This document is Amendment 0004 to Solicitation N4008524R2518 for a Design-Bid-Build (DBB), Indefinite Delivery/Indefinite Quantity (IDIQ) Multiple Award Construction Contract (MACC) for General Construction Services at Marine Corps Air Station (MCAS) Beaufort, Marine Corps Recruit Depot (MCRD) Parris Island, and NAS Beaufort (Naval Hospital), South Carolina.

The amendment extends the proposal due date from May 20, 2024 to May 28, 2024, while keeping the Past Performance Information (PPI) cut-off date of May 6, 2024 unchanged. It provides responses to various PPI questions regarding corporate experience, project size requirements, and past performance evaluation criteria. The amendment also confirms that no hazardous materials abatement is required for the seed project and clarifies requirements for the site superintendent, Quality Control Manager (QCM), and Site Safety and Health Officer (SSHO) roles. Additionally, it provides supplemental site photos for the seed project to repair Building 1103.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

Design-Bid-Build (DBB), Indefinite Delivery/Indefinite Quantity (IDIQ) Multiple Aw ard Construction Contract (MACC) for General Construction Services at Marine Corps Air Station (MCAS) Beaufort, Marine Corps Recruit Depot (MCRD) Parris Island, and NAS Beaufort (Naval Hospital), South Carolina

The proposal due date of 20 May 2024 has been extended to 28 May 2024. The PPI cut-off date of 06 May 2024 remains unchanged.

See Continuation Page(s).

1. CONTRACT ID CODE PAGE OF PAGES

J 1 8

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 14-May-2024

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X N4008524R2518

X 9B. DATED (SEE ITEM 11)

04-Apr-2024

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

14-May-2024

CODE

NAVFACSYSCOM MID-ATLANTIC

CONTRACTING CORE

9324 VIRGINIA AVENUE

NORFOLK VA 23511-3095

N40085 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

N4008524R2518

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)

The following have been added by full text:

AMENDMENT 0004

This amendment is issued to incorporate the following:

1. Provide responses to PPIs.

2. Provide additional site photos.

3. Extend the proposal due date from 20 May 2024 to 28 May 2024. The PPI cut-off date of 06 May 2024 remains unchanged.

1. PPI Responses:

Date Submitted

LEAVE

BLANK

Reference Question Government Response

Page Section Paragraph

04/16/24 Jan-00 (1) Factor 1, Corporate Experience

1 Upon reviewing the solicitation, I noticed that it emphasizes the importance of proposers' experience in construction services. However, I also noted the stipulation that experience as a subcontractor, as well as that of any subcontractors, will not be considered. While my firm has not directly acted as a prime contractor for construction services in the past, we have established a strategic partnership with a reputable construction firm that possesses extensive experience in this field.

Together, we believe we can offer a comprehensive solution that meets the requirements outlined in the solicitation. Given this collaborative approach, I wanted to seek clarification on whether proposals from firms like ours, which plan to partner with experienced construction firms, would be considered acceptable under the evaluation criteria outlined in the solicitation. Additionally, I would appreciate any guidance on how such partnerships should be presented in our proposal to ensure they are appropriately evaluated.

As per the solicitation, "Offeror must have performed as prime contractor on all submitted projects; offeror’s experience performing as a subcontractor will not be considered." Please check with your SBA office on information regarding partnership agreements.

04/22/24 7 00 21 00 4 Normally there are two volumes - one for technical items and another for price information. We did not see the listing for separate volumes or how you want the two organized. Please provide some additional details on the organization (i.e. Tab A, Tab B, etc), which will make all offerors submit similar information.

As per the solicitation, "The Price and Non-cost/price Factors shall be submitted in separate files and submitted in Portable Document Format (PDF). Price information included in the non-price/technical proposal will not be considered.

Likewise, non-price/technical information included in the price proposal will not be considered."

04/22/24 9 00 21 00 4.2 Responsibility Determination Information - There are 4 items listed, which are to be a separate Tab, but not designated as Tab A or B, etc. Clarify which Tab this should be.

