Ambulatory Care Center/Dental Clinic Replacement Hadnot Point Hazardous Material Survey Report

September 2017

Table 1 – Lead Based Paint Results

Sample # Location Component Detail Paint Color Area (ft2) / Length (lf)

Highest XRF Reading (mg/cm²)

331-008 Building 331 Exterior concrete window sills White 23 ft2 3.45

331-009 Building 331 Exterior metal wall strips White 3.5 ft2 3.70

332-004 Building 332 Exterior metal wall strips Red 4.3 ft2 1.32

332-015 Building 332 Interior concrete support columns White 40 ft2 4.29

408-008 Building 408 Interior floor stripes Yellow 150 ft2 2.03

408-009 Building 408 Interior concrete support column bases Yellow 61 ft2 2.31

408-011 Building 408 Interior concrete bollard Yellow 56 ft2 1.89

408-012 Building 408 Interior metal attic access ladder Red 5.6 ft2 2.64

408-013 Building 408 Interior metal attic support trusts/beams Orange/Grey 3,415 ft2 3.43

408-019 Building 408 Exterior metal porch support columns White 125 ft2 3.59

408-026 Building 408 Interior metal fire alarm panel Red 2.8 ft2 1.56

441-008 Building 441 Interior concrete wall base paint Black 300 ft2 3.76

441-009 Building 441 Interior concrete floor striping Yellow 15 ft2 2.07

*P010-IN

*P011-IN

Building 460;

Interior

Lead-Lined doors in X-Ray room (2 doors) Not Painted 80 ft2 5.6

*P012-IN Building 460;

Interior

Lead-Lined walls in X-Ray room (4 walls) White/Off-White 384 ft2 4.1

*P013-OUT Building 460;

Exterior

Exterior Steps to northwestern side entrance door

Yellow w/ red undercoat 20 ft2 4.5

*P014-OUT Building 460;

Exterior

Exterior Steps to southwestern side entrance door

Yellow w/ red undercoat 20 ft2 6.7

(*) indicates results from the LBP survey performed on 28-29 October 2013.

1.0 PROJECT OVERVIEW
2.0 LEAD-BASED PAINT SURVEY
2.1 LBP Survey Findings
2.2 LBP Survey Conclusion and Recommendations
3.0 ASBESTOS SURVEY
3.1 Asbestos Survey Findings
3.2 Asbestos Survey Conclusion and Recommendations
4.0 PCBs / MERCURY / UNIVERSAL WASTE
4.1 PCB Survey
4.2 Mercury Survey
4.3 Universal Waste Survey
4.4 Environmental Considerations

5.0 SURVEY LIMITATIONS