PM GUIDE

NUMBER

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

A-4 1

WATER MAIN

ROOM

GAST 5CLA-22-M500X 0494 3/4 HP

AIR COMPRESSOR

SERVING DRY PIPE SPRINKLER

SYSTEM

A-4 2 CHILLER ROOM KARGARD A99927 200 PSI AIR COMPRESSOR

A-4 3 CHILLER ROOM KARGARD A99927 200 PSI AIR COMPRESSOR

A-7 1

FIRST FLOOR IRS

CEILING

YORK L-1EU240 NMWS623955 R-22

20 TON

6,800 CFM

AIR CONDITIONING MACHINE,

PACKAGE UNIT

"CENTRAL ENVIRONMENTAL SYSTEM"

A-7 2

SOUTH

BASEMENT

COAST GUARD

CEILING

CARRIER 50AH060500 1889G43853 R-410a

AIR CONDITIONING MACHINE,

PACKAGE UNIT

(AIR COOLED WITH ACCESSORY

HEATER)

A-9 1

SOUTH

BASEMENT

COAST GUARD

CEILING

CARRIER AIR COOLED CONDENSOR

A-9 2

BASEMENT

CAFETERIA

CEILING

CARRIER 50AH500252 1889G43853 R-22 AIR COOLED CONDENSOR

A-11 1

BOILER ROOM

MEZZANINE

MCQUAY LSL 111CH 3XK01380-06 GOOD 10,700 CFM

AIR HANDLER UNIT

(SERVES BASEMENT IRS

WAREHOUSE)

A-11 2

BASEMENT

CAFETERIA

CEILING

MCQUAY LSL 111CH 3XK01378-06 GOOD 5,720 CFM

AIR HANDLER UNIT

(SERVES CAFETERIA)

A-11 3

BASEMENT

NURSE'S AREA

MCQUAY LSL 111CH 3XK01379-06 INACTIVE 3,850 CFM

AIR HANDLER UNIT

(SERVES HEALTH UNIT NURSE'S

STATION)

A-11 4

BOILER ROOM

MEZZANINE

MCQUAY L5 117DH 3XK00982-04 GOOD 4,530 CFM

AIR HANDLER UNIT

AHU #1

CONSTANT VOLUME SYSTEM

WITH PRE-HEAT

(SERVING MAIN DAYCARE AREA,

NORTH BASEMENT)

A-11 5

BASEMENT IRS

WAREHOUSE

CEILING

MCQUAY LSL 111CH 3XK00983-06 GOOD 3,850 CFM

AIR HANDLER UNIT

AHU 5A

(FIRST FLOOR FRONT, SOUTH)

A-11 6

ELECTRICAL

SWITCHGEAR

STORAGE AREA

CEILING

MCQUAY LSL 111CH 3XK00984-06 GOOD 3,850 CFM

AIR HANDLER UNIT

AHU 5B

(FIRST FLOOR FRONT, NORTH)

A-11 7

FIRST FLOOR

ROOF NORTH

MCQUAY RDS 806BY 3XJ01753-06 GOOD 26,100 CFM

AIR HANDLER UNIT

(FIRST FLOOR IRS LARGE OFFICE

AREA, NORTH)

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

GSA Confidential Page 1 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

A-11 8

FIRST FLOOR

ROOF SOUTH

MCQUAY RDS 806BY 3XJ01752-06 GOOD 25,500 CFM

AIR HANDLER UNIT

(FIRST FLOOR IRS LARGE OFFICE

AREA, SOUTH)

A-11 9

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

MCQUAY LYF 122DH 3XJ00987-04 GOOD 13,800 CFM

AIR HANDLER UNIT

AHU 8

(SERVES SECOND FLOOR SOUTH)

A-11 10

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

MCQUAY LYF 122DH 3XJ00988-04 GOOD 12,600 CFM

AIR HANDLER UNIT

AHU 9

(SERVES SECOND FLOOR NORTH)

A-11 11

THIRD FLOOR

ROOF, SOUTH

MCQUAY RDS 804BY 3XJ01754-06 GOOD 16,100 CFM

AIR HANDLER UNIT

(SERVES THIRD FLOOR SOUTH AREA)

A-11 12

THIRD FLOOR

ROOF, NORTH

MCQUAY RDS 804BY 3XJ01755-06 GOOD 16,300 CFM

AIR HANDLER UNIT

(SERVES THIRD FLOOR NORTH AREA)

A-11 13

MAIN TELEPHONE

ROOM

MCQUAY 800 CFM

AIR HANDLER UNIT

(SERVES MAIN TELEPHONE ROOMS)

B-1 1

EMERGENCY

GENERATOR

ROOM

ONAN

BATTERY CHARGER

TRICKLE CHARGER INSIDE ATS

B-1 2

FIRST FLOOR

GUARDS OFFICE

FIRELITE R45-24 1977-41

BATTERY CHARGER

REMOTE BATTERY CHARGER FOR

FIRE PANEL BATTERY

B-2 1 BOILER ROOM KEWANEE L3W-150-G02 99423 EXCELLENT 1992 OIL, NG 5021 MBH BOILER #1

B-2 2 BOILER ROOM KEWANEE L3W-150-G02 99422 EXCELLENT 1992 OIL, NG 5021 MBH BOILER #2

B-3, 4 1 BOILER ROOM KEWANEE AK129078 EXCELLENT 1992 OIL, NG BURNER #1

B-3, 4 2 BOILER ROOM KEWANEE AK129079 EXCELLENT 1992 OIL, NG BURNER #2

B-4 1 BOILER ROOM AJAX B4E 84474 GOOD NG

BURNER FOR AJAX HOT WATER

HEATER

B-6 1 BOILER ROOM ROSEMOUNT

BOILER, INSTRUMENTS / CONTROLS

BOILER ELECTRICAL CONTROLLER

PANEL BOX

C-2 1

BOILER ROOM

MEZZANINE

REMOTE AIR INTAKE DAMPER

GSA Confidential Page 2 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

C-2 2

BASEMENT

WINDOW

OPENING

REMOTE AIR INTAKE DAMPER

C-2 3

BOILER ROOM

MEZZANINE

REMOTE AIR INTAKE DAMPER

C-2 4 BASEMENT REMOTE AIR INTAKE DAMPER

C-2 5 BASEMENT REMOTE AIR INTAKE DAMPER

C-2 6

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

REMOTE AIR INTAKE DAMPER

C-2 7

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

REMOTE AIR INTAKE DAMPER

C-2 8

BASEMENT

COAST GUARD

CEILING

REMOTE AIR INTAKE DAMPER

C-2 9 BOILER ROOM REMOTE AIR INTAKE DAMPER

C-4 1 BOILER ROOM JOHNSON CONTROL METASYS CENTRAL MINI-COMPUTER, HVAC

C-5 1-111

THROUGHOUT

OFFICE AREA

ENVIRO-TEC (ETI) BY

JOHNSON CONTROLS

SSD-II

AUTOMATIC MIXING BOX

ELECTRIC VAV BOXES

VARIOUS SIZES / CFM's

C-5 112-114

THROUGHOUT

OFFICE AREA

ENVIRO-TEC (ETI) BY

JOHNSON CONTROLS

WF-11

AUTOMATIC MIXING BOX

ELECTRIC VAV BOXES

VARIOUS SIZES / CFM's

C-6 1-24

ON AHU SUPPLY

PIPING

JOHNSON CONTROL 130 G GA-1

CONTROLS, CENTRAL SYSTEM, HVAC

VALVE ACTUATORS

(24)

C-6 25-48

MOUNTED ON

AHU'S

JOHNSON CONTROL A70HA-1

CONTROLS, CENTRAL SYSTEM, HVAC

FREEZE STATS

(24)

C-6 49-72

MOUNTED ON

AHU'S

JOHNSON CONTROL EDA-8102-1102

CONTROLS, CENTRAL SYSTEM, HVAC

DAMPER ACTUATORS

(24)

