Mid-Valley Sanitary Landfill - LFG Flare Station - Design Plans - 06-18-2025~1.pdf

PDF 23 MB Posted

Attached to
Landfill Gas Flare Station at the Mid Valley Landfill
Solicitation number
PWG126-SOLID-6143
Issued by
San Bernardino County, San Bernardino City, California

About this file

This document is a comprehensive set of design plans and technical drawings for the Mid-Valley Sanitary Landfill Landfill Gas Flare Station project prepared by San Bernardino County Department of Public Works, Solid Waste Management Division. The project involves the construction of a new flare station facility located at 2390 N. Alder Avenue, Rialto, California 92377, designed to manage and safely dispose of landfill gas from Units 1-4 at the facility. The design includes installation of two low-NOx flare stacks (5,000 SCFM and 1,000 SCFM capacity), two gas handling skids (GHS-1 and GHS-2), two rotary screw compressors with associated equipment, a condensate management system with an 8,700-gallon poly storage tank, site improvements including grading and drainage infrastructure, a 40-foot by 40-foot pre-fabricated steel canopy structure, and ancillary equipment and controls. The project requires a Class "A" Contractor's License and encompasses 42 sheets of detailed civil, structural, mechanical, and electrical design drawings prepared under the supervision of registered professional engineers.

The design plans contain comprehensive technical specifications for concrete foundations, structural steel components, HDPE piping systems, electrical systems including a 2,000-amp switchgear, seismic design criteria consistent with the 2022 California Building Code, and various equipment anchorage requirements. The project includes demolition and salvage of the existing flare station and relocation of existing equipment including storage containers, operational trailers, and utility infrastructure. Construction details specify material requirements, reinforcement specifications, installation procedures, and special inspection requirements for structural elements, welding operations, and post-installed adhesive anchors. The site plan indicates the relocation of existing condensate sumps, compressed air lines, and interconnect piping systems, with field verification requirements for underground facilities. Equipment specifications identify manufacturers including PEI, Kaishan, ISCO Industries, Grundfos, and other suppliers, with major components including Lonestar Blower centrifugal blowers, condensate sump assemblies, and granular activated carbon treatment systems.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S M

A R

K D

A

TE

SHT. NO.

NO CHANGES RESIDENT ENGINEER

CHANGESMARK

TOT. SHT'S.

DATE

421PREPARED UNDER THE SUPERVISION OF DATE

PREPARED BY:

3.

Pavement or to the Top of Curb, unless otherwise noted.

All Pavement Width Dimensions shown on the plans are to the Edge of lines, shall be protected in place.

All Trees & Vegetation outside the limits of excavation and embankment slope

GENERAL NOTES

5.

on the plans or as determined by the Engineer.

Asphalt Concrete Overlays shall be feathered to meet existing as shown4.

1.

Transitions and Warping shall be as shown and as determined by the Engineer.

2.

Dimensions are subject to tolerances specified in the State Standard Specifications.

SAN BERNARDINO COUNTY

DEPARTMENT OF PUBLIC WORKS

SOLID WASTE MANAGEMENT DIVISION

G-002

C-103

G-001

DESCRIPTION

SITE IMPROVEMENTS/GRADING/FIELD PIPING PLAN

TITLE AND INDEX OF SHEETS

VENTURA

MONO

SAN BERNARDINO

INYO

TULARE

LOS

ANGELES

KERN

IMPERIAL

RIVERSIDE

ORANGE

SAN DIEGO

LASSEN

MODOC

BUTTE SIERRA

PLUMAS

SISKIYOU

TRINITY

TEHAMA

GLENN

MENDOCINO

SHASTA

ALPINE

SU

TTER

M

EN

TO

SA

CR

A-

AMADOR

EL DORADO

PLACER

MARIPOSA

MADERACLARA

STANISLAUS

MERCED

CALA

VERAS

TUOLUMNE

JO

AQUINSAN

COLUSA

LAKE

NAPASONOMA

SANTA

SAN MATEO

SAN FRANCISCO

MARIN

CONTRA

CRUZ

SOLANO

SANTA

ALAMEDA

COSTA

YOLO

YUBA NEVADA

HUMBOLDT

DEL NORTE

FRESNO

KINGS

BENITO

MONTEREY

SAN

SANTA

OBISPO

BARBARA

LUIS

SAN

FLARE STATION DETAILS

M-101 M-501 M-502

STRUCTURAL DETAILS 4

ELECTRICAL PLAN

POWER SINGLE LINE DIAGRAM AND LOAD SCHEDULE

S-101

S-501

SYMBOLS AND ABBREVIATIONS

S-502

E-101

OVERALL SITE PLAN

E-601

FLARE STATION DETAILS

STRUCTURAL DETAILS 1

PROJECT LOCATION

NOT TO SCALE

VICINITY MAP

LOCATION MAP

FLARE STATION ASSEMBLY PLAN

LANDFILL GAS FLARE STATION AT THE

MID-VALLEY SANITARY LANDFILL

SAN BERNARDINO COUNTY

NOEL CASTILLO, DIRECTOR OF PUBLIC WORKS

THIS PROJECT REQUIRES A CLASS "A" CONTRACTOR'S LICENSE

APPROVED BY:

DATE

21700 Copley Drive, Suite 200 Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

STRUCTURAL DETAILS 3S-503

G-004 FLARE STATION CONSTRUCTION NOTES

CONDUIT/WIRE SCHEDULE, DETAILS AND NOTESE-501

SANITARY LANDFILL

MID-VALLEY

RIALTO MUNICIPAL

AIRPORT MIRO FIELD

BASELINE RD S

IE

R R

A A

V E

C

IT

R U

S A

V E

P A

LM

E

TO

A

V E

A

LD

E R

A V

E

LO

C

U S

T A

V E

LI

N

D E

N A

V E

A Y

A

LA

A V

E

SIERRA LAKES PKWY

CASMALIA ST

BOHNERT AVE

HIGHLAND AVE

C

IT

Y O

F R

IA

LT

O

C

IT

Y O

F F

O N

TA

N

A

N.T.S.

SHT. NO.

STRUCTURAL DETAILS 2

S-504

C-301 SUMP "A" AND GHS-1 INLET PIPING PROFILE

C-302 SUMP "B" AND GHS-2 INLET PIPING PROFILE

C-102 DEMOLITION/SALVAGE PLAN

C-101 SITE PLAN/SURVEY CONTROL/RELOCATION PLAN

C-501 DETAILS

G-003 DEMOLITION/SALVAGE/SITE IMPROVEMENTS CONSTRUCTION NOTES

CONDENSATE MANAGEMENT SYSTEM PROCESS FLOW DIAGRAMD-601

CONCEPTUAL EQUIPMENT CANOPY ISOMETRIC

S-505

DWG. NO.

DWG. NO.

G-001

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT

DIAL

BEFORE

YOU DIG

TWO

WORKING

DAYS

BEFORE

YOU DIG

S-001 GENERAL STRUCTURAL NOTES

S-002 SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS

S-102 OFFICE AND STORAGE CONTAINER FOUNDATION PLAN

S-103 FLARE AND BLOWER FOUNDATION PLAN

S-104 CONDENSATE TANK AND PREFABRICATED STEEL

S-301 FLARE SECTION23

S-302 TANK SECTION24

ELECTRICAL DETAILSE-502

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 1-

G -0

-T t.d w g

/1 8/

0:

:4 m ar co s.

ar m ijo

C-104 FLARE STATION DRAINAGE PLAN8

C-201 NORTH AND SOUTH WALL PROFILES10

C-202 EAST AND WEST WALL PROFILES11

STRUCTURAL DETAILS 5

M-503

S-303 CANOPY SECTION

22 CANOPY FOUNDATION PLAN

POWER SINGLE LINE DIAGRAM AND LOAD SCHEDULEE-602

S-506

STRUCTURAL DETAILS 6

FLARE STATION PROCESS FLOW DIAGRAMD-602

C-502 DETAILS

NOT TO SCALE

SITE ADDRESS:

2390 N. ALDER AVE.

RIALTO, CA 92377

INDEX OF SHEETS

C-105 WATER LINE PLAN9

16C-503 WATER LINE STANDARD DETAILS

TITLE AND INDEX OF

SHEETS

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025

10/14/2025

Noel Castillo e sig vector

COMPRESSOR

SELECTOR

INSTRUMENT SYMBOLS

FILTER/REGULATOR/LUBRICATOR

VARIABLE SPEED DRIVE

GROUND

HIGH DENSITY POLYETHYLENE

HAND-OFF-AUTO

FLOW SWITCH OR FINISH SURFACE

FIBERGLASS REINFORCED PLASTIC

FLOW SAFETY VALVE (CHECK VALVE)

GROUND FAULT INTERRUPTER

GAS MONITOR

GROUND FAULT

FUSE HOLDER

GRADE BREAK

FLOW VALVE

FUTURE

FLOW SWITCH LOW

FLOW TRANSMITTER

FUSE

FLOW SWITCH HIGH

PRESSURE CONTROL VALVE

PRESSURE INDICATOR

POLYETHYLENE

PHONE

PILOT GAS

PRESSURE DIFFERENTIAL INDICATOR

PRESSURE ALARM LOW LOW

PRESSURE ALARM HIGH HIGH

PURGE AUTO

PRESSURE ALARM HIGH

PRESSURE ALARM LOW

PRESSURE DIFFERENTIAL INDICATOR

PRESSURE CONTROLLER

PUMP

EVENT INDICATOR CONTROLLER

POSITION SWITCH CLOSED

POSITION SWITCH OPENED

POSITION INDICATOR

POSITION SWITCH

POSITION CONTROLLER

POSITION ALARM

EVENT INDICATOR

VIBRATION SWITCH HIGH

VIBRATION TRANSMITTER

EVENT ALARM

EXPLOSION PROOF

WEATHER PROOF

TRANSFORMER

WATTS

WATER COLUMN

MOTOR OPERATED VALVE

EXISTING

TEMPERATURE

NAMEPLATE

FLOW ELEMENT (FLOW METER)

