ATTACHMENT_K_Design Revision 01.pdf
PDF 257 KB Posted
- Attached to
- REPLACE HVAC, BLDG SP-366
- Solicitation number
- N4008521R0046
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N40085-21-R-0046 Amendment 0001.pdf | ||
| ATTACHMENT_I_Site Vist Log.pdf | ||
| ATTACHMENT_J_PPI Responses.pdf | ||
| General Requirements.pdf | ||
| ATTACHMENT_E_ODP.xls | XLS spreadsheet | |
| ATTACHMENT_A_SP366_1487319_SPEC.pdf | ||
| ATTACHMENT_H_Provision 52.204-24.pdf | ||
| ATTACHMENT_G_PRICE PROPOSAL.pdf | ||
| ATTACHMENT_D_SECNAV_ 5512_1.pdf | ||
| ATTACHMENT_B_SP366_1487319_DWGS.pdf | ||
| ATTACHMENT_C_Wage Determination.pdf | ||
| ATTACHMENT_F_Pre-Proposal_Inquiry_Form 1516511.xls | XLS spreadsheet |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PWD Norfolk, Facilities Engineering and Acquisition Division Page 1 of 1
Design Revision 01 eProjects Work Order Number: 1487319
Construction Contract Number:
Building: SP-366
Project Title: REPLACE HVAC SYSTEM
Date: February 24, 2021
Design Revision Purpose
1. Response to PPI.
Drawing Revisions
SECTION 00 01 15 LIST OF DRAWINGS
1.2 CONTRACT DRAWINGS
The following drawings are revised as of February 24, 2021 and accompany this Design Revision:
NAVFAC Dwg. No. Title
Mechanical 12,819,614 (M-703) Controls
Electrical 12,819,626 (E-401) Partial First Floor Power Plan – Mechanical & Flight
On NAVFAC Drawing No. 12,819,583 (HM101) PARTIAL 1ST FLOOR CEILING PLAN – MECH RM 108 – GWB CEILING – HAZMAT ABATEMENT WORK: Revise the following note: “EXISTING STRUCTURAL BEAM WITH GWB SHEATHING TO REMAIN, NIC.” Revised note to read: “EXISTING STRUCTURAL BEAM WITH GWB SHEATHING. BEAM TO REMAIN. REMOVE GWB
SHEATHING AND BLOCKING COMPLETE PER DETAIL A1 ON SHEET AD402. ASSUME PRESENCE OF
ASBESTOS CONTAMINATED GWB SHEATHING AND JOINT COMPOUND.”
OUTSIDE
AIR
NC
NO
FILTER
HEATING
COIL
RETURN
AIR
COOLING
COIL
SA FAN SUPPLY
AIR
H L
NORTH WALL
FLOW
STN
AI2
T
AO4
MD
MDAO5
T
AI6
AFS
AI5
T
AI4
VFD
BI2
AO1 BO1
T
AI3
PS BI1 SP
AI1
TO FACP
SD
AO3 AO2
FILTER
DPS
BI4
DPS
BI3
M
CHWR
CHWS
HWR
HWS
T
BI8
M
OCCUPIED MODE:
AHU-1 SHALL BE STARTED THRU THE DDC. UPON A SIGNAL TO START THE AHU FROM THE DDC SYSTEM, THE SUPPLY FAN SHALL ENERGIZE AND THE OUTSIDE AIR DAMPER SHALL OPEN TO ITS MINIMUM POSITION.
PROVIDE AN AIRFLOW MEASURING STATION IN THE OUTSIDE AIR DUCT. UPON A FALL OR RISE IN OUTSIDE AIR CFM BELOW OR ABOVE SETPOINT, THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN SETPOINT. THE SUPPLY FAN VFD SHALL MODULATE TO MAINTAIN THE DOWNSTREAM DUCT PRESSURE SETPOINT. THE DUCT STATIC PRESSURE SETPOINT SHALL BE SENT BY THE DDC AND SHALL BE RESET BETWEEN THE MINIMUM AND MAXIMUM STATIC PRESSURE LIMITS TO MAINTAIN THE CRITICAL ZONE VAV AIR DAMPER IN A POSITION BETWEEN 65% AND 75% OPEN. THE DDC SHALL RESET THE DUCT STATIC PRESSURE SETPOINT BASED ON THE POSITION OF THE FURTHEST OPEN VAV DAMPER. WHEN THE UNIT IS IN THE UNOCCUPIED MODE THE CONTROLLER SHALL MODULATE THE SPEED OF THE VFD TO 50%. IF THE DUCT STATIC PRESSURE SENSOR FAILS, THE VFD SHALL MODULATE ITS SPEED TO 50% AND AN ALARM SHALL BE ANNUNCIATED AT THE BAS.
