Site Visit Log and Inspection Reports.pdf
PDF 3 MB Posted
- Attached to
- Fire protection
- Solicitation number
- N4008524R2525
About this file
This document is a set of fire protection inspection reports for various buildings at the Philadelphia Navy Yard and the Philadelphia Naval Business Center. The reports detail the inspection and testing of fire alarm systems, kitchen hood systems, pre-action sprinkler systems, and carbon dioxide suppression systems across multiple facilities.
The key details include:
- Inspection dates, technicians, and contact information
- Descriptions of the fire protection systems, including manufacturer models and system types
- Test results for system components such as detectors, pull stations, notification appliances, and supervisory devices
- Identification of any deficiencies or required maintenance
- Recommentations for system upgrades or replacements
- Details on the status of the systems, including whether they were left in service or red-tagged as non-compliant.
The reports indicate the fire protection systems are critical infrastructure supporting various naval and government facilities, and the inspections are conducted to verify compliance with applicable fire codes and standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 24R2525_Amendment0004.pdf | ||
| 24R2525_Amendment0003.pdf | ||
| 24R2525_Amendment0002.pdf | ||
| 24R2525_Amendment0001.pdf | ||
| Base Access Spreadsheet.xls | XLS spreadsheet | |
| Section F - Deliveries or Performance.pdf | ||
| Section C - Annexes.pdf | ||
| J-0200000-06 ELINS KTR Fill In.xlsx | XLSX spreadsheet | |
| 24R2525_Fire Protection_RFP.pdf | ||
| 1502000 J Facility Investment.pdf | ||
| 0200000 J Management and Administration.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Submitted To:
NAVFAC
Philadelphia Navy Yard
Fire Protection Inspection Report
NAVFAC Building #1000 | 22169
Building #1000 Fire Alarm Inspection
Date of Inspection: June-22-2023 20:00 Technician: Title: Fire inspector
Type of Inspection: Annual Semi-Annual Protected Property
Name: PNBC Building #1000
Address: Philadelphia Navy Yard
City: Philadelphia State: PA Zip: 19112
System
Name: NAVFAC Address: 4921 S. Broad Street, Bldg. 1, 2nd Floor
City: Philadelphia State: PA Zip: 19112
Type of Fire Alarm System System ID: 1000 Type: Proprietary Does this system include mass notification? Yes
Fire Alarm Signaling System Monitoring
Is this system monitored off-site? Yes No If yes, make and model of DACT: AES
If yes, provide name, location, and phone number of monitoring company: Dispatch Region Norfolk, Power Supply System
Primary Power (Dedicated):
Yes No N/A
Locked Out? Yes No N/A Disconnecting Means Location: 1st fl chiller rm ERP Panel Brk 21
Secondary: Battery Voltage/Amp Hour Rating: 24Vdc 55Ah Battery Type: Battery Type: Dry-Cell Nickel-Cadmium Sealed Lead-Acid Lead-Acid Other (Specify):
Tested Ok? Yes No N/A Location:
Battery Condition: Pass Fail Notes/Comments:
Load Voltage: Pass Fail Notes/Comments:
Discharge Test: Pass Fail Notes/Comments:
Charger Test: Pass Fail Notes/Comments:
Remote Panel Batteries: Pass Fail Notes/Comments:
Engine Driven Generator Rating: Tested, Ok? Yes No N/A
Fueled by: Storage Capacity:
Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
No Yes (Please refer to deficiency comments page) Alarm Initiating Devices
Device Tested Deficiencies Remarks Manual Pull Stations 35 0 Heat Detectors 3 0 Smoke Detectors 81 0 Duct Detectors 17 0 Waterflow 11 0
Alarm Indicating Devices
Device Number Failed Deficiency Description Bells Horns/Strobes Chimes Speakers Speaker Strobes Remote Annunciators Visual Signals
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 4 Are circuits monitored for integrity? Yes No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches 15 0 Pressure Switches Temperature Switches Water Supply Level
Fire Pump 1 0 Control Unit
Manufacturer: Notifier Model #: 640
Type: Hardwired Multiplex Addressable Addressable with Voice Evacuation Other (Specify)
Circuit Style: Class A Class B Class C Class D Class X Software Revision: Date of Last Software Revision:
Device Tested Deficiencies Remarks Lamps/LEDs/LCDs Pass No Fuses Pass No Trouble Signals Pass No Zone Disable Pass No Disconnect Switches Pass No Supervisory Signals Pass No Ground Fault Pass No Transmit Off Premises
Fail No Region does not receive signals. PNBC dispatch bldg. 29 received signals
Remote Power Panels Pass No
Other Pass No
Are all devices uniquely identified where applicable? Yes No
Inspection Deficiencies West lobby Elevator: fireman’s Hat not flashing on fire alarm in elevator machine room.
Accessible bathrooms – no a/v. Penthouse; Bell strobe at egress – no bell function. Remove old fire pump points from program. Horn strobe room 288, no flash. Bell column E10, no sound.
Fourth floor, north office spaces, horn strobes out of sync. Third floor horn strobes out of sync.
Second and first floor horn strobes out of sync.