FLOW TOTALIZER INDICATOR

FLOW INDICATING RECORDER

FLOW INDICATING TRANSMITTER

FLARE

FLEXIBLE HOSE

FORWARD

FLOW RECORDER

FILTER REGULATOR

FAIL OPEN

PORT FILTER

FULL LOAD AMPS

FLOWLINE

FINISH GRADE

FLAME FAILURE ALARM

FLOW INDICATOR

OXYGEN ALARM HIGH HIGH

OXYGEN TRANSMITTER

OXYGEN INDICATING RECORDER

OXYGEN INDICATOR

OXYGEN ELEMENT

OVERLOAD

OXYGEN INDICATOR TRANSMITTER

OXYGEN SENSOR FAILURE

NOT TO SCALE

OPEN/CLOSE

OXYGEN

OXIDES OF NITROGEN

OXYGEN ANALYZER

OXYGEN ALARM HIGH

ON CENTER

FUSED DISCONNECT

FLOW CONTROL VALVE

FEEDER

FLOW ALARM LOW LOW

FAIL CLOSE

FLOW CONTROLLER

FURNISHED BY OTHERS

FILTER

FLOW ALARM HIGH HIGH

FLOW ALARM LOW

FLOW ALARM HIGH

FLAME ARRESTER

DEGREE FAHRENHEIT

EXPLOSION PROOF

NORMALLY OPEN TIMED TO CLOSE

NORMALLY CLOSED TIMED TO OPEN

NORMALLY CLOSED TIMED TO CLOSE

NORMALLY OPEN

NOT IN CONTRACT

NEGATIVE

NORMALLY OPEN TIMED TO OPEN

NEUTRAL BLOCK

NORMALLY CLOSED

NON-AUTOMATIC

MANWAY

MOUNTED

MAIN SWITCH BOARD

MOTOR STARTER

VIBRATION ALARM

VIBRATION INDICATING RECORDER

VIBRATION ALARM HIGH HIGH

VARIABLE FREQUENCY DRIVE

VIBRATION INDICATOR

VAPOR PROOF

VIBRATION SWITCH

VIBRATION ALARM HIGH

UNINTERRUPTIBLE POWER SUPPLY

TEMPERATURE TRANSMITTER

UNDERGROUND

VESSEL

ULTRAVIOLET SCANNER

TYPICAL

TOP OF WALL

TEMPERATURE SAFETY VALVE

TEMPERATURE SAFETY ELEMENT

TEMPERATURE SWITCH HIGH

TEMPERATURE SWITCH LOW

TEMPERATURE RECORDER

TIGHT SHUTOFF

TEMPERATURE SWITCH OR TOP OF SLAB

TIMER

TEMPERATURE INDICATOR RECORDER

TEMPERATURE ELEMENT WELL

TEMPERATURE ELEMENT SWITCH

TEMPERATURE INDICATOR

TEMPERATURE INDICATOR CONTROLLER

TEMPERATURE INDICATOR TRANSMITTER

THERMOSTAT

ELECTRICAL DISTRIBUTION PANEL

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE INDICATOR

ELECTRICAL METALLIC TUBING

VOLTAGE INDICATOR

EMERGENCY

EQUIPMENT

ENCLOSURE, ENCLOSED

ELAPSED TIME METER

EXHAUST

ELEVATION

DRAWING

VOLTAGE TRANSFORMER

ELECTRICAL MOTOR

DISCONNECT SWITCH

MANHOLE

METHANE INDICATOR

MODEM

METHANE INDICATING RECORDER

METHANE INDICATOR TRANSMITTER

MOTOR

MANUAL MOTOR STARTER

MINIMUM

METHANE ALARM LOW LOW

MOTOR CONTROL CENTER

MAIN CONTROL PANEL

THOUSAND CIRCULAR MILS

MAXIMUM

MANWAY

MAGNETIC

CONTROL VALVE (MODULATING)

CONTROL POWER TRANSFORMER

DISTRIBUTION

DAYLIGHT

CURRENT TRANSFORMER

DRYER

CURRENT SWITCH HIGH

METHANE ANALYZER

LUBRICATOR

METHANE ALARM LOW

MILLIAMPS

MOTOR

LIGHTING

LEVEL TRANSMITTER OR LIGHT(S)

LEVEL SWITCH LOW LOW

LEVEL SWITCH

LIGHTING PANEL

LOCK-OUT-STOP

LEVEL SWITCH LOW

LEVEL SWITCH HIGH HIGH

LEVEL SWITCH HIGH

LOCAL

TEMPERATURE ALARM LOW

TEMPERATURE ALARM LOW LOW

TEMPERATURE CONTROLLER POSITIONER

TEMPERATURE CONTROLLER OR TOP OF CURB

TEMPERATURE ELEMENT (THERMOCOUPLE)

TEMPERATURE CONTROL VALVE

TIME DELAY RELAY

TERMINAL BLOCK

TEMPERATURE ALARM HIGH HIGH

TEMPERATURE ALARM HIGH

TANK

TACHOMETER

STRAINER

SWITCH

SYSTEM

SURGE ARRESTOR

SHUNT TRIP

STATION

STANDARD

SOLENOID VALVE

SAMPLE PORT

STAINLESS STEEL

SPECIFICATION

SEQUENCE, SEQUENCER

SIGHT GLASS

SPEED INDICATOR

SHEET

SHIELD, SHIELDED

SUPPLEMENTAL FUEL

SENSOR FAILURE

MISCELLANEOUS SYMBOLS

RELAY FUNCTION DESIGNATIONS TYPES

CURRENT TRANSFORMER

ALUMINUM

KILOWATTS

COMBUSTIBLE GAS HIGH HIGH

COMBUSTIBLE GAS INDICATOR

CIRCUIT

CONDUIT ONLY

CHANNEL

LOWER EXPLOSIVE LIMIT

LEVEL GAGE

LANDFILL GAS

LUBE OIL

LEVEL ELEMENT

LATCHING CONTROL RELAY

LOCAL CONTROL PANEL

LAMP

LEVEL CONTROLLER HIGH

LEVEL CONTROLLER LOW

LEVEL CONTROLLER

LEVEL ALARM LOW LOW

LEVEL ALARM LOW

LEVEL ALARM HIGH HIGH

LEVEL ALARM HIGH

BARE COPPER

AUTOMATIC

BURNER ALARM LOW LOW

BLOWER

AMPERE TRIP

AMPERES, AMPERAGE

INSTRUMENT

KILOVOLTS

KILOVOLT AMPERES

TIME INDICATOR

CURRENT TRANSMITTER

SHORT CIRCUIT CURRENT

INVERT

CURRENT INDICATING RECORDER

IGNITOR

INSTRUMENT AIR SUPPLY

CURRENT ALARM LOW

CURRENT ALARM HIGH HIGH

CURRENT ALARM HIGH

INSTANTANEOUS

CURRENT ALARM LOW LOW

STANDARD CUBIC FEET PER MINUTE

SHUTDOWN OR ON

SECTION

SECONDARY, SECONDS

SHUTDOWN VALVE

SHUTDOWN OR STORM DRAIN

SCHEDULE

RETENTION TIME CALCULATOR

REVOLUTIONS PER MINUTE

RIGID GALVANIZED STEEL

AIR STRIPPER

RETENTION TIME

SPECTACLE BLIND

RELAY MODULE

RESISTOR

POLYVINYL CHLORIDE

RUPTURE DISK ALARM HIGH

RUPTURE DISK

RUPTURE DISK SWITCH

RECEPTACLE

TOTALIZER

POWER

REQUIRED

PRESSURE SAFETY ELEMENT

PRESSURE TRANSMITTER

POUNDS PER SQUARE INCH

PRESSURE RELIEF VALVE

PRESSURE SWITCH LOW

PRESSURE SWITCH HIGH

PRESSURE SWITCH

MISCELLANEOUS ABBREVIATIONS

ACTUAL CUBIC FEET PER MINUTE

ANALOG OUTPUT

ANALOG INPUT OUTPUT

ANALOG INPUT

ASPHALT CONCRETE OR AIR CONDITIONER

CURRENT INDICATOR

CURRENT

HAND VALVE PORT

HEAT TRACE

HAND VALVE

HEATER

HERTZ

HORSEPOWER OR HIGH POINT

HAND SWITCH

PROGRAMMABLE LOGIC CONTROLLER

POWER PANEL or POWER POLE

PRESSURE INDICATING RECORDER

POSITION, POSITIVE

POSITIONER

POTENTIOMETER

PANEL

PILOT

PIPING AND INSTRUMENTATION DIAGRAM

PRESSURE INDICATING CONTROLLER

INDUSTRIAL TECHNICAL CORPORATION

LEVEL INDICATOR

PUSH BUTTON

BUILDING PROTECTION SYSTEM

ACTUATOR

AUTO DIALER SYSTEM

AMPERE FRAME SIZE (CIRCUIT BREAKER)

ABOVE FINISH FLOOR

AMERICAN WIRE GAUGE

BATTERY

BURNER GLASS

BURNER ELEMENT (UV SCANNER)

BREAKER

BILL OF MATERIAL

BURNER SWITCH (FLAME SAFEGUARD)

BRITISH THERMAL UNIT

CONDUIT

CURRENT ALARM HIGH

CURRENT ALARM LOW

CABLE

CENTER TO CENTER

COMBUSTIBLE GAS HIGH

COMBUSTIBLE GAS TRANSMITTER

CHART RECORDER

CURRENT INDICATOR

COUNTER

COMMUNICATION

CONTROL PANEL OR CONTROL POINT

CHLORINATED POLYVINYL CHLORIDE

CONTROL RELAY

CARBON STEEL

CURRENT SWITCH LOW

COPPER

DIGITAL INPUT

DELTA OR DIFFERENTIAL PRESSURE

PLC CONTROLLED DEVICE

LOCALLY PANEL MOUNTED UNIT

INSTRUMENT MOUNTED BEHIND BOARD

CONTROL PANEL MOUNTED INSTRUMENT

LOCALLY MOUNTED INSTRUMENT

REMOTE CONTROL

REMOTE MONITORING

PILOT LIGHT (R=RED; G=GREEN; A=AMBER; B=BLUE;

INSTRUMENT MOUNTED BEHIND LOCAL BOARD

LOCAL BOARD MOUNTED INSTRUMENT

W=WHITE; C=CLEAR; N=NEON)

CONTROL PANEL MOUNTED INSTRUMENT

AUTO/MANUAL

LOCAL/REMOTE

HAND/OFF/AUTO

ANALOG/DIGITAL

CURRENT TO PNEUMATIC

DETAIL NUMBER

INTERLOCK IF ANY ONE OR MORE INPUTS EXIST

RESET FOR LATCH TYPE ACTUATOR

INTERLOCK

SOLENOID VALVE

INTERLOCK IF ALL INPUTS EXIST

SHEET NUMBER DETAIL IS DRAWN ON

I/P

A/M

A/D

L/R

HOA

S

I

R

AND

OR

PILOT TUBE OR PILOT VENTURI TUBE

PISTON OPERATED VALVE WITH HANDWHEEL,

SELF-CONTAINED PRESSURE CONTROL VALVE

HYDRAULIC OR PNEUMATIC (SPRING RETURN)

