N4008524B0015 Dwgs.pdf

PDF 4 MB Posted

Attached to
ATS Replacement at FC445, FC443, FC442
Solicitation number
N4008525R9011
Issued by

About this file

This document is a comprehensive set of engineering and architectural drawings for an Automatic Transfer Switch (ATS) Replacement project at Marine Corps Base Camp Lejeune, North Carolina. The project involves replacing existing 2000A automatic transfer switches at three buildings (FC445, FC443, and FC442) within the Wastewater Treatment Plant, with new 2000A, 3-phase, 4-pole, 480/277V closed transition automatic transfer switches that include bypass and isolation capabilities.

The detailed drawings cover multiple aspects of the project, including site utilities, electrical distribution, demolition plans, renovation plans, electrical transition stages, and specific electrical configurations for various buildings such as the Generator Building, Chemical Building, Admin/Control Building, and Primary Sludge Pump Station. The project requires carefully coordinated power outages, temporary backup generators for each critical system, and meticulous electrical reconnections to minimize disruption to the wastewater treatment facility's operations. The drawings provide specific technical details for electrical connections, conduit routing, and equipment placement, with a focus on maintaining continuous power to critical infrastructure during the upgrade process.

View the file

Other files

File Type Posted
Spec 33 32 16.pdf PDF
Amend 0004 240015.pdf PDF
Amend 0003 240015.pdf PDF
Amend 0002 240015.pdf PDF
Amend 0001 print.pdf PDF
N4008524B0015 Specs.pdf PDF
24-0015 SOW.pdf PDF
combined pricing sheet and RFP.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAP - CAMP LEJEUNE, N.C.

24-0015 ATS REPLACEMENT AT FC445, FC443 AND FC442 (WASTEWATER TREATMENT PLANT)

MCB CAMP LEJEUNE, NORTH CAROLINA

NORTHEAST CREEK

A T L A N T I

C O

C E A N

N E W R I V E R

NEW RIVER

AIR STATION

LANDFILL

PWD/ROICC

OFFICE

BLDG 1005

DRMO

SFC450

SFC449

SFC453

SFC454

SFC456

SFC455

SFC460

SFC438

SFC448

SFC468

SFC451

SFC465

FC444

SFC463

SFC466

FC447

FC364

SFC359

FC400

FC371

FC359

FC416

FC412

FC415

FC414

FC420

FC365

FC306

FC360

FC364

FC370

FC443

FC442

FC445

FC467

CTR139

FC436

FC441

SFC366

GREENWAY TRAIL

SITE MAP - N.T.S.

CONST. CONTR. NO.

