MB-1791 MGCW PLANS signed.pdf
PDF 3 MB Posted
- Attached to
- Myriad Gardens Chilled Water Installation
- Solicitation number
- MB-1791
- Issued by
- Oklahoma County, Hobart City, Oklahoma
About this file
The document is a comprehensive set of mechanical design and construction documents for the Myriad Gardens Chilled Water Installation project in Oklahoma City, Oklahoma. The project is being undertaken by the City of Oklahoma City's Public Works Department and involves the installation of new chilled water piping, air handling units (AHUs), and associated mechanical systems. The project is scheduled for bid on August 4, 2025, with detailed plans for replacing and modifying existing HVAC infrastructure at the Myriad Gardens facility located at 301 W. Reno Avenue. The design includes demolition of existing air handling units, installation of new air handlers, chilled water piping, control valves, and associated mechanical components across multiple building levels.
The project involves seven new air handling units, each rated at 42.3 tons with a flow rate of 101 GPM, connected to a 6-inch chilled water supply and return system. The design includes specific routing instructions for piping, careful coordination with existing building structures, and provisions for minimal disruption to the facility. The mechanical design by Olsson engineering firm includes detailed specifications for valve types, actuators, and connection methods, with careful attention to maintaining access for maintenance and adhering to existing building constraints. The project appears to be funded by the City of Oklahoma City and the Myriad Gardens Foundation, with the work to be performed by a mechanical contractor selected through the bidding process.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| MB-1791 Bidding Documents.pdf | ||
| Anti Noncollusion Affidavit.pdf | ||
| Business Relationship Affidavit.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
!F
I
RJ, I I'>' I
t==
- I I /J ai;::;,7__
- I i llv, oa f'i-- If=' r------ I - /J ''"'- "'J IIn
I 1--, ,, ,Y' I - V ...._
I '" !l.,,J; -- I 'JY wµ,o ;:/' I ··-" I..J'v) ll,-K I [<, 7 I,.-{.n N
I\ ..
1/, '" il--,,, 7:~·n r.2, ')I I/ I
- tr 'ff '--, I'.. I'-.
I'.:! h -v I L- I , f.t I J . - - /1 -
1:1{.,,_ r--- - r � I -- ·+,1 � � i'-rr I,... 1--r' ,J
/_V s ..______ ,___ .. £ -- w,itt, / ff:
PROJECT Thf' City nf lOC ... IION 1n-1 .. 1u,111;, f'il.1
'\ l':l ., x,� I/ .
�--J :.,,--I \ + 11�r--.. I -------
WA 03
1,,-' r----.. I I"--.-
,. 1Rs j I=
FFII,.
-- :-,._ L �� - C---
I I I I l
I .___I-
( I J WARD◄ I -
J l r'r - -,_ �L � I ...._ i
I ---•� � ';>'!,-:.f I - I
I � h �'7 �u - I
I _j
MB-1791
MYRIAD GARDENS CHILLED
WATER INSTALLATION
Arc
ADG B
920W .
Oklahoma Cit 405.232.
301 W RENO AVE
OKLAHOMA CITY, OK 73102
AUGUST 4, 2025
ISSUED FOR BID
Owner
MYRIAD GARDENS FOUNDATION
301 W RENO AVENUE
OKLAHOMA CITY. OK 73102
405.445.7080
MEP
OLSSON
11600 BROADWAY EXTENSION. SUITE 300
OKLAHOMA CITY. OK 73114
405.242.6600
The City of
OKLAHOMA CITY
Public Works Department
DAVID HOLT
COUNCIL MEMBERS
BRADLEY CARTER
JAMES COOPER
Katrina Avers
TODD STONE
MATT HINKLE
JOBETH HAMON
Camal Pennington
MARK K. STONECIPHER
CRAIG FREEMAN
DEBBIE MILLER, P.E.
SHEET INDEX
Mayor
Ward1 Ward2 Ward3 Ward4 Ward5 Ward6 Ward7 Ward8
City Manager
Director Public Works/City Engineer
ONE CALL UTILITY LOCATION NUMBER
840-5032
1-800-522-6543
PREPARED BY
Anlhony J. Blatt
This number is to be uwd fQr information on the location of all uOOerground ublitiu. Contact this number and other number$ $peeifi•d in the plaM prior to any excavation.
REGISTERED PROFESSIONAL ARCHITECT
NO 3765
RECOMMENDED FOR APPROVAL
� INEER A_ DA�/�u
APPROVED AS FINAL PLANS
MAYOR DATE
DATE
CTNO.
i�========================�========================================================================�============================�
28'
31.1
CCDDEE
PROVIDE 48"WX72"H STEEL SCREENS
ON STEEL POSTS EMBEDDED IN 24"
DIAMETER BY 36" DEEP CONCRETE
FOOTING PER MANUFACTUERE
INSTRUCTIONS. BASIS OF DESIGN OF
METAL PANEL SHALL BE A 'REVAMP
PANEL' - PATTERN "POPPY FIELD",
COLOR TBD. COORDINATE EXACT
LOCATION WITH ARCHITECT PRIOR
TO INSTALLATION
CHILLED WATER LINES TO PENETRATE
EXISTING ACRYLITE ACRYILIC MULTI-SKIN
PANEL. CUT PANEL PER MANUFACTURER
INSTRUCTIONS. PROVIDE OPENING 3/4"
LARGER THAN PENETRATING PIPES.
PROVIDE 1/2" WIDE ALUMINUM CHANNEL
SIMILAR TO EXISTING ALUMINUM
CHANNELS TO WRAP CIRCULAR OPENING
AND ATTACH PER PANEL MANUFACTURER
INSTRUCTIONS. SEAL ALUMINUM
CHANNEL TO PIPE WITH COMMERCIAL
GRADE NON-SAG SILCONE SEALANT.
