Mid-Valley Sanitary Landfill - LFG Flare Station - Design Plans - 06-18-2025~1.pdf
PDF 23 MB Posted
- Solicitation number
- PWG126-SOLID-6143
- Issued by
- San Bernardino County, San Bernardino City, California
About this file
This document is a comprehensive set of design plans and technical drawings for the Mid-Valley Sanitary Landfill Landfill Gas Flare Station project prepared by San Bernardino County Department of Public Works, Solid Waste Management Division. The project involves the construction of a new flare station facility located at 2390 N. Alder Avenue, Rialto, California 92377, designed to manage and safely dispose of landfill gas from Units 1-4 at the facility. The design includes installation of two low-NOx flare stacks (5,000 SCFM and 1,000 SCFM capacity), two gas handling skids (GHS-1 and GHS-2), two rotary screw compressors with associated equipment, a condensate management system with an 8,700-gallon poly storage tank, site improvements including grading and drainage infrastructure, a 40-foot by 40-foot pre-fabricated steel canopy structure, and ancillary equipment and controls. The project requires a Class "A" Contractor's License and encompasses 42 sheets of detailed civil, structural, mechanical, and electrical design drawings prepared under the supervision of registered professional engineers.
The design plans contain comprehensive technical specifications for concrete foundations, structural steel components, HDPE piping systems, electrical systems including a 2,000-amp switchgear, seismic design criteria consistent with the 2022 California Building Code, and various equipment anchorage requirements. The project includes demolition and salvage of the existing flare station and relocation of existing equipment including storage containers, operational trailers, and utility infrastructure. Construction details specify material requirements, reinforcement specifications, installation procedures, and special inspection requirements for structural elements, welding operations, and post-installed adhesive anchors. The site plan indicates the relocation of existing condensate sumps, compressed air lines, and interconnect piping systems, with field verification requirements for underground facilities. Equipment specifications identify manufacturers including PEI, Kaishan, ISCO Industries, Grundfos, and other suppliers, with major components including Lonestar Blower centrifugal blowers, condensate sump assemblies, and granular activated carbon treatment systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S M
A R
K D
A
TE
SHT. NO.
NO CHANGES RESIDENT ENGINEER
CHANGESMARK
TOT. SHT'S.
DATE
421PREPARED UNDER THE SUPERVISION OF DATE
PREPARED BY:
3.
Pavement or to the Top of Curb, unless otherwise noted.
All Pavement Width Dimensions shown on the plans are to the Edge of lines, shall be protected in place.
All Trees & Vegetation outside the limits of excavation and embankment slope
GENERAL NOTES
5.
on the plans or as determined by the Engineer.
Asphalt Concrete Overlays shall be feathered to meet existing as shown4.
1.
Transitions and Warping shall be as shown and as determined by the Engineer.
2.
Dimensions are subject to tolerances specified in the State Standard Specifications.
SAN BERNARDINO COUNTY
DEPARTMENT OF PUBLIC WORKS
SOLID WASTE MANAGEMENT DIVISION
G-002
C-103
G-001
DESCRIPTION
SITE IMPROVEMENTS/GRADING/FIELD PIPING PLAN
TITLE AND INDEX OF SHEETS
VENTURA
MONO
SAN BERNARDINO
INYO
TULARE
LOS
ANGELES
KERN
IMPERIAL
RIVERSIDE
ORANGE
SAN DIEGO
LASSEN
MODOC
BUTTE SIERRA
PLUMAS
SISKIYOU
TRINITY
TEHAMA
GLENN
MENDOCINO
SHASTA
ALPINE
SU
TTER
M
EN
TO
SA
CR
A-
AMADOR
EL DORADO
PLACER
MARIPOSA
MADERACLARA
STANISLAUS
MERCED
CALA
VERAS
TUOLUMNE
JO
AQUINSAN
COLUSA
LAKE
NAPASONOMA
SANTA
SAN MATEO
SAN FRANCISCO
MARIN
CONTRA
CRUZ
SOLANO
SANTA
ALAMEDA
COSTA
YOLO
YUBA NEVADA
HUMBOLDT
DEL NORTE
FRESNO
KINGS
BENITO
MONTEREY
SAN
SANTA
OBISPO
BARBARA
LUIS
SAN
FLARE STATION DETAILS
M-101 M-501 M-502
STRUCTURAL DETAILS 4
ELECTRICAL PLAN
POWER SINGLE LINE DIAGRAM AND LOAD SCHEDULE
S-101
S-501
SYMBOLS AND ABBREVIATIONS
S-502
E-101
OVERALL SITE PLAN
E-601
FLARE STATION DETAILS
STRUCTURAL DETAILS 1
PROJECT LOCATION
NOT TO SCALE
VICINITY MAP
LOCATION MAP
FLARE STATION ASSEMBLY PLAN
LANDFILL GAS FLARE STATION AT THE
MID-VALLEY SANITARY LANDFILL
SAN BERNARDINO COUNTY
NOEL CASTILLO, DIRECTOR OF PUBLIC WORKS
THIS PROJECT REQUIRES A CLASS "A" CONTRACTOR'S LICENSE
APPROVED BY:
DATE
21700 Copley Drive, Suite 200 Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
STRUCTURAL DETAILS 3S-503
G-004 FLARE STATION CONSTRUCTION NOTES
CONDUIT/WIRE SCHEDULE, DETAILS AND NOTESE-501
SANITARY LANDFILL
MID-VALLEY
RIALTO MUNICIPAL
AIRPORT MIRO FIELD
BASELINE RD S
IE
R R
A A
V E
C
IT
R U
S A
V E
P A
LM
E
TO
A
V E
A
LD
E R
A V
E
LO
C
U S
T A
V E
LI
N
D E
N A
V E
A Y
A
LA
A V
E
SIERRA LAKES PKWY
CASMALIA ST
BOHNERT AVE
HIGHLAND AVE
C
IT
Y O
F R
IA
LT
O
C
IT
Y O
F F
O N
TA
N
A
N.T.S.
SHT. NO.
STRUCTURAL DETAILS 2
S-504
C-301 SUMP "A" AND GHS-1 INLET PIPING PROFILE
C-302 SUMP "B" AND GHS-2 INLET PIPING PROFILE
C-102 DEMOLITION/SALVAGE PLAN
C-101 SITE PLAN/SURVEY CONTROL/RELOCATION PLAN
C-501 DETAILS
G-003 DEMOLITION/SALVAGE/SITE IMPROVEMENTS CONSTRUCTION NOTES
CONDENSATE MANAGEMENT SYSTEM PROCESS FLOW DIAGRAMD-601
CONCEPTUAL EQUIPMENT CANOPY ISOMETRIC
S-505
DWG. NO.
DWG. NO.
G-001
A PUBLIC SERVICE BY
UNDERGROUND SERVICE ALERT
DIAL
BEFORE
YOU DIG
TWO
WORKING
DAYS
BEFORE
YOU DIG
S-001 GENERAL STRUCTURAL NOTES
S-002 SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS
S-102 OFFICE AND STORAGE CONTAINER FOUNDATION PLAN
S-103 FLARE AND BLOWER FOUNDATION PLAN
S-104 CONDENSATE TANK AND PREFABRICATED STEEL
S-301 FLARE SECTION23
S-302 TANK SECTION24
ELECTRICAL DETAILSE-502
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 1-
G -0
-T t.d w g
/1 8/
0:
:4 m ar co s.
ar m ijo
C-104 FLARE STATION DRAINAGE PLAN8
C-201 NORTH AND SOUTH WALL PROFILES10
C-202 EAST AND WEST WALL PROFILES11
STRUCTURAL DETAILS 5
M-503
S-303 CANOPY SECTION
22 CANOPY FOUNDATION PLAN
POWER SINGLE LINE DIAGRAM AND LOAD SCHEDULEE-602
S-506
STRUCTURAL DETAILS 6
FLARE STATION PROCESS FLOW DIAGRAMD-602
C-502 DETAILS
NOT TO SCALE
SITE ADDRESS:
