ATTACHMENT B - X132_12909821-12909851_DWGS.pdf

PDF 4 MB Posted

Attached to
X-132 Modify Service Center 179 and IT Customer Service Rm 186
Solicitation number
N4008524R2710
Issued by

About this file

This document is a set of architectural, mechanical, electrical, and telecommunications drawings for the renovation of Building X-132 at the Naval Station Norfolk in Virginia. The project involves modifying the Service Center (Room 179) and the IT Customer Service (Room 186) areas.

The key details include:

  • The project scope involves demolition and new construction work in the specified areas of Building X-132.
  • The architectural work includes reconfiguring the floor plan, updating finishes, and installing new doors, partitions, and signage.
  • The mechanical work includes replacing existing HVAC systems and modifying the ductwork and controls.
  • The electrical work involves upgrading lighting, power, and telecommunications infrastructure, including new receptacles, cable trays, and data/voice outlets.
  • The project is solicited under Solicitation Number N4008524R2710 by the Department of the Navy, Naval Facilities Engineering Command.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NAVAL STATION - NORFOLK, VIRGINIA

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND MID-ATLANTIC

PUBLIC WORKS DEPARTMENT

FACILITIES ENGINEERING AND ACQUISITION DIVISION

NORFOLK, VIRGINIA

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

GI001

BU

IL

DI

NG

X -1

CO

VE

R

SH

EE

T

PCR

12,909,821

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

BUILDING X-132

MODIFY SERVICE CENTER (179) & IT CUSTOMER SERVICE (186)

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

WILLOUGHBY BAY

NAVAL SUPPORT

ACTIVITY

U.S. NAVAL STATION

SEWELLS POINT

NORFOLK

U.S. NAVAL

AIR STATION

CHESAPEAKE BAY

LITTLE CREEK

U.S. NAVAL

AMPHIBIOUS BASE

VA BEACH

OCEANA

NAVAL AIR

STATION

CHESAPEAKE

SOUTHERN BRANCH

EASTERN BRANCH

ST. JULIEN'S CREEK

U.S. NAVAL ANNEX

ELIZABETH RIVER

58 460

PORTSMOUTH

U.S. ARMY CRANEY

ISLAND DISPOSAL AREA

NANSEMOND RIVER

WESTERN BRANCH

CRANEY

ISLAND NAVY

DEPOT

PROJECT SITE

NORTH

A-901 PHOTOGRAPH

INDICATOR

PHOTOGRAPH NUMBER

SHEET WHERE SHOWN

A1

ROOM

101 ROOM IDENTIFIER

DETAIL NUMBER

SHEET WHERE DRAWN

DETAIL TAG

ROOM NAME

ROOM NUMBER

A-401 INTERIOR ELEVATION

INDICATOR

INTERIOR ELEVATION NUMBER

SHEET WHERE DRAWN

DETAIL NUMBER

SHEET REFERENCED FROM

WALL / PARTIAL BUILDING

SECTION INDICATOR

GENERAL PROJECT SYMBOLS

KEYNOTE INDICATOR

KEYNOTE NUMBER

TRUE NORTH

A-101

A1

A1

A1

A1

GRAPHIC SCALE

GRAPHIC SCALE

0 4' 8' 16'

VIEW NAME

SCALE: 1/8" = 1'-0"A1 (A-101)

0 4' 8' 16'

PLAN

NORTH

VIEW NAME

SCALE: 1/8" = 1'-0"

PLAN TITLE

A1 A-301

SECTION NUMBER

SHEET WHERE DRAWN

BUILDING

SECTION

INDICATOR

A1 A-301

A1

A-301

BUILDING

SECTION NUMBER

SHEET WHERE DRAWN

REVISION NUMBER

REVISION TAG1

PIER 11

PIER 10

PIER 9

PROJECT SITE

BUNKER HILL

DILLINGHAM BLVD

BU

NK

ER

H

ILL

DE

CA

TU

R

AV

E

105TH ST

RO

DG

ER

S

AV

E

HULL ST

PREBLE ST

VIRGINIA AVE

MARYLAND AVE

DILLINGHAM BLVD

MASSEY

HUGHES DR

MARYLAND AVE

NORTH

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

GI002

BU

IL

DI

NG

X -1

LI

ST

O F

SH

EE

TS

, G

EN

ER

AL

P

RO

JE

CT

N

O

TE

S

AN

D

SY

M

BO

LS

PCR

12,909,822

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

LIST OF SHEETS

SHEET NO.

NAVFAC DWG. NO. SHEET TITLENO. SHEET

GENERAL

1 GI001 12,909,821 COVER SHEET

2 GI002 12,909,822 LIST OF SHEETS, GENERAL PROJECT NOTES AND SYMBOLS

ARCHITECTURAL

3 A-001 12,909,823 ARCHITECTURAL ABBREVIATIONS, NOTES, SYMBOLS, AND OVERALL PLAN

4 AD101 12,909,824 PARTIAL FIRST FLOOR PLAN - DEMOLITION

5 AD102 12,909,825 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - DEMOLITION

6 AE101 12,909,826 PARTIAL FIRST FLOOR PLAN

7 AE102 12,909,827 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN

8 AE103 12,909,828 PARTIAL FIRST FLOOR SIGNAGE PLAN

9 AE601 12,909,829 DOOR SCHEDULE AND DETAILS

INTERIORS

10 IF101 12,909,830 PARTIAL FIRST FLOOR FURNITURE PLAN (FOR REFERENCE ONLY)

11 IN101 12,909,831 PARTIAL FIRST FLOOR FINISH PLAN

12 IN601 12,909,832 FIRST FLOOR INTERIOR FINISH SCHEDULE

FIRE PROTECTION

13 FD101 12,909,833 PARTIAL FIRST FLOOR - DEMOLITION

14 FX101 12,909,834 FIRST FLOOR PLAN - FIRE SUPPRESSION

MECHANICAL

15 M-001 12,909,835 MECHANICAL LEGEND, ABBREVIATIONS AND NOTES

16 MD101 12,909,836 PARTIAL FIRST FLOOR MECHANICAL HVAC PLAN - DEMOLITION

17 MH101 12,909,837 PARTIAL FIRST FLOOR MECHANICAL HVAC PLAN

18 MI601 12,909,838 MECHANICAL SCHEDULES

ELECTRICAL

19 E-001 12,909,839 ELECTRICAL SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES

20 E-002 12,909,840 OVERALL ELECTRICAL FIRST FLOOR PLAN

21 ED101 12,909,841 PARTIAL FIRST FLOOR LIGHTING PLAN - DEMOLITION

22 ED102 12,909,842 PARTIAL FIRST FLOOR POWER PLAN - DEMOLITION

23 EL101 12,909,843 PARTIAL FIRST FLOOR LIGHTING PLAN

24 EP101 12,909,844 PARTIAL FIRST FLOOR POWER PLAN

25 EL501 12,909,845 LUMINAIRE DETAILS AND SCHEDULE

26 EP501 12,909,846 ELECTRICAL DETAILS

27 EP701 12,909,847 PANELBOARD SCHEDULES

TELECOMMUNICATIONS

28 T-001 12,909,848 TELECOMMUNICATIONS SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES

29 TD101 12,909,849 PARTIAL FIRST FLOOR TELECOMMUNICATIONS PLAN - DEMOLITION

30 TN101 12,909,850 FLOOR PLAN - TELECOMMUNICATIONS

31 TN501 12,909,851 TELECOMMUNICATIONS DETAILS

VICINITY MAP

GENERAL PROJECT NOTES GOVERNING REGULATIONS

LOCATION MAP

BUILDING CODE:

UNIFIED FACILITIES CRITERIA (UFC) 1-200-01 DoD BUILDING CODE (01 SEPT. 2022)

INTERNATIONAL BUILDING CODE (IBC) 2021

INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2021

ACCESSIBILITY CODE:

ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS (2015)

MECHANICAL CODE:

INTERNATIONAL MECHANICAL CODE (IMC) 2018

ELECTRICAL CODE:

NFPA 70, NATIONAL ELECTRIC CODE (NEC) 2020

PLUMBING CODE:

INTERNATIONAL PLUMBING CODE (IPC) 2018

FIRE PROTECTION & LIFE SAFETY CODE:

UNIFIED FACILITIES CRITERIA (UFC) 3-600-01 FIRE PROTECTION ENGINEERING FOR

FACILITIES (CHANGE 6, 06 MAY 2021)

UNIFIED FACILITIES CRITERIA (UFC) 4-021-01 DESIGN AND O&M: MASS

NOTIFICATION SYSTEMS (CHANGE 1, JANUARY 2010)

NFPA 101, LIFE SAFETY CODE, 2021

NFPA 13, STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS, 2019

NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2019

A. WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION

REQUIRED BY THESE DOCUMENTS. REPAIR THE DAMAGED ITEM(S) WITH

MATERIALS TO MATCH THE ADJACENT MATERIAL, TEXTURE AND COLOR.

B. FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING MATERIALS OR

BEGINNING DEMOLITION.

C. ALL ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND

INSTALLED UNDER THE REQUIREMENTS OF THIS CONTRACT.

D. COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO

THE PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE

ESTABLISHED BY THE CONTRACTING OFFICER. PROPOSED LAY DOWN

AREA IS INDICATED ON OVERALL FLOOR PLAN ON SHEET A-001.

E. MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE

PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL BE

ACCEPTABLE PROVIDED THEY MATCH THE COLOR, FINISHES, TEXTURES

AND PATTERNS OF THE MANUFACTURER LISTED, AND MEET THE TECHNICAL

REQUIREMENTS OF THE SPECIFICATIONS.

F. OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY

REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.

G. CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH

WILL REMAIN OPERATIONAL. AVOID INTERFERENCE WITH THE OPERATIONAL

WORK ROUTINE.

H. ALL SUBMITTALS REQUIRED BY THESE DRAWINGS OR SPECIFICATIONS

MUST BE SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL TO

COMMENCEMENT OF RELATED WORK.

I. STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER,

AND AT ONCE, REPORT TO THE CONTRACTING OFFICER ANY ERRORS,

INCONSISTENCIES, OR OMISSIONS DISCOVERED. ANY CONSTRUCTION

ACTIVITY PERFORMED KNOWING IT INVOLVES A RECOGNIZED ERROR,

INCONSISTENCY OR OMISSION IN THE CONTRACT DOCUMENTS WITHOUT

SUCH NOTICE TO THE CONTRACTING OFFICER, THE CONTRACTOR WILL

ASSUME RESPONSIBILITY FOR SUCH PERFORMANCE AND WILL BEAR THE

AMOUNT OF THE COST OF THE CONSTRUCTION.

J. REFER TO SPECIFICATION 01 14 00 - WORK RESTRICTIONS FOR SPECIAL

SCHEDULING REQUIREMENTS.

SY

M

DE

S C

RI

PT

I O N

DA

TE

DOOR NUMBER

(REFER TO DOOR SCHEDULE)

DOOR TAG

ARCHITECTURAL SYMBOLS

PARTITION TYPE DESIGNATION

(REFER TO PARTITION SCHEDULE)

PARTITION TYPE TAG

PARTITION IN PLAN

A

REFER TO SHEET GI002 FOR

ADDITIONAL PROJECT SYMBOLS

SIGNAGE TYPE

(REFER TO SIGNAGE SCHEDULE)

SIGNAGE TAGA

MATERIALS LEGEND

STEEL

BATT/LOOSE FILL INSULATION

WOOD BLOCKING

ALUMINUM

GYPSUM BOARD

PLYWOOD

ACOUSTICAL TILE CEILING

AREA NOT IN CONTRACT

119118116

101131

MAIN ENTRANCE

107107B

AD101

A1

138A

138B

138C

139146

153163

157 159

151B

147 148

AD102

A1

ST04

A-105

A-102 A-101

A-104A-103

A-128

A-127

ST06

A-126

A-125

A-118

A-124A-123A-122

ST05

A-121

A-120ST03

A-119A-117

A-106

A-107

A-108

A-109

A-110

A-111 A-112

A-113A-114

A-115

A-116

AE101

A1

AE102

A1

182 181

AE103

A1

PROPOSED LAY DOWN AREA. REFER TO GENERAL

NOTES ON GI002 FOR ADDITIONAL INFORMATION. SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

A-001

BU

IL

DI

NG

X -1

AR

CH

IT

EC

TU

RA

L

AB

BR

EV

IA

TI

O

NS

, N O

TE

S, S

YM

BO

LS

, A

ND

O

VE

RA

LL

P

LA

N

PCR

12,909,823

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

APPR APPROVED BY

BLDG BUILDING

CHK CHECKED BY

CLR CLEAR

CMU CONCRETE MASONRY UNIT

DEMO DEMOLITION

DES DESIGNED BY

DIM DIMENSION

DRW DRAWN BY

DWG DRAWING

ELEC ELECTRIC / ELECTRICAL

EQ EQUAL

EXIST EXISTING

FT FOOT, FEET

GA GAUGE

GWB GYPSUM WALL BOARD

HDW HARDWARE

HM HOLLOW METAL

MAX MAXIMUM

MECH MECHANICAL

MFG MANUFACTURING

MIN MINIMUM / MINUTE

MISC MISCELLANEOUS

NIC NOT IN CONTRACT

NO NUMBER

OC ON CENTER

OPH OPPOSITE HAND

PT PAINT

REV REVISION

RM ROOM

SF SQUARE FOOT

SIM SIMILAR

SQ SQUARE

SYM SYMBOL

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

WD WOOD

0 15' 30' 60'

PLAN

NORTH

SCALE: 1" = 30'-0"

OVERALL FIRST FLOOR PLAN

GENERAL ARCHITECTURAL NOTESARCHITECTURAL ABBREVIATIONS

A. ALL ITEMS INDICATED TO BE REMOVED MUST BE DISPOSED OF OFF-SITE

UNLESS OTHERWISE NOTED.

B. ALL MATERIALS MUST BE NEW AND PROVIDED BY THE CONTRACTOR

UNLESS SPECIFICALLY NOTED AS EXISTING OR AS PROVIDED BY THE

GOVERNMENT.

C. ALL WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN DETAILS AND

SECTIONS MUST BE CONTINUOUS UNLESS SPECIFICALLY NOTED

OTHERWISE.

D. VERIFY ALL FIELD CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING

WITH THE WORK. DIMENSIONS FOR EXISTING WORK ARE INDICATED AS "±".

ALL DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE CONTRACTING OFFICER IN WRITING.

E. REFER TO INTERIORS, FIRE PROTECTION, MECHANICAL, ELECTRICAL, AND

TELECOMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION.

F. DIMENSIONS INDICATED FOR NEW WORK ARE TO FACE OF STUD, FACE OF

MASONRY OR FACE OF EXISTING SURFACES UNLESS OTHERWISE NOTED.

G. REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.

DCA B E

KEY PLAN

AREA OF WORK

SY

M

DE

S C

RI

PT

I O N

DA

TE

DN

16 17 18 19

C

D

E

F

HALL

IT CUSTOMER SERVICE

SERVICE CENTER

18'-10" ±

'-4

'-9

17'-10" ±

'-0

'-0

'-0

20'-0" ± 20'-0" ± 20'-0" ±

8'- 6"

3'-

2"

36'-11" ± 19'-4" ±

OPEN OFFICE

OFFICE

5TYP

5 TYP

5 TYP

TRAINING ROOM

8'- 6"

4'-

6"

18'-7" ± 14'-2" ± 7'-6" ± 16'-1" ±

2'-

6 6

10 10

11 TYPSIPR

RACK

SIPR

RACK

SIPR

RACK

NIPR

RACK

7 7

7 7

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

AD101

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

PL

AN

DE

M

O

LI

TI

O

N

PCR

12,909,824

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0" (A-001)

PARTIAL FIRST FLOOR PLAN - DEMOLITIONA1

GENERAL SHEET NOTES

KEYNOTES

1 NO ARCHITECTURAL WORK IN THIS AREA.

2 DEMOLISH EXISTING DOOR, FRAME, AND HARDWARE COMPLETE, UNLESS

OTHERWISE NOTED. SALVAGE EXISTING BALANCED MAGNETIC SWITCHES

(BMS), CARD READER, AND MOTION ACTIVATED REQUEST TO EXIT (REX) FOR

REINSTALLATION.

3 EXISTING RAISED ACCESS FLOORING SYSTEM TO REMAIN. REMOVE

EXISTING RAISED ACCESS FLOORING FINISH COMPLETE AND PREPARE TO

RECEIVE TO NEW FINISH PER MANUFACTURER'S RECOMMENDATION.

REMOVE AND REPLACE IN KIND ANY DAMAGED RAISED ACCESS FLOOR

TILES OR SUPPORTS.

4 EXISTING DOOR, FRAME, AND HARDWARE TO REMAIN. PREPARE EXISTING

DOOR AND FRAME TO RECEIVE NEW PAINT.

5 DEMOLISH EXISTING WALL BASE COMPLETE. PREPARE EXISTING WALL TO

RECEIVE NEW FINISH PER MANUFACTURER'S RECOMMENDATION.

6 REMOVE EXISTING SIGNAGE COMPLETE. PREPARE EXISTING WALL TO

RECEIVE NEW SIGNAGE.

7 REMOVE EXISTING FURNITURE AND EQUIPMENT COMPLETE, UNLESS

OTHERWISE NOTED.

8 EXISTING SAFE TO BE REMOVED BY COMMAND PRIOR TO DEMOLITION

PHASE. COORDINATE SCHEDULING WITH CONTRACTING OFFICER.

9 REMOVE AND SALVAGE EXISTING TV AND WALL MOUNT FOR

REINSTALLATION.

10 DEMOLISH EXISTING WALL TO EXTENTS TO ACCOMMODATE NEW DOOR

OPENING. REFER TO DETAILS ON SHEET AE601 FOR ADDITIONAL

INFORMATION.

11 EXISTING NIPR & SIPR RACKS TO REMAIN. PROTECT FROM DUST & DEBRIS

DURING CONSTRUCTION. COORDINATE OUTAGES WITH CONTRACTING

OFFICER.

