BP1-D_(JP-5_Tank).pdf
PDF 8 MB Posted
- Attached to
- INSPECTION, TESTING, AND MAINTENANCE OF ABOVE STORAGE TANK AND UNDER STORAGE TANK AT U. S. NAF ATSUGI, JAPAN
- Solicitation number
- N40084-14-T-8708
About this file
BP1-D
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BP1-C_(Day_Tank).pdf | ||
| NAFA_UST__Inventory_FY14_Maintenance_Contract.pdf | ||
| drawing_of_AST_1600.pdf | ||
| AST_Inventory_FY2014_w__photos.pdf | ||
| 226-1 226-2(Fuel_Tank).pdf | ||
| drawing_of_AST_226.pdf | ||
| 14T8708_0003.pdf | ||
| 14T8708_inquiries_and_answers.pdf | ||
| J-0200000-07_ELINs_BLANK.xls | XLS spreadsheet | |
| drawing_of_AST_226-1 2.pdf | ||
| drawing_of_AST_2100.pdf | ||
| NAF_Atsugi_UST_Testing__FINAL_10Apr2012.pdf | ||
| 14T870_0002.PDF | ||
| 14T8708_0001.pdf | ||
| 14T8708_C.pdf | ||
| 14T8708_SV_LIST.xls | XLS spreadsheet | |
| 14T8708_B.pdf | ||
| 14T8708_A.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Tightness Testing of Underground Storage Tank (UST) Systems, Naval Air Facility(NAF) Atsugi, Kanagawa, Japan
Tightness Testing Report
Prepared For:
US Army Corps of Engineers, Japan Engineer District
Contract No. W912HV-11-P-0038
FINAL
10 April 2012
PAGE INTENTIONALLY BLANK
NAF Atsugi UST Tightness Testing i W912HV-11-P-0038
CERTIFICATION
US Army Corps of Engineers, Japan Engineer District –Tightness Testing of Underground Storage
Tanks Systems, Naval Air Facility Atsugi, Kanagawa, Japan
JED Contract Number W912HV-11-P-0038
The undersigned attests that the attached completed Tightness Testing Report for the contracted project conforms to the following:
Except as described otherwise in the report, all documents have been checked and coordinated, Except as described otherwise in the report, the site investigation was actually conducted, Except as described otherwise in the report, the UST systems have been tested in accordance to the testing manufacturer’s testing procedures and requirements, Except as described otherwise in the report, the results indicate the UST system as being tight or leaking. If leaking, the report indicates to the maximum extent possible the approximate location of the leak in the UST or fuel pipeline, and
The information contained herein is accurate to the best of the investigator’s knowledge.
Environmental Science Corporation
Company
Kiyohito Hirota
Project Manager
Date: 10 April 2012
NAF Atsugi UST Tightness Testing ii W912HV-11-P-0038
EXECUTIVE SUMMARY
Environmental Science Corporation (ESC) received contract number W912HV-11-P-0038 from the U.S.
Army Corps of Engineers (USACE) Japan Engineer District (JED) to conduct underground storage tank
(UST) tightness testing and prepare an economic analysis of UST verses aboveground storage tank
(AST) lifecycle costs at Naval Air Facility (NAF) Atsugi, Japan.
This report presents results of UST tightness testing. In accordance with the project statement of work
(SOW), tightness testing was conducted in compliance with Chapter 19 of the Japan Environmental
Governing Standards (JEGS) using a US Environmental Protection Agency (USEPA) third party certified tank testing method.
UST integrity testing was conducted during January and February 2012. Thirteen UST systems were tested under this contract. All tank systems passed tightness testing.
Report contents include a tabular summary of integrity testing results, a description of test methods used, and recommendations for repair to UST systems based on field observations. Individual test reports are included in the report appendices. The UST verses AST lifecycle cost analysis has been submitted separately.