2390 N. ALDER AVE.
RIALTO, CA 92377
INDEX OF SHEETS
C-105 WATER LINE PLAN9
16C-503 WATER LINE STANDARD DETAILS
TITLE AND INDEX OF
SHEETS
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025
10/14/2025
Noel Castillo e sig vector
COMPRESSOR
SELECTOR
INSTRUMENT SYMBOLS
FILTER/REGULATOR/LUBRICATOR
VARIABLE SPEED DRIVE
GROUND
HIGH DENSITY POLYETHYLENE
HAND-OFF-AUTO
FLOW SWITCH OR FINISH SURFACE
FIBERGLASS REINFORCED PLASTIC
FLOW SAFETY VALVE (CHECK VALVE)
GROUND FAULT INTERRUPTER
GAS MONITOR
GROUND FAULT
FUSE HOLDER
GRADE BREAK
FLOW VALVE
FUTURE
FLOW SWITCH LOW
FLOW TRANSMITTER
FUSE
FLOW SWITCH HIGH
PRESSURE CONTROL VALVE
PRESSURE INDICATOR
POLYETHYLENE
PHONE
PILOT GAS
PRESSURE DIFFERENTIAL INDICATOR
PRESSURE ALARM LOW LOW
PRESSURE ALARM HIGH HIGH
PURGE AUTO
PRESSURE ALARM HIGH
PRESSURE ALARM LOW
PRESSURE DIFFERENTIAL INDICATOR
PRESSURE CONTROLLER
PUMP
EVENT INDICATOR CONTROLLER
POSITION SWITCH CLOSED
POSITION SWITCH OPENED
POSITION INDICATOR
POSITION SWITCH
POSITION CONTROLLER
POSITION ALARM
EVENT INDICATOR
VIBRATION SWITCH HIGH
VIBRATION TRANSMITTER
EVENT ALARM
EXPLOSION PROOF
WEATHER PROOF
TRANSFORMER
WATTS
WATER COLUMN
MOTOR OPERATED VALVE
EXISTING
TEMPERATURE
NAMEPLATE
FLOW ELEMENT (FLOW METER)
FLOW TOTALIZER INDICATOR
FLOW INDICATING RECORDER
FLOW INDICATING TRANSMITTER
FLARE
FLEXIBLE HOSE
FORWARD
FLOW RECORDER
FILTER REGULATOR
FAIL OPEN
PORT FILTER
FULL LOAD AMPS
FLOWLINE
FINISH GRADE
FLAME FAILURE ALARM
FLOW INDICATOR
OXYGEN ALARM HIGH HIGH
OXYGEN TRANSMITTER
OXYGEN INDICATING RECORDER
OXYGEN INDICATOR
OXYGEN ELEMENT
OVERLOAD
OXYGEN INDICATOR TRANSMITTER
OXYGEN SENSOR FAILURE
NOT TO SCALE
OPEN/CLOSE
OXYGEN
OXIDES OF NITROGEN
OXYGEN ANALYZER
OXYGEN ALARM HIGH
ON CENTER
FUSED DISCONNECT
FLOW CONTROL VALVE
FEEDER
FLOW ALARM LOW LOW
FAIL CLOSE
FLOW CONTROLLER
FURNISHED BY OTHERS
FILTER
FLOW ALARM HIGH HIGH
FLOW ALARM LOW
FLOW ALARM HIGH
FLAME ARRESTER
DEGREE FAHRENHEIT
EXPLOSION PROOF
NORMALLY OPEN TIMED TO CLOSE
NORMALLY CLOSED TIMED TO OPEN
NORMALLY CLOSED TIMED TO CLOSE
NORMALLY OPEN
NOT IN CONTRACT
NEGATIVE
NORMALLY OPEN TIMED TO OPEN
NEUTRAL BLOCK
NORMALLY CLOSED
NON-AUTOMATIC
MANWAY
MOUNTED
MAIN SWITCH BOARD
MOTOR STARTER
VIBRATION ALARM
VIBRATION INDICATING RECORDER
VIBRATION ALARM HIGH HIGH
VARIABLE FREQUENCY DRIVE
VIBRATION INDICATOR
VAPOR PROOF
VIBRATION SWITCH
VIBRATION ALARM HIGH
UNINTERRUPTIBLE POWER SUPPLY
TEMPERATURE TRANSMITTER
UNDERGROUND
VESSEL
ULTRAVIOLET SCANNER
TYPICAL
TOP OF WALL
TEMPERATURE SAFETY VALVE
TEMPERATURE SAFETY ELEMENT
TEMPERATURE SWITCH HIGH
TEMPERATURE SWITCH LOW
TEMPERATURE RECORDER
TIGHT SHUTOFF
TEMPERATURE SWITCH OR TOP OF SLAB
TIMER
TEMPERATURE INDICATOR RECORDER
TEMPERATURE ELEMENT WELL
TEMPERATURE ELEMENT SWITCH
TEMPERATURE INDICATOR
TEMPERATURE INDICATOR CONTROLLER
TEMPERATURE INDICATOR TRANSMITTER
THERMOSTAT
ELECTRICAL DISTRIBUTION PANEL
DIFFERENTIAL PRESSURE SWITCH
DIFFERENTIAL PRESSURE INDICATOR
ELECTRICAL METALLIC TUBING
VOLTAGE INDICATOR
EMERGENCY
EQUIPMENT
ENCLOSURE, ENCLOSED
ELAPSED TIME METER
EXHAUST
ELEVATION
DRAWING
VOLTAGE TRANSFORMER
ELECTRICAL MOTOR
DISCONNECT SWITCH
MANHOLE
METHANE INDICATOR
MODEM
METHANE INDICATING RECORDER
METHANE INDICATOR TRANSMITTER
MOTOR
MANUAL MOTOR STARTER
MINIMUM
METHANE ALARM LOW LOW
MOTOR CONTROL CENTER
MAIN CONTROL PANEL
THOUSAND CIRCULAR MILS
MAXIMUM
MANWAY
MAGNETIC
CONTROL VALVE (MODULATING)
CONTROL POWER TRANSFORMER
DISTRIBUTION
DAYLIGHT
CURRENT TRANSFORMER
DRYER
CURRENT SWITCH HIGH
METHANE ANALYZER
LUBRICATOR
METHANE ALARM LOW
MILLIAMPS
MOTOR
LIGHTING
LEVEL TRANSMITTER OR LIGHT(S)
LEVEL SWITCH LOW LOW
LEVEL SWITCH
LIGHTING PANEL
LOCK-OUT-STOP
LEVEL SWITCH LOW
LEVEL SWITCH HIGH HIGH
LEVEL SWITCH HIGH
LOCAL
TEMPERATURE ALARM LOW
TEMPERATURE ALARM LOW LOW
TEMPERATURE CONTROLLER POSITIONER
TEMPERATURE CONTROLLER OR TOP OF CURB
TEMPERATURE ELEMENT (THERMOCOUPLE)
TEMPERATURE CONTROL VALVE
TIME DELAY RELAY
TERMINAL BLOCK
TEMPERATURE ALARM HIGH HIGH
TEMPERATURE ALARM HIGH
TANK
TACHOMETER
STRAINER
SWITCH
SYSTEM
SURGE ARRESTOR
SHUNT TRIP
STATION
STANDARD
SOLENOID VALVE
SAMPLE PORT
STAINLESS STEEL
SPECIFICATION
SEQUENCE, SEQUENCER
SIGHT GLASS
SPEED INDICATOR
SHEET
SHIELD, SHIELDED
SUPPLEMENTAL FUEL
SENSOR FAILURE
MISCELLANEOUS SYMBOLS
RELAY FUNCTION DESIGNATIONS TYPES
CURRENT TRANSFORMER
ALUMINUM
KILOWATTS
COMBUSTIBLE GAS HIGH HIGH
COMBUSTIBLE GAS INDICATOR
CIRCUIT
CONDUIT ONLY
CHANNEL
LOWER EXPLOSIVE LIMIT
LEVEL GAGE
LANDFILL GAS
LUBE OIL
LEVEL ELEMENT
LATCHING CONTROL RELAY
LOCAL CONTROL PANEL
LAMP
LEVEL CONTROLLER HIGH
LEVEL CONTROLLER LOW
LEVEL CONTROLLER
LEVEL ALARM LOW LOW
LEVEL ALARM LOW
LEVEL ALARM HIGH HIGH
LEVEL ALARM HIGH
BARE COPPER
AUTOMATIC
BURNER ALARM LOW LOW
BLOWER
AMPERE TRIP
AMPERES, AMPERAGE
INSTRUMENT
KILOVOLTS
KILOVOLT AMPERES
TIME INDICATOR
CURRENT TRANSMITTER
SHORT CIRCUIT CURRENT
INVERT
CURRENT INDICATING RECORDER
IGNITOR
INSTRUMENT AIR SUPPLY
CURRENT ALARM LOW
CURRENT ALARM HIGH HIGH
CURRENT ALARM HIGH
INSTANTANEOUS
CURRENT ALARM LOW LOW
STANDARD CUBIC FEET PER MINUTE
SHUTDOWN OR ON
SECTION
SECONDARY, SECONDS
SHUTDOWN VALVE
SHUTDOWN OR STORM DRAIN
SCHEDULE
RETENTION TIME CALCULATOR
REVOLUTIONS PER MINUTE
RIGID GALVANIZED STEEL
AIR STRIPPER
RETENTION TIME
SPECTACLE BLIND
RELAY MODULE
RESISTOR
POLYVINYL CHLORIDE
RUPTURE DISK ALARM HIGH
RUPTURE DISK
RUPTURE DISK SWITCH
RECEPTACLE
TOTALIZER
POWER
REQUIRED
PRESSURE SAFETY ELEMENT
PRESSURE TRANSMITTER
POUNDS PER SQUARE INCH
PRESSURE RELIEF VALVE
PRESSURE SWITCH LOW
PRESSURE SWITCH HIGH
PRESSURE SWITCH
MISCELLANEOUS ABBREVIATIONS
ACTUAL CUBIC FEET PER MINUTE
ANALOG OUTPUT
ANALOG INPUT OUTPUT
ANALOG INPUT
ASPHALT CONCRETE OR AIR CONDITIONER
CURRENT INDICATOR
CURRENT
HAND VALVE PORT
HEAT TRACE
HAND VALVE
HEATER
HERTZ
HORSEPOWER OR HIGH POINT
HAND SWITCH
PROGRAMMABLE LOGIC CONTROLLER
POWER PANEL or POWER POLE
PRESSURE INDICATING RECORDER
POSITION, POSITIVE
POSITIONER
POTENTIOMETER
PANEL
PILOT
PIPING AND INSTRUMENTATION DIAGRAM
PRESSURE INDICATING CONTROLLER
INDUSTRIAL TECHNICAL CORPORATION
LEVEL INDICATOR
PUSH BUTTON
BUILDING PROTECTION SYSTEM
ACTUATOR
AUTO DIALER SYSTEM
AMPERE FRAME SIZE (CIRCUIT BREAKER)
ABOVE FINISH FLOOR
AMERICAN WIRE GAUGE
BATTERY
BURNER GLASS
BURNER ELEMENT (UV SCANNER)
BREAKER
BILL OF MATERIAL
BURNER SWITCH (FLAME SAFEGUARD)
BRITISH THERMAL UNIT
CONDUIT
CURRENT ALARM HIGH
CURRENT ALARM LOW
CABLE
CENTER TO CENTER
COMBUSTIBLE GAS HIGH
COMBUSTIBLE GAS TRANSMITTER
CHART RECORDER
CURRENT INDICATOR
COUNTER
COMMUNICATION
CONTROL PANEL OR CONTROL POINT
CHLORINATED POLYVINYL CHLORIDE
CONTROL RELAY
CARBON STEEL
CURRENT SWITCH LOW
COPPER
DIGITAL INPUT
DELTA OR DIFFERENTIAL PRESSURE
PLC CONTROLLED DEVICE
LOCALLY PANEL MOUNTED UNIT
INSTRUMENT MOUNTED BEHIND BOARD
CONTROL PANEL MOUNTED INSTRUMENT
LOCALLY MOUNTED INSTRUMENT
REMOTE CONTROL
REMOTE MONITORING
PILOT LIGHT (R=RED; G=GREEN; A=AMBER; B=BLUE;
INSTRUMENT MOUNTED BEHIND LOCAL BOARD
LOCAL BOARD MOUNTED INSTRUMENT
W=WHITE; C=CLEAR; N=NEON)
CONTROL PANEL MOUNTED INSTRUMENT
AUTO/MANUAL
LOCAL/REMOTE
HAND/OFF/AUTO
ANALOG/DIGITAL
CURRENT TO PNEUMATIC
DETAIL NUMBER
INTERLOCK IF ANY ONE OR MORE INPUTS EXIST
RESET FOR LATCH TYPE ACTUATOR
INTERLOCK
SOLENOID VALVE
INTERLOCK IF ALL INPUTS EXIST
SHEET NUMBER DETAIL IS DRAWN ON
I/P
A/M
A/D
L/R
HOA
S
I
R
AND
OR
PILOT TUBE OR PILOT VENTURI TUBE
PISTON OPERATED VALVE WITH HANDWHEEL,
SELF-CONTAINED PRESSURE CONTROL VALVE
HYDRAULIC OR PNEUMATIC (SPRING RETURN)
SOLENOID-OPERATED 2-WAY VALVE
INSTRUMENTATION DEVICES & ACCESSORIES
PNEUMATIC TRANSMISSION, INSTRUMENT AIR
SUPPLY AND/OR GAS SIGNAL, PIPE OR TUBING
ELECTRICAL TRANSMISSION
SOFTWARE COMMUNICATION LINK
CONNECTION TO PROCESS, MECHANICAL LINK
CONDENSATE TRANSMISSION PIPING
LINE & SIGNAL SYMBOLS
SIDE-MOUNTED
PISTON-OPERATED VALVE
SOLENOID-OPERATED 3-WAY VALVE
PRESSURE RELIEF VALVE OR VENT
PISTON-OPERATED VALVE WITH OPEN AND
CLOSED POSITION SWITCHES AND WITH
HANDWHEEL, SIDE MOUNTED
CONTROL VALVE WITH I/P TRANSDUCER
BUTTERFLY VALVE, HAND OPERATED
BALL VALVE, HAND OPERATED
NEEDLE VALVE, HAND OPERATED
HAND VALVE, HAND OPERATED
3-WAY HAND VALVE, HAND OPERATED
PRESSURE REGULATOR W/PRESSURE GAUGE
BUTTERFLY VALVE, AUTOMATED
GEAR OPERATOR
Y-STRAINER
PNEUMATIC POSITIONER
FLEX CONNECTOR
FLEX CONNECTOR WITH FLANGE CONNECTION
FLANGE CONNECTION
BLIND FLANGE
UNION
CAP OR PLUG
CONCENTRIC REDUCER
ECCENTRIC REDUCER
SAMPLE PORT
MANUAL ACTUATOR/OVERRIDEMA
G
S
S
PSV
G
ZSO ZSC
P
G
A
PI
WIRING SCHEMATIC SYMBOLS
CONTACT, N.C.
