 6
3 0 A 2 A 20 REC WEST WALL RM186 4
UNKNOWN 30
0 A 3 A 20 REC WEST WALL RM186 2
CKT
NO. LOAD DESCRIPTION
COND
SIZE
WIRE
SIZE
BKR
TRIP A B C A B C
BKR
TRIP
WIRE
SIZE
COND
SIZE LOAD DESCRIPTION
CKT
NO.
AMP BUS 225 A 208/120 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 10 KAIC RECESSED
PANEL P9 SCHEDULE 1
TOTAL CONNECTED AMPS: A: 35.8 B: 27.7 C: 13.4
41 C2 -- -- 20 0 A 0 A 20 -- -- C3 42
39 SPARE IN JBOX -- -- 20 0 A 0 A 20 -- -- D2 40
37 A1 -- -- 20 0 A 0 A 20 -- -- D1 38
35 B1 -- -- 20 0 A 0 A 36
33 A2 -- -- 20 0 A 0 A 34
31 B2 -- -- 20 0 A 0 A
60 REDUNDANT HEAT CRADA
29 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 30
27 A3 #2 -- -- 20 0 A 0 A 20 -- -- D1 #2 28
25 A3 #1 -- -- 20 0 A 0 A 20 -- -- D1 #1 26
23 0 A 0 A 24
UNKNOWN 30
0 A 0 A
30 UNKNOWN
19 0 A 0 A 20 -- -- UNKNOWN 20
UNKNOWN 30
0 A 13 A 18
15 0 A 28 A 16
UNKNOWN 30
0 A 36 A
60 REDUNDANT HEAT CRADA
11 0 A 0 A 12
9 0 A 0 A 10
A3 #2 20
0 A 0 A
20 D1 #2
5 0 A 0 A 6
3 0 A 0 A 4
A3 #1 20
0 A 0 A
20 D1 #1
CKT
NO. LOAD DESCRIPTION
COND
SIZE
WIRE
SIZE
BKR
TRIP A B C A B C
BKR
TRIP
WIRE
SIZE
COND
SIZE LOAD DESCRIPTION
CKT
NO.
AMP BUS 225 A 208/120 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 10 KAIC SURFACE
PANEL UPS-14 SCHEDULE 1
TOTAL CONNECTED AMPS: A: 12.0 B: 9.6 C: 12.0
41 SPACE -- -- -- -- -- -- -- -- SPACE 42
39 SPACE -- -- -- -- -- -- -- -- SPACE 40
37 SPACE -- -- -- -- -- -- -- -- SPACE 38
35 SPACE -- -- -- -- -- -- -- -- SPACE 36
33 SPACE -- -- -- -- -- -- -- -- SPACE 34
31 FB#8 1/2 12 20 2 A -- -- -- -- SPACE 32
29 FB#7 1/2 12 20 3 A -- -- -- -- SPACE 30
27 SIPR SHELF REC 1/2 12 20 8 A -- -- -- -- SPACE 28
25 NIPR SHELF #2 1/2 12 20 8 A 2 A 20 12 1/2 PRINTER REC 26
23 NIPR SHELF #1 1/2 12 20 8 A 3 A 20 12 1/2 FB#6 24
21 UNKNOWN -- -- 20 0 A 3 A 20 12 1/2 FB#5 22
19 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 20
17 UNKNOWN -- -- 20 0 A 0 A 20 -- -- UNKNOWN 18
15 UNKNOWN -- -- 20 0 A 0 A 16
13 UNKNOWN -- -- 20 0 A 0 A
30 UNKNOWN
11 UNKNOWN -- -- 20 0 A 0 A 12
9 SHUNT TRIP -- -- 20 0 A 0 A
30 UNKNOWN
7 FB#4 1/2 12 20 3 A 0 A 8
5 FB#3 1/2 12 20 3 A 0 A
30 UNKNOWN
3 FB#2 1/2 12 20 3 A 0 A 4
1 FB#1 1/2 12 20 3 A 0 A
30 UNKNOWN
CKT
NO. LOAD DESCRIPTION
COND
SIZE
WIRE
SIZE
BKR
TRIP A B C A B C
BKR
TRIP
WIRE
SIZE
COND
SIZE LOAD DESCRIPTION
CKT
NO.