NAF Atsugi UST Tightness Testing iii W912HV-11-P-0038
CONTENTS
CERTIFICATION ...................................................................................................................................... i
EXECUTIVE SUMMARY ....................................................................................................................... iii
ACRONYMS AND ABBREVIATIONS.................................................................................................. iv
1.0 INTRODUCTION
2.0 TESTING SITE LOCATIONS
3.0 TIGHTNESS TESTING METHOD
3.1 VacuTectTM Method
3.2 VacuTectTM Testing Technicians
4.0 FIELD EFFORT
4.1 Preliminary Site Visit
4.2 UST System Testing
5.0 RESULTS
6.0 RECOMMENDATIONS
7.0 REFERENCES
TABLES
TABLE 1: FIELD TESTING EXECUTION SUMMARY
TABLE 2: SUMMARY OF TIGHTNESS TEST RESULTS
FIGURES
FIGURE 1: MAP OF INSTALLATION AND UST LOCATIONS
APPENDICES
A. TANK TIGHTNESS TEST REPORTS
B. VACUTECTTM 3RD PARTY CERTIFICATION
C. VACUTECTTM TESTING TECHNICIAN LICENSES AND CERTIFICATIONS
D. TANK RECONNAISSANCE SURVEY RESULTS
NAF Atsugi UST Tightness Testing iv W912HV-11-P-0038
ACRONYMS AND ABBREVIATIONS
AST Aboveground Storage Tank
BGL Below Ground Level cm Centimeter
ESC Environmental Science Corporation
FOR Fuel Oil Return
FOS Fuel Oil Supply
FY Fiscal Year gal Gallon gph Gallons Per Hour
JED Japan Engineer District
JEGS Japan Environmental Governing Standards
LEL Lower Explosive Limit mm Millimeter
N/A Not Applicable
NAF Naval Air Facility
NEX Navy Exchange
NT Not Tested
NWGLDE National Work Group on Leak Detection Evaluations
POL Petroleum, Oil, and Lubricants
SOW Statement of Work
SS Suction System
ST Steel
TM Trade Mark
USACE U.S. Army Corps of Engineers
USEPA U.S. Environmental Protection Agency
USFJ U.S. Forces Japan
UST Underground Storage Tank
NAF Atsugi UST Tightness Testing 1 W912HV-11-P-0038
1.0 INTRODUCTION
Environmental Science Corporation (ESC) received contract number W912HV-11-P-0038 from the U.S.
Army Corps of Engineers (USACE) Japan Engineer District (JED) to conduct underground storage tank
(UST) tightness testing and prepare an economic analysis of UST verses aboveground storage tank
(AST) lifecycle costs at Naval Air Facility (NAF) Atsugi, Japan.
This report presents results of UST tightness testing. The objective of this project was to conduct an integrity testing on UST systems including associated fuel lines that do not have permanent leak detection systems, as required by Chapter 19 of the Japan Environmental Governing Standards (JEGS)
(U.S. Forces Japan [USFJ], 2010).
2.0 TESTING SITE LOCATIONS
ESC conducted integrity testing on thirteen UST systems under this contract. All UST systems were located at NAF Atsugi, Kanagawa, Japan. Tank locations are shown in Figure 1.
NAF Atsugi UST Tightness Testing 2 W912HV-11-P-0038
FIGURE 1: MAP OF INSTALLATION AND UST LOCATIONS
Bldg. No. 1050 Tank No. 21-2
Bldg. No. 1301 Tank No. 1301-1,2,3,4,5,6,7
Bldg. No. 1445 Tank No. 1445-1
Bldg. No. 1504 Tank No. 1504-1,2
Bldg. No. 1521 Tank No. 1521-1, 2
Main Gate
NAF Atsugi UST Tightness Testing 3 W912HV-11-P-0038
3.0 TIGHTNESS TESTING METHOD
The VacuTect™ tank testing system was employed for all UST system tightness testing under this contract. This tank testing method is an independent third party verified test method capable of meeting the detection requirements required by JEGS Chapter 19 and the project SOW. Individual technician and third-party tank test method certifications are included in Appendix B and Appendix C of this report. The test method is described in further detail in Section 3.1.
3.1 VACUTECT
TM
METHOD
VacuTect™ is a reduced pressure (vacuum) based test method. During the VacuTect™ process, the ullage of the tank is subjected to a slight vacuum. When a leak is encountered, negative pressure
(vacuum) recovers, and bubbles are formed at the hole. The formation of bubbles produces a distinctive sound signature which is recorded using a high-quality hydrophone. Similarly to bubbles, above fuel-level leaks produce a high-pitched whistling sound that is also recorded. Leaks below groundwater level are detected using a sensor that records changes in the level of water inside the tank. The VacuTect™ process is applicable to both fuel tanks and directly connected pipelines.
