About this file

This document is a Facility Investment specification for a federal contract opportunity. It outlines the requirements for the Contractor to perform maintenance, repair, alteration, demolition and minor construction work on HVAC systems, refrigeration systems, and icemaker systems at various locations.

The key requirements include: 1) Recurring Work - The Contractor shall perform Emergency, Urgent, and Routine service orders, as well as develop and implement a Preventive Maintenance program, to ensure the HVAC and icemaker systems are fully functional and in normal working condition. 2) Non-Recurring Work - The Contractor may be issued task orders to accomplish any identified work within the installation boundary, whether or not the HVAC and icemaker systems are specifically listed. The Contractor must comply with various workmanship, material, and safety standards. The work will be ordered through DoD FEDMALL or task orders.

View the file

Other files

File Type Posted
A0002-S.pdf PDF
N4008425B04090001.pdf PDF
Amend 0001.pdf PDF
N4008425B0409_Attachment (2) SOP and J-2000000-13 ELINs.xlsx XLSX spreadsheet
N4008425B0409_Attachment (1) Performance Work Statement.pdf PDF
N4008425B0409_Attachment (3) PreBid Inquiry Form.xlsx XLSX spreadsheet
N4008425B0409.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1502000 – Facility Investment Table of Contents

Spec Item Title 1 General Information

1.1 Outline of Services

2 Management and Administration

2.1 Definitions and Acronyms

2.2 Personnel

2.2.1 Certification, Training, and Licensing

2.3 Special Requirements

2.3.1 Workmanship and Material Standards

2.3.2 Historical Preservation

2.3.3 Business Permits

2.4 References and Technical Documents

3 Recurring Work

3.1 Emergency, Urgent, and Routine (E/U/R) Work

3.1.1 Emergency

3.1.2 Urgent

3.1.3 Routine

3.2 Projects

3.2.1 Minor

3.2.2 Major

3.3 Preventive Maintenance (PM) Program

3.3.1 HVAC and Refrigeration Systems

3.3.2 Icemaker Systems

4 Non-Recurring Work

Spec Item Title Description 1 General

Information

1.1 Outline of

Services

The intent of 1502000 Facility Investment is to specify the requirements for Sustainment, Restoration, and Modernization (SRM) sub-functions only. The Facility Investment requirements within this sub-annex primarily consist of infrastructure sustainment and minimal restoration and modernization work.

Sustainment is the maintenance and repair necessary to keep an inventory of facilities and other assets in good working order. Restoration and modernization normally consist of major rehabilitation and capital improvements that is accomplished through other Navy programs. Some major repair, minor construction and stand-alone demolition may be accomplished as part of Facility Investment.

The Contractor shall perform maintenance, repair, alteration, demolition and minor construction for the following:

Building Systems

− Heating, Ventilation and Air Conditioning (HVAC) Systems, and Refrigeration Systems

Miscellaneous − Icemaker Systems

2 Management and

Administration

2.1 Definitions and

Acronyms

Definitions and Acronyms are listed in J-1502000-01.

2.2 Personnel In addition to the Employee Requirements specified in Annex 2, the Contractor shall provide personnel with the qualifications specified below.

2.2.1 Certification, Training, and Licensing

All maintenance and repair work at the site shall be performed by personnel trained and certified by the Original Equipment manufacturer (OEM) and by personnel who possess appropriate license or certification as follows.

Personnel working on systems, equipment or components containing chlorofluorocarbons (CFCs) and/or hydro-chlorofluorocarbons (HCFCs) must be certified under an Environmental Protection Agency (EPA) approved technical certification program per OPNAVINST 5090.1 Chapter 6 or registered as “Dai-1-syu -Furonrui- Kaishuugyousha.

Electric Work: Personnel working with or on electrical or electronic equipment, exception of electric wiring and control boards equipped at equipment, must be trained and certified per NAVFAC MO-200, or the electricians who have license of first grade electrician, "Dai-1-syu Denki Kohjishi", or second grade electrician, "Dai-2-syu Denki Kohjishi".

All maintenance trade personnel certifying or inspecting repair or maintenance work that does not require an inspector certified by a governing directive shall be qualified at the journeyman level.

The Contractor shall submit proof of all certification, training, and licensing requirements per Section F.

2.3 Special

Requirements

2.3.1 Workmanship

and Material Standards

The Contractor shall be responsible for maintaining all facilities, systems, and equipment, identified in this technical sub-annex, to a standard that prevents deterioration beyond that which results from normal wear and tear and corrects deficiencies in a timely manner to assure full life expectancy of the facilities, systems, and equipment. Best commercial practices shall be applied in the performance of work. All work shall be completed per approved and accepted industry and equipment manufacturers’ standards and shall comply with building and safety codes, applicable activity, local, state, and federal regulations, and other technical requirements identified within this technical sub-annex.

Workmanship for maintenance and repair shall include all work necessary to complete facility and system restoration, including touch-up painting and operational checks. Upon completion of work, the Contractor shall ensure all facilities, systems, and equipment are free of missing components or defects which would affect the safety, appearance, or habitability of the facilities and structures or would prevent any electrical, mechanical, plumbing or structural system from functioning in accordance with design intent. Repairs shall be made in accordance with the manufacturers’ specifications and guidelines, and standard building codes. The quality of repairs shall meet the applicable standards and shall prevent any malfunction reoccurrences caused by poor workmanship or other contractor inadequacies. The quality of the repaired areas shall be fully compatible with adjacent surfaces or equipment. Except where otherwise specified, replacements shall match existing in dimensions, finish, color, design, and functionality and shall have an appearance similar to the original finished appearance with only minor unobjectionable deterioration resulting from normal use.

The Contractor shall not allow debris to spread unnecessarily into adjacent areas nor accumulate in the work area. All such debris, excess material, and parts shall be cleaned up and removed at the completion of the job and at the end of each day work is in progress. Upon completion of work, any stains and other unsightly marks shall be removed.

2.3.2 Historical

Preservation

Buildings and facilities designated as historical sites shall be maintained in accordance with Federal, state, and local historical policies and regulations.

2.3.3 Business Permits The Prime Contractor and/or Sub-contractor shall have business permits of specific construction permit (Tokutei-Kensetsu-Gyou) or common construction permit (Ittupan- Kensetsu-Gyou), under GOJ construction industry law article 3, section 1 (Dai-3-jou, Dai-1-kou) for proper to contract with maintenance repair and replacement services, and disposal of generated industrial waste, under this contract.

The Contractor's specific construction permit or common construction permit shall include the following minimum required types of construction work.

• Machine appliance setting construction business

• Steel structure construction (Kou-Kouzoubutsu-Kouji)

• Paving work (Hosou-Kouji)

• Sheet metal work (Bankin-Kouji)

• Paint work (Tosou-Kouji)

• Telecommunications work (Denki-Tsuushinn-Kouji)

• Water supply facility work (Suidou-Shisetsu-Kouji)

• Construction work (Kenchiku-Kouji)

• Electrical construction (Denki-Kouji)

• General construction business (Ittspan-Kenchiku-Kouji)

• Plumbing work (Kan-Kouji)

• Scaffolding, Earthwork and Concrete work (Tobi-Dokou, Konkurihto-

Kouji)

The copy of specified permits above shall be submitted per Section F, for proof of prime Contractor and/or Sub-contractor ownership.

2.4 References and

Technical Documents

References and Technical Documents are listed in J-1502000-02.

Spec Item Title Performance

Objective Related Information Performance

Standard 3 Recurring Work The Contractor shall maintain, repair, and alter HVAC systems and Refrigeration Systems, and Icemaker Systems to ensure they are fully functional and in normal working condition.