Device Test Log
Device ID Device Type Location Result Notes L1D002 Smoke detector 1st floor west freight elevator Pass
L1D003 Smoke detector 1st floor Northeast freight elevator Pass
L1D004 Smoke detector 1st floor southeast freight elevator Pass
L1D005 Smoke detector 1st floor east side passenger elevator
Pass
L1D006 Smoke detector 1st floor southwest electrical substation
Pass
L1D007 Smoke detector 2nd floor northeast freight elevator Pass
L1D008 Smoke detector 2nd floor East passenger elevator Pass
L1D009 Smoke detector 2nd floor northwest freight elevator Pass
L1D010 Duct detector 2nd floor northwest mechanical room as-1 supply
Pass
L1D011 Duct detector 2nd floor Northwest mechanical room as-1 return
Pass
L1D012 Smoke detector 2nd floor southwest mechanical room as-2 supply
Pass
L1D013 Duct detector 2nd floor southwest mechanical room as-2 return
Pass
L1D014 Duct detector 2nd floor southeast mechanical room as-3 supply
Pass
L1D015 Duct detector 2nd floor southeast mechanical room as-3 return
Pass
L1D016 Duct detector 2nd floor northeast mechanical room as-4 supply
Pass
L1D017 Duct detector 2nd floor northeast mechanical room as -4 return
Pass
L1D090 Duct detector 2nd floor mechanical room 237 Pass
L1D018 Duct detector Ahu 8 penthouse supply Pass
L1D019 Duct detector Ahu 6 penthouse supply Pass
L1D020 Duct detector Ahu 10 penthouse supply Pass
L1D021 Duct detector Ahu 9 penthouse supply Pass
L1D022 Duct detector Ahu 5 penthouse supply Pass
L1D023 Duct detector Ahu 7 penthouse supply Pass
L1D024 Smoke detector 2nd floor southeast freight elevator Pass
L1D025 Smoke detector 3rd floor Northeast freight elevator Pass
L1D026 Smoke detector 3rd floor Southeast freight elevator Pass
L1D027 Smoke detector 3rd floor east passenger elevator Pass
L1D028 Smoke detector 3rd floor Northwest freight elevator Pass
L1D029 Smoke detector 4th floor east passenger elevator Pass
L1D030 Smoke detector 4th floor northeast freight elevator Pass
L1D031 Smoke detector 4th floor northwest freight elevator Pass
L1D032 Smoke detector 4th floor southeast freight elevator Pass
L1D033 Smoke detector 2nd floor Rm 261 Pass
L1D034 Smoke detector 2nd floor Rm 261 Pass
L1D035 Duct detector 4th floor northwest rest room exhaust
Pass
L1D036 Duct detector 4th floor southeast rest room exhaust
Pass
L1D037 Duct detector 4th floor Northeast restroom exhaust
Pass
L1D038 Duct detector 4th floor southwest rest room exhaust
Pass
L1D039 Smoke detector 3rd floor Northeast substation Pass
L1D040 Smoke detector 3rd floor Northeast substation Pass
L1D041 Smoke detector 3rd floor Southeast substation Pass
L1D042 Smoke detector 3rd floor Northwest substation Pass
L1D043 Smoke detector 3rd floor Southwest substation Pass
L1D044 Smoke detector Northeast mezzanine electrical substation
Pass
L1D045 Smoke detector 1st floor southeast electrical substation
Fail circuit shorted out
L1D046 Heat detector Northwest 1st floor electrical substation
Pass
L1D047 Heat detector Northwest Mezzanine electrical substation
Pass
L1D049 Heat detector Southwest mezzanine substation Pass
L1D050 Smoke detector 2nd floor office room 258 Pass
L1D051 Smoke detector 1st floor west passenger elevator lobby
Pass
L1D052 Smoke detector 2nd floor west passenger elevator lobby
Pass
L1D053 Smoke detector 4th floor west passenger elevator lobby
Pass
L1D054 Smoke detector West passenger elevator mechanical room
Pass
L1D055 Smoke detector Roof top southeast freight elevator mechanical room
L1D056 Smoke detector Northwest roof freight elevator machine room
Pass Device removed/Bypassed
L1D059 Smoke detector Northeast roof elevator machine room
Pass
L1D060 Smoke detector Penthouse northeast Pass
L1D061 Smoke detector Penthouse center east Pass
L1D062 Smoke detector Penthouse center east Pass
L1D063 Smoke detector Penthouse Southeast Pass
L1D064 Smoke detector Penthouse Southeast Pass
L1D065 Smoke detector Penthouse Southeast Pass
L1D066 Smoke detector Penthouse northeast Pass
L1D067 Smoke detector Penthouse Southeast Pass
L1D068 Smoke detector Penthouse center east Pass
L1D069 Smoke detector Penthouse northeast Pass
L1D070 Smoke detector Penthouse center south Pass
L1D071 Smoke detector Penthouse center Pass
L1D072 Smoke detector Penthouse center north Pass
L1D073 Smoke detector Penthouse center south Pass
L1D074 Smoke detector Penthouse center Pass
L1D075 Smoke detector Penthouse center north Pass
L1D076 Smoke detector Penthouse center south Pass
L1D077 Smoke detector Penthouse center Pass
L1D078 Smoke detector Penthouse center north Pass
L1D079 Smoke detector Penthouse southwest Pass
L1D080 Smoke detector Penthouse center west Pass
L1D081 Smoke detector Penthouse northwest Pass
L1D082 Smoke detector Penthouse southwest Pass
L1D083 Smoke detector Penthouse center west Pass
L1D084 Smoke detector Penthouse northwest Pass
L1D085 Smoke detector Penthouse southwest Pass
L1D086 Smoke detector Penthouse center west Pass
L1D087 Smoke detector Penthouse northwest Pass
L1D089 Smoke detector Penthouse northeast freight machine room
Pass
L1D100 Smoke detector West passenger elevator shaft Pass
L1D101 Smoke detector Stairwell 4S5 Pass
L1D102 Smoke detector Stairwell 4S1 Pass
L1D103 Smoke detector Stairwell 4S2 Pass
L1D104 Smoke detector Stairwell 4S4 Pass
L1D105 Smoke detector Stairwell 4S7 Pass
L1D106 Smoke detector Stairwell 4S6 Pass
L1D107 Smoke detector Stairwell 4S3 Pass
L1D109 Smoke detector 2nd floor room 289 Pass
L1D110 Smoke detector 2nd floor room 253 Pass
L1D111 Smoke detector 2nd floor room 254 EPS Lab storage
Pass
L1D112 Smoke detector 2nd floor room 254 EPS Lab storage
Pass
L1D113 Smoke detector 2nd floor room 254 EPS Lab storage
Pass
L1D114 Smoke detector 2nd floor room 289 rear Pass
L1D115 Smoke detector 3rd floor west elevator lobby Pass
L1D116 Smoke detector 2nd floor center west electrical room
Pass
L1D118 Duct detector 3rd floor mechanical room 307 Pass
L1D119 Duct detector 3rd floor mechanical room 307 Pass
L1D117 Smoke detector 2nd floor center west data closet Pass
L1M001 Water flow 2nd floor ceiling south Pass
L1M006 Water flow 2nd floor ceiling north Pass
L1M005 Tamper 2nd floor ceiling south No access
L1M007 Tamper 2nd floor ceiling north No access
L1M002 Tamper 3rd floor room 320 paint booth Pass
L1M003 Tamper 3rd floor ceiling south No access
L1M016 Tamper 3rd floor north ceiling No access
L1M0108 Tamper 3rd floor above roof room 301 Pass
L1M004 Water flow 3rd floor ceiling north Pass
L1M011 Water flow 3rd floor ceiling south Pass
L1M008 Water flow 1st floor sub life ceiling south Pass
L1M012 Water flow 1st floor ceiling north Pass
L1M020 Tamper South sub life ceiling south No access
L1M021 Tamper 1st floor level 1 ceiling north No access
L1M095 Tamper Fire pump house Pass
L1M096 Water flow Fire pump house Pass
L1M097 Tamper Fire pump house Pass
L1M098 Tamper Fire pump house Pass
L1M110 Tamper Fire pump House Pass
L1M111 Tamper Fire pump house Pass
L1M099 Fire pump run Fire pump house Pass
L1M100 Fire pump fail Fire pump house Pass
L1M101 Fire pump Phase/Rev.