C-6 73-96

MOUNTED ON

AHU'S

ACTROL PENN / P32AC-2 & P32AF-2 12-1240 Pa

CONTROLS, CENTRAL SYSTEM, HVAC

DIFFERENTIAL PRESSURE SWITCHES

(24)

GSA Confidential Page 3 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

C-6 97-210

THROUGHOUT

OFFICE AREA

CEILING

JOHNSON CONTROL

CONTROLS, CENTRAL SYSTEM, HVAC

VAV BOX CONTROLS / THERMOSTATS

(111)

C-6 211-358

ON RADIATOR

LOOP PIPING

JOHNSON CONTROL VA-8050-a

CONTROLS, CENTRAL SYSTEM, HVAC

VALVE ACTUATORS

(148)

C-7 1-13

AT EACH AIR

HANDLER

LITTLE GIANT 554902 GOOD

CONDENSATE PUMPS

SERVING EACH AIR HANDLER

CONDENSATE RETURN

C-9 1 NORTH ROOF EVAPCO LSTA-4-181 895306 GOOD 100 TON COOLING TOWER, MAINTENANCE

C-9 2 NORTH ROOF EVAPCO LSTA-4-181 895307 GOOD 100 TON COOLING TOWER, MAINTENANCE

C-10 1 NORTH ROOF EVAPCO LSTA-4-181 895306 GOOD 100 TON

COOLING TOWER, CLEANING

FLUSHING REQUIREMENT

C-10 2 NORTH ROOF EVAPCO LSTA-4-181 895307 GOOD 100 TON

COOLING TOWER, CLEANING

FLUSHING REQUIREMENT

C-13 1 BOILER ROOM

CRANE, ELECTRIC

CABLE TYPE, MOTOR DRIVEN

C-24 1

FIRST FLOOR

ROOF

YORK H1CE090A25A NHXM162579 FAIR R-22 10 TON CONDENSING UNIT, REFRIGERATION

C-24 2

FIRST FLOOR

ROOF

YORK H1CE090A25A NHXM141987 FAIR R-22 10 TON CONDENSING UNIT, REFRIGERATION

C-24 3

GSA OFFICE

WINDOW WELL

MCQUAY 2 TON CONDENSING UNIT, REFRIGERATION

D-1 1

SECURE PARKING

AREAS

OVERHEAD DOOR 13'-6" X 15'

DOOR, POWER OPERATED,

OVERHEAD

WITH LIFTMASTER CONTROLS

D-1 2

SECURE PARKING

AREAS

OVERHEAD DOOR 12'-6" X 15'

DOOR, POWER OPERATED,

OVERHEAD

WITH LIFTMASTER CONTROLS

D-1 3

SECURE PARKING

AREAS

OVERHEAD DOOR 10' X 10'

DOOR, POWER OPERATED,

OVERHEAD

WITH LIFTMASTER CONTROLS

D-3 1-50 ROOF AREAS

ROOF DRAINS, AND DRAINS

THROUGHOUT BUILDING

D-4 1-2

NORTHEAST

ENTRANCE

STANLEY

DOORS, AUTOMATIC HANDICAPPED

ENTRANCE, MAIN ENTRANCE

GSA Confidential Page 4 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

D-5 1-4

SOUTHEAST SIDE

ENTRANCE

DOORS, MAIN ENTRANCE

D-5 5-8

SOUTH SIDE

ENTRANCE

DOORS, MAIN ENTRANCE

ENTERING CAFETERIA

ONE WITH AUTOMATIC MAGNETIC

FIRE DOOR RELEASE

D-5 9-20

SOUTHWEST

ENTRANCE

DOORS, MAIN ENTRANCE

ENTERING NEAR COAST GUARD

D-5 21 LOADING DOCK

DOORS, MAIN ENTRANCE

ENTERING NEAR DUMPSTER

D-5 22 LOADING DOCK

DOORS, MAIN ENTRANCE

FROM STREET TO PARKING AREA

D-5 23-26 LOADING DOCK

DOORS, MAIN ENTRANCE

ENTERING IRS WAREHOUSE

D-5 27

SECURE PARKING

AREAS

DOORS, MAIN ENTRANCE

ENTERING INTO BOILER ROOM

MEZZANINE

D-5 28-29

SECURE PARKING

AREAS

DOORS, MAIN ENTRANCE

ENTERING INTO BOILER ROOM

MEZZANINE

D-5 30

SECURE PARKING

AREAS

DOORS, MAIN ENTRANCE

CORRIDOR NEAR MAIN DAYCARE

D-5 31-32 HOADLEY PLACE

DOORS, MAIN ENTRANCE

ENTERING INTO GENERATOR OIL

TANK ROOM

D-5 33

FOOTGUARD /

NORTH SIDE

DOORS, MAIN ENTRANCE

ENTERING INTO MAIN DAYCARE

D-5 34-35

FOOTGUARD /

NORTH SIDE

DOORS, MAIN ENTRANCE

ENTERING INTO FIRST FLOOR IRS

D-6 1-19

EAST AND NORTH

WINDOW WELLS

DRAINS, STORM

ON PERIMETER

D-6 20-22

FRONT PATIO

AREAS

DRAINS, AREAWAY

D-10 1-2 CAFETERIA ATLAS 23155A DOORS, OVERHEAD, MANUAL

E-19 1-10

DAYCARE SOUTH

BASEMENT

CORRIDOR

EMERGENCY LIGHTS

DRY CELL

GSA Confidential Page 5 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-24 1

INSIDE MAIN

FIRE PUMP

CONTROLLER

FIRETROL FTA435

PHASE FAILURE / REVERSAL

MONITOR

E-26 1

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC AKR-7D-50 0333A6793-016-004 1,600A

LOW VOLTAGE MOLDED CASE

CIRCUIT BREAKER

SPARE, MCB SECTION A-2

E-26 2

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TJL4V2606 600A

LOW VOLTAGE CIRCUIT BREAKER

SPARE, MOUNTED TOP SECTION OF

A1

E-26 3

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC AKR-7F-100 0337A6793-021-001 4,000A

LOW VOLTAGE MOLDED CASE

CIRCUIT BREAKER

E-26 4

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC AKR-7D-50 033A6793-018-001 1,600A

LOW VOLTAGE MOLDED CASE

CIRCUIT BREAKER

SPARE, MCB SECTION B-1

E-26 5

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC AKR-7D-50 033A6793-018-001 1,600A

LOW VOLTAGE CIRCUIT BREAKER

SPARE, MCB SECTION B-2

E-26 6

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL 1-125"

E-26 7

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL N"

E-26 8

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL P-1"

E-26 9

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL C"

E-26 10

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL 1-123"

E-26 11

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL FP"

E-26 12

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL R"

E-26 13

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL BLP-3"

E-26 14

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136050WL 50A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL MP-1"

E-26 15

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL LP-2"

GSA Confidential Page 6 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-26 16

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL 567"

E-26 17

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

PANEL "TELEPHONE ROOM"

E-26 18

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136070WL 70A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL B-83"

E-26 19

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL 3"

E-26 20

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136090WL 90A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL B-108"

E-26 21

TELEPHONE

INVERTER ROOM

GENERAL ELECTRIC TJ4V2603 70A

LOW VOLTAGE CIRCUIT BREAKER

2-POLE MAIN BREAKER

E-26 22

EMERGENCY

GENERATOR

ROOM

SQUARE D FA34050 50A

LOW VOLTAGE CIRCUIT BREAKER

(SPARE)

E-26 23

EMERGENCY

GENERATOR

ROOM

SQUARE D FA34050 50A

LOW VOLTAGE CIRCUIT BREAKER

(SPARE)

E-26 24

EMERGENCY

GENERATOR

ROOM

SQUARE D FA34050 70A

LOW VOLTAGE CIRCUIT BREAKER

(SPARE)

E-26 25

BOILER ROOM

INSIDE PANEL

"CTP"

