RESPONSE TO REQUEST FOR CLARIFICATIONS.

View the file

Other files for this federal contract opportunity

Other files attached to USNS WILLIAM MCLEAN ROH/DD, newest first.
File Type Posted
AMENDMENT_0005-20181222124641.pdf PDF
Ref_2(1).zip ZIP file
Ref_1(1).zip ZIP file
Ref_2(4).zip ZIP file
Ref_1(5).zip ZIP file
Ref_1(3).zip ZIP file
Ref_1(4).zip ZIP file
Ref_1(2).zip ZIP file
Ref_2(2).zip ZIP file
Ref_2(3).zip ZIP file
J_-_2_Category_A_Items_MCLEAN.xls XLS spreadsheet
4258_A3.docx DOCX document
0802_A_AUXILIARY_PRESTAGE_AREA_REFRIGERATION_INSTALLATION_(T-ALT_485)_Rev_10-3-18.doc DOC document
243-8498653_-_REV_1_26_JUNE_2018.pdf PDF
331-8495060_RelayLanternsExamRmTALT299_ABS_(2).pdf PDF
532-8499083_-LT_FW_Cooling_Sys_WMC.pdf PDF
N3220518R4258_FINAL_SOLICITATION.docx DOCX document
J-6_CDRLs.zip ZIP file
J_Attachments.zip ZIP file
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N3220518R4258

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION B - SUPPLIES OR SERVICES AND PRICES

The following have been added by full text:

ANSWERS TO RFIC

REQUEST FOR SPECIFICATION CLARIFICATION #1

SPECIFICATION ITEM NO.: 369

PARAGRAPH / SECTION NO: 2.1.1

TITLE: INSTALL RELAY LANTERNS IN EXAMINATION ROOM (T-ALT 299)

QUESTION:

Please provide verification that Dwg. No. 331-8495060, Relay Operated Lanterns Over Medical Table Lighting Installation listed in paragraph 2.1.1 is equivalent to the JHSV Drawing (NAVSEA Dwg. No. 434-8495060) that was provided in the references.

ANSWER:

Attached is drawing 331-8495060, Relay Lanterns in Examination Room Lighting Installation.

REQUEST FOR SPECIFICATION CLARIFICATION #2

SPECIFICATION ITEM NO.: 1003

PARAGRAPH / SECTION NO: 3.1.2, 7.3.2

TITLE: RAM TENSIONER ACCUMULATOR HP AIR PIPE SUPPORT BRACKET REPLACEMENT

QUESTION:

Paragraph 3.1.2 states there are 21 brackets; paragraph 7.3.2 states there are 28 brackets. Please clarify.

ANSWER:

Paragraph 3.1.2 states there are 21 brackets - That's the number of brackets currently installed that will require removal.

IAW Paragraph 7.3.1 Remove existing Ram Tensioner Accumulator HP air pipe support brackets, three (3) per station.

No need for three (3) brackets per station. It'll just be overkill.

The contractor shall manufacture and install fourteen (14) brackets, two (2) per station. That's twenty-eight (28) bracket Halves as per the drawings that was provided.

REQUEST FOR SPECIFICATION CLARIFICATION #3

SPECIFICATION ITEM NO.: 941

PARAGRAPH / SECTION NO: 2.1

TITLE: Fresh Water (Closed Loop) Stern Tube Lubrication

QUESTION:

Ref. 2.1.8 - MSC Dwg 243-8498653, Stern Tube Aft Seal Adapter Plate was not provided. Please provide.

Attached is drawing 243-8498653, Stern Tube Aft Seal Adapter Plate.

REQUEST FOR SPECIFICATION CLARIFICATION #4

SPECIFICATION ITEM NO.: 0369

PARAGRAPH / SECTION NO: 2.1.2

TITLE: INSTALL RELAY LANTERNS IN EXAMINATION ROOM (T-ALT 299)

QUESTION:

The drawing referenced is 331-8495060, Relay Operated Lanterns over Medical Table Lighting Installation but the drawing provided is 434-8495060 (for JHSV class vessels). Please provide drawing 331-8495060.

Attached is drawing 331-8495060, Relay Lanterns in Examination Room Lighting Installation.

REQUEST FOR SPECIFICATION CLARIFICATION #5

SPECIFICATION ITEM NO.: 0532

PARAGRAPH / SECTION NO:

TITLE: HT/LT Fresh Water and Chill System Flush

QUESTION:

Ref 2.4 MSC DWG No. 532-8499083 Low Temp Freshwater Cooling System Diagram was not provided with package. Please provide.

Attached is drawing 532-8499083, Low Temperature Freshwater Cooling System Diagram.

(End of Summary of Changes) image1.wmf