FINAL T1

D POKHREL

D. POKHREL

J. SIDES, P.E

D. POKHREL

J. REED, P.E

PWO

ATS REPLACEMENT AT

FC445, FC443, FC442

LOCATION MAPS AND DRAWING INDEX

60041960 24-0015

NOTED NA 1 32

PROJECT LOCATION

WASTEWATER TREATMENT PLANT FC445

FC442

FC443

GONZALEZ BLVD

GO

NZ

AL

EZ

B

LV

D

GONZALEZ BLVD

CONNER ST

J.C SMITH BLVD

ANDERSON ST

INDEX OF DRAWINGS

GENERAL

SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION

T1 1 LOCATION, MAPS AND DRAWING INDEX

C1 2 EXISTING SITE UTILITIES

C1.1 3 EXISTING SITE LAYOUT

E101 4 ELECTRICAL GENERAL NOTES AND LEGEND

E201 5 SITE ELECTRICAL DISTRIBUTION

E301 6 EXISTING ONE LINE DIAGRAM

E401 7 EXISTING UNIT SUBSTATION

E501 8 ELECTRICAL DETAILS

INDEX OF DRAWINGS

BASE BID - BUILDING FC445

SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION

A1 9 GENERATOR BUILDING FC445 DEMOLITION PLAN

A1.1 10 GENERATOR BUILDING FC445 RENOVATION PLAN

E1 11 ADMIN/CONTROL BUILDING FC436 ELECTRICAL PLAN

E1.1 12 PRIMARY SLUDGE PUMP STATION FC436 AND MAINTENANCE BLDG. FC441 ELECTRICAL PLAN

E1.2 13 UV DISINFECTION SYSTEM BLDG. FC447 ELECTRICAL PLAN

E1.3 14 GENERATOR BUILDING FC445 ELECTRICAL PLAN

E1.4 15 FC445 ELECTRICAL TRANSITION PLAN STAGE 1

E1.5 16 FC445 ELECTRICAL TRANSITION PLAN STAGE 2

E1.6 17 FC445 ELECTRICAL TRANSITION PLAN STAGE 3

INDEX OF DRAWINGS

BID OPTION 1 - BUILDING FC443

SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION

A2 18 GENERATOR BUILDING FC443 DEMOLITION PLAN

A2.1 19 GENERATOR BUILDING FC443 RENOVATION PLAN

E2 20 MOTOR CONTROL CENTER 2MCC11 AND ATAD BLDG. FC446 ELECTRICAL PLAN

E2.1 21 GENERATOR BUILDING FC443 ELECTRICAL PLAN

E2.2 22 FC443 ELECTRICAL TRANSITION PLAN STAGE 1

E2.3 23 FC443 ELECTRICAL TRANSITION PLAN STAGE 2

E2.4 24 FC443 ELECTRICAL TRANSITION PLAN STAGE 3

INDEX OF DRAWINGS

BID OPTION 2 - BUILDING FC442

SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION

A3 25 GENERATOR BUILDING FC442 DEMOLITION PLAN

A3.1 26 GENERATOR BUILDING FC442 RENOVATION PLAN

E3 27 BYPASS PUMP PLAN

E3.1 28 CHEMICAL BUILDING FC444 ELECTRICAL NEW WORK

E3.2 29 GENERATOR BUILDING FC442 ELECTRICAL PLAN

E3.3 30 FC442 ELECTRICAL TRANSITION PLAN STAGE 1

E3.4 31 FC442 ELECTRICAL TRANSITION PLAN STAGE 2

E3.5 32 FC442 ELECTRICAL TRANSITION PLAN STAGE 3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LEJEUNE BLVD

AutoCAD SHX Text

TO WILMINGTON

AutoCAD SHX Text

VERONA LOOP ROAD

AutoCAD SHX Text

NEW RIVER INLET RD

AutoCAD SHX Text

RANGE RD

AutoCAD SHX Text

DIXON-SNEADS FERRY RD

AutoCAD SHX Text

OCEAN DRIVE

AutoCAD SHX Text

BEACH RD

AutoCAD SHX Text

MARINES RD

AutoCAD SHX Text

LYMAN RD

AutoCAD SHX Text

WALLACE CREEK RD

AutoCAD SHX Text

PINEY GREEN RD

AutoCAD SHX Text

HOLCOMB BLVD

AutoCAD SHX Text

BREWSTER BLVD

AutoCAD SHX Text

CURTIS

AutoCAD SHX Text

STONE ST

AutoCAD SHX Text

STONE BAY

AutoCAD SHX Text

FRENCH

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

MAIN SERVICE RD

AutoCAD SHX Text

INTRACOASTAL WATERWAY

AutoCAD SHX Text %%uSNEADS FERRY

AutoCAD SHX Text

MEANS HIGH WATER +1.10

AutoCAD SHX Text

MEANS SEA LEVEL 0.00

AutoCAD SHX Text

MEANS LOW WATER +0.35

AutoCAD SHX Text

LEJEUNE RAILROAD

AutoCAD SHX Text

CAMP

AutoCAD SHX Text

SEABOARD COAST LINE RAILROAD

AutoCAD SHX Text

SNEADS FERRY RD

AutoCAD SHX Text

SETH

AutoCAD SHX Text

WALLACE

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

SOUTHWEST CREEK

AutoCAD SHX Text

WILSON

AutoCAD SHX Text

BAY

AutoCAD SHX Text

TRAPS

AutoCAD SHX Text

BAY

AutoCAD SHX Text

CHADWICK

AutoCAD SHX Text

BAY

AutoCAD SHX Text

HOWARD BAY

AutoCAD SHX Text

COURTHOUSE

AutoCAD SHX Text

BAY

AutoCAD SHX Text

ELLIS

AutoCAD SHX Text

COVE

AutoCAD SHX Text

TO

AutoCAD SHX Text

MOREHEAD CITY

AutoCAD SHX Text

BEAR

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

BEAR

AutoCAD SHX Text

INLET

AutoCAD SHX Text

STONE

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

MILL

AutoCAD SHX Text

STONE CREEK

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

MUDDY

AutoCAD SHX Text

MILL CREEK

AutoCAD SHX Text

TOWN

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

WHITE

AutoCAD SHX Text

HURST

AutoCAD SHX Text

CR.

AutoCAD SHX Text

SNEADS

AutoCAD SHX Text

FERRY

AutoCAD SHX Text

ROAD

AutoCAD SHX Text

TARAWA

AutoCAD SHX Text

TERRACE

AutoCAD SHX Text

KNOX

AutoCAD SHX Text

TR. PARK

AutoCAD SHX Text

MONTFORD

AutoCAD SHX Text

LANDING RD

AutoCAD SHX Text

MIDWAY

AutoCAD SHX Text

PARK

AutoCAD SHX Text

NAVAL

AutoCAD SHX Text

HOSPITAL

AutoCAD SHX Text

FRENCH

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

AREA

AutoCAD SHX Text

MAGAZINE

AutoCAD SHX Text

AREA

AutoCAD SHX Text

HADNOT

AutoCAD SHX Text

POINT

AutoCAD SHX Text

AREA

AutoCAD SHX Text

INDUSTRIAL

AutoCAD SHX Text

AREA

AutoCAD SHX Text

PARADISE

AutoCAD SHX Text

POINT

AutoCAD SHX Text

AREA

AutoCAD SHX Text

RIFLE

AutoCAD SHX Text

RANGE

AutoCAD SHX Text

AMPHIBIAN

AutoCAD SHX Text

BASE

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

AREA

AutoCAD SHX Text

TRIANGLE

AutoCAD SHX Text

OUTPOST

AutoCAD SHX Text

BEACH

AutoCAD SHX Text

AREA

AutoCAD SHX Text

BERKELEY

AutoCAD SHX Text

MANOR

AutoCAD SHX Text

WATKINS

AutoCAD SHX Text

VILLAGE

AutoCAD SHX Text

CAMP

AutoCAD SHX Text

GEIGER

AutoCAD SHX Text

CAMP

AutoCAD SHX Text

GEIGER

AutoCAD SHX Text

BROWNS

AutoCAD SHX Text

INLET

AutoCAD SHX Text

EVERETT CREEK

AutoCAD SHX Text

WILLI

AutoCAD SHX Text

AMS

AutoCAD SHX Text

BLVD

AutoCAD SHX Text

GOLF

AutoCAD SHX Text

COURSE

AutoCAD SHX Text

SWAMP

AutoCAD SHX Text

BELL

AutoCAD SHX Text

CREEK

AutoCAD SHX Text

FREEMAN

AutoCAD SHX Text

ROAD

AutoCAD SHX Text

BRINSON CREEK

AutoCAD SHX Text

HOPE ROAD

AutoCAD SHX Text

RIVER

AutoCAD SHX Text

ROAD

AutoCAD SHX Text

DUCK CREEK

AutoCAD SHX Text

HOLCOMB

AutoCAD SHX Text

GATE

AutoCAD SHX Text

MONTFORD

AutoCAD SHX Text

POINT

AutoCAD SHX Text

AREA

AutoCAD SHX Text

PAVILION

AutoCAD SHX Text

MARINA

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

OWL

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

LHA

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

ORIOLE

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

SANDPIPER

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

EGRET

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

CANARY

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

DOVE

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

PLOVER

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

HERON

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

DODO

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

GOOSE

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

FALCON

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

OSPREY

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

QUAIL

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

ALBATROSS

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

BLUEBIRD

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

JAYBIRD

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

CRANE

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

GULL

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

PENGUIN

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

LARK

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

PIGEON

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

TERN

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

COOT

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

SWAN

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

WOODPECKER

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

ROBIN

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

SPARROW

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

MALLARD

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

KIWI

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

CONDOR

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text Z

AutoCAD SHX Text

CARDINAL

AutoCAD SHX Text

FRENCH CREEK BORROW PIT

AutoCAD SHX Text

SNEADS FERRY RD

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC#

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

OF

SFC450

SFC449

SFC453

SFC454

SFC456

SFC455

SFC460

SFC438

SFC448

SFC468

SFC451

SFC465

FC444

SFC463

SFC466

FC443

FC442

FC445

FC467

FC436

FC441

6'' 8''