DCA B E

KEY PLAN

A. REFER TO SHEET A-001 FOR ADDITIONAL GENERAL ARCHITECTURAL NOTES.

B. THE WORK INCLUDES THE DEMOLITION AND REMOVAL OF ALL

CONSTRUCTION INDICATED, NOTED, OR NECESSARY TO ACCOMPLISH THE

WORK AS INDICATED OR SPECIFIED. IT IS THE GENERAL INTENT OF THE

DEMOLITION WORK TO COMPLETELY REMOVE ALL ITEMS OF EXISTING

CONSTRUCTION, WHERE NOTED OR INDICATED ON THE DRAWINGS,

INCLUDING, BUT NOT LIMITED TO: ANCHORS, FASTENERS, BRACKETS, CLIPS,

RODS, HANGERS, AND SUPPORTS COMPLETE.

C. EXISTING DIMENSIONS ARE BASED ON EXISTING DRAWINGS AND FIELD

WORK. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD PRIOR TO

PERFORMING ANY WORK. BRING ANY DISCREPANCIES TO THE ATTENTION

OF THE CONTRACTING OFFICER PRIOR TO PERFORMING ANY WORK.

D. ALL INTERIOR FINISHED SURFACES WHICH ARE DAMAGED WHILE

PERFORMING WORK UNDER THIS CONTRACT MUST BE PATCHED AND/OR

REPLACED AND FINISHED TO MATCH ADJACENT AREAS AT NO COST TO THE

GOVERNMENT.

E. DEMOLITION OF INTERIOR DESIGN, FIRE PROTECTION, MECHANICAL,

ELECTRICAL, AND TELECOMMUNICATION ITEMS INDICATED ON THE

ARCHITECTURAL DRAWINGS IS NOT INTENDED TO INCLUDE ALL NECESSARY

DEMOLITION WORK FOR THESE ITEMS. REFER TO INTERIOR DESIGN, FIRE

PROTECTION, MECHANICAL, ELECTRICAL, AND TELECOMMUNICATION

DRAWINGS FOR ADDITIONAL INFORMATION.

(THIS SHEET ONLY)

SY

M

DE

S C

RI

PT

I O N

DA

TE

OS

REFLECTED CEILING PLAN

LEGEND - DEMOLITION

SYMBOL DESCRIPTION

LIGHT FIXTURE.

REFER TO ELECTRICAL DRAWINGS.

CEILING SUPPLY/RETURN DIFFUSER.

REFER TO MECHANICAL DRAWINGS.

NO CEILING - EXPOSED TO EXISTING CONCRETE FLOOR

SLAB ABOVE.

EXIT SIGN .

REFER TO ELECTRICAL DRAWINGS.

FINISHED CEILING HEIGHT ABOVE FINISHED FLOOR.(±X'-X")

EXISTING SUSPENDED ACOUSTICAL CEILING TILE AND

GRID TO REMAIN.

AREA NOT IN CONTRACT.

DEMOLISH EXISTING SUSPENDED ACOUSTICAL CEILING

TILE AND GRID COMPLETE.

EMERGENCY LIGHT FIXTURE.

REFER TO ELECTRICAL DRAWINGS.

16 17 18 19

C

D

E

F

HALL

IT CUSTOMER SERVICE

SERVICE CENTER

OPEN OFFICE

(± 10'-0" AFF)

(± 10'-0" AFF)

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

AD102

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

RE

FL

EC

TE

D

CE

IL

IN

G

P

LA

N -D

EM

O

LI

TI

O N

PCR

12,909,825

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

GENERAL SHEET NOTES

KEYNOTES#

DCA B E

KEY PLAN

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0" (A-001)

PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - DEMOLITIONA1

A. REFER TO SHEET A-001 FOR ADDITIONAL GENERAL ARCHITECTURAL NOTES.

B. THE WORK INCLUDES THE DEMOLITION AND REMOVAL OF ALL

CONSTRUCTION INDICATED, NOTED, OR NECESSARY TO ACCOMPLISH THE

WORK AS INDICATED OR SPECIFIED. IT IS THE GENERAL INTENT OF THE

DEMOLITION WORK TO COMPLETELY REMOVE ALL ITEMS OF EXISTING

CONSTRUCTION, WHERE NOTED OR INDICATED ON THE DRAWINGS,

INCLUDING, BUT NOT LIMITED TO: ANCHORS, FASTENERS, BRACKETS, CLIPS,

RODS, HANGERS, AND SUPPORTS COMPLETE.

C. EXISTING DIMENSIONS ARE BASED ON EXISTING DRAWINGS AND FIELD

WORK. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD PRIOR TO

PERFORMING ANY WORK. BRING ANY DISCREPANCIES TO THE ATTENTION

OF THE CONTRACTING OFFICER PRIOR TO PERFORMING ANY WORK.

D. ALL INTERIOR FINISHED SURFACES WHICH ARE DAMAGED WHILE

PERFORMING WORK UNDER THIS CONTRACT MUST BE PATCHED AND/OR

REPLACED AND FINISHED TO MATCH ADJACENT AREAS AT NO COST TO THE

GOVERNMENT.

E. DEMOLITION OF INTERIOR DESIGN, FIRE PROTECTION, MECHANICAL,

ELECTRICAL, AND TELECOMMUNICATION ITEMS INDICATED ON THE

ARCHITECTURAL DRAWINGS IS NOT INTENDED TO INCLUDE ALL NECESSARY

DEMOLITION WORK FOR THESE ITEMS. REFER TO INTERIOR DESIGN, FIRE

PROTECTION, MECHANICAL, ELECTRICAL, AND TELECOMMUNICATION

DRAWINGS FOR ADDITIONAL INFORMATION.

1 NO ARCHITECTURAL WORK IN THIS AREA.

2 DEMOLISH EXISTING ACOUSTICAL CEILING TILES AND GRID COMPLETE.

3 NO CEILING - EXPOSED TO STRUCTURE ABOVE.

(THIS SHEET ONLY)

SY

M

DE

S C

RI

PT

I O N

DA

TE

C

D

E

F

IT CUSTOMER SERVICE

SERVICE CENTER

18'-10" ±

'-4

'-9

17'-10" ±

'-0

'-0

'-0

20'-0" ± 20'-0" ± 20'-0" ±

OPEN OFFICE

OFFICE

TRAINING ROOM

3180B

183 182

180A

178A

179A

179B

2 2

8'- 6"

3'- 2"

36'-11" 19'-4"

8'- 6"

4'- 6"

18'-7" ± 14'-2" ± 7'-6" ± 16'-1" ±

HALL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

AE101

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

PL

AN

PCR

12,909,826

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

GENERAL SHEET NOTES

KEYNOTES

DCA B E

KEY PLAN

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0" (A-001)

PARTIAL FIRST FLOOR PLANA1

1 NO ARCHITECTURAL WORK IN THIS AREA.

2 EXISTING DOOR, FRAME, AND HARDWARE TO REMAIN. PREPARE AND PAINT

EXISTING DOOR AND FRAME AS SCHEDULED.

3 PROVIDE CORNER GUARDS (CG-1) ON ALL OUTSIDE CORNERS. REFER TO

DETAILS D1 & B1 ON SHEET AE601 FOR ADDITIONAL INFORMATION.

4 ACTIVE DOOR LEAF.

5 NON-ACTIVE DOOR LEAF, USED FOR EGRESS ONLY.

6 REINSTALL EXISTING SALVAGED TV AND WALL MOUNT.

7 PATCH AND REPAIR ALL HOLES AND DAMAGED GYPSUM WALL BOARD.

A. REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.

B. REFER TO INTERIOR DESIGN, FIRE PROTECTION, MECHANICAL, ELECTRICAL,

AND TELECOMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION.

C. DIMENSIONS ARE FROM FACE OF STUD, FACE OF EXISTING, AND COLUMN

CENTERLINE, UNLESS OTHERWISE NOTED.

D. ALL INTERIOR FINISHED SURFACES WHICH ARE DAMAGED WHILE

PERFORMING WORK UNDER THIS CONTRACT MUST BE PATCHED AND/OR

REPLACED AND FINISHED TO MATCH ADJACENT AREAS AT NO COST TO THE

GOVERNMENT.

(THIS SHEET ONLY) SY

M

DE

S C

RI

PT

I O N

DA

TE

16 17 18 19

C

D

E

F

IT CUSTOMER SERVICE

SERVICE CENTER

3'-

0" EQ

EQ

OPEN OFFICE

HALL

(± 10'-0" AFF)

(± 10'-0" AFF)

(± 9'-0" AFF)

(± 10'-0" AFF)

A1

AE601

REFLECTED CEILING PLAN LEGEND

SYMBOL DESCRIPTION

2' - 0" X 2' - 0" ACOUSTICAL CEILING TILE.

EMERGENCY LIGHT FIXTURE.

REFER TO ELECTRICAL DRAWINGS.

CEILING SUPPLY / RETURN / EXHAUST DIFFUSER.

REFER TO MECHANICAL DRAWINGS.

NO CEILING - EXPOSED TO ROOF DECK ABOVE.

AREA NOT IN CONTRACT.

HORN/STROBE.

REFER TO FIRE PROTECTION DRAWINGS.

EXIT SIGN.

REFER TO ELECTRICAL DRAWINGS.

OCCUPANCY SENSOR.

REFER TO ELECTRICAL DRAWINGS.

OS

FINISHED CEILING HEIGHT ABOVE FINISHED FLOOR.(X'-X")

GYPSUM BOARD CEILING.

LIGHT FIXTURE.