The Contractor shall develop, implement, and execute an Emergency, Urgent, and Routine (E/U/R) Work, Maintenance Program, Inspection, Testing, and Certification Program, and Other Recurring Service Program to maintain and repair HVAC systems and refrigeration stems, and icemaker systems.

The Contractor shall provide all necessary test instruments, equipment, and tools required to perform maintenance and repair.

Building map is provided in J- 1502000-03.

HVAC systems and Refrigeration Systems, and Icemaker Systems are in normal working condition and function properly in accordance with specified standards.

3.1 Emergency, Urgent, and Routine (E/U/R) Work

The Contractor shall perform service order work in a timely manner and ensure HVAC systems and Refrigeration Systems, and Icemaker Systems are restored to a safe, in normal working condition and function properly.

The Contractor shall receive E/U/R work in accordance with the work reception requirements in Annex 2.

The Contractor shall schedule and perform E/U/R work in a way that minimizes disruptions to customers and Government operations.

E/U/R work will include a wide variety of work. Samples of required work and historical E/U/R work order data is provided in J-1502000-04.

Historical E/U/R work data associated with contracts prior to this solicitation may present data that may not be representative of requirements specified. The Government makes no warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of the historical E/U/R work order data.

The Contractor shall maintain sufficient materials and equipment on hand to support

E/U/R work is responded to and completed within the specified time.

HVAC systems and Refrigeration Systems, and Icemaker Systems are fully functional, in normal working condition and function properly in accordance with OEM specifications, including recertification if applicable.

When a work order is complete the HVAC systems and Refrigeration Systems, and Icemaker Systems do not present danger to personnel or equipment.

Objective Related Information Performance

Standard E/U/R work requirements.

Lack of availability of material or equipment will not relieve the Contractor from the requirement to complete E/U/R work within the time limits specified.

The Government may combine multiple requirements received for the same facility, system, ground structure or other asset at the same time into one work order.

Unless otherwise specified, the Contractor has full responsibility for any work up to the work order limit of liability of ¥200,000 in direct labor and direct material cost per work order. The Government will only pay for the portion of direct labor and/or direct material that exceeds the E/U/R work order limits of liability.

The Contractor shall notify the KO and COR upon identification that the work order will exceed the specified limits of liability in accordance with reporting requirements in Annex 2. If a non-recurring work is issued for the portion exceeding the specified E/U/R work order limits of liability, the Government will only pay for the portion of direct labor and/or direct material that exceeds the work order limits.

Examples of work exceeding the E/U/R Work Order limits of liability:

• If a work order requires

¥210,000 in direct labor and direct material cost, the Government may issue a task order in accordance with the Non-recurring Work portion of the contract

Objective Related Information Performance

Standard for the ¥10,000 in direct labor and direct material cost that exceeds the work limit of liability.

The Contractor may invoice for completed E/U/R work orders.

The Contractor shall not invoice for incomplete work orders and work orders not issued. A modification will be processed at the end of each period of performance to deduct for work orders not issued and incomplete work orders. Deduction will be based on the unit prices specified in Attachment J- 0200000-13 ELINs.

The Contractor shall submit a monthly summary of completed E/U/R work order reports and per Section F.

The Contractor shall submit an accumulated summary list of completed E/U/R work orders and per Section F.

3.1.1 Emergency The Contractor shall

perform emergency work orders in a timely manner to ensure HVAC systems and Refrigeration Systems, and Icemaker Systems are fully functional, in normal working condition and function properly in accordance with specified standards.

The Contractor shall perform emergency work orders 24 hours a day, seven days a week throughout the contract period.

The Contractor shall respond to emergency work orders with the appropriate service personnel and equipment to commence work immediately.

The Contractor shall remain at the work site until the emergency has been arrested.

If follow-up work is required (after the emergency condition is arrested) to complete the restoration and ensure facilities, systems, ground structures and other assets are fully functional and in normal working condition, the Contractor may request time extension equal to

Emergency work orders responded to within one hour of receipt of call.

Work continues without interruption until emergent condition is arrested and damage to HVAC systems and Refrigeration Systems, and Icemaker Systems are mitigated.

Objective Related Information Performance

Standard a Routine Work Order. The emergency mitigation and follow-up work shall be considered part of the original work order.

Informational Note:

Historically, approximately two emergency work orders originate after normal working hours during four years.

3.1.2 Urgent The Contractor shall

perform urgent work orders in a timely manner to ensure HVAC systems and Refrigeration Systems, and Icemaker Systems are fully functional, in normal working condition and function properly in accordance with specified standards.

The Contractor shall perform urgent work orders without extended delay.

Urgent work orders are completed within five working days.

3.1.3 Routine The Contractor shall

perform routine work orders in a timely manner to ensure HVAC systems and Refrigeration Systems, and Icemaker Systems are restored to a safe, in normal working condition and function properly.

Performance of routine work orders is not required outside of Government regular working hours.

Routine work orders are completed within 30 calendar days.

3.2 Projects The Contractor shall

perform Project Work Orders in a timely manner to ensure requested work is complete in accordance with specified standards.

The Contractor shall receive Project Work Orders in accordance with the work reception requirements in Annex 02.

Project work will include a wide variety of work. Sample of historical Project Work Order data is provided in J- 1502000-05.

The Contractor shall schedule project work in a way that minimizes disruptions to Government operations.

Project order work responded to and completed within the 30 calendar days.

HVAC systems and Refrigeration Systems, and Icemaker Systems are fully functional, in normal working condition, and function properly in accordance with the specified, manufacturers’, workmanship and material standards, including recertification if applicable.

Objective Related Information Performance

Standard Project orders will be ordered to accomplish any work identified within the entire boundary of the installation, whether or not, HVAC systems and Refrigeration Systems, and Icemaker Systems are identified in Section J.

The Government may combine multiple requirements into one Project Work Order.

The Contractor shall maintain sufficient personnel, materials, and equipment on hand to support Project Work Order.

Lack of availability of personnel, material, or equipment will not relieve the Contractor from the requirement to complete Project Work Order within the time specified.

The Contractor shall submit a summary completion report of completed Project Work Orders per Section F.

When project order is complete the HVAC systems and refrigeration systems, and icemaker systems do not present danger to personnel or equipment.

3.2.1 Minor The Contractor shall

perform Project Work Orders in a timely manner to ensure requested work is complete in accordance with specified standards.

Minor Project Work Orders are limited to a maximum of ¥300,000 in direct labor and direct material cost per Project Work Order. Each Project Order shall be approved by the

KO.

Historical Project Work Order is estimated at 50 projects average per year.

When project order is complete the HVAC systems and refrigeration systems, and icemaker systems do not present danger to personnel or equipment.

3.2.2 Major The Contractor shall

perform Project Work Orders in a timely manner to ensure requested work is complete in accordance with specified standards.

Major Project Work Orders are limited to a maximum of ¥600,000 in direct labor and direct material cost per Project Work Order. Each Project Order shall be approved by the

KO.

Historical Project Work Order is estimated at 30 projects average per year.

When project order is complete the HVAC systems and refrigeration systems, and icemaker systems do not present danger to personnel or equipment.

Objective Related Information Performance

Standard

3.3 Preventive

Maintenance (PM) Program

The Contractor shall develop and implement a PM program for HVAC systems and Refrigeration Systems, and Icemaker Systems to ensure proper operation, to minimize breakdowns, and to maximize useful life.