Under JEGS, UST system integrity testing methods must be capable of detecting a 0.1 gallons-per-hour
(gph) leak rate with a probability of detection of 95% and probability of false alarm of 5% from any portion of the tank that routinely contains product while accounting for the effects of thermal expansion or contraction of the product, vapor pockets, tank end deflections, evaporation or condensation, temperature change, wind, vibration, noise, and the location of the water table (USFJ, 2010).
VacuTect™ is a National Work Group on Leak Detection Evaluations (NWGLDE) third-party certified test method which meets both JEGS and USEPA requirements for tightness testing methods. For more information on NWGLDE and the VacuTect™ test method, visit http://www.nwglde.org.
3.2 VACUTECT
TM
TESTING TECHNICIANS
All VacuTect™ method testing of UST systems at NAF Atsugi was performed by trained field technicians certified to perform testing. Copies of testing licenses and certifications are included in
Appendix C.
NAF Atsugi UST Tightness Testing 4 W912HV-11-P-0038
4.0 FIELD EFFORT
4.1 PRELIMINARY SITE VISIT
A preliminary site visit was conducted on 9 January 2012 after the project start-up meeting. The site visit included a visual inspection of facilities for testing, meetings with NAF Atsugi Environmental and
Facilities Maintenance staff, and data gathering. Information gathered during the site visit is shown in individual tank reconnaissance survey forms included in Appendix D.
4.2 UST SYSTEM TESTING
UST system integrity testing was conducted in two separate mobilization split into two days each during
January and February 2012. A second mobilization was required because of Navy Exchange (NEX) gasoline station renovation construction. Integrity testing methods and procedures were performed in accordance with the project work plan (ESC, 2011). After completion of testing, fuel systems were restored to their original conditions. Final operational testing of each tested system was coordinated with facility operators at the site immediately following UST system restoration.
The project field execution schedule is shown in Table 1. This table describes total field effort, including site preparation, testing efforts, and site restoration activities.
TABLE 1: FIELD TESTING EXECUTION SUMMARY
January February
23 24 25 26 27 20 21 22 23 24No. Bldg. Tank ID
M T W T F M T W T F
Capacity
(gallons) Contents Facility use
1 1050 21-1 X 850 Diesel Medical Clinic
2 1504 1504-1 X 13,209 Diesel Utilities
3 1504 1504-2 X 13,209 Diesel Utilities
4 1521 1521-1 X 4,755 Fuel Oil Utilities
5 1521 1521-2 X 4,755 Fuel Oil Utilities
6 1301 1301-1 X 10,000 Gasoline NEX Gas Satiation
7 1301 1301-2 X 10,000 Gasoline NEX Gas Satiation
8 1301 1301-3 X 10,000 Gasoline NEX Gas Satiation
9 1301 1301-4 X 10,000 Gasoline NEX Gas Satiation
10 1301 1301-5 X 5,000 Kerosene NEX Gas Satiation
11 1301 1301-6 X 5,000 Diesel NEX Gas Satiation
12 1301 1301-7 X 500 Waste Oil NEX Gas Satiation
13 1445 1445-1 X 800 Diesel Fire Department
NAF Atsugi UST Tightness Testing 5 W912HV-11-P-0038
5.0 RESULTS
The results of all tightness tests were summarized on Table 2 below. Individual UST tightness test reports are included at Appendix A. All UST systems passed tightness testing. In accordance with standard commercial practices in Japan, testing certification stickers were placed on vent pipe of each system.
TABLE 2: SUMMARY OF TIGHTNESS TEST RESULTS
No. Tank No. Product Capacity (Gallons)
Total Pipe
Length* (meters)
Test Method Tank
Result Line
Result System Result
Activity
1 21-1 Diesel 850 14 VacuTect™ Pass Pass Pass Medical Clinic
2 1504-1 Diesel 13,209 70 VacuTect™ Pass Pass Pass Utility (Boiler)
3 1504-2 Diesel 13,209 66 VacuTect™ Pass Pass Pass Utility (Boiler)
4 1521-1 Diesel 4,755 49 VacuTect™ Pass Pass Pass Utility (Boiler)
5 1521-2 Diesel 4,755 55 VacuTect™ Pass Pass Pass Utility (Boiler)
6 1301-1 Gasoline 7,926 27 VacuTect™ Pass Pass Pass NEX Gas Station
7 1301-2 Gasoline 7,926 31 VacuTect™ Pass Pass Pass NEX Gas Station
8 1301-3 Gasoline 7,926 22 VacuTect™ Pass Pass Pass NEX Gas Station
9 1301-4 Gasoline 7,926 29 VacuTect™ Pass Pass Pass NEX Gas Station
10 1301-5 Kerosene 5,000 43 VacuTect™ Pass Pass Pass NEX Gas Station
11 1031-6 Diesel 5,000 50 VacuTect™ Pass Pass Pass NEX Gas Station
12 1301-7 Waste Oil 500 30 VacuTect™ Pass Pass Pass NEX Garage
13 1445-1 Diesel 800 13 VacuTect™ Pass Pass Pass Fire Department
Note:
* Total Pipe Length represents the sum of all underground product carrying piping (FOS, FOR, Fill, etc). Totals are rounded down to the nearest meter. Vent pipelines are not included in Total Pipe Lengths.
