This document contains answers to questions from potential offerors regarding solicitation number N3220520R4088 for post-shakedown availability and drydocking of the USNS Puerto Rico with the Military Sealift Command. The questions pertained to specification items for work involving an e-console interface, greywater three-way valve, CHT washdown modification, CHT transfer pump, waste oil pump strainer, and stern ramp piping. The answers clarified that the relevant references would be resent via DOD SAFE. Additionally, a question regarding heat trace installation referenced an existing system, and electrical drawings would be required upon job completion.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MILITARY SEALIFT COMMAND
N3220520R4088
QUESTIONS AND ANSWERS 2
The following are answers to questions received from potential offerors. The answers provide clarification only and DO
NOT constitute an amendment to the solicitation.
QUESTION #1:
SPECIFICATION ITEM NO.: 406
PARAGRAPH / SECTION NO: 2.1.02
TITLE: E- Console Interface
Reference 2.1.2 was not provided with the solicitation. Please provide.
ANSWER:
Reference 2.1.2 will be resent via DOD SAFE.
QUESTION #2:
SPECIFICATION ITEM NO.: 504
PARAGRAPH / SECTION NO: 2.1.1
TITLE: Greywater 3 Way Valve
Reference 2.1.1 was not provided with the original solicitation. Please provide.
Reference 2.1.2 will be resent via DOD SAFE.
QUESTION #3:
SPECIFICATION ITEM NO.: 505
PARAGRAPH / SECTION NO: 2.1
TITLE: CHT Washdown Mod
Reference 2.1 was not provided with the original solicitation. Please provide the reference.
Reference 2.1 will be resent via DOD Safe.
QUESTION #4:
SPECIFICATION ITEM NO.: 506
PARAGRAPH / SECTION NO: 2.0
TITLE: CHT Transfer Pump
None of the references were provided for this work item. Please provide.
References will be resent via DOD Safe.
QUESTION #5:
SPECIFICATION ITEM NO.: 507
PARAGRAPH / SECTION NO: 2.2
TITLE: Waste Oil Pump Strainer
Reference 2.2 was not provided with the solicitation. Please provide.
Reference 2.2 will be resent via DOD Safe.
QUESTION #6:
SPECIFICATION ITEM NO.: 518
PARAGRAPH / SECTION NO: 2.0
TITLE: Stern Ramp Piping
None of the references were provided for this work item. Please provide.
References will be resent via DOD Safe.
QUESTION #7:
SPECIFICATION ITEM NO.: 524
PARAGRAPH / SECTION NO: 7.8.1
TITLE: Heat Trace
Paragraph 7.8.1 references other items installing heat trace. What other item is the specification referencing for heat trace installation?
A heat trace system was previously installed. Heat trace cabling should be installed on the new hot and cold potable water piping and tied into the existing heat trace system. Electrical load calulations will be required prior to install. Revised electrical drawings for the heat trace system will be required upon completion. Austal USA drawing 430-324-01-714 provided as reference.