A .1
CHILLED WATER LINES TO PENETRATE EXISTING ACRYLITE
ACRYILIC MULTI-SKIN PANEL. CUT PANEL PER
MANUFACTURER INSTRUCTIONS. PROVIDE OPENING 3/4"
LARGER THAN PENETRATING PIPES. PROVIDE 1/2" WIDE
ALUMINUM CHANNEL SIMILAR TO EXISTING ALUMINUM
CHANNELS TO WRAP CIRCULAR OPENING AND ATTACH PER
PANEL MANUFACTURER INSTRUCTIONS. SEAL ALUMINUM
CHANNEL TO PIPE WITH COMMERCIAL GRADE NON-SAG
SILCONE SEALANT.
PROVIDE 48"WX72"H STEEL SCREENS ON
STEEL POSTS EMBEDDED IN 24" DIAMETER BY
36" DEEP CONCRETE FOOTING PER
MANUFACTUERE INSTRUCTIONS. BASIS OF
DESIGN OF METAL PANEL SHALL BE A
'REVAMP PANEL' - PATTERN "POPPY FIELD",
COLOR TBD. COORDINATE EXACT
LOCATION WITH ARCHITECT PRIOR TO
INSTALLATION
4' - 0"
C
ONST RUCT ION
CON
STR
U C
T I O
N
REV
IEW
S E T
THIS
DOCUMENT IS
PRELIMINARY IN
NATURE AND IS NOT
A FINAL, SIGNED
AND SEALED
DOCUMENT
N O
T
FO
R
NOT FOR
SE T
R E
V
IE
W
Date:
ADGB Project:
Sheet No.
Revisions:
C o p y ri g h t
A D
G B
LA
TT
P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552
Web: www.adgblatt.com
101 S. Broadway, Suite 200
Edmond, OK 73034
Phone-OKC: 405.232.5700
/4
/2
:0
:3
A M
A2.1
PARTIAL FIRST
FLOOR PLAN &
NORTH ELEVATION
23-113
08/04/2025
M B
-1
M Y
R
IA
D G
A R
D E N
S C
H
IL
LE
D
W A
TE
R
I N
S
TA
LL
A
TI
O
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
S U
E D
F O
R B
ID
NORTH
1/4" = 1'-0"
PARTIAL FIRST FLOOR PLAN
1/4" = 1'-0"
NORTH ELEVATION
ACCESS
KW
V
SD
KITCHEN WASTE
VENT
SOIL OR WASTE
STORM DRAIN
DOMESTIC COLD WATER
DOMESTIC HOT WATER (120°F)
140°F
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER (140°F)
CD
RL
RS
CONDENSATE DRAIN
REFRIGERANT LIQUID
REFRIGERANT SUCTION (GAS)
RISER UP (ELBOW)
RISER DOWN (ELBOW)
TEE UP
TEE DOWN
TOP CONNECTION
SIDE CONNECTION
GATE VALVE
BALL VALVE
BOTTOM CONNECTION
CHECK VALVE
BUTTERFLY VALVE
GLOBE VALVE
PRESSURE REDUCING VALVE
CONTROL VALVE, 2 WAY
PLUG VALVE
RISE OR DROP
SS
CONTROL VALVE, 3 WAY
WCO
FCO
FPHB
CLEANOUT, FLOOR
STRAINER, "Y" TYPE
CLEANOUT, WALL
REDUCER, ECCENTRIC
BACKFLOW PREVENTION DEVICE
REDUCER, CONCENTRIC
CAP
FPWH
FD
RD
SD
FREEZE PROOF WALL HYDRANT
FLOW IN DIRECTION OF ARROW
FLOOR DRAIN
ROOF DRAIN
SHOWER DRAIN
SLOPE PIPE, RISE (R) DROP (D)
FREEZE PROOF HOSE BIBB, OR
FIRE DEPARTMENT CONNECTION
DHWR
DHW
DCW
OSD OVERFLOW STORM DRAIN
HWS HEATING WATER SUPPLY
HWR HEATING WATER RETURN
G NATURAL GAS
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CWS CONDENSER WATER SUPPLY
CWR CONDENSER WATER RETURN
ORD OVERFLOW ROOF DRAIN
REFER TO ASHRAE FUNDAMENTALS CHAPTER 37 FOR ADDITIONAL ABBREVIATIONS USED.
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AI ANALOG INPUT
ALT ALTERNATE
AO ANALOG OUTPUT
APD AIR PRESSURE DROP
ARCH ARCHITECT
ATC AUTOMATIC TEMPERATURE CONTROL
BAS BUILDING AUTOMATION SYSTEM
BI BINARY INPUT
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BO BINARY OUTPUT
BOD BOTTOM OF DUCT
BOI BOTTOM OF INSULATION
BOP BOTTOM OF PIPE
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CI CAST IRON
CL CENTER LINE
CLG CEILING
CORR CORRIDOR
CTRL CONTROL
CU COPPER
CUP CENTRAL UTILITY PLANT
DCV DEMAND CONTROL VENTILATION
DDC DIRECT DIGITAL CONTROL
DEG (°) DEGREE
DEMO DEMOLITION / DEMOLISH
DI DIGITAL INPUT
DIA OR Ø DIAMETER
DIV DIVISION
DN DOWN
DO DIGITAL OUTPUT
DP DEW POINT TEMPERATURE
DTL DETAIL
DWG DRAWING
DWV DRAIN, WASTE, AND VENT
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECON ECONOMIZER
EFF EFFICIENCY
ELEC ELECTRIC
ELEV ELEVATION
EMCS ENERGY MANAGEMENT AND CONTROL SYSTEM
EMS ENERGY MANAGEMENT SYSTEM
ESP EXTERNAL STATIC PRESSURE
EST ESTIMATE
EWT ENTERING WATER TEMPERATURE
FC FAIL CLOSED
FFA FROM FLOOR ABOVE
FFB FROM FLOOR BELOW
FIP FAIL IN PLACE
FLA FULL LOAD AMPS
FLR FLOOR
FO FAIL OPEN
FPM FEET PER MINUTE
FPS FEET PER SECOND
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HP HORSEPOWER
HR HOUR
HT HIGH (HEIGHT)