PROVIDE ALARMS FOR FAN FAILURE (COMMANDED ON BUT THE STATUS IS OFF), FAN RUNNING IN HAND (COMMANDED OFF BUT THE STATUS IS ON), AND FILTER DIFFERENTIAL STATIC PRESSURES. IF DISCHARGE STATIC PRESSURE RISES ABOVE 3.00 INCHES WC (ADJ), DE-ENERGIZE THE SUPPLY FAN AND SEND AN ALARM.
ON A RISE IN DISCHARGE AIR TEMPERATURE ABOVE THE COOLING SETPOINT (55°F, ADJ), THE CHILLED WATER VALVE SHALL MODULATE TO MAINTAIN SETPOINT. ON A FALL IN DISCHARGE AIR TEMPERATURE BELOW THE COOLING SETPOINT, THE CHILLED WATER VALVE SHALL CLOSE. ON A FURTHER FALL IN DISCHARGE AIR TEMPERATURE BELOW THE HEATING SETPOINT (52°F, ADJ.), THE HEATING WATER VALVE SHALL OPEN AND MODULATE TO MAINTAIN SETPOINT. ON A RISE IN DISCHARGE AIR TEMPERATURE ABOVE THE HEATING
SETPOINT, THE HEATING WATER VALVE SHALL CLOSE.
ON A RISE IN DISCHARGE AIR TEMPERATURE ABOVE SETPOINT FOR GREATER THAN 5 MINUTES, AN ALARM SHALL BE SIGNALED TO THE DDC SYSTEM. ON A FALL IN DISCHARGE AIR TEMPERATURE BELOW SETPOINT
FOR GREATER THAN 5 MINUTES, AN ALARM SHALL BE SIGNALED TO THE DDC SYSTEM.
PROVIDE A FREEZESTAT IMMEDIATELY UPSTREAM OF THE COOLING COIL. OPERATION SHALL BE SUCH THAT ON A FALL IN MIXED AIR TEMPERATURE BELOW 38 °F, THE UNIT SHALL DE-ENERGIZE, THE OUTSIDE AIR DAMPER SHALL FULLY CLOSE, THE COOLING AND HEATING COIL VALVES SHALL FULLY OPEN, AND AN ALARM
SHALL BE SIGNALED TO THE DDC SYSTEM.
ON RECEIPT OF A SIGNAL FROM EITHER OF THE AIR HANDLER'S CORRESPONDING DUCT SMOKE DETECTOR, THE UNIT SHALL DEENERGIZE AND AN ALARM SHALL BE SIGNALED TO THE DDC SYSTEM. THE UNIT WILL DEENERGIZE AND GENERATE AN ALARM UPON RECEIVING A SIGNAL FROM THE EMERGENCY STOP SWITCH.
UPON DEENERGIZING OF THE UNIT FOR ANY REASON, THE OUTSIDE AIR DAMPER SHALL FULLY CLOSE.
UNOCCUPIED MODE:
UPON ENTERING UNOCCUPIED MODE, THE UNIT'S SUPPLY FAN SHALL DE-ENERGIZE, THE OUTSIDE AIR DAMPER SHALL FULLY CLOSE. ON A CALL FOR HEATING IN THE UNOCCUPIED MODE, THE SUPPLY AIR FAN VFD SHALL ENERGIZE AND MODULATE FAN SPEED TO MAINTAIN DOWN DUCT STATIC PRESSURE AT SETPOINT. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE HEATING COIL VALVE SHALL MODULATE TO MAINTAIN
THE DISCHARGE AIR TEMPERATURE AT SETPOINT.
UPON A CALL FOR COOLING FROM ANY OF THE ZONES SERVED BY THE AHU, THE SUPPLY AIR FAN VFD SHALL ENERGIZE AND MODULATE FAN SPEED TO MAINTAIN DOWN DUCT STATIC PRESSURE AT SETPOINT. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE COOLING COIL VALVE SHALL MODULATE TO MAINTAIN
DISCHARGE AIR TEMPERATURE AT SETPOINT.