Bid per Solicitation instructions.

04/22/24 9 00 21 00 4.2 Responsibility Determination Information - Items #3 and 4: For #3 do you want a tabular listing such as descriptions, identification of item, etc.?

#4 - We assume a tabular form with contract number, amount, end date, etc. - please clarify items needed.

Bid per Solicitation instructions.

04/22/24 10 00 21 00 4.(1) Factor 1; Size - Some firms are D/B firms that also perform design. If we did a design on a $1M construction project, will that qualify under your size definition? As the designer, we were involved during the construction period.

The Size requirement is defined in the solicitation as the price paid for construction services. "Final construction cost is defined as the total price paid by the customer for the construction services, including original contract award amount and any modifications executed during performance."

04/22/24 10 00 21 00 4.(1)(i)(1) (1) Experience with at least one (1) New Construction Project…. And (2) At least one (1) relevant project….

Just to be clear you do not intend to have one new construction and one renovation project be $1,000,000 or greater. We ask, since both are relevant projects.

Also, under Notes, 3rd bullet has requirements for new and renovations, which reference the size standards.

At least one (1) relevant project submitted must have a final construction cost of $1,000,000 or greater.

04/22/24 11 00 21 00 4.2.(1)(i) The first full paragraph on page 11, states: "Ongoing projects will not be considered." In some cases a project is substantially complete, but is awaiting a minor item. Will you allow substantially complete projects?

We are not allowing substantially complete projects. Ongoing projects will not be considered.

04/22/24 11 00 21 00 4.2.(1)(i) In the 2nd full paragraph on page 11 references several items required in Attachment C. Please clarify if you want those items in Box 8, 9 or 10?

Bid per Solicitation instructions.

04/22/24 11 00 21 00 4.2.(1)(i) In the 4th full paragraph on page 11 references Attachment C and allows blocks on the form to be expanded.

Does this allow us to modify some of the other blocks that have a lot of white space, but will keep the form to two pages?

Bid per Solicitation instructions.

04/22/24 12 00 21 00 4.2.(1)(ii) If we submit five (5) projects, and you score four (4) projects as acceptable, but you feel one project does not meet the relevant criteria, will you disregard this project and look at the four other projects? Or does that one project not meeting the criteria score this criteria as unacceptable?

As per the solicitation, Offerors must submit a minimum of three (3) up to a maximum of five (5) relevant construction projects. Offerors that do not submit a minimum of three (3) relevant Construction Experience Projects will be rated

UNACCEPTABLE.

04/22/24 13 &

00 21 00 (3)(i) The requirement states: "The offeror shall include all completed CPARS (interim and final) for a project." The next sentence indicates a PPQ is required if there is not a completed CPARS. We interpret this to mean if there is an interim CPARS, then a PPQ is not needed. Please clarify if the interim CPARS requires a PPQ or not?

Interpretation is correct, if offeror provides an interim CPARS for a project then a PPQ is not needed.

04/22/24 14 00 21 00 (3)(i) 2nd full paragraph - Offerors are highly encouraged to provide any information on problems encountered and the corrective actions taken on projects submitted under Factor 1 - Corporate Experience. Additionally, offerors are highly encouraged to address any adverse past performance issues. Are we to interpret these as two separate issues? The first sentence relates only to the projects submitted in Factor 1, but does the 2nd sentence relate to any project except the Factor 1 projects?

Bid per Solicitation instructions. The second sentence relates to any projects, including projects submitted under Factor 1.

04/30/204 10 Construction Experience

1 Factor 1 – Corporate Experience, states in part, “Offeror must have performed as prime contractor on all submitted projects;…”. In many cases our company has performed “turnkey” projects of similar scope, size and complexity as demonstrated by the seed project. Will the Government reconsider its requirements for subcontractors experiencing on similar projects please?

As per the solicitation, Offeror must have performed as prime contractor on all submitted projects; offeror’s experience performing as a subcontractor will not be considered.