ITE BQ2B060 60A

LOW VOLTAGE CIRCUIT BREAKER

2-POLE BREAKER

E-26 26

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D FH36050 50A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANE PPD1

E-26 27-30

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D FH36070 70A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANE PPD1

E-26 31-34

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D FH36090 90A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANE PPD1

E-27 1

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC THLC3640 400A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL Q"

E-27 2

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC THLC3640 400A

LOW VOLTAGE CIRCUIT BREAKER

"NORTH ELEVATOR"

GSA Confidential Page 7 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-27 3

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC THLC3640 400A

LOW VOLTAGE CIRCUIT BREAKER

"SOUTH ELEVATOR"

E-27 4

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC THLC3640 400A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL S-S1"

E-27 5

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC THLC3640 400A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL XX"

E-27 6

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC THLC3640 400A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL WW"

E-27 7

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-6"

E-27 8

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-7"

E-27 9

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"1LP1 / 1LP2"

E-27 10

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"1LP1 / 3LP4"

E-27 11

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"2LP1 / 3LP1"

E-27 12

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"2LP1 / 3LP1"

E-27 13

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"2LP2 / 3LP2"

E-27 14

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"2LP3 / 3LP3"

E-27 15

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-1"

E-27 16

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-2"

E-27 17

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-3"

E-27 18

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-4"

GSA Confidential Page 8 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-27 19

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-5A"

E-27 20

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"AHU-5B"

E-27 21

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"SPARE"

E-27 22

INSIDE

SWITCHBOARD

"A"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"SPARE"

E-27 23

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TJ4V2603 300A

LOW VOLTAGE CIRCUIT BREAKER

"ATS / EDP"

E-27 24

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL M"

E-27 25

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL F & 1 - 129"

E-27 26

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL G"

E-27 27

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL H"

E-27 28

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL J"

E-27 29

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL K"

E-27 30

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL L"

E-27 31

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL E"

E-27 32

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC TEL136100WL 100A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL 1-121"

E-27 33

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL 1-71 & 1-83"

E-27 34

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL D"

GSA Confidential Page 9 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-27 35

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL BB/B-86"

E-27 36

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL A"

E-27 37

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 175A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL CP"

E-27 38

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 150A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL LP"

E-27 39

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL KP"

E-27 40

INSIDE

SWITCHBOARD

"B"

GENERAL ELECTRIC SFLA36AT0250 225A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL LP-1"

E-27 41

SWITCHBOARD

ROOM

GENERAL ELECTRIC TJ4V2603 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL BLP-1, PANEL MAIN

E-27 42

FIRST FLOOR IRS

LARGE

COMPUTER ROOM

SQUARE D 175A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL CP, MAIN BREAKER

E-27 43

FIRST FLOOR

PERSONNEL

WESTINGHOUSE 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL AC

3-POLE MAIN BREAKER

E-27 44

FIRST FLOOR IRS

PERSONNEL

SQUARE D 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL P-1 MAIN BREAKER

E-27 45

SOUTH ELEVATOR

MECHANICAL

ROOM

GENERAL ELECTRIC TFK236T175 175A

LOW VOLTAGE CIRCUIT BREAKER

ELEVATOR #1 MAIN

E-27 46

SOUTH ELEVATOR

MECHANICAL

ROOM

GENERAL ELECTRIC TFK236T175 175A

LOW VOLTAGE CIRCUIT BREAKER

ELEVATOR #2 MAIN

E-27 47

THIRD FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TEF134100 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL XX, PANEL LL MAIN

E-27 48

THIRD FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TEF134100 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL XX, PANEL MM MAIN

E-27 49

THIRD FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TEF134100 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL XX, PANEL T MAIN

E-27 50

THIRD FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TEF134100 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL XX, PANEL KK MAIN

GSA Confidential Page 10 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-27 51

NORTH

ELEVATOR

MECHANICAL

ROOM

GENERAL ELECTRIC TFK236F000 125A

LOW VOLTAGE CIRCUIT BREAKER

ELEVATOR #3 MAIN

E-27 52

NORTH

ELEVATOR

MECHANICAL

ROOM

GENERAL ELECTRIC TFK436T350 350A

LOW VOLTAGE CIRCUIT BREAKER

ELEVATOR #4 MAIN

E-27 53

SECOND FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TFK236F000 125A

LOW VOLTAGE CIRCUIT BREAKER

PANEL JJ MAIN

E-27 54

SECOND FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TFK236F000 125A

LOW VOLTAGE CIRCUIT BREAKER

PANEL HH MAIN

E-27 55

SECOND FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TFK236F000 125A

LOW VOLTAGE CIRCUIT BREAKER

PANEL GG MAIN

E-27 56

SECOND FLOOR

ELECTRICAL

CLOSET

GENERAL ELECTRIC TFK236F000 125A

LOW VOLTAGE CIRCUIT BREAKER

SPARE

E-27 57 FIRST FLOOR IRS GENERAL ELECTRIC LJ-8988 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL EM-12, MAIN BREAKER

E-27 58 FIRST FLOOR IRS GENERAL ELECTRIC LJ-8988 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL EM-11, MAIN BREAKER

E-27 59

EMERGENCY

GENERATOR

ROOM

SQUARE D LJ-8211 100A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL EM-11"

E-27 60

EMERGENCY

GENERATOR

ROOM

SQUARE D LJ-8212 100A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL PP-1"

E-27 61

EMERGENCY

GENERATOR

ROOM

SQUARE D LJ-8211 100A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL EM-12"

E-27 62

EMERGENCY

GENERATOR

ROOM

SQUARE D LJ-8921 250A

LOW VOLTAGE CIRCUIT BREAKER

"PANEL EDP MAIN"

E-27 63

EMERGENCY

GENERATOR

ROOM

SQUARE D KA36150 150A

LOW VOLTAGE CIRCUIT BREAKER

SPARE

E-27 64 BOILER ROOM GENERAL ELECTRIC TQD32200 200A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL PP-1, PANEL MAIN

E-27 65 BOILER ROOM ITE ED63A100 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE MCC- CIRCUIT CWP-1

E-27 66 BOILER ROOM ITE ED63A100 100A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE MCC- CIRCUIT CWP-2

GSA Confidential Page 11 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-27 67 BOILER ROOM ITE JXD23B300 300A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL "CTP" PANEL MAIN

E-27 68-69 BOILER ROOM ITE QJ23B175 175A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE PANEL "CTP" BRANCH

CIRCUITS

E-27 70-71 FIRE PUMP ROOM WESTINGHOUSE HMCP250W5C 141D88G28 250A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE MAIN FIRE PUMP CONTROLLER

E-27 72

SWITCHBOARD

ROOM

GENERAL ELECTRIC

SPECTRA RMS /

SKLA36AT1200

1,200A

LOW VOLTAGE CIRCUIT BREAKER

INSIDE MAIN FIRE PUMP MAIN PANEL

E-27 73

FIRST FLOOR IRS

NORTH COLUMN

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 1LP2 MAIN

E-27 74

FIRST FLOOR IRS

CENTER COLUMN

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 1LP3 MAIN

E-27 75

FIRST FLOOR IRS

SOUTH BY

STAIRWELL

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 1LPA MAIN

E-27 76

FIRST FLOOR IRS

NORTH ON WALL

OF COMPUTER

ROOM

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 1LP1 MAIN

E-27 77

SECOND FLOOR

ROOM 212

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 2LP3 MAIN

E-27 78

SECOND FLOOR

CENTER

ROOM 230

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 2LP2 MAIN

E-27 79

SECOND FLOOR

IRS TRAINING

ROOM 210

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 2LP1 MAIN

E-27 80

THIRD FLOOR

SOUTH ROOM 311

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 3LP3 MAIN

E-27 81

THIRD FLOOR

CORE ROOM 340

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 3LP2 MAIN

E-27 82

THIRD FLOOR

CORE ROOM 371

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL 3LP1 MAIN

E-27 83

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D Q2L3150H 150A

LOW VOLTAGE CIRCUIT BREAKER

PANEL PLP1 MAIN

GSA Confidential Page 12 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-30 1