MORNING WARMUP PULLDOWN:
PRIOR TO TRANSITIONING FROM UNOCCUPIED TO OCCUPIED MODE, THE UNIT SHALL EXECUTE A MORNING WARMUP/PULLDOWN SEQUENCE. THE UNIT SHALL IMPLEMENT AN OPTIMAL START ALGORITHM TO MINIMIZE THE WARMUP OR PULLDOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF THE
SCHEDULED OCCUPIED PERIOD.
H W
S H
W R
H W
C O
IL
T
SUPPLY FAN
MS
UH-1 & EF-2 SEQUENCE OF OPERATION :
UH-1 UNIT SHALL BE CONTROLLED BY DDC AND 2-WAY HEATING
COIL VALVE SHALL OPEN AND FAN SHALL RUN TO MAINTAIN 60°F
(ADJ) IN SPACE AIR TEMPERATURE DURING WINTER.
UH-1 FAN SHALL RUN TO MAINTAIN 85°F (ADJ) IN SPACE AIR
TEMPERATURE DURING SUMMER.
UPON A RISE IN SPACE AIR TEMPERATURE ABOVE 85°F (ADJ),
OUTSIE AIR DAMPER AND EXHAUST AIR DAMPER OPEN AND
EXHAUST FAN SHALL RUN. UPON A FALL IN SPACE AIR
TEMPERATURE BELOW 85°F (ADJ) REVERSE SHALL OCCUR.
OUTSIDE & EXHAUST AIR DAMPERS SHALL BE INTERLOCKED TO
EXHAUST FAN.
THE BUILDING DDC SYSTEM SHALL MONITOR FANs & DAMPERs STATUs AND SPACE TEMPERATURE. UPON SENSING UNIT FAILURE
THE ALARM SHALL BE SENT TO THE BUILDING DDC SYSTEM.
AI1 BO1
BO2 BI2
MD
OUTSIDE AIR
DAMPER
BACKDRAFT
EXHAUST
AIR DAMPER
EXHAUST FAN
MS
BO3 BI3
BI4
EF-1 SEQUENCE OF OPERATION :
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE.
OCCUPIED MODE:
UNIT EXHAUST AIR DAMPER OPEN AND EXHAUST FAN SHALL RUN.
UNOCCUPIED MODE:
UNIT EXHAUST AIR DAMPER CLOSE AND EXHAUST FAN SHALL STOP.
THE BUILDING DDC SYSTEM SHALL MONITOR FAN STATU. UPON SENSING UNIT FAILURE THE ALARM SHALL BE SENT TO THE BUILDING
DDC SYSTEM.
BACKDRAFT
EXHAUST AIR
DAMPER
EXHAUST FAN
MS
BO3 BI3
H W
S H
W R
H W
C O
IL
T
FTR SEQUENCE OF OPERATION :
FTR -1 UNIT SHALL BE CONTROLLED BY DDC AND 2-WAY HEATING COIL VALVE SHALL OPEN AND FAN SHALL RUN TO MAINTAIN 68°F (ADJ) IN SPACE
AIR TEMPERATURE.
THE BUILDING DDC SYSTEM SHALL MONITOR SPACE TEMPERATURE. UPON SENSING UNIT FAILURE THE ALARM SHALL BE SENT TO THE BUILDING
DDC SYSTEM.
AI1 BO1
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 06 APRIL 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
H A
M P
T O
N R
O A
D S
IP
T
P
W D
N O
R F
O
LK
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K , V
A
S.M. SWEENEY, P.E.
N O
R F
O
LK
N A
V A
L S
T A
T
IO
N N
O R
F O
LK
, V
IR
G
IN
IA
AS NOTED
M-703
B U
IL
D
IN
G
S P
-3
R E
P
LA
C E
H V
A C
S Y
S
TE
M
CO
NT
RO
LS
BG
12,819,614
LXL LXL
06/15/2020
KIRK STEVENS
LILY LI, P.E.