REFER TO ELECTRICAL DRAWINGS.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

AE102

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

RE

FL

EC

TE

D

CE

IL

IN

G

P

LA

N

PCR

12,909,827

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

GENERAL SHEET NOTES

KEYNOTES

DCA B E

KEY PLAN

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0" (A-001)

PARTIAL FIRST FLOOR REFLECTED CEILING PLANA1

1 NO ARCHITECTURAL WORK IN THIS AREA.

2 PROVIDE ACOUSTICAL CEILING TILES AND GRID AS SCHEDULED.

3 NO CEILING - EXPOSED TO STRUCTURE ABOVE.

4 PROVIDE GWB SOFFIT. PAINT AS SCHEDULED.

(THIS SHEET ONLY)

A. REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.

B. REFER TO INTERIOR DESIGN, FIRE PROTECTION, MECHANICAL, ELECTRICAL,

AND TELECOMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION.

C. UNLESS OTHERWISE NOTED, CEILING TILES MUST BE CENTERED IN EACH

ROOM IN ACCORDANCE WITH THE LAYOUTS SHOWN.

D. MAKE ADJUSTMENTS NECESSARY TO ELIMINATE ADDITIONAL, SMALL, OR

ODD PIECES OF CEILING TILE.

E. WHERE CEILING TILES ARE CUT, COPE AND FINISH EDGES TO MATCH

UNCUT TILE.

F. CENTER ALL LIGHTS, DIFFUSERS, FIXTURES, SPRINKLER HEADS, ETC. IN

CEILING TILES UNLESS OTHERWISE NOTED.

G. DAMP CLEAN AND HAND DRY ALL FIXTURES AND LAMPS JUST PRIOR TO

FINAL INSPECTION.

SY

M

DE

S C

RI

PT

I O N

DA

TE

16 17 18

C

D

E

F

HALL

IT CUSTOMER SERVICE

SERVICE CENTER

'-0

'-0

'-0

20'-0" ± 20'-0" ±

OPEN OFFICE

OFFICE

TRAINING ROOM

A

A

A

A

A

A

A

179B

179A

178A

180A

182183

180B

CONFERENCE ROOM

C F

F

9"

BO

TT

OM

O

F

TA

CT

ILE

C

HA

RA

CT

E R

4- 0"

M

IN

A

ND

5' -0

" M

AX

MOUNT ON LATCH SIDE OF

DOOR OR ADJACENT WALL,

UNLESS OTHERWISE INDICATED.

CL

ELECTRICAL

3" 2"

9"

TEXT: 1-1/2" TACTILE ROOM

NUMBER WITH GRADE 2

BRAILLE HELVETICA NEUE 55

ROMAN

TEXT: 3/4" TACTILE ROOM NAME,

HELVETICA NEUE 55 ROMAN

SIGN TYPE A

REMOVABLE END CAPS

ROOM

NAME

REMOVABLE END CAPS

9"

3" 6"

9"

TEXT: 1-1/2" TACTILE ROOM

NUMBER WITH GRADE 2

BRAILLE HELVETICA NEUE 55

ROMAN

TEXT: 3/4" PRINTED PAPER

ROOM NAME, HELVETICA

NEUE 55 ROMAN

SIGN TYPE C

CONFERENCE

ROOM

IN USE VACANT

TEXT: 1-1/2" TACTILE ROOM

NUMBER WITH GRADE 2

BRAILLE HELVETICA NEUE

55 ROMAN

TEXT: 3/4" TACTILE ROOM

NUMBER, HELVETICA NEUE

55 ROMAN

9"

3" 6"

9"

SLIDING INSERT

TEXT: 5/8" PRINTED MESSAGE,

HELVETICA NEUE 55 ROMAN

SIGN TYPE F REMOVABLE END CAPS

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

AE103

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

SI

G

NA

G E

PL

AN

PCR

12,909,828

PPB PPB

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

JDW

M

ID

LA

N

T -P

W D

N O

R

FO

LK

GENERAL SHEET NOTES

KEYNOTES

DCA B E

KEY PLAN

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0" (A-001)

PARTIAL FIRST FLOOR SIGNAGE PLANA1

1 NO ARCHITECTURAL WORK IN THIS AREA.

(THIS SHEET ONLY)

A. REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.

B. REFER TO INTERIOR DESIGN, FIRE PROTECTION, MECHANICAL, ELECTRICAL,

AND TELECOMMUNICATION DRAWINGS FOR ADDITIONAL INFORMATION.

C. INSTALL MATERIALS/PRODUCTS PER MANUFACTURER'S INSTALLATION

REQUIREMENTS.

D. DO NOT SUBTITUTE MATERIALS DUE TO ORDERING LEAD TIMES. IT IS THE

CONTRACTOR'S RESPONSIBILITY TO ORDER ALL MATERIALS IN TIME TO

AVOID DELAYS.

SIGNAGE TYPES

0 1' 2' 4'SCALE: 1/2" = 1'-0"

SIGNAGE MOUNTING DETAIL - WALLD3

SIGNAGE SCHEDULE

ROOM LOCATION

SIGN TYPE SIGN TEXT QTY

DOORWAY

LOCATIONNO. NAME

178 OPEN OFFICE A OFFICE 1 2

179 SERVICE CENTER A SERVICE CENTER 2 2

181 CONFERENCE

ROOM

F CONFERENCE

ROOM

1 2

182 TRAINING ROOM F TRAINING ROOM 1 2

183 OFFICE C OFFICE 1 2

185 CORRIDOR A CORRIDOR 1 2

186 IT CUSTOMER

SERVICE

A IT CUSTOMER

SERVICE

2 2

A-126 JECC STORAGE A STORAGE 1 2

SY

M

DE

S C

RI

PT

I O N

DA

TE

FLUSH PANEL

(PAIR)

A

FINISHED FLOOR

FIRST FLOOR

DOOR WIDTH

EQ 2" EQ

DO

OR

H

EI

GH

T REFER TO DETAIL

FOR TYP HM FRAME PROFILE

F-1

HOLLOW METAL

(WELDED)

2"

WIDTH

DOOR 2"

2"

DO

OR

H

EI

GH

T

FINISHED FLOOR

FIRST FLOOR

REMOVABLE HM MULLION

/A4 AE601

5/8

2"

VARIES

1 15/16" 1 9/16"

1/2" 1/16"

EXISTING

PARTITION - FIELD

VERIFY DIMENSION

EXISTING PARTITION TO REMAIN.

CONTINUOUS SEALANT, BOTH SIDES.

HOLLOW METAL FRAME AS SCHEDULED.

2"

DOOR AS SCHEDULED.

FIELD VERIFY

4 7/8" ±

METAL STUD HEADER.

GWB TO MATCH EXISTING, BOTH SIDES.

EXISTING PARTITION TO REMAIN.

CONTINUOUS SEALANT, BOTH SIDES.

HOLLOW METAL FRAME AS

SCHEDULED.2"

DOOR AS SCHEDULED.

STEEL STUD ANCHORS (3 PER JAMB).

FIELD VERIFY

4 7/8" ±

DOUBLE STUD AT JAMB.

GWB TO MATCH EXISTING, BOTH SIDES.

DOOR FRAME (BEYOND) - PAINT

AS SCHEDULED.

DOOR AS SCHEDULED.

1'- 4"

FI

EL

D

VE

RI

FY

ALUMINUM SADDLE THRESHOLD

SET IN FULL BED OF SEALANT,

FASNTEND TO EXISTING WOOD

BLOCKING.

EXISTING WOOD BLOCKING TO

REMAIN.

EXISTING PARTITION TO REMAIN.

EXISTING RAISED ACCESS

FLOOR SUPPORT TO REMAIN.

FLOOR FINISH AS SCHEDULE ON

EXISTING RAISED ACCESS FLOOR

SYSTEM TO REMAIN.

AUTOMATIC DOOR BOTTOM.

EXISTING PARTITION

TO REMAIN.

2"

2"

SURFACE MOUNT

CORNER GUARD.

ALUMINUM RETAINER.

FASTENERS

STAGGERED.

BASE AS SCHEDULED.

FINISH FLOOR.

HE

IG

HT

BA

SE

2"

4'- 0"

FACE OF WALL.

END CLOSURE CAP.

5/8" GYPSUM WALL BOARD.

20 GA. 3 5/8" METAL STUDS AT 16" OC.

BOTTOM OF BULKHEAD

± 9'-0" AFF

CEILING HEIGHT

± 10'-0" AFF

4" M

IN

EQ EQ

RECESSED LIGHT FIXTURE.

REFER TO ELEC DRAWINGS.

CEILING AS SCHEDULED.

CORNER BEAD (TYP AT ALL CORNERS).

4" M

IN

3'-0"

BOTTOM OF EXISTING SLAB

± 13'-0" AFF

EXISTING CONCRETE

SLAB TO REMAIN.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

AE601

BU

IL

DI

NG

X -1

DO

O

R

SC

HE

DU

LE

A

ND

D

ET

AI

LS

PCR

12,909,829

DAS DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

ALP

M

ID

LA

N

T -P

W D

N O

R

FO

LK

D

OO

R

NO

DOOR FRAME

FI

RE

R

AT

IN

G

H

AR

DW

AR

E S

ET

N O.