SWITCHBOARD

"A" ROOM

GENERAL ELECTRIC 2D 1,500A

SWITCHBOARDS, MEDIUM VOLTAGE

WITH WESTINGHOUSE IQ METEREING

MAIN A1 SECTION

E-30 2

SWITCHBOARD

"A" ROOM

GENERAL ELECTRIC

SWITCHBOARDS, MEDIUM VOLTAGE

IQ-A1-A2

E-30 3

SWITCHBOARD

"A" ROOM

GENERAL ELECTRIC 1,600A

SWITCHBOARDS, MEDIUM VOLTAGE

DEAD FRONT TYPE

E-30 4

SWITCHBOARD

"A" ROOM

GENERAL ELECTRIC 1,600A

SWITCHBOARDS, MEDIUM VOLTAGE

MCB A2 SECTION

E-30 5

SWITCHBOARD

"B" ROOM

GENERAL ELECTRIC

SWITCHBOARDS, MEDIUM VOLTAGE

SP-B1-B2 SECTION

E-30 6

SWITCHBOARD

"B" ROOM

GENERAL ELECTRIC 1,600A

SWITCHBOARDS, MEDIUM VOLTAGE

MCB B1 SECTION

E-30 7

SWITCHBOARD

"B" ROOM

GENERAL ELECTRIC 1,600A

SWITCHBOARDS, MEDIUM VOLTAGE

MCB B2 SECTION

E-30 8

SWITCHBOARD

"B" ROOM

GENERAL ELECTRIC 1,600A

SWITCHBOARDS, MEDIUM VOLTAGE

DEAD FRONT TYPE

E-34 1-4

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

ITE SN423 100A

DISCONNECTS

SERVING PENTHOUSE MECHANICAL

E-34 5

FOURTH FLOOR

SOUTH ROOF

ITE NFR351 30A

DISCONNECT

SERVING AHU-10

E-34 6

FOURTH FLOOR

SOUTH ROOF

ITE NFR351 30A

DISCONNECT

SERVING AHU-11

E-34 7-8

FIRST FLOOR

ROOF

WESTINGHOUSE RGFN422N 60A

DISCONNECTS

SERVING A-9-1 & 2

E-34 9-10

FIRST FLOOR

ROOF

ITE NFR353 100A

DISCONNECTS

SERVING SUPPLY FANS ON A-11-6 & 7

E-34 11-12

FIRST FLOOR

ROOF

ITE NFR352 60A

DISCONNECTS

SERVING RETURN FANS ON A-11-6 & 7

E-34 13

FIRST FLOOR IRS

CEILING

DISCONNECT

FOR YORK A/C PACKAGE UNIT A-7-1

GSA Confidential Page 13 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-34 14

MAIN TELEPHONE

ROOM

GENERAL ELECTRIC 100A

DISCONNECT

FOR TELEPHONE INVERTER

EQUIPMENT

E-34 15

NORTH

BASEMENT

CORRIDOR

WADSWORTH 60A DISCONNECT

E-34 16

ELECTRICAL

SWITCHGEAR

STORAGE AREA

CEILING

ITE JU321 30A

DISCONNECT

FOR A-11-5, AHU-5A

E-34 17

IRS WAREHOUSE

CEILING

ITE JU321 30A

DISCONNECT

FOR A-11-5, AHU-5A

E-34 18

SOUTH

BASEMENT

COAST GUARD

CEILING

FEDERAL PACIFIC 100A

DISCONNECT

FOR CARRIER A/C UNIT A-7-2

E-34 19

BOILER ROOM

MEZZANINE

ITE JU321 30A

DISCONNECT

FOR MCQUAY AHU #1, A-11-4

E-34 20

BOILER ROOM

MEZZANINE

ITE NF352 60A

DISCONNECT

FOR MCQUAY AHU, A-11-1

E-34 21-24 BOILER ROOM GENERAL ELECTRIC 30A

DISCONNECTS

FOR EQUIPMENT C-7-1 & 2

E-34 25-28 BOILER ROOM ITE JU321 30A

DISCONNECTS

SERVING HEAT PUMPS

E-34 29

BOILER ROOM ON

COLUMN

WESTINGHOUSE CAU321 30A DISCONNECT

E-34 30-35 BOILER ROOM GENERAL ELECTRIC 30A

DISCONNECTS

SERVING EQUIPMENT B-4-1 & 2

E-34 36-37 CHILLER ROOM ITE NF353 100A

DISCONNECTS

SERVING CHWP-1 & 2

E-34 38-39 CHILLER ROOM ITE NF352 60A

DISCONNECTS

SERVING CWP-1 & 2

E-34A 1-4

SECOND FLOOR

ELECTRICAL

CLOSET

ITE JN424 200A

DISCONNECTS

FUSED TYPE

E-34A 5

EMERGENCY

GENERATOR

ROOM

SQUARE D 600A

DISCONNECT

EMERGENCY GENERATOR ISOLATION

GSA Confidential Page 14 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-34A 6

EMERGENCY

GENERATOR

ROOM

CUTLER HAMMER 200A

DISCONNECT

EMERGENCY POWER ISOLATION

E-35 1 BOILER ROOM CONTINENTAL

MOTOR CONTROL CENTER

SERVING CHILLER MAINS

E-35 2 BOILER ROOM SIEMENS

MOTOR CONTROL CENTER

SERVING CHILLED / CONDENSATE

WATER PUMP MOTORS

E-35 3-4 CHILLER ROOM WESTINGHOUSE C707T3

MOTOR CONTROL CENTERS

SERVING CHILLERS R-5-1 & 2

CAT#: R89455AG1B

E-35 4-5 BOILER ROOM WESTINGHOUSE

MOTOR CONTROL CENTERS

CONTROLLING P-5 (P-1) & P-6 (P-2)

E-35 6 BOILER ROOM JOHNSON CONTROL

MOTOR CONTROL CENTER

COOLING TOWER FANS

E-35 7 BOILER ROOM SIEMENS

MOTOR CONTROL CENTER

INDUCED DRAFT FAN CONTROLLER

E-35 8-9 BOILER ROOM DUNHAM BUSH

MOTOR CONTROL CENTERS

CONTROLLING CONDENSATE PUMPS

(C-7-1-2)

E-35 10 FIRE PUMP ROOM FIRETROL FTA1000-AB50H GOOD 50 HP

MOTOR CONTROL CENTER

MAIN FIRE PUMP CONTROLLER

E-35 11 FIRE PUMP ROOM FIRETROL FTA500-AA01H-R GOOD 1 HP

MOTOR CONTROL CENTER

JOCKEY FIRE PUMP CONTROLLER

E-36 1

SOUTH

PENTHOUSE

ELEVATOR

MECHANICAL

ONAN OTBAA100-4U/9401E J840730592 100A

AUTOMATIC TRANSFER SWITCH

SERVING EMERGENCY POWER FOR

SOUTH ELEVATOR

E-36 2

SOUTH

PENTHOUSE

ELEVATOR

MECHANICAL

ONAN OTBAA100-4U/9401E J840730595 100A

AUTOMATIC TRANSFER SWITCH

SERVING EMERGENCY POWER FOR

SOUTH ELEVATOR

E-36 3

NORTH

PENTHOUSE

ELEVATOR

MECHANICAL

100A

AUTOMATIC TRANSFER SWITCH

SERVING EMERGENCY POWER FOR

NORTH ELEVATOR

E-36 4

NORTH

PENTHOUSE

ELEVATOR

MECHANICAL

ROOM

100A

AUTOMATIC TRANSFER SWITCH

SERVING EMERGENCY POWER FOR

NORTH ELEVATOR

E-36 5

EMERGENCY

GENERATOR

ROOM

600A

AUTOMATIC TRANSFER SWITCH

SERVING MAIN EMERGENCY POWER

GSA Confidential Page 15 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-37 1-8