4''

6''

8''

8''

3'

4''

8''

8''

8''

6''

6''

6''

6''

PB8

PB9

PB6

PB5

PB2

PB4

PB3

PB1

PB11

PB10

PB67

PB441

PB436

G G

G

FC2

FC2

FC

FC2

FC

FC

FC

FC2

FC2

FC

FC

FC

FC2

FC

FC2

FC

FC2

FC

FC2

FC2

FC2

FC

FC

FC

FC2

FC2

FC

FC

FC

FC

FC2

FC2

FC

FC

FC

FC2

FC2

FC

FC2

FC

FC2

FC2

FC2

FC2

FC2

FC

FC

FC

FC2 FC2

FC

FC2

FC2 24

18''

15''

18''

15''

18''

24'' 15''

18''

15'' 18''

15''

15''

15''

15''

18''

24'' 24''

15''

15''

12''

18''

24''

15''

15''

18''

15''

4''

4''

4'' 4''4''

4''

4''

8''

8''

8''

FC03

FC04

FC01FC02

TRAFFIC RATED HANDHOLE

ELECTRICAL SWITCH POINT, FUSE CUTOUT

ELECTRICAL RISER POINT

EXISTING UTILITY POLE

EXTERIOR LIGHTING

EXISTING MANHOLE

COMMUNICATION MANHOLE

COMMUNICATION RISER POINT

CIRCUIT BREAKER

EX. UNDERGROUND ELECTRICAL CABLE IN DUCTBANK

EX. PRIMARY ELECTRIC CABLE, OVERHEAD

WASTEWATER CLEANOUT POINT

WASTE WATER MANHOLE

COMMUNICATION SPEAKER

MANHOLE, STORM WATER

VALVE, WASTEWATER

FIRE HYDRANT

WATER VALVE

WASTE WATER, GRAVITY MAIN

WATER LINE, POTABLE

STORM WATER PIPE

WASTE WATER, LATERAL

COMMUNICATION LINE

FENSE

EXISTING PAD MOUNTED SWITCHGEAR

ROAD CENTERLINE

CONST. CONTR. NO.

FINAL C1

D. POKHREL

D. POKHREL

J. SIDES, P.E

D. POKHREL

J. REED, P.E

PWO

PWO

ATS REPLACEMENT AT

FC445, FC443 AND FC442

EXISTING SITE UTILITIES

60041961 24-0015

NOTED NA 2 32

EXISTING SITE UTILITIES

NOT TO SCALE

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text

SS

AutoCAD SHX Text

SS

AutoCAD SHX Text

SS

AutoCAD SHX Text

SS

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text

SS

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC#

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

CONST. CONTR. NO.

FINAL C1.1

D. POKHREL

D. POKHREL

J. SIDES, P.E

D. POKHREL

J. REED, P.E

PWO

ATS REPLACEMENT AT

FC445, FC443 AND FC442

EXISTING SITE LAYOUT

60041962 24-0015

NOTED NA 3 32

EXISTING SITE LAYOUT

NO SCALE

AutoCAD SHX Text

A20 BNR SYSTEM

AutoCAD SHX Text

INTERMEDIATE LIFT STATION/

AutoCAD SHX Text

SAND FILTER

AutoCAD SHX Text

ATAD OR ATP

AutoCAD SHX Text

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text

CLARIFIER

AutoCAD SHX Text #1

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text

CLARIFIER

AutoCAD SHX Text #2

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text

CLARIFIER

AutoCAD SHX Text #3

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text

CLARIFIER

AutoCAD SHX Text #4

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

BUILDING FC442

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

BUILDING FC443

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

BUILDING FC445

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text

PRIMARY CLARIFIER

AutoCAD SHX Text

BARDENPHO BNR SYSTEM

AutoCAD SHX Text

ADMIN BLDG

AutoCAD SHX Text

TRUCK LOADING STATION

AutoCAD SHX Text

POST AERATION

AutoCAD SHX Text

UV DISINFECTION

AutoCAD SHX Text

CHEMICAL BLDG.

AutoCAD SHX Text

GRIT REMOVAL SYSTEM

AutoCAD SHX Text

PRIMARY SLUDGE

AutoCAD SHX Text

PUMP STATION

AutoCAD SHX Text

MAINTENANCE

AutoCAD SHX Text

BLDG.

AutoCAD SHX Text

ARCHIMEDES' SCREW PUMPS

AutoCAD SHX Text

FLOW MEASUREMENT

AutoCAD SHX Text

STRUCTURE

AutoCAD SHX Text

FC447

AutoCAD SHX Text

FC440

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC#

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

ELECTRICAL GENERAL NOTESELECTRICAL LEGEND

SYMBOL DESCRIPTION

1. ALL ELECTRICAL WORK MUST BE IN FULL COMPLIANCE WITH NFPA 70, UFCs, ALL

LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS

OF THE LOCAL AUTHORITY HAVING JURISDICTION.

2. CONTRACTOR MUST FIELD VERIFY ALL EXISTING UTILITY CONDITIONS AND

PERFORM UTILITY LOCATES PRIOR TO BEGINNING ANY WORK. DRAWINGS ARE A

FUNCTIONAL REPRESENTATION OF RELEVANT SCOPE SPECIFIC CONDITIONS AND

INTENDED FOR GENERAL INFORMATION USE ONLY. ALL UTILITIES IN THE AREA

ARE *NOT* INDICATED ON THE DRAWINGS. DO NOT USE DIGGERS OR TRENCHES

UNTIL A THOROUGH REVIEW OF SITE CONDITIONS AND UTILITY LOCATES ARE

PERFORMED. DO NOT CUT THROUGH ANY EXISTING UTILITIES. FIELD VERIFY ALL

ELECTRICAL CHARACTERISTICS AND SYSTEM VOLTAGES BEFORE ORDERING

MATERIALS OR BEGINNING WORK.

3. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR MUST BE LISTED AND LABELED

BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE

AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL

MATERIAL, EQUIPMENT AND DEVICES MUST BE NEW CURRENT PRODUCTS OF

MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH

PRODUCTS. EQUIPMENT MUST BE SUITABLE FOR ITS APPLICATION (E.G. WHEN

INSTALLED OUTDOORS, IT MUST BE WEATHERPROOF, ETC.)

4. THE CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR

WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL

EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND FUNCTIONAL MANNER.

5. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED

BY THE CONTRACTOR MUST BE COMPLETE AND FULLY-FUNCTIONING AFTER

INSTALLATION.

6. TEMPORARY POWER CONNECTIONS AS REQUIRED MUST BE PROVIDED BY THE

CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING

MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE

CONTRACTOR MUST PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW

PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL

EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR

STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS,

TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE UTILITY

PROVIDER AS REQUIRED.

7. THE WORK MUST INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING

AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR

ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND

EQUIPMENT.

8. ALL ELECTRICAL EQUIPMENT MUST, AT ALL TIMES DURING CONSTRUCTION, BE

ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER

AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT MUST NOT BE STORED OUT OF

DOORS, BUT MUST BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS

HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR

THE ELEMENTS, SUCH DAMAGE MUST BE REPLACED AT NO ADDITIONAL COST.

9. DO NOT SCALE ELECTRICAL DRAWINGS. CONTRACTOR MUST FIELD VERIFY ALL

DIMENSIONS.

10. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR

OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT

ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE

RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT

ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE

CONTRACTOR MUST ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE

INSTALLATION.

11. DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST

EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO

AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. IF NOT SHOWN ON

THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL

DRAWINGS, VERIFY EXACT LOCATION WITH THE GOVERNMENT PRIOR TO

ROUGH-IN.

12. CONDUIT TERMINATING IN PRESSED STEEL BOXES MUST BE RIGID. CONDUITS

TERMINATING IN GASKETED ENCLOSURES MUST BE TERMINATED WITH

GROUNDING TYPE CONDUIT HUBS.

13. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE

CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED.

ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL MUST BE INCLUDED EVEN IF

NOT EXPLICITLY SHOWN.

14. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS AND ROOF

WATERTIGHT.

15. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES MUST BE

WEATHER-RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER.

16. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS MUST BE PROPERLY

SEALED SMOKETIGHT.

17. ALL RACEWAYS MUST BE CONCEALED WHERE POSSIBLE.

18. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY

SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS

AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS

MUST BE RUN STRAIGHT WITH QUALITY WORKMANSHIP-LIKE MANNER. RUN

PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE

PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME

CENTERLINE TO MAKE BENDS PARALLEL.

19. PATCHING OF WATERPROOFED SURFACES MUST RENDER THE AREA OF THE

PATCHING COMPLETELY WATERPROOF.

20. ALL MOTORS AND OTHER VIBRATING EQUIPMENT MUST BE CONNECTED TO THE

CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF

FLEXIBLE CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING

CONDUCTOR MUST BE INSTALLED INSIDE THE FLEXIBLE CONDUIT AND TERMINATE

AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.

21. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES,

RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR

WALLS MUST BE SUPPORTED BY SPACERS TO PROVIDE A MINIMUM 1/4" MINIMUM

CLEARANCE BETWEEN THE WALL AND EQUIPMENT.

22. TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR

POCKET MUST REFLECT FINAL CONDITIONS AND ACTUAL ROOM NAMES AND

NUMBERS IN ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL

SCHEDULES ON THE DRAWINGS.

23. THE CONTRACTOR MUST VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR

CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR

USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH

LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR MUST NOTIFY THE

GOVERNMENT IMMEDIATELY FOR EVALUATION/CORRECTION.

24. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY

DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL

ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED.

25. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS MUST

CONSIST OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT

GROUND CONDUCTORS IN 3/4” MINIMUM RACEWAY.

26. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A

TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT

HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR

RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE

HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. IF 277 VOLT CIRCUITS ARE

SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH

CIRCUITS WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR

BRANCH CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED

TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH

(INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.

27. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT

POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION

RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP

CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS

AT EACH OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND

COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY

THE MANUFACTURER.

28. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE

GOVERNMENT. HOMERUNS MUST BE CONTINUOUS FROM THE LAST OUTLET BOX

TO THE SERVING PANELBOARD.

29. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED

ON THE DRAWINGS.

30. DO NOT CHANGE CIRCUITING SHOWN WITHOUT PERMISSION OF THE

GOVERNMENT.

31. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS.

32. PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE SAFETY SYSTEMS,

FIRE ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION

THROUGHOUT THE PROGRESS OF THE WORK. NOTIFY THE GOVERNMENT IF

SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE

DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE

GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN

SERVICE.

33. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL

IN ACCORDANCE WITH THE NEC INCLUDING EXTERIOR RECEPTACLES AND

RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS.

34. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE RESPECTIVE

CONTRACTOR, VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST

LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO

ACCOMMODATE THIS EQUIPMENT. ADVISE THE GOVERNMENT OF CONFLICTS

BEFORE ROUGH-IN.

35. ALL EXTERIOR ENCLOSURE MUST BE NEMA 4X STAINLESS STEEL.

36. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE

CONTRACTOR PROVIDING THE EQUIPMENT.

37. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR MUST MAKE FINAL

CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS.

VERIFY THE TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING

METHOD. THE CONTRACTOR MUST COORDINATE WITH THE MECHANICAL TRADE,

PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY

MECHANICAL EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE ELECTRICAL

DESIGN.

38. THE CONTRACTOR MUST COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS

AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS

FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.

39. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT MUST BE

RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.

40. THE CONTRACTOR MUST VISIT THE SITE AND BECOME FAMILIAR WITH THE

EXISTING ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION

OF THE PROPOSAL BY THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT

HE OR HIS REPRESENTATIVE HAS VISITED THE SITE AND BUILDINGS AND NOTED

THE LOCATION AND CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED

AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS GOVERNING HIS

WORK.