The Contractor shall develop and submit a PM program by each building system per Section F. At a minimum, the PM program shall include:

• PM management and technical approach

• Procedures to evaluate equipment reliability and corrective actions.

• Job plans tailored to the OEM technical documentation.

• Qualification requirements of the maintenance personnel.

The Contractor is fully responsible for and shall perform any incidental repairs, including replacement, discovered during scheduled maintenance work up to a total of ¥300,000 per occurrence in direct labor and direct material cost under the recurring work portion of the Contract.

Incidental repairs performed under maintenance are not considered E/U/R work

Notification of repair work exceeding the incidental repairs limit shall be submitted to the KO within two hours of identification. The Government may issue E/U/R work or non-recurring work for the portion of the repairs exceeding the incidental repairs limit. The Government will only pay for the portion of direct labor and/or direct material that exceeds the specified limits of liability.

Example: If an individual occurrence of incidental repair requires ¥310,000 in direct labor and/or direct material cost, the Government may issue E/U/R work or non-recurring work in accordance with the

Maintenance is accomplished in accordance with the Contractor’s PM program and work schedule.

PM is performed in accordance with manufacturers’ recommended procedures and OEM standards.

Objective Related Information Performance

Standard non-recurring work provisions of the contract for the ¥10,000 in direct labor and/or direct material cost that exceeds the specified incidental repair limit of liability.

The Contractor shall not use breakdown maintenance as part of the PM program.

The PM program shall provide an economical approach manufacturers’ recommended procedures, OEM standards, and maintenance required to satisfy equipment warranties and keep f HVAC systems and Icemaker Systems in normal working condition.

Excessive or repeated system or equipment breakdowns or deficiencies may indicate the need to adjust or modify the Contractor’s PM program.

These changes will be made at no additional cost to the Government.

The Contractor shall submit a monthly PM work schedule by each building system per Section F.

The Contractor shall submit a monthly summary of completed PM work report by each building system per Section F.

The Contractor shall submit actual monthly workload under the limit of liability by each system per Section F.

The Contractor shall submit accumulated workload under the limit of liability by each system per Section F.

3.3.1 HVAC and

Refrigeration Systems

The Contractor shall maintain HVAC and refrigeration systems

Temperature setting for HVAC and refrigeration systems are provided in J-1502000-06.

Conditioned spaces are continuously maintained at the

Objective Related Information Performance

Standard to ensure proper operation, to minimize breakdowns, and to maximize useful life.

Descriptions for HVAC and refrigeration systems are provided in J-1502000-07.

The reference PM work requirements for HVAC and refrigeration systems are provided in J-1502000-08.

The site plans for HVAC and refrigeration systems are provided in J-1502000-09.

The Contractor shall not vent or otherwise dispose of any ozone-depleting substances in a manner that will permit its release into the environment.

Refrigerants shall be captured and recycled per Annex 02 ODS Requirements for Refrigerant Recycling.

temperature(s) specified.

Air quality in conditioned space meet EPA and ASHREA air quality standards.

HVAC and refrigeration systems comply with environmental regulations.

3.3.2 Icemaker

Systems

The Contractor shall maintain icemaker systems to ensure proper operation, to minimize breakdowns, and to maximize useful life.

PM work shall be performed in accordance with OEM maintenance manual and recommended procedure.

Descriptions for icemaker systems are provided in J- 1502000-10.

The reference PM work requirements for Icemaker Systems are provided in J- 1502000-11.

The site plans for icemaker systems are provided in J- 1502000-12.

Maintenance is performed in accordance with Contractor's PM program and work schedule.

Spec Item Title Performance Objective Related Information Performance

Standard 4 Non-Recurring

Work Non-recurring work may be ordered utilizing DoD FEDMALL in accordance with Section H or on a task order in accordance with the

PROCEDURES FOR

ISSUING ORDERS clause in Section G. The order will specify the exact locations and types of work to be accomplished. The period of performance will be specified in each order.

Refer to non-recurring work ELINs for task listings, descriptions and related requirements. All periods of performance are measured from issue date of order to acceptance of the work. Performance Standards for non-recurring work will be the same as those in Spec Item 3 where applicable.

Attachment J-1502000-07 Systems Descriptions for HVAC and Refrigeration Systems

CNIC FUNDING PORTION

1. NDK-100134:

Mechanical Equipment:

I.D No. TYPE MODEL No. MANUFACTURER LOCATION QTY AC-1W Air Cooled Heat Pump Unit SHYGJ80G Daikin Co., Ltd 1st FL Office 1 AC-1E Air Cooled Heat Pump Unit SZRG80BV Daikin Co., Ltd 1st FL Office 1 AC-2 Air Cooled Heat Pump Unit SZRG56BV Daikin Co., Ltd 1st FL Break RM 2 AC-3 Air Cooled Heat Pump Unit SYA56CAV Daikin Co., Ltd 1st FL Office 1 EH-1 Panel Heater PXS-750 Inter Central Co., Ltd 1st FL Toilet 2 SF-1 Supply Air Duct Fan JF-30CSD Mitsubishi Denki Co., Ltd 1st FL Fire Hydrant Pump

RM

SF-2 Supply Air Duct Fan JF-40FTD Mitsubishi Denki Co., Ltd 1st FL Electric RM 1 SF-3 Supply Air Sirocco Fan EG-60ETB Mitsubishi Denki Co., Ltd 1st FL Storage RM 4 SF-4 Supply Air Sirocco Fan BFS-45KT-50 Mitsubishi Denki Co., Ltd 1st FL Storage RM 2 SF-5 Supply Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 2nd FL Storage RM 8 SF-6 Supply Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 2nd FL Storage RM 4 SF-7 Supply Air Static Pressure Fan EG-60ETB (7 EA)

Mitsubishi Denki Co., Ltd 3rd FL Storage RM 7

EG-60ETA-Q (1 EA) 1

SF-8 Supply Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 3rd FL Storage RM 4

SF-9W Supply Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd RF FL Elevator Machine

RM

SF-9E Supply Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd RF FL Elevator Machine

RM

SF-10 Supply Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd RF FL Elevator Machine

RM

EF-1 Exhaust Duct Fan JF-30CSD Mitsubishi Denki Co., Ltd 1st FL Fire Hydrant Pump

RM

EF-2 Exhaust Duct Fan JF-40FTD Mitsubishi Denki Co., Ltd 1st FL Electric RM 1 EF-3 Exhaust Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 1st FL Storage RM 8 EF-4 Exhaust Air Static Pressure Fan JF-50GTD Mitsubishi Denki Co., Ltd 1st FL Storage RM 2 EF-5 Exhaust Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 1st FL Storage RM 8 EF-6 Exhaust Duct Fan JF-50GTD Mitsubishi Denki Co., Ltd 2ND FL Storage RM 2 EF-7 Exhaust Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 3rd FL Storage RM 8 EF-8 Exhaust Air Static Pressure Fan EG-60ETB Mitsubishi Denki Co., Ltd 3rd FL Storage RM 2

EF-9 Exhaust Air Static Pressure Fan EG-60ETB w/ Thermos Switch (FS-10B)

Mitsubishi Denki Co., Ltd Roof FL Elevator Machine

RM

EF-10 Exhaust Air Static Pressure Fan EG-60ETB w/ Thermos Switch (FS-10B)

Mitsubishi Denki Co., Ltd Roof FL Elevator Machine

RM

EF-11 Exhaust Ceiling Mounted Fan VD-18ZB4 Mitsubishi Denki Co., Ltd Janitor’s CloLS at 1st, 2nd and 3rd FL