ST

C

RA

TIN

G

R

EM

AR

KS

TY

PE

SIZE

M

AT

ER

IA

L

TY

PE

M

AT

ER

IA

L

DETAILS ON THIS SHEET UON

W

ID

TH

H

EIG

HT

TH

IC

KN

ES

S

HEAD JAMB SILL

178A EXISTING TO REMAIN 5'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

179A EXISTING TO REMAIN 3'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

179B EXISTING TO REMAIN 6'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

180A EXISTING TO REMAIN 6'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

180B EXISTING TO REMAIN 6'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

181 EXISTING TO REMAIN 3'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

182 EXISTING TO REMAIN 3'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

183 EXISTING TO REMAIN 3'-0" 7'-0" 1 3/4" HM - HM - - - - - - 1, 2

186 A 6'-2" 7'-0" 1 3/4" HM F-1 HM D2 B2 A2 - 1 - 2, 3

DOOR SCHEDULE

0 2' 4' 8'SCALE: 1/4" = 1'-0"

DOOR TYPESB4 0 2' 4' 8'SCALE: 1/4" = 1'-0"

FRAME TYPESB5

0 1" 2" 4"SCALE: 6" = 1'-0"

HM FRAME PROFILEA4

0 2" 4" 8"SCALE: 3" = 1'-0"

DOOR HEAD - EXISTING PARTITIOND2

0 2" 4" 8"SCALE: 3" = 1'-0"

DOOR JAMB - EXISTING PARTITIONB2

1. EXISTING DOOR AND FRAME TO REMAIN.

2. PAINT DOOR AND FRAME AS SCHEDULED.

3. 3'-0" WIDE PAIR OF DOORS WITH A 2" REMOVABLE MULLION.

DOOR SCHEDULE REMARKS

0 2" 4" 8"SCALE: 3" = 1'-0"

DOOR SILL - RAISED ACCESS FLOORA2

(AE601)

(AE601)

(AE601)

(AE601) (AE601)0 1" 2" 4"SCALE: 6" = 1'-0"

CORNER GUARD DETAILB1

0 4" 8" 1'-4"SCALE: 1 1/2" = 1'-0"

CORNER GUARD ELEVATIOND1

0 4" 8" 1'-4"SCALE: 1 1/2" = 1'-0" (AE102)

BULKHEAD DETAILA1

(AE101)

(AE101)

(AE601)

SY

M

DE

S C

RI

PT

I O N

DA

TE

REF.

IT CUSTOMER SERVICE

SERVICE CENTER

OPEN OFFICE

OFFICE

TRAINING ROOM

HALL

16 17 18 19

C

D

E

F

WS1

WS1

WS1 WS1

QTY. 6

WD1

SH2

SH2

SH2

CH1

WB1

CH2

SH1 SH1

SH1SH1

SIPR

RACK

SIPR

RACK

SIPR

RACK

NIPR

RACK

3'-1"

M1

M2

CW1

CH2

WB1

SH3

CH3

CH3

T1 M3

WS3

WS2

WS2

CONFERENCE ROOM

CORRIDOR

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

IF101

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

FU

RN

IT

UR

E

PL

AN

(F O

R

RE

FE

RE

NC

E

O

NL

Y)

JDW

12,909,830

PPB PPB

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

JDW

M

ID

LA

N

T -P

W D

N O

R

FO

LK

A. ALL FURNITURE, FIXURES, AND EQUIPMENT (FF&E) INDICATED IS PROVIDED

FOR COORDINATION PURPOSES ONLY. PROCUREMENT OF NEW FF&E IS

NOT PART OF THE BASE BID CONSTRUCTION CONTRACT. CONSTRUCTION

FUNDS WILL NOT BE USED. FF&E WILL BE FUNDED SEPARATELY AS AN

OPTION TO THE CONSTRUCTION CONTRACT.

B. COORDINATE FURNITURE WITH ELECTRICAL AND DATA OUTLET LOCATIONS.

REFER TO ELECTRICAL PLANS.

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR FURNITURE PLAN (FOR REFERENCE ONLY)A1

1 NO INTERIORS WORK IN THIS AREA.

2 EXISTING NIPR AND SIPR RACKS

FURNITURE SCHEDULE

MARK DESCRIPTION

CH1 UPHOLSTERED TASK CHAIR WITH ARMS

CH2 STOOL WITHOUT ARMS

CH3 TRAINING CHAIR WITH GLIDES AND NO ARMS

CW1 SYSTEMS WORK SURFACE 30" DEPTH

M1 LATERAL FILE 3 DRAWER 30"W

M2 MICROWAVE COUNTERTOP

M3 REFRIGERATOR

SH1 METAL INDUSTRIAL SHELVING, 36W x 24D x 72H SH2 STORAGE SHELVING 48W x 18D x 76H SH3 METAL INDUSTRIAL SHELVING 48W x 18D x 76H

T1 ROUND TABLE, 30DIA

WB1 WORKBENCH, 72W x 30D

WD1 2 DOOR WARDROBE 30"W

WS1 60" x 60" WORKSTATION WS2 60" x 54" WORKSTATION WS3 TEST KIOSK 36"W x 24"D

GENERAL SHEET NOTES

KEYNOTES

DCA B E

AREA OF WORK

KEY PLAN

# (THIS SHEET ONLY)

SY

M

DE

S C

RI

PT

I O N

DA

TE

REF.

C

D

E

F

1 1 1

4 44

OPEN OFFICE

IT CUSTOMER SERVICE

SERVICE CENTER

HALL

TRAINING ROOM

OFFICE

CORRIDOR

CONFERENCE ROOM

181 1

FINISH PLAN LEGEND

SYMBOL DESCRIPTION

2' - 0" X 2' - 0" EXISTING RAISED ACCESS FLOORING, NEW

FINISH AS SCHEDULED.

AREA NOT IN CONTRACT.

RUBBER TILE FLOORING AS SCHEDULED.

STATIC DISSIPATIVE TILE AS SCHEDULED.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

IN101

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R

FI

NI

SH

P

LA

N

JDW

12,909,831

PPB PPB

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

JDW

M

ID

LA

N

T -P

W D

N O

R

FO

LK

A. FOR QUESTIONS REGARDING INTERIOR DESIGN DRAWINGS AND

SPECIFICATIONS CONTACT: NAVFAC CONTRACTING OFFICER.

B. FINISHES INDICATED ARE THE APPROVED BASIS OF DESIGN TO CONVEY

COLOR, PATTERN, TEXTURE AND SALIENT CHARACTERISTICS ONLY. THE

LISTING OF MANUFACTURER INFORMATION IS NOT INTENDED TO LIMIT THE

SELECTION OF PRODUCTS PROVIDED BY OTHER MANUFACTURERS.

PRODUCTS MEETING THESE CRITERIA WILL BE CONSIDERED AND MUST BE

REVIEWED BY THE INTERIOR DESIGNER OF RECORD (IDOR) AND THE

NAVFAC INTERIOR DESIGNER AND APPROVED BY THE CONTRACTING

OFFICER.

C. FINISH ITEMS ARE NOT TO BE SUBSTITUTED DUE TO ORDERING LEAD TIMES.

IT IS THE CONTRACTOR’S RESPONSIBILITY TO ORDER ALL MATERIALS IN

TIME TO AVOID DELAYS.

D. SPRAY PAINT ELECTRICAL PANELS, ACCESS PANELS, AND EXPANSION

JOINTS TO MATCH THE ADJACENT WALL COLOR. PANELS PAINTED BY

BRUSH ARE NOT ACCEPTABLE.

E. TRANSITIONS MUST MEET ABA GUIDELINES.

F. TRANSITIONS OCCURRING UNDER DOORS MUST BE CENTERED UNDER

DOOR.

G. INCLUDE METAL TRANSITIONS ON ALL OUTSIDE AND INSIDE CORNERS, AS

WELL AS THE INTERSECTION BETWEEN THE FLOOR AND WALL TILE FOR A

COMPLETE INSTALLATION IN ALL ROOMS IDENTIFIED TO RECEIVE TILE.

H. PROVIDE CORNER GUARDS (CG1) ON ALL OUTSIDE CORNERS. (DO NOT USE

CORNER GUARDS ON CMU WALLS OR MANUFACTURED STONE WALLS)

I. COORDINATE ROOM EXACT ROOM NAMES FOR SIGNAGE WITH

CONSTRUCTION MANAGER DURING CONSTRUCTION SUBMITTAL

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR FINISH PLANA1

1 NO INTERIORS WORK IN THIS AREA.

2 STATIC DISSIPATIVE TILE ON RAISED ACCESS FLOORING SYSTEM AS

SCHEDULED.

3 RUBBER MATTING FLOORING AS SCHEDULED ON EXISTING RAISED ACCESS

FLOORING SYSTEM.

4 PROVIDE CORNER GUARDS (CG1) ON ALL OUTSIDE CORNERS. REFER TO

DETAIL B1 / AE601 FOR ADDITIONAL INFORMATION.