NAF Atsugi UST Tightness Testing 6 W912HV-11-P-0038
6.0 RECOMMENDATIONS
General recommendations are:
1. Conduct tightness testing annually for USTs without functioning automatic leak detection systems using a test method which meets USEPA requirements in accordance with JEGS requirements.
2. Ensure that pipeline repair / replacement incorporates JEGS requirements for automatic leak detection equipment and/or double-wall construction as appropriate. Pipeline leak detection systems should be compatible with their associated UST / facility leak detection systems.
3. Existing USTs and piping that do not meet the requirements of Section 19-3.2 of the JEGS should be properly closed if not needed, or be upgraded or replaced to meet new UST system requirements as required by the JEGS.
NAF Atsugi UST Tightness Testing 7 W912HV-11-P-0038
7.0 REFERENCES
Environmental Science Corporation, 2011. Work Plan, “Underground Storage Tank (UST) System Tightness Testing and Life Cycle Cost Analysis For UST vs. AST System,” US Naval Air Facility (NAF) Atsugi, Kanagawa, Japan
US Army Corps of Engineers (USACE), 2008, EM 385-1-1 Safety and Health Requirements Manual
United States Army Corps of Engineers, Japan Engineer District. 2011. Statement of Work “UST System Tightness Testing and Life Cycle Cost Analysis for UST vs. AST Systems” 6 September 2011.
United States Forces Japan (USFJ). 2010. “Japan Environmental Governing Standards.” Headquarters, U.S. Forces Japan, Department of Defense. September 2011.
APPENDIX A
TANK TIGHTNESS TEST REPORTS
NAF Atsugi UST Tightness Testing A-1 W912HV-11-P-0038
N A
F A tsugi U
ST Tightness Testing A
-2 W
912H V
-11-P-0038
NAF Atsugi UST Tightness Testing A-3 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-4 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-5 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-6 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-7 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-8 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-9 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-10 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-11 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-12 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-13 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-14 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-15 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-16 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-17 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-18 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-19 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-20 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-21 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-22 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-23 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-24 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-25 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-26 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-27 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-28 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-29 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-30 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-31 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-32 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-33 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-34 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-35 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-36 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-37 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-38 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-39 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-40 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-41 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-42 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-43 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-44 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-45 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-46 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing A-47 W912HV-11-P-0038
APPENDIX B
VACUTECTTM 3RD PARTY CERTIFICATION
VacuTect
NON-VOLUMETRIC TANK TIGHTNESS TEST METHOD (VACUUM)
Certification Leak rate of 0.1 gph with PD = 100% and PFA = 0%.
Leak Threshold
A tank system should not be declared tight when:
sonic emission of air ingress is detected in ullage area and/or; sonic emission of bubbles formed by air ingress is detected in product-filled portion of the tank and/or; water ingress is detected by the water sensor.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4, waste oil.
Other liquids may be tested after consultation with the manufacturer. Water miscible products limit the effectiveness of water ingress detection.
Tank Capacity
Maximum of 75,000 gallons.
Test is generally conducted with tank between 60 and 95% full.
However, test may be performed at minimum 5% full if total ullage volume does not exceed 20,000 gallons.
Maximum of 30,000 gallons per tank and 60,000 gallons cumulative capacity for manifolded tank systems with microphone (hydrophone) and water sensor in each tank.
Waiting Time None between delivery and testing.
Test Period Minimum not specified to declare a tank "non-tight".
There must be no dispensing or delivery during test.