TIMED CONTACT (N.C.T.O.)
TIMED CONTACT (N.O.T.0.)
TIMED CONTACT (N.O.T.C.)
CONTACT, N.O.
TIMED CONTACT (N.C.T.C.)
COIL (RELAY, TIMER, ETC.)
LATCHING RELAY
PILOT LIGHT
PILOT LIGHT (PUSH TO TEST)
PILOT (DUAL INPUT)
SOLENOID VALVE COIL
BUZZER OR HORN
ELECTRONIC AUDIBLE DEVICE
OR ELAPSED TIME METER
PUSHBUTTON, N.O.
PUSHBUTTON, N.C.
PUSHBUTTON, MUSHROOM HEAD
PUSH-PULL UNIT
(MAINTAINED CONTACTS)
PUSHBUTTON (1=N.O.; 1=N.C.)
SELECTOR SWITCH (2-POSITION)
SELECTOR SWITCH (3-POSITION)
SELECTOR SWITCH (3-POSITION WITH
CENTER POSITION CONTACT CLOSURE)
PRESSURE SWITCH, CLOSE ON INCREASE
PRESSURE SWITCH, CLOSE ON DECREASE
TEMPERATURE SWITCH, CLOSE ON INCREASE
TEMPERATURE SWITCH, CLOSE ON DECREASE
LEVEL SWITCH, CLOSE ON RISE
LEVEL SWITCH, CLOSE ON DROP
FLOW SWITCH, CLOSE ON FLOW
FLOW SWITCH, OPEN ON FLOW
LIMIT SWITCH, N.O.
LIMIT SWITCH, N.O. HELD CLOSED
LIMIT SWITCH, N.C. HELD OPEN
LIMIT SWITCH, N.C.
FUSE
GROUND CONNECTION
JUNCTION
CONTROL PANEL TERMINAL
REMOTE PANEL TERMINAL
DISCONNECTING (ISOLATING) TERMINAL
CONTROL TRANSFORMER
IGNITER
U.V. FLAME SCANNER
THERMOCOUPLE
WIRES CROSSING, NO CONNECTION
WIRES CONNECTING
INTERNAL WIRING
FIELD WIRING
SHIELDED WIRES
(INDICATES GROUND WHEN REQUIRED)
LOCAL HAND/OFF SWITCH
SINGLE LINE DIAGRAMS
CIRCUIT BREAKER
TRANSFORMER
MOTOR STARTER
FUSED SWITCH
CMP or COMP
CV
CPT
DISTR
DL
CT
D
CSH
AL
CGHH
CGI
CIR
CO
CH
BC
AUTO
BALL
B
AT
AMP
ACFM
AOUT
AIO
AI
AC or A/C
BPS
A
ADS
AF
AFF
AWG
BATT
BG
BE
BKR
BOM
BS
BTU
C
CAH
CAL
CBL
CC
CGH
CGT
CHR
CI
CNT
COMM
CP
CPVC
CR
CS
CSL
CU
DI
DP
ETM
FALL
EXIST
F.C.
FCV
FAHH
FBO
FA
DWG
E
EMER
ENCL
EDP
DPI
DPS
E/E
EI
EL OR ELEV
EMT
EQPT
EXH
EXP
°F
FLT or F
FAH
FAL
FC
FD
DS
FDR
FE
FFA
FG
FI
FIR
FIT
FL
FLA
FLR
FX or FLEX
FLTP
F.O.
FOR
FQI
FR
FRG
FRL
FRP
FS
FSH
FSL
FSV
FT
FU
FUH
FUT
FV
GB
GF
GFI
GM
GND or GRND
HDPE
HOA
HP
HS
HT
HTR
HV
HVP
HZ
I
II
I/I
IAH
IAHH
IAL
IALL
IAS
IG or IGN
IIR
INST
INSTR
INV
ISC
IT
ITC
KI
KV
KVA
KW
LAH
LAHH
LAL
LALL
LC
LCH
LCL
LCP
LCR
LE
LEL
LFG
LG
LI
LMP
LO
LOC
LOS
LP
LS
LSH
LSHH
LSL
LSLL
LT
LTG
LUB
M
MA
M.A.
MAL
MALL
MAG
MAN
MAX
MCC
MCM
MCP
MH
MI
MIR
MIN
MIT
MMS
MOV
MS
MSB
MTD
M.W.
NA
NBK
N.C.
N.C.T.C.
N.C.T.O.
NEG
NIC
N.O.
N.O.T.C.
N.O.T.O.
NP
NTS
NOX
O O/C O.C.
OA
OAH
OAHH
OE
OI
OIR
OT
OIT
OSF
OL
PDI
PMP or P
PB
PA
PAH
PAHH
PAL
PALL
PC
PCV
PDI
PE
PG
PH
PI
P&ID
PIC
PIR
PLC
PLT
PNL
POS
POT
POZ
PP
PS
PSE
PSH
PSI
PSL
PT
PSV
PVC
PWR
QL
REQD
RD
RDAH
RDS
RECEPT
RES
RGS
RM
RPM
RT
RTC
S
SB
SCFM
SCH
SD
SD/O
SDV
SEC
SECT
SEL
SEQ
SF
SFR
SG
SHLD
SHT
SI
SPECS
SS
SSR
ST
STA
STD
STR
SW
SYS
T or TK
TACH
TAH
TAHH
TAL
TALL
TB
TC
TCV
TCZ
TD or TDR
TE
TEMP
TES
TEW
THERM
TI
TIC
TIR
TIT
TMR
TR
TS
TSE
TSH
TSL
TSO
TSV
TT
TW
TYP
UG
UPS
UV
V
VA
VAH
VAHH
VFD
VI
VIR
VP
VS
VSD
VSH
VT
W
W.C.
WP
XFMR
XP
YA
YI
YIC
ZA
ZC
ZI
ZS
ZSC
ZSO
MOT SP
MOD SOV
GRANULAR ACTIVATED CARBONGAC
PRESSURE INDICATING TRANSMITTERPIT
VARIABLE FREQUENCY DRIVE (VFD)
INTERNAL WIRE CONNECTION WITHIN DEVICE
ABBREVIATIONS
G-002
GAS COLLECTION AND CONTROL SYSTEMGCCS
BOTTOMBTM
POSITIONERZ
SYMBOLS AND
GAS HANDLING SKIDGHS
EXISTING GRADEEG
TEMPERATURE VALVETV
TOP OF FOOTINGTF
BOTTOM OF FOOTING OR BLIND FLANGEBF
FORCEMAINFM
DUAL CONTAINMENT PIPINGD/C
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 2-
G -0
.d w g
/1
8/
0:
:5 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
NONE
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
E4635 Johnny Gayman 2024
DEMOLITION/SALVAGE/RELOCATION CONSTRUCTION NOTES (PER SHEET C-101/C-102)
RELOCATE SEWAGE TANK AND DRAIN LINE TO FLARE STATION
RELOCATE PORTABLE STAIR CASES
REMOVE/DEMO 6' HIGH CHAIN LINK FENCE WITH 3-STRAND BARBED WIRE, GATES
RELOCATE CARGO AND STORAGE CONTAINERS, VARIOUS SIZES AND WEIGHTS PER PLAN
REMOVE/DEMO EXISTING CONCRETE SLABS/FOOTINGS (THICKNESS VARIES) AND CONDUITS
RELOCATE STORAGE CONTAINER TO FLARE STATION OR AREA DESIGNATED BY COUNTY
PROTECT EXISTING STRUCTURE/PIPE IN PLACE
DESCRIPTION# QTY (OR APPROVED EQUAL) REFERENCE NOTES
RELOCATE COUNTY OPERATION'S TRAILER (12' X 40') TO FLARE STATION 1 EA EXISTING SEE C-101/M-101 CONNECT ALL UILITIES
1 EA EXISTING SEE C-101/M-101 CONNECT WITH 3" LINE TO TRAILER
3 EA EXISTING SEE C-101/M-101 -
5 EA EXISTING SEE C-101/M-101 -
1 EA EXISTING SEE C-101/M-101 AFTER NEW FLARE STATION IS OPERATIONAL
AS REQ'D EXISTING SEE C-102 PREVIOUS POWER PLANT CONDUITS NOT SHOWN
400 LF EXISTING SEE C-102 -
4 EA EXISTING SEE C-102/M-101 -
AS REQ'D - SEE C-102/C502
AS REQ'D - - -
120 LF - -
IF ENCOUNTERED DURING GRADING/EARTHWORK
AS REQ'D EXISTING
30 LF EXISTING - -
SUPPLIER OR MFR. DETAIL/SHEET
PART NO.