41. SAFETY

A. COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.

B. FOR EQUIPMENT BEING REMOVED AND REPLACED, THE CONTRACTOR SHALL

DE-ENERGIZE THE EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL AND

COMPLY WITH OSHA REQUIREMENTS FOR LOCKING-OUT AND TAGGING

EQUIPMENT TO PREVENT INADVERTENT RE-ENERGIZING.

ABBREVIATIONS

PERMANENT GENERATOR ON A CONCRETE PAD

TEMPORARY BACKUP GENERATOR, CONTRACTOR PROVIDED

TRAFFIC RATED HANDHOLE

ELECTRICAL SWITCH POINT, FUSE CUTOUT

ELECTRICAL RISER POINT

EXISTING UTILITY POLE

EXTERIOR LIGHTING

"EQUIPMENT NAME"

SOURCE: PANEL "###"

SOURCE LOCATION "###"

RATING: ### AMPS

VOLTAGE: 208/120V, 3Ø, 4WRATING DESIGNATION 1/4" WHITE

ENGRAVED LETTERS

SOURCE DESIGNATION 1/4" WHITE

ENGRAVED LETTERS

EQUIPMENT DESIGNATION 3/8" WHITE

ENGRAVED LETTERS

VOLTAGE & PHASE DESIGNATION 1/4" WHITE

ENGRAVED LETTERS

Arc Flash and Shock Hazard Appropriate PPE required

NOTES:

1. LABEL SHOWN CAN BE SOURCED FROM SAFETYSIGN.COM, OTHER SUPPLIERS ARE

COMPLIANTSIGNS.COM & SETON.COM

2. THIS WARNING LABEL MINIMALLY COMPLIES WITH NEC, HOWEVER IF ELECTRICAL

EQUIPMENT IS LIKELY TO REQUIRE EXAMINATION OR MAINTENANCE WHILE

ENERGIZED A DETAILED SHORT CIRCUIT AND ARC FLASH HAZARD ANALYSIS IS

RECOMMENDED.

BLACK LETTERS ON WHITE

BACKGROUND

NOT TO SCALE1 ELECTRICAL EQUIPMENT WARNING LABEL DETAIL

BLACK LETTERS AND SYMBOL ON

SAFETY ORANGE BACKGROUND

MACHINE SCREW WITH ACORN NUT AND

LOCKWASHER, TYP.

SOURCE LOCATION DESIGNATION 1/4"

WHITE ENGRAVED LETTERS

NOTE: SEE SPECS. SECTION 260553 FOR NAMEPLATE MATERIAL

AND ENGRAVING COLORS.

NOT TO SCALE3 TYPICAL EQUIPMENT NAMEPLATE DETAIL

WARNING

4 1/2" MINIMUM

7/

8" M

IN

IM

U M

3/

4"

EXISTING MANHOLE

AUTOMATIC TRANSFER SWITCH, 3 PHASE

TRANSFORMER

COMMUNICATION MANHOLE

COMMUNICATION RISER POINT

CIRCUIT BREAKER

EX. UNDERGROUND ELECTRICAL CABLE IN DUCTBANK

NEW UNDERGROUND ELECTRICAL CABLE

EX. PRIMARY ELECTRIC CABLE, OVERHEAD

WASTEWATER CLEANOUT POINT

WASTE WATER MANHOLE

COMMUNICATION SPEAKER

MANHOLE, STORM WATER

VALVE, WASTEWATER

FIRE HYDRANT

WATER VALVE

WASTE WATER, GRAVITY MAIN

WATER LINE, POTABLE

STORM WATER PIPE

WASTE WATER, LATERAL

COMMUNICATION LINE

FENSE

D.S

CB

AS

MH

EX

PMT

KVA

MDP

ATS

KWH

KW

CND

GND

CU

DISCONNECT SWITCH

CIRCUIT BREAKER

AIR STATION, NEW RIVER

MAN HOLE

EXISTING

PAD MOUNTED TRANSFORMER

KILO-VOLT-AMPERE

MAIN DISTRIBUTION PANEL

AUTOMATIC TRANSFER SWITCH

KILO WATT HOUR

ELECTRICAL PHASE

KILO WATT

CONDUIT

GROUND WIRE

COPPER

ɸ

SD SERVICE DISCONNECT

CONCRETE PAD

HH HAND HOLE

CONST. CONTR. NO.

FINAL E101

D. POKHREL

D. POKHREL

J. SIDES, PE

D. POKHREL

J. REED, PE

PWO

ATS REPLACEMENT AT

FC445, FC443, FC442

ELECTRICAL LEGEND, ABBREVIATIONS& GENERAL NOTES

60041963 24-0015

NOTED 4 32

T

G

ELECTRICAL PANEL

EXISTING PAD MOUNTED SWITCHGEAR

ROAD CENTERLINE

SCOPE OF WORK

THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, EQUIPMENT, AND SUPERVISION REQUIRED TO ACCOMPLISH THE

FOLLOWING.

GENERAL DESCRIPTION: THE SCOPE OF WORK IS TO BE ACCOMPLISHED AT WASTEWATER TREATMENT PLANT ON GONZALEZ BLVD., CAMP LEJEUNE, NC. THE CONTRACTOR SHALL PROVIDE MATERIAL, EQUIPMENT AND LABOR TO REPLACE THREE EXISTING 2000A AUTOMATIC TRANSFER SWITCHES AT BUILDINGS FC445, FC443 AND FC442 WITH NEW 2000A, 3ɸ, 4POLE, 480/277V CLOSED TRANSITION AUTOMATIC TRANSFER SWITCHES WITH BY-PASS / ISOLATION. THE SCOPE ALSO INCLUDES TO DEMOLISH THE WALLS OF THE BUILDINGS TO GET THE SWITCHES IN AND OUT OF THE BUILDINGS AND INSTALL ROLL-UP DOORS. SEE ARCHITECTURAL SHEETS FOR

THE DESIGN OF ROLL UP DOORS.