Fire pump Pass
L1M013 Tamper 4th floor north ceiling No access
L1M014 Tamper 4th floor south ceiling No access
L1M015 Water flow 4th floor north ceiling Pass
L1M017 Water flow 4th floor south ceiling Pass
L1M022 Water flow Penthouse south ELMR room/Tamper
Pass
L1M066 Water flow Penthouse west passenger elevator mechanical room
Pass Tested via switch
L1M067 Tamper Penthouse West elevator machine room
Pass
L1M023 Smoke detector 1st floor cake box No access
L1M031 Pull station 1st floor high bay to main lobby Pass
L1M032 Pull station 1st floor high bay column A4 Pass
L1M033 Pull station 1st floor high bay north entrance Pass
L1M034 Pull station 1st floor high bay column E1 Pass
L1M035 Pull station 1st floor high bay northeast stair Pass
L1M036 Pull station 1st floor center east stair Pass
L1M037 Pull station 1st floor high bay southeast stairwell
Pass
L1M038 Pull station 1st floor high bay south exit Pass
L1M039 Pull station 1st floor high bay southwest stairwell
L1M040 Pull station 2nd floor center east stairwell Pass
L1M041 Pull station 2nd floor southeast stairwell Pass
L1M042 Pull station 2nd floor room 219 southeast Pass
L1M043 Pull station 2nd floor room 219 southeast Pass
L1M044 Pull station 2nd floor room 219 south Pass
L1M045 Pull station 2nd floor room 205 Pass
L1M046 Pull station 2nd floor southwest Pass
L1M047 Pull station 2nd floor center west stairwell Pass
L1M048 Pull station 2nd floor Northwest stairwell Pass
L1M049 Pull station 2nd floor fire lab room 281 Pass
L1M050 Pull station 2nd floor Northeast stairwell Pass
L1M051 Pull station 3rd floor east center stairwell Pass
L1M052 Pull station 3rd floor Northeast stairwell Pass
L1M053 Pull station 3rd floor Southeast stairwell Pass
L1M054 Pull station 3rd floor center west stairwell Pass
L1M055 Pull station 4th floor center east stairwell Pass
L1M056 Pull station 4th floor Northeast stairwell Pass
L1M057 Pull station 4th floor southeast stairwell Pass
L1M058 Pull station 4th floor northwest stairwell Pass
L1M059 Pull station 4th floor southwest stairwell Pass
L1M060 Pull station Penthouse east Pass
L1M061 Pull station Penthouse north Pass
L1M062 Pull station 3rd floor Northwest stairwell Pass
L1M063 Pull station 3rd floor Northwest stairwell Pass
L1M064 Pull station 4th floor center west stairwell Pass
L1M065 Pull station 1st floor hazmat room 135 Pass
Images Device ID Device Type
Remote Panel Test Log Panel Type Panel Location Class A/B Battery
Type Battery 1 Volts/Ah
Battery 2 Volts /Ah
Pass/Fail Comments
AES Above Facp B Sealed Lead-Acid
12.V/7Ah N/A Pass
FACP FACP B Sealed
12V/55Ah 12V/55Ah Fail Failed load test
Nac Power supply
By FACP B Sealed Lead-Acid
12V/7Ah 12V/7Ah Pass
NnnNac Nac Power supply
By FACP B Sealed Lead-Acid
12.V/7Ah 12.V/7Ah Pass
NAC
NnnNac Nac Power supply
By FACP B Sealed Lead-Acid
12.V/7AH 12.V/7Ah Pass
Nac Power supply
2nd floor N/W B Sealed Lead-Acid
12/7Ah 12/7Ah Pass
Nac Power supply
3rd floor AHU room
B Sealed
12V/7Ah 12V/7Ah Pass
1. Penthouse
a. Add additional notification devices.
2. 4th Floor
a. No synchronization North office space
b. Add Horn strobes South office spaces
3. 3rd Floor
a. Strobe outside vault inside cage area – no function
b. No synchronization
c. Add Horn strobes old vault area
d. Add Horn strobe north end cage area
4. 2nd Floor
a. No synchronization/add horns to rm 268 and 245
b. Bell strobe by stairwell 254 weak sound/288 no flash
c. No synchronization/add horns to rm 268 and 245
d. Bell strobe S/W office ctr column no sound
e. Bell strobe column E15 no flash rm 288 no flash or sound
5. 1st Floor
a. Bell column E8 – bell no function
b. No synchronization
c. Bell strobe column C15 facing wrong direction.
d. N/E electrical substation AHU 100 Two duct detectors not integrated to facp
e. Add Horn strobe Sub life office
f. Add Horn strobe Pollution abatement lab
g. Add Horn strobe Chiller room
h. Add Horn strobe column D10
6. Locked Rooms (locked rooms, not accessible.
a. Cake Box, no access 2nd Cake box
7. Add or move pull station to egress Hazmat locker room 135
1. Kitchenette by 463 – recommend changing to strobe from horn/strobe.
2. Several rooms/areas no a/v coverage or lacking a/v coverage (some considerations listed below) 435 conference room 429 lab 104A
Nac Power supply
4th fl S/E B Sealed
12V/7Ah 12V/7Ah Pass
General Inspection Notes
104B 116A 118 lab 1st fl Columns C17/D17 1st fl Columns D5/D6/D7 130 mod offices 1st floor utility room 1st floor lobby 219 center column 2nd fl Column C7 2nd fl additional strobe to gym weight room Fire lab West end lobby All restrooms Elevator lobbies
Recommend changing all bell strobes to horn strobes; change existing horns and strobes to same manufacturer. Inadequate notification in areas listed above.
