July 2011

Solicitation: N4008521R0046 Title: Building SP-366 HVAC Replacement

1 2/17/2021

M-601 Schedules & E-401 Note 4 Indicate that Exhaust Fan EF-2 is to be a 2-Speed Fan (please note it does not indicate EF-3 to be a 2-Speed Fan). M-703 Detail A1 does not indicate 2-Speed control for any fan.

Additionally E-401 Note 4 Requires Electrical Contractors to provide New Automated controls for 2-Speed Powered Roof Ventilators #2 & #3. There appears to be no control system diagram or sequence of Operation for EF-3. Please provide clarification as to the controls for EF-1, EF-2 and EF-3 with respect to these concerns. See Questions 2-6 below for more specifics.

DELETE 2-SPEED FAN CONTROL, ONLY

ONE POINT FOR LOW SPEED CONTROL.

DELTET M-703 EXHAUST AIR DAMPER

CONTROL SINCE ROOF EXHANUST FAN

WITH BACKDRAFT DAMPER. 1

2 2/17/2021

Refer to the Information Contain in Question 1 Above: Is EF-2 to be controlled as a 2-Speed Fan? (Requires two outputs to change speed) Would also need a Control Sequence for Speed controls

SEE RESPONSE 1

3 2/17/2021 Refer to the Information Contain in Question 1 Above: Is EF-3 a 2- Speed Fan?

SEE RESPONSE 1

4 2/17/2021 Refer to the Information Contain in Question 1 Above: Is EF-3 to be controlled by the DDC system?

SEE RESPONSE 1

5 2/17/2021

If EF-3 is to be controlled by the DDC and/or Controlled as 2-Speed fan, please provide the necessary Controls Diagrams and Sequences as they may apply.

SEE RESPONSE 1

6 2/17/2021

M-703 Control Diagram and Sequences indicate an Outside Air Damper is to be controlled with EF-2 (Potentially EF-3, as well), however notes on MD-102 indicate the Existing Roof Ventilation Dampers are to have their the pneumatic damper actuator removed and be locked closed. New Work plans do not appear to include new dampers that would be associated with these fans. Please indicate if the "Outside Air Damper" shown on M-703 is to be controlled and its location/s if it is.

MD101 NOTE 12 - OUTSIDE AIR DAMPER

INTERLOCKED WITH EF-3.

M-401 NOTE 17 - OUTSIDE AIR DAMPER

INTERLOCKED WITH EF-2. N/A

7 2/24/2021

Sheet HM101 Partial 1st floor ceiling plan Mech Rm 108 Has note that sheathing on beam is NIC. Sheet AD402 Section A1 shows the sheathing and blocking being demoed. Please advise?

Revised note to read: “EXISTING

STRUCTURAL BEAM WITH GWB

SHEATHING. BEAM TO REMAIN. REMOVE

GWB SHEATHING AND BLOCKING

COMPLETE PER DETAIL A1 ON SHEET

AD402. ASSUME PRESENCE OF

ASBESTOS CONTAMINATED GWB

SHEATHING AND JOINT COMPOUND.”