AMP BUS 225 A 208/120 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 100 KAIC RECESSED
PANEL UPS-16 SCHEDULE 1
TOTAL CONNECTED AMPS: A: 0.0 B: 0.0 C: 0.0
29 0 A 0 A 30
27 0 A 0 A 28
PRIMARY FEED CRADA 60
0 A 0 A
60 PRIMARY FEED CRADA
23 TRNG RM FB #81 & #82 -- -- 20 0 A 0 A 20 -- -- UNKNOWN 24
21 TRNG RM FB 80 -- -- 20 0 A 0 A 20 -- -- CONF RM FB #71 & #72 22
19 TRNG RM FB #79 -- -- 20 0 A 0 A 20 -- -- CONF RM TABLE FB #69 20
17 TRNG RM FB #73 & #78 -- -- 20 0 A 0 A 20 -- -- CONF RM FB#70 18
15 TRNG RM FB #74 & #77 -- -- 20 0 A 0 A 20 -- -- CONF RM PLASMAS 16
13 TRNG RM FB #75 & #76 -- -- 20 0 A 0 A 20 -- -- TRNG RM WALL REC 14
11 UNKNOWN -- -- 20 0 A 0 A 20 -- -- RIGHT SIDE FIBER CAB #12 12
9 LEFT SIDE FIBER CAB #8 -- -- 20 0 A 0 A 20 -- -- RIGHT SIDE FIBER CAB #11 10
7 LEFT SIDE FIBER CAB #7 -- -- 20 0 A 0 A 20 -- -- UNKNOWN 8
5 UNCLASSED CAB #3 -- -- 20 0 A 0 A 20 -- -- CLASSED CAB #6 6
3 UNCLASSED CAB #2 -- -- 20 0 A 0 A 20 -- -- CLASSED CAB #5 4
1 UNCLASSED CAB #1 -- -- 20 0 A 0 A 20 -- -- UNKNOWN 2
CKT
NO. LOAD DESCRIPTION
COND
SIZE
WIRE
SIZE
BKR
TRIP A B C A B C
BKR
TRIP
WIRE
SIZE
COND
SIZE LOAD DESCRIPTION
CKT
NO.
AMP BUS 225 A 208/120 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. 10 KAIC SURFACE
PANEL UPS-15 SCHEDULE 1
TOTAL CONNECTED AMPS: A: 6.3 B: 11.9 C: 13.5
41 SPACE -- -- -- -- -- -- -- -- SPACE 42
39 SPACE -- -- -- -- -- -- -- -- SPACE 40
37 SPACE -- -- -- -- -- -- -- -- SPACE 38
35 SPACE -- -- -- -- 0 A 36
33 SPACE -- -- -- -- 0 A 34
31 SPACE -- -- -- -- 0 A
20 DOOR 24
29 SPACE -- -- -- -- 0 A 30
27 SPACE -- -- -- -- 0 A 28
25 AHU-8 -- -- 20 3 A 0 A
20 FIRE RATED DOOR
23 AHU-6 -- -- 20 0 A 0 A 24
21 AHU-7 -- -- 20 11 A 0 A 22
19 AHU-9 -- -- 20 3 A 0 A
15 HP-3
17 EF -- -- 20 0 A 0 A 18
15 LTS COMP ROM NEW ADO -- -- 20 0 A 0 A 16
13 MV1 -- -- 20 0 A 0 A
15 HP-2
11 0 A 0 A 12
9 0 A 0 A 10
HP-4 20
0 A 0 A
15 HP-1
5 LTS WAREHOUSE NORTH -- -- 20 0 A 13 A 20 -- -- AHU-10 6
3 LTS RM 178 -- -- 20 0 A 0 A 20 -- -- HP-5 4
1 LTS RM 178 20 0 A 0 A 20 -- -- LTG RM 178 2
CKT
NO. LOAD DESCRIPTION
COND
SIZE
WIRE
SIZE
BKR
TRIP A B C A B C
BKR
TRIP
WIRE
SIZE
COND
SIZE LOAD DESCRIPTION
CKT
NO.
AMP BUS 225 A 480/277 Wye VOLTS 3PH, 4W, SN, 60HZ MIN. KAIC SURFACE
PANEL LP SCHEDULE
KEYNOTES# (THIS SHEET ONLY)
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
AUDIO/VISUAL
ICIC INTERCOMM
C CLOCK
WTS WIRELESS/WALL TOUCH SCREEN
MICROPHONE. ( INDICATES BRACKET, WALL MOUNTED.)