PLAN NOTES:

1. THE OBJECTIVE IS TO REPLACE THE AUTOMATIC TRANSFER SWITCHES AT WASTEWATER TREATMENT PLANT (BLDG FC445, FC443, FC442) WITH MINIMUM POWER OUTAGE AS IT IS A CRITICAL FACILITY. TWO OF THE SYSTEMS AT THE PLANT, UV DISINFECTION SYSTEM AND SCREW PUMP SYSTEM SHALL HAVE ZERO POWER OUTAGE. COORDINATE WITH PATRICK MULLALLY AT

PATRICK.MULLALLY@USMC.MIL OR 910-526-9570 FOR POWER OUTAGES.

2. IDEAL POWER OUTAGE TIME IS EARLY IN THE MORNING DURING LOW FLOW HOURS OF 0400-0600 EST.

3. PROVIDE TEMPORARY EMERGENCY BACKUP POWER TO THE SYSTEMS ALONG WITH AUTOMATIC TRANSFER SWITCHES BEFORE

SHUTTING DOWN POWER TO THE SYSTEM TO REPLACE 2000A ATS.

4. EXISTING 750KW GENERATOR SHALL NOT BE USED BECAUSE OF AIR QUALITY PERMITTING ISSUES. CONTRACTOR WILL PROVIDE A

750kW TEMPORARY DIESEL ENGINE GENERATOR.

4. CONTRACTOR IS RESPONSIBLE TO PROVIDE AND REMOVE TEMPORARILY PROVIDED EMERGENCY GENERATORS FROM THE SITE

AFTER THE CONSTRUCTION IS COMPLETE. ONLY THE 60KW GENERATOR WILL STAY ON SITE PERMANENTLY. ALL NEW ATSs TO

REMAIN ON SITE PERMANENTLY.

5. THE LOCATIONS OF NEW EQUIPMENT ARE APPROXIMATE. COORDINATE WITH PATRICK MULLALLY AT PATRICK.MULLALLY@USMC.MIL OR 910-526-9570 FOR EXACT LOCATIONS BEFORE INSTALLATION. AVOID INSTALLATION IN LOW-LYING AREAS PRONE TO WATER ACCUMULATION. AVOID EXISTING UNDERGROUND UTILITIES.

6. CONTRACTOR IS RESPONSIBLE FOR THE OPERATION OF TEMPORARY GENERATORS THROUGHOUT THE DURATION OF CONSTRUCTION.

7. IF POSSIBLE, AVOID SOUTH-FACING AUTOMATIC TRANSFER SWITCH INSTALLATION - PROTECT DISPLAY FROM DIRECT SUNLIGHT.

AutoCAD SHX Text

SYM.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text E

AutoCAD SHX Text

ATS

AutoCAD SHX Text C

AutoCAD SHX Text

SS

AutoCAD SHX Text D

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC#

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

OF

AutoCAD SHX Text

NUE

AutoCAD SHX Text

NUE

AutoCAD SHX Text

NUE

E

T

FINAL E201

D POKHREL

D. POKHREL

J.SIDES, P.E

D. POKHREL

J. REED, P.E

PWO

PWO

ATS REPLACEMENT AT

FC445, FC443 AND FC442

EXISTING ELECTRICAL DISTRIBUTION

60041964 24-0015

NOTED NA 5 32

1M

CC

(X) HANDHOLE

(X) UNIT SUBSTATION #1

(X) BLDG FC 445

SECONDARY

CLARIFIER #3

SECONDARY

CLARIFIER #4

SECONDARY

CLARIFIER #2

SECONDARY

CLARIFIER #1

EXISITNG ELECTRICAL DISTRIBUTION

NOT TO SCALE

ADMIN/

CONTROL

BLDG.

(X) MANHOLE #2

(X) MANHOLE #1

(X) MANHOLE #3

(X) MANHOLE #4

SAND FILTER

PO

ST

A

ER

AT

IO

N

SLUDGE

HOLDING TANK

(X) HANDHOLE

MAINT.

BLDG.

(X) UV DISINFECTION

SYSTEM

(X) SECURITY FENCE

(X) MOTOR CONTROL CENTER

1MCC6

(X) 4 WAY PAD MOUNTED

PRIMARY AIR SWITCH

15kV, 600A

(X) HANDHOLE

1MCC3

(X) MOTOR CONTROL

CENTER 1MCC3

BAR SCREEN/

GRIT

REMOVAL

PRIMARY

CLARIFIER

BARDENPHO BIOLOGICAL

NUTRIENT REMOVAL

SYSTEM

A20 BIOLOGICAL

NUTRIENT REMOVAL

SYSTEM

INTER.

PUMP

STATION

FC442

CHEMICAL

BLDG. FC444

FC443

(X) MOTOR CONTROL CENTER

2MCC8ATAD OR ATP

(X) GEN. BLDG. FC443

(X) UNIT SUBSTATION #2

(X) 2MCC11

(X) GEN. BLDG. FC442

(X) UNIT SUBSTATION #3

ENTRANCE TO FRENCH CREEK TREATMENT PLANT

(X) MOTOR CONTROL CENTER

3MCC9

(X) MOTOR CONTROL CENTER

3MCC7

FC445

REVISIONS

DATE APPROVED

FC446

(X) POWER POLE

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text 12.47

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC#

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

FINAL E301

D. POKHREL

D. POKHREL

J. SIDES, P.E

D. POKHREL

J. REED, P.E

PWO

PWO

ATS REPLACEMENT AT

FC445, FC443 AND FC442

EXISTING ONE LINE

60041965 24-0015

NOTED NA 6 32

EXISTING ONE LINE DIAGRAM

NOT TO SCALE

REVISIONS

DATE APPROVED

AutoCAD SHX Text

FUTURE

AutoCAD SHX Text

ALTERNATE

AutoCAD SHX Text

SOURCE

AutoCAD SHX Text 1B

AutoCAD SHX Text 1A

AutoCAD SHX Text 1C

AutoCAD SHX Text 1D

AutoCAD SHX Text K

AutoCAD SHX Text 600A

AutoCAD SHX Text 600A

AutoCAD SHX Text

UNIT SUBSTATION #1

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text

1500 KVA

AutoCAD SHX Text

2000 AF

AutoCAD SHX Text

2000 AT

AutoCAD SHX Text

ATS #1 (2000A)