SOLENOID-OPERATED 2-WAY VALVE

INSTRUMENTATION DEVICES & ACCESSORIES

PNEUMATIC TRANSMISSION, INSTRUMENT AIR

SUPPLY AND/OR GAS SIGNAL, PIPE OR TUBING

ELECTRICAL TRANSMISSION

SOFTWARE COMMUNICATION LINK

CONNECTION TO PROCESS, MECHANICAL LINK

CONDENSATE TRANSMISSION PIPING

LINE & SIGNAL SYMBOLS

SIDE-MOUNTED

PISTON-OPERATED VALVE

SOLENOID-OPERATED 3-WAY VALVE

PRESSURE RELIEF VALVE OR VENT

PISTON-OPERATED VALVE WITH OPEN AND

CLOSED POSITION SWITCHES AND WITH

HANDWHEEL, SIDE MOUNTED

CONTROL VALVE WITH I/P TRANSDUCER

BUTTERFLY VALVE, HAND OPERATED

BALL VALVE, HAND OPERATED

NEEDLE VALVE, HAND OPERATED

HAND VALVE, HAND OPERATED

3-WAY HAND VALVE, HAND OPERATED

PRESSURE REGULATOR W/PRESSURE GAUGE

BUTTERFLY VALVE, AUTOMATED

GEAR OPERATOR

Y-STRAINER

PNEUMATIC POSITIONER

FLEX CONNECTOR

FLEX CONNECTOR WITH FLANGE CONNECTION

FLANGE CONNECTION

BLIND FLANGE

UNION

CAP OR PLUG

CONCENTRIC REDUCER

ECCENTRIC REDUCER

SAMPLE PORT

MANUAL ACTUATOR/OVERRIDEMA

G

S

S

PSV

G

ZSO ZSC

P

G

A

PI

WIRING SCHEMATIC SYMBOLS

CONTACT, N.C.

TIMED CONTACT (N.C.T.O.)

TIMED CONTACT (N.O.T.0.)

TIMED CONTACT (N.O.T.C.)

CONTACT, N.O.

TIMED CONTACT (N.C.T.C.)

COIL (RELAY, TIMER, ETC.)

LATCHING RELAY

PILOT LIGHT

PILOT LIGHT (PUSH TO TEST)

PILOT (DUAL INPUT)

SOLENOID VALVE COIL

BUZZER OR HORN

ELECTRONIC AUDIBLE DEVICE

OR ELAPSED TIME METER

PUSHBUTTON, N.O.

PUSHBUTTON, N.C.

PUSHBUTTON, MUSHROOM HEAD

PUSH-PULL UNIT

(MAINTAINED CONTACTS)

PUSHBUTTON (1=N.O.; 1=N.C.)

SELECTOR SWITCH (2-POSITION)

SELECTOR SWITCH (3-POSITION)

SELECTOR SWITCH (3-POSITION WITH

CENTER POSITION CONTACT CLOSURE)

PRESSURE SWITCH, CLOSE ON INCREASE

PRESSURE SWITCH, CLOSE ON DECREASE

TEMPERATURE SWITCH, CLOSE ON INCREASE

TEMPERATURE SWITCH, CLOSE ON DECREASE

LEVEL SWITCH, CLOSE ON RISE

LEVEL SWITCH, CLOSE ON DROP

FLOW SWITCH, CLOSE ON FLOW

FLOW SWITCH, OPEN ON FLOW

LIMIT SWITCH, N.O.

LIMIT SWITCH, N.O. HELD CLOSED

LIMIT SWITCH, N.C. HELD OPEN

LIMIT SWITCH, N.C.

FUSE

GROUND CONNECTION

JUNCTION

CONTROL PANEL TERMINAL

REMOTE PANEL TERMINAL

DISCONNECTING (ISOLATING) TERMINAL

CONTROL TRANSFORMER

IGNITER

U.V. FLAME SCANNER

THERMOCOUPLE

WIRES CROSSING, NO CONNECTION

WIRES CONNECTING

INTERNAL WIRING

FIELD WIRING

SHIELDED WIRES

(INDICATES GROUND WHEN REQUIRED)

LOCAL HAND/OFF SWITCH

SINGLE LINE DIAGRAMS

CIRCUIT BREAKER

TRANSFORMER

MOTOR STARTER

FUSED SWITCH

CMP or COMP

CV

CPT

DISTR

DL

CT

D

CSH

AL

CGHH

CGI

CIR

CO

CH

BC

AUTO

BALL

B

AT

AMP

ACFM

AOUT

AIO

AI

AC or A/C

BPS

A

ADS

AF

AFF

AWG

BATT

BG

BE

BKR

BOM

BS

BTU

C

CAH

CAL

CBL

CC

CGH

CGT

CHR

CI

CNT

COMM

CP

CPVC

CR

CS

CSL

CU

DI

DP

ETM

FALL

EXIST

F.C.

FCV

FAHH

FBO

FA

DWG

E

EMER

ENCL

EDP

DPI

DPS

E/E

EI

EL OR ELEV

EMT

EQPT

EXH

EXP

°F

FLT or F

FAH

FAL

FC

FD

DS

FDR

FE

FFA

FG

FI

FIR

FIT

FL

FLA

FLR

FX or FLEX

FLTP

F.O.

FOR

FQI

FR

FRG

FRL

FRP

FS

FSH

FSL

FSV

FT

FU

FUH

FUT

FV

GB

GF

GFI

GM

GND or GRND

HDPE

HOA

HP

HS

HT

HTR

HV

HVP

HZ

I

II

I/I

IAH

IAHH

IAL

IALL

IAS

IG or IGN

IIR

INST

INSTR

INV

ISC

IT

ITC

KI

KV

KVA

KW

LAH

LAHH

LAL

LALL

LC

LCH

LCL

LCP

LCR

LE

LEL

LFG

LG

LI

LMP

LO

LOC

LOS

LP

LS

LSH

LSHH

LSL

LSLL

LT

LTG

LUB

M

MA

M.A.

MAL

MALL

MAG

MAN

MAX

MCC

MCM

MCP

MH

MI

MIR

MIN

MIT

MMS

MOV

MS

MSB

MTD

M.W.

NA

NBK

N.C.

N.C.T.C.

N.C.T.O.

NEG

NIC

N.O.

N.O.T.C.

N.O.T.O.

NP

NTS

NOX

O O/C O.C.

OA

OAH

OAHH

OE

OI

OIR

OT

OIT

OSF

OL

PDI

PMP or P

PB

PA

PAH

PAHH

PAL

PALL

PC

PCV

PDI

PE

PG

PH

PI

P&ID

PIC

PIR

PLC

PLT

PNL

POS

POT

POZ

PP

PS

PSE

PSH

PSI

PSL

PT

PSV

PVC

PWR

QL

REQD

RD

RDAH

RDS

RECEPT

RES

RGS

RM

RPM

RT

RTC

S

SB

SCFM

SCH

SD

SD/O

SDV

SEC

SECT

SEL

SEQ

SF

SFR

SG

SHLD

SHT

SI

SPECS

SS

SSR

ST

STA

STD

STR

SW

SYS

T or TK

TACH

TAH

TAHH

TAL

TALL

TB

TC

TCV

TCZ

TD or TDR

TE

TEMP

TES

TEW

THERM

TI

TIC

TIR

TIT

TMR

TR

TS

TSE

TSH

TSL

TSO

TSV

TT

TW

TYP

UG

UPS

UV

V

VA

VAH

VAHH

VFD

VI

VIR

VP

VS

VSD

VSH

VT

W

W.C.

WP

XFMR

XP

YA

YI

YIC

ZA

ZC

ZI

ZS

ZSC

ZSO

MOT SP

MOD SOV

GRANULAR ACTIVATED CARBONGAC

PRESSURE INDICATING TRANSMITTERPIT

VARIABLE FREQUENCY DRIVE (VFD)

INTERNAL WIRE CONNECTION WITHIN DEVICE

ABBREVIATIONS

G-002

GAS COLLECTION AND CONTROL SYSTEMGCCS

BOTTOMBTM

POSITIONERZ

SYMBOLS AND

GAS HANDLING SKIDGHS

EXISTING GRADEEG

TEMPERATURE VALVETV

TOP OF FOOTINGTF

BOTTOM OF FOOTING OR BLIND FLANGEBF

FORCEMAINFM

DUAL CONTAINMENT PIPINGD/C

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 2-

G -0

.d w g

/1

8/

0:

:5 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

NONE

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

E4635 Johnny Gayman 2024

DEMOLITION/SALVAGE/RELOCATION CONSTRUCTION NOTES (PER SHEET C-101/C-102)

RELOCATE SEWAGE TANK AND DRAIN LINE TO FLARE STATION

RELOCATE PORTABLE STAIR CASES

REMOVE/DEMO 6' HIGH CHAIN LINK FENCE WITH 3-STRAND BARBED WIRE, GATES

RELOCATE CARGO AND STORAGE CONTAINERS, VARIOUS SIZES AND WEIGHTS PER PLAN

REMOVE/DEMO EXISTING CONCRETE SLABS/FOOTINGS (THICKNESS VARIES) AND CONDUITS

RELOCATE STORAGE CONTAINER TO FLARE STATION OR AREA DESIGNATED BY COUNTY

PROTECT EXISTING STRUCTURE/PIPE IN PLACE

DESCRIPTION# QTY (OR APPROVED EQUAL) REFERENCE NOTES

RELOCATE COUNTY OPERATION'S TRAILER (12' X 40') TO FLARE STATION 1 EA EXISTING SEE C-101/M-101 CONNECT ALL UILITIES

1 EA EXISTING SEE C-101/M-101 CONNECT WITH 3" LINE TO TRAILER

3 EA EXISTING SEE C-101/M-101 -

5 EA EXISTING SEE C-101/M-101 -

1 EA EXISTING SEE C-101/M-101 AFTER NEW FLARE STATION IS OPERATIONAL

AS REQ'D EXISTING SEE C-102 PREVIOUS POWER PLANT CONDUITS NOT SHOWN

400 LF EXISTING SEE C-102 -

4 EA EXISTING SEE C-102/M-101 -

AS REQ'D - SEE C-102/C502

AS REQ'D - - -

120 LF - -

IF ENCOUNTERED DURING GRADING/EARTHWORK

AS REQ'D EXISTING

30 LF EXISTING - -

SUPPLIER OR MFR. DETAIL/SHEET

PART NO.