SPEAKER. ( INDICATES BRACKET, WALL MOUNTED.)
PROJECTOR
TELEVISIONTV
S
M
SECURITY
SECURITY CAMERA
CARD READERCR
BALANCE MAGNETIC SWITCHBMS
DOOR PROP ALARMA
DOOR STRIKEDS
SYSTEMS PUSH BUTTON
TELEPHONE/DATA
TELEPHONE OUTLET. MOUNT 18" AFF. UON.
FIBER DATA OUTLET. MOUNT 18" AFF. UON.
TELEPHONE TERMINAL BACKBOARD
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
TYPE "F" CONNECTOR FOR CABLE TELEVISION. SYSTEM MOUNTED
IN SINGLE GANG BOX WITH FACEPLATE.
TMGB
TELECOMMUNICATIONS GROUNDING BUSBARTGB
DATA OUTLET. MOUNT 18" AFF. UON.
VOICE/DATA OUTLET. FLUSH FLOOR MOUNT.
LAN AND DATA SYSTEM MULTI-PORT PATCH PANEL.
CONDUIT, AND RACEWAY
LADDER RACK CABLE TRAY, SIZE AND TYPE AS INDICATED.
WIRE BASKET CABLE TRAY, SIZE AND TYPE AS INDICATED.
CONDUIT TURNED DOWN
CONDUIT TURNED UP
GENERAL
DEMOLITION AND NEW WORK KEYNOTE - REFER TO "KEYNOTES"
FOR EACH SHEET
# SPECIALTY NOTE - REFER TO "SPECIALTY NOTES" FOR EACH SHEET
X. GENERAL NOTE - REFER TO "GENERAL NOTES" FOR EACH SHEET
OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS
NEW OR PROPOSED FOR CONSTRUCTION, UON.
OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS
EXISTING TO BE REMOVED-DEMOLISHED, UON.
OBJECTS ON DRAWINGS AT THIS LINETYPE ARE CATEGORIZED AS
EXISTING TO REMAIN, UON.
NEW TO EXISTING CONNECTION
REMOVE TO THIS POINT
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
T-001
BU
IL
DI
NG
X -1
TE
LE
CO
M
M
UN
IC
AT
IO
NS
S
YM
BO
LS
, L
EG
EN
D, A
BB
RE
VI
AT
IO
NS
, A
ND
N
O
TE
S
CJM
12,909,848
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL TELECOMMUNICATION AND
SPECIAL SYSTMES NOTES
TELECOMMUNICATIONS LEGEND TELECOMMUNICATIONS ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
BFG BELOW FINSHED GRADE
C CONDUIT
EA EACH
EXIST EXISTING
GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
QU QUANTITY
REQ'D REQUIRED
RM ROOM
SHT SHEET
T TELEPHONE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
A. SPECIAL SYSTEMS ARE AUDIOVISUAL AND ELECTRONIC SECURITY
SYSTEMS.
B. THE COPPER HORIZONTAL CABLING THROUGHOUT THE AREA DOES NOT
EXCEED 295 FEET TO MEET EIA/TIA STANDARDS. ROUTE PATHWAYS AND
CABLES TO ENSURE THIS DISTANCE IS NOT EXCEEDED.
C. HORIZONTAL CABLING SERVING WALL MOUNTED COMMUNICATIONS
OUTLETS MUST BE ROUTED FROM COMMUNICATIONS OUTLET IN MINIMUM
1" CONDUIT FROM EACH COMMUNICATIONS OUTLET TO AREA CABLE TRAY
AND IN AREA CABLE TRAY TO SERVICE CENTER (179). ROUTE CONDUITS IN
FINISHED AREAS CONCEALED IN WALL, UON. WHERE COMMUNICATIONS
OUTLETS ARE INSTALLED EXPOSED, CONDUITS MUST BE SURFACE
MOUNTED. CONDUIT ROUTED EXPOSED MUST BE PAINTED TO MATCH
ADJACENT SURFACES.
