Amendment0010.pdf
PDF 91 KB Posted
- Attached to
- ENERGY REPAIRS MULT BLDGS NSF IH Federal contract opportunity
- Solicitation number
- N4008018R3519
About this file
Amendment0010.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment0009.pdf | ||
| Vetting_Form_SECNAV_5512-1.pdf | ||
| Amendment0008.pdf | ||
| Amendment0007.pdf | ||
| Amendment0006_N4008018R3519.pdf | ||
| SiteVisitLog.pdf | ||
| Amendment07__P-231_CBIRF.pdf | ||
| DB_MD180055_07062018.docx | DOCX document | |
| NAVFAC_WASH_PWD_SP_IH_Visit_Request.docx | DOCX document | |
| SECNAV_5512_1_11787_APPROVED_AC_PASS_ID_FORM1_(003)_Attachment_C.pdf | ||
| AMENDMENT_0001_EnergyRepairs.docx | DOCX document | |
| Request_for_Information_EnergyReparis_Attachment_A.doc | DOC document | |
| SECNAV_5512_1_11787_APPROVED_AC_PASS_ID_FORM1_(003)_Attachment_C.pdf | ||
| IH_EnergyRepair_Specs_Final.pdf | ||
| IH_EnergyRepair_Drawing_Set_Final.pdf | ||
| N4008018R3519_IH_EnergyRepair_Drawing_Set_Final.pdf | ||
| N4008018R3519_PreSolicitationForEnergy_Repairs.pdf | ||
| N4008018R3519_IH_EnergyRepair_Specs_Final.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT A
PRE-PROPOSAL INQUIRY
RFP: N40080-18-R-3519
SOLICITATION NO#: N40080-18-R-3519 - ENERGY REPAIRS MULT BLDGS NSF IH, NAVAL
SUPPORT FACILITY (NSF) INDIAN HEAD, NAVAL SUPPORT ACTIVITY (NSA) SOUTH POTOMAC,
MARYLAND
NOTE: ALL PRE-PROPOSAL INQUIRIES SHALL BE SUBMITTED BY E-MAIL, ON THIS FORM TO
THE FOLLOWING E-MAIL ADDRESSES: anita.w.sampson@navy.mil and kennett.morris@navy.mil
DATE OF PROPOSAL INQUIRY: August 27, 2018
FROM FIRM: Service Mechanical Inc.
ADDRESS: 7907 Kincannon Place, Lorton, VA 22079
PHONE NO. 703-372-1700
E-MAIL ADDRESS: Trey.Rosch.SMI@gmail.com
POC: Trey Rosch
FAX/PHONE NUMBER: 703-372-1716
PROPOSAL INQUIRY: On Drawing M-10, Note 6 states to duct to intake of new Hi-E Dry
Dehumidifier. What Model number is this New Hi-E Dry Dehumidifier, as there are no specifications that give the model number of the unit or accessories required?
GOVERNMENT RESPONSE:
CHANGE Note 6 CFM from 300 CFM to 250 CFM to match products available.
Hi Dry 100 (6.8 pints/KWH efficiency) will provide 255 CFM of Air Flow. Provide the unit with standard options for ducted installation to include, condensate pump, built-in controller and power chord.
AMENDMENT 0010
N40080-18-R-3519: ENERGY REPAIRS MULT BLDGS NSF
N40080-18-R-3519: ENERGY REPAIRS MULT BLDGS NSF
mailto:anita.w.sampson@navy.mil mailto:kennett.morris@navy.mil