EF-12 Exhaust Ceiling Mounted Fan VD-10Z4 Mitsubishi Denki Co., Ltd 1st FL Hot Water Heater

RM

EF-13 Exhaust Ceiling Mounted Fan VD-10Z4 Mitsubishi Denki Co., Ltd 1st FL Shower RM 2 EF-14 Exhaust Ceiling Mounted Fan VD-15ZP4 Mitsubishi Denki Co., Ltd 1st FL Toilet RM 2 EF-15 Range Hood Fan VL-60 Takara Standard Co., Ltd 1st FL Kitchen 2 EF-16 Exhaust Sirocco PVC Fan #3POSV-RHCT Hitachi Co., Ltd 2nd FL Battery RM 2 EF-17 Exhaust Ceiling Mounted Fan VD-18ZB4 Mitsubishi Denki Co., Ltd 1st FL Office 1 HF-1 Heat Recovery Ventilation Fan LGH-35CST Mitsubishi Denki Co., Ltd 1st FL Office 2 HF-2 Heat Recovery Ventilation Fan LGH-25CST Mitsubishi Denki Co., Ltd 1st FL Office 2

2. NDK-100137

ID No. Name Specification Model No. Serial No/ OEM QTY

RC-1-1

RC-1-2

Freezing Unit w/ Condensing Unit (Freezing Unit Integrated type)

40,850 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

ECOV-D150MA-

BSG

2XW00131 Mitsubishi Electric Co., Ltd

RC-1-3 Unit Cooler Blade Fin Tube Type, 120m³ / h 3Phase, 200V, 0.78kw

UCH-D15VNA 2ZW02139

2ZW02176

Mitsubishi Electric Co., Ltd

RC-2-1

RC-2-2

Freezing Unit w/ Condensing Unit (Freezing Unit Integrated type)

40,850 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

ECOV-D150MA-

BSG

2XW00130 Mitsubishi Electric

RC-2-3 Unit Cooler Blade Fin Tube Type, 120m³ / h 3Phase, 200V, 0.78kw

UCH-D15VNA 2ZW02140

2ZW02177

RC-3-1 Freezing Unit 67,800 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN260A1 26W00488 Mitsubishi Electric Co., Ltd

RC-3-2 Condensing Unit Refrigerant: R410A, Fan: Ø 400 Power: 1Phase, 200V, 50Hz, 7.2A Air Volume: 308m3/min

RM-N165A-BSG 12W00160

26W00210

Mitsubishi Electric Co., Ltd

RC-3-3 Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz, 23.5kW Air Volume: 241m3/min

UCL-D15VHA 25W01501

25W01491 25W01498

RC-4-1 Freezing Unit 67,800 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN260A1 24W00472 Mitsubishi Electric Co., Ltd

RC-4-2 Condensing Unit Refrigerant: R410A, Fan: Ø 400 Power: 1Phase, 200V, 50Hz, 7.2A Air Volume: 308m3/min

RM-N165A-BSG 26W00199

26W00196

Mitsubishi Electric Co., Ltd

RC-4-3 Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz, 23.5kW Air Volume: 241m3/min

UCL-D15VHA 25W01496

2XW01650

2XW01651

Mitsubishi Electric

RC-5-1 Freezing Unit 67,800 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN260A1 26W00489 Mitsubishi Electric Co., Ltd

RC-5-2 Condensing Unit Refrigerant: R410A, Fan: Ø 400 Power: 1Phase, 200V, 50Hz, 7.2A Air Volume: 308m3/min

RM-N165A-BSG 26W00198

1YW00148

Mitsubishi Electric Co., Ltd

RC-5-3 Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz, 23.5kW Air Volume: 241m3/min

UCL-D15VHA 25W01495

2XW01652

25W01497

Mitsubishi Electric Co., Ltd

RC-6-1 Freezing Unit 4,085 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN45DCA 28W00744 Mitsubishi Electric Co., Ltd

RC-6-2 Condensing Unit Refrigerant: R410A, Fan: Ø 490 Power: 1Phase, 200V, 50Hz, 2.4A Air Volume: 308m3/min

RM-N55A-BSG 2ZW00031 Mitsubishi Electric Co., Ltd

RC-6-3 Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz,15.9kW Air Volume: 175m3/min

UCL-D10VHA 2ZW02140 Mitsubishi Electric Co., Ltd

RC-7-1 Freezing Unit 67,800 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN260A1 24W00477 Mitsubishi Electric

RC-7-2 Condensing Unit Refrigerant: R410A, Fan: Ø 400 Power: 1Phase, 200V, 50Hz, 7.2A Air Volume: 308m3/min

RM-N165A-BSG 26W00195

26W00205

Mitsubishi Electric Co., Ltd

RC-7-3 Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz, 23.5kW Air Volume: 241m3/min

UCL-D15VHA 2ZW01184

2ZW01212

Mitsubishi Electric Co., Ltd

RC-8-1 Freezing Unit 67,800 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN260A1 26W00485 Mitsubishi Electric Co., Ltd

RC-8-2 Condensing Unit Refrigerant: R410A, Fan: Ø 400 Power: 1Phase, 200V, 50Hz, 7.2A Air Volume: 308m3/min

RM-N165A-BSG 26W00209

26W00200

Mitsubishi Electric Co., Ltd

RC-8-3 Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz, 23.5kW Air Volume: 241m3/min

UCL-D15VHA 28W01098

2ZW01215

Mitsubishi Electric Co., Ltd

RC-9-1 Freezing Unit 4,085 kcal / h, R410A, Connecting Center Monitoring System 3Phase, 200V, 50Hz

• Spring Isolation Vibration Pad

• Solenoid Valve

• Electric Expansion Valve

• Capillary Tube

ECV-EN45DCA 28W00743 Mitsubishi Electric Co., Ltd

RC-9-2 Condensing Unit Refrigerant: R410A, Fan: Ø 490 Power: 1Phase, 200V, 50Hz, 2.4A Air Volume: 308m3/min

RM-N55A-BSG 2ZW00030 Mitsubishi Electric Co., Ltd

RC-9-3

Unit Cooler Refrigerant: R410A, Fan: Ø 400 Power: 3Phase, 200V, 50Hz,15.9kW Air Volume: 175m3/min

UCL-D10VHA 2ZW02139 Mitsubishi Electric

AC-1 Air Curtain Static Pressure Type, Size: 1,000 m / m, 3Ø, 200V, 0.12kw

MK-3512T Mitsubishi Electric Co., Ltd

AC-2 Air Curtain Static Pressure Type, Size: 1,200 m / m, 3Ø, 200V, 0.21kw

MK-3575T Mitsubishi Electric Co., Ltd

AC-2 Air Curtain Static Pressure Type, Size: 750 m / m, 3Ø, 200V, 0.1kw

MK-3510T Mitsubishi Electric

Center Monitoring System:

ID No. Name Specification Model No. Serial No/ OEM QTY N/W

Central Monitoring System

Unknown AE200J Unknown

3. YSK-5229:

ID No. Name Specification Model No. Serial No/ OEM QTY AC-01 Air Cooled Heat Pump

Unit (Outside Unit)

Cooling Capacity: 2.5kw Heating Capacity: 2.8kw 1Ø, 100V, 50Hz

R25LESE2 COOO220 Daikin Co., Ltd. 1

Inside Unit F25LTES-W C503120 1

4. YSK-2046:

ID No. Name Specification Model No. Serial No/ OEM QTY RA-1 Absorption Cooling

Chiller Unit

310RT

Accessary:

• Control Valve

• Three (3) Way Motor Valve

MDS-31B Mitsubishi Jukou Co., Ltd.