When water level in tank excavation backfill is below bottom of tank:
Minimum of 1 hour to declare tank tight.
When water level in tank excavation backfill is above bottom of tank:
Minimum to declare a tank tight may need to be extended because a water sensor must be used.
When water level in tank excavation backfill is not determined:
Minimum to declare a tank tight may need to be extended because a water sensor must be used.
To determine test period, water level in tank excavation backfill must be assumed to be just above bottom of tank.
When using a water sensor, the test period is determined based on tank size, water level inside tank prior to test, tank tilt, type of water sensor, water sensor location in the tank, and water level in tank excavation backfill relative to bottom of tank. Tank tilt is determined by an inclinometer, or by measuring tank bottom elevations at two points within tank. Water sensor is placed in low end of tank or in pre-existing cross section of water inside tank.
For example:
For a printed circuit board water sensor, the test period to detect a 0.1 gph leak rate in a 10,000 gallon (96"dia x 324"lg) level tank without a striker plate and without water in the tank is 51 minutes for water ingress to contact the water sensor plus 38 minutes to allow the sensor to detect the "minimum detectable change in water level" (see "Water Sensor" section below).
For example:
For a magnetostrictive water sensor, the test period to detect a 0.1 gph leak
NAF Atsugi UST Tightness Testing B-1 W912HV-11-P-0038 rate in a 10,000 gallon (96"dia x 324"lg) level tank without a striker plate and without water in the tank is 37 minutes for water ingress to contact the water sensor plus 2 minutes to allow the sensor to detect the "minimum detectable change in water level" (see "Water Sensor" section below).
Test Pressure Required test pressure is a function of tank construction, burial depth, product level in the tank, and water level in tank excavation backfill.
Pressure differential across tank wall at the bottom of the tank must be at least
0.5 psi.
Pressure differential across the tank wall is equal to the absolute value of vacuum applied to tank, plus the pressure of the tank excavation backfill on tank, plus groundwater pressure on tank, minus pressure of liquid in tank.
If water level in tank excavation backfill is not determined by wells, probes or pump boxes in the tank excavation backfill, test pressure calculation must account for both:
1) water level just above bottom of tank to achieve minimum 0.5 psi at worst case condition, and
2) tank completely submerged to assure tank is not damaged from over pressurization.
Temperature Sonic emission and water ingress are independent of product temperature.
Water Sensor Must be used if water level in tank excavation backfill is above tank bottom or if water level in tank excavation backfill was not determined.
Printed circuit board sensor minimum detectable water level is 0.022 inch, and minimum detectable change in water level is 0.016 inch.
Magnetostrictive sensor minimum detectable water level is 0.017 inch, and minimum detectable change in water level 0.001 inch.
Groundwater If groundwater level in tank excavation backfill is above bottom of tank, or if groundwater level in tank excavation backfill is not determined, test time must be sufficient to detect water ingress using one of the above water sensors.
Comments Evaluated using gasoline, diesel, Jet-A, and JP-4.
Microphone (hydrophone) should be located within 60 feet of any possible leak source.
Vacuum test method may not be effective in some tank excavation backfill (such as clay) because it may plug holes in tank.
If free product is present in tank excavation backfill, a leak in the free product zone may not be detected by a vacuum test method.
A well point or observation well in the tank excavation backfill can help identify the presence of free product, tank excavation backfill material, and water elevation in the tank excavation backfill.
More that 4 psi pressure differential across the tank wall at any location in the tank could damage tank.
Evaluator: Ken Wilcox Associates Tel: (816) 443-2494 Dates of Evaluation: 10/28/91, 09/18/92, 02/20/92, 01/18/94, 02/23/96
NAF Atsugi UST Tightness Testing B-2 W912HV-11-P-0038
APPENDIX C
VACUTECTTM TESTING TECHNICIAN LICENSES AND CERTIFICATIONS
NAF Atsugi UST Tightness Testing C-1 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing C-2 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing C-3 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing C-4 W912HV-11-P-0038
NAF Atsugi UST Tightness Testing C-5 W912HV-11-P-0038
APPENDIX D
TANK RECONNAISSANCE SURVEY RESULTS
I. Contact Information
Prime Contact No.: W912HV-11-P-0036 Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
BHC Atsugi:
Contact:
Ms. Lea Dickantone USNH Yokosuka
DSN 243-5183
II. Site Information
UST Identification No. 21-1 Date of Field Survey: 9 January 2012 Location Building 1050 Tank/Building Usage: Emergency Generator
UST Installation Date: 1988 Current UST Status In-service Drawings Available:
Date Prepared:
Yes December 1987
Previous UST Site Surveys Reviewed:
Title/Company:
Date Prepared:
N/A
III. Testing History
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Date Tested:
Results:
Previous Pipeline Test:
Testing Company:
Contract No.:
Never been tested Method Used:
IV. UST System Inspection Notes
UST field reconnaissance was conducted with visual inspection. Inspection measures were limited to visual inspection.
