MH105 - HVAC PROPOSED FLOOR PLAN.pdf

PDF 2 MB Posted

Attached to
Y1NB--Replace Air Handling Unit No. 2 and 3 Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This package includes construction drawings and specifications for replacing air handling units at a Department of Veterans Affairs medical center. The drawings show the proposed HVAC system layout and details for the basement, first floor, and roof areas, with notes on demolition scope, protection of existing utilities, fire protection shutdown and reinstallation, and construction of new shaft enclosures. Unit designations, equipment schedules and specifications are provided. The related opportunity notice seeks proposals to replace Air Handling Units 2 and 3 per the specifications, with submissions due on the originally stated date. Relevant agencies are the Department of Veterans Affairs and Veterans Health Administration.

View the file

Other files for this federal contract opportunity

Other files attached to Y1NB--Replace Air Handling Unit No. 2 and 3, newest first.
File Type Posted
MH107 - HVAC PROPOSED FLOOR PLAN.pdf PDF
MH301 - HVAC SECTIONS.pdf PDF
SF 30 Amendment 36C24822R0103 0004.pdf PDF
MH108 - HVAC PROPOSED FLOOR PLAN.pdf PDF
MH106 - HVAC PROPOSED FLOOR PLAN.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

DN

345610

D

E

F

G

A

B

C

B

C

D

E

F

G

A

123456789101112 8. 9. 10. 12. 14. 15. 16. 18. 19.7891112

"X

"X

1-TU-61-BB-4

1-TU-61-BB-1

1-TU-61-BB-9

1-TU-61-BB-3

1-TU-61-BB-10

1-TU-61-BB-17

1-TU-61-BB-19

1-TU-61-BB-7

1-TU-61-BB-14

1-TU-61-BB-12

1-TU-61-BD-2

1-TU-61-BD-1

1-TU-61-BD-3

1-TU-61-BD-5

1-TU-61-BD-13

1-TU-61-BD-4

1-TU-61-BD-6

1-TU-61-BB-5

1-TU-61-BD-7

1-TU-61-BB-6

1-TU-61-BB-22

1-TU-62-BA-10

1-TU-62-BA-11

1-TU-62-BA-2

8"X6"

"ø

1-TU-61-BB-18

1-TU-61-BB-15 1-TU-61-BB-16

C

105 CFM

C

105 CFM

D

240 CFM

D

240 CFM

D

235 CFM

D

235 CFM

E

250 CFM

E

255 CFM

E

255 CFM

E

300 CFM

E

295 CFM

E

300 CFM

E

295 CFM

E

335 CFM

E

335 CFM

E

330 CFM

D

185 CFM

D

165 CFM

C

140 CFM

C

160 CFM C

165 CFM

D

185 CFM

I

50 CFM

E

250 CFM

I

260 CFM

I

260 CFM

I

260 CFM

I

255 CFM

C

110 CFM

I

110 CFM

C

100 CFM I

100 CFM

D

170 CFM

I

170 CFM

I

190 CFM

I

190 CFM

D

180 CFM

C

130 CFM

I

360 CFM I

100 CFM

C

100 CFM

C

130 CFM

I

350 CFM

D

175 CFM

I

250 CFM

I

650 CFM

I

250 CFM

"X

"X

"X

C

135 CFM

C

140 CFM 1

"X

"X

"X

"X

"X

24"X6"

24"X6"

24"X6"24"X6"

24"X6"

24"X6"

18"X6"

18"X6"

18"X6"

"X

"X

"X

"X

8"X6"

24"X6"

20"X8"10"ø

"X

"X

"X

" 6"ø

6"ø

8"X6"

8"X6"

150 CFM

150 CFM

150 CFM

290 CFM

620 CFM

625 CFM

620 CFM 620 CFM

625 CFM

620 CFM

C

100 CFM

8"X6"

C

130 CFM

C

130 CFM

740 CFM

C

110 CFM

I

110 CFM

"X

"X

"X

8"X6"

