ATTACHMENT_J_PPI Responses.pdf
PDF 93 KB Posted
- Attached to
- REPLACE HVAC, BLDG SP-366
- Solicitation number
- N4008521R0046
View the file
Other files
| File | Type | Posted |
|---|---|---|
| N40085-21-R-0046 Amendment 0001.pdf | ||
| ATTACHMENT_I_Site Vist Log.pdf | ||
| ATTACHMENT_K_Design Revision 01.pdf | ||
| General Requirements.pdf | ||
| ATTACHMENT_E_ODP.xls | XLS spreadsheet | |
| ATTACHMENT_A_SP366_1487319_SPEC.pdf | ||
| ATTACHMENT_H_Provision 52.204-24.pdf | ||
| ATTACHMENT_B_SP366_1487319_DWGS.pdf | ||
| ATTACHMENT_C_Wage Determination.pdf | ||
| ATTACHMENT_F_Pre-Proposal_Inquiry_Form 1516511.xls | XLS spreadsheet | |
| ATTACHMENT_G_PRICE PROPOSAL.pdf | ||
| ATTACHMENT_D_SECNAV_ 5512_1.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
July 2011
Solicitation: N4008521R0046 Title: Building SP-366 HVAC Replacement
1 2/17/2021
M-601 Schedules & E-401 Note 4 Indicate that Exhaust Fan EF-2 is to be a 2-Speed Fan (please note it does not indicate EF-3 to be a 2-Speed Fan). M-703 Detail A1 does not indicate 2-Speed control for any fan.
Additionally E-401 Note 4 Requires Electrical Contractors to provide New Automated controls for 2-Speed Powered Roof Ventilators #2 & #3. There appears to be no control system diagram or sequence of Operation for EF-3. Please provide clarification as to the controls for EF-1, EF-2 and EF-3 with respect to these concerns. See Questions 2-6 below for more specifics.
DELETE 2-SPEED FAN CONTROL, ONLY
ONE POINT FOR LOW SPEED CONTROL.
DELTET M-703 EXHAUST AIR DAMPER
CONTROL SINCE ROOF EXHANUST FAN
WITH BACKDRAFT DAMPER. 1
2 2/17/2021
Refer to the Information Contain in Question 1 Above: Is EF-2 to be controlled as a 2-Speed Fan? (Requires two outputs to change speed) Would also need a Control Sequence for Speed controls
SEE RESPONSE 1
3 2/17/2021 Refer to the Information Contain in Question 1 Above: Is EF-3 a 2- Speed Fan?
SEE RESPONSE 1
4 2/17/2021 Refer to the Information Contain in Question 1 Above: Is EF-3 to be controlled by the DDC system?
SEE RESPONSE 1
5 2/17/2021
If EF-3 is to be controlled by the DDC and/or Controlled as 2-Speed fan, please provide the necessary Controls Diagrams and Sequences as they may apply.
SEE RESPONSE 1
6 2/17/2021
M-703 Control Diagram and Sequences indicate an Outside Air Damper is to be controlled with EF-2 (Potentially EF-3, as well), however notes on MD-102 indicate the Existing Roof Ventilation Dampers are to have their the pneumatic damper actuator removed and be locked closed. New Work plans do not appear to include new dampers that would be associated with these fans. Please indicate if the "Outside Air Damper" shown on M-703 is to be controlled and its location/s if it is.
MD101 NOTE 12 - OUTSIDE AIR DAMPER
INTERLOCKED WITH EF-3.
M-401 NOTE 17 - OUTSIDE AIR DAMPER
INTERLOCKED WITH EF-2. N/A
7 2/24/2021
Sheet HM101 Partial 1st floor ceiling plan Mech Rm 108 Has note that sheathing on beam is NIC. Sheet AD402 Section A1 shows the sheathing and blocking being demoed. Please advise?
Revised note to read: “EXISTING
STRUCTURAL BEAM WITH GWB
SHEATHING. BEAM TO REMAIN. REMOVE
GWB SHEATHING AND BLOCKING
COMPLETE PER DETAIL A1 ON SHEET
AD402. ASSUME PRESENCE OF
ASBESTOS CONTAMINATED GWB
SHEATHING AND JOINT COMPOUND.”
Question No. QUESTION GOVERNMENT RESPONSEDate Received Posted on Amend No.