700 Robbins Street
215.294.7093
Reviewed by:
2023-07-06
NAVFAC NSA Building #1 | 22169
NSA Building #1 Fire Alarm Inspection
Date of Inspection: July-06-2023 15:00 Technician: Title: Fire Inspector
Type of Inspection: Annual Semi-Annual Protected Property
Name: NSA Building #1
Address: Philadelphia Navy Yard
City: Philadelphia State: PA Zip: 19112 Contact:
Phone:
System Owner Name: NAVFAC Address: 4921 S. Broad Street Bldg. #1 2nd Floor City: Philadelphia State: PA Zip: 19112
Type of Fire Alarm System System ID: 01
Type: Remote Station Does this system include mass notification? No Fire Alarm Signaling System Monitoring
Is this system monitored off-site? Yes If yes, make and model of DACT: Digitizer Det-68 If yes, provide name, location, and phone number of monitoring company: Dispatch Region, Norfolk Va
Power Supply System Primary Power (Dedicated):
Yes No N/A
Locked Out? Yes No N/A Disconnecting Means Location: Switch room 1112
Secondary: Battery Voltage/Amp Hour Rating: 24VDC 18 AH Battery Type: Battery Type: Dry-Cell Nickel-Cadmium Sealed Lead-Acid Lead-Acid Other (Specify):
Tested, Ok? Yes No N/A Location: FACP
Battery Condition: Pass Fail Notes/Comments:
Load Voltage: Pass Fail Notes/Comments:
Discharge Test: Pass Fail Notes/Comments:
Charger Test: Pass Fail Notes/Comments:
Remote Panel Batteries: Pass Fail Notes/Comments: See battery report Engine Driven Generator Rating: NA Tested Ok? NA
Fueled by: NA Storage Capacity: NA Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
No Yes (Please refer to deficiency comments page) Alarm Initiating Devices
Device Tested Deficiencies Remarks Manual Pull Stations 44 0 Heat Detectors 306 23 Smoke Detectors 14 0 Duct Detectors 5 2 Waterflow 39 0
Alarm Indicating Devices Device Number Failed Deficiency Description Bells 0 Horns/Strobes 0
Chimes NA Speakers NA Speaker Strobes NA Remote Annunciators NA Fire Alarm Strobes 0 MNS Strobes NA Sounder Bases NA Visual Signals 0 IR Detectors NA Other NA
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 3 Are circuits monitored for integrity? Yes No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches 4 0 Low Air Switches NA Pressure Switches NA Temperature Switches NA Water Supply Level NA Fire Pump NA
Control Unit Manufacturer: (7) FCI Panels Model #: 72 Type: Hardwired/Conventional Circuit Style: Class B Software Revision: NA Date of Last Software Revision: NA Device Tested Deficiencies Remarks Lamps/LEDs/LCDs Pass No Fuses Pass No Trouble Signals Pass No Zone Disable Pass No Disconnect Switches Pass No Supervisory Signals Pass No Ground Fault Pass No Transmit Off Premises Pass No Remote Power Panels NA Other NA
Are all devices uniquely identified where applicable? Yes No
Inspection Deficiencies Remove delay relay switches on FACP.
Heat detectors wing one, credit union failed.
Heat Detector Location 1st floor wing two above FACP wires removed from FACP.
Heat Detector 1st floor wing command center 1208 conference room ceiling mounted detector above ceiling.
Duct Detector 1st floor wing four AHU-1 No signal received/No power.
Heat Detector Wing 5 zone 12 above ceiling devices are bypassed/resistored.
Heat Detector 1st floor wing six NW office removed from ceiling thrown above ceiling.
Heat Detector 1st floor wing six 4 column from entrance removed from ceiling tile.
Device ID Device Type Location Result Notes ZONE 5/6 Heat Detector 1st floor wing one room 1101 Pass Above ceiling/Ceiling
ZONE 5/6 Heat Detector 1st floor wing one room 1103 Pass Above ceiling/Ceiling
ZONE 5/6 Heat Detector 1st floor wing one hallway to restrooms
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 1st floor wing one women's room Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 1st floor wing one men�s room Pass Above ceiling/Ceiling
Zone 19 Heat Detector 1st floor wing one above FACP Pass Zone 5 Heat Detector 1st floor wing one Duty officer�s guestroom No access Tested via circuit
Zone 3 Smoke Detector 1st floor wing one Duty officers VIP Room
No access Tested via circuit
Zone 5/6 Heat Detector 1st floor wing one hallway by storage room 1105
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 1st floor wing one hallway center Pass Above ceiling/Ceiling Zone 6 Heat Detector 1st floor wing one dispatch office room 1111 Pass Above ceiling
Zone 6 Heat Detector 1st floor wing one room 1113 Pass Above ceiling
Zone 6 Heat Detector 1st floor wing one room 1115 Pass Above ceiling Zone 5/6 Heat Detector 1st floor wing one hallway by rm
Pass Above ceiling/Ceiling
Zone 5 Heat Detector 1st floor wing one switch room Pass Two devices
Zone 5/6 Heat Detector 1st floor wing one hallway by rm
No access Above ceiling/Ceiling
Zone 5/6 Heat Detector 1st floor wing one room 1117 No access Tested via circuit
Zone 5/6 Heat Detector 1st floor wing one room 1119 No access Tested via circuit
5/6 Heat Detector 1st floor wing one credit union rm 1121
Fail Four ceiling mounted four above ceiling
Zone 5/6 Heat Detector 1st floor wing one hallway by card access door
Pass One ceiling mounted one above ceiling
Zone 8 Heat Detector 2nd floor wing one south stairwell
Pass
Zone 8/9 Heat Detector 2nd floor wing one conference room
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one by south exit Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one 3rd column from south exit
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one 5th column from south exit
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one eighth column from south exit
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one 10th column from south exit
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one Northwest office
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one west center office
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one north conference room
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one northeast office
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one southeast office
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one conference room 2101
No access Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one room 2101 No access Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one room 2102 Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one room 2103 Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing one hallway by office 2102
Pass
Zone 8/9 Heat Detector 2nd floor wing one women�s room
Pass Above ceiling/ceiling
Zone 11 Smoke Detector 3rd floor wing one north stairwell Pass Zone 12/13 Heat Detector 3rd floor wing one hallway by office 3101 Pass Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing one room 3101 Pass Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing one room 3102 Pass Three ceiling mounted three above ceiling
Zone 12/13 Heat Detector 3rd floor wing one by south exit Pass Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing one by fifth column from south exit
Pass
Zone 12/13 Heat Detector 3rd floor wing one by eighth column from south exit
Pass Above ceiling/Ceiling
12/13 Heat Detector 3rd floor wing one by tenth column from south exit
Pass Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing one 10th column north- east office
Pass Two above ceiling. One for below ceiling and tossed above ceiling due to tile replaced.