I

100 CFM

"X

C

130 CFM

C

135 CFM

C

135 CFM

C

130 CFM

I

300 CFM

I

360 CFM

F

570 CFM

F

565 CFM

F

565 CFM

I

950 CFM

I

950 CFM

F

500 CFM

F

500 CFM

I

800 CFM

F

550 CFM

F

550 CFM

F

550 CFM

1150 CFM

1150 CFMF

550 CFM

C

130 CFM

I

130 CFM

D

190 CFM

I

190 CFM

C

100 CFM

I

100 CFM

C

100 CFM I

100 CFM

D

200 CFM

I

100 CFM

F

500 CFM

F

500 CFM

F

500 CFM

F

500 CFM

I

1050 CFM

I

1050 CFM

F

525 CFM

F

525 CFM

F

525 CFM

F

525 CFM

D

200 CFM

I

100 CFM

C

60 CFM

C

60 CFM

C

60 CFM

I

295 CFM

D

195 CFM

I

60 CFM

I

60 CFM

I

60 CFM

D

220 CFM

I

320 CFMI

100 CFM

I

100 CFM

I

100 CFM

I

100 CFM

C

145 CFM

C

145 CFM

I

290 CFM

C

100 CFM

I

100 CFM

C

100 CFM

I

100 CFM

D

195 CFM

D

190 CFM

D

195 CFM

I

580 CFM

C

125 CFM

C

130 CFM

C

125 CFM

E

380 CFM

D

190 CFM

I

190 CFM

E

320 CFM

C

135 CFM

C

130 CFM

E

400 CFM

C

135 CFM

D

250 CFM

D

190 CFM

I

190 CFM

C

120 CFM

I

100 CFM

I

150 CFM

I

250 CFM

C

120 CFM

I

750 CFM

I

350 CFM

I

350 CFM

I

190 CFM

I

190 CFM

I

255 CFM

I

205 CFM

I

205 CFM

I

85 CFM

16"X12"14"X10"14"X8"8"X8" 22"X10"

16"X10"

12"X10" 12"X6"

"X

"X

"X

8"X8"

14"X10"

14"X8" 10"X8"8"X6"

14"X10"

24"X10"

"X

"X

8"X6"

F

500 CFM

I

400 CFM

1-TU-61-BB-2

I

420 CFM

1-TU-61-BB-20

SPS

28"X16"

24"X10"

"X

"X

"X

8"X8"

"X

"X

22"X10"

"X

10"X6"

8"X6"

40"X14"

"X

40"X20"

"X

12"X6"

8"X6"

16"X10"

18"X8"

"X

"X

"X

14"X8"

8"X6"

8"X6"

14"X12" 10"X6"

"X

26"X10"

18"X10"20"X16"

F DPR

F DPR F DPR

F DPR

F DPR

F DPR

F DPR

F DPR

I

100 CFM

I

110 CFM

G

730 CFM

I

740 CFM

G

730 CFM

"X

50"X18"46"X18"

"X

"X

30"X18"

30"X26"

"X

14"X8"

34"X12"

"X

40"X20"42"X20"

"X

"X

"X

"X

"X

32"X10"

"X

"X

"X

"X

"X

24"X10"

"X

14"X10"

"X

46"X22" 44"X22"

34"X22"

"X

"X

8"X6"

"X

16"X6"

12"X8"

8"X6"

8"X6"

"X

"X

"X

8"X6"

"X

"X

"X

8"X6"

12"X8"

"X

"X

14"X6"

20"X8"

8"X6"12"X6"

"X

36"X10"

"X

8"X6"

8"X6"

8"X6"

"X ø8"

8"X6"

10"X8"

16"X12"

"X

"X

28"X12"

"X

"X

12"X6"12"X8"

8"X6"

6"X8"

6"X12"

"X

"X

8"X8"12"X8"

12"X6" 12"X8"

8"X6"

"X

"X

"X

"X

10"X6"

"X

"X

8"X6"

10"X6"

12"X6" 8"X6"

12"X10"

12"X6"

8"X6"

"X

"X

"X

10"X6"

10"X6"

14"X8" 10"X6"

"X

"X

"X

10"X8"

18"X10"

"X

"X

10"X6"

"X

10"X6" 8"X6"

"X

12"X6" 8"X6"

8"X6"12"X6"

"X

8"X6"

"X

"X

12"X6" 8"X6"

"X

8"X6"

8"X6"

"X

8"X6"

16"X8"18"X10"

"X

"X

"X

" 12"X8"

"X

"X

"X

10"X6"

20"X10"

12"X8"

20"X12"

"X

"X

12"X8"

10"X6"

"X

12"X8"

8"X6"

22"X8"

8"X6"

"X

8"X6"

8"X6"

C

100 CFM

I

100 CFM

"X

70"X20"

14"X8"

20"X10" 20"X10"

14"X8"

20"X10"

"X

"ø

10"X14"

8"X6"

8"X6"

"X

18"X6" 12"X8"

"X

10"X6"

8"X6" 14"X8"

"X

12"X8"

14"X8"

"X

12"X8"

"X

10"X8"

"ø

14"X12"

24"X12" 16"X12"

"X

"X

"14"X8"

"X

"X

"X

"X

24"X10"

8"X6"

"X

"X

"ø

"X

"X

8"X6"

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Project No. AD182-19

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

ENGINEER - OF - RECORD FL. P.E. NO.