04/30/204 11 Construction Experience

1 States in part, “Projects submitted for the offeror shall have been completed within the past five (5) years of the date of issuance of this RFP. The impact of COVID-19 has staggered many small business ability to win and execute construction contracts.

Will the Government reconsider the past years on completed from five (5) years to seven (7) years please?

Projects submitted by the offeror shall have been completed within the past five (5) years.

04/30/204 1 Amendment 0001 to Repair Bldg

2 Demolish fuel day tank/pump/stand in generator room. See photo. Drain the tank of fuel, remove hoses cut pipes at floor level and grout pipe closed.

Dispose of debris off of Government property.

Description is correct.

04/30/204 1 Amendment 0001 to Repair Bldg

2 Seed Project SOW, is contractor responsible for fuel disposal, please provide estimated quantity of fuel remaining?

We believe the tank is empty but offerors should base bid on disposal of no more than 15 gallons of diesel fuel.

04/30/204 1 Amendment 0001 to Repair Bldg

2 Is the concrete pad where the generator now sits require to be demolished?

No, leave the pad.

04/30/204 1 Amendment 0001 to Repair Bldg

5 Seed Project SOW, has the soil surrounding the fuel tank been tested for contamination? If yes, please provide testing company information.

No, spread soil on site, do not remove.

04/30/204 22 Final Spec 01 30 00

1.3 and 1.4 01 30 00 (1.3 and 1.4) requires photos to be taken every week, during the site walk photos were not permitted. Will this activity be approved for the awardee?

Arrangements will be made for one person to take photos.

05/02/24 10 Factor 1, Corporate Experience

When an Offeror is submitting a proposal as a Joint Venture and if the Joint Venture has no completed past performance, each firm within the Joint Venture must include projects as part of the proposal. Please clarify the number of projects that each Joint Venture firm must include to support the total requirement of five.

As per the solicitation, "If the Joint Venture does not have shared experience, projects may be submitted for the Joint Venture members. Offerors are still limited to a total of five (5) projects combined."

05/02/24 10 Factor 1, Corporate Experience

If the Offeror is a joint venture and part of an approved SBA Mentor Protégé - will NAVFAC still require the each JV firm even though under a SBA mentor protégé to provide a minimum number of projects? If yes how many projects out of the five can the joint venture non 8a member firm also referred to as the SBA Mentor be allowed to submit? In some cases, other agencies have allowed the mentor to submit all five projects while the 8a protégé has not submitted any.

Offerors are still limited to a total of five (5) projects combined. Bid per Solicitation Instructions regarding 8(a) Mentor- Protégé requirements.

05/02/24 10 Factor 1, Corporate Experience

The solicitation specifies that a final construction cost of $500,000 or greater or $1,000,000 or greater is required for submission. RFP states normal Task Orders Projects for the MACC will have an estimated construction cost between $20,000.00 and $2,000,000.00; is there a maximum dollar limit for a project used for past performance, such as $5M, $6M etc - or should we keep them around the $2M amount?

There is no maximum dollar limit for a project submitted under Factor 1, Corporate Experience.

05/02/24 14 Factor 3, Past Performance

Can prior Past Performance Questionnaire (PPQ) forms completed within the last 12 months be used if it is the current USACE/NAVFAC format?

Bid per Solicitation instructions.

05/02/24 14 Factor 3, Past Performance

For adverse past performance issues it states we are limited to 4 pages. Is NAVFAC going to verify this information against final CPAR reports that have been filed?

As per the solicitation, sources of past performance information include Past performance information obtained from any other sources available to the Government, to include, but not limited to, Contractor Performance Assessment Reporting System (CPARS), Federal Awardee Performance and Integrity Information System (FAPIIS), Electronic Subcontract Reporting System (eSRS), or other databases; the Defense Contract Management Agency; and interviews with Program Managers, Contracting Officers, and Fee Determining Officials.