BASEMENT IRS

WAREHOUSE TO

MCC E-35-1

CONTINENTAL CAT#: 3300 2,000A

BUS DUCT, LOW VOLTAGE

ALUMINUM BUS DUCT

E-41, A 1

EMERGENCY

GENERATOR

ROOM

CUMMINS NT855G 30117748 GOOD DIESEL 295-355 HP

EMERGENCY GENERATOR, ELECTRIC

DIESEL ENGINE

D# 56334

E-42A, B, C 1

EMERGENCY

GENERATOR

ROOM

ONAN 180.0DFE-15R/27189L J8440730963 GOOD 180KW EMERGENCY GENERATOR, ELECTRIC

E-43 1-12

EMERGENCY

GENERATOR

ROOM

MIDSTATE 12 CELLS LEAD ACID BATTERY (PER CELL)

E-44 1-2

FIRST FLOOR

COAST GUARD'S

OFFICE

POWERSONIC PS-12250

NICKEL CADMIUM BATTERY

FIRE ALARM SYSTEM BACK-UP

BATTERIES

E-57 1-4

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

MAGNETEK CAT#: 223-3194-055 30KVA

LOW VOLTAGE DRY TYPE

TRANSFORMER

E-57 5-8

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

MAGNETEK CAT#: 223-3194-055 30KVA

LOW VOLTAGE DRY TYPE

TRANSFORMER

E-57 9-10

SECOND FLOOR

ELECTRICAL

CLOSET

MAGNETEK CAT#: 223-3224-055 45KVA

LOW VOLTAGE DRY TYPE

TRANSFORMER

E-57 11-12

SECOND FLOOR

ELECTRICAL

CLOSET

MAGNETEK CAT#: 223-3224-055 50KVA

LOW VOLTAGE DRY TYPE

TRANSFORMER

E-PL 1 PENTHOUSE SQUARE D 12-3464421D0 EXCELLENT 1993

600A

208 / 120V

ELECTRICAL PANEL

"PPD1"

E-PL 2 PENTHOUSE SQUARE D NQ0D424L100 EXCELLENT 1993

100A

208 / 120V

ELECTRICAL PANEL

"PLP1"

E-PL 3 PENTHOUSE SQUARE D NQ0D424M100 EXCELLENT 1993

100A

208 / 120V

ELECTRICAL PANEL

"PLP2"

E-PL 4 PENTHOUSE FEDERAL PACIFIC POOR

100A

208 / 120V

ELECTRICAL PANEL

E-PL 5

THIRD FLOOR

SOUTH

GENERAL ELECTRIC AQF3422CBX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"M"

GSA Confidential Page 16 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-PL 6

THIRD FLOOR

SOUTH

GENERAL ELECTRIC AQF3301CBX EXCELLENT 2006

125A

208 / 120V

ELECTRICAL PANEL

"MM"

E-PL 7

THIRD FLOOR

SOUTH

SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"3LP3"

E-PL 8

THIRD FLOOR

SOUTH

GENERAL ELECTRIC AQF3301CBX EXCELLENT 2006

125A

208 / 120V

ELECTRICAL PANEL

"LL"

E-PL 9

SSA OHA THIRD

FLOOR

COMPUTER ROOM

GENERAL ELECTRIC AQU3422RCX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"1G-A"

E-PL 10

SSA OHA THIRD

FLOOR

COMPUTER ROOM

GENERAL ELECTRIC AQU3302RCX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"1G-B"

E-PL 11

THIRD FLOOR

SOUTH

GENERAL ELECTRIC AQF3422CBX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"L"

E-PL 12

THIRD FLOOR

SOUTH

SQUARE D POOR 1966

225A

208 / 120V

ELECTRICAL PANEL

"EM32"

E-PL 13

THIRD FLOOR

NORTH CLOSET

GENERAL ELECTRIC AEF3302MBX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"T"

E-PL 14

THIRD FLOOR

NORTH CLOSET

GENERAL ELECTRIC AEF3244KBX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"XX"

E-PL 15

THIRD FLOOR

NORTH CLOSET

GENERAL ELECTRIC EXCELLENT 2006 200A

ELECTRICAL PANEL

"IG PANEL MAIN"

E-PL 16

THIRD FLOOR

NORTH CLOSET

SQUARE D POOR 1966

225A

208 / 120V

ELECTRICAL PANEL

"EM-31"

E-PL 17

THIRD FLOOR

NORTH

FEDERAL PACIFIC NALP 30-4L POOR

100A

208 / 120V

ELECTRICAL PANEL

E-PL 18

THIRD FLOOR

NORTH

CONTINENTAL AH-788087 POOR

225A

208 / 120V

ELECTRICAL PANEL

E-PL 19 ROOM 371 SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"3LP1"

E-PL 20

SECOND FLOOR

NORTH

FEDERAL PACIFIC D-798532 POOR

200A

208 / 120

ELECTRICAL PANEL

E-PL 21 ROOM 268 GENERAL ELECTRIC AQU3241AB EXCELLENT 2006

125A

208 / 120V

ELECTRICAL PANEL

GSA Confidential Page 17 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-PL 22

SECOND FLOOR

NORTH CLOSET

CONTINENTAL AH-788229 POOR

300A

208 / 120V

ELECTRICAL PANEL

"WW"

E-PL 23 ROOM 271 SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"2LP1"

E-PL 24 ROOM 220 CONTINENTAL AH-788795K POOR

225A

208 / 120V

ELECTRICAL PANEL

"HH"

E-PL 25

SECOND FLOOR

MID

GENERAL ELECTRIC AQF3422CBX EXCELLENT 2006

225A

208 / 120V

ELECTRICAL PANEL

"H"

E-PL 26

SECOND FLOOR

SOUTH

GENERAL ELECTRIC AQF3301SBX EXCELLENT 2006

125A

208 / 120V

ELECTRICAL PANEL

"J"

E-PL 27 ROOM 210 SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"2LP3"

E-PL 28 ROOM 230 CONTINENTAL AH-788794K POOR

225A

208 / 120V

ELECTRICAL PANEL

"JJ"

E-PL 29

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798846 POOR

100A

208 / 120V

ELECTRICAL PANEL

"D"

E-PL 30

FIRST FLOOR IRS

WALK-IN

SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"1LP1"

E-PL 31

FIRST FLOOR IRS

WALK-IN

SQUARE D 44-67020-2B GOOD

DEC.

100A

208 / 120V

ELECTRICAL PANEL

"EM-12"

E-PL 32

FIRST FLOOR IRS

WALK-IN

SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"1LP2"

E-PL 33

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798847 POOR

200A

208 / 120

ELECTRICAL PANEL

"E"

E-PL 34

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC POOR

100A

208 / 120V

ELECTRICAL PANEL

"1-125"

E-PL 35

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798482 POOR

100A

208 / 120V

ELECTRICAL PANEL

"FP"

E-PL 36

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC POOR

100A

208 / 120V

ELECTRICAL PANEL

"N"

E-PL 37

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798438 POOR

100A

208 / 120V

ELECTRICAL PANEL

"1-123"

GSA Confidential Page 18 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-PL 38

FIRST FLOOR IRS

WALK-IN

SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"1LP3"

E-PL 39

FIRST FLOOR IRS

WALK-IN

SQUARE D 44-67020-2B GOOD

DEC.