Zone 11 Smoke Detector 3rd floor wing one south stairwell Pass Zone 14 Heat Detector Penthouse Pass Zone 1 Pull Station 1st floor wing one south exit Pass
Zone 2 Pull Station 1st floor wing one north exit Pass
Zone 1 Pull Station 1st floor wing one south restroom exit
Pass
Zone 1 Pull Station 1st floor wing one south handicapped entrance
Zone 7 Pull Station 2nd floor wing one north Pass
Zone 7 Pull Station 2nd floor wing one south exit Pass
Zone 10 Pull Station 3rd floor wing one north Pass
Zone 10 Pull Station 3rd floor wing one south Pass
Zone 15 Waterflow Switch 1st floor wing one north Pass Tested via switch Zone 15 Waterflow Switch 1st floor wing one south Pass Tested via switch Zone 16 Waterflow Switch 2nd floor wing one north Pass Tested via switch Zone 16 Waterflow Switch 2nd floor wing one south Pass Tested via switch ZONE 17 Waterflow Switch 3rd floor wing one north Pass Tested via switch Zone 17 Waterflow Switch 3rd floor wing one south Pass Tested via switch Zone 18 Waterflow Switch Penthouse Pass Tested via switch
FACP 72
24Vdc 18Ah FACP 1st floor wing two Pass (3) Nac circuits. Safety switch room 1112, communicator Digitizer Det-6B one 12Vdc 7 Ah battery
Not integrated into facp
Heat Detector 1st floor wing two above FACP Fail
Zone 2/3 Heat Detector 1st floor wing two office N983 Pass Three mounted ceiling three above ceiling
Zone 2/3 Heat Detector 1st floor wing two south office by water flow
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two hallway by conference room
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two north of conference room
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two west of third column from south exit
Pass
Zone 2/3 Heat Detector 1st floor wing two fifth column from south exit
Pass One ceiling mounted one above
Zone 2/3 Heat Detector 1st floor wing two 5th column from south exit east
Pass
Zone 2/3 Heat Detector 1st floor wing two 6th column from south exit west
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two between columns 7 an 8 from south exit
Pass Two ceiling mounted two above ceiling
Zone 2/3 Heat Detector 1st floor wing two Bev Thomas conference room
Pass One ceiling mounted one above ceiling
Zone 2/3 Heat Detector 1st floor wing two room N9833 Not Tested No access
Zone 2/3 Heat Detector 1st floor wing two room 1123 No access
Zone 2/3 Heat Detector 1st floor wing two women's room
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two hallway outside women's room
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two men's room Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing two room 1131 Pass Above ceiling
Zone 2/3 Heat Detector 1st floor wing two room 1201 Pass
Zone 2/3 Heat Detector 1st floor wing two hallway outside room 1202
Pass Above ceiling/Ceiling
Zone 5 Heat Detector 2nd floor wing two south stairwell
Pass
Zone 5/6 Heat Detector 2nd floor wing two by south water flow
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two south office no room number
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two hallway by 1st column from south exit
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two third column from south exit
Pass One ceiling mounted one above ceiling
Zone 6 Heat Detector 2nd floor wing two third column from south exit west
Pass By column M10
Zone 6 Heat Detector 2nd floor wing two 3rd column west above
Pass
Zone 5/6 Heat Detector 2nd floor wing two column K10 Pass One ceiling mounted one above ceiling
Zone 6 Heat Detector 2nd floor wing two west of 5th column from south exit
Pass Above ceiling
Zone 5/6 Heat Detector 2nd floor wing two by double blue doors
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two conference room
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two hallway outside room 2105
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two room 2105 Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two women's bathroom
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two room 2104 Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two men's room
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two room 2203 Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing two room 2223 Pass Above ceiling/Ceiling
Zone 8 Smoke Detector 3rd floor wing two south stairwell
Pass
Zone 9/10 Heat Detector 3rd floor wing two east of south exit
Pass Two mounted ceiling two above ceiling
Zone 9/10 Heat Detector 3rd floor west of south exit offices
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor 1st column from south exit
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing two 4th column from south exit
Zone 9/10 Heat Detector 3rd floor wing two 7th column from south exit
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing two tele conference cubicle
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing two room 3103 Pass Two ceiling mounted two above ceiling
Zone 9/10 Heat Detector 3rd floor wing two room 3104 Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing two room 3106 Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing two room 3105 Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing two women's bathroom
Pass
Zone 9/10 Heat Detector 3rd floor wing two conference room 3201
No access
Zone 1 Pull Station 1st floor wing two south exit Pass
Zone 4 Pull Station 2nd floor wing two south exit Pass
Zone 7 Pull Station 3rd floor wing two south exit Pass
Zone 11 Waterflow Switch 1st floor wing two north Pass Tested via switch Zone 12 Waterflow Switch 1st floor wing two south Pass Tested via switch
Zone 13 Waterflow Switch 2nd floor wing two north Pass Tested via switch
Zone 14 Waterflow Switch 2nd floor wing two south Pass Tested via switch
Zone 15 Waterflow Switch 3rd floor wing two north Pass Tested via switch
Zone 16 Waterflow Switch 3rd floor wing two south Pass Tested via switch
Command center
FACP 1st floor wing command center Pass (3) NAC circuits. Two 12Vdc 18Ah batteries safety switch for 120AC in wing 1 room 1112
4/5 Heat Detector 1st floor wing command center hallway by heater room 1204
Pass One ceiling mounted one above ceiling
Zone 4/5 Heat Detector 1st floor wing command center business office
Pass five) mounted on ceiling five above ceiling
Zone 4/5 Heat Detector 1st floor wing command center 1205B
Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing command center 2205A
Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing command center 1208 conference room
Pass Above ceiling/ceiling H/D for ceiling above ceiling due to tile change
4/5 Heat Detector 1st floor command center rm
Pass One ceiling mounted one above ceiling
Zone 3 Heat Detector 1st floor wing command center rm 1204 heater rm