D. HORIZONTAL CABLING SERVING WALL MOUNTED SYSTEMS FURNITURE
JUNCTION BOX FEEDS MUST BE ROUTED FROM OUTLET LOCATION ON
SYSTEMS FURNITURE, VIA SYSTEMS FURNITURE WIRE CHANNELS,
THROUGH WALL JUNCTION BOX, IN CONDUIT TO CABLE TRAY, AND IN CABLE
TRAY TO SERVICE CENTER (179). PROVIDE MINIMUM TWO 1" CONDUITS
FROM EACH WALL MOUNTED SYSTEMS FURNITURE JUNCTION BOX FEED TO
AREA CABLE TRAY. PROVIDE SPIRAL WRAP FOR COMMUNICATIONS CABLES
TO MODULAR FURNITURE CONNECTION POINT.
E. ALL ELECTRONIC SECURITY MUST BE COORDINATED WITH THE ACTIVITY
SITE SECURITY OFFICER PRIOR TO INSTALLATION.
F. THE EXISTING ESS IS LENEL.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
1 1 1
8 9
NIPR
CABINET
SIPR CABINETS
(TYP OF 3)
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
TD101
BU
IL
DI
NG
X -1
PA
RT
IA
L
FI
RS
T
FL
O O
R
TE
LE
CO
M M
UN
IC
AT
IO
NS
P
LA
N
-D
EM
O
LI
TI
O
N
CJM
12,909,849
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR TELECOMMUNICATIONS PLAN - DEMOLITIONA1
GENERAL SHEET NOTES
KEYNOTES
DCA B E
AREA OF WORK
KEY PLAN
# (THIS SHEET ONLY)
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
1 NO TELECOMMUNICATIONS WORK IN THIS AREA.
2 REFER TO KEYNOTE #8 ON SHEET ED102.
3 REFER TO KEYNOTE #9 ON SHEET ED102.
4 REFER TO KEYNOTE #10 ON SHEET ED102.
5 REFER TO KEYNOTE #11 ON SHEET ED102.
6 EXISTING CABLE TRAY LOCATED BELOW RAISED ACCESS FLOOR SHALL
REMAIN.
7 DEMOLISH FIBER OUTLETS, PULL BACK 3-FIBER CABLES BACK TO SIPR
CABINET IN ROOM 179. PROVIDE BLANK COVER PLATE.
8 DEMOLISH SIPR OUTLET, PULL BACK 4-SIPR CABLES BACK TO SIPR CABINET
IN ROOM 179. PROVIDE BLANK COVER PLATE.
9 DEMOLISH VOICE OUTLET, PULL BACK 6-VOICE CABLES BACK TO
TELECOMMUNICATIONS BACKBOARD IN ROOM 179. PROVIDE BLANK COVER
PLATE.
10 EXISTING NIPR CABINET TO REMAIN.
11 EXISTING SIPR CABINETS TO REMAIN.
12 EXISTING CATV OUTLETS TO REMAIN. CATV CABLE LOCATED IN EXISTING
CABLE TRAY UNDER RAISED ACCESS FLOOR TO REMAIN.
A. REFER TO SHEET T-001 FOR TELECOMMUNICATIONS & SPECIAL SYSTEMS
SYMBOLS, LEGEND, ABBREVIATIONS, AND GENERAL NOTES.
B. COORDINATE THE DISCONNECTION AND REMOVAL OF EXISTING
TELECOMMUNICATION CABLES WITH ACTIVITY PRIOR TO DISCONNECTION
AND REMOVAL.
1 1 1
SIPR
CABINETS NIPR CABINET
TELECOMMUNICATIONS
BACKBOARD
SIPR
WORKSTATION
NIPR
WORKSTATION
EXIST
TELECOM
CABLE TRAY
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
TN101
BU
IL
DI
NG
X -1
FL
O
O R
PL
AN
TE
LE
CO
M M
UN
IC
AT
IO
NS
CJM
12,909,850
FVP FVP
05/09/2024
JECC - MICHAEL FREDERICK
M O
DI
FY
S
ER
VI
CE
C
EN
TE
R
(1
IT
C
US
TO
M
ER
S
ER
VI
CE
(1
DUSTIN A. SCHULZE, R.A.
1683970
N/A
N O
R
FO
LK
, V
IR
G
IN
IA
N
AV
AL
S
TA
TI
O N
J. MILLER, P.E.
CJM
M
ID
LA
N
T
P W
D N
O R
F O
L K
GENERAL SHEET NOTES
KEYNOTES
DCA B E
AREA OF WORK
KEY PLAN
# (THIS SHEET ONLY)
0 2' 4' 8'
PLAN
NORTH
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR TELECOMMUNICATIONS PLANA1
1 NO TELECOMMUNICATIONS WORK IN THIS AREA.
2 REFER TO KEYNOTE 5 ON SHEET EP101. IN BOTTOM OF DIVIDED CHANNEL
RACEWAY, PROVIDE (3) 2-PORT RED CAT6 STP COMM MODULES. PROVIDE 2"
C W/(6) RED CAT6 STP CABLES FROM RACEWAY TO EXIST CABLE TRAY AND
CONNECT TO SIPR CABINET.