MODEL OR

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

2 EA - -

EXISTING

EXISTING

EXISTING

EXISTING

REMOVE EXISTING 24" STORM DRAIN LINE/BURIED HEADWALL11

PLUG/GROUT END OF EXISTING 24" STORM DRAIN LINE12

SAWCUT AND REMOVE SECTION OF AC BERM14

INSTALL 12" CONCRETE AROUND OUTLET GRATE

- -20 LF ISCO INDUSTRIES - -

4 EA ISCO INDUSTRIES - GHS-1/GHS-2 DRAIN AND SUMP BALANCE LINES

10 EA GRAINGER PER DETAIL 1/C-302 GHS-2 DRAIN LINE CONNECTION

8 EA PER DETAIL 8/C-501 -

SITE IMPROVEMENTS/GRADING/FIELD PIPING CONSTRUCTION NOTES (C-103, C-301, C-302, C-501, C-502, C-503)

CONSTRUCT 6" AC PAVEMENT OVER 12" CLASS 2 BASE

CONSTRUCT 6" THICK CONCRETE V-DITCH, APPROX. 5' WIDE, DEPTH VARIES

INSTALL 6" ATRIUM STYLE INLET GRATE

INSTALL 6" SINGLE WALL DRAIN PIPE, HDPE

SAWCUT AND REMOVE AC PAVEMENT SECTION

9,550 SF CONTRACTOR OR SUB SEE DWG C-103/C-105

11 CY CONTRACTOR OR SUB SEE DETAIL 2/C-501 WITH 6x6 W1.4/1.4 WWM

100 LF ADVANCED DRAINAGE SYS SEE DWG C-103 DRAINAGE SWALE DRAIN PIPE

1 EA LOCAL SUPPLIER SEE DWG C-103 V-DITCH INLET STRUCTURE

2,000 SF CONTRACTOR OR SUB SEE DWG C-103/C-105 SEE DETAILS 6 & 7/C-501

PER PLAN

PER PLAN

INSTALL 1" SDR 11 HDPE PIPE & FITTINGS

INSTALL 2" HDPE SADDLE

INSTALL 2" SS CHECK VALVE, Y SPRING TYPE

INSTALL 6" STEEL BOLLARD AND PLASTIC SLEEVE

6 EA --61 INSTALL 2" X 1" HDPE REDUCER

6 EA --62 INSTALL 1" HDPE TO SS TRANSITION FITTING

6 EA --63 INSTALL 1" SS COUPLING

2 EA --64 INSTALL 1" X 3/4" SS REDUCER BUSHING

4 EA --65 INSTALL 1" X 1/2" SS REDUCER BUSHING

66 INSTALL 3/4" SS PIPE NIPPLE

CUSTOM

ISCO INDUSTRIES

ISCO INDUSTRIES

GRAINGER

GRAINGER

GRAINGER

GRAINGER2 EA

67 INSTALL 1/2" SS PIPE NIPPLE

68 INSTALL 4" X 2" HDPE D/C TERMINATION FITTING

69 INSTALL 8" X 4" HDPE D/C TERMINATION FITTING

GRAINGER4 EA --

ISCO INDUSTRIES6 EA --

ISCO INDUSTRIES6 EA --

ISCO INDUSTRIES6 EA --

ISCO INDUSTRIES6 EA --

72 INSTALL 4" HDPE BALL VALVE, BUTT X BUTT ISCO INDUSTRIES1 EA --

SUMP CONNECTION AND SUMP BALANCE LINES

SUMP CONNECTION

SUMP CONNECTION

SUMP LIQUID DISCHARGE CONNECTION

SUMP AIR & BALANCE LINE CONNECTION

4" CONDENSATE LINE CLEAN-OUT

73 INSTALL 30" SDR 17 HDPE PIPE ISCO INDUSTRIES80 LF SEE DETAIL 6/C-501-

74 INSTALL 30" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, AND HARDWARE ISCO INDUSTRIES3 ASSY --

INSTALL 30" X 24" HDPE REDUCER

ISCO INDUSTRIES

2 EA

INSTALL 24" X 18" HDPE REDUCER

ISCO INDUSTRIES

2 EA

INSTALL 18" X 12" HDPE REDUCER

ISCO INDUSTRIES

4 EA

INSTALL 18" SDR 17 HDPE PIPE

ISCO INDUSTRIES

100 LF

INSTALL 18" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, AND HARDWARE

ISCO INDUSTRIES

4 EA

INSTALL 18" HDPE ELBOW, 90°, SDR 17

ISCO INDUSTRIES

2 EA

SEE DETAIL 7/C-501-

81 ISCO INDUSTRIES --

82 ISCO INDUSTRIES --

INSTALL 30" HDPE TEE, SDR 17

INSTALL 30" HDPE ELBOW, 90°, SDR 17 2 EA

1 EA

INSTALL 2" SDR 11 HDPE x 4" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS 140 LF83 ISCO INDUSTRIES -

INSTALL 4" SDR 11 HDPE x 8" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS 220 LF84 ISCO INDUSTRIES -

INSTALL SALVAGED 12" BUTTERFLY VALVE 2 EA85 - -

(DELETED) -86 - -

SEE DETAILS 6 & 7/C-501

INSTALL 24" SDR 17 HDPE PIPE

INSTALL 12" SDR 17 HDPE PIPE

INSTALL 2" SDR 9 HDPE PIPE & FITTINGS

INSTALL 2" SDR 11 HDPE PIPE & FITTINGS

INSTALL 1 1/2" DOUBLE CHECK VALVE ASSEMBLY PER SAN BERNARDINO COUNTY STANDARDS

100 LF ISCO INDUSTRIES

20 LF ISCO INDUSTRIES

200 LF ISCO INDUSTRIES

40 LF ISCO INDUSTRIES

1 ASSY

SEE DETAIL 10/C-501 UNIT #4 HEADER

- INLET TO GHS-2

- COMPRESSED AIR LINE

- CONDENSATE FORCEMAIN

INSTALL 24" BUTTERFLY VALVE WITH 3' VALVE EXTENSION AND GEAR OPERATOR 1 ASSY -

INSTALL 24" HDPE TEE, SDR 17 1 EA ISCO INDUSTRIES -

INSTALL 24" HDPE ELBOW, 90°, SDR 17 2 EA ISCO INDUSTRIES -

INSTALL 24" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT 5 EA ISCO INDUSTRIES -

INSTALL 24" PVC BLIND FLANGE 1 EA ISCO INDUSTRIES UNIT #4 HEADER

5 EA CUSTOM SEE DETAIL 2/C-502 SUMP OUTLET PIPING

3 EA ISCO INDUSTRIES -

4 EA ISCO INDUSTRIES -

550 LF - WATER LINE FOR SWMD TRAILER

INSTALL 2" HDPE BALL VALVE, BUTT X BUTT 11 EA ISCO INDUSTRIES CONDENSATE FORCEMAIN, 2" CLEAN-OUT

JOIN EXISTING 6" WATER LINE PER SAN BERNARDINO COUNTY STANDARDS 1 EA - SEE DETAIL 2/C-503 -

SEE WALL PROFILES, C-201/C-202

INSTALL 2" HDPE TO STAINLESS STEEL TRANSITION FITTING (BUTT x MPT) 20 EA ISCO INDUSTRIES SEE DETAIL 1/C-301/302 CONDENSATE FORCEMAIN CHECK VALVES

1 ASSY REAL ENV. PRODUCTS SEE DWG C-301/D-601 -

INSTALL CONDENSATE SUMP ASSEMBLY "B", SERIES 7000 SUMP, 18" X 24" DUAL CONTAINED 1 ASSY REAL ENV. PRODUCTS SEE DWG C-302/D-601 -

SITE IMPROVEMENTS/GRADING/FIELD PIPING CONSTRUCTION NOTES (C-103, C-104. C-301, C-302, C-501, C-502)

ISCO INDUSTRIES

INSTALL PIPE SUPPORT, CONCRETE FOOTING AND SIGN

INSTALL 12" HDPE ELBOW, 90°, SDR 17

INSTALL 12" HDPE FLANGE ADAPTER, D.I, BACK-UP RING, GASKET, AND BOLT KIT

INSTALL 1 1/2" CLASS 150 PVC WATER PIPE & FITTINGS

SEE SHEET C-503

PER PLAN

PER PLAN

JOIN EXISTING AS REQ'D -

INSTALL 6" AC BERM

GRADE AREA TO CONTOURS SHOWN (PRIMARILY CUT TO INSTALL FOOTINGS & WALLS)

55 LF CONTRACTOR OR SUB SEE DWG C-103

PER PLAN CONTRACTOR OR SUB SEE DWG C-103

1 EA ISCO INDUSTRIES

COORDINATE WITH COUNTY/SCE

PER PLAN

AS REQ'D -

INSTALL CONDENSATE SUMP ASSEMBLY "A", SERIES 7000 SUMP, 30" X 36" DUAL CONTAINED

EXISTING HIGH VOLTAGE POWER POLE(S) TO BE REMOVED BY OTHERS

SEE DETAIL 3/C-503

(DELETED)

INSTALL 12" 22 1/2° HDPE ELBOW, SDR 17

SEE SUMP "A" AND GHS-1 INLET PIPING PROFILE

SEE SUMP "B" AND GHS-2 INLET PIPING PROFILE

SEE DETAIL 1/C-301

SEE DETAIL 1/C-302

INSTALL 4" X 2" HDPE REDUCER, SDR 11 5 EA ISCO INDUSTRIES

DESCRIPTION# QTY (OR APPROVED EQUAL) REFERENCE NOTES

SUPPLIER OR MFR. DETAIL/SHEET

PART NO.

MODEL OR

DESCRIPTION# QTY (OR APPROVED EQUAL) REFERENCE NOTES

SUPPLIER OR MFR. DETAIL/SHEET

PART NO.

MODEL OR

CONDENSATE FORCEMAIN

SUMP AIR & BALANCE LINE CONNECTION

SUMP LIQUID DISCHARGE CONNECTION

INSTALL 4" X 2" HDPE D/C 45° WYE FITTING

INSTALL 8" X 4" HDPE D/C 45° WYE FITTING

ESTIMATED ESTIMATED

INSTALL 1 1/2" CLASS 150 PVC BALL VALVE, NSF/ANSI 61 STANDARD AND HOSE BIB 1 ASSY87 HAYWARD OR EQUAL -

INSTALL WATER LINE THRUST BLOCK88 2 EA - - SEE DETAIL 1/C-503

REMOVE/SALVAGE EXISTING SUMP, VALVES, PIPE, AND FITTINGS AFTER NEW FLARE STATION IS OPERATIONAL

INSTALL 6" MITERED DRAINAGE GRATE (JOIN WITH FERNCO COUPLING) 1 EA DRAINAGE SOLUTIONS 6MD3P

RELOCATE EXISTING FLARE STATION O&M TRAILER TO NEW FLARE STATION COMPOUND

DEMOLITION AND DISPOSAL OF THE EXISTING FLARE STATION: INCLUDES ALL CONCRETE

SLABS, FOOTINGS, WALLS, FENCING, FLARE STACKS, INTERCONNECT GAS SYSTEM PIPING

AND FITTINGS (ABOVE AND BELOW GRADE), PIPE SUPPORTS AND FOOTINGS,

INSTRUMENTATION, COMPRESSORS, COMPRESSED AIR LINES (ABOVE AND BELOW GRADE),

CONDENSATE DRAIN LINES (ABOVE AND BELOW GRADE), CONDENSATE INJECTION SYSTEM

(ABOVE AND BELOW GRADE), FLARE PILOT FUEL SYSTEM (PROPANE, ABOVE AND BELOW

GRADE), CONDENSATE STORAGE TANK, PUMPS, BLOWERS, KNOCK-OUT VESSEL, VALVES,

ELECTRICAL PANELS, CONDUITS (ABOVE AND BELOW GRADE), WIRING, AND SWITCHGEAR

AS DIRECTED BY THE COUNTY. SALVAGE BLOWERS AND ANY OTHER ITEMS AT THE

DISCRETION OF THE COUNTY.