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR-CONDITIONING
HW HOT WATER
I/O INPUT / OUTPUT
ISO ISOMETRIC
KW KILOWATT
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FEET (FOOT)
LWT LEAVING WATER TEMPERATURE
MAINT MAINTENANCE
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MECH MECHANICAL
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM
MOCP MAXIMUM OVER CURRENT PROTECTION
MTG MOUNTING
N/A NOT APPLICABLE
NC NOISE CRITERIA / NORMALLY CLOSED
NEG NEGATIVE
NG NATURAL GAS
NO NUMBER / NORMALLY OPEN
NPSH NET POSITIVE SUCTION HEAD
NPSHA NET POSITIVE SUCTION HEAD AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD REQUIRED
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
PH OR Φ PHASE
POS POSITIVE
PSI POUNDS PER SQUARE INCH
PSIA PSI ABSOLUTE
PSIG PSI GAUGE
QTY QUANTITY
RA RETURN AIR
RF RELIEF AIR
REF REFERENCE
REQ'D REQUIRED
RS REFRIGERANT SUCTION (GAS)
RL REFRIGERANT LIQUID
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
SF SQUARE FEET
SP STATIC PRESSURE
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
STRU STRUCTURAL
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TFD TO FLOOR DRAIN
THRU THROUGH
TOA TEMPERED OUTDOOR AIR
TSTAT THERMOSTAT
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VAV VARIABLE AIR VOLUME
VTR VENT THROUGH ROOF
W/ WITH
W/O WITHOUT
WB WET BULB TEMPERATURE
W.C. WATER COLUMN
ABBREVIATIONS
(5) A/200
GRILLES, REGISTERS, & DIFFUSERS:
SYSTEMS ABBREVIATIONS
SYMBOL DESCRIPTION
S(#) STEAM - (#) PSI
LPC LP STEAM CONDENSATE (<=15 PSIG)
HPC HP STEAM CONDENSATE (>15 PSIG)
FOS FUEL OIL SUPPLY
FOR FUEL OIL RETURN
PC PUMPED STEAM CONDENSATE
BLIND FLANGE
FLANGE JOINT
UNION (THREADED)
PIPING AND FLOW DIAGRAM SYMBOLS
SYMBOL DESCRIPTION
THERMOMETER, INDUSTRIAL STYLE
P PRESSURE GAUGE AND VALVE
PUMP SUCTION DIFFUSER
PUMP
AIR / DIRT SEPARATOR
SAFETY RELIEF VALVE
CALIBRATED MANUAL BALANCING VALVE
WITH INTEGRAL TEST PORTS
AUTOMATIC FLOW LIMITING VALVEA
AUTOMATIC AIR VENT
MANUAL AIR VENTMAV
FDC
R
STEAM TRAP
EXTENT OF DEMOLITION
DEMOLISH BEYOND
CONNECT TO EXISTING
RENOVATION SYMBOLS
SYMBOL DESCRIPTION
DUCT / EQUIPMENT / PIPING TO BE REMOVED
NEW DUCT / EQUIPMENT / PIPING TO BE
PROVIDED
EXISTING TO REMAIN
CONTROL DEVICE SYMBOLS FOR FLOORPLANS
SYMBOL DESCRIPTION
WALL MOUNTED DEVICES:
C = CONTROLLER
CO2 = CARBON DIOXIDE TRANSMITTER
CO = CARBON MONOXIDE TRANSMITTER
EPB = EMERGENCY PUSH BUTTON SWITCH
HS = ZONE HUMIDITY SENSOR
H = ZONE HUMIDISTAT
OCC = OCCUPANCY SENSOR
REF = ZONE REFRIGERANT SENSOR
RPM = ROOM PRESSURE MONITOR
TS = ZONE TEMPERATURE SENSOR
T = ZONE THERMOSTAT
DUCT / EQUIP. / PIPE MOUNTED DEVICES:
AFMS = AIRFLOW MEASUREMENT STATION
FM = FLOW METER
SPT = DUCT STATIC PRESSURE
TRANSMITTER
HVAC SYMBOLS
SYMBOL DESCRIPTION
SUPPLY AIR
RETURN AIR
EXHAUST AIR
RECTANGULAR DUCT12"/12"
12"Ø ROUND DUCT
FLAT OVAL DUCT24"X12"Ø
BREAK LINE (CONTINUATION)
DAMPER TYPES:
(NO LABEL) = MANUAL BALANCING
DAMPER
FD = FIRE DAMPER
SD = SMOKE DAMPER
FSD = COMBINATION FIRE/SMOKE DAMPER
CD = MOTORIZED CONTROL DAMPER
BD = BACKDRAFT DAMPER
ALL DAMPERS EXCEPT MANUAL
BALANCING DAMPER SHALL HAVE
ADJACENT ACCESS PANEL FOR
MAINTENANCE.
90 DEGREE ROUND RADIUS ELBOW,
STAMPED, HORIZONTAL
90 DEGREE RECTANGULAR MITERED
ELBOW W/ TURNING VANES UP
90 DEGREE ROUND / FLAT OVAL ELBOW
DOWN
90 DEGREE ROUND / FLAT OVAL RADIUS
ELBOW, 5 GORE, HORIZONTAL
90 DEGREE RECTANGULAR RADIUS ELBOW
UP
45 DEGREE ROUND / FLAT OVAL RADIUS
ELBOW, 3 GORE, HORIZONTAL
90 DEGREE ROUND / FLAT OVAL ELBOW UP
90 DEGREE RECTANGULAR MITERED
ELBOW W/ TURNING VANES, HORIZONTAL
PROVIDE ACCESS PANEL UPSTREAM OF
TURNING VANES FOR MAINTENACE.
LO LOSS TEE (SHOE SADDLE TAP)
Ø
HIGH EFFICIENCY TAKE-OFF (HETO)
Ø
BEVELED TAP
45° LATERAL SADDLE TAP
Ø
FLEX DUCT
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE
DRAWINGS, AND AS SPECIFIED AND REQUIRED BY CODE.
CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO
CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. DRAWINGS DO NOT SHOW ALL
MINOR ITEMS THAT MUST BE INSTALLED.
THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE
APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST
CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE
CONDITIONS AND SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING
INSTALLED.
ALL REQUIRED OFFSETS FOR DUCT AND PIPING ARE NOT SHOWN ON THE
DRAWINGS. REQUIRED OFFSETS SHALL BE DETERMINED BY CONTRACTOR DURING
THE SHOP DRAWING STAGE AND SHALL NOT BE AN ADDITIONAL COST TO THE
OWNER.
PLAN AND SECTION DRAWINGS DO NOT SHOW ALL REQUIRED BRANCH PIPING OR
VALVES AND ACCESSORIES. REFER TO FLOW DIAGRAMS, DETAILS, AND PROJECT
SPECIFICATIONS FOR REQUIRED PIPING, VALVES, AND ACCESSORIES.
SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER FOR REVIEW FOR ALL
DUCTWORK, PIPING, CONTROLS, ETC. PRIOR TO ANY WORK STARTING.
ALL DEMOLISHED MATERIALS SHALL BE OFFERED TO THE OWNER FOR FIRST RIGHT
OF REFUSAL IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ANY MATERIAL
NOT SELECTED BY THE OWNER SHALL BE REMOVED FROM THE PROPERTY AND
DISPOSED OF IN ACCORDANCE WITH LOCAL LAWS AND REGULATIONS.
INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
PROVIDE VIBRATION ISOLATION AND FLEXIBLE CONNECTIONS FOR ALL MECHANICAL
EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE
AND ASSOCIATED DUCT / PIPING SYSTEMS.
COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER DISCIPLINES
SHOWN ON OTHER CONTRACT DOCUMENT DRAWINGS.
COORDINATE WITH GENERAL CONTRACTOR TO PROVIDE ACCESS PANELS FOR
INSTALLATION IN WALLS AND CEILINGS, WHERE REQUIRED, TO PERMIT SERVICE
ACCESS FOR DAMPERS, VALVES, SMOKE DETECTORS, TURNING VANES, AND OTHER
CONCEALED MECHANICAL EQUIPMENT. ACCESS PANELS SHALL BE TURNED OVER TO
THE GENERAL CONTRACTOR FOR INSTALLATION. NOTIFY ENGINEER FOR ADDITIONAL
ACCESS PANELS NOT SHOWN ON PLANS FOR APPORVAL PRIOR TO INSTALLATION.
ALL DUCT SIZES INDICATED REPRESENT INSIDE CLEAR DIMENSIONS. CONTRACTOR
SHALL ADJUST SHEET METAL SIZE TO ACCOUNT FOR LINER THICKNESS WHEN LINER
IS REQUIRED PER THE CONTRACT DOCUMENTS.
MODIFY ROUTING OF DUCTING AND PIPING AT EQUIPMENT CONNECTION POINTS
FROM THAT SHOWN TO MATCH ACTUAL LOCATION OF CONNECTION POINTS FOR
SPECIFIC EQUIPMENT PURCHASED.
PIPING, DUCTWORK, AND EQUIPMENT HANGERS AND SUPPORTS SHALL NOT
INTERFERE WITH OPERATION AND MAINTENANCE OF EQUIPMENT.
PROVIDE HINGED ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL
SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, BACKDRAFT DAMPERS,
COILS, UPSTREAM OF TURNING VANES, AND OTHER ITEMS LOCATED IN THE
DUCTWORK THAT REQUIRE SERVICE AND / OR INSPECTION. MINIMUM ACCESS
PANEL SIZES SHALL BE 6"x6" FOR DUCT DIMENSIONS 12 INCH AND LESS, 12"x12" FOR DUCT DIMENSIONS 14 INCH - 24 INCH, AND 18"x18" FOR DUCT DIMENSIONS GREATER
THAN 26 INCH.
LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT
ACCESS PANELS, CONTROLS, AND VALVING.
RUNS OF FLEXIBLE DUCTWORK SHALL BE LIMITED TO 3 FT IN LENGTH AND SHALL BE
LIMITED TO GRILLES, REGISTER, AND DIFFUSER CONNECTIONS TO ASSOCIATED
BRANCH DUCTS.
ALL 90° MITERED ELBOWS SHALL BE PROVIDED WITH TURNING VANES. TURNING
VANES SHALL BE DOUBLE WALL.
UNLESS NOTED OTHERWISE, LOCATE ALL ROOM THERMOSTATS AND OTHER WALL
MOUNTED CONTROL DEVICES 4'-0" AFF. NOTIFY THE ENGINEER OF ANY ROOMS
WHERE THE SPECIFIED LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A
QUESTION ON LOCATION.
LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN
ACCESSIBLE LOCATIONS WITH THE STRAIGHT SECTION OF DUCT / PIPE UP-AND-
DOWNSTREAM OF DEVICE AS RECOMMENDED BY MANUFACTURER. NOTIFY
ENGINEER OF ANY DEVICES WHOSE PROPOSED LOCATION DOES NOT MEET THE
MANUFACTURERS MINIMUM REQUIREMENTS.
INSTALL PIPING SO ALL VALVES, PIPING SPECIALTIES, AND OTHER APPURTENANCES
REQUIRING ACCESS ARE ACCESSIBLE.
ALL SERVICE ISOLATION VALVES SHALL BE SUITABLE FOR DEAD END SERVICE AND
INSTALLED SUCH THAT THE VALVE WILL REMAIN IN SERVICE WHEN EQUIPMENT
PIPING IS BEING EVACUATED OR REMOVED.
ALL HYDRONIC EQUIPMENT SHALL BE PROVIDED WITH TEST PORTS FOR TESTING,
ADJUSTING, AND BALANCING.
GENERAL CONTRACTOR SHALL COORDINATE ALL TRADES TO ENSURE ALL
MATERIALS INSTALLED WITHIN A RETURN AIR PLENUM ARE PLENUM RATED.