5 PROVIDE ACCENT PAINT PT2

GENERAL SHEET NOTES

KEYNOTES

KEY PLAN

# (THIS SHEET ONLY)

DCA B E

AREA OF WORK

SY

M

DE

S C

RI

PT

I O N

DA

TE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

IN601

BU

IL

DI

NG

X -1

FI

RS

T

FL

O O

R

IN

TE

RI

O R

FI

NI

SH

S

CH

ED

UL

E

JDW

12,909,832

PPB PPB

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

JDW

M

ID

LA

N

T -P

W D

N O

R

FO

LK

FINISH SCHEDULE NOTES

1 REFER TO PARTIAL REFLECTED CEILING PLAN FOR VARIABLE CEILING TYPES, FINISHES, AND HEIGHTS.

2 NO CEILING - EXPOSED TO CONCRETE DECK ABOVE.

3 REFER TO PARTIAL FINISH PLAN FOR ACCENT PAINT LOCATIONS.

A. FOR QUESTIONS REGARDING INTERIOR DESIGN DRAWINGS AND

SPECIFICATIONS CONTACT: NAVFAC CONTRACTING OFFICER.

B. FINISHES INDICATED ARE THE APPROVED BASIS OF DESIGN TO CONVEY

COLOR, PATTERN, TEXTURE AND SALIENT CHARACTERISTICS ONLY. THE

LISTING OF MANUFACTURER INFORMATION IS NOT INTENDED TO LIMIT THE

SELECTION OF PRODUCTS PROVIDED BY OTHER MANUFACTURERS.

PRODUCTS MEETING THESE CRITERIA WILL BE CONSIDERED AND MUST BE

REVIEWED BY THE INTERIOR DESIGNER OF RECORD (IDOR) AND THE

NAVFAC INTERIOR DESIGNER AND APPROVED BY THE CONTRACTING

OFFICER.

C. FINISH ITEMS ARE NOT TO BE SUBSTITUTED DUE TO ORDERING LEAD TIMES.

IT IS THE CONTRACTOR’S RESPONSIBILITY TO ORDER ALL MATERIALS IN

TIME TO AVOID DELAYS.

D. SPRAY PAINT ELECTRICAL PANELS, ACCESS PANELS, AND EXPANSION

JOINTS TO MATCH THE ADJACENT WALL COLOR. PANELS PAINTED BY

BRUSH ARE NOT ACCEPTABLE.

E. TRANSITIONS MUST MEET ABA GUIDELINES.

F. TRANSITIONS OCCURRING UNDER DOORS MUST BE CENTERED UNDER

DOOR.

G. INCLUDE METAL TRANSITIONS ON ALL OUTSIDE AND INSIDE CORNERS, AS

WELL AS THE INTERSECTION BETWEEN THE FLOOR AND WALL TILE FOR A

COMPLETE INSTALLATION IN ALL ROOMS IDENTIFIED TO RECEIVE TILE.

H. PROVIDE CORNER GUARDS (CG1) ON ALL OUTSIDE CORNERS. (DO NOT USE

CORNER GUARDS ON CMU WALLS OR MANUFACTURED STONE WALLS)

I. COORDINATE ROOM EXACT ROOM NAMES FOR SIGNAGE WITH

CONSTRUCTION MANAGER DURING CONSTRUCTION SUBMITTAL

GENERAL SHEET NOTESFINISH SCHEDULE - FIRST FLOOR

ROOM

FLOOR BASE

CEILING WALL

NOTESNO. NAME FINISH HEIGHT

NORTH

FINISH

EAST

FINISH

SOUTH

FINISH

WEST

FINISH

179 SERVICE CENTER SDT1 RB1 PT4 10'-0" AFF PT1 PT1 PT1 PT1 2

180 HALL RTF1 RB1 ACT1 10'-0" AFF PT1 PT2 PT1 PT2 3

186 IT CUSTOMER SERVICE SDT1 RB1 ACT1/PT3 VARIABLE PT1 PT1 PT2 PT1 1

FINISH LEGEND

FINISH TAG FINISH MANUFACTURER STYLE / TYPE COLOR NOTES

FLOOR

RTF1 RUBBER TILE FLOORING - 20" x 40" NORA SYSTEMS, INC. - NORAMENT ARAGO 5178 CALM 1 SDT1 STATIC DISSIPATIVE TILE - 24" x 24" STATIC SMART - NORTHLAND SERIES - KODIAK 1

BASE

RB1 RUBBER BASE - 4" HIGH COVE BASE JOHNSONITE - TRADITIONAL COVE TA8 4" HIGH WELSH CASTLE 2

WALL

PT1 PAINT FIELD - GYPSUM WALL (EGGSHELL) SHERWIN WILLIAMS SW7575 CHOPSTICKS 4

PT2 PAINT ACCENT - GYPSUM WALL (EGGSHELL) SHERWIN WILLIAMS SW7532 URBAN PUTTY 4

CEILING

ACT1 ACOUSTICAL CEILING TILE - 24" x 24" x 7/8" - ANGULAR

TEGULAR 15/16"

ARMSTRONG - CORTEGA 704A WHITE 3

PT3 PAINT - GYPSUM BOARD CEILING SOFFIT (FLAT) SHERWIN WILLIAMS SW 7007 BRIGHT WHITE 4 PT4 PAINT - UNDERSIDE OF CONCRETE DECK (FLAT) SHERWIN WILLIAMS SW 7007 BRIGHT WHITE -

DOORS

PT6 PAINT - DOOR FRAME & PANEL (SEMI-GLOSS) SHERWIN WILLIAMS SW7532 URBAN PUTTY -

MISCELLANEOUS

CG1 CORNER GUARD - 3/4" - SURFACE MOUNT KOROSEAL 3/4" SERIES

#G875

BUCKEYE

ALMOND

S1 SIGNAGE BACKGROUND 2/90 ESSENTIALS 156 BRONZE

S2 SIGNAGE COPY 2/90 ESSENTIALS 713 SAND

S3 SIGNAGE TRIM 2/90 ESSENTIALS 156 BRONZE

FINISH LEGEND NOTES

1 ADHERE FLOOR FINISH TO RAISED ACCESS FLOORING SYSTEM.

2 AS SELECTED FROM MANUFACTURER'S STANDARD COLORS.

3 PRELUDE XL 15/16" EXPOSED GRID SUSPENSION SYSTEM.

4 FINISH ALL GYPSUM BOARD SURFACES (WALLS & CEILINGS) WITH A LEVEL 5 FINISH.

5 PROVIDE CORNER GUARDS (CG-1) ON ALL OUTSIDE CORNERS. REFER TO DETAIL B1 / AE601 FOR ADDITIONAL INFORMATION.

SY

M

DE

S C

RI

PT

I O N

DA

TE

HALL

IT CUSTOMER SERVICE

SERVICE CENTER

OPEN OFFICE

OFFICE

TRAINING ROOM

CORRIDOR

CONFERENCE ROOM

181 1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

FD101

BU

IL

DI

NG

X -1

PA

RT

IA

L

FI

RS

T

FL

O O

R -D

EM

O

LI

TI

O N

PCR

12,909,833

MWB MWB

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

HPN

M

ID

LA

N

T -P

W D

N O

R

FO

LK

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR PLAN - DEMOLITIONA1

1 NO FIRE PROTECTION SYSTEM WORK IN THIS AREA.

2 REMOVE FM200 SYSTEM IN ENTIRETY, INCLUDING, BUT NOT LIMITED TO, ALL

DEVICES, NOTIFICATION APPLIANCES, RELEASING PANEL, AND ASSOCIATED

WIRE, CONDUIT, JUNCTION/BACK BOXES. DEPROGRAM FM-200 SYSTEM

FROM FIRE ALARM SYSTEM. TURN OVER TO BASE FIRE ALARM SHOP.

3 EXISTING FIRE SPRINKLER SYSTEM TO REMAIN. PROTECT EXISTING

SYSTEM FROM DAMAGE FROM WORK IN THIS AREA.

4 PROTECT EXISTINGFIRE SPRINKLER SYSTEM FROM DAMAGE FROM ANY

WORK IN THIS AREA.

GENERAL SHEET NOTES

KEYNOTES

DCA B E

AREA OF WORK

KEY PLAN

# (THIS SHEET ONLY)

A. THE FIRE SUPPRESSION SYSTEM DESIGNER MUST BE CERTIFIED AS A NICET

TECHNICIAN III IN WATER BASED SYSTEMS LAYOUT SUBFIELD OF FIRE

PROTECTION ENGINEERING TECHNOLOGIES AND INSTALLED BY A LICENSED

/ CERTIFIED COMPANY WHERE EMPLOYEES ARE LICENSED / CERTIFIED TO

INSTALL FIRE PROTECTION EQUIPMENT.

B. ALL COMPONENTS AND ASSEMBLIES USED IN THIS FIRE PROTECTION

SYSTEM MUST BE SPECIFICALLY UL LISTED OR FM APPROVED FOR THEIR

INTENDED USE.

C. ALL WORK MUST BE IN ACCORDANCE WITH THE LATEST EDITION OF NFPA

13.

D. PROVIDE ALL NECESSARY COMPONENTS FOR A WET-PIPE SYSTEM IN ALL

AREAS INDICATED. AT A MINIMUM PROVIDE COMPONENTS AS INDICATED

ON THESE DRAWINGS. CONTRACTOR MUST PROVIDE ADDITIONAL

COMPONENTS AND MODIFICATIONS AS REQUIRED TO PROVIDE A FULLY

FUNCTIONING FIRE SUPPRESSION SYSTEM.

E. ALL SYSTEMS WHICH REQUIRE COORDINATION BETWEEN TRADES MUST BE

TO THE SATISFACTION OF THE ENGINEER AND AUTHORITY HAVING

JURISDICTION. ANY DEFICIENCIES, INCONSISTENCIES, OR POORLY

COORDINATED INSTALLATIONS MUST BE CORRECTED BY THE CONTRACTOR

AT NO ADDITIONAL COST.