Pass Two devices
Zone 8 Smoke Detector 2nd floor wing command stairwell
Pass
Zone 8/9 Heat Detector 2nd floor wing command center hallway
Zone 8/9 Heat Detector 2nd floor wing command center rm 2207
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2206
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor command center women�s room 2229
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center hallway by 2221
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2222
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center hallway center
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2207A
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2207B
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2221
Pass Above ceiling/Ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2213A-B
Pass Four ceiling mounted four above ceiling
Zone 8/9 Heat Detector 2nd floor wing command center lobby
Pass Two ceiling mounted two above ceiling
Zone 8/9 Heat Detector 2nd floor wing command center rm 2209
Pass Four ceiling mounted four above ceiling
Zone 8 Heat Detector 2nd floor wing command center rm 2209
Pass One detector in each closet
Zone 12 Smoke Detector 3rd floor wing command center stairwell
Pass
Zone 12/13 Heat Detector 3rd floor wing command center
Pass Three ceiling mounted three above ceiling
Zone 12/13 Heat Detector 3rd floor wing command center command Ops
Pass Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing command center
VTC1
Pass Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing command center rm 3205
No access Above ceiling/Ceiling
Zone 12/13 Heat Detector 3rd floor wing command center rm 3205 equipment rm
No access Above ceiling/Ceiling
12/13 Heat Detector 3rd floor wing command center rm 3206
Not Tested One ceiling mounted one above ceiling
12/13 Heat Detector 3rd floor wing command center rm 3209
Not Tested One ceiling mounted one above ceiling
12/13 Heat Detector 3rd floor wing command center comptroller
Pass two ceiling mounted two above ceiling
12/13 Heat Detector 3rd floor wing command center conference rm
Pass One ceiling mounted one above ceiling
Zone 12 Smoke Detector 3rd floor wing command center conference rm
Pass
12/13 Heat Detector 3rd floor wing command center
Pass Seven ceiling mounted seven above ceiling
Zone 11 Smoke Detector 3rd floor wing command center vault
Not Tested
No zone listed as duct
Duct Detector 1st floor wing command center mechanical rm
Pass
Zone 18 Pull Station 1st floor south wing command center by FACP
Pass
Zone 2 Pull Station 1st floor wing command center mechanical rm
Pass
Zone 1 Pull Station 1st floor south wing command center outside
Pass
Zone 7 Pull Station 2nd floor wing command center stairwell
Pass
Zone 6 Pull Station 2nd floor north wing command center
Pass
Zone 10 Pull Station 3rd floor wing command center stairwell
Pass
Zone 14 Waterflow Switch 1st floor wing command center Pass Tested via switch
Zone 15 Waterflow Switch 2nd floor wing command center Pass Tested via switch
Zone 15 Waterflow Switch 3rd floor wing command center Pass Tested via switch
Wing 3 FACP 1st floor wing three Pass (3) NAC circuits 24 Vdc 18 Ah batteries Safety switch rm 1112
Zone 18 Heat Detector 1st floor wing three above FACP Pass 2/3 Heat Detector 1st floor wing three CDR Lee
Eubanks office Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three Matthew O�Neill office
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three Fleet Outfitting office
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three 2nd column from entrance
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three 5th column from entrance
Pass Above ceiling/Ceiling
ZONE 2/3 Heat Detector 1st floor wing three outside conference rm
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three conference room
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three outside mailroom
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three mailroom Pass Two ceiling mounted two above ceiling
Zone 2/3 Heat Detector 1st floor wing three men's room
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three women's room 1307
Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three room 1308 Pass Above ceiling/Ceiling
Zone 2/3 Heat Detector 1st floor wing three room 1313 No access
Zone 2/3 Heat Detector 1st floor wing three room 1309 Pass Tested via circuit
Zone 2/3 Heat Detector 1st floor wing three freight elevator room 1314
No test Replace device, painted over.
Remove tape
Zone 2/3 Heat Detector 1st floor wing three outside women's room
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three South east office
Pass
ZONE 5/6 Heat Detector 2nd floor wing three south Conference room
Pass Above ceiling/Ceiling
ZONE 5/6 Heat Detector 2nd floor wing three by 1st column from entrance
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three by 2nd column from entrance
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three by 5th column from entrance
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three by 7th column from entrance
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three north east office
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three north west office
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three outside men's room
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three men's room Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three women's room
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three outside office 2305
Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three office 2305 Pass Above ceiling/Ceiling
Zone 5/6 Heat Detector 2nd floor wing three office 2307 Pass Above ceiling/Ceiling
Zone 8 Smoke Detector 3rd floor wing three south stairwell
Pass
Zone 9/10 Heat Detector 3rd floor wing three South east office N9819
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three south east office Meghan
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three south west office
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three south west office
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three 1st column from entrance
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three by 4th column from entrance
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three by 5th column from entrance
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three by 7th column
Zone 9/10 Heat Detector 3rd floor wing three Defense travel office
No access
Zone 9/10 Heat Detector 3rd floor wing three office 3211 Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three outside men's room
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three men's room Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three women's room