REMOVAL OF EQUIPMENT FROM FLARE STATION

SHALL BE COMPLETED AFTER THE NEW FLARE

STATION IS OPERATIONAL, INCLUDING SOURCE

TESTING. THE COUNTY WILL DETERMINE IF ANY

OF THE EXISTING FLARE STATION EQUIPMENT IS

SALVAGEABLE FOR COUNTY PURPOSES PRIOR

TO DISPOSAL/REMOVAL. THE COUNTY WILL

ASSIGN AN AREA NEAR THE FLARE STATION FOR

EQUIPMENT STORAGE.

SEE SHEET C-102 FOR

EXISTING FLARE

STATION AREA

AS REQ'D EXISTING - --EXISTING TELEPHONE LINE TO BE REMOVED FROM POWER POLE BY OTHERS15

DEMOLITION/SALVAGE/

SITE IMPROVEMENTS

CONSTRUCTION NOTES

G-003 NONE

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 3-

G -0

.d w g

/1

8/

0:

:5 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

FLARE STATION CONSTRUCTION NOTES (M-101, M-501, M-502)

INSTALL/ANCHOR GAS HANDLING SKID (GHS-1) WITH EPOXY ANCHORS

INSTALL/ANCHOR GAS HANDLING SKID (GHS-2) WITH EPOXY ANCHORS

INSTALL/ANCHOR 5,000 SCFM LOW NOx FLARE STACK AND COMBUSTION AIR BLOWER

INSTALL SALVAGED SEPTIC TANK AND TRAILER DRAIN LINE (HOLE THROUGH WALL)

INSTALL/ANCHOR 1,000 SCFM LOW NOx FLARE STACK AND COMBUSTION AIR BLOWER

INSTALL INTERCONNECT PIPING, VALVES, EQUIPMENT

INSTALL 40'W x 40'L x 14'-8"H PRE-FABRICATED ROOF STRUCTURE

INSTALL 55 GALLON GRANULAR ACTIVATED CARBON DRUM AND 4X8 COCONUT CARBON

INSTALL LED AREA FLOOD LIGHT (2 PER POLE)

DESCRIPTION# QTY MANUFACTURER REFERENCE NOTES

INSTALL/ANCHOR ROTARY SCREW COMPRESSOR, DRYER, OIL/WATER SEPARATOR 2 ASSY SUPPLIED BY P.E.I./KAISHAN SEE P.E.I. REF. DWGS ANCHOR PER

1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS ANCHOR PER

1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS ANCHOR PER

1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS FLR-2

1 ASSY SUPPLIED BY P.E.I. SEE P.E.I. REF. DWGS FLR-1

- SUPPLIED BY P.E.I. -

1 ASSY EXISTING - -

1 ASSY EMPIRE STEEL OR EQUAL SEE SHEET S-303/M-503 -

1 EA TETRASOLV FILTRATION - V-3 (TK-701 VENT STACK)

12 EA E-CONOLIGHT SEE SHEET M-101/E-101 -

6 EA SEE SHEET M-101/E-101 -

VARIOUS DURALABEL SEE DETAIL 3/M-502 -

1 ASSY CONTRACTOR OR SUB SEE STRUCTURAL DWGS SEE SHEETS C-201, C-202

20 LF - - COMPRESSED AIR @ FLARES

110 LF - - FLARE PILOT LINES

150 LF - - FLARE CONDENSATE INJECTION

120 LF HARRINGTON PLASTICS - PIPING BETWEEN TK-701/PMP-701/702

SUPPLIER OR DETAIL/SHEET

PART NO.

MODEL OR

CUSTOM FABRICATION

CUSTOM FABRICATION

EXISTING

VFV-250

E-FFA26 SERIES

E-PS4E20SDB

KRSB-40

CUSTOM FABRICATION

CUSTOM FABRICATION

CUSTOM FABRICATION

CUSTOM FABRICATION

E-CONOLIGHTINSTALL 4" SQUARE STEEL POLE, FLOOD LIGHT

6 EA E-CONOLIGHTINSTALL BULLHORN, FLOOD LIGHT SEE SHEET M-101/E-101E-PT2E180DB

INSTALL PIPE AND EQUIPMENT LABELS, 3.2MM THICK ADHESIVE

INSTALL 1/2" GALVANIZED STEEL PIPE & FITTINGS (COMPRESSED AIR)

INSTALL 1/2" SCH 40 STAINLESS STEEL PIPE & FITTINGS (CONDENSATE INJECTION)

INSTALL STRUCTURAL SLAB, BLOCK WALL, FOOTINGS, PILASTERS, PADS, ETC.

INSTALL 1" SCH 80 PVC PIPE & FITTINGS

VARIOUS

140 LF - - --INSTALL 1" SCH 40 GALVANIZED STEEL PIPE & FITTINGS (COMPRESSED AIR)

- - SEE DETAIL 5/M-501 --

INSTALL 2" SDR 9 HDPE PIPE & FITTINGS (COMPRESSED AIR) 60 LF ISCO INDUSTRIES - PIPING FROM PMP-701/702 TO FIELD-

INSTALL 2" SDR 11 HDPE PIPE & FITTINGS (CONDENSATE) 100 LF ISCO INDUSTRIES - KNOCK-OUT DRAIN LINES-

INSTALL 2" SCH 80 PVC PIPE & FITTINGS (VENT PIPING, DRAIN LINES)

INSTALL 1/2" SCH 40 BLACK IRON PIPE & FITTINGS (PROPANE)

INSTALL 8" SQUARE METAL SIGN, WHITE BACKGROUND, BLACK LETTERING, 1/2" MIN.

INSTALL TK-701 DRAIN AND CONDENSATE FM ON WALL

INSTALL 12" SDR 17 HDPE PIPE

INSTALL 12" SCH 10 304SS PIPE

INSTALL 24" SDR 17 HDPE PIPE

INSTALL PIPE SUPPORT RACK

50 LF HARRINGTON PLASTICS

3 EA LOCAL SIGN COMPANY

50 LF ISCO INDUSTRIES

40 LF -

30 LF ISCO INDUSTRIES

1 ASSY CONTRACTOR

- TK-701/GAC VENT PIPING-

SEE DETAIL 4&5/M-501 MOUNT W ITH SCREWSCUSTOM FABRICATION

SEE DETAIL 6/M-501 --

- GHS-2 INLET PIPING/INTERCONNECT-

- DISCHARGE PIPING TO POWER PLANT-

- GHS-1 INLETE PIPING-

DETAIL 1/M-501 TK-701 PIPE RACKCUSTOM FABRICATION

INSTALL SMALL PIPE SUPPORT AND CONCRETE FOOTING 1 EA CONTRACTOR TK-701 DRAIN

INSTALL SMALL CONDUIT/PIPE ANCHOR AS REQ'D CONTRACTOR -

INSTALL PIPE SUPPORT 3 EA CONTRACTOR TK-701 DRAIN AND INLET LINES

INSTALL SIGN, 7" X 10" (DANGER-NO SMOKING, MATCHES, OR OPEN LIGHTS) 3 EA McMASTER CARR FASTEN TO WALL

INSTALL 3/8"Ø X 6" LONG CONCRETE ANCHOR AS REQ'D SIMPSON -

INSTALL LEVEL TRANSMITTER (0-14'), STANDARD ACCURACY, 4-20mA OUT, 24VDC, 40' CABLE 1 EA KELLER AMERICA DETAIL 1/M-501 LT-701 @ TK-70181355

CAMERA, NETWORK,1080P FULL HD, 20X ZOOM, NEMA 4X, 60W UPoE 4 EA VIVOTEK - -SD9361-EHL

INSTALL CABLE RAMP, 3' WIDE X 2' LONG (4" X 4" CHANNEL), ALUMINUM, DIAMOND PLATE 2 EA MCMASTER CARR M-101 -2233T75

INSTALL PORTABLE EMERGENCY EYEWASH STATION (MOUNT TO BLOCK WALL) 1 EA McMASTER CARR M-101 -54285T16

INSTALL FIRE EXTINGUISHER, 5 LB CLASS A,B,C, MOUNTING BRACKET 1 EA McMASTER CARR M-101 -6430T16

RELOCATE EXISTING TRAILERS/STORAGE CONTAINERS PER ASSEMBLY PLAN 7 EA EXISTING C-102/M-101 COORDINATE WITH COUNTYEXISTING

INSTALL 8700 GALLON POLY CONDENSATE TANK, DOUBLE WALL, WITH APPURTENANCES 1 ASSY POLY PROCESSING/CORE-ROSION SEE D-601 WITH FITTINGS, TK-701ASSEMBLY 1

INSTALL AUTOMATIC SLIDING GATE OPENER, 1 1/4 HP MOTOR, UP TO 40' LENGTH, 5700 LBS 1 ASSY TOPENS WITH TKPS WIRELESS KEYPAD AND (4) M12 REMOTE CONTROLSCK2600

INSTALL 3/8"Ø X 4" LONG CONCRETE ANCHOR AS REQ'D SIMPSON - -TITEN HD

INSTALL POST BASE, 1 5/8" X 1 5/8", GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --

INSTALL STRUT CHANNEL, 1 5/8" X 1 5/8", 0.105 , GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --

INSTALL STRUT CHANNEL, 1 5/8" X 3 1/4", 0.105, GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --

INSTALL PIPE CLAMP, STRUT CHANNEL, GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - -SIZE VARIES

INSTALL PLASTIC STRUT CHANNEL END CAP, 1 5/8" X 1 5/8" AS REQ'D ACME CONSTRUCTION SUPPLY - --

AS REQ'D ACME CONSTRUCTION SUPPLY - --

INSTALL STRUT CHANNEL "L" BRACKET FITTING, GALVANIZED AS REQ'D ACME CONSTRUCTION SUPPLY - --

INSTALL STRUT CHANNEL FLAT "T" FITTING, GALVANIZED 4 EA ACME CONSTRUCTION SUPPLY - --

2 EA ACME CONSTRUCTION SUPPLY - --

INSTALL 2" PVC BALL VALVE, TRUE UNION, S xS 3 EA HARRINGTON PLASTICS - --

AS REQ'D - - ALL EXPOSED CONDENSATE LINES-

2 EA - -HARRINGTON PLASTICS - GAC INLET & OUTLET-

AS REQ'D ASAHI --

1 EA GROTH SEE DETAIL 1/M-501 TANK VENT7622B

6 EA HARRINGTON PLASTCIS - GAC INLET & OUTLET, TANK VENT-

3 EA EXISTING PER SHEET M-101 LEVEL AND SET WITH TRAILEREXISTING

DETAIL 2/M-501CUSTOM FABRICATION

DETAIL 3/M-501CUSTOM FABRICATION

DETAIL 4/M-501CUSTOM FABRICATION

DETAIL 1/M-50257235T75

-TITEN HD

INSTALL PLASTIC STRUT CHANNEL END CAP, 1 5/8" X 3 1/4"

INSTALL POST BASE, 1 5/8" X 3 1/4", GALVANIZED

INSTALL PIPE INSULATION

INSTALL 2" PVC UNION, S x S

INSTALL 1/4" LABCOCK VALVE, MPT X HOSE

INSTALL 2" STAINLESS STEEL FLAME CHECK

FLARE STATION CONSTRUCTION NOTES (M-101, M-501, M-502)

INSTALL 8" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT

INSTALL 12" x 8" HDPE REDUCER

INSTALL 12" BUTTERFLY VALVE, SS DISK & STEM, VITON SEALS AND SEATS, GEAR OP

INSTALL 12" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT

INSTALL 24" X 18" HDPE REDUCER

DESCRIPTION# QTY MANUFACTURER REFERENCE NOTES

TK-701 DRAIN LINE

3 EA ISCO INDUSTRIES - CONDENSATE SYSTEM

2 EA LOCAL SUPPLIER - FLARE PILOT FUEL @ GHS-1

AS REQ'D ISCO INDUSTRIES - -

1 EA ISCO INDUSTRIES - GHS-1/GHS-2 INLET INTERCONNECT

1 EA ISCO INDUSTRIES - GHS-2 INLET CONNECTION

1 EA ISCO INDUSTRIES -

1 EA ISCO INDUSTRIES -

2 ASSY ISCO INDUSTRIES -

2 EA ISCO INDUSTRIES - GHS-1 INLET PIPING

2 EA -

SEE BASE PLATES PER 1/S-502

1 ASSY ISCO INDUSTRIES - GHS-1 CONNECTION

4 EA - - DISCHARGE PIPING TO POWER PLANT

1 ASSY CUSTOM FABRICATION - WITH LOCKING MECHANISM

1 ASSY CUSTOM FABRICATION SEE DETAIL 2/M-502 AND DETAILS 4,5,6,7/S-504

4 EA - -

12 EA SIMPSON - BLOWER SKID ANCHORING

SUPPLIER OR DETAIL/SHEET

PART NO.

MODEL OR

ISCO INDUSTRIESINSTALL 18" X 12" HDPE REDUCER

13 EA CUSTOM FABRICATIONINSTALL PIPE SUPPORT RACK SEE DETAIL 1/S-506

INSTALL 3' X 8' CHAIN LINK FENCE MAN GATE WITH TAN PLASTIC SLATS

INSTALL 12" STAINLESS STEEL ELBOW, SCH 10S

INSTALL 12" 150# STAINLESS STEEL FLANGE, WELD NECK OR SOCKET WELD, SHORT

INSTALL 3/4"Ø ALL-THREAD RODS WITH SIMPSON SET-3G EPOXY, 6" MINIMUM EMDEDMENT

- - - -(DELETED)

1 ASSY EATON OR EQUAL

INSTALL 1" STAINLESS STEEL BALL VALVE, NPT 2 EA - - -

INSTALL PRESSURE TRANSMITTER, 0-200 PSIG, 4-20Ma OUTPUT, 9 TO 36 VDC, 1/4" 1 EA AUTOMATION DIRECT - COMPRESSOR DISCHARGE (PT-401)

INSTALL 2-10'± CHAIN LINK FENCE GATES WITH TAN PLASTIC SLATS

INSTALL 22' WIDE X 8' TALL SLIDING GATE AND APPURTENANCES

INSTALL 2,000 AMP/480V ELECTRICAL SWITCHGEAR, 3 SECTION

INSTALL/ANCHOR 24" PIPE SUPPORT

INSTALL ALUMINUM PLATFORM WITH STAIRS, HANDRAILS, PLATFORM, AND SUPPORTS

INSTALL 24" HDPE TEE, SDR 17

INSTALL 1/2"Ø ALL-THREAD RODS WITH SIMPSON SET-3G EPOXY, 6" MINIMUM EMBEDMENT

1 ASSY CUSTOM

2 EA

5 EA

2 EA CUSTOM

1 ASSY MCMASTER CARR

1 EA ISCO INDUSTRIES

8 EA SIMPSON

- WITH LOCKING MECHANISM

GHS-2 OUTLET

GHS-2 INLET PIPING

SEE DETAIL 5/S-505 GHS-1 INLET PIPING

- GHS-1 INLET PIPING

- COMPRESSOR ANCHORS-

2 ASSY BY CONTRACTOR

PURCHASED BY COUNTY (LONG-LEAD ITEM)

SPT25-20-0299D

4198N42(2), 4198N62(2), 4198N52, 4198N72

SEE P.E.I. REF. DWGS

INSTALL 2" PVC MALE ADAPTER, MPT x SOC

(DELETED)

INSTALL TRAILER STAIRCASES

INSTALL 2" PVC CAMLOCK AND PLUG 2 EA HARRINGTON PLASTICS SEE P.E.I. REF. DWGS

INSTALL 2" HDPE BALL VALVE, BUTT x BUTT

INSTALL 5 GALLON PROPANE BOTTLE

INSTALL 2" HDPE TO STAINLESS STEEL TRANSITION FITTING, BUTT x MPT

INSTALL 12" HDPE TEE, SDR 17

CUSTOM SEE DETAIL 3/S-505

CUSTOM SEE DETAIL 4/S-505

INSTALL/ANCHOR 8" PIPE SUPPORT

INSTALL/ANCHOR 12" PIPE SUPPORT

27"H X 24"W, 60" PLATFORM

SEE DETAIL 1/E-502

INSTALL 12" PE-RT ELECTRO-FUSION COUPLING

INSTALL 18" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT

GAC INLET & OUTLET

- GHS-2 INLET CONNECTION

GHS-1/GHS-2 INLET INTERCONNECT

GHS-1/GHS-2 INTERCONNECT VALVE

GHS-1/GHS-2 INLET PIPING

DISCHARGE PIPING TO POWER PLANT

ESTIMATED

INSTALL 2" AIR AND CONDENSATE DRAIN LINES ON WALL

ESTIMATED

1 ASSY OLDCASTLE PRECAST OR EQUAL191 INSTALL 4' X 6' PRE-CAST PME CONCRETE SLAB (SCE SWITCH PAD)

1 ASSY OLDCASTLE PRECAST OR EQUAL192 INSTALL 10' X 12' PRE-CAST CONCRETE SLAB AND BOX (SCE TRANSFORMER PAD/BOX)

- VERIFY WITH SCE DESIGNSCE APPROVED

- VERIFY WITH SCE DESIGNSCE APPROVED

FLARE STATION

CONSTRUCTION NOTES

G-004

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 4-

G -0

.d w g

/1

8/

0:

:0 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

NONE

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

S D

S D

120/240V/1Ø

100 AMP

24"

UNIT #4

UNIT #1

UNIT #3 UNIT #2

UNIT #5

PROPOSED NEW FLARE

STATION LOCATION

PROPOSED RENEWABLE

ENERGY PLANT LOCATIONEXISTING FLARE

STATION LOCATION

SCALE HOUSE

CONTROL POINT 26

N 1874864.4010 E 6737564.6290

ELEV.=1568.80

MID-VALLEY LANDFILL

EXISTING LANDFILL

OPERATIONS COMPOUND

CONTROL POINT 20

N 1872967.9410 E 6733650.6400

ELEV.=1548.67

A

LD

E R

A V

E

M A

N G

O A

V E

CASMALIA ST.

LOCATION OF EXISTING

OR PROPOSED COUNTY

TRAILER AND TWO (2)

STORAGE CONTAINERS

1 2 3 4

CONTROL POINT 41

N 1874994.5390 E 6735079.7580

ELEV.=1593.31

210 FREEWAY

TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT.

RELOCATE EXISTING SEWAGE TANK AND DRAIN LINE TO FLARE STATION

RELOCATE EXISTING PORTABLE STAIR CASES TO FLARE STATION

RELOCATE EXISTING CARGO AND CARGO CONTAINERS TO FLARE STATION

RELOCATE EXISTING COUNTY OPERATION'S TRAILER (12' X 40') TO FLARE STATION 1

CONSTRUCTION NOTES

RELOCATE EXISTING STORAGE CONTAINERS TO NEW FLARE STATION8 OR AREA DESIGNATED BY COUNTY

RELOCATE EXISTING FLARE STATION O&M TRAILER AND APPURTENANCES

TO NEW FLARE STATION OR AREA DESIGNATED BY COUNTY

SITE PLAN/SURVEY CONTROL/

RELOCATION PLAN

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 5-

C -1

.d w g

/1

8/

0:

:1 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

C-101 1"=300' 5

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

FUTURE RENEWABLE ENERGY POWER PLANT AREA

EXISTING

FLARE

STATION

UNIT #2

ACCESS ROAD

EXISTING OPERATIONS COMPOUND

STORAGE CONTAINER

EDGE OF SLAB

AC PAVEMENT

INLET STRUCTURE

AC CURB FOR 14

7 10

WIDTH TO MATCH

NEW DRIVE ENTRANCE

PER SHEET C-103

EXISTING INLET

STRUCTURE

B-9 B-6

B-10

B-7

FORMER POWER PLANT AREA

UNIT #4

E

E

E

E S

D S

D S

D S

D S

D S

D S

D S

D S

D S

D S

D S

D S

D S

D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

120/240V/1Ø

100 AMP

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

24"

E E E

PP

PP

SLAB

(UNDER CONSTRUCTION)

MAIN ACCESS ROAD (PAVED)

W W

E

E E

EXISTING 6" WATER LINE

O/H ELEC

O/H ELEC

WATER LINE

POWER PLANT UTILITY TRENCH 10

TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT AND SURVEY PERFORMED BY TETRA TECH ON

4/3/2022 AT FLARE STATION AREA.

