Minimum Salient Characteristics B3323 Pre-action riser.pdf

PDF 166 KB Posted

Attached to
B3323 Fire Riser
Solicitation number
FA303025Q0020
Issued by

About this file

This file contains minimum salient characteristics and specifications for a fire riser assembly replacement project, including detailed images of both a 2" pre-action valve and complete fire riser assembly system.

The technical specifications call for a 2" black iron pipe schedule 40 system with specific components including: malleable 90-degree elbows (150 lb threaded), black iron malleable tee (150 lb threaded), bronze angle valve (125 lb rising stem threaded), fire gate valve, swing check valve with ball drip, pipe stands, and pressure gauges. The images show the existing installation setup that needs to be replaced, providing visual reference for contractors to understand the configuration and space constraints of the current system.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Minimum Salient Characteristics

2” pre-action valve

Fire Riser Assembly

Black iron pipe schedule 40 - 2”, Malleable 90 deg elbows 150 lb. threaded, black iron malleable tee 150

lb. threaded, Angle valve bronze 125 lb. rising stem threaded, fire gate valve, Swing check valve with ball drip, pipe stands, pressure gauges.