MODEL OR
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
2 EA - -
EXISTING
EXISTING
EXISTING
EXISTING
REMOVE EXISTING 24" STORM DRAIN LINE/BURIED HEADWALL11
PLUG/GROUT END OF EXISTING 24" STORM DRAIN LINE12
SAWCUT AND REMOVE SECTION OF AC BERM14
INSTALL 12" CONCRETE AROUND OUTLET GRATE
- -20 LF ISCO INDUSTRIES - -
4 EA ISCO INDUSTRIES - GHS-1/GHS-2 DRAIN AND SUMP BALANCE LINES
10 EA GRAINGER PER DETAIL 1/C-302 GHS-2 DRAIN LINE CONNECTION
8 EA PER DETAIL 8/C-501 -
SITE IMPROVEMENTS/GRADING/FIELD PIPING CONSTRUCTION NOTES (C-103, C-301, C-302, C-501, C-502, C-503)
CONSTRUCT 6" AC PAVEMENT OVER 12" CLASS 2 BASE
CONSTRUCT 6" THICK CONCRETE V-DITCH, APPROX. 5' WIDE, DEPTH VARIES
INSTALL 6" ATRIUM STYLE INLET GRATE
INSTALL 6" SINGLE WALL DRAIN PIPE, HDPE
SAWCUT AND REMOVE AC PAVEMENT SECTION
9,550 SF CONTRACTOR OR SUB SEE DWG C-103/C-105
11 CY CONTRACTOR OR SUB SEE DETAIL 2/C-501 WITH 6x6 W1.4/1.4 WWM
100 LF ADVANCED DRAINAGE SYS SEE DWG C-103 DRAINAGE SWALE DRAIN PIPE
1 EA LOCAL SUPPLIER SEE DWG C-103 V-DITCH INLET STRUCTURE
2,000 SF CONTRACTOR OR SUB SEE DWG C-103/C-105 SEE DETAILS 6 & 7/C-501
PER PLAN
PER PLAN
INSTALL 1" SDR 11 HDPE PIPE & FITTINGS
INSTALL 2" HDPE SADDLE
INSTALL 2" SS CHECK VALVE, Y SPRING TYPE
INSTALL 6" STEEL BOLLARD AND PLASTIC SLEEVE
6 EA --61 INSTALL 2" X 1" HDPE REDUCER
6 EA --62 INSTALL 1" HDPE TO SS TRANSITION FITTING
6 EA --63 INSTALL 1" SS COUPLING
2 EA --64 INSTALL 1" X 3/4" SS REDUCER BUSHING
4 EA --65 INSTALL 1" X 1/2" SS REDUCER BUSHING
66 INSTALL 3/4" SS PIPE NIPPLE
CUSTOM
ISCO INDUSTRIES
ISCO INDUSTRIES
GRAINGER
GRAINGER
GRAINGER
GRAINGER2 EA
67 INSTALL 1/2" SS PIPE NIPPLE
68 INSTALL 4" X 2" HDPE D/C TERMINATION FITTING
69 INSTALL 8" X 4" HDPE D/C TERMINATION FITTING
GRAINGER4 EA --
ISCO INDUSTRIES6 EA --
ISCO INDUSTRIES6 EA --
ISCO INDUSTRIES6 EA --
ISCO INDUSTRIES6 EA --
72 INSTALL 4" HDPE BALL VALVE, BUTT X BUTT ISCO INDUSTRIES1 EA --
SUMP CONNECTION AND SUMP BALANCE LINES
SUMP CONNECTION
SUMP CONNECTION
SUMP LIQUID DISCHARGE CONNECTION
SUMP AIR & BALANCE LINE CONNECTION
4" CONDENSATE LINE CLEAN-OUT
73 INSTALL 30" SDR 17 HDPE PIPE ISCO INDUSTRIES80 LF SEE DETAIL 6/C-501-
74 INSTALL 30" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, AND HARDWARE ISCO INDUSTRIES3 ASSY --
INSTALL 30" X 24" HDPE REDUCER
ISCO INDUSTRIES
2 EA
INSTALL 24" X 18" HDPE REDUCER
ISCO INDUSTRIES
2 EA
INSTALL 18" X 12" HDPE REDUCER
ISCO INDUSTRIES
4 EA
INSTALL 18" SDR 17 HDPE PIPE
ISCO INDUSTRIES
100 LF
INSTALL 18" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, AND HARDWARE
ISCO INDUSTRIES
4 EA
INSTALL 18" HDPE ELBOW, 90°, SDR 17
ISCO INDUSTRIES
2 EA
SEE DETAIL 7/C-501-
81 ISCO INDUSTRIES --
82 ISCO INDUSTRIES --
INSTALL 30" HDPE TEE, SDR 17
INSTALL 30" HDPE ELBOW, 90°, SDR 17 2 EA
1 EA
INSTALL 2" SDR 11 HDPE x 4" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS 140 LF83 ISCO INDUSTRIES -
INSTALL 4" SDR 11 HDPE x 8" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS 220 LF84 ISCO INDUSTRIES -
INSTALL SALVAGED 12" BUTTERFLY VALVE 2 EA85 - -
(DELETED) -86 - -
SEE DETAILS 6 & 7/C-501
INSTALL 24" SDR 17 HDPE PIPE
INSTALL 12" SDR 17 HDPE PIPE
INSTALL 2" SDR 9 HDPE PIPE & FITTINGS
INSTALL 2" SDR 11 HDPE PIPE & FITTINGS
INSTALL 1 1/2" DOUBLE CHECK VALVE ASSEMBLY PER SAN BERNARDINO COUNTY STANDARDS
100 LF ISCO INDUSTRIES
20 LF ISCO INDUSTRIES
200 LF ISCO INDUSTRIES
40 LF ISCO INDUSTRIES
1 ASSY
SEE DETAIL 10/C-501 UNIT #4 HEADER
- INLET TO GHS-2
- COMPRESSED AIR LINE
- CONDENSATE FORCEMAIN
INSTALL 24" BUTTERFLY VALVE WITH 3' VALVE EXTENSION AND GEAR OPERATOR 1 ASSY -
INSTALL 24" HDPE TEE, SDR 17 1 EA ISCO INDUSTRIES -
INSTALL 24" HDPE ELBOW, 90°, SDR 17 2 EA ISCO INDUSTRIES -
INSTALL 24" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT 5 EA ISCO INDUSTRIES -
INSTALL 24" PVC BLIND FLANGE 1 EA ISCO INDUSTRIES UNIT #4 HEADER
5 EA CUSTOM SEE DETAIL 2/C-502 SUMP OUTLET PIPING
3 EA ISCO INDUSTRIES -
4 EA ISCO INDUSTRIES -
550 LF - WATER LINE FOR SWMD TRAILER
INSTALL 2" HDPE BALL VALVE, BUTT X BUTT 11 EA ISCO INDUSTRIES CONDENSATE FORCEMAIN, 2" CLEAN-OUT
JOIN EXISTING 6" WATER LINE PER SAN BERNARDINO COUNTY STANDARDS 1 EA - SEE DETAIL 2/C-503 -
SEE WALL PROFILES, C-201/C-202
INSTALL 2" HDPE TO STAINLESS STEEL TRANSITION FITTING (BUTT x MPT) 20 EA ISCO INDUSTRIES SEE DETAIL 1/C-301/302 CONDENSATE FORCEMAIN CHECK VALVES
1 ASSY REAL ENV. PRODUCTS SEE DWG C-301/D-601 -
INSTALL CONDENSATE SUMP ASSEMBLY "B", SERIES 7000 SUMP, 18" X 24" DUAL CONTAINED 1 ASSY REAL ENV. PRODUCTS SEE DWG C-302/D-601 -
SITE IMPROVEMENTS/GRADING/FIELD PIPING CONSTRUCTION NOTES (C-103, C-104. C-301, C-302, C-501, C-502)
ISCO INDUSTRIES
INSTALL PIPE SUPPORT, CONCRETE FOOTING AND SIGN
INSTALL 12" HDPE ELBOW, 90°, SDR 17
INSTALL 12" HDPE FLANGE ADAPTER, D.I, BACK-UP RING, GASKET, AND BOLT KIT
INSTALL 1 1/2" CLASS 150 PVC WATER PIPE & FITTINGS
SEE SHEET C-503
PER PLAN
PER PLAN
JOIN EXISTING AS REQ'D -
INSTALL 6" AC BERM
GRADE AREA TO CONTOURS SHOWN (PRIMARILY CUT TO INSTALL FOOTINGS & WALLS)
55 LF CONTRACTOR OR SUB SEE DWG C-103
PER PLAN CONTRACTOR OR SUB SEE DWG C-103
1 EA ISCO INDUSTRIES
COORDINATE WITH COUNTY/SCE
PER PLAN
AS REQ'D -
INSTALL CONDENSATE SUMP ASSEMBLY "A", SERIES 7000 SUMP, 30" X 36" DUAL CONTAINED
EXISTING HIGH VOLTAGE POWER POLE(S) TO BE REMOVED BY OTHERS
SEE DETAIL 3/C-503
(DELETED)
INSTALL 12" 22 1/2° HDPE ELBOW, SDR 17
SEE SUMP "A" AND GHS-1 INLET PIPING PROFILE
SEE SUMP "B" AND GHS-2 INLET PIPING PROFILE
SEE DETAIL 1/C-301
SEE DETAIL 1/C-302
INSTALL 4" X 2" HDPE REDUCER, SDR 11 5 EA ISCO INDUSTRIES
DESCRIPTION# QTY (OR APPROVED EQUAL) REFERENCE NOTES
SUPPLIER OR MFR. DETAIL/SHEET
PART NO.
MODEL OR
DESCRIPTION# QTY (OR APPROVED EQUAL) REFERENCE NOTES
SUPPLIER OR MFR. DETAIL/SHEET
PART NO.