TEST BORING LOCATION (FORMER POWER PLANT PROJECT)

LEGEND

B-1

X X EXISTING CHAIN LINK FENCE

SD EXISTING STORM DRAIN LINE

EXISTING STREET LIGHT FIXTURE

E EXISTING OVERHEAD ELECTRICAL AND POWER POLE (PP)

PP

REMOVE/DEMO 6' HIGH CHAIN LINK FENCE WITH 3-STRAND BARBED WIRE, GATES

REMOVE/DEMO EXISTING CONCRETE SLABS/FOOTINGS (THICKNESS VARIES) AND CONDUITS

PROTECT EXISTING STRUCTURE/PIPE IN PLACE

REMOVE EXISTING 24" STORM DRAIN LINE/BURIED HEADWALL11

PLUG/GROUT END OF EXISTING 24" STORM DRAIN LINE12

SAWCUT AND REMOVE SECTION OF AC BERM

CONSTRUCTION NOTES

15 EXISTING TELEPHONE LINE TO BE REMOVED FROM POWER POLE BY OTHERS

RELOCATE EXISTING STORAGE CONTAINERS TO NEW FLARE STATION AREA OR AREA DESIGNATED BY COUNTY8

REMOVE/SALVAGE EXISTING CONDENSATE SUMP, VALVES, PIPES, AND FITTINGS9

RELOCATE EXISTING FLARE STATION O&M TRAILER AND APPURTENANCES TO NEW FLARE STATION5 OR AREA DESIGNATED BY COUNTY

EXISTING POWER PLANT UTILITY TRENCH

FLARE STATION DEMOLITION AND REMOVAL (SEE SHEET G-003 AND SPECIFICATIONS FOR SCOPE OF WORK)13

42 EXISTING HIGH VOLTAGE POWER POLE(S) AND OVERHEAD LINE TO BE MOVED BY OTHERS

1"=20' 6

DEMOLITION/SALVAGE PLAN

C-102

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 6-

C -1

.d w g

/1

8/

0:

:2 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

(1590)

3.2%

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

120/240V/1Ø

100 AMP

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

FLARE STATION

ATHEN'S

OPERATIONS

COMPOUND

UNIT #1 LFG

AIR & COND.

EDGE OF

AC ROAD

INLET STRUCTURE

1591.0 TF/TS

1591.25 TS

1592.25 TS

1587.50 TF

1601.50 TW

1587.50 TF

1601.50 TW

(1592.50 FS)

(1

2.

T C

(1587.86 AC/TC=0)

1585.00 BF

1585.50 BF

.0

(1592.00 FS)

SEPTIC

XFMR

1593.50 TC

(1

1.

T C

A

E 6735141.59

N 1874906.46

E 6735005.59

N 1874906.46

1590.2 FS

E 6735141.59

N 1874766.46

1577.5 INV

1586.9± FS

1593.99± CL K-O

(1590.30 TS)

(1589.60 FL)

(1

3.

T C

(1

3.

T C

(1593.36 TC)

.5

TC

1590.8 TS/FL

(1583.53 FL)

(1583.57 TOE)

(1582.88 FL)

E

E

1588.0 BF

(1590.46 FS)

(1590.34 TS)

(1590.24 TS)

1589.59 FL

1589.99 FL/GB

1590.14 FL0.

5%

EXIST

SLAB

EXISTING STORAGE CONTAINER

EXIST SLAB

1.

0%

GR=1583.5±

INV=1579.5±

1576.9± INV

33 FUTURE UNIT #4

LFG CONNECTION

3.4%

A

3.0%

APPROXIMATE

LIMIT OF GRADING

U N

IT

LF

G

A

A

(1590)

(1592)

(1588)

(1586)

1599.50 TW

1591.50 TS

1583.0 TF

1580.5 BF

1585.0 FS

(1580)

SWITCHGEAR

1594.10 FG

(SEE C-104/S-101/M-101)

1592.00

1590.60 TS

1590.5 FS

1590.24

N 1874796.46

E 6735034.93

C

-5

C-501

1585.9± FS

1577.0± ELBOW

1593.83± CL K-O

36" PIPE, 1582.4± INV

(1584)

1575.0

INV

1576.0

INV

1577.0

INV

1579.0±SD INV

1580.0±

SD INV

1580.7±

SD INV

PAVEMENT

EXISTING AC

N 1874840.46 E 6735005.59

ANGLE PT

1593.5

(1

3.

TC

(1

2.

TC

4.0% (1592)

1586.0

OUTLET

(1584.63 AC)

(1582)

1587.30 EL OUTLET

2.0%

82 82

EXIST

SLAB

(1590.29 EX SLAB)

1599.84 TW

1589.37 FL INLET

(8 EA)

LFG, CONDENSATE FORCEMAIN, AND RNG TRENCH

TO POWER PLANT (SEE ARCHAEA AS-BUILT DWGS)

832523 84

(1590.29 FS)

(1590.18 FS)

E 6734924.8

UNIT #1

1%

C-501

FLARE

SLAB

1591.0

C-501

START FL

C-202WING WALL

SEE DETAILS

PAD 1591.5 FF

EXISTING TWIN 36" STORM DRAIN PIPES

AND 2" X 4" D/C FORCEMAIN (UNIT #4)

EXISTING 12" HDPE HEADER, 2" AIR,

1578.0±

INV

SUMP

18" INV=1575.0 (EAST)

A

IR

C

O N

D E

N S

A

TE

N 1874813.3

UNIT #1 SUMP

SUMP "B"

GR=1586.0

E 6734951.3 N 1874811.1

(UNIT #2/3/4)

SUMP "A"

GR=1585.8±

TOP OF FLANGE=1586.0

24" INV=1579.0 (WEST)

24" INV=1575.0 (EAST)

SUMP BTM=1567.0

TOP OF FLANGE=1586.0

18" INV=1581.0 (WEST)

SEE DETAIL

C-502

PAVED ENTRANCE ROAD

EXISTING POWER PLANT

PIPELINE TRENCH (SEE

ARCHAEA DWGS)

60(3 EA)

EXISTING

FLARE

STATION

C-501

10' X 12'

GATE TRACK

.0

@1.3%

1% MIN

HB

W W W W

W

W

W

O/H ELEC

FLARE

SLAB

1591.0

1"=20' 7

SITE IMPROVEMENTS/

GRADING/FIELD PIPING PLAN

C-103

NOTES:

2. TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT AND FIELD SURVEY PERFORMED BY TETRA TECH ON 4-3-2022

AT FLARE STATION AREA. SEE SHEET C-101 FOR CONTROL POINTS.

1. SEE SHEETS G-003 AND G-004 FOR CONSTRUCTION NOTES.

LEGEND

PROPOSED PAVEMENT AREA (BLOCK WALL TO EXISTING PAVED ACCESS ROAD)

1586 PROPOSED FINISH SURFACE CONTOUR

PROPOSED DUAL CONTAINED CONDENSATE FORCEMAIN, SIZE PER PLAN

A PROPOSED COMPRESSED AIR LINE

PROPOSED BELOW GRADE PIPING, SIZE PER PLAN, UNLESS NOTED OTHERWISE

EXISTING PIPING OR PIPE TRENCH BY OTHERS BELOW GRADE, SIZE VARIES

EXISTING INTERIM CONTOUR(1588)

EXISTING INDEX CONTOUR(1590)

DRAINAGE FLOW LINE DIRECTION

EXISTING HIGH VOLTAGE OVERHEAD ELECTRICALE

EXISTING STORM DRAIN LINE, SIZE VARIESSD

PROTECT EXISTING STRUCTURE/PIPE IN PLACE10

CONSTRUCT 6" AC PAVEMENT OVER 12" CLASS 2 BASE

CONSTRUCT 6" THICK CONCRETE V-DITCH, APPROX. 5' WIDE, DEPTH VARIES

INSTALL 6" ATRIUM STYLE INLET GRATE

INSTALL 6" SINGLE WALL DRAIN PIPE, HDPE

SAWCUT AC PAVEMENT

INSTALL 6" STEEL BOLLARD AND PLASTIC SLEEVE

73 INSTALL 30" SDR 17 HDPE PIPE

INSTALL 30" X 24" HDPE REDUCER

INSTALL 18" X 12" HDPE REDUCER

INSTALL 18" SDR 17 HDPE PIPE

INSTALL 18" HDPE ELBOW, 90°, SDR 1782

INSTALL 30" HDPE TEE, SDR 17

INSTALL 30" HDPE ELBOW, 90°, SDR 17

INSTALL 2" SDR 11 HDPE x 4" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS 83

INSTALL 4" SDR 11 HDPE x 8" SDR 17 HDPE DUAL CONTAINED PIPE & FITTINGS84

INSTALL 6" MITERED DRAIN GRATE (CONTOUR CONCRETE /PAVEMENT AROUND GRATE OUTLET)51

INSTALL 24" SDR 17 HDPE PIPE

INSTALL 12" SDR 17 HDPE PIPE

INSTALL 2" SDR 9 HDPE PIPE & FITTINGS

INSTALL 24" BUTTERFLY VALVE WITH 3' VALVE EXTENSION AND GEAR OPERATOR

INSTALL 24" HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET, AND BOLT KIT

INSTALL 24" PVC BLIND FLANGE

INSTALL CONDENSATE SUMP ASSEMBLY "B", SERIES 7000 SUMP, 18" X 24" DUAL CONTAINED

JOIN EXISTING

GRADE AREA TO CONTOURS

INSTALL CONDENSATE SUMP ASSEMBLY "A", SERIES 7000 SUMP, 30" X 36" DUAL CONTAINED

EXISTING HIGH VOLTAGE POWER POLE TO BE REMOVED BY OTHERS

SEE SUMP "A" AND GHS-1 INLET PIPING PROFILE

SEE SUMP "B" AND GHS-2 INLET PIPING PROFILE

CONSTRUCTION NOTES

38 INSTALL 2" WATER LINE PER SHEET C-105 AND C-503

INSTALL 18" SDR 17 HDPE FLANGE ADAPTER, D.I. BACK-UP RING, GASKET AND BOLT KIT81

48 INSTALL 6" AC BERM

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 7-

C -1

.d w g

/1

8/

0:

:2 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

LANDFILL

OPERATIONS

COMPOUND

1591.0 TS/TF

1591.25 TS

1592.25 TS

1599.84 TW

1588.0 BF

1587.50 TF1601.50 TW

1587.50 TF

1593.33 TOP OF CONCRETE WALL

.5

TS

.5

B F

.0 T

F

.5

TW

1585.00 BF

1585.50 BF

1591.00 TS

.60

TS

C O

N S

TR

U

C

TI

O N

J O

IN

T

36" THICK SLAB

1C-202

C-201

C S-302

C

-2

C-201

0.