V. Recommendations
None
NAF Atsugi UST Tightness Testing D-1 W912HV-11-P-0038
VI. UST System Information
A. UST Information
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 1200mm (diameter) 2700mm (length)
Capacity: 3,000Litters (Drawing) 850gal, 3,220L (Sign Board)
Product Volume at Time of Testing: 74cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 65mm Length: 0m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 25mm Length(s): 7m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 32mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level Alarm with ATG
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: No No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: 144cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly investigated, and that the information contained within are complete and accurate to the best of the investigator’s knowledge.
Preparer:
Name Kiyohito Hirota Signature :
Title Environmental Scientist Date 14 March 2012
Principal Reviewer:
Name Eric S. Newman Signature :
Title President Date 14 March 2012
NAF Atsugi UST Tightness Testing D-2 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1504-1 Date of Field Survey: 9 January 2012 Location Building 1504 Tank/Building Usage: Boiler
UST Installation Date: 1995 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-3 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 2,800mm (diameter) 8,500mm (length)
Capacity: 50,000Litters 13,209gallons
Product Volume at Time of Testing: 190cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 11.6m Drop Tube: No Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 29m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level Alarm with ATG
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Overfill Prevention: High level Alarm with ATG at 48,000L Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: 379 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-4 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1504-2 Date of Field Survey: 9 January 2012 Location Building 1504 Tank/Building Usage: Boiler
UST Installation Date: 1995 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-5 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 2,800mm (diameter) 8,500mm (length)
Capacity: 50,000Litters 13,209gallons
Product Volume at Time of Testing: 211cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 15.6m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 25m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes, Overfill Prevention: High level Alarm with ATG at 48,000L
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: 372 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-6 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1521-1 Date of Field Survey: 9 January 2012 Location Building 1521 Tank/Building Usage: Boiler
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-7 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 1,900mm (diameter) 5,500mm (length)
Capacity: 18,000Litters 4,755gallons
Product Volume at Time of Testing: 66cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 6.5m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 21m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: Not installed
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: 280 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-8 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1521-2 Date of Field Survey: 9 January 2012 Location Building 1521 Tank/Building Usage: Boiler
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-9 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 1,900mm (diameter) 5,500mm (length)
Capacity: 18,000Litters 4,755gallons
Product Volume at Time of Testing: 142cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 8.5m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 23m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: Not installed
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: 277cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-10 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-1 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-11 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Gasoline
Dimensions: 2,200mm (diameter) 8,200mm (length)
Capacity: 30,000Litters 7,926gallons
Product Volume at Time of Testing: 66cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 18m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 8.4m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level alarm on Automatic Tank Gage (ATG)
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable On dispenser nozzle Permanent Leak Monitoring System: ATG leak detection function Not Installed
D. Groundwater
Water Table Depth Estimate: 340 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-12 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-2 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-13 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Gasoline
Dimensions: 2,200mm (diameter) 8,200mm (length)
Capacity: 30,000Litters 7,926gallons
Product Volume at Time of Testing: 82cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 21m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 10m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level alarm on Automatic Tank Gage (ATG)
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable On dispenser nozzle Permanent Leak Monitoring System: ATG leak detection function Not Installed
D. Groundwater
Water Table Depth Estimate: 303 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-14 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-3 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-15 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Gasoline
Dimensions: 2,200mm (diameter) 8,200mm (length)
Capacity: 30,000Litters 7,926gallons