AutoCAD SHX Text

1200 AF

AutoCAD SHX Text

1200 AT

AutoCAD SHX Text

750 KW

AutoCAD SHX Text

GENSET #1

AutoCAD SHX Text

250AF

AutoCAD SHX Text

250AT

AutoCAD SHX Text

250AF

AutoCAD SHX Text

250AT

AutoCAD SHX Text

250AF

AutoCAD SHX Text

250AT

AutoCAD SHX Text

600AF

AutoCAD SHX Text

600AT

AutoCAD SHX Text

100AF

AutoCAD SHX Text

100AT

AutoCAD SHX Text

SWITCHBOARD #1

AutoCAD SHX Text K

AutoCAD SHX Text 600A

AutoCAD SHX Text 600A

AutoCAD SHX Text

UNIT SUBSTATION #2

AutoCAD SHX Text

1500 KVA

AutoCAD SHX Text

2000 AF

AutoCAD SHX Text

2000 AT

AutoCAD SHX Text

ATS #2 (2000A)

AutoCAD SHX Text

1200 AF

AutoCAD SHX Text

1200 AT

AutoCAD SHX Text

750 KW

AutoCAD SHX Text

GENSET #2

AutoCAD SHX Text

1200AF

AutoCAD SHX Text

1200AT

AutoCAD SHX Text

400AF

AutoCAD SHX Text

400AT

AutoCAD SHX Text

100AF

AutoCAD SHX Text

100AT

AutoCAD SHX Text

SWITCHBOARD #2

AutoCAD SHX Text K

AutoCAD SHX Text 600A

AutoCAD SHX Text 600A

AutoCAD SHX Text

UNIT SUBSTATION #3

AutoCAD SHX Text

1500 KVA

AutoCAD SHX Text

2000 AF

AutoCAD SHX Text

2000 AT

AutoCAD SHX Text

ATS #3 (2000A)

AutoCAD SHX Text

1600 AF

AutoCAD SHX Text

1600 AT

AutoCAD SHX Text

900 KW

AutoCAD SHX Text

GENSET #3

AutoCAD SHX Text

2000AF

AutoCAD SHX Text

2000AT

AutoCAD SHX Text

100AF

AutoCAD SHX Text

100AT

AutoCAD SHX Text

SWITCHBOARD #3

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

MANHOLE #2

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

MANHOLE #1

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

MANHOLE #3

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

MANHOLE #4

AutoCAD SHX Text

DIST.

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

1DP1

AutoCAD SHX Text

DIST.

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

1DP2

AutoCAD SHX Text

1MCC3

AutoCAD SHX Text

1MCC6

AutoCAD SHX Text

DIST.

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

1DP13

AutoCAD SHX Text

AM

AutoCAD SHX Text

VM

AutoCAD SHX Text

VS

AutoCAD SHX Text

AS

AutoCAD SHX Text

WHD

AutoCAD SHX Text

AM

AutoCAD SHX Text

VM

AutoCAD SHX Text

VS

AutoCAD SHX Text

AS

AutoCAD SHX Text

WHD

AutoCAD SHX Text

AM

AutoCAD SHX Text

VM

AutoCAD SHX Text

VS

AutoCAD SHX Text

AS

AutoCAD SHX Text

WHD

AutoCAD SHX Text

2MCC11

AutoCAD SHX Text

DIST.

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

2DP14

AutoCAD SHX Text

(480V, 3PH, 2000A BUS)

AutoCAD SHX Text

(480V, 3PH, 2000A BUS)

AutoCAD SHX Text

(480V, 3PH, 2000A BUS)

AutoCAD SHX Text

800AF

AutoCAD SHX Text

800AT

AutoCAD SHX Text

3MCC9

AutoCAD SHX Text

3MCC7

AutoCAD SHX Text

DIST.

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

3DP15

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

NORMAL

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

STANDBY

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

NORMAL

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

STANDBY

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

NORMAL

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

STANDBY

AutoCAD SHX Text 3-2000/5

AutoCAD SHX Text 3-2000/5

AutoCAD SHX Text 3-2000/5

AutoCAD SHX Text

KEY

AutoCAD SHX Text

INTERLOCK

AutoCAD SHX Text

KEY

AutoCAD SHX Text

INTERLOCK

AutoCAD SHX Text

KEY

AutoCAD SHX Text

INTERLOCK

AutoCAD SHX Text

GENERATOR BUILDING #445

AutoCAD SHX Text

GENERATOR BUILDING #442

AutoCAD SHX Text

GENERATOR BUILDING #443

AutoCAD SHX Text

(MAINT.

AutoCAD SHX Text

BLDG.)

AutoCAD SHX Text

(CONT/

AutoCAD SHX Text

ADMIN.

AutoCAD SHX Text

BLDG.)

AutoCAD SHX Text

(PRIMARY

AutoCAD SHX Text

SLUDGE

AutoCAD SHX Text

PUMP

AutoCAD SHX Text

STATION)

AutoCAD SHX Text

(EFFLUENT

AutoCAD SHX Text

FLUSHING

AutoCAD SHX Text

WATER

AutoCAD SHX Text

BLDG.)

AutoCAD SHX Text

(GENERATOR

AutoCAD SHX Text

BLDG. #1)

AutoCAD SHX Text

(ATAD OR

AutoCAD SHX Text

ATP)

AutoCAD SHX Text

(GENERATOR

AutoCAD SHX Text

BLDG. #2)

AutoCAD SHX Text

(GENERATOR

AutoCAD SHX Text

BLDG. #2)

AutoCAD SHX Text

(CHEMICAL

AutoCAD SHX Text

BLDG.)

AutoCAD SHX Text

(CHEMICAL

AutoCAD SHX Text

BLDG.)

AutoCAD SHX Text

(GENERATOR

AutoCAD SHX Text

BLDG. #3)

AutoCAD SHX Text

"E" RATED CARTRIDGE

AutoCAD SHX Text

FUSE SHALL BE SIZED BY

AutoCAD SHX Text

EQUIPMENT MANUFACTURER.