05/02/24 14 Factor 3, Past Performance

Is NAVFAC going to review CPARS for an offeror's prior completed projects that are not included in the proposal and outside the 5-year period?

As per the solicitation, sources of past performance information include Past performance information obtained from any other sources available to the Government, to include, but not limited to, Contractor Performance Assessment Reporting System (CPARS), Federal Awardee Performance and Integrity Information System (FAPIIS), Electronic Subcontract Reporting System (eSRS), or other databases; the Defense Contract Management Agency; and interviews with Program Managers, Contracting Officers, and Fee Determining Officials.

05/02/24 Final Specs

Seed project Can the site superintendent serve as the QCM and SSHO?

The site superintendent can serve as the SSHO but not the QCM.

05/03/24 13 of

3 i Please advise if Offerors can use/receive credit for previously completed PPQs for projects identified for Factor 3 if recent and relevant.

An offeror shall not submit a PPQ when a completed CPARS is available.

05/03/24 SF1442

, 7 of

4 2.a.1 The SF1442 states in Section 13.

Additional Solicitation Requirements, A. Sealed offers in original and 1 copies is required. Page 7 of 80 says the offeror shall submit one (1) electronic copy via PIEEE. This information is conflicting. Please advise if Offerors are to submit 1 original and 1 copy of the Price Volume, and 1 original and 1 copy of the Non-Price/Technical proposal.

As per the solicitation, Offerors shall submit one

(1) electronic copy of the solicitation submittal requirements via PIEE. The Price and Non-cost/price Factors shall be submitted in separate files and submitted in Portable Document Format (PDF).

05/06/24 S-301 02 41 00 3.1.3..2 Para. 3.1.3.2 section 02 41 00 of the project specifications directs the contractor to leave the existing roof in place. This direction is contradicted via detail 4 page S-301 of the contract drawings that indicates the existing roof is to remain in place. Please provide clarification in this matter

There is no mention of the existing roof in detail 4 on sheet S-301. Detail 3 on the sheet explicitly states the existing roof to remain.

05/06/24 01 32 17.00 1.8 The contractor is directed to maintain all project schedules using Primavera P6 software in a version compatible with the government’s current version.

Is Micro Soft Project an acceptable alternate to Primavera P6? If Microsoft Project is not an acceptable alternate please provide current version of P6 presently in use by the government.

Primavera P6 software is required.

05/06/24 Given the age of the building and the results of the Hazmat Report, please confirm that hazmat abatement is not a requirement for the seed project.

Correct, no hazardous materials to be removed in this project.

05/06/24 84 01 35 26 1.7.1.1.1 This specification section for the seed project affectively states that the QCM needs to be separate from both the SSHO and superintendent. Please confirm if this will be necessary, given the relatively small size of the seed project. Also, please indicate whether this would be standard practice on future projects for this MACC, or if this will be on a case-by-case basis.

Specification is correct, QCM should be separate from both the SSHO and superintendent.

05/06/24 AD901 During the site walk, we noticed a generator outside of the building that is not shown on AD901. Please confirm that there is no work associated with this additional generator included in the seed project scope of work.

Correct, no work associated with the generators outside the building.

05/06/24 10 Factor 1. 4 This section states that we need to demonstrate at least one new construction project or renovation of a building, followed by stating "Experience with at least one (1) New Construction Project and at least one

(1) Renovation Project (as defined above)". Please advise if we need one

Bid per Solicitation instructions.

of type of project or if we need one or the other.

05/06/24 X X X Would you please extend the due date of the proposal?

See Amendment 0004 for due date extension.

05/06/24 Location of cement stucco is unclear.

Please confirm that the entire exterior will need stucco application.

Yes, the entire exterior to be stucco finish.

2. See attachment posted for additional Site photos for the seed project Repair Building 1103 (“Building 1103 Doors.pdf”).

SECTION 00 10 00 - SOLICITATION

The required response date/time has changed from 20-May-2024 02:00 PM to 28-May-2024 02:00 PM.

(End of Summary of Changes)