MODEL OR
CONDENSATE FORCEMAIN
SUMP AIR & BALANCE LINE CONNECTION
SUMP LIQUID DISCHARGE CONNECTION
INSTALL 4" X 2" HDPE D/C 45° WYE FITTING
INSTALL 8" X 4" HDPE D/C 45° WYE FITTING
ESTIMATED ESTIMATED
INSTALL 1 1/2" CLASS 150 PVC BALL VALVE, NSF/ANSI 61 STANDARD AND HOSE BIB 1 ASSY87 HAYWARD OR EQUAL -
INSTALL WATER LINE THRUST BLOCK88 2 EA - - SEE DETAIL 1/C-503
REMOVE/SALVAGE EXISTING SUMP, VALVES, PIPE, AND FITTINGS AFTER NEW FLARE STATION IS OPERATIONAL
INSTALL 6" MITERED DRAINAGE GRATE (JOIN WITH FERNCO COUPLING) 1 EA DRAINAGE SOLUTIONS 6MD3P
RELOCATE EXISTING FLARE STATION O&M TRAILER TO NEW FLARE STATION COMPOUND
DEMOLITION AND DISPOSAL OF THE EXISTING FLARE STATION: INCLUDES ALL CONCRETE
SLABS, FOOTINGS, WALLS, FENCING, FLARE STACKS, INTERCONNECT GAS SYSTEM PIPING
AND FITTINGS (ABOVE AND BELOW GRADE), PIPE SUPPORTS AND FOOTINGS,
INSTRUMENTATION, COMPRESSORS, COMPRESSED AIR LINES (ABOVE AND BELOW GRADE),
CONDENSATE DRAIN LINES (ABOVE AND BELOW GRADE), CONDENSATE INJECTION SYSTEM
(ABOVE AND BELOW GRADE), FLARE PILOT FUEL SYSTEM (PROPANE, ABOVE AND BELOW
GRADE), CONDENSATE STORAGE TANK, PUMPS, BLOWERS, KNOCK-OUT VESSEL, VALVES,
ELECTRICAL PANELS, CONDUITS (ABOVE AND BELOW GRADE), WIRING, AND SWITCHGEAR
AS DIRECTED BY THE COUNTY. SALVAGE BLOWERS AND ANY OTHER ITEMS AT THE
DISCRETION OF THE COUNTY.
REMOVAL OF EQUIPMENT FROM FLARE STATION
SHALL BE COMPLETED AFTER THE NEW FLARE
STATION IS OPERATIONAL, INCLUDING SOURCE
TESTING. THE COUNTY WILL DETERMINE IF ANY
OF THE EXISTING FLARE STATION EQUIPMENT IS
SALVAGEABLE FOR COUNTY PURPOSES PRIOR
TO DISPOSAL/REMOVAL. THE COUNTY WILL
ASSIGN AN AREA NEAR THE FLARE STATION FOR
EQUIPMENT STORAGE.
SEE SHEET C-102 FOR
EXISTING FLARE
STATION AREA
AS REQ'D EXISTING - --EXISTING TELEPHONE LINE TO BE REMOVED FROM POWER POLE BY OTHERS15
DEMOLITION/SALVAGE/
SITE IMPROVEMENTS
CONSTRUCTION NOTES
G-003 NONE
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 3-
G -0
.d w g
/1
8/
0:
:5 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
FLARE STATION CONSTRUCTION NOTES (M-101, M-501, M-502)
INSTALL/ANCHOR GAS HANDLING SKID (GHS-1) WITH EPOXY ANCHORS
INSTALL/ANCHOR GAS HANDLING SKID (GHS-2) WITH EPOXY ANCHORS
INSTALL/ANCHOR 5,000 SCFM LOW NOx FLARE STACK AND COMBUSTION AIR BLOWER
INSTALL SALVAGED SEPTIC TANK AND TRAILER DRAIN LINE (HOLE THROUGH WALL)
INSTALL/ANCHOR 1,000 SCFM LOW NOx FLARE STACK AND COMBUSTION AIR BLOWER
INSTALL INTERCONNECT PIPING, VALVES, EQUIPMENT
INSTALL 40'W x 40'L x 14'-8"H PRE-FABRICATED ROOF STRUCTURE
INSTALL 55 GALLON GRANULAR ACTIVATED CARBON DRUM AND 4X8 COCONUT CARBON
INSTALL LED AREA FLOOD LIGHT (2 PER POLE)
DESCRIPTION# QTY MANUFACTURER REFERENCE NOTES
INSTALL/ANCHOR ROTARY SCREW COMPRESSOR, DRYER, OIL/WATER SEPARATOR 2 ASSY SUPPLIED BY P.E.I./KAISHAN SEE P.E.I. REF. DWGS ANCHOR PER
1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS ANCHOR PER
1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS ANCHOR PER
1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS FLR-2
1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS FLR-1
- SUPPLIED BY P.E.I. -
1 ASSY EXISTING - -
1 ASSY EMPIRE STEEL OR EQUAL SEE SHEET S-303/M-503 -
1 EA TETRASOLV FILTRATION - V-3 (TK-701 VENT STACK)
12 EA E-CONOLIGHT SEE SHEET M-101/E-101 -
6 EA SEE SHEET M-101/E-101 -
VARIOUS DURALABEL SEE DETAIL 3/M-502 -
1 ASSY CONTRACTOR OR SUB SEE STRUCTURAL DWGS SEE SHEETS C-201, C-202
20 LF - - COMPRESSED AIR @ FLARES
110 LF - - FLARE PILOT LINES
150 LF - - FLARE CONDENSATE INJECTION
120 LF HARRINGTON PLASTICS - PIPING BETWEEN TK-701/PMP-701/702
SUPPLIER OR DETAIL/SHEET
PART NO.
MODEL OR
CUSTOM FABRICATION
CUSTOM FABRICATION
EXISTING
VFV-250
E-FFA26 SERIES
E-PS4E20SDB
KRSB-40
CUSTOM FABRICATION
CUSTOM FABRICATION
CUSTOM FABRICATION
CUSTOM FABRICATION
E-CONOLIGHTINSTALL 4" SQUARE STEEL POLE, FLOOD LIGHT
6 EA E-CONOLIGHTINSTALL BULLHORN, FLOOD LIGHT SEE SHEET M-101/E-101E-PT2E180DB
INSTALL PIPE AND EQUIPMENT LABELS, 3.2MM THICK ADHESIVE
INSTALL 1/2" GALVANIZED STEEL PIPE & FITTINGS (COMPRESSED AIR)
INSTALL 1/2" SCH 40 STAINLESS STEEL PIPE & FITTINGS (CONDENSATE INJECTION)
INSTALL STRUCTURAL SLAB, BLOCK WALL, FOOTINGS, PILASTERS, PADS, ETC.
INSTALL 1" SCH 80 PVC PIPE & FITTINGS
VARIOUS
140 LF - - --INSTALL 1" SCH 40 GALVANIZED STEEL PIPE & FITTINGS (COMPRESSED AIR)
- - SEE DETAIL 5/M-501 --
INSTALL 2" SDR 9 HDPE PIPE & FITTINGS (COMPRESSED AIR) 60 LF ISCO INDUSTRIES - PIPING FROM PMP-701/702 TO FIELD-
INSTALL 2" SDR 11 HDPE PIPE & FITTINGS (CONDENSATE) 100 LF ISCO INDUSTRIES - KNOCK-OUT DRAIN LINES-
INSTALL 2" SCH 80 PVC PIPE & FITTINGS (VENT PIPING, DRAIN LINES)
INSTALL 1/2" SCH 40 BLACK IRON PIPE & FITTINGS (PROPANE)
INSTALL 8" SQUARE METAL SIGN, WHITE BACKGROUND, BLACK LETTERING, 1/2" MIN.
INSTALL TK-701 DRAIN AND CONDENSATE FM ON WALL
INSTALL 12" SDR 17 HDPE PIPE
INSTALL 12" SCH 10 304SS PIPE
INSTALL 24" SDR 17 HDPE PIPE
INSTALL PIPE SUPPORT RACK
50 LF HARRINGTON PLASTICS
3 EA LOCAL SIGN COMPANY
50 LF ISCO INDUSTRIES
40 LF -
30 LF ISCO INDUSTRIES
1 ASSY CONTRACTOR
- TK-701/GAC VENT PIPING-
SEE DETAIL 4&5/M-501 MOUNT W ITH SCREWSCUSTOM FABRICATION
SEE DETAIL 6/M-501 --
- GHS-2 INLET PIPING/INTERCONNECT-
- DISCHARGE PIPING TO POWER PLANT-
- GHS-1 INLETE PIPING-
DETAIL 1/M-501 TK-701 PIPE RACKCUSTOM FABRICATION
INSTALL SMALL PIPE SUPPORT AND CONCRETE FOOTING 1 EA CONTRACTOR TK-701 DRAIN
INSTALL SMALL CONDUIT/PIPE ANCHOR AS REQ'D CONTRACTOR -
INSTALL PIPE SUPPORT 3 EA CONTRACTOR TK-701 DRAIN AND INLET LINES
INSTALL SIGN, 7" X 10" (DANGER-NO SMOKING, MATCHES, OR OPEN LIGHTS) 3 EA McMASTER CARR FASTEN TO WALL
INSTALL 3/8"Ø X 6" LONG CONCRETE ANCHOR AS REQ'D SIMPSON -
INSTALL LEVEL TRANSMITTER (0-14'), STANDARD ACCURACY, 4-20mA OUT, 24VDC, 40' CABLE 1 EA KELLER AMERICA DETAIL 1/M-501 LT-701 @ TK-70181355
CAMERA, NETWORK,1080P FULL HD, 20X ZOOM, NEMA 4X, 60W UPoE 4 EA VIVOTEK - -SD9361-EHL
INSTALL CABLE RAMP, 3' WIDE X 2' LONG (4" X 4" CHANNEL), ALUMINUM, DIAMOND PLATE 2 EA MCMASTER CARR M-101 -2233T75
INSTALL PORTABLE EMERGENCY EYEWASH STATION (MOUNT TO BLOCK WALL) 1 EA McMASTER CARR M-101 -54285T16
INSTALL FIRE EXTINGUISHER, 5 LB CLASS A,B,C, MOUNTING BRACKET 1 EA McMASTER CARR M-101 -6430T16
RELOCATE EXISTING TRAILERS/STORAGE CONTAINERS PER ASSEMBLY PLAN 7 EA EXISTING C-102/M-101 COORDINATE WITH COUNTYEXISTING
INSTALL 8700 GALLON POLY CONDENSATE TANK, DOUBLE WALL, WITH APPURTENANCES 1 ASSY POLY PROCESSING/CORE-ROSION SEE D-601 WITH FITTINGS, TK-701ASSEMBLY 1
INSTALL AUTOMATIC SLIDING GATE OPENER, 1 1/4 HP MOTOR, UP TO 40' LENGTH, 5700 LBS 1 ASSY TOPENS WITH TKPS WIRELESS KEYPAD AND (4) M12 REMOTE CONTROLSCK2600
INSTALL 3/8"Ø X 4" LONG CONCRETE ANCHOR AS REQ'D SIMPSON - -TITEN HD
INSTALL POST BASE, 1 5/8" X 1 5/8", GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --
INSTALL STRUT CHANNEL, 1 5/8" X 1 5/8", 0.105 , GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --
INSTALL STRUT CHANNEL, 1 5/8" X 3 1/4", 0.105, GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --
INSTALL PIPE CLAMP, STRUT CHANNEL, GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - -SIZE VARIES