F. FINAL DESIGN REQUIREMENTS (DEVICE QUANTITY, SIZE, AND LOCATIONS)

ARE THE SOLE RESPONSIBILITY OF THE FIRE SUPPRESSION CONTRACTOR.

DRAWINGS INDICATE MINIMUM REQUIREMENTS; THE FIRE SUPPRESSION

CONTRACTOR WILL BE RESPONSIBLE FOR VERIFYING AND COORDINATING

FINAL DESIGN REQUIREMENTS WITH THESE CONSTRUCTION DOCUMENTS,

SPECIFICATIONS, REFERENCE DOCUMENTS, APPLICABLE CODES, AND

FACILITY USER REQUIREMENTS.

G. PROVIDE CONSTRUCTION SUBMITTALS FOR REVIEW INCLUDING SHOP

DRAWINGS, DESIGNER AND INSTALLER QUALIFICATIONS, AND CATALOG

DATA OF ALL EQUIPMENT AND MATERIAL USED.

H. PERFORM HYDROSTATIC TEST IN ACCORDANCE WITH NFPA 13 ON ALL NEW

SPRINKLERS AND PIPING INSTALLED.

I. SUBMIT HYDROSTATIC TEST RESULTS FOR REVIEW. ONCE RESULTS ARE

APPROVED A FINAL INSPECTION CAN BE SCHEDULED. ALLOW AT LEAST 14

DAYS FROM RESULT APPROVAL TO THE FINAL INSPECTION. THE FINAL MUST

BE WITNESSED BY A NAVFAC MID ATLANTIC FIRE PROTECTION ENGINEER.

SY

M

DE

S C

RI

PT

I O N

DA

TE

HALL

IT CUSTOMER SERVICE

SERVICE CENTER

OPEN OFFICE

OFFICE

TRAINING ROOM

CORRIDOR

CONFERENCE ROOM

181 1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

FX101

BU

IL

DI

NG

X -1

FI

RS

T

FL

O O

R

PL

AN

FI

RE

S

UP

PR

ES

SI

O

N

PCR

12,909,834

MWB MWB

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

HPN

M

ID

LA

N

T -P

W D

N O

R

FO

LK

0 2' 4' 8'

PLAN

NORTH

SCALE: 1/4" = 1'-0"

PARTIAL FIRST FLOOR PLAN - FIRE SUPPRESSIONA1

GENERAL SHEET NOTES

KEYNOTES

DCA B E

AREA OF WORK

KEY PLAN

# (THIS SHEET ONLY)

1 NO FIRE PROTECTION SYSTEM WORK IN THIS AREA.

2 MODIFY EXISTING FIRE SPRINKLER SYSTEM TO ACCOMMODATE NEW

CEILING WORK IN THIS AREA. ANY DAMAGED SPRINKLER MUST BE

REPLACED WITH NEW IN-KIND. NEW PIPING MUST MATCH EXISTING.

3 NO FIRE PROTECTION SYSTEM WORK EXPECTED IN THIS AREA. IF EXISTING

SPRINKLERS GET DAMAGED, REPLACE WITH NEW IN-KIND.

A. THE FIRE SUPPRESSION SYSTEM DESIGNER MUST BE CERTIFIED AS A NICET

TECHNICIAN III IN WATER BASED SYSTEMS LAYOUT SUBFIELD OF FIRE

PROTECTION ENGINEERING TECHNOLOGIES AND INSTALLED BY A LICENSED

/ CERTIFIED COMPANY WHERE EMPLOYEES ARE LICENSED / CERTIFIED TO

INSTALL FIRE PROTECTION EQUIPMENT.

B. ALL COMPONENTS AND ASSEMBLIES USED IN THIS FIRE PROTECTION

SYSTEM MUST BE SPECIFICALLY UL LISTED OR FM APPROVED FOR THEIR

INTENDED USE.

C. ALL WORK MUST BE IN ACCORDANCE WITH THE LATEST EDITION OF NFPA

13.

D. PROVIDE ALL NECESSARY COMPONENTS FOR A WET-PIPE SYSTEM IN ALL

AREAS INDICATED. AT A MINIMUM PROVIDE COMPONENTS AS INDICATED

ON THESE DRAWINGS. CONTRACTOR MUST PROVIDE ADDITIONAL

COMPONENTS AND MODIFICATIONS AS REQUIRED TO PROVIDE A FULLY

FUNCTIONING FIRE SUPPRESSION SYSTEM.

E. ALL SYSTEMS WHICH REQUIRE COORDINATION BETWEEN TRADES MUST BE

TO THE SATISFACTION OF THE ENGINEER AND AUTHORITY HAVING

JURISDICTION. ANY DEFICIENCIES, INCONSISTENCIES, OR POORLY

COORDINATED INSTALLATIONS MUST BE CORRECTED BY THE CONTRACTOR

AT NO ADDITIONAL COST.

F. FINAL DESIGN REQUIREMENTS (DEVICE QUANTITY, SIZE, AND LOCATIONS)

ARE THE SOLE RESPONSIBILITY OF THE FIRE SUPPRESSION CONTRACTOR.

DRAWINGS INDICATE MINIMUM REQUIREMENTS; THE FIRE SUPPRESSION

CONTRACTOR WILL BE RESPONSIBLE FOR VERIFYING AND COORDINATING

FINAL DESIGN REQUIREMENTS WITH THESE CONSTRUCTION DOCUMENTS,

SPECIFICATIONS, REFERENCE DOCUMENTS, APPLICABLE CODES, AND

FACILITY USER REQUIREMENTS.

G. PROVIDE CONSTRUCTION SUBMITTALS FOR REVIEW INCLUDING SHOP

DRAWINGS, DESIGNER AND INSTALLER QUALIFICATIONS, AND CATALOG

DATA OF ALL EQUIPMENT AND MATERIAL USED.

H. PERFORM HYDROSTATIC TEST IN ACCORDANCE WITH NFPA 13 ON ALL NEW

SPRINKLERS AND PIPING INSTALLED.

I. SUBMIT HYDROSTATIC TEST RESULTS FOR REVIEW. ONCE RESULTS ARE

APPROVED A FINAL INSPECTION CAN BE SCHEDULED. ALLOW AT LEAST 14

DAYS FROM RESULT APPROVAL TO THE FINAL INSPECTION. THE FINAL MUST

BE WITNESSED BY A NAVFAC MID ATLANTIC FIRE PROTECTION ENGINEER.

SY

M

DE

S C

RI

PT

I O N

DA

TE

FLEXIBLE DUCTWORK (2X LINE)

DUCT WITH ACOUSTICAL LINING

DUCT WITH FLEXIBLE CANVAS CONNECTION

DUCT W/ TRANSITION

ELBOW WITH TURNING VANES

DUCT SECTION, RETURN AIR

DUCT WITH ROUND ELBOW 1.5∅" TURNING RADIUS MINIMUM

BRANCH TAKE-OFF

DUCT BREAK (CONTINUATION)

NG

HWS

HWR

D

RL

12x20

RS

HG

SUPPLY DIFFUSER

CONCENTRIC REDUCER

FLEXIBLE CONNECTOR

QUICK DISCONNECT

PIPE SLEEVE (STEEL OR CAST IRON)

XX

XXX

XXX

T

T

BD

M

ELBOW

DUCT SECTION, EXHAUST AIR

REFER TO SHEET GI002 FOR ADDITIONAL PROJECT SYMBOLS

MECHANICAL LEGEND

NEW WORK ITEMS (SOLID)

POINT OF DISCONNECTION

POINT OF CONNECTION

SPACE CO2 SENSOR / DDC POINT TAG

EXISTING ITEMS (SOLID, LIGHT)

GENERAL ITEMS PIPING

HOT WATER RETURN

HOT WATER SUPPLY

UNOCCUPIED

EQUIPMENT WITH CLEARANCE

DEMOLISHED ITEMS (DASHED)

OCCUPIED

CONDENSATE DRAIN

NATURAL GAS

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

DIRECTION OF FLOW

DIRECTION OF SLOPE

AIR TERMINAL TAG WITH AIR FLOW (CFM)

CAP / BLIND FLANGE

DROP / RISE IN PIPING

TEE UP

TEE DOWN

UNION

PIPE BREAK (CONTINUATION)

BALL VALVE

DUCT SIZE, FIRST FIGURE IS SIDE SHOWN

BUTTERFLY VALVE

DUCT SECTION, SUPPLY AIR

GATE VALVE

CHECK VALVE

MANUAL BALANCING VALVE

PRESSURE REDUCING VALVE

VALVES & PIPE ACCESSORIES

GLOBE VALVE

MANUAL FLOW CONTROL BALANCING VALVE

2-WAY VALVE

3-WAY VALVE

STRAINER

STRAINER WITH BLOWDOWN VALVE

PRESSURE GAUGE WITH SHUTOFF COCK

THERMOMETER

P & T RELIEF VAVLE (PIPE TO DRAIN)

MANUAL AIR VENT

AUTOMATIC AIR VENT

PT PORT

PUMP

DUCTWORK

RETURN GRILLE

EXHAUST GRILLE

DUCT DAMPERS

BACKDRAFT DAMPER

BALANCE VOLUME DAMPER

FIRE DAMPER

FIRE / SMOKE DAMPER

MOTORIZED DAMPER

SMOKE DAMPER

OPPOSITE BLADE DAMPER

PARALLEL BLADE DAMPER

AIRFLOW DIRECTION

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G S

YS

TE

M S

C O

M M

AN

D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

AS NOTED

M-001

BU

IL

DI

NG

X -1

M

EC

HA

NI

CA

L

LE

G

EN

D, A

BB

RE

VI

AT

IO

NS

A

ND

N

O

TE

S

MRW

12,909,835

YG DAS

05/09/2024

JECC - MICHAEL FREDERICK

M O

DI

FY

S

ER

VI

CE

C

EN

TE

R

(1

IT

C

US

TO

M

ER

S

ER

VI

CE

(1

DUSTIN A. SCHULZE, R.A.