5%

1589.99 FL

(1590.29 FS)

1589.37 FL/INLET

1591.50 FS

B S-301

PER DETAIL 1/S-504

PER DETAIL 1/S-504

1587.30 FL/OUTLET

1.3%

ELECT. PEDESTAL

(EXISTING SLAB)

2'Ø LIGHT POLE FOOTING

PER DETAIL 1/S-504

2'Ø LIGHT POLE FOOTING

PER DETAIL 1/S-504

2'Ø LIGHT POLE FOOTING

PER DETAIL 1/S-504

2'Ø LIGHT POLE FOOTING

2'Ø LIGHT POLE FOOTING

PER DETAIL 1/S-504

2'Ø LIGHT POLE FOOTING

1.0%

.0

.5

.7

G B

1590.04 FL

1590.09 FL

.2 5 15

.0

1590.14 FL

1590.19 FL

0.

5%

0.

5%

0.

5%

1589.89 FL

1589.79 FL

1589.69 FL

1589.59 FL

1589.49 FL

1590.80 FS/FL

0.

5%

1.

0%

1.

0%

1.

0%

1.

0%

1.

0%

1.1%

0.7%

.0

1.0%

1592.25 FS/TS

1.

2%

0.

6%

1.

0%

RIDGE LINE

18" SLAB

1.

0%

.60 B

F

1601.50 TW

C-501

DRAINAGE OUTLET

EDGE OF SLAB/FOOTING

CONSTRUCTION JOINTCONSTRUCTION JOINT/1591.75

CONSTRUCTION JOINT/1592.0

C

O N

S

TR

U C

TI

O

N J

O

IN

T

C O

N S

TR

U

C

TI

O N

J O

IN

T

1591.00

CONTRACTOR TO COORDINATE

WITH BUILDING CONTRACTOR

ON SIZE AND LOCATION OF

FOOTINGS REQUIRED FOR

40' X 40' ROOF CANOPY, TYP

1591.90 TS

1591.82 TS 1591.25 TS

1591.59 TS

1591.75 TS1591.75 TS

1591.50 FL

1.

2%

1.

3%

C O

N S

TR

U

C

TI

O N

JO

IN

T/

.5

1591.75 TS

0.8%

1591.50 TS

CONSTRUCTION JOINT/1591.50

1591.50 TS

.2

1591.25 TS

1.0%

1.0%

1591.58 TS

1591.75 TS

.0

1.0%

2.8%

1591.25 TS/FL

CONSTRUCTION JOINT

1591.50 TS 1591.40 TS

CONSTRUCTION JOINT

CONSTRUCTION JOINT

ELECTRICAL CONDUITS FROM NEW

TRANSFORMER WALL TO MSB-1

0.5%

1590.90

0.

5%

1590.24 FL

(1590.34 TS)

(1590.30 TS)

1586.00 FL/OUTLET

0.

5%

SKID SHIMMED AND GROUTED

TO ELEV. 1591.70

(SEE NOTES 2 & 3)

SKID SHIMMED AND GROUTED

TO ELEV. 1591.45

(SEE NOTES 2 & 3)

.9

LEVEL

FLARE

SLAB

1591.00 TS

LEVEL

FLARE

SLAB

1591.00 TS

1590.8 FS/FL

1590.85 FL

.7

.8

R

ID

G E

RIDGE

RIDGE

.0

1591.0

1590.95 FL

0.

5%

FL

O

W L

IN

E

R

ID

G E

.0 1590.9

1590.80 FS/FL

DRAINAGE OUTLET15

.9

.8

.7

1590.90

0.8%2.5%

0.8%

1591.75

TANK PAD

LEVEL

1"=8' 8

FLARE STATION

C-104

DRAINAGE PLAN

NOTES:

1. SEE STRUCTURAL DRAWINGS FOR DETAILS ON FOOTINGS, FOUNDATIONS, AND WALLS.

2. SEE SPECIFICATIONS FOR NON-SHRINK GROUT TO BE USED DURING INSTALLATION OF SKIDS.

3. PROVIDE 1" OPENINGS IN GROUT AT 12" O.C. FOR DRAINAGE.

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 8-

C -1

.d w g

/1

8/

0:

:3 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

(1590)

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

S D

120/240V/1Ø

100 AMP

SD

SD

SD

SD

SD

SD

SD

E

FLARE STATION

ATHEN'S OPERATIONS

COMPOUND

EDGE OF

AC ROAD

SEPTIC

XFMR

1584 1585

EXIST

SLAB

EX. STORAGE CONTAINER

3.4%

U N

IT

LF

G

A

(1590)

(1592)

(1588)

(1586)

(1580)

(SEE C-104/S-101/M-101)

(1584)

(1592)

(1582)

LFG, CONDENSATE FORCEMAIN, AND RNG

TRENCH TO POWER PLANT (SEE ARCHAEA DWGS)

UNIT #4

UNIT #1

EXISTING TWIN 36" STORM DRAIN PIPES

AND 2" X 4" D/C FORCEMAIN (UNIT #4)

EXISTING 12" HDPE HEADER, 2" AIR,

SUMP

A

IR

C

O N

D E

N S

A

TE

PAVED ENTRANCE ROAD

POWER PLANT

PIPELINE TRENCH (SEE

ARCHAEA DWGS)

EXISTING

FLARE

STATION

W W

E E

E

W W W W W

44ELEV. 1588.68

W

29 87

10'

CONNECT TO SWMD TRAILER

EXISTING 6"

WATER LINE

EDGE OF

AC ROAD

(1

0)

(1

0)

(1

0)

(1

0)

52 5814 4858 52

1"=40' 9

WATER LINE PLAN

C-105

NOTES:

2. TOPOGRAPHY SOURCE: 6/21/2022 UAS FLIGHT AND FIELD SURVEY PERFORMED BY TETRA TECH ON 4-3-2022

AT FLARE STATION AREA. SEE SHEET C-101 FOR CONTROL POINTS.

1. SEE SHEETS G-003 AND G-004 FOR CONSTRUCTION NOTES.

LEGEND

PROPOSED PAVEMENT AREA (BLOCK WALL TO EXISTING PAVED ACCESS ROAD)

1586 PROPOSED FINISH SURFACE CONTOUR

EXISTING INTERIM CONTOUR(1588)

EXISTING INDEX CONTOUR(1590)

PROPOSED 2" CLASS 150 PVC WATER LINE

CONSTRUCTION NOTES

INSTALL 1-1/2" DOUBLE CHECK VALVE ASSEMBLY PER DETAIL 3/C-503

JOIN EXISTING 6" WATER LINE PER DETAIL 2/C-503

INSTALL 1-1/2" CLASS 150 PVC WATER PIPE & FITTINGS

INSTALL 1-1/2" CLASS 150 PVC BALL VALVE, NSF/ANSI 61 STANDARD, AND HOSE BIB87

INSTALL WATER LINE THRUST BLOCK PER DETAIL 1/C-503 88

W

EXISTING 6" WATER LINEW

1. THE CONTRACTOR SHALL COMPLY WITH SAN BERNARDINO COUNTY PUBLIC WORKS

SPECIAL DISTRICTS STANDARDS FOR WATER.

2. THE CONTRACTOR SHALL DISINFECT THE NEW WATER LINE FROM THE TEE

CONNECTION POINT TO THE TRAILER AS REQUIRED BY AWWA STANDARD ANSI/AWWA

C651-14.

GENERAL NOTES

SAWCUT AND REMOVE SECTION OF AC BERM14

CONSTRUCT 6" AC PAVEMENT OVER 12" CLASS 2 BASE

SAWCUT AND REMOVE AC PAVEMENT SECTION

48 INSTALL 6" AC BERM

A P

P R

R

E V

IS

IO

N S

M A

R K

D A

TE

A

P P

R

R E

V

IS

IO

N

S

DESIGNED BYDRAWN BY PROJ. ENGR.

DEPARTMENT OF PUBLIC WORKS

SUBMITTED BY

TOT. SHT'S.

SAN BERNARDINO COUNTY

SHT. NO.SCALEDWG NO.DATE

RECOMMENDED / APPROVED BY

M A

R K

D A

TE

DATESAMI H AYASS

PREPARED UNDER THE SUPERVISION OF: DATECHIEF ENGINEER

DEPUTY DIRECTOR DATEPROJECT MANAGER DATE 6/2025 42

MID-VALLEY SANITARY LANDFILL

SNA/SHA SHA

LANDFILL GAS FLARE STATION

21700 Copley Drive, Suite 200

Diamond Bar, CA 91765

TEL 909.860.7777 FAX 909.860.8017

H :\d w g\

S bs w m d\ M id -V al le y\ Fl ar e

S ta tio n\

\D W

G S

\0 9-

C -1

.d w g

/1

8/

0:

:4 m ar co s.

ar m ijo

SNA

PRO S IO

TE

R

GE

I S

C84806

CIVIL

RED

ER

N

N E

G I

LAN

E

SFE

AMAS

I H AY

SS

STATE OF CA L I FORN IA

06/18/2025 06/18/2025SAMI H AYASS

E4635 Text Box 06/26/2025

E4635 Text Box 06/26/2025

.60

FS/FL

1591.00 TF

1583.00 TF

1581.00 BF

FINISH SURFACE

ALONG WALL

(PAVEMENT)

TOP OF 30" INTERIOR SLAB

1588.00 BF

TOP OF INTERIOR SLAB

10'-8" 10'-8" 10'-8" 22'-8"

1583.00 TF

1583.83 TF

1584.67 TF

1585.50 TF

" S

S T

O R

N G

/1 6"

S

TE

E L

S

LE

E V

E

" S

S T

O L

FG

TE

/1 6"

S

TE

E L

S

LE

E V

E

1599.50 TW1600 1599.84 TW

5' WIDE CONCRETE

DRAINAGE SWALE

EXISTING CONCRETE SLAB

20'-0" 32'-0"

3" GALVANIZED FENCE POST SET IN

THICKENED EDGE FOOTING, 2 PLACES

20'-0"

S E

E S

TR

U

C

TU

R A

L D

E

TA

IL

S

FO

R

P

IP

E P

E N

E

TR

A

TI

O N

S E

E S

TR

U

C

TU

R A

L D

E

TA

IL

S

FO

R

P

IP

E P

E N

E

TR

A

TI

O N

ROUGH GATE OPENING

FOR 8' HIGH CHAIN

LINK FENCE, DOUBLE

GATE, WITH TAN

PLASTIC SLATS, AND

LOCKING MECHANISM

STRUT CHANNELS

MOUNTED TO WALL

(FOR AIR AND

CONDENSATE LINES)

SIGN PER DETAIL 1/M-502

CONSTRUCTION

JOINT @ CONCRETE

RETAINING WALL, TYPICAL

ALL…

This is the start of the file's text. The full file is on GovTribe.