CT-1 Cooling Tower

(RF)

Double Effect Absorption Type, Low Noise, Anti Harvey Corrosive Salt

• Cooling Capacity: 1,520,000 kcal/h

SDW-U250ASC 515552C Ebara Shinwa Co., Ltd.

• Cater Capacity: 4,610 L/min

• 3Ǿ, 200V, 5.5kw x 2, 50Hz.

PCD-1 Cooling Water (CW) Pump

(1FL MECH RM)

Single Suction Centrifugal Type,

• 150A, 4,610 L/min, 26m, 3 Ǿ, 200V, 50Hz, 37kw.

• Spring Vibration Isolation Pad

Note: Interlocking with RA-1

150x125FS4L-537 Ebara Co., Ltd 1

PC-1 Child Water Pump

(1FL MECH RM)

Single Suction Centrifugal Type,

• 100A, 1,375 L/min, 15m, 3 Ǿ, 200V, 50Hz, 7.5kw.

Note: Interlocking with RA-1

100x80FS4-J57.5 Ebara Co., Ltd 2

PH-1 Hot Water (HW) Pump (1FL

MECH RM)

Single Suction Centrifugal Type, Automatic Alternating Operation

• 100A, 1,530 L/min, 12m, 3 Ǿ, 200V, 50Hz, 7.5kw.

Note: Interlocking with Relay-1

125x100FS4J-57.5 Ebara Co., Ltd 1

ACP-1 Air Cooled (A/C) Heat Pump Outside Unit

Multi-Operation Type, Anti Harvey Corrosive Salt

• Cooling Capacity: 23.9kw

• Heating Capacity: 19.9kw

RXYP280FCH A000227 Daikin Kogyo Co., Ltd. 1

ACP-1A

Rm101

Air Cooled (A/C) Heat Pump Inside Unit

(RM101)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 2.2kw,

• Heating Capacity: 2.9kw

• Power: 1Ø, 200V, 0.015kw, 50Hz With Control Switch

FXYCP28EB E006379 Daikin Kogyo Co., Ltd. 1

ACP-1B

Rm103

Air Cooled (A/C) Heat Pump Inside Unit

(RM103)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 2.3kw, FXYCP28EB E005460 Daikin Kogyo Co., Ltd. 1

• Heating Capacity: 1.5kw

• Power: 1Ø, 200V, 0.015kw, 50Hz With Control Switch

ACP-1C

Rm104

Air Cooled (A/C) Heat Pump Inside Unit

(RM104)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 1.4kw,

• Heating Capacity: 0.4kw

• Power: 1Ø, 200V, 0.01kw, 50Hz With Control Switch

FXYCP22EB E006941 Daikin Kogyo Co., Ltd. 1

ACP-1D

Rm105

Air Cooled (A/C) Heat Pump Inside Unit

(RM105)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 1.6kw,

• Heating Capacity: 1.3kw

• Power: 1Ø, 200V, 0.01kw, 50Hz With Control Switch

FXYCP22EB E006796 Daikin Kogyo Co., Ltd. 1

ACP-1E

Rm106

Air Cooled (A/C) Heat Pump Inside Unit

(RM106)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 2.9kw,

• Heating Capacity: 2.1kw

• Power: 1Ø, 200V, 0.015kw, 50Hz With Control Switch

FXYCP36EB E005861 Daikin Kogyo Co., Ltd. 1

ACP-1F

Rm107

Air Cooled (A/C) Heat Pump Inside Unit

(RM106)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 0.3kw,

• Heating Capacity: 0.2kw

• Power: 1Ø, 200V, 0.01kw, 50Hz With Control Switch

FXYCP22EB E006939 Daikin Kogyo Co., Ltd.

ACP-1G

Rm108

Air Cooled (A/C) Heat Pump Inside Unit

(RM108)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 0.4kw,

• Heating Capacity: 0.3kw

• Power: 1Ø, 200V, 0.01kw, 50Hz With Control Switch

FXYCP22EB E006985 Daikin Kogyo Co., Ltd. 1

ACP-1H

Rm111

Air Cooled (A/C) Heat Pump Inside Unit

(RM111)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 4.1kw,

• Heating Capacity: 3.8kw

• Power: 1Ø, 200V, 0.02kw, 50Hz With Control Switch

FXYCP45EB E006775 Daikin Kogyo Co., Ltd. 1

ACP-1I

Rm112

Air Cooled (A/C) Heat Pump Inside Unit

(RM112)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 1.6kw,

• Heating Capacity: 1.1kw

• Power: 1Ø, 200V, 0.01kw, 50Hz With Control Switch

FXYCP22EB E006801 Daikin Kogyo Co., Ltd. 1

ACP-2 Air Cooled (A/C) Heat Pump Outside Unit

Multi-Operation Type, Anti Harvey Corrosive Salt

• Cooling Capacity: 8.2kw

• Heating Capacity: 18.5kw

RXYP160DDH A000119 Daikin Kogyo Co., Ltd. 1

ACP-2A Air Cooled (A/C) Heat Pump Inside Unit

(RM306)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 3.1kw,

• Heating Capacity: 5.7kw

• Power: 1Ø, 200V, 0.02kw, 50Hz With Control Switch

FXYCP56EB E006894

E006728

Daikin Kogyo Co., Ltd. 2

ACP-2B Air Cooled (A/C) Heat Pump Inside Unit

(RM503)

Ceiling CasLSte Type, Two (2) Way Blow, Built in Drain-up Pump

• Cooling Capacity: 3.6kw,

• Heating Capacity: 4.1kw

• Power: 1Ø, 200V, 0.02kw, 50Hz With Control Switch

MPL-RP50LA 74W00868 Mitsubishi Denki 1

ACP-3 Air Cooled (A/C) Heat Pump Outside Unit (RM301, Computer

RM)

All Year Cooling Type, Built-in Electric Heater, Anti Harvey Corrosive Salt

• Cooling Capacity: 15.2kw

• Heating Capacity: 3.2kw

• Air Blow Capacity: 4,080m³/h

CRP224AAKH A000290

A000292

Daikin Kogyo Co., Ltd.

• Outside Unit: 3Ø, 200V, 5.5kw, 50Hz

Note: One (1) unit is spare.

Air Cooled (A/C) Heat Pump Inside Unit

Floor Mounted Type,

• Inside Unit: 3Ø, 200V, 0.75kw, 50Hz

• Electric Heater: 3Ø, 200V, 0.34kw, 50Hz

FRP224BK A000379

A000382

ACP-4 Air Cooled (A/C) Heat Pump Outside Unit (RM302, Computer

RM)

All Year Cooling Type, Built-in Electric Heater, Anti Harvey Corrosive Salt

• Cooling Capacity: 10.0kw

• Heating Capacity: 1.7kw

• Air Blow Capacity: 2,880m³/h

• Outside Unit: 3Ø, 200V, 7.5kw x 2, CRP224AAKH A000274

A000294

Daikin Kogyo Co., Ltd. 2

Air Cooled (A/C) Heat Pump Inside Unit

Floor Mounted Type,

• Inside Unit: 3Ø, 200V, 0.75kw, 50Hz

• Electric Heater: 3Ø, 200V, 1.7kw, 50Hz

FRP224BK A000383

A000384

ACP-5 Air Cooled (A/C) Heat Pump Outside Unit (RM401, Computer

RM)

All Year Cooling Type, Built-in Electric Heater, Anti Harvey Corrosive Salt

• Cooling Capacity: 49.6kw

• Heating Capacity: 5.0kw

• Air Blow Capacity: 8,100m³/h

• Outside Unit: 3Ø, 200V, 7.5kw x 2, No.1

CRP300AAKH

No.2

CRJ300AAKH

No.3

CRP300AAKH

No.1 A000374 A000376 No.2 A000380 A000386 No.3 A000382 A000375

Daikin Kogyo Co., Ltd. 3

Heat Pump Inside Unit

Floor Mounted Type,

• Inside Unit: 3Ø, 200V, 0.75kw, 50Hz

• Electric Heater: 3Ø, 200V, 1.7kw, 50Hz

FRP600BK A000698

A000699 A000

RF-1 Return Fan

(1FL MECH RM)

Single Suction Sirocco Type, Ceiling Hanging

• #3, 14,850m³/h, 31mmAq, 755rpm.