1487319
N/A
NOT TO SCALE
AHU-1 VARIABLE AIR HANDLING UNIT CONTROL SEQUENCE AND DIAGRAMA3
AHU-1 DCC POINT LIST
CONTROL MARK POINT NAME
AI1 2/3 DUCT PRESSURE
AI2 OUTSIDE AIR TEMPERATURE
AI3 SUPPLY AIR TEMPERATURE
AI4 MIXED AIR TEMPERATURE
AI5 MIN OA FLOW
AI6 RETURN AIR TEMPERATURE
AO1 SUPPLY FAN SPEED
AO2 CW CONTROL VALVE
AO3 HW CONTROL VALVE
AO4 OA AIR DAMPERS %OPEN
AO5 RETURN AIR DAMPERS %OPEN
BI1 DUCT HIGH STATIC ALARM
BI2 SUPPLY FAN STATUS
BI3 FILTER STATUS
BI4 FILTER STATUS
BI5 OA AIR DAMPER STATUS
BI6 RA AIR DAMPER STATUS
BI7 SMOKE DETECTOR STATUS
BI8 LOW LIMIT TEMP STATUS
BO1 SUPPLY FAN START/STOP
NOT TO SCALE
RM108 ROOM CONTROL SEQUENCE AND DIAGRAM (TYP. OF RM110)A1
RM108 DCC POINT LIST
CONTROL MARK POINT NAME
AI1 SPACE TEMPERATURE
BI2 SUPPLY FAN STATUS
BI3 EXHAUST FAN STATUS
BI4 OA AIR DAMPER STATUS
BO1 HW CONTROL VALVE
BO2 SUPPLY FAN START/STOP
BO3 EXHAUST FAN START/STOP
NOT TO SCALE
EF-1 CONTROL SEQUENCE AND DIAGRAMB1
EF-1 DCC POINT LIST
CONTROL MARK POINT NAME
BI3 EXHAUST FAN STATUS
BO3 EXHAUST FAN START/STOP
NOT TO SCALE
FTR CONTROL SEQUENCE AND DIAGRAM (TYP.)C1
FTR DCC POINT LIST
CONTROL MARK POINT NAME
AI1 SPACE TEMPERATURE
BO1 HW CONTROL VALVE
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
D es ig n
R ev is io n
2/
/2
LX
L
MDP
J
M
M
M
M
M
M
UH-1
PP
SDP
EM
L H
HWP-1
HWP-2
B-2 B-1
AHU-1
AHU-2
VAV-2
VAV-1
CRAHU-2
T1
PP - 1,3,5
PP - 2,4,6
L - 1
PP - 7,9,11
PP - 8,10,12
PP - 13,15,17
PP - 19,21,23
PP - 20,22,24
L - 32
L - 34
TELEPHONE BACKBOARD
VFD
VFD
VFD
VFD
MECH/ELEC
107112
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G C
O M
M
AN
D
DRAWFORM REVISION: 06 APRIL 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
H
AM
PT
O
N R
O
AD
S
IP
T
- P
W D
N O
R
FO
LK
N
AV
AL
S
TA
TI
O
N
N O
R
FO
LK
, V
A
S.M. SWEENEY, P.E.
N O
R
FO
LK
N
AV
AL
S
TA
TI
O
N N
O R
FO
LK
, V
IR
G
IN
IA
AS NOTED
E-401
B U
IL
D
IN
G
S P
-3
R E
P
LA
C E
H V
A C
S Y
S
TE
M
PA
RT
IA
L
FI
RS
T
FL
O O
R
PO
W
ER
P
LA
N
- M
EC
HA
NI
CA
L
FL
IG
HT
T
RA
IN
ER
R
O O
M S
MPH
12,819,626
CJM CJM
6/15/2020
KIRK STEVENS
LILY LI, P.E.
1487319
N/A
0 2" 4" 8"SCALE: 3/8" = 1'-0" (E-101)
PARTIAL FIRST FLOOR POWER PLAN - MECHANICAL & TRAINER RMA1
GENERAL NOTES
NOTES
KEY PLAN
1 REFER TO SHEET E-001 FOR GENERAL NOTES.
2 COORDINATE FIRE ALARM WORK WITH FIRE PROTECTION DRAWINGS AND
MANUFACTURER'S RECOMMENDATIONS.
3 IF A CONFLICT OCCURS WITH THE LAYOUT OF ARCHITECTURAL, MECHANICAL,
PLUMBING OR FIRE PROTECTION DEVICES, NOTIFY THE CONTRACTING OFFICER
PRIOR TO PROCEEDING WORK.
