Attachment E - N4008017R0006 - Multiple HVAC - PPI Government Response.xlsx

XLSX spreadsheet 21 KB Posted

Attached to
REPAIR HVAC – MULTIPLE BUILDINGS – FY23
Solicitation number
N4008017R0006
Issued by

About this file

This document contains responses to questions from potential offerors on solicitation number N4008017R0006 from the Department of the Navy Naval Facilities Engineering Command. The solicitation is for repair of HVAC systems and replacement of roofs at the Davis Center Building 3300 at Marine Corps Base Quantico in Virginia. Drawings can be provided for all buildings except Building 26100. The proposal due date is August 9, 2023 at 1200 PM. The entire roof must be replaced according to the provided plans and Basis of Design report. Alternate roofing systems or repairs will not be considered. Lower roofs must also be replaced. Dedicated contractor personnel are required for each task role.

The responses clarify the scope of work requires replacing all roofs according to provided drawings and specifications, with no alternatives or partial repairs accepted. The proposal due date and exclusions are also noted.

View the file

Other files

File Type Posted
RFP Attachment A - Statement of Work revised 8-22-2023.pdf PDF
N4008017R0006- RFP Amendment 0006 - Repair HVAC Multiple Bldgs FY23.pdf PDF
RFP Attachment C - Price Proposal Form revised 8-22-2023.xlsx XLSX spreadsheet
N4008017R0006- RFP Amendment 0005 - Repair HVAC Multiple Bldgs FY23.pdf PDF
N4008017R0006- RFP Amendment 0004 - Repair HVAC Multiple Bldgs FY23.pdf PDF
Attachment J - N4008017R0006 - Multiple HVAC - PPI 4-6 Government Response.xlsx XLSX spreadsheet
Attachment H - N4008017R0006 - Multiple HVAC - PPI 2 Government Response.xlsx XLSX spreadsheet
N4008017R0006- RFP Amendment 0003 - Repair HVAC Multiple Bldgs FY23.pdf PDF
Attachment I - N4008017R0006 - Site Visit Bldg 3098 7-26-23.pdf PDF
N4008017R0006- RFP Amendment 0002 - Repair HVAC Multiple Bldgs FY23.pdf PDF
RFP_Attachmen A - SOW Repair HVAC Multiple Bldgs FY23 revised.pdf PDF
Attachment F - N4008017R0006 - Site Visit Log 7-19-23.pdf PDF
N4008017R0006- RFP Amendment 0001 - Repair HVAC Multiple Bldgs FY23.pdf PDF
Attachment D - DBA Wage Determination VA20230162.pdf PDF
Attachment B - Pre-Bid Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment A - SOW Repair HVAC Multiple Bldg FY23.pdf PDF
N4008017R0006- Request For Proposal - Repair HVAC Multiple Bldgs. FY23.pdf PDF
Attachment C - Price Proposal Form.xlsx XLSX spreadsheet
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

AMENDMENT 0001
ATTACHMENT A - N4008017R0006 - GOVERNMENT RESPONSE TO PRE-PROPOSAL INQUIRIES
Question No.Date ReceivedREFERENCEQUESTIONGOVERNMENT RESPONSEPosted on Amend No.
PageSectionPara.
17/14/23---The SOW states that this is a Design-Bid-Build. There are no drawings included in the contract documents. Will Drawings be provided or is this a Design Build?Drawings can be provided for every building listed with the exception of Building 26100.0001
27/14/23---The RFP States that the proposal due date is Monday August 9th. August 9th is a Wednesday. Is the proposal due date August 9th or August 7th?The proposal due date is 1200 PM Wednesday, August 9, 2023.0001
36/9/23BoD; 1-1;6-1Chap. 1,62.2a;6.1.1-6.1.3Must the entire roof be replaced or is it eligible for a restoration?YES - Replace entire Roof. See Plans A107 through A505 plus Chapters 1 and 6 of the Basis-of-Design (BoD) Report0001
46/9/23BoD; 1-1;6-1Chap. 1,62.2a;6.1.1-6.1.3Would a 20 year NDL warranted, USDA Bio Preferred, fully reinforced fluid applied restoration system be considered as an alternate to the replacement modified bitumen system specified?NO. Please build according to the Plans and Specs. See Plans A107 through A505 plus Chapters 1 and 6 of the Basis-of-Design (BoD) Report0001
56/12/23BoD; 1-1;6-1Chapter 1,62.2a; 6.1.1; 6.1.3Are the lower roofs in the SOW to be repaired?YES - Replace all Roofs. See Plans A107 through A505 plus chapters 1 & 6 of the Basis of Design (BoD) Report.0001
66/12/232Spec Section 00 22 13.00 201.2bCan one person work like triple hat?NO triple/double hats - required Contractor officials shall be dedicated to their particular/single tasks.0001

SOLICITATION NO. &"-,Bold"N4008017R0006&"-,Regular" PROJECT TITLE/LOCATION: Repair HVAC and Replace Roof, Davis Center, Building 3300, Marine Corps Base Quantico, VA 22134