ALL GRILLES, REGISTERS, AND DIFFUSER LOCATIONS SHALL BE COORDINATED WITH
ARCHITECTS REFLECTED CEILING PLAN.
FRESH AIR INTAKES SHALL BE A MINIMUM OF 10 FT AWAY FROM CONTAMINATION
SOURCES. THIS INCLUDES PLUMBING VENTS, EXHAUST FANS, AND COOLING TOWER
PLUMES.
ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC
CODE AND DIVISION 26 SPECIFICATION.
CONTRACTOR SHALL VERIFY DEPTH, SIZE, LOCATION OF ALL EXISTING UTILITIES IN
FIELD BEFORE STARTING WORK.
SOIL AND WASTE PIPE SHALL SLOPE 2% (1/4 INCH PER FT) MINIMUM, UNLESS NOTED
OTHERWISE. CONDENSATE DRAIN AND STORM DRAIN PIPING SHALL SLOPE 1% (1/8
INCH PER FT) MINIMUM, UNLESS NOTED OTHERWISE.
ALL EQUIPMENT LOCATED IN MECHANICAL ROOMS SHALL BE PROVIDED WITH A 4
INCH THICK HOUSEKEEPING PAD. PAD SHALL EXTEND MINIMUM OF 6 INCHES BEYOND
EDGES OF EQUIPMENT.
ALL BRANCH DUCTS TO GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH MANUAL
BALANCING DAMPERS. WHERE DUCT IS EXTERNALLY INSULATED, THE DAMPER
SHALL BE PROVIDED WITH A HANDLE EXTENSION TO CLEAR THE INSULATION.
ALL RATED WALL, FLOOR, PARTITION, CEILING, AND SHAFT DUCT PENETRATIONS
SHALL BE PROVIDED WITH AN APPROPRIATE LIFE SAFETY DAMPER TO MAINTAIN THE
RATING OF THE ASSEMBLY IN ACCORDANCE WITH LOCAL CODES AND REGULATIONS.
COORDINATE WITH ARCHITECTURAL PLANS FOR LOCATIONS OF RATED WALL'S AND
WALL CONSTRUCTION.
ALL DOMESTIC HOT WATER RETURN BRANCHES SHALL EXTEND TO FIXTURE.
CONNECTIONS IN EXCESS OF 12 INCHES FROM THE FAUCET CONNECTION WILL NOT
BE ALLOWED.
ALL PIPING BELOW AMBIENT TEMPERATURE SHALL BE PROVIDED WITH INSULATION
TO PREVENT CONDENSATION. INSULATION SHALL BE 1/2 INCH THICK MINIMUM OR AS
INDICATED IN SPECIFICATIONS.
ALL PIPING PENETRATIONS OF FINISHED SURFACES SHALL BE PROVIDED WITH AN
ESCUTCHEON FOR CLEAN APPEARANCE.
ROOF MOUNTED EQUIPMENT WITHIN 10 FT OF ROOF EDGES SHALL BE PROVIDED
WITH A GUARD RAIL AT THE ROOF EDGE IN ACCORDANCE WITH IBC.
ALL UNDERFLOOR WORK SHALL BE COORDINATED WITH FOUNDATION, FOOTINGS,
GRADE BEAMS, ETC. REFER TO STRUCTURAL PLANS. UNDERFLOOR PIPING SHALL
NOT PENETRATE STRUCTURAL MEMBERS WITHOUT APPROVAL FROM THE
STRUCTURAL ENGINEER.
GENERAL PROJECT NOTES
AC AIR COMPRESSOR
ADS COMBINATION AIR / DIRT SEPARATOR
AFMS AIRFLOW MEASURING STATION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
AST ABOVEGROUND STORAGE TANK
BLR BOILER
BBH BASEBOARD HEATER
BCU BLOWER COIL UNIT
BDD BACKDRAFT DAMPER
BT BUFFER TANK
CAV CONSTANT VOLUME TERMINAL UNIT
CC COOLING COIL
CD CONTROL DAMPER
CDP CONDENSATE PUMP
CH CHILLER
CHWP CHILLED WATER PUMP
CP CIRCULATING PUMP
CR STEAM CONDENSATE RECEIVER
CRAC COMPUTER ROOM AIR-CONDITIONING UNIT
CT COOLING TOWER
CV CONTROL VALVE
CWP CONDENSER WATER PUMP
DAT DEAREATOR TANK
DCV DOUBLE CHECK VALVE
DHWP DOMESTIC HOT WATER LOOP PUMP
DN DOWNSPOUT NOZZLE (LAMB'S TONGUE)
DOAS DEDICATED OUTDOOR AIR UNIT
DT FUEL OIL DAY TANK
DWH DOMESTIC WATER HEATER
EAV EXHAUST AIR VENTURI VALVE
EF EXHAUST FAN
ERV ENERGY RECOVERY VENTILATOR
EWC ELECTRIC WATER COOLER
FCU FAN COIL UNIT
FCO FLOOR CLEAN OUT
FD FIRE DAMPER OR FLOOR DRAIN
FF FILTER FEEDER
FM FLOW METER
FPVAV FAN POWERED VAV TERMINAL UNIT
FS FLOOR SINK
FSD COMBINATION FIRE/SMOKE DAMPER
FT FLASH TANK
FWD FOOD WASTE DISPOSAL (GARBAGE DISPOSAL)
FWP BOILER FEED WATER PUMP
GEN GENERATOR
GI GREASE INTERCEPTOR
GMU GLYCOL MAKE-UP UNIT
GSHP GROUND SOURCE HEAT PUMP
GV GRAVITY VENTILATOR
HB HOSE BIBB
HC HEATING COIL
HT HEAT TRACE
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
IDU SPLIT SYSTEM INDOOR UNIT
KS KITCHEN SINK (MULTI COMPARTMENT SINK)
LAV LAVATORY
LV LOUVER
MAV MAKE-UP AIR VENTURI VALVE
MAU MAKE-UP AIR UNIT
MS MOP SINK
PCHP PRIMARY CHILLED WATER PUMP
PRV PRESSURE REDUCING (REGULATING) VALVE
ODU SPLIT SYSTEM OUTDOOR UNIT
ORD OVERFLOW ROOF DRAIN
RAF RETURN AIR FAN
RD ROOF DRAIN
REG GAS REGULATOR
RF RELIEF FAN
RH ROOF HYDRANT
RO RO WATER TREATMENT SYSTEM
RPZ RPZ BACKFLOW PREVENTER
RRU REFRIGERANT RECOVERY UNIT