4 COORDINATE ELECTRICAL CONNECTIONS TO ARCHTECTURAL, MECHANICAL
AND PLUMBING EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS TO
ENSURE PROPER OPERATION OF EQUIPMENT.
1 PROVIDE A 150A, 480/277V, 3P, 4W, 36 CIRCUIT, MCB, SURFACE-MOUNTED
PANELBOARD. CIRCUIT CONSISTS OF 4-#1/0 & 1-#6 GND. IN 2" CONDUIT BACK TO
PANEL MDP. CONTRACTOR SHALL VERIFY PANEL DIMENSIONS AND LOCATION
PRIOR TO ORDERING PANEL TO ENSURE IT WILL FIT IN AVAILABLE SPACE.
2 PROVIDE A NEW 150A, 3P, 480V CIRCUIT BREAKER IN PANEL MDP. EXISTING MDP
IS ARROW HART TYPE.
3 RELOCATE DDC CONTROL PANEL TO WALL. CONTRACTOR SHALL REROUTE
FEEDER CONDUIT TO PANEL'S NEW LOCATION. COORDINATE WORK WITH
MECHANICAL PLANS. REROUTE CONDUITS ALONG WALL TO ALLOW FOR
PLACEMENT OF PANEL.
4 REROUTE EXISTING CIRCUIT TO NEW CONTROLS AND EXTEND CIRCUIT TO NEW
PANEL "PP". REFER TO MECHANICAL DRAWINGS FOR DETAILS. LABEL
CONTROLLER FOR RESPECTIVE VENILATOR UNIT.
5 PROVIDE FEEDER FOR NEW DDC PANEL FROM PANEL L. CIRCUIT CONSISTS OF
2-#12 & 1-#12 GND. IN 1/2"C. PROVIDE PLENUM-RATED, CAT 6 CABLE FROM
TELEPHONE BACKBOARD TO NEW DDC PANEL.
6 PROVIDE A 30A, 3P, 600V, NEMA 1, FUSED DISCONNECT SWITCH FOR AHU.
FUSES SHALL BE RATED AT 25A. CIRCUIT CONSISTS OF 3-#10 & 1-#10 GND. IN
3/4"C. LABEL DISCONNECT SWITCH AHU-1 OR AHU-2 FOR RESPECTIVE UNIT.
7 VFD PROVIDED WITH AIR HANDLING UNIT. CONNECT PER MANUFACTURER'S
RECOMMENDATIONS.
8 PROVIDE A 30A, 3P, 600V, NEMA 1, FUSED DISCONNECT SWITCH FOR CRAHU-2.
FUSES SHALL BE RATED AT 30A. CIRCUIT CONSISTS OF 3-#8 & 1-#10 GND. IN
3/4"C. LABEL DISCONNECT SWITCH FOR RESPECTIVE UNIT.
9 PROVIDE A 30A, 2P, 240V, NEMA 1, FUSED DISCONNECT SWITCH FOR UNIT
HEATER. FUSES SHALL BE RATED AT 5A. CIRCUIT CONSISTS OF 2-#12 & 1-#12
GND. IN 1/2"C. CIRCUIT IS 120V. LABEL DISCONNECT SWITCH FOR RESPECTIVE
UNIT.
10 PROVIDE A 20A, 1P, 120V, MOTOR-RATED, TOGGLE SWITCH. MOUNT SWITCH ON
VAV BOX. CIRCUIT CONSISTS OF 2-#12 & 1-#12 GND. IN 1/2"C.
11 PROVIDE A 30A, 3P, 600V, NEMA 1, FUSED DISCONNECT SWITCH FOR HOT
WATER PUMP. FUSES SHALL BE RATED AT 5A. CIRCUIT CONSISTS OF 3-#10 &
1-#10 GND. IN 1/2"C. LABEL HWP-1 OR HWP-2 FOR RESPECTIVE UNIT.
PLAN
NORTH
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
De sig n R ev isi on
2/2 4/2
CJ
M
FLOOR 1
PLAN
NORTH
| 2017-SP366-1487319-E-401.pdf |
| Sheets |
| E-401 - PARTIAL FIRST FLOOR POWER PLAN - MECHANICAL & FLIGHT TRAINER ROOMS |
| 2017-SP366-1487319-M-703.pdf |
| Sheets |
| M-703 - CONTROLS |