RESPONSE TO REQUEST FOR CLARIFICATIONS.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| AMENDMENT_0005-20181222124641.pdf | ||
| Ref_2(1).zip | ZIP file | |
| Ref_1(1).zip | ZIP file | |
| Ref_2(4).zip | ZIP file | |
| Ref_1(5).zip | ZIP file | |
| Ref_1(3).zip | ZIP file | |
| Ref_1(4).zip | ZIP file | |
| Ref_1(2).zip | ZIP file | |
| Ref_2(2).zip | ZIP file | |
| Ref_2(3).zip | ZIP file | |
| J_-_2_Category_A_Items_MCLEAN.xls | XLS spreadsheet | |
| 4258_A3.docx | DOCX document | |
| 0802_A_AUXILIARY_PRESTAGE_AREA_REFRIGERATION_INSTALLATION_(T-ALT_485)_Rev_10-3-18.doc | DOC document | |
| 243-8498653_-_REV_1_26_JUNE_2018.pdf | ||
| 331-8495060_RelayLanternsExamRmTALT299_ABS_(2).pdf | ||
| 532-8499083_-LT_FW_Cooling_Sys_WMC.pdf | ||
| N3220518R4258_FINAL_SOLICITATION.docx | DOCX document | |
| J-6_CDRLs.zip | ZIP file | |
| J_Attachments.zip | ZIP file |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N3220518R4258
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION B - SUPPLIES OR SERVICES AND PRICES
The following have been added by full text:
ANSWERS TO RFIC
REQUEST FOR SPECIFICATION CLARIFICATION #1
SPECIFICATION ITEM NO.: 369
PARAGRAPH / SECTION NO: 2.1.1
TITLE: INSTALL RELAY LANTERNS IN EXAMINATION ROOM (T-ALT 299)
QUESTION:
Please provide verification that Dwg. No. 331-8495060, Relay Operated Lanterns Over Medical Table Lighting Installation listed in paragraph 2.1.1 is equivalent to the JHSV Drawing (NAVSEA Dwg. No. 434-8495060) that was provided in the references.
ANSWER:
Attached is drawing 331-8495060, Relay Lanterns in Examination Room Lighting Installation.
REQUEST FOR SPECIFICATION CLARIFICATION #2
SPECIFICATION ITEM NO.: 1003
PARAGRAPH / SECTION NO: 3.1.2, 7.3.2
TITLE: RAM TENSIONER ACCUMULATOR HP AIR PIPE SUPPORT BRACKET REPLACEMENT
QUESTION:
Paragraph 3.1.2 states there are 21 brackets; paragraph 7.3.2 states there are 28 brackets. Please clarify.
ANSWER:
Paragraph 3.1.2 states there are 21 brackets - That's the number of brackets currently installed that will require removal.
IAW Paragraph 7.3.1 Remove existing Ram Tensioner Accumulator HP air pipe support brackets, three (3) per station.
No need for three (3) brackets per station. It'll just be overkill.
The contractor shall manufacture and install fourteen (14) brackets, two (2) per station. That's twenty-eight (28) bracket Halves as per the drawings that was provided.
REQUEST FOR SPECIFICATION CLARIFICATION #3
SPECIFICATION ITEM NO.: 941
PARAGRAPH / SECTION NO: 2.1
TITLE: Fresh Water (Closed Loop) Stern Tube Lubrication
QUESTION:
Ref. 2.1.8 - MSC Dwg 243-8498653, Stern Tube Aft Seal Adapter Plate was not provided. Please provide.
Attached is drawing 243-8498653, Stern Tube Aft Seal Adapter Plate.
REQUEST FOR SPECIFICATION CLARIFICATION #4
SPECIFICATION ITEM NO.: 0369
PARAGRAPH / SECTION NO: 2.1.2
TITLE: INSTALL RELAY LANTERNS IN EXAMINATION ROOM (T-ALT 299)
QUESTION:
The drawing referenced is 331-8495060, Relay Operated Lanterns over Medical Table Lighting Installation but the drawing provided is 434-8495060 (for JHSV class vessels). Please provide drawing 331-8495060.
Attached is drawing 331-8495060, Relay Lanterns in Examination Room Lighting Installation.
REQUEST FOR SPECIFICATION CLARIFICATION #5
SPECIFICATION ITEM NO.: 0532
PARAGRAPH / SECTION NO:
TITLE: HT/LT Fresh Water and Chill System Flush
QUESTION:
Ref 2.4 MSC DWG No. 532-8499083 Low Temp Freshwater Cooling System Diagram was not provided with package. Please provide.
Attached is drawing 532-8499083, Low Temperature Freshwater Cooling System Diagram.