• 3Ø, 200V, 5.5kw, 50Hz With Spring Vibration Isolation Pad and Earth Quake Proof Steel Fame

Note: Interlocking with AHU-1

No3 ½ -SRM3 PX781555 Ebara Co. Ltd. 3

RF-2 Return Fan

(3FL MECH RM)

Single Suction Sirocco Type, Ceiling Hanging

• #3, 8,590m³/h, 30mmAq, 800rpm.

• 3Ø, 200V, 2.2kw, 50Hz With Spring Vibration Isolation Pad and Earth Quake Proof Steel Fame

Note: Interlocking with AHU-5

No3-SRM3 PY714026 Ebara Co. Ltd. 1

FCV-2-13 Fan Convector (RM- 109)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,380kcal

• 1Ø, 100V, 41w, 50Hz

DSRD-21W Showa Tekkou Co., Ltd.

FCV-2-1 Fan Convector

(RM-110)

Ceiling Mounted Type, Hot Water, Right Connecting

• Heating Capacity: 1,020kcal

• 1Ø, 100V, 41w, 50Hz

DSRD-21W Showa Tekkou Co., Ltd.

FCV-2-2 Fan Convector

(RM-113)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,140kcal

• 1Ø, 100V, 41w, 50Hz

DSRD-21W Showa Tekkou Co., Ltd.

FCV-2-3 Fan Convector

(RM-117)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,180kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 31WK Showa Tekkou Co., Ltd.

FCV-3-2 Fan Convector

(RM-118)

Ceiling Mounted Type, Hot Water, Left DSR-D 31WK Showa Tekkou Co., Connecting

• Heating Capacity: 1,780kcal

• 1Ø, 100V, 41w, 50Hz

FCV-2-4 Fan Convector (1FL HW Supply

RM)

Ceiling Mounted Type, Hot Water, Right Connecting

• Heating Capacity: 1,190kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WT Showa Tekkou Co., Ltd.

FCV-3-3 Fan Convector

(RM-212)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,840kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 31WK Showa Tekkou Co., Ltd.

FCV-2-5 Fan Convector

(RM-222)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,540kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

FCV-2-6 Fan Convector (2FL HW Supply

RM)

Ceiling Mounted Type, Hot Water, Right Connecting

• Heating Capacity: 1,090kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

FCV-2-7 Fan Convector

(RM-304)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 800kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

FCV-3-4 Fan Convector

(RM-309)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,850kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 31WK Showa Tekkou Co., Ltd.

FCV-2-8 Fan Convector (3FL HW Supply

RM)

Ceiling Mounted Type, Hot Water, Right Connecting

• Heating Capacity: 1,090kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

FCV-4-1 Fan Convector

(RM-407)

Ceiling Mounted Type, Hot Water, Left Connecting

DSR-D 41WK Showa Tekkou Co.,

• Heating Capacity: 2,830kcal

• 1Ø, 100V, 82w, 50Hz

FCV-2-9 Fan Convector

(RM-409)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,460kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., FCV-2-10 Fan Convector (4FL HW Supply

RM)

Ceiling Mounted Type, Hot Water, Right Connecting

• Heating Capacity: 1,090kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

FCV-2-11 Fan Convector

(RM-506)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 1,420kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 31WK Showa Tekkou Co., Ltd.

FCV-3-5 Fan Convector

(RM-507)

Ceiling Mounted Type, Hot Water, Left Connecting

• Heating Capacity: 2,240kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

FCV-2-12 Fan Convector (5FL HW Supply

RM)

Ceiling Mounted Type, Hot Water, Right Connecting

• Heating Capacity: 1,140kcal

• 1Ø, 100V, 41w, 50Hz

DSR-D 21WK Showa Tekkou Co., Ltd.

CW-1 Convector (1FL Women Bath

RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 2,030kcal

CW-1 9903-602 Showa Tekkou Co., Ltd.

CW-2 Convector (1FL Men Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,630kcal

CW-2 9903-602 Showa Tekkou Co., Ltd.

CW-5 Convector (2FL Student Men Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,630kcal

CW-5 9903-602 Showa Tekkou Co., Ltd.

CW-6 Convector (2FL Women Bath

RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,840kcal

CW-6 9903-602 Showa Tekkou Co., CW-9 Convector (2FL Men Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,480kcal

CW-9 9903-602 Showa Tekkou Co., Ltd.

CW-10 Convector (3FL Women Bath

RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,840kcal

CW-10 9903-602 Showa Tekkou Co., Ltd.

CW-11 Convector (3FL Men Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,480kcal

CW-11 Showa Tekkou Co., Ltd.

CW-14 Convector (4FL Women Bath

RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,840kcal

CW-14 9903-602 Showa Tekkou Co., Ltd.

CW-15 Convector (4FL Men Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,480kcal

CW-15 Showa Tekkou Co., Ltd.

CW-18 Convector (5FL Women Bath

RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,990kcal

CW-18 Showa Tekkou Co., Ltd.

CW-19 Convector (5FL Men Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 1,620kcal

CW-19 Showa Tekkou Co., Ltd.

PW-1 Panel Heater (5FL HW Supply

RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 720kcal

• 1Ø, 200V, 1.0kw, 50Hz

81-17641 447185 Tokyo Denki Kogyo Co., Ltd.

PW-2 Panel Heater (5FL Bath RM)

Wall Mounted Type, Hot Water

• Heating Capacity: 720kcal

• 1Ø, 200V, 1.0kw, 50Hz

81-17641 447185 Tokyo Denki Kogyo Co., Ltd.

HEA-1 Ventilation Fan (RM- 101)

Ceiling CasLSte Type,

• 60m³/h, 6mmAq

• 1Ǿ, 100V, 46w, 50Hz With Control Switch (P-100SL)

VL-140ZS 9901 Mitsubishi Denki Co., Ltd.

HEA-2 Ventilation Fan

(RM-103)

Ceiling CasLSte Type,

• 90m³/h, 3mmAq

• 1Ǿ, 100V, 42w, 50Hz With

• Control Switch: P-100SL

VL-160ZS 9711 Mitsubishi Denki Co.,

• Deep Hood (SUS) with Grill: PZ-

10VS2

HEA-3 Ventilation Fan

(RM-104)

Ceiling CasLSte Type,

• 90m³/h, 3mmAq

• 1Ǿ, 100V, 42w, 50Hz With

• Control Switch: P-100SL

• Deep Hood (SUS) with Grill: PZ-

10VS2

VL-120Z 9810 Mitsubishi Denki Co., Ltd.

HEA-4 Ventilation Fan

(RM-105)

Ceiling CasLSte Type,

• 60m³/h, 3mmAq

• 1Ǿ, 100V, 42w, 50Hz With

• Control Switch: P-100SL

• Deep Hood (SUS) with Grill: PZ-

10VS2

VL-140ZS 9901 Mitsubishi Denki Co., Ltd.