100A

208 / 120V

ELECTRICAL PANEL

"EM-11"

E-PL 40

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798838 POOR

200A

208 / 120

ELECTRICAL PANEL

"1-121"

E-PL 41

FIRST FLOOR IRS

WALK-IN

SQUARE D NQ0D442M225 EXCELLENT 1993

225A

208 / 120V

ELECTRICAL PANEL

"1LPA"

E-PL 42

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798831 POOR

100A

208 / 120V

ELECTRICAL PANEL

"1-129"

E-PL 43

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798480 POOR

100A

208 / 120V

ELECTRICAL PANEL

"F"

E-PL 44

FIRST FLOOR IRS

WALK-IN

FEDERAL PACIFIC D-798827 POOR

100A

208 / 120V

ELECTRICAL PANEL

"1-83"

E-PL 45

IRS SERVER

ROOM

WESTINGHOUSE PRL1A400L42 CAT#: 5158C04G04 FAIR

SPRING

400A

208 / 120V

ELECTRICAL PANEL

"AC"

E-PL 46

IRS SERVER

ROOM

SQUARE D NQ0DQ2 FAIR

SPRING

225A

240VAC

ELECTRICAL PANEL

"CP-1"

E-PL 47

IRS SERVER

ROOM

ABANDONED 100A

ELECTRICAL PANEL

"#11"

E-PL 48 IRS IT ROOM FEDERAL PACIFIC 798836 POOR

100A

120 / 208V

ELECTRICAL PANEL

"1-71"

E-PL 49

FIRST FLOOR

SLOP SINK

FEDERAL PACIFIC POOR

100A

208 / 120V

ELECTRICAL PANEL

"C"

E-PL 50 IRS TAXPAYER SQUARE D NQ0D412M100 EXCELLENT 1993

100A

208 / 120V

ELECTRICAL PANEL

E-PL 51

SECOND FLOOR

NORTH CLOSET

SQUARE D POOR

225A

208 / 120V

ELECTRICAL PANEL

"EM-21"

E-PL 52

BASEMENT

NORTH

FEDERAL PACIFIC D-798488 POOR

200A

208 / 120

ELECTRICAL PANEL

"A"

E-PL 53

BASEMENT

JANITORIAL

STORAGE

CONTINENTAL

100A

208 / 120V

ELECTRICAL PANEL

"LP"

GSA Confidential Page 19 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-PL 54

BASEMENT

JANITORIAL

STORAGE

GENERAL ELECTRIC AQU3182RCX EXCELLENT 2005

225A

208 / 120V

ELECTRICAL PANEL

"MP/A"

E-PL 55

BASEMENT

DAYCARE

GENERAL ELECTRIC AQF3422MT EXCELLENT 1994

225A

208 / 120V

ELECTRICAL PANEL

E-PL 56

EMERGENCY

GENERATOR

ROOM

SQUARE D 44-67020-2A EXCELLENT 1993

250A

208 / 120V

ELECTRICAL PANEL

"EDP"

E-PL 57

EMERGENCY

GENERATOR

ROOM

SQUARE D POOR

225A

208 / 120V

ELECTRICAL PANEL

"EM-B1"

E-PL 58

BASEMENT IRS

WAREHOUSE

FEDERAL PACIFIC POOR

100A

208 / 120V

ELECTRICAL PANEL

"B-108"

E-PL 59

BASEMENT IRS

WAREHOUSE

GENERAL ELECTRIC AQF3301CBX EXCELLENT 2001

125A

208 / 120V

ELECTRICAL PANEL

"PM"

E-PL 60

BASEMENT IRS

WAREHOUSE

GENERAL ELECTRIC AQF3362MBX EXCELLENT 2001

225A

208 / 120V

ELECTRICAL PANEL

"BB"

E-PL 61

BASEMENT IRS

WAREHOUSE

GENERAL ELECTRIC AQU3182RCX EXCELLENT 2001

225A

208 / 120V

ELECTRICAL PANEL

"PP/2"

E-PL 62

BASEMENT IRS

WAREHOUSE

SQUARE D GOOD

225A

208 / 120V

ELECTRICAL PANEL

"EM-B2"

E-PL 63

BASEMENT

WAREHOUSE

FEDERAL PACIFIC D-798832 POOR

200A

208 / 120V

ELECTRICAL PANEL

"B-86"

E-PL 64

LOADING DOCK

AREA

GENERAL ELECTRIC AQF3424MB EXCELLENT 1993

400A

208 / 120V

ELECTRICAL PANEL

"B"

E-PL 65 KITCHEN FEDERAL PACIFIC CD-808353 POOR

225A

208 / 120V

ELECTRICAL PANEL

"KP"

E-PL 66

BASEMENT

COAST GUARD

GENERAL ELECTRIC AQF341MB EXCELLENT 1993

125A

208 / 120V

ELECTRICAL PANEL

"LP2"

E-PL 67 BOILER ROOM SIEMENS CDP-7 GOOD ~ 1990

400A

208 / 120V

ELECTRICAL PANEL

"SUB 1"

E-PL 68 BOILER ROOM ITE

300A

BREAKER

ELECTRICAL PANEL

E-PL 69 BOILER ROOM GENERAL ELECTRIC NLAB GOOD ~ 1990

200A

208 / 120V

ELECTRICAL PANEL

"PP1"

GSA Confidential Page 20 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-PL 70 BOILER ROOM GENERAL ELECTRIC 6160070C01 EXCELLENT ~ 1990 1600A

ELECTRICAL PANEL

"MCC"

E-PL 71 BOILER ROOM SQUARE D NQ0D424M100CU EXCELLENT ~ 1990

100A

208 / 120V

ELECTRICAL PANEL

"PPEF"

E-PL 72

BASEMENT

ELECTRICAL

CLOSET

INDUSTRIAL ELECTRIC

MANUFACTURING

PIB 019729-0152 FAIR 100A

ELECTRICAL PANEL

"SLB2C-14K"

E-VD 1

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130740

VARIABLE SPEED DRIVE

CONTROLLER

SERVING SOUTH PENTHOUSE

MECHANICAL UNITS

E-VD 2

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130750

VARIABLE SPEED DRIVE

CONTROLLER

SERVING SOUTH PENTHOUSE

MECHANICAL UNITS

E-VD 3

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130760

VARIABLE SPEED DRIVE

CONTROLLER

SERVING SOUTH PENTHOUSE

MECHANICAL UNITS

E-VD 4

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130770

VARIABLE SPEED DRIVE

CONTROLLER

SERVING SOUTH PENTHOUSE

MECHANICAL UNITS

E-VD 5

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130700

VARIABLE SPEED DRIVE

CONTROLLER

SERVING NORTH PENTHOUSE

MECHANICAL UNITS

E-VD 6

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130710

VARIABLE SPEED DRIVE

CONTROLLER

SERVING NORTH PENTHOUSE

MECHANICAL UNITS

E-VD 7

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130720

VARIABLE SPEED DRIVE

CONTROLLER

SERVING NORTH PENTHOUSE

MECHANICAL UNITS

E-VD 8

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

27-130730

VARIABLE SPEED DRIVE

CONTROLLER

SERVING NORTH PENTHOUSE

MECHANICAL UNITS

E-VD 9

SECOND FLOOR

UTILITY ROOM

CLOSET

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

VARIABLE SPEED DRIVE

CONTROLLER

"2-1"

E-VD 10

SECOND FLOOR

UTILITY ROOM

CLOSET

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

VARIABLE SPEED DRIVE

CONTROLLER

"2-2"

E-VD 11

SECOND FLOOR

UTILITY ROOM

CLOSET

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

VARIABLE SPEED DRIVE

CONTROLLER

"2-3"

E-VD 12

SECOND FLOOR

ELECTRICAL

CLOSET

SQUARE D

E-FLEX ADJUSTABLE SPEED

DRIVE CONTROLLER

VARIABLE SPEED DRIVE

CONTROLLER

"2-4"

GSA Confidential Page 21 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

E-VD 13-25

THIRD FLOOR

ELECTRICAL

CLOSET

VARIABLE SPEED DRIVE

CONTROLLERS

SERVING ROOF EXHAUST FANS

E-VD 26-27

NORTH ROOF AT

COOLING

TOWERS

SIEMENS

VARIABLE SPEED DRIVE

CONTROLLERS

SERVING COOLING TOWER #1

HIGH AND LOW SPEED CONTROLLERS

E-VD 28-29

NORTH ROOF AT

COOLING

TOWERS

SIEMENS

VARIABLE SPEED DRIVE

CONTROLLERS

SERVING COOLING TOWER #2

HIGH AND LOW SPEED CONTROLLERS

F-1,A 1

MAIN SPRINKLER

ROOM

2"