INSTALL PLASTIC STRUT CHANNEL END CAP, 1 5/8" X 1 5/8" AS REQ'D ACME CONSTRUCTION SUPPLY - --
AS REQ'D ACME CONSTRUCTION SUPPLY - --
INSTALL STRUT CHANNEL "L" BRACKET FITTING, GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --
INSTALL STRUT CHANNEL FLAT "T" FITTING, GALVANIZED 4 EA ACME CONSTRUCTION SUPPLY - --
2 EA ACME CONSTRUCTION SUPPLY - --
INSTALL 2" PVC BALL VALVE, TRUE UNION, S xS 3 EA HARRINGTON PLASTICS - --
AS REQ'D - - ALL EXPOSED CONDENSATE LINES-
2 EA - -HARRINGTON PLASTICS - GAC INLET & OUTLET-
AS REQ'D ASAHI --
1 EA GROTH SEE DETAIL 1/M-501 TANK VENT7622B
6 EA HARRINGTON PLASTCIS - GAC INLET & OUTLET, TANK VENT-
3 EA EXISTING PER SHEET M-101 LEVEL AND SET WITH TRAILEREXISTING
DETAIL 2/M-501CUSTOM FABRICATION
DETAIL 3/M-501CUSTOM FABRICATION
DETAIL 4/M-501CUSTOM FABRICATION
DETAIL 1/M-50257235T75
-TITEN HD
INSTALL PLASTIC STRUT CHANNEL END CAP, 1 5/8" X 3 1/4"
INSTALL POST BASE, 1 5/8" X 3 1/4", GALVANIZED
INSTALL PIPE INSULATION
INSTALL 2" PVC UNION, S x S
INSTALL 1/4" LABCOCK VALVE, MPT X HOSE
INSTALL 2" STAINLESS STEEL FLAME CHECK
FLARE STATION CONSTRUCTION NOTES (M-101, M-501, M-502)
INSTALL 8" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT
INSTALL 12" x 8" HDPE REDUCER
INSTALL 12" BUTTERFLY VALVE, SS DISK & STEM, VITON SEALS AND SEATS, GEAR OP
INSTALL 12" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT
INSTALL 24" X 18" HDPE REDUCER
DESCRIPTION# QTY MANUFACTURER REFERENCE NOTES
TK-701 DRAIN LINE
3 EA ISCO INDUSTRIES - CONDENSATE SYSTEM
2 EA LOCAL SUPPLIER - FLARE PILOT FUEL @ GHS-1
AS REQ'D ISCO INDUSTRIES - -
1 EA ISCO INDUSTRIES - GHS-1/GHS-2 INLET INTERCONNECT
1 EA ISCO INDUSTRIES - GHS-2 INLET CONNECTION
1 EA ISCO INDUSTRIES -
1 EA ISCO INDUSTRIES -
2 ASSY ISCO INDUSTRIES -
2 EA ISCO INDUSTRIES - GHS-1 INLET PIPING
2 EA -
SEE BASE PLATES PER 1/S-502
1 ASSY ISCO INDUSTRIES - GHS-1 CONNECTION
4 EA - - DISCHARGE PIPING TO POWER PLANT
1 ASSY CUSTOM FABRICATION - WITH LOCKING MECHANISM
1 ASSY CUSTOM FABRICATION SEE DETAIL 2/M-502 AND DETAILS 4,5,6,7/S-504
4 EA - -
12 EA SIMPSON - BLOWER SKID ANCHORING
SUPPLIER OR DETAIL/SHEET
PART NO.
MODEL OR
ISCO INDUSTRIESINSTALL 18" X 12" HDPE REDUCER
13 EA CUSTOM FABRICATIONINSTALL PIPE SUPPORT RACK SEE DETAIL 1/S-506
INSTALL 3' X 8' CHAIN LINK FENCE MAN GATE WITH TAN PLASTIC SLATS
INSTALL 12" STAINLESS STEEL ELBOW, SCH 10S
INSTALL 12" 150# STAINLESS STEEL FLANGE, WELD NECK OR SOCKET WELD, SHORT
INSTALL 3/4"Ø ALL-THREAD RODS WITH SIMPSON SET-3G EPOXY, 6" MINIMUM EMDEDMENT
- - - -(DELETED)
1 ASSY EATON OR EQUAL
INSTALL 1" STAINLESS STEEL BALL VALVE, NPT 2 EA - - -
INSTALL PRESSURE TRANSMITTER, 0-200 PSIG, 4-20Ma OUTPUT, 9 TO 36 VDC, 1/4" 1 EA AUTOMATION DIRECT - COMPRESSOR DISCHARGE (PT-401)
INSTALL 2-10'± CHAIN LINK FENCE GATES WITH TAN PLASTIC SLATS
INSTALL 22' WIDE X 8' TALL SLIDING GATE AND APPURTENANCES
INSTALL 2,000 AMP/480V ELECTRICAL SWITCHGEAR, 3 SECTION
INSTALL/ANCHOR 24" PIPE SUPPORT
INSTALL ALUMINUM PLATFORM WITH STAIRS, HANDRAILS, PLATFORM, AND SUPPORTS
INSTALL 24" HDPE TEE, SDR 17
INSTALL 1/2"Ø ALL-THREAD RODS WITH SIMPSON SET-3G EPOXY, 6" MINIMUM EMBEDMENT
1 ASSY CUSTOM
2 EA
5 EA
2 EA CUSTOM
1 ASSY MCMASTER CARR
1 EA ISCO INDUSTRIES
8 EA SIMPSON
- WITH LOCKING MECHANISM
GHS-2 OUTLET
GHS-2 INLET PIPING
SEE DETAIL 5/S-505 GHS-1 INLET PIPING
- GHS-1 INLET PIPING
- COMPRESSOR ANCHORS-
2 ASSY BY CONTRACTOR
PURCHASED BY COUNTY (LONG-LEAD ITEM)
SPT25-20-0299D
4198N42(2), 4198N62(2), 4198N52, 4198N72
SEE P.E.I. REF. DWGS
INSTALL 2" PVC MALE ADAPTER, MPT x SOC
(DELETED)
INSTALL TRAILER STAIRCASES
INSTALL 2" PVC CAMLOCK AND PLUG 2 EA HARRINGTON PLASTICS SEE P.E.I. REF. DWGS
INSTALL 2" HDPE BALL VALVE, BUTT x BUTT
INSTALL 5 GALLON PROPANE BOTTLE
INSTALL 2" HDPE TO STAINLESS STEEL TRANSITION FITTING, BUTT x MPT
INSTALL 12" HDPE TEE, SDR 17
CUSTOM SEE DETAIL 3/S-505
CUSTOM SEE DETAIL 4/S-505
INSTALL/ANCHOR 8" PIPE SUPPORT
INSTALL/ANCHOR 12" PIPE SUPPORT
27"H X 24"W, 60" PLATFORM
SEE DETAIL 1/E-502
INSTALL 12" PE-RT ELECTRO-FUSION COUPLING
INSTALL 18" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT
GAC INLET & OUTLET
- GHS-2 INLET CONNECTION
GHS-1/GHS-2 INLET INTERCONNECT
GHS-1/GHS-2 INTERCONNECT VALVE
GHS-1/GHS-2 INLET PIPING
DISCHARGE PIPING TO POWER PLANT
ESTIMATED
INSTALL 2" AIR AND CONDENSATE DRAIN LINES ON WALL
ESTIMATED
1 ASSY OLDCASTLE PRECAST OR EQUAL191 INSTALL 4' X 6' PRE-CAST PME CONCRETE SLAB (SCE SWITCH PAD)
1 ASSY OLDCASTLE PRECAST OR EQUAL192 INSTALL 10' X 12' PRE-CAST CONCRETE SLAB AND BOX (SCE TRANSFORMER PAD/BOX)
- VERIFY WITH SCE DESIGNSCE APPROVED
- VERIFY WITH SCE DESIGNSCE APPROVED
FLARE STATION
CONSTRUCTION NOTES
G-004
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 4-
G -0
.d w g
/1
8/
0:
:0 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
NONE
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
S D
S D
120/240V/1Ø
100 AMP
24"
UNIT #4
UNIT #1
UNIT #3 UNIT #2
UNIT #5
PROPOSED NEW FLARE
STATION LOCATION
PROPOSED RENEWABLE
ENERGY PLANT LOCATIONEXISTING FLARE
STATION LOCATION
SCALE HOUSE
CONTROL POINT 26
N 1874864.4010 E 6737564.6290
ELEV.=1568.80
MID-VALLEY LANDFILL
EXISTING LANDFILL
OPERATIONS COMPOUND
CONTROL POINT 20
N 1872967.9410 E 6733650.6400
ELEV.=1548.67
A
LD
E R
A V
E
M A
N G
O A
V E
CASMALIA ST.
LOCATION OF EXISTING
OR PROPOSED COUNTY
TRAILER AND TWO (2)
STORAGE CONTAINERS
1 2 3 4
CONTROL POINT 41
N 1874994.5390 E 6735079.7580
ELEV.=1593.31
210 FREEWAY
TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT.
RELOCATE EXISTING SEWAGE TANK AND DRAIN LINE TO FLARE STATION
RELOCATE EXISTING PORTABLE STAIR CASES TO FLARE STATION
RELOCATE EXISTING CARGO AND CARGO CONTAINERS TO FLARE STATION
RELOCATE EXISTING COUNTY OPERATION'S TRAILER (12' X 40') TO FLARE STATION 1
CONSTRUCTION NOTES
RELOCATE EXISTING STORAGE CONTAINERS TO NEW FLARE STATION8 OR AREA DESIGNATED BY COUNTY
RELOCATE EXISTING FLARE STATION O&M TRAILER AND APPURTENANCES
TO NEW FLARE STATION OR AREA DESIGNATED BY COUNTY
SITE PLAN/SURVEY CONTROL/
RELOCATION PLAN
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 5-
C -1
.d w g
/1
8/
0:
:1 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
C-101 1"=300' 5
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
FUTURE RENEWABLE ENERGY POWER PLANT AREA
EXISTING
FLARE
STATION
UNIT #2
ACCESS ROAD
EXISTING OPERATIONS COMPOUND
STORAGE CONTAINER
EDGE OF SLAB
AC PAVEMENT
INLET STRUCTURE
AC CURB FOR 14
7 10
WIDTH TO MATCH
NEW DRIVE ENTRANCE
PER SHEET C-103
EXISTING INLET
STRUCTURE
B-9 B-6
B-10
B-7
FORMER POWER PLANT AREA
UNIT #4
E
E
E
E S
D S
D S
D S
D S
D S
D S
D S
D S
D S
D S
D S
D S
D S
D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
120/240V/1Ø
100 AMP
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
24"
E E E
PP
PP
SLAB
(UNDER CONSTRUCTION)
MAIN ACCESS ROAD (PAVED)
W W
E
E E
EXISTING 6" WATER LINE
O/H ELEC
O/H ELEC
WATER LINE
POWER PLANT UTILITY TRENCH 10
TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT AND SURVEY PERFORMED BY TETRA TECH ON
4/3/2022 AT FLARE STATION AREA.