HEA-5 Ventilation Fan

(RM-106)

Ceiling CasLSte Type,

• 240m³/h, 5mmAq

• 1Ǿ, 100V, 156w, 50Hz With

• Control Switch: PZ-05SLB2

• Interior Panel: PZ235CP3

LGH-35CS2 9812 Mitsubishi Denki Co., Ltd.

HEA-6 Ventilation Fan

(RM-107)

Ceiling CasLSte Type,

• 30m³/h, 3mmAq

• 1Ǿ, 100V, 42w, 50Hz With

• Control Switch: P-100SL

• Deep Hood (SUS) with Grill: PZ-

10VS2

VL-120Z 9810 Mitsubishi Denki Co., Ltd.

HEA-7 Ventilation Fan

(RM-108)

Ceiling CasLSte Type,

• 30m³/h, 5mmAq

• 1Ǿ, 100V, 42w, 50Hz With Control Switch (P-100SL)

VL-120Z 9812 Mitsubishi Denki Co., HEA-8 Ventilation Fan

(RM-111)

Ceiling CasLSte Type,

• 120m³/h, 4mmAq

• 1Ǿ, 100V, 97w, 50Hz With

• Control Switch: PZ-05SLB2

• Interior Panel: PZ15CP3

LGH-15CS2 9812 Mitsubishi Denki Co., Ltd.

HEA-9 Ventilation Fan

(RM-113)

Ceiling CasLSte Type,

• 30m³/h, 3mmAq

• 1Ǿ, 100V, 42w, 50Hz With Control Switch (P-100SL)

VL-120Z 9812 Mitsubishi Denki Co., Ltd.

HEA-11 Ventilation Fan

(RM-301 & 302)

Ceiling CasLSte Type,

• 120m³/h, 4mmAq

• 1Ǿ, 100V, 97w, 50Hz With

• Control Switch: PZ-05SLB2

• Interior Panel: PZ15CP3

• Deep Hood (SUS) with Grill: PZ- 15VS2 x 2EA

LGH-15CS2 9901

Mitsubishi Denki Co., Ltd.

HEA-12 Ventilation Fan

(RM-306)

Ceiling CasLSte Type,

• 150m³/h, 5mmAq

• 1Ǿ, 100V, 119w, 50Hz With

• Control Switch: PZ-05SLB2

• Interior Panel: PZ15CP3

• Deep Hood (SUS) with Grill: PZ-

15VS2

LGH-25RS2 9901 Mitsubishi Denki Co., Ltd.

HEA-13 Ventilation Fan

(RM-401)

Ceiling CasLSte Type,

• 60m³/h, 2mmAq

• 1Ǿ, 100V, 42w, 50Hz With

• Control Switch: P-100SL

• Deep Hood (SUS) with Grill: PZ-

VL-120Z 9904

Mitsubishi Denki Co., 10VS2

HEA-14 Ventilation Fan

(RM-503, 501C &

501A)

Ceiling CasLSte Type,

• 60m³/h, 2mmAq

• 1Ǿ, 100V, 42w, 50Hz With

• Control Switch: P-100SL

• Deep Hood (SUS) with Grill: PZ-

10VS2

VL-120Z Mitsubishi Denki Co., Ltd.

FS-1 Supply Air Fan

(1FL MECH RM)

Single Suction Sirocco Type, Ceiling Hanging Type

• #3, 7,000m³/h, 18mmAq, 585rpm.

• 3Ǿ, 200V, 1.5kw, 50Hz With Spring Vibration Isolation Pad and Earth Quake Proof Steel Fame Note: Thermostat Operation

No3-SRM3 P14714484 Ebara Co. Ltd. 1

FS-2 Supply Air Fan

(1FL ELECT RM)

Single Suction Sirocco Type, Ceiling Hanging Type

• #4½, 17,100m³/h, 11mmAq, 355rpm.

• 3Ǿ, 200V, 2.2kw, 50Hz With Spring Vibration Isolation Pad and Earth Quake Proof Steel Fame Note: Thermostat Operation

No4½-SRM3 PX781557 Ebara Co. Ltd. 1

FS-3 Supply Air Fan

(1~ 5FL ELECT RM)

Straight Sirocco Type, Ceiling Hanging Type

• #1¼, 400³/h, 5mmAq

• 1Ǿ, 100V, 57w, 50Hz With Deep Hood (SUS) with Grill: PZ-

20VS2

Note: Thermostat Operation

BFS-40S 1F 9903

2F 9902 3F 9901 4F 9903 5F 9903

Mitsubishi Denki Co., Ltd.

FS-4 Supply Air Fan

(EV MECH RM)

Static Pressure Propeller Type, Wall Mounted

• 350 Dia., 820³/h, 5mmAq

• 1Ǿ, 100V, 100w, 50Hz

EWF-35CSA-Q 1902 Mitsubishi Denki Co., With

• Electric Shutter: PS-35SM

• Safety Guard: G-35EB

• SUS Weather Hood: W-50SL

FE-1 Exhaust Air Fan

(1FL MECH RM)

Static Pressure Propeller Type, Wall Mounted

• 350 Dia., 820³/h, 5mmAq

• 1Ǿ, 100V, 100w, 50Hz With

• Electric Shutter: PS-40SMT

• Safety Guard: G-40EB Note: Interlocking with FS-1

EF-40ETB22 8901 Mitsubishi Denki Co., Ltd.

FE-2 Exhaust Air Fan

(1FL MECH RM)

Single Suction Sirocco Type, Ceiling Hanging

• #4, 17,100³/h, 21mmAq, 575rpm.

• 3Ǿ, 200V, 5.5kw, 50Hz With Spring Vibration Isolation Pad and Earth Quake Proof Steel Fame Note: Interlocking with FS-2

No4-SRM3 PX781558 Ebara Co. Ltd. 1

FE-3 Exhaust Air Fan

(1~ 5FL ELECT RM)

Static Pressure Propeller Type, Wall Mounted

• 250 Dia., 400³/h, 4mmAq

• 1Ǿ, 100V, 25w, 50Hz With

• Electric Shutter: PS-25SM

• Safety Guard: G-25EB

• SUS Weather Hood: W-35SL

• Bard Screen: LB-35

EF-25ASB14 1F 9904

2F 9903 3F 9901 4F 9904 5F 9903

Mitsubishi Denki Co., Ltd.

FE-4 Exhaust Air Fan

(1~ 5FL MECH T

RM)

Static Pressure Propeller Type, Wall Mounted

• 350 Dia., 1,500³/h, 5mmAq

• 3Ǿ, 200V, 1.0kw, 50Hz With

EF-35CTB07 1F 9903

2F 9901 3F 9904 4F 9903 5F 9904

Mitsubishi Denki Co.,

• Electric Shutter: PS-35SMT

• Safety Guard: G-35EB

• SUS Weather Hood: W-50SL

• Bard Screen: LB-50

FE-5 Exhaust Air Fan (1~ 5FL Women Bath

RM)

Straight Sirocco Type, Ceiling Hanging

• #1¼, 570³/h, 7mmAq

• 1Ǿ, 100V, 65w, 50Hz With Deep Hood (SUS) with Grill: PZ-

20VS2

BFS-65S

5F BFS-50S

1F 9811 2F 9902 3F Unknown 4F 9902 5F 9903

Mitsubishi Denki Co., Ltd.