FIRE ALARM CHECK VALVE AND

ACCESSORIES

SERVING BASEMENT ZONE

F-1,A 2

MAIN SPRINKLER

ROOM

1-1/2"

FIRE ALARM CHECK VALVE AND

ACCESSORIES

SERVING DRY PIPE ZONE

F-1,A 3 FIRE PUMP ROOM NIBCO 2"

FIRE ALARM CHECK VALVE AND

ACCESSORIES

SERVING STANDPIPE RISERS

F-2 1

MAIN SPRINKLER

ROOM

F 3"

DRY PIPE VALVE

STAR VALVE

SERVING LOADING DOCK AREAS

F-4 1-2

MAIN SPRINKLER

ROOM

AVK 8"

FIRE CONTROL VALVES

OS & Y VALVES

MAIN BACKFLOW PREVENTER

ISOLATION VALVE

F-4 3 FIRE PUMP ROOM AVK 8"

FIRE CONTROL VALVES

OS & Y VALVE

FIRE PUMP ISOLATION

F-4 4-7 FIRE PUMP ROOM KV BFV-GI-1993 8"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVES

F-4 8

MAIN SPRINKLER

ROOM

KV 6"

FIRE CONTROL VALVES

OS & Y VALVE

BASEMENT ZONE

F-4 9

MAIN SPRINKLER

ROOM

KV 3"

FIRE CONTROL VALVES

OS & Y VALVE

DRY PIPE ZONE

F-4 10

SOUTH

BASEMENT

CEILING BY GSA

OFFICE

KV 6"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVE

F-4 11

BASEMENT

LADIES ROOM

CEILING BY

CAFETERIA

KV 6"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVE

F-4 12

BASEMENT IRS

WAREHOUSE

CEILING

KV 6"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVE

DAY CARE SYSTEM ISOLATION

GSA Confidential Page 22 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-4 13

BASEMENT IRS

WAREHOUSE

CEILING

KV 4"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVE

DAY CARE SYSTEM ISOLATION

F-4 14

NEW DAY CARE

AREA CEILING

AVK 6"

FIRE CONTROL VALVES

OS & Y VALVE

SERVING STANDPIPE RISER

F-4 15-16

THIRD FLOOR

UTILITY CLOSET

ROOM 319

KV 6"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVE

F-4 17

BASEMENT IRS

WAREHOUSE

CEILING

WATCHMAN 4"

FIRE CONTROL VALVES

GROOVED BUTTERFLY VALVE

DAY CARE SYSTEM ISOLATION

F-6, A, B 1 FIRE PUMP ROOM ITT SIZE: 8X6X13F 921-83407-01-1

1780 RPM

1250 GPM

FIRE PUMP, ELECTRIC MOTOR DRIVEN

MAIN FIRE PUMP

SPLIT CASE CENTRIFUGAL PUMP

F-6, A, B 2 FIRE PUMP ROOM GRUNDFOS 240 TYPE: CR2UH9208 3450 RPM

FIRE PUMP, ELECTRIC MOTOR DRIVEN

JOCKEY FIRE PUMP

F-9,A 1

BASMENT IRS

WAREHOUSE

ENTRANCE

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 2

BASMENT IRS

WAREHOUSE

REAR WELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 3

BASEMENT

SOUTH FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 4

BASMENT NORTH

DAY CARE

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 5

BASEMENT

NORTH

CORRIDOR

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 6

FIRST FLOOR

SOUTH REAR FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 7

FIRST FLOOR

SOUTH MAIN

CORRIDOR

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 8

FIRST FLOOR IRS

FREIGHT

ELEVATOR

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 9

FIRST FLOOR

NORTH REAR

FIRE STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 10

FIRST FLOOR

NORTH MAIN

CORRIDOR

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

GSA Confidential Page 23 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-9,A 11

SECOND FLOOR

SOUTH REAR FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 12

SECOND FLOOR

SOUTH MAIN FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 13

SECOND FLOOR

CENTER

CORRIDOR

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 14

SECOND FLOOR

NORTH MAIN FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 15

SECOND FLOOR

NORTH REAR

FIRE STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 16

THIRD FLOOR

SOUTH REAR FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 17

THIRD FLOOR

SOUTH MAIN FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 18

THIRD FLOOR

CENTER

CORRIDOR

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 19

THIRD FLOOR

NORTH MAIN FIRE

STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 20

THIRD FLOOR

NORTH REAR

FIRE STAIRWELL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 21

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 22-23

FOURTH FLOOR

NEAR DOOR TO

COOLING

TOWERS

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 24

FOURTH FLOOR

NORTH

PENTHOUSE

MECHANICAL

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 25

MAIN SPRINKLER

ROOM

2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

F-9,A 26 FIRE PUMP ROOM 2-1/2"

FIRE DEPARTMENT HOSE

CONNECTION

GSA Confidential Page 24 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-10 1

EXTERIOR

OUTSIDE MAIN

SPRINKLER ROOM

DIXON POWHATAN INACTIVE

FIRE DEPARTMENT PUMPER

CONNECTION

F-11 1-3

BASEMENT

NORTH MAIN

LOBBY

FIRE DOOR

FROM REST ROOMS TO BASEMENT

LOBBY

F-11 4

BASEMENT

NORTH MAIN

LOBBY

FIRE DOORS

FROM TELEPHONE ROOM TO

BASEMENT LOBBY

F-11 5

BASEMENT

NORTH FRONT

CORRIDOR

FIRE DOOR

FROM SWITCHGEAR ROOM TO

BASEMENT CORRIDOR

F-11 6-7

BASEMENT

NORTH FRONT

CORRIDOR

FIRE DOORS

BETWEEN BASEMENT CORRIDOR AND

LOBBY

F-11 8

BASEMENT

NORTH

CORRIDOR

FIRE DOOR

BETWEEN BOILER ROOM AND

CORRIDOR

F-11 9-10

BASEMENT

NORTH

CORRIDOR

FIRE DOORS

FROM IRS STORAGE TO CORRIDOR

BY CLEANERS OFFICE

F-11 11-12

BASEMENT

NORTH

CORRIDOR

FIRE DOORS

FROM DAYCARE TO CORRIDOR

F-11 13

BASEMENT

NORTH

CORRIDOR

FIRE DOOR

FROM DAYCARE TO CORRIDOR AT

MAIN DAYCARE

F-11 14-15

BASEMENT

NORTH

CORRIDOR

FIRE DOORS

IRS WAREHOUSE TO BASEMENT

CORRIDOR

F-11 16

BASEMENT

NORTH REAR

FIRE DOOR

EXIT FROM STAIRWELL TO DAYCARE

PLAY AREA

F-11 17

BASEMENT

SOUTH REAR

FIRE DOOR

EXIT FROM STAIRWELL

WITH AUTOMATIC MAGNETIC

RELEASE

F-11 18-19

BASEMENT

SOUTH REAR

FIRE DOORS

IRS WAREHOUSE TO SOUTH

CORRIDOR

F-11 20-21

BASEMENT

SOUTH REAR

FIRE DOORS

INTERIOR SET OF DOORS FROM

CORRIDOR TO STREET

F-11 22

FIRST FLOOR

NORTH MAIN

LOBBY

FIRE DOOR

FROM GUARD'S OFFICE INTO LOBBY

F-11 23 FIRST NORTH IRS

FIRE DOOR

EXIT DOOR FROM STAIRWELL TO

DAYCARE PLAY AREA

GSA Confidential Page 25 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-11 24-26 FIRST NORTH IRS