Pass
Zone 9/10 Heat Detector 3rd floor wing three outside office 3306
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three conference room 3306
Pass Above ceiling/Ceiling
Zone 9/10 Heat Detector 3rd floor wing three office 3307 Pass Above ceiling/Ceiling
Zone 8 Smoke Detector 3 floor wing three stairwell Pass Zone 17 Heat Detector Penthouse Pass Zone 1 Pull Station 1st floor south wing three Pass
Zone 4 Pull Station 2nd floor south wing three Pass
Zone 7 Pull Station 3rd floor south wing 3 Pass
Zone 11 Waterflow Switch 1st floor north wing three Pass Tested via switch Zone 12 Waterflow Switch 1st floor south wing three Pass Tested via switch Zone 13 Waterflow Switch 2nd floor north wing three Pass Tested via switch
Zone 14 Waterflow Switch 2nd floor south wing three Pass Tested via switch Zone 16 Waterflow Switch 3rd floor north wing three Pass Tested via switch Zone 16 Waterflow Switch 3rd floor south wing three Pass Tested via switch
Zone 17 Waterflow Switch Wing 3 Penthouse Pass Tested via switch Wing 4 FACP 1st floor wing 4 FACP Pass (4) NAC circuits two 12Vdc 18Ah batteries safety switch electrical room 3
Zone 19 Heat Detector 1st floor south wing 4 Pass Zone 3 Heat Detector 1st floor wing four south west
HVAC room Pass
Zone 3/4 Heat Detector 1st floor wing four south east office
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor wing four south east office
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor wing four south west office
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor wing four outside conference room
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor wing four 4th column from entrance
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor wing four west of 4th column
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor 7th column from entrance
Zone 3 Heat Detector 1st floor wing four by elevator south exit
Pass
Zone 3/4 Heat Detector 1st floor wing four human resources
Pass Above ceiling/Ceiling
Zone 3/4 Heat Detector 1st floor wing four outside electrical room
Pass Above ceiling/Ceiling
Zone 3 Heat Detector 1st floor wing four electrical room 1316
No access
Zone 4 Heat Detector 1st floor wing four room 1401 Pass Three above ceiling Zone 2 Heat Detector 1st floor wing four room 1403 No access Three ceiling mounted three above ceiling Zone 3/4 Heat Detector 1st floor wing four outside room
Pass Above ceiling/Ceiling
Zone 6 Smoke Detector 3rd floor wing four south stairwell
Pass
Zone 6/7 Heat Detector 2nd floor wing four south west office
Pass Above ceiling/Ceiling
Zone 6/7 Heat Detector 2nd floor wing four south west office
Pass Above ceiling/Ceiling
Zone 6/7 Heat Detector 2nd floor wing four south east office
Pass
Zone 6/7 Heat Detector 2nd floor wing four by 2nd column from entrance
Pass
Zone 6/7 Heat Detector 2nd floor wing four 5th column from entrance
Pass Above ceiling/Ceiling
Zone 7 Heat Detector 2nd floor east wing four 6th column from south
Pass Above ceiling
Zone 7 Heat Detector 2nd floor wing four 5th column west
Pass Above ceiling
Zone 6/7 Heat Detector 2nd floor wing four 8th column from entrance
Pass Above ceiling/Ceiling
Zone 7 Heat Detector 2nd floor wing four west conference rm
Pass Above ceiling
Zone 7 Heat Detector 2nd floor east memorial conference rm
Pass Above ceiling
Zone 6/7 Heat Detector 2nd floor wing four hallway by 2400 doors
Pass Above ceiling/Ceiling
Zone 6/7 Heat Detector 2nd floor wing four room 2310 Pass Two above ceiling/two ceiling
Zone 6/7 Heat Detector 2nd floor wing four outside room
Pass Above ceiling/Ceiling
Zone 6/7 Heat Detector 2nd floor wing four room 2309 Pass Above ceiling/Ceiling
Zone 6/7 Heat Detector 2nd floor wing four room 2311 Pass Above ceiling/Ceiling
Zone 9 Smoke Detector 3rd floor north wing four stairwell
Pass
10/11 Heat Detector 3rd floor wing four south west office
Pass
Zone 10/11 Heat Detector 3rd floor wing four south east office
Zone 10/11 Heat Detector 3rd floor wing four 1st column from entrance
Pass Above ceiling/Ceiling
Zone 10/11 Heat Detector 3rd floor wing four 3rd column from entrance
Pass Above ceiling/Ceiling
Zone 10/11 Heat Detector 3rd floor wing four 6 th column from entrance
Pass Above ceiling/Ceiling
ZONE 10/11 Heat Detector 3rd floor wing four 8th column from entrance
Pass Above ceiling/Ceiling
Zone 10/11 Heat Detector 3rd floor wing four 8th column east
Pass Above ceiling/Ceiling
Zone 10/11 Heat Detector 3rd floor wing four outside room
Pass Above ceiling/Ceiling
Zone 10/11 Heat Detector 3rd floor wing four room 3309 Pass Above ceiling/Ceiling
Zone 10/11 Heat Detector 3rd floor wing four room 3401 Pass Six above ceiling/six ceiling Zone 10/11 Heat Detector 3rd floor wing four outside 3400 doors Pass Above ceiling/Ceiling
Zone 1 Pull Station 1st floor wing four south Pass
Zone 1 Pull Station 1st floor wing four south by elevator
Pass
Zone 5 Pull Station 2nd floor wing four south Pass
Zone 5 Pull Station 2nd floor wing four north Pass
Zone 8 Pull Station 3rd floor wing four south Pass
Zone 8 Pull Station 3rd floor wing four north Pass
Zone 21 Duct Detector 1st floor wing four AHU-1 Fail Not powered no signal Zone 20 Duct Detector 2nd floor wing four AHU-2 No access Zone 22 Duct Detector 3rd floor wing four AHU-3 Pass Tripped FACP/unit did not secure Zone 13 Waterflow Switch 1st floor north wing four Pass Tested via switch Zone 14 Waterflow Switch 1st floor south wing four Pass Tested via switch
Zone 15 Waterflow Switch 2nd floor north wing four Pass Tested via switch
Zone 16 Waterflow Switch 2nd floor south wing four Pass Tested via switch
Zone 17 Waterflow Switch 3rd floor north wing four Pass Tested via switch
Zone 18 Waterflow Switch 3rd floor south wing four Pass Tested via switch
Wing 5 FACP 1st floor wing five FACP Pass (3) NAC circuits two 12Vdc 18 Ah batteries safety switch ER 3
Zone 16 Heat Detector 1st floor wing five above FACP Pass Zone 4/5 Heat Detector 1st floor wing five outside SW office Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five SW office Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five opposite from SW office
Pass Above ceiling/Ceiling
Zone 5 Heat Detector 1st floor wing five SE offices Pass Two devices above ceiling Zone 5 Heat Detector 1st floor wing five by 1st column from entrance Pass Above ceiling
Zone 5 Heat Detector 1st floor wing five by 5th column from entrance
Pass Above ceiling
Zone 5 Heat Detector 1st floor wing five by 6th column from entrance
Pass Above ceiling
Zone 5 Heat Detector 1st floor wing five NE office 7th column
Pass Above ceiling
Zone 4/5 Heat Detector 1st floor wing five old engineers program tech library
Pass Above ceiling/ceiling devices missing