TEST BORING LOCATION (FORMER POWER PLANT PROJECT)
LEGEND
B-1
X X EXISTING CHAIN LINK FENCE
SD EXISTING STORM DRAIN LINE
EXISTING STREET LIGHT FIXTURE
E EXISTING OVERHEAD ELECTRICAL AND POWER POLE (PP)
PP
REMOVE/DEMO 6' HIGH CHAIN LINK FENCE WITH 3-STRAND BARBED WIRE, GATES
REMOVE/DEMO EXISTING CONCRETE SLABS/FOOTINGS (THICKNESS VARIES) AND CONDUITS
PROTECT EXISTING STRUCTURE/PIPE IN PLACE
REMOVE EXISTING 24" STORM DRAIN LINE/BURIED HEADWALL11
PLUG/GROUT END OF EXISTING 24" STORM DRAIN LINE12
SAWCUT AND REMOVE SECTION OF AC BERM
CONSTRUCTION NOTES
15 EXISTING TELEPHONE LINE TO BE REMOVED FROM POWER POLE BY OTHERS
RELOCATE EXISTING STORAGE CONTAINERS TO NEW FLARE STATION AREA OR AREA DESIGNATED BY COUNTY8
REMOVE/SALVAGE EXISTING CONDENSATE SUMP, VALVES, PIPES, AND FITTINGS9
RELOCATE EXISTING FLARE STATION O&M TRAILER AND APPURTENANCES TO NEW FLARE STATION5 OR AREA DESIGNATED BY COUNTY
EXISTING POWER PLANT UTILITY TRENCH
FLARE STATION DEMOLITION AND REMOVAL (SEE SHEET G-003 AND SPECIFICATIONS FOR SCOPE OF WORK)13
42 EXISTING HIGH VOLTAGE POWER POLE(S) AND OVERHEAD LINE TO BE MOVED BY OTHERS
1"=20' 6
DEMOLITION/SALVAGE PLAN
C-102
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 6-
C -1
.d w g
/1
8/
0:
:2 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
(1590)
3.2%
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
120/240V/1Ø
100 AMP
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
FLARE STATION
ATHEN'S
OPERATIONS
COMPOUND
UNIT #1 LFG
AIR & COND.
EDGE OF
AC ROAD
INLET STRUCTURE
1591.0 TF/TS
1591.25 TS
1592.25 TS
1587.50 TF
1601.50 TW
1587.50 TF
1601.50 TW
(1592.50 FS)
(1
2.
T C
(1587.86 AC/TC=0)
1585.00 BF
1585.50 BF
.0
(1592.00 FS)
SEPTIC
XFMR
1593.50 TC
(1
1.
T C
A
E 6735141.59
N 1874906.46
E 6735005.59
N 1874906.46
1590.2 FS
E 6735141.59
N 1874766.46
1577.5 INV
1586.9± FS
1593.99± CL K-O
(1590.30 TS)
(1589.60 FL)
(1
3.
T C
(1
3.
T C
(1593.36 TC)
.5
TC
1590.8 TS/FL
(1583.53 FL)
(1583.57 TOE)
(1582.88 FL)
E
E
1588.0 BF
(1590.46 FS)
(1590.34 TS)
(1590.24 TS)
1589.59 FL
1589.99 FL/GB
1590.14 FL0.
5%
EXIST
SLAB
EXISTING STORAGE CONTAINER
EXIST SLAB
1.
0%
GR=1583.5±
INV=1579.5±
1576.9± INV
33 FUTURE UNIT #4
LFG CONNECTION
3.4%
A
3.0%
APPROXIMATE
LIMIT OF GRADING
U N
IT
LF
G
A
A
(1590)
(1592)
(1588)
(1586)
1599.50 TW
1591.50 TS
1583.0 TF
1580.5 BF
1585.0 FS
(1580)
SWITCHGEAR
1594.10 FG
(SEE C-104/S-101/M-101)
1592.00
1590.60 TS
1590.5 FS
1590.24
N 1874796.46
E 6735034.93
C
-5
C-501
1585.9± FS
1577.0± ELBOW
1593.83± CL K-O
36" PIPE, 1582.4± INV
(1584)
1575.0
INV
1576.0
INV
1577.0
INV
1579.0±SD INV
1580.0±
SD INV
1580.7±
SD INV
PAVEMENT
EXISTING AC
N 1874840.46 E 6735005.59
ANGLE PT
1593.5
(1
3.
TC
(1
2.
TC
4.0% (1592)
1586.0
OUTLET
(1584.63 AC)
(1582)
1587.30 EL OUTLET
2.0%
82 82
EXIST
SLAB
(1590.29 EX SLAB)
1599.84 TW
1589.37 FL INLET
(8 EA)
LFG, CONDENSATE FORCEMAIN, AND RNG TRENCH
TO POWER PLANT (SEE ARCHAEA AS-BUILT DWGS)
832523 84
(1590.29 FS)
(1590.18 FS)
E 6734924.8
UNIT #1
1%
C-501
FLARE
SLAB
1591.0
C-501
START FL
C-202WING WALL
SEE DETAILS
PAD 1591.5 FF
EXISTING TWIN 36" STORM DRAIN PIPES
AND 2" X 4" D/C FORCEMAIN (UNIT #4)
EXISTING 12" HDPE HEADER, 2" AIR,
1578.0±
INV
SUMP
18" INV=1575.0 (EAST)
A
IR
C
O N
D E
N S
A
TE
N 1874813.3
UNIT #1 SUMP
SUMP "B"
GR=1586.0
E 6734951.3 N 1874811.1
(UNIT #2/3/4)
SUMP "A"
GR=1585.8±
TOP OF FLANGE=1586.0
24" INV=1579.0 (WEST)
24" INV=1575.0 (EAST)
SUMP BTM=1567.0
TOP OF FLANGE=1586.0
18" INV=1581.0 (WEST)
SEE DETAIL
C-502
PAVED ENTRANCE ROAD
EXISTING POWER PLANT
PIPELINE TRENCH (SEE
ARCHAEA DWGS)
60(3 EA)
EXISTING
FLARE
STATION
C-501
10' X 12'
GATE TRACK
.0
@1.3%
1% MIN
HB
W W W W
W
W
W
O/H ELEC
FLARE
SLAB
1591.0
1"=20' 7
SITE IMPROVEMENTS/
GRADING/FIELD PIPING PLAN
C-103
NOTES:
2. TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT AND FIELD SURVEY PERFORMED BY TETRA TECH ON 4-3-2022
AT FLARE STATION AREA. SEE SHEET C-101 FOR CONTROL POINTS.
1. SEE SHEETS G-003 AND G-004 FOR CONSTRUCTION NOTES.
LEGEND
PROPOSED PAVEMENT AREA (BLOCK WALL TO EXISTING PAVED ACCESS ROAD)
1586 PROPOSED FINISH SURFACE CONTOUR
PROPOSED DUAL CONTAINED CONDENSATE FORCEMAIN, SIZE PER PLAN
A PROPOSED COMPRESSED AIR LINE
PROPOSED BELOW GRADE PIPING, SIZE PER PLAN, UNLESS NOTED OTHERWISE
EXISTING PIPING OR PIPE TRENCH BY OTHERS BELOW GRADE, SIZE VARIES
EXISTING INTERIM CONTOUR(1588)
EXISTING INDEX CONTOUR(1590)
DRAINAGE FLOW LINE DIRECTION
EXISTING HIGH VOLTAGE OVERHEAD ELECTRICALE
EXISTING STORM DRAIN LINE, SIZE VARIESSD
PROTECT EXISTING STRUCTURE/PIPE IN PLACE10
CONSTRUCT 6" AC PAVEMENT OVER 12" CLASS 2 BASE
CONSTRUCT 6" THICK CONCRETE V-DITCH, APPROX. 5' WIDE, DEPTH VARIES
INSTALL 6" ATRIUM STYLE INLET GRATE
INSTALL 6" SINGLE WALL DRAIN PIPE, HDPE
SAWCUT AC PAVEMENT
INSTALL 6" STEEL BOLLARD AND PLASTIC SLEEVE
73 INSTALL 30" SDR 17 HDPE PIPE
INSTALL 30" X 24" HDPE REDUCER
INSTALL 18" X 12" HDPE REDUCER
INSTALL 18" SDR 17 HDPE PIPE
INSTALL 18" HDPE ELBOW, 90°, SDR 1782
INSTALL 30" HDPE TEE, SDR 17
INSTALL 30" HDPE ELBOW, 90°, SDR 17
INSTALL 2" SDR 11 HDPE x 4" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS 83
INSTALL 4" SDR 11 HDPE x 8" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS84
INSTALL 6" MITERED DRAIN GRATE (CONTOUR CONCRETE /PAVEMENT AROUND GRATE OUTLET)51
INSTALL 24" SDR 17 HDPE PIPE
INSTALL 12" SDR 17 HDPE PIPE
INSTALL 2" SDR 9 HDPE PIPE & FITTINGS
INSTALL 24" BUTTERFLY VALVE WITH 3' VALVE EXTENSION AND GEAR OPERATOR
INSTALL 24" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT
INSTALL 24" PVC BLIND FLANGE
INSTALL CONDENSATE SUMP ASSEMBLY "B", SERIES 7000 SUMP, 18" X 24" DUAL CONTAINED
JOIN EXISTING
GRADE AREA TO CONTOURS
INSTALL CONDENSATE SUMP ASSEMBLY "A", SERIES 7000 SUMP, 30" X 36" DUAL CONTAINED
EXISTING HIGH VOLTAGE POWER POLE TO BE REMOVED BY OTHERS
SEE SUMP "A" AND GHS-1 INLET PIPING PROFILE
SEE SUMP "B" AND GHS-2 INLET PIPING PROFILE
CONSTRUCTION NOTES
38 INSTALL 2" WATER LINE PER SHEET C-105 AND C-503
INSTALL 18" SDR 17 HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET AND BOLT KIT81
48 INSTALL 6" AC BERM
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 7-
C -1
.d w g
/1
8/
0:
:2 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
LANDFILL
OPERATIONS
COMPOUND
1591.0 TS/TF
1591.25 TS
1592.25 TS
1599.84 TW
1588.0 BF
1587.50 TF1601.50 TW
1587.50 TF
1593.33 TOP OF CONCRETE WALL
.5
TS
.5
B F
.0 T
F
.5
TW
1585.00 BF
1585.50 BF
1591.00 TS
.60
TS
C O
N S
TR
U
C
TI
O N
J O
IN
T
36" THICK SLAB
1C-202
C-201
C S-302
C
-2
C-201
0.