FIRE DOORS

MAIN ENTRANCE TO IRS WORK AREA

F-11 27

FIRST FLOOR

NORTH MAIN

LOBBY

FIRE DOOR

FROM NORTH STAIRS TO BASEMENT

F-11 28 MAIN LOBBY

FIRE DOOR

FROM ROOM 108 TO CORRIDOR

F-11 29 MAIN LOBBY

FIRE DOOR

FROM ROOM 106 TO CORRIDOR

F-11 30 MAIN LOBBY

FIRE DOOR

FROM ROOM 125 (PERSONNEL)

TO CORRIDOR

F-11 31 MAIN LOBBY

FIRE DOOR

FROM ROOM 107 TO CORRIDOR

F-11 32 MAIN LOBBY

FIRE DOOR

FROM ROOM 120 TO CORRIDOR

F-11 33 MAIN LOBBY

FIRE DOOR

FROM ROOM 102 TO CORRIDOR

F-11 34 MAIN LOBBY

FIRE DOOR

SECURITY DOOR TO FIRST FLOOR IRS

WAITING AREA

F-11 35-36

SECOND FLOOR

NORTH

FIRE DOORS

EXIT DOORS INTO NORTH STAIRWELL

F-11 37-38

SECOND FLOOR

NORTH

FIRE DOORS

GLASS DOUBLE DOORS FROM

CORRIDOR INTO LOBBY

F-11 39

SECOND FLOOR

NORTH

FIRE DOOR

EXIT DOOR INTO REAR STAIRWELL

F-11 40-41

SECOND FLOOR

NORTH

FIRE DOORS

EXIT DOOR INTO REAR SOUTH

STAIRWELL

F-11 42

SECOND FLOOR

SOUTH

FIRE DOOR

EXIT DOOR INTO REAR STAIRWELL

F-11 43-44

SECOND FLOOR

SOUTH

FIRE DOORS

GLASS DOUBLE DOORS FROM

CORRIDOR INTO LOBBY

GSA Confidential Page 26 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-11 45-46

THIRD FLOOR

NORTH

FIRE DOORS

EXIT DOORS INTO NORTH STAIRWELL

F-11 47

THIRD FLOOR

NORTH

FIRE DOOR

EXIT DOOR INTO REAR STAIRWELL

F-11 48-49

THIRD FLOOR

SOUTH

FIRE DOORS

EXIT DOORS INTO SOUTH STAIRWELL

F-11 50

THIRD FLOOR

SOUTH

FIRE DOOR

EXIT DOOR INTO REAR STAIRWELL

F-11 51

FOURTH FLOOR

SOUTH

FIRE DOOR

EXIT FROM ROOF TO SOUTH STAIRS

F-11 52-53

FOURTH FLOOR

NORTH

FIRE DOORS

EXIT DOORS TO ROOF FROM STAIRS /

ELEVATOR MECHANICAL ROOM

F-11 54

FOURTH FLOOR

SOUTH ELEVATOR

MECHANICAL

ROOM

FIRE DOOR

EXIT FROM SPACE ONTO ROOF

F-11 55

FOURTH FLOOR

NORTH

FIRE DOOR

FROM COOLING TOWER AREA

F-11 56

BASEMENT

SOUTH REAR

AREA

FIRE DOOR

DOOR TO FIRE SPRINKLER ROOM

F-13 1-2

MAIN SPRINKLER

ROOM

POTTER ELEC.

FIRE SUPERVISORY SIGNALS

POST-IN-GROOVE VALVE TAMPER

SWITCHES

SEE EQUIPMENT F-4-1 & 2

F-13 3-4 FIRE PUMP ROOM MILWAUKEE BB-SCSO

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCHES

SERVING JOCKEY PUMP ISOLATION

F-13 5-8 FIRE PUMP ROOM

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCHES

SEE EQUIPMENT F-4-4-7

F-13 9 FIRE PUMP ROOM POTTER ELEC.

FIRE SUPERVISORY SIGNALS

POST-IN-GROOVE VALVE TAMPER

SWITCH

SEE EQUIPMENT F-4-3

F-13 10

MAIN SPRINKLER

ROOM

POTTER ELEC. OSYS-B

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-8

F-13 11

MAIN SPRINKLER

ROOM

POTTER ELEC. OSYS-B

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-9

F-13 12

SOUTH

BASEMENT

CEILING BY GSA

OFFICE

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-10

GSA Confidential Page 27 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-13 13

CEILING OF

BASEMENT

LADIES ROOM

NEAR CAFETERIA

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-11

F-13 14-15

BASEMENT IRS

WAREHOUSE

CEILING

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-12-13

F-13 16

DAYCARE CEILING

AREA

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-14

F-13 17-18

THIRD FLOOR

UTILITY CLOSET

ROOM 319

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-15-16

F-13 19

BASEMENT IRS

WAREHOUSE

CEILING

FIRE SUPERVISORY SIGNALS

VALVE TAMPER SWITCH

SEE EQUIPMENT F-4-17

F-14 1-4

NORTH

ELEVATOR

LOBBIES ALL

FLOORS

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

F-14 5-8

SOUTH ELEVATOR

LOBBIES ALL

FLOORS

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

F-14 9-10

BOILER ROOM

MEZZANINE

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-1

F-14 11-12

BASEMENT

CAFETERIA

CEILING

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-2

F-14 13-14

BASEMENT

NURSE'S AREA

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-3

F-14 15-16

BOILER ROOM

MEZZANINE

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-4

F-14 17-18

BASEMENT IRS

WAREHOUSE

CEILING

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-5A

F-14 19-20

ELECTRICAL

SWITCHGEAR

STORAGE AREA

CEILING

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-5B

F-14 21-22

FIRST FLOOR

ROOF - NORTH

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-6

F-14 23-24

FIRST FLOOR

ROOF - SOUTH

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-7

GSA Confidential Page 28 12/19/2011 (REV. 10/09)

EQUIPMENT

NUMBER

LOCATION MANUFACTURER MODEL / MODEL NUMBER SERIAL NUMBER CONDITION YEAR REFRIG. FUEL SIZE DESCRIPTION AND REMARKS

GSA 1736 EQUIPMENT INVENTORY LIST

BUILDING, NUMBER,

NAME AND ADDRESS

CT0013 - WILLIAM R. COTTER FEDERAL

BLDG. 135 HIGH ST. HARTFORD, CT

F-14 25-26

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-8

F-14 27-28

FOURTH FLOOR

SOUTH

PENTHOUSE

MECHANICAL

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-9

F-14 29-30

THIRD FLOOR

ROOF SOUTH

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-10

F-14 31-32

MAIN TELEPHONE

ROOM

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

SUPPLY AND RETURN DUCTS A-11-12

F-14 33-34

SOUTH

BASEMENT

ELEVATOR LOBBY

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

AT FIRE DOOR TO CAFETERIA

F-14 35-36

SOUTH

BASEMENT

CORRIDOR

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

AT FIRE DOOR, ENTRANCE TO CAFE.

F-14 37-38

SOUTH

BASEMENT

CORRIDOR

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

AT FIRE DOOR TO REAR STAIRS

F-14 39-40

SOUTH MAIN

STAIRWELL

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

ABOVE STAIRS, FROM FIRST FLOOR

TO BASEMENT

F-14 41-42

FIRST FLOOR

SOUTH MAIN

CORRIDOR

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

F-14 43-44

NORTH MAIN

STAIRS BETWEEN

FIRST FLOOR AND

BASEMENT

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

MOUNTED ON EITHER SIDE OF FIRE

DOOR

F-14 45-47

FIRST FLOOR

NORTH MAIN

CORRIDOR

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

F-14 48-49

FIRST FLOOR

GUARDS OFFICE

AUTOMATIC FIRE DETECTION

SMOKE DETECTORS

MOUNTED ON EITHER SIDE OF FIRE

DOOR

F-14 50

FIRST FLOOR IRS

ENTRANCE

AUTOMATIC FIRE…