FE-6 Exhaust Air Fan (1~ 5FL Men Bath

RM)

Straight Sirocco Type, Ceiling Mounted

• #1¼, 520³/h, 7mmAq

• 1Ǿ, 100V, 45w, 50Hz With Deep Hood (SUS) with Grill: PZ-

20VS2

BFS-50S

3F, 5F BFS-65S

1F 9811 2F 9902 3F 9902 4F 9903 5F 9902

Mitsubishi Denki Co., Ltd.

FE-7 Exhaust Air Fan (1FL Storage RM)

Straight Sirocco Type, Ceiling Hanging

• #1¼, 290³/h, 6mmAq

• 1Ǿ, 100V, 20w, 50Hz With Deep Hood (SUS) with Grill: PZ-

15VS2

BFS-40SC 806 Mitsubishi Denki Co., Ltd.

FE-8 Ventilation Fan (1~5FL Janitor RM)

Ceiling Mounted Type,

• 50m³/h, 3mmAq

• 1Ǿ, 100V, 9.4w, 50Hz With Deep Hood (SUS) with Grill: PZ-

10VS2

1F VD-10ZJ9

2F VD-10ZVC4

3F VD-13Z9

4F VD-10ZJ7

5F VD-10Z9

1F 2G24A4 2F A4191125 3F 4G07A4 4F 9902 5F Unknown

Mitsubishi Denki Co., Ltd.

FE-9 Ventilation Fan (Shower RM)

Ceiling Mounted Type,

• 80m³/h, 8mmAq

• 1Ǿ, 100V, 16w, 50Hz

With

• Deep Hood (SUS) with Grill: PZ-

10VS2

• FD Deep Hood (SUS) with Grill: PZ-

5F VD-13Z9

VD-13ZT2

4F VD-13Z9

VD-13ZC10

3F VD-13ZT6

VD-13ZT9

2F VD-13ZT7

VD-13ZT6

1F VD-15Z7

5F Unknown Unknown

4F VD-13Z9

A5180522 3F 7A20A5 A5151225

2F VD-13ZT7

VD-13ZT6

1F 8E26A3

Mitsubishi Denki Co., 10VSD2

• Safety Guard: G-35EB

• SUS Weather Hood: W-50SL

• Bard Screen: LB-50

VD-13ZT6 7A23A5

FE-10 Ventilation Fan

(RM-117)

Ceiling Mounted Type,

• 100m³/h, 4mmAq

• 1Ǿ, 100V, 16w, 50Hz With SD Deep Hood (SUS) with Grill:

PZ-10VSD2

VD-13ZT6 7A23A5 Mitsubishi Denki Co., Ltd.

FE-11 Ventilation Fan

(RM-118)

Ceiling Mounted Type,

• 230m³/h, 3mmAq

• 1Ǿ, 100V, 25w, 50Hz With SD Deep Hood (SUS) with Grill:

PZ-15VSD2

VD-18ZB4 9812 Mitsubishi Denki Co., Ltd.

FE-12 Ventilation Fan

(RM-102)

Straight Sirocco Type, Ceiling CasLSte

• 140³/h, 9mmAq

• 1Ǿ, 100V, 16w, 50Hz With Interior Panel: BPS-15PK

FY-32BK7HBL2 443 Mitsubishi Denki Co., Ltd.

FE-13 Ventilation Fan

(RM-109)

Ceiling Mounted Type,

• 160m³/h, 4mmAq

• 1Ǿ, 100V, 25w, 50Hz With SD Deep Hood (SUS) with Grill:

PZ-15VSD2

VD-18ZB4 9812 Mitsubishi Denki Co., Ltd.

FE-14 Ventilation Fan

(RM-109)

Ceiling Mounted Type,

• 60m³/h, 8mmAq

• 1Ǿ, 100V, 14w, 50Hz

VD-13BZ8 Mitsubishi Denki Co., Ltd.

FE-15 Ventilation Fan (1FL Women Locker

RM)

Ceiling Mounted Type,

• 160m³/h, 8mmAq

• 1Ǿ, 100V, 25w, 50Hz

VD-18ZB4 9812 Mitsubishi Denki Co., Ltd.

FE-16 Ventilation Fan (1FL Petty Officer Bath RM)

Ceiling Mounted Type,

• 160m³/h, 8mmAq

• 1Ǿ, 100V, 25w, 50Hz

VD-18ZB4 Mitsubishi Denki Co., FE-17 Ventilation Fan

(RM-113)

Ceiling Mounted Type,

• 130m³/h, 7mmAq

• 1Ǿ, 100V, 22w, 50Hz

VD-15ZP4 Mitsubishi Denki Co., Ltd.

FE-18 Ventilation Fan (1FL Officer Bath

RM)

Ceiling Mounted Type,

• 130m³/h, 7mmAq

• 1Ǿ, 100V, 22w, 50Hz

VD-15ZP4 Mitsubishi Denki Co., Ltd.

FE-20 Ventilation Fan (1~5FL Kitchenette

RM)

Range Hood Type,

• 400m³/h, 4mmAq

• 1Ǿ, 100V, 77w, 50Hz With

• Deep Hood (SUS) with Grill: PZ-

15VS2

• Side Panel: P3220KP

V-604K-2

1F 9903 2F 9903

Mitsubishi Denki Co., FE-21 Ventilation Fan

(RM-212)

Ceiling Mounted Type,

• 330m³/h, 6mmAq

• 1Ǿ, 100V, 42w, 50Hz With Deep Hood (SUS) with Grill: PZ-

15VS2

VD-20ZB4 9902 Mitsubishi Denki Co., Ltd.

FE-22 Ventilation Fan (2FL Student Bath

RM)

Straight Sirocco Type, Ceiling Mounted

• #1¼, 450³/h, 7mmAq

• 1Ǿ, 100V, 45w, 50Hz With Deep Hood (SUS) with Grill: PZ-

20VS2

BFS-50S 9902 Mitsubishi Denki Co., Ltd.

FE-23 Ventilation Fan (2~5FL Storage RM)

Straight Sirocco Type, Ceiling Hanging

• #1¼, 280³/h, 6mmAq

• 1Ǿ, 100V, 20w, 50Hz With Deep Hood (SUS) with Grill: PZ-

15VS2

BFS-40S

5F BFS-40SA

2F 9901 3F 9901 4F 9903 5F 407

Mitsubishi Denki Co., Ltd.

FE-25 Ventilation Fan

(RM-221)

Ceiling Mounted Type,

• 310³/h, 12mmAq

• 1Ǿ, 100V, 74w, 50Hz

VD-23ZB4 9902 Mitsubishi Denki Co., FE-26 Ventilation Fan (2~4FL Women Locker RM)

Ceiling Mounted Type,

• 220³/h, 5mmAq

• 1Ǿ, 100V, 42w, 50Hz With Deep Hood (SUS) with Grill: PZ-

15VS2

VD-20ZB4 2F 9902

3F 9902 4F 9902

Mitsubishi Denki Co., Ltd.

FE-27 Ventilation Fan

(RM-309)

Ceiling Mounted Type,

• 340³/h, 8mmAq

• 1Ǿ, 100V, 74w, 50Hz With Deep Hood (SUS) with Grill: PZ-

15VS2

VD-23ZB10-IN A3180109 Mitsubishi Denki Co., Ltd.

FE-28 Ventilation Fan

(RM-407)

Straight Sirocco Type, Ceiling Mounted

• #1, 520³/h, 9mmAq

• 1Ǿ, 100V, 65w, 50Hz With Deep Hood (SUS) with Grill: PZ-

20VS2

BFS-65S 9811 Mitsubishi Denki Co., Ltd.

FE-29 Ventilation Fan

(RM-506)

Ceiling…