Zone 4/5 Heat Detector 1st floor wing five server room Pass above ceiling/ceiling
Zone 5 Heat Detector 1st floor wing five NE office 7th column
Pass Above ceiling
Zone 5 Heat Detector 1st floor wing five NE after column 7
Pass
Zone 4/5 Heat Detector 1st floor wing five hallway by rm
Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five room 1601 Pass
Zone 4/5 Heat Detector 1st floor wing five rm 1419 Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five room 1416 No access
Zone 4/5 Heat Detector 1st floor wing five room 1417 No access Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five payroll office No access
Zone 4/5 Heat Detector 1st floor wing five outside rm
Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five room 1415 Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five room 1412 Pass Tested via circuit
Zone 3 Heat Detector 1st floor wing five electrical room
Pass
Zone 4 Heat Detector 1st floor wing five steam pit room
Pass
Zone 4/5 Heat Detector 1st floor wing five women's room Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five room 1409 Pass
Zone 4/5 Heat Detector 1st floor wing five outside men's room
Pass Above ceiling/Ceiling
Zone 4/5 Heat Detector 1st floor wing five men's room Pass Above ceiling/ceiling also ceiling device above ceiling due to tile replaced
Zone 7/8 Heat Detector 2nd floor wing five NW office Raymond Chin
Pass One ceiling mounted one above ceiling
Zone 7/8 Heat Detector 2nd floor wing five NW office Elaine Smith
Pass Above ceiling/Ceiling
Zone 8 Heat Detector 2nd floor wing five NE offices Pass Two Above ceiling Zone 7/8 Heat Detector 2nd floor wing five 2nd column from entrance Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing four 4th column from entrance
Zone 7/8 Heat Detector 2nd floor wing five 9th column from entrance
Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing five room 2401 Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing five room 2411 Pass
Zone 7/8 Heat Detector 2nd floor wing five break room Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing five outside room
Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing five room 2408 Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing 5 room 2406 No access Zone 7/8 Heat Detector 2nd floor wing five room 2404 No access
Zone 7/8 Heat Detector 2nd floor wing five women's room 2407
Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing five room 2405 Pass Above ceiling/Ceiling Zone 7/8 Heat Detector 2nd floor wing five men's room
Pass Above ceiling/Ceiling
Zone 7/8 Heat Detector 2nd floor wing five room 2402 No access Tested via circuit
Zone 7/8 Heat Detector 2nd floor wing five outside men's room
Pass Above ceiling/Ceiling
Zone 10 Smoke Detector 3rd floor wing five stairwell Pass
Zone 11/12 Heat Detector 3rd floor wing five NW office Fail One ceiling mounted one above ceiling
Zone 12 Heat Detector 3rd floor wing five SE break room Fail Above ceiling
Zone 12 Heat Detector 3rd floor wing five SE office Fail Above ceiling
Zone 11/12 Heat Detector 3rd floor wing five 1st column from entrance
Fail Above ceiling/Ceiling
Zone 11/12 Heat Detector 3rd floor wing five 4th column from entrance
Fail Above ceiling/ceiling Above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five 7th column from entrance
Fail Above ceiling/ceiling Above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five 9th column from entrance
Fail Above ceiling/ceiling Above ceiling failed
Zone 10 Steam Detector 3rd floor north wing five stairwell Pass
Zone 11/12 Heat Detector 3rd floor wing five NE offices Fail Two ceiling mounted two above ceiling/above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five room 3413 Fail One ceiling mounted one above ceiling/above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five room 3410 Fail One ceiling mounted one above ceiling/above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five room 3411 Fail One ceiling mounted one above ceiling/above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five room 3408 Fail One ceiling mounted one above ceiling/above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five room 3406 Fail One ceiling mounted one above ceiling
Zone 11/12 Heat Detector 3rd floor wing five room 3404 Fail One ceiling mounted one above ceiling
Zone 11/12 Heat Detector 3rd floor wing five women's room
Fail One ceiling mounted one above ceiling
Zone 11/12 Heat Detector 3rd floor wing five room 3405 Not Tested
Zone 11/12 Heat Detector 3rd floor wing five men's room Fail One ceiling mounted one above ceiling above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five room 3402 Fail One ceiling mounted one above ceiling above ceiling failed
Zone 11/12 Heat Detector 3rd floor wing five outside room
Fail Ceiling device removed bracket thrown above ceiling
Zone 11/12 Heat Detector 3rd floor wing five outside men's room
Fail One ceiling mounted one above ceiling. Ceiling device removed
Zone 1 Pull Station 1st floor wing five outside south entrance
Pass
Zone 2 Pull Station 1st floor wing five south exit Pass
Zone 2 Pull Station 1st floor wing five north exit Pass
Zone 2 Pull Station 1st floor wing five south maintenance exit
Pass
Zone 6 Pull Station 2nd floor wing five south exit Pass
Zone 6 Pull Station 2nd floor wing five north exit Pass
Zone 6 Pull Station 2nd floor wing five south exit Pass
Zone 9 Pull Station 3rd floor wing five north exit Pass
Zone 9 Pull Station 3rd floor wing five south exit Pass
Zone 13 Waterflow Switch 1st floor wing five Pass Tested via switch
Zone 14 Waterflow Switch 2nd floor wing five Pass Tested via switch
Zone 15 Waterflow Switch 3rd floor wing five Pass
Wing 6 FACP 1st floor wing six FACP Pass (3) NAC circuits two 12Vdc 18Ah batteries safety switch electrical room
Zone 14 Heat Detector 1st floor wing six above FACP Pass
Zone 2 Heat Detector 1st floor wing six NW office Fail Removed from ceiling thrown above tiles
Zone 3 Heat Detector 1st floor wing six SW office Pass Above ceiling
Zone 2/3 Heat Detector 1st floor wing six 4 column from entrance
Pass Above ceiling/ceiling device missing
Zone 3 Heat Detector 1st floor wing six 3rd column from entrance
Pass Ceiling device missing
Zone 2/3 Heat Detector 1st floor wing six outside conference room
Pass Above ceiling
Zone 3 Heat Detector 1st floor wing six conference room
Pass Above ceiling
Zone 5/6 Heat Detector 2nd floor wing six conference room
Pass Above ceiling
Zone 5/6 Heat Detector 2nd floor wing six FA18 supply Pass Above ceiling
Zone 5/6 Heat Detector 2nd floor wing six west offices Pass Above ceiling Zone 5/6 Heat Detector 2nd floor wing six 1st column from entrance Pass Above ceiling/ceiling
Zone…