AutoCAD SHX Text

"E" RATED CARTRIDGE

AutoCAD SHX Text

FUSE SHALL BE SIZED BY

AutoCAD SHX Text

EQUIPMENT MANUFACTURER.

AutoCAD SHX Text

"E" RATED CARTRIDGE

AutoCAD SHX Text

FUSE SHALL BE SIZED BY

AutoCAD SHX Text

EQUIPMENT MANUFACTURER.

AutoCAD SHX Text

12.47 KV

AutoCAD SHX Text 480Y/277V

AutoCAD SHX Text

5 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

5 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

3 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

12.47 KV

AutoCAD SHX Text 480Y/277V

AutoCAD SHX Text

5 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

5 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

3 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

12.47 KV

AutoCAD SHX Text 480Y/277V

AutoCAD SHX Text

5 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

5 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

4 SETS

AutoCAD SHX Text

4 #500 MCM

AutoCAD SHX Text

2MCC8

AutoCAD SHX Text

PAD MOUNTED

AutoCAD SHX Text

PRIMARY SWITCH #1

AutoCAD SHX Text

15 KV, 600A

AutoCAD SHX Text

OVERHEAD DISTRIBUTION

AutoCAD SHX Text

TO POWER POLE T30

AutoCAD SHX Text

3 - 1/C #2/0, 15KV &

AutoCAD SHX Text

1 - 1/C #2/0 600V NEUTRAL (TYPICAL)

AutoCAD SHX Text Y

AutoCAD SHX Text Y

AutoCAD SHX Text Y

AutoCAD SHX Text

GF

AutoCAD SHX Text

GF

AutoCAD SHX Text

GF

AutoCAD SHX Text

SHEET:

AutoCAD SHX Text 80091

AutoCAD SHX Text E1

AutoCAD SHX Text

MARINE CORPS BASE

AutoCAD SHX Text

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

AutoCAD SHX Text

CAMP LEJEUNE, NORTH CAROLINA

AutoCAD SHX Text

DESIGN DIR.

AutoCAD SHX Text

SUBMITTED BY:

AutoCAD SHX Text

NAVFAC DRAWING NO.

AutoCAD SHX Text

CODE IDENT. NO

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SPEC#

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

SATISFACTORY TO:

AutoCAD SHX Text

APPROVED: PWO OR OICC:

AutoCAD SHX Text

DR.

AutoCAD SHX Text

DES.

AutoCAD SHX Text

CHK.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

A

A

A

CONST. CONTR. NO.

FINAL E401

D. POKHREL

D. POKHREL

J. SIDES, P.E

D. POKHREL

J. REED, P.E

PWO

PWO

ATS REPLACEMENT AT

FC445, FC443, FC442

EXSTING UNIT SUBSTATIONS

60041966 24-0015

NOTED NA 7 32

(X) UNIT SUBSTATION #1 IN FC445

NOT TO SCALE

(X) UNIT SUBSTATION #2 AT FC443

NOT TO SCALE

(X) UNIT SUBSTATION #3 AT FC442

NOT TO SCALE

REVISIONS

DATE APPROVED

AutoCAD SHX Text

600 AMP

AutoCAD SHX Text

PRIMARY

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

600 AMP

AutoCAD SHX Text

PRIMARY

AutoCAD SHX Text

SWITCH/

AutoCAD SHX Text

FUSE

AutoCAD SHX Text

CONCRETE PAD

AutoCAD SHX Text

1500 KVA

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

METERING

AutoCAD SHX Text

COMPARTMENT

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

2000 AMP

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

2000 AMP

AutoCAD SHX Text

AUTOMATIC

AutoCAD SHX Text

TRANSFER/

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

ISOLATION

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

2000 AMP

AutoCAD SHX Text

MAIN LUGS

AutoCAD SHX Text

AM

AutoCAD SHX Text

VM

AutoCAD SHX Text

AS

AutoCAD SHX Text

WHM

AutoCAD SHX Text

VS

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

100 AMP

AutoCAD SHX Text

GEN. BLDG

AutoCAD SHX Text

FC445

AutoCAD SHX Text

300 AMP

AutoCAD SHX Text

MAINT. BLDG

AutoCAD SHX Text

FC441

AutoCAD SHX Text

250 AMP

AutoCAD SHX Text

PRI.SLUDGE BLD

AutoCAD SHX Text

FC467

AutoCAD SHX Text

600 AMP

AutoCAD SHX Text

EFF FLUSH BLDG

AutoCAD SHX Text

FC447

AutoCAD SHX Text

400 AMP

AutoCAD SHX Text

ADMIN BLDG

AutoCAD SHX Text

FC436

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

1DP13

AutoCAD SHX Text

1DP13

AutoCAD SHX Text

1MCC3

AutoCAD SHX Text

1MCC6

AutoCAD SHX Text

1DP2

AutoCAD SHX Text

600 AMP

AutoCAD SHX Text

PRIMARY

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

600 AMP

AutoCAD SHX Text

PRIMARY

AutoCAD SHX Text

SWITCH/

AutoCAD SHX Text

FUSE

AutoCAD SHX Text

CONCRETE PAD

AutoCAD SHX Text

1500 KVA

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

METERING

AutoCAD SHX Text

COMPARTMENT

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

2000 AMP

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

2000 AMP

AutoCAD SHX Text

AUTOMATIC

AutoCAD SHX Text

TRANSFER/

AutoCAD SHX Text

BYPASS

AutoCAD SHX Text

ISOLATION

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

2000 AMP

AutoCAD SHX Text

MAIN LUGS

AutoCAD SHX Text

AM

AutoCAD SHX Text

VM

AutoCAD SHX Text

AS

AutoCAD SHX Text

WHM

AutoCAD SHX Text

VS

AutoCAD SHX Text

1200 AMP

AutoCAD SHX Text

ATAD BLDG

AutoCAD SHX Text

FC446

AutoCAD SHX Text

MDP

AutoCAD SHX Text

100 AMP

AutoCAD SHX Text

GEN. BLDG

AutoCAD SHX Text

FC443

AutoCAD SHX Text

2DP14

AutoCAD SHX Text

400 AMP

AutoCAD SHX Text

GEN. BLDG

AutoCAD SHX Text

FC445

AutoCAD SHX Text

2MCC11

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

A…