Product Volume at Time of Testing: 90cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 12m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 10m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level alarm on Automatic Tank Gage (ATG)
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable On dispenser nozzle Permanent Leak Monitoring System: ATG leak detection function Not Installed
D. Groundwater
Water Table Depth Estimate: 329 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-16 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-4 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-17 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Gasoline
Dimensions: 2,200mm (diameter) 8,200mm (length)
Capacity: 30,000Litters 7,926gallons
Product Volume at Time of Testing: 83cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 16m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 13m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level alarm on Automatic Tank Gage (ATG)
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable On dispenser nozzle Permanent Leak Monitoring System: ATG leak detection function Not Installed
D. Groundwater
Water Table Depth Estimate: 332 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-18 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-5 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-19 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Kerosene
Dimensions: 1,900mm (diameter) 6,500mm (length)
Capacity: 18,000Litters (Drawing) 4,755gallon
Product Volume at Time of Testing: 94cm Water Level 2mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 33m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 10m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level alarm on Automatic Tank Gage (ATG)
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable On dispenser nozzle Permanent Leak Monitoring System: ATG leak detection function Not Installed
D. Groundwater
Water Table Depth Estimate: 307 mm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-20 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-6 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-21 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 1,900mm (diameter) 6,500mm (length)
Capacity: 18,000Litters (Drawing) 4,755 gallon
Product Volume at Time of Testing: 94cm Water Level 15mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 80mm Length: 12m Drop Tube: Yes Product Piping: Material Steel Type: Single Wall Size: 40mm Length(s): 8m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 50mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: High level alarm on Automatic Tank Gage (ATG)
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable On dispenser nozzle Permanent Leak Monitoring System: ATG leak detection function Not Installed
D. Groundwater
Water Table Depth Estimate: 310 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-22 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1301-7 Date of Field Survey: 19 February 2012 Location Building 1301 Tank/Building Usage: Gasoline Station
UST Installation Date: 2002 Current UST Status In-service Drawings Available:
Date Prepared:
Yes Unknown
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-23 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Waste Oil
Dimensions: 950mm (diameter) 2,700mm (length)
Capacity: 1,900Litters 500gal, Product Volume at Time of Testing: 13cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 50mm Length: 30m Drop Tube: Yes Product Piping: Material Not Applicable Type: Not Applicable Size: Not Applicable Length(s):
Check Valves Not Applicable Location(s):
Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 32mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: Not Installed
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: 202 cm BGL Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-24 W912HV-11-P-0038
Contracting Firm:
Contact:
Environmental Science Corporation 03-5283-9221
Final Report Recipient:
Contact:
Mr. Robert A. Brochu, Project manager, JED USACE DSN: 315-263-8072 Commercial: 046-407-8072
US Military Installation:
Contact:
Ms. Christine Ricafrente, Naval Air Facility Atsugi, Environmental Office
DSN 264-4141
II. Site Information
UST Identification No. 1445-1 Date of Field Survey: 9 January 2012 Location Building 1445 Tank/Building Usage: Emergency Generator
UST Installation Date: 2004 Current UST Status In-service Drawings Available:
Date Prepared:
Yes August 2004
Previous UST Site Surveys Reviewed:
Previous UST Test:
Testing Company:
Contract No.:
Never been tested Method Used:
Contract No.:
Never been tested Method Used:
NAF Atsugi UST Tightness Testing D-25 W912HV-11-P-0038
Material: Steel Type: Single Wall Product Currently Stored: Diesel
Dimensions: 1,200mm (diameter) 2,700mm (length)
Capacity: 3,100Litters 800gallons
Product Volume at Time of Testing: 46cm Water Level 0mm
Manifolds to UST ID No.: No
B. Piping Information
Fill Piping Material Steel Type: Single Wall Size: 65mm Length: 5.5m Drop Tube: No Removable:
Product Piping: Material Steel Type: Single Wall Size: 25mm Length(s): 4m Check Valves Yes Location(s): Top of the UST in a manhole Shutoff Valve(s) No Location(s) Manifold (s) No Vent Piping: Material: Steel Size: 32mm
Height above Ground: 4m
C. Ancillary Equipment
Level Gage: Yes Overfill Prevention: Not installed
Spill Prevention: Fill port spill containment Tank Piping
Secondary Containment: Concrete vault No Cathodic Protection: Not installed Not Installed
Vapor Recovery: Not Applicable Not Applicable Permanent Leak Monitoring System: 4 vapor ports around the tank Not Installed
D. Groundwater
Water Table Depth Estimate: Source: Vapor ports
VII. Certification
I certify that all documents have been checked and coordinated, the site and UST system thoroughly
NAF Atsugi UST Tightness Testing D-26 W912HV-11-P-0038
File details come from the government source that posted it. Updated .