RTU PACKAGED ROOFTOP UNIT
S SINK
SCHP SECONDARY CHILLED WATER PUMP
SCP STEAM CONDENSATE PUMP
SD SMOKE DAMPER OR SHOWER DRAIN
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SI SOLIDS INTERCEPTOR
SP SUMP PUMP
SRV SAFETY RELIEF VALVE
ST STEAM TRAP
SUT SURGE TANK
TCHP TERTIARY CHILLED WATER PUMP
TD TRENCH DRAIN
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
U URINAL
UH UNIT HEATER
US UTILITY SINK
UST UNDERGROUND STORAGE TANK
VAV VARIABLE VOLUME TERMINAL UNIT
VFD VARIABLE FREQUENCY DRIVE
WC WATER CLOSET
WCO WALL CLEAN OUT
WF WATER FILTRATION SYSTEM
WH WALL HYDRANT
WM WATER METER
WS WATER SOFTENER SYSTEM
WSB WATER SUPPLY BOX
WSHP WATER SOURCE HEAT PUMP
XFRP TRANSFER PUMP
XT EXPANSION TANK
EQUIPMENT DESIGNATIONS
NPW NON-POTABLE WATER
CF CHEMICAL FEED
BD BLOWDOWN
CBD CONTINOUS BLOWDOWN
CA COMPRESSED AIR
N
O
NITROGEN
MEDICAL AIR
OXYGEN
A
WAGD WASTE ANESTHESIA GAS DISPOSAL
MEDICAL GAS ABBREVIATIONS
SYMBOL DESCRIPTION
VAC MEDICAL VACUUM
M-301
AIR FLOW (CFM)
DEVICE TAG. REF TO SCHEDULE.
MECHANICAL CALLOUTS
SECTION / DETAIL:
DTL NO.
SHEET NO. WHERE DETAIL
OR SECTION IS DRAWN
KEYNOTES:
1 KEYNOTE NO.
QTY.
SW SOFTENED WATER
RO RO WATER
DI DI WATER
FW BOILER FEED WATER
DUCT SIZE:
ALL DIMENSIONS ARE IN INCHES
UNLESS NOTED OTHERWISE
90 DEGREE RECTANGULAR MITERED
ELBOW W/ TURNING VANES DOWN
90 DEGREE RECTANGULAR RADIUS ELBOW
DOWN
FIRE SPRINKLERF
EXPANSION TANK
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-001
MECHANICAL
LEGEND,
ABBREVIATIONS,
AND NOTES
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
08/04/2025
SUMMARY OF MECHANICAL WORK:
1.
A.
2.
A.
3.
A.
4.
A.
5.
A.
B.
6.
A.
7.
A.
8.
A.
B.
A.
B.
C.
D.
E.
A.
B.
A.
SUMMARY OF WORK
THE WORK COVERED BY THESE DOCUMENTS CONSISTS OF FURNISHING ALL LABOR, MATERIAL AND EQUIPMENT IN PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF THE MECHANICAL SYSTEMS DESIGNATED ON THE DRAWINGS AND/OR DESCRIBED HEREIN. ANY INCIDENTAL WORK NOT SHOWN OR SPECIFIED, BUT WHICH CAN BE PRESUMED AS BELONGING TO, OR DEEMED NECESSARY FOR, THE SATISFACTORY COMPLETION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED. THE WORK SHALL BE COORDINATED WITH THE REQUIREMENTS OF THE SPECIFICATIONS (WHERE APPLICABLE) AND WITH ALL OF THE DRAWINGS FOR THE ENTIRE PROJECT. THE WORK SHALL BE ACCOMPLISHED ON SUCH A SCHEDULE AND IN SUCH A MANNER AS NOT TO DELAY OR
INTERFERE WITH OTHER CONSTRUCTION.
VISITING THE SITE
THE CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH THE CONDITIONS TO BE MET, AS NO EXTRAS WILL BE ALLOWED TO COVER WORK WHICH THE CONTRACTOR DID NOT INCLUDE IN HIS BID DUE TO HIS FAILURE TO INFORM HIMSELF OF THE
CONDITION AT THE SITE.
DRAWINGS
THE DRAWINGS AND SPECIFICATIONS COVER THE EXTENT AND GENERAL ARRANGEMENT OF THE VARIOUS SYSTEMS, SUBJECT TO THE INDIVIDUAL CHARACTERISTICS OF THE MECHANICAL EQUIPMENT WITH REGARD TO SIZE, INTERNAL ARRANGEMENT, CONNECTIONS, ETC. THE EXACT LOCATION AND INSTALLATION OF THE METERS FOR UTILITIES SHALL CONFORM TO THE APPLICABLE REQUIREMENTS OF THE LOCAL UTILITIES. THE MECHANICAL DRAWINGS ARE DIAGRAMMATICAL ONLY AND ARE NOT INTENDED TO INCLUDE ALL OF THE DETAILS OR DIMENSIONS SHOWN ON THE OTHER DIVISIONS OF THIS PROJECT, AND CONVERSELY THE SAME.
HOWEVER, EACH DRAWING IS INTENDED TO SUPPLEMENT THE OTHERS AND INTERPRETATION OF THE DRAWINGS SHALL BE SUCH THAT THE ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL DETAILS ARE INCLUDED ON ALL OF THE VARIOUS DRAWINGS. WHERE NO FIGURES OR DIMENSIONS ARE NOTED, THE DRAWINGS SHALL BE ACCURATELY FOLLOWED. EXCEPTIONS TO, OR CONFLICTS BETWEEN, THE DRAWINGS, SPECIFICATIONS, AND OR INTERPRETATION OF THE IMPLIED INTENT OF THE DESIGN SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION 10 DAYS PRIOR TO BID OPENING. IF THESE ARE NOT DISCLOSED PRIOR TO THIS TIME, THE CONTRACTOR SHALL RESOLVE THESE CONFLICTS TO THE ARCHITECT'S SATISFACTION AT NO INCREASE IN CONTRACT COST.