3 REFER TO KEYNOTE 6 ON SHEET EP101. IN MIDDLE OF MULTI-CHANNEL
RACEWAY, PROVIDE (4) 2-PORT GREEN CAT6 UTP COMM MODULES. IN
BOTTOM CHANNEL, PROVIDE (4) AQUA DUPLEX LC CONNECTORS. PROVIDE
2" C W/(8) GREEN CAT6 AND (8) 2-STRAND, 1-PAIR AQUA OM3 CABLES FROM
CHANNEL TO EXIST CABLE TRAY AND CONNECT TO NIPR CABINET.
4 REFER TO KEYNOTE 8 ON SHEET EP101. IN BOTTOM OF DIVIDED CHANNEL
RACEWAY, PROVIDE (5) 2-PORT RED CAT6 STP COMM MODULES. PROVIDE
2-1/2" C W/(10) RED CAT6 STP CABLES FROM RACEWAY TO EXIST CABLE
TRAY AND CONNECT TO SIPR CABINET.
5 REFER TO KEYNOTE 9 ON SHEET EP101. IN MIDDLE OF MULTI-CHANNEL
RACEWAY, PROVIDE (5) GREEN CAT6 UTP COMM MODULES. IN BOTTOM
CHANNEL, PROVIDE (5) AQUA DUPLEX LC CONNECTORS. PROVIDE 2-1/2" C
W/(10) GREEN CAT6 AND (10) 2-STRAND, 1-PAIR AQUA OM3 CABLES FROM
CHANNEL TO EXIST CABLE TRAY AND CONNECT TO NIPR CABINET. ALL
PORTS NOT SHOWN ON PLAN FOR CLARITY.
6 REFER TO KEYNOTE 7 ON SHEET EP101 AND FLOOR BOX LAYOUT, DETAIL C1
ON SHEET EP501. IN EACH FLOOR BOX, PROVIDE THE FOLLOWING: FIBER-(2)
AQUA LC CONNECTORS, (2) 2-STRAND, 1-PAIR AQUA OM3 CABLES TO EXIST
CABLE TRAY AND CONNECT TO NIPR CABINET; FOR NIPR-(2) GREEN AND (1)
BLACK CAT6 UTP COMM MODULES; FOR NIPR DATA-(2) GREEN CAT6 UTP
CABLES TO EXIST CABLE TRAY AND CONNECT TO NIPR CABINET; FOR
VOICE-(1) BLACK CAT6 UTP CABLE TO EXIST CABLE TRAY TO
TELECOMMUNICATIONS BACKBOARD; FOR SIPR-(2) RED CAT6 STP COMM
MODULES AND (2) RED CAT6 STP CABLES TO EXIST CABLE TRAY AND
CONNECT TO SIPR CABINET.
A. REFER TO SHEET T-001 FOR TELECOMMUNICATIONS & SPECIAL SYSTEMS
SYMBOLS, LEGEND, ABBREVIATIONS, AND GENERAL NOTES.
B. COORDINATE WITH THE SYSTEMS FURNITURE PROVIDER TO ENSURE THAT
COMMUNICATION POLES ARE OF ADEQUATE SIZE TO ACCOMMODATE THE
TYPE AND QUANTITY OF COMMUNICATIONS CABLINGS.
C. CLASSIFIED COMMUNICATIONS CABLING MUST BE CAT 6 SHIELDED TWISTED
PAIR (STP).
D. UNCLASSIFIED COMMUNICATIONS CABLING MUST BE CAT 6 UNSHIELDED
TWISTED PAIR (UTP).
E. FIBER OPTIC CABLING MUST BE OM3.
F. COORDINATE CONNECTION OF TELECOMMUNICATIONS WITH ACTIVITY. SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
R ev is i on
/2
4/
FB#7
FB#8
FB#5
FB#3
FB#4
FB#6
FB#1
FB#2
(TYP OF 8)
File details come from the government source that posted it. Updated .