REPLACE AIR HANDLING UNIT

(AHU) 2

573-18-602

GAINESVILLE, FLORIDA

FINAL DESIGN SUBMITTAL

APPROVED FOR CONSTRUCTION

This item has been electronically signed and sealed by the individual named at right.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

/9

/2

:1

:4

P M

JHK WRB

WILLIAM RODRIGUEZ 69663

JANUARY 21, 2022

MH105

HVAC PROPOSED FLOOR PLAN

SHEET KEYNOTES

SHEET NOTES

1. SEE CONSTRUCTION PHASING PLAN FOR SEQUENCE

OF WORK.

2. CONTRACTOR SHALL TEST AND BALANCE NEW HVAC

SYSTEM AFTER COMPLETION OF WORK WITHIN EACH

SMOKE COMPARTMENT ZONE.

3. SEE ARCHITECTURAL PLANS FOR SCOPE OF WORK IN

REGARDS TO CONSTRUCTION OF NEW DUCT RISER

SHAFTS. CONTRACTOR SHALL COMPLY WITH VA'S LIFE

SAFETY CODE THROUGHOUT CONSTRUCTION.

4. SEE ELECTRICAL PLANS FOR SCOPE OF WORK

RELATED TO RELOCATION OF EXISTING CONDUITS AND

IT/DATA CABLE TRAYS.

5. UNLESS OTHERWISE NOTED, CONTRACTOR SHALL

PROTECT EXISTING ELECTRICAL CONDUITS, IT/DATA

CABLE TRAYS, FIRE ALARM CONDUITS, PLUMBING PIPES,

MEDICAL GAS PIPES, SPRINKLER PIPES DURING

CONSTRUCTION. ANY CEILING DEVICES IN CONFLICT

WITH NEW HVAC SYSTEM SHALL BE TEMPORARILY

RELOCATED. NOTIFY THE OWNER AND ENGINEER OF

RECORD PRIOR TO SHUTDOWN OF ANY UTILITY

SERVICES.

6. CONTRACTOR SHALL TEMPORARILY SHUT DOWN FIRE

PROTECTION SYSTEM DURING CONSTRUCTION. DRAIN

DOWN THE FIRE SPRINKLER PIPES. ALL SPRINKLER

HEAD AND PIPES TO RADIANT CEILING PANEL SHALL BE

REPLACED WITH NEW FLEXIBLE METAL TUBING AND

SPRINKLER HEAD. REFER TO ARCHITECTURAL PLANS

FOR NEW CEILING HEIGHTS. CONTRACTOR SHALL

COMPLY WITH ILSM REQUIREMENT (INTERIM LIFE

SAFETY MEASURES).

7. NEW 2-HOUR RATED SHAFT ENCLOSURE AND PIPE

CHASE SHALL BE COORDINATED WITH STRUCTURAL

AND ARCHITECTURAL CONTRACTOR.

1/8" = 1'-0"

HVAC BASEMENT FLOOR PLAN - Callout 1

1. CONNECT TO EXISTING FUME HOOD EXHAUST DUCT.

SEE SHEET NOTE 4 ON MD101.

2. CONNECT TO EXISITNG GRILLE.

11 T-4

T-6

T -7

T -1

A

NEW BED TOWER

T-2

T-5

E-WING

ROOF TOP

1st FLOOR

T -1

B

T-11

T -8

T-3

MECH. BLDG.

MAIN

HOSPITAL

T-9

T-10

AMBULATORY

CARE

2 2

Revisions: Date:

1 Bulletin No. 2 09-09-2022

Sheets
MH105 - HVAC PROPOSED FLOOR PLAN
MH106 - HVAC PROPOSED FLOOR PLAN
MH107 - HVAC PROPOSED FLOOR PLAN
MH108 - HVAC PROPOSED FLOOR PLAN
MH301 - HVAC SECTIONS
2022-09-09T14:24:05-0400
William Rodriguez, P.E.
2022-09-09T14:30:11-0400
William Rodriguez, P.E.

File details come from the government source that posted it. Updated .