1683970

N/A

NO

RF

OL

K, V

IR

GI

NI

A

NA

VA

L S

TA

TI

ON

J. MILLER, P.E.

JMS

M

ID

LA

N

T -P

W D

N O

R

FO

LK

DESIGN CONDITIONS

WINTER SUMMER

INDOOR OUTDOOR INDOOR OUTDOOR (1% DB) OUTDOOR (1% WB)

DB (°F) RH DB (°F) WB (°F) DB (°F) RH DB (°F) WB (°F) DB (°F) WB (°F)

CONDITIONED 68 - 27 25 78 50 91 77 87 79

CONDITIONED SETBACK 55 - 27 25 85 50 91 77 87 79

NON-OCCUPIED 55 - 27 25 - - 91 77 87 79

GPM GALLONS PER MINUTE

GRH GRAVITY ROOF HOOD

H HUMIDIFIER (ELECTRIC)

HGRC HOT GAS REHEAT COIL (DX)

HGRH HOT GAS REHEAT

HHWS HOT HEATING WATER SYSTEM

HP HEAT PUMP, HORSEPOWER

HR HOUR / HEAT RECOVERY

HT HEIGHT

HX HEAT EXCHANGER

IAW IN ACCORDANCE WITH

IC IN CEILING

IDU INDOOR UNIT (VRF)

IN. INCH

IWG INCHES WATER GAUGE

KW KILOWATT

LBS POUNDS

LPS LOW PRESSURE STEAM

LV LOUVER

LWT LEAVING WATER TEMPERATURE

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MBH 1,000 BTUH

MCA MAXIMUM CIRCUIT AMPS

MD MOTOR OPERATED DAMPER

MIN MINIMUM

NC NORMALLY CLOSED, NOISE CRITERIA

NO NUMBER, NORMALLY OPEN

NP NOT PROVIDED

OA OUTSIDE AIR

OAU OUTSIDE AIR UNIT

OCC OCCUPANCY

ODU OUTDOOR UNIT (VRF)

OG ON GRADE

OH OPPOSITE HAND

PA PRIMARY AIR (VAV TERMINAL)

PH PHASE

PRV POWER ROOF VENTILATOR

PSIG POUNDS PER SQUARE INCH GAUGE

PTAC PACKAGED TERMINAL AIR CONDITIONING UNIT

PTHP PACKAGED TERMINAL HEAT PUMP

PTP PRESSURE/TEMPERATURE TEST PORT

QTY QUANTITY

RA RETURN AIR

RD ROOF DRAIN

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

SA SUPPLY AIR

SAT SUPPLY AIR TEMPERATURE

SD STORM DRAIN

SEER SEASONAL ENERGY EFFICIENCY RATIO

SIM SIMILAR

SP STATIC PRESSURE

SQ SQUARE

SQFT SQUARE FEET

TYP. TYPICAL

UH UNIT HEATER

UOI UNLESS OTHERWISE INDICATED

UON UNLESS OTHERWISE NOTED

V VOLTS

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

VRF VARIABLE REFRIGERANT FLOW

VWV VARIABLE WATER VOLUME

W WIDTH

WB WET BULB

WC WATER COLUMN (PRESSURE)

WH WALL HOOD

WPD WATER PRESSURE DROP

° DEGREES

Ø DIAMETER

Φ OVAL

A/C AIR CONDITIONING

AC ABOVE CEILING

AD ACCESS DOOR

AFD ACCESS FLOOR DIFFUSER

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AI ANALOG INPUT

AIP ABANDON IN PLACE

AL ACOUSTIC LINING (DUCTWORK)

AO ANALOG OUTPUT

AP ACCESS PANEL

APD AIR PRESSURE DROP

AS AIR SEPARATOR

ATFP ANTI-TERRORISM FORCE PROTECTION

AV ANALOG VALUE

B BOILER

BAS BUILDING AUTOMATIC SYSTEM (DDC)

BD BALANCING DAMPER

BDD BACKDRAFT DAMPER (DUCTWORK)

BG BELOW GROUND

BHP BRAKE HORSEPOWER

BI BINARY INPUT

BO BINARY OUTPUT

BOD BOTTOM OF DUCT

BR BASEBOARD RADIATOR

BSB BRANCH SELECTOR BOX (VRF)

BTUH BRITISH THERMAL UNITS PER HOUR

BV BINARY VALUE

CC CEILING CASSETTE / COOLING COIL

CD CEILING DIFFUSER

CER CEILING EXHAUST REGISTER

CFM CUBIC FEET PER MINUTE

CFT CHEMICAL FEED TANK

CH CHILLER

CHP CHILLER PUMP

CLG CEILING

CND CONDENSER

COP COEFFICIENT OF PERFORMANCE

COV CHANGE OF VALUE

CRAHU COMPUTER ROOM HANDLING UNIT

CRG CEILING RETURN GRILLE

CSD CEILING SUPPLY DIFFUSER

CT COOLING TOWER

CTG CEILING TRANSER GRILLE

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

Cv LOSS COEFFICIENT

DB DRY BULB

DCW DOMESTIC COLD WATER (POTABLE)

DDC DIRECT DIGITAL CONTROL

DEG DEGREE

DIA DIAMETER

DOAS DEDICATED OUTSIDE AIR UNIT

DWGS DRAWINGS

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC ELECTRIONICALLY COMMUTATED (MOTOR) / ELECTRIC HEAT COIL

EER ENERGY EFFICENCY RATIO

EF EXHAUST FAN

EFF EFFECTIVENESS / EFFICIENCY

EH ELECTRIC HEAT

ERV ENERGY RECOVERY VENTILATOR

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETR EXISTING TO REMAIN

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER TEMPERATURE

F FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FT FEET

FT WG FEET WATER GAUGE

G NATURAL GAS

A. THESE GENERAL MECHANICAL NOTES APPLY TO ALL MECHANICAL

DRAWINGS IN THIS SET. SHEET SPECIFIC NOTES ARE INDICATED ON EACH

SHEET UNDER GENERAL SHEET NOTES.

B. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR

REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS

AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY

CODE.

C. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, CONTRACT

DOCUMENTS, APPLICABLE CODES, AND REGULATIONS.

D. EXISTING DUCT AND PIPING SIZES INDICATED ARE APPROXIMATE. FIELD

VERIFY ALL EXISTING CONDITIONS.

E. PATCH ALL HOLES FROM REMOVAL OF PIPING, DUCTWORK, OR EQUIPMENT

TO MATCH ADJACENT CONSTRUCTION.

F. CONCEAL ALL DUCTWORK AND PIPING ABOVE SUSPENDED CEILINGS AND IN

WALLS, UNLESS OTHERWISE NOTED.

G. PROVIDE VIBRATION ISOLATORS FOR ALL MECHANICAL EQUIPMENT AND

PIPING TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING

STRUCTURE.

H. PROVIDE ACCESS PANELS IN WALLS AND CEILINGS, WHERE REQUIRED, TO

SERVE FIRE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER

CONCEALED MECHANICAL EQUIPMENT THAT REQUIRES ROUTINE

MAINTENANCE. ACCESS PANELS MUST BE SIZED AS REQUIRED TO ALLOW

WORKING CLEARANCE FOR DUCT ACCESS DOORS.

I. ALL 90 DEGREE RECTANGULAR MITERED DUCT ELBOWS IN SUPPLY AND

RETURN DUCTWORK MUST HAVE TURNING VANES. PROVIDE AN ACCESS

DOOR UPSTREAM OF ELBOW FOR TURNING VANE INSPECTION AND

CLEANING.

J. PROVIDE PIPE SLEEVES FOR ALL PIPING PENETRATIONS THRU WALLS AND

FLOORS. EACH PIPE MUST BE SEPARATELY SLEEVED. PROVIDE

CONTINUOUS SEALANT JOINT AROUND PIPE SLEEVE, BOTH SIDES OF WALL,

WATERTIGHT.

K. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC.,

MUST BE FIRE STOPPED.

L. PROVIDE P-TRAPS IN CONDENSATE DRAIN PIPING AT EACH AC UNIT UNLESS

THE RTU IS EQUIPPED WITH AN INTERNAL TRAP.

M. CONDENSATE DRAIN PIPING CLEANOUTS SHALL BE INSTALLED AT EACH

CHANGE IN DIRECTION GREATER THAN 45 DEGREES. WHERE MORE THAN

ONE CHANGE OF DIRECTION…