5%
1589.99 FL
(1590.29 FS)
1589.37 FL/INLET
1591.50 FS
B S-301
PER DETAIL 1/S-504
PER DETAIL 1/S-504
1587.30 FL/OUTLET
1.3%
ELECT. PEDESTAL
(EXISTING SLAB)
2'Ø LIGHT POLE FOOTING
PER DETAIL 1/S-504
2'Ø LIGHT POLE FOOTING
PER DETAIL 1/S-504
2'Ø LIGHT POLE FOOTING
PER DETAIL 1/S-504
2'Ø LIGHT POLE FOOTING
2'Ø LIGHT POLE FOOTING
PER DETAIL 1/S-504
2'Ø LIGHT POLE FOOTING
1.0%
.0
.5
.7
G B
1590.04 FL
1590.09 FL
.2 5 15
.0
1590.14 FL
1590.19 FL
0.
5%
0.
5%
0.
5%
1589.89 FL
1589.79 FL
1589.69 FL
1589.59 FL
1589.49 FL
1590.80 FS/FL
0.
5%
1.
0%
1.
0%
1.
0%
1.
0%
1.
0%
1.1%
0.7%
.0
1.0%
1592.25 FS/TS
1.
2%
0.
6%
1.
0%
RIDGE LINE
18" SLAB
1.
0%
.60 B
F
1601.50 TW
C-501
DRAINAGE OUTLET
EDGE OF SLAB/FOOTING
CONSTRUCTION JOINTCONSTRUCTION JOINT/1591.75
CONSTRUCTION JOINT/1592.0
C
O N
S
TR
U C
TI
O
N J
O
IN
T
C O
N S
TR
U
C
TI
O N
J O
IN
T
1591.00
CONTRACTOR TO COORDINATE
WITH BUILDING CONTRACTOR
ON SIZE AND LOCATION OF
FOOTINGS REQUIRED FOR
40' X 40' ROOF CANOPY, TYP
1591.90 TS
1591.82 TS 1591.25 TS
1591.59 TS
1591.75 TS1591.75 TS
1591.50 FL
1.
2%
1.
3%
C O
N S
TR
U
C
TI
O N
JO
IN
T/
.5
1591.75 TS
0.8%
1591.50 TS
CONSTRUCTION JOINT/1591.50
1591.50 TS
.2
1591.25 TS
1.0%
1.0%
1591.58 TS
1591.75 TS
.0
1.0%
2.8%
1591.25 TS/FL
CONSTRUCTION JOINT
1591.50 TS 1591.40 TS
CONSTRUCTION JOINT
CONSTRUCTION JOINT
ELECTRICAL CONDUITS FROM NEW
TRANSFORMER WALL TO MSB-1
0.5%
1590.90
0.
5%
1590.24 FL
(1590.34 TS)
(1590.30 TS)
1586.00 FL/OUTLET
0.
5%
SKID SHIMMED AND GROUTED
TO ELEV. 1591.70
(SEE NOTES 2 & 3)
SKID SHIMMED AND GROUTED
TO ELEV. 1591.45
(SEE NOTES 2 & 3)
.9
LEVEL
FLARE
SLAB
1591.00 TS
LEVEL
FLARE
SLAB
1591.00 TS
1590.8 FS/FL
1590.85 FL
.7
.8
R
ID
G E
RIDGE
RIDGE
.0
1591.0
1590.95 FL
0.
5%
FL
O
W L
IN
E
R
ID
G E
.0 1590.9
1590.80 FS/FL
DRAINAGE OUTLET15
.9
.8
.7
1590.90
0.8%2.5%
0.8%
1591.75
TANK PAD
LEVEL
1"=8' 8
FLARE STATION
C-104
DRAINAGE PLAN
NOTES:
1. SEE STRUCTURAL DRAWINGS FOR DETAILS ON FOOTINGS, FOUNDATIONS, AND WALLS.
2. SEE SPECIFICATIONS FOR NON-SHRINK GROUT TO BE USED DURING INSTALLATION OF SKIDS.
3. PROVIDE 1" OPENINGS IN GROUT AT 12" O.C. FOR DRAINAGE.
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 8-
C -1
.d w g
/1
8/
0:
:3 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
(1590)
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
S D
120/240V/1Ø
100 AMP
SD
SD
SD
SD
SD
SD
SD
E
FLARE STATION
ATHEN'S OPERATIONS
COMPOUND
EDGE OF
AC ROAD
SEPTIC
XFMR
1584 1585
EXIST
SLAB
EX. STORAGE CONTAINER
3.4%
U N
IT
LF
G
A
(1590)
(1592)
(1588)
(1586)
(1580)
(SEE C-104/S-101/M-101)
(1584)
(1592)
(1582)
LFG, CONDENSATE FORCEMAIN, AND RNG
TRENCH TO POWER PLANT (SEE ARCHAEA DWGS)
UNIT #4
UNIT #1
EXISTING TWIN 36" STORM DRAIN PIPES
AND 2" X 4" D/C FORCEMAIN (UNIT #4)
EXISTING 12" HDPE HEADER, 2" AIR,
SUMP
A
IR
C
O N
D E
N S
A
TE
PAVED ENTRANCE ROAD
POWER PLANT
PIPELINE TRENCH (SEE
ARCHAEA DWGS)
EXISTING
FLARE
STATION
W W
E E
E
W W W W W
44ELEV. 1588.68
W
29 87
10'
CONNECT TO SWMD TRAILER
EXISTING 6"
WATER LINE
EDGE OF
AC ROAD
(1
0)
(1
0)
(1
0)
(1
0)
52 5814 4858 52
1"=40' 9
WATER LINE PLAN
C-105
NOTES:
2. TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT AND FIELD SURVEY PERFORMED BY TETRA TECH ON 4-3-2022
AT FLARE STATION AREA. SEE SHEET C-101 FOR CONTROL POINTS.
1. SEE SHEETS G-003 AND G-004 FOR CONSTRUCTION NOTES.
LEGEND
PROPOSED PAVEMENT AREA (BLOCK WALL TO EXISTING PAVED ACCESS ROAD)
1586 PROPOSED FINISH SURFACE CONTOUR
EXISTING INTERIM CONTOUR(1588)
EXISTING INDEX CONTOUR(1590)
PROPOSED 2" CLASS 150 PVC WATER LINE
CONSTRUCTION NOTES
INSTALL 1-1/2" DOUBLE CHECK VALVE ASSEMBLY PER DETAIL 3/C-503
JOIN EXISTING 6" WATER LINE PER DETAIL 2/C-503
INSTALL 1-1/2" CLASS 150 PVC WATER PIPE & FITTINGS
INSTALL 1-1/2" CLASS 150 PVC BALL VALVE, NSF/ANSI 61 STANDARD, AND HOSE BIB87
INSTALL WATER LINE THRUST BLOCK PER DETAIL 1/C-503 88
W
EXISTING 6" WATER LINEW
1. THE CONTRACTOR SHALL COMPLY WITH SAN BERNARDINO COUNTY PUBLIC WORKS
SPECIAL DISTRICTS STANDARDS FOR WATER.
2. THE CONTRACTOR SHALL DISINFECT THE NEW WATER LINE FROM THE TEE
CONNECTION POINT TO THE TRAILER AS REQUIRED BY AWWA STANDARD ANSI/AWWA
C651-14.
GENERAL NOTES
SAWCUT AND REMOVE SECTION OF AC BERM14
CONSTRUCT 6" AC PAVEMENT OVER 12" CLASS 2 BASE
SAWCUT AND REMOVE AC PAVEMENT SECTION
48 INSTALL 6" AC BERM
A P
P R
R
E V
IS
IO
N S
M A
R K
D A
TE
A
P P
R
R E
V
IS
IO
N
S
DESIGNED BYDRAWN BY PROJ. ENGR.
DEPARTMENT OF PUBLIC WORKS
SUBMITTED BY
TOT. SHT'S.
SAN BERNARDINO COUNTY
SHT. NO.SCALEDWG NO.DATE
RECOMMENDED / APPROVED BY
M A
R K
D A
TE
DATESAMI H AYASS
PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER
DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42
MID-VALLEY SANITARY LANDFILL
SNA/SHA SHA
LANDFILL GAS FLARE STATION
21700 Copley Drive, Suite 200
Diamond Bar, CA 91765
TEL 909.860.7777 FAX 909.860.8017
H :\d w g\
S bs w m d\ M id -V al le y\ Fl ar e
S ta tio n\
\D W
G S
\0 9-
C -1
.d w g
/1
8/
0:
:4 m ar co s.
ar m ijo
SNA
PRO S IO
TE
R
GE
I S
C84806
CIVIL
RED
ER
N
N E
G I
LAN
E
SFE
AMAS
I H AY
SS
STATE OF CA L I FORN IA
06/18/2025 06/18/2025SAMI H AYASS
E4635 Text Box 06/26/2025
E4635 Text Box 06/26/2025
.60
FS/FL
1591.00 TF
1583.00 TF
1581.00 BF
FINISH SURFACE
ALONG WALL
(PAVEMENT)
TOP OF 30" INTERIOR SLAB
1588.00 BF
TOP OF INTERIOR SLAB
10'-8" 10'-8" 10'-8" 22'-8"
1583.00 TF
1583.83 TF
1584.67 TF
1585.50 TF
" S
S T
O R
N G
/1 6"
S
TE
E L
S
LE
E V
E
" S
S T
O L
FG
TE
/1 6"
S
TE
E L
S
LE
E V
E
1599.50 TW1600 1599.84 TW
5' WIDE CONCRETE
DRAINAGE SWALE
EXISTING CONCRETE SLAB
20'-0" 32'-0"
3" GALVANIZED FENCE POST SET IN
THICKENED EDGE FOOTING, 2 PLACES
20'-0"
S E
E S
TR
U
C
TU
R A
L D
E
TA
IL
S
FO
R
P
IP
E P
E N
E
TR
A
TI
O N
S E
E S
TR
U
C
TU
R A
L D
E
TA
IL
S
FO
R
P
IP
E P
E N
E
TR
A
TI
O N
ROUGH GATE OPENING
FOR 8' HIGH CHAIN
LINK FENCE, DOUBLE
GATE, WITH TAN
PLASTIC SLATS, AND
LOCKING MECHANISM
STRUT CHANNELS
MOUNTED TO WALL
(FOR AIR AND
CONDENSATE LINES)
SIGN PER DETAIL 1/M-502
CONSTRUCTION
JOINT @ CONCRETE
RETAINING WALL, TYPICAL
ALL…