COORDINATION
THE WORK OF THE MECHANICAL AND PLUMBING SPECIFICATIONS SHALL BE COORDINATED WITH THE REQUIREMENTS OF THE OTHER TRADES AND WITH ALL OF THE WORK FOR THE ENTIRE PROJECT. ALL WORK SHALL BE ACCOMPLISHED ON SUCH A SCHEDULE AND IN
SUCH A MANNER AS NOT TO DELAY OR INTERFERE WITH OTHER CONSTRUCTION WORK.
ORDINANCES, PERMITS, METERS AND UTILITIES
THE CONTRACTOR SHALL PROCURE ALL NECESSARY PERMITS OR LICENSES TO CARRY OUT HIS WORK; THE LAWFUL FEES THEREFORE SHALL BE PAID BY THE CONTRACTOR. HE SHALL ALSO OBTAIN THE NECESSARY CERTIFICATES OF APPROVAL, THE COST OF WHICH SHALL BE INCLUDED BY THE CONTRACTOR. THE CONTRACTOR SHALL PAY ALL FEES REQUIRED FOR THE CONNECTION OF
WATER, GAS AND SEWER LINES (AND METER FEES) TO UTILITY COMPANY MAINS.
THE CONTRACTOR SHALL COMPLY WITH ALL LOCAL, STATE AND NATIONAL CODES, INCLUDING APPLICABLE ASME AND NFPA
REQUIREMENTS, AND LOCAL UTILITY COMPANY REQUIREMENTS.
WARRANTY
THE CONTRACTOR SHALL WARRANTY ALL EQUIPMENT AND THE INSTALLATION THEREOF FROM DEFECT FOR A PERIOD OF ONE YEAR AFTER FINAL ACCEPTANCE OF THE BUILDING (UNLESS NOTED OTHERWISE FOR A SPECIFIC ITEM OF EQUIPMENT OR INDICATED
OTHERWISE IN THE GENERAL OR SUPPLEMENTAL CONDITIONS).
LOCATION OF PIPES, DUCTS, ETC.
THE LOCATION OF ALL PIPES, DUCTS, OUTLETS, EQUIPMENT, ETC., SHOWN ON THE DRAWINGS INDICATE THE GENERAL INTENT AND ARRANGEMENT ONLY, AND UNDERSTOOD TO BE SUBJECT TO SUCH REVISION AS MAY BE FOUND NECESSARY OR DESIRABLE AT THE TIME THE WORK IS INSTALLED. ALL SUCH OFFSETS OR REROUTING OF PIPES AND DUCTWORK SHALL BE MADE WHERE REQUIRED TO CLEAR OBSTRUCTIONS, PROVIDED THAT SUCH WORK IS PROPERLY COORDINATED WITH ALL OTHER WORK AND THAT THERE BE NO IMPAIRMENT OF SYSTEM OPERATION AS A RESULT, AND AT NO INCREASE IN CONTRACT COST. GENERALLY, ALL OUTLETS SHALL BE PROPERLY LOCATED FOR THE PURPOSE FOR WHICH THEY ARE INTENDED, OR CENTERED IN ROOMS, PANELS OR FINISHED WORK, AND SHALL NOT INTERFERE WITH OUTLETS OR EQUIPMENT OF OTHER TRADES AND SHALL MEET THE DIMENSIONS OR SCALE DRAWING OF THE ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND DETAILS FOR EXACT LOCATIONS. IN CASES OF CONFLICT, THE SHEETMETAL WORK SHALL TAKE PRECEDENCE, BUT SHALL ALSO BE RESPONSIBLE FOR PRIOR
COORDINATION WITH ALL OTHER TRADES.
QUALITY ASSURANCE
THE INSTALLATION OF ALL WORK IS TO BE DONE IN STRICT ACCORDANCE WITH ALL APPLICABLE LOCAL ORDINANCES AND STATE STATUTES. IN CASE OF CONFLICT, THE CODE HAVING IMMEDIATE JURISDICTION IS TO GOVERN. THE METHODS TO BE USED IN THE INSTALLATION OF THE EQUIPMENT AND MATERIALS MUST MEET OR EXCEED THESE REQUIREMENTS OF THE GOVERNING CODES AND STANDARDS. WHERE THE APPLICATION OF A STANDARD OR CODE APPEARS TO BE IN CONFLICT WITH THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS, CODE COMPLIANCE WILL GOVERN.
EXCEPT AS NOTED OTHERWISE, THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS WILL GOVERN:
--- LOCAL PLUMBING AND MECHANICAL CODE
AABA ASSOCIATED AIR BALANCE COUNCIL
AMCA AIR MOVING AND CONDITIONING ASSOCIATION
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE (SUCCESSOR TO ASASI AND ASA)
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING, AND AIR CONDITIONING ENGINEERS.
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY OF TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
AWWA AMERICAN WATER WORKS ASSOCIATION
CISPI CAST IRON SOIL PIPE INSTITUTE
CTI COOLING TOWER INSTITUTE
FM FACTORY MUTUAL ENGINEERING COMPANY
FS FEDERAL SPECIFICATIONS
MSS MANUFACTURER'S STANDARDIZATION SOCIETY OF THE VALVE AND FITTING INDUSTRY
NEC NATIONAL ELECTRICAL CODE BY NFPA
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
OSHA OCCUPATIONAL SAFETY AND HEALTH ASSOCIATION
PDI PLUMBING AND DRAINAGE INSTITUTE
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION
9. UTILITY CONNECTIONS
ASCERTAIN FROM THE UTILITY DEPARTMENT OF UTILITY COMPANY THE EXACT AMOUNT OF WORK REQUIRED IN CONNECTION OF UTILITIES. WORK REQUIRED WHICH IS NOT PROVIDED BY THE UTILITY DEPARTMENT OR COMPANY SHALL BE PROVIDED BY THE
CONTRACTOR, UNLESS INDICATED OTHERWISE.
VERIFY THE LOCATION AND DEPTH OF ALL UTILITIES AND CALL TO THE ATTENTION OF THE OWNER ANY DISCREPANCIES WHICH
INVOLVE ADDITIONAL WORK BEFORE SIGNING THE CONTRACT.
AFTER THE CONTRACT IS SIGNED, ANY ADDITIONAL WORK REQUIRED FOR THE COMPLETE AND WORKING JOB SHALL BE PROVIDED
AT NO ADDITIONAL COST TO THE OWNER, UNLESS INDICATED OTHERWISE.
LOCATIONS, DEPTHS, SIZES, CAPACITIES, ETC., OF THE UTILITY LINES SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO DOING ANY OTHER WORK ON PIPING SYSTEMS WHICH ARE TO CONNECT TO SUCH UTILITY LINES. ANY WORK RENDERED UNUSABLE BY FAILURE
TO COMPLY WITH THIS PROVISION SHALL BE REPLACED AT NO COST TO THE OWNER.
UTILITIES AS MENTIONED IN THIS DIVISION OF THE SPECIFICATIONS SHALL INCLUDE WATER, SEWER, GAS AND OTHER PIPING
SYSTEMS NECESSARY TO THE OPERATION OF NEW OR EXISTING SYSTEMS AND EQUIPMENT.
10. LAYING OUT OF THE WORK
LAY OUT WORK ON THE PREMISES AND MAKE PROPER PROVISIONS TO COORDINATE WITH OTHER TRADES. THE EXACT LOCATION OF EACH ITEM SHALL BE DETERMINED BY REFERENCE TO THE GENERAL PLANS, BY MEASUREMENTS AT THE BUILDING AND IN COOPERATION WITH OTHER CONTRACTORS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ACCURATELY LOCATING ALL
OPENINGS FOR DUCTS, PIPES, ETC., AND ACCESS DOORS REQUIRED.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING OWNER ACCEPTABLE ACCESS TO ALL AREAS ON EQUIPMENT. DEVICE CONTROLS MANUAL ADJUSTMENT DEVICES, GAUGES AND OTHER MISCELLANEOUS ITEMS SHALL BE EASILY VISIBLE AND ADJUSTABLE
FROM THE DEVICE CONTROL SIDE OF THE UNIT.
11. MECHANICAL COORDINATION
THE INSTALLER OF MECHANICAL WORK IS TO CAREFULLY EXAMINE ALL MECHANICAL, ELECTRICAL, STRUCTURAL, ARCHITECTURAL AND OTHER CONTRACT DRAWINGS BEFORE BEGINNING THE WORK. REPORT ANY APPARENT CONFLICTS, ERRORS, OMISSIONS, OR AMBIGUITIES IN THE CONTRACT DOCUMENTS TO THE OWNER FOR INTERPRETATION OR EXPLANATION BEFORE PERFORMING THE WORK. THE WORK IS TO BE DONE BY CRAFTSMEN SKILLED IN EACH TRADE UNDER THE SUPERVISION OF A FOREMAN WHO IS
EXPERIENCED IN ALL PHASES OF THE WORK REQUIRED BY THIS DIVISION.
B.
C.
D.
E.
F.
IN GENERAL, DRAWINGS FOR THE WORK ARE DIAGRAMMATIC EXCEPT WHERE ITEMS ARE SPECIFICALLY LOCATED BY DIMENSION. THE DRAWINGS SHOW THE LOCATION OF PLUMBING FIXTURES, REFRIGERATION, AIR CONDITIONING, HEATING AND OTHER EQUIPMENT. WHERE CONDITIONS NECESSITATE A REARRANGEMENT OF ANY MECHANICAL EQUIPMENT, THE CONTRACTOR IS TO PREPARE AND SUBMIT FOR APPROVAL SCALED (NO SMALLER THAN 1/4" = 1'-0") DRAWINGS SHOWING HE PROPOSED REARRANGEMENT.
THE MECHANICAL WORK IS TO BE CAREFULLY COORDINATED WITH THE WORK SHOWN ON THE ELECTRICAL, STRUCTURAL, ARCHITECTURAL, AND OTHER DRAWINGS IN ORDER TO AVOID CONFLICTS IN SPACE REQUIREMENTS FOR THE EQUIPMENT INSTALLED. PLAN THE WORK SO THAT ALL EQUIPMENT, VALVES, PIPING AND SPECIALTIES ARE INSTALLED IN SUCH A MANNER AS TO BE ACCESSIBLE FOR MAINTENANCE. IN ORDER TO ACCOMPLISH THIS, MINOR DEVIATIONS FROM THE DRAWINGS DUE TO ARCHITECTURAL DETAILS AND JOB CONDITIONS WILL BE PERMITTED WHEN REQUESTED. PROVIDE ALL OFFSETS AS REQUIRED IN THE PIPING AND DUCTWORK IN ORDER TO PRODUCE A NEAT AND
FUNCTIONAL ARRANGEMENT.
AFTER APPROVAL OF THE MAJOR ITEMS OF EQUIPMENT, IF SUCH EQUIPMENT DIFFERS DIMENSIONALLY FROM THAT SHOWN ON THE DRAWINGS, BEFORE PROCEEDING WITH ANY PART OF THE WORK, THE CONTRACTOR IS TO PREPARE AND SUBMIT FOR APPROVAL FIELD AND SHOP DRAWINGS SHOWING PROPERLY DIMENSIONED LAYOUTS OF THE EQUIPMENT WITHIN THE ALLOTTED SPACES. THESE DRAWINGS ARE TO SHOW THE EXACT LOCATION AND DETAILS OF ALL PIPING. EQUIPMENT THAT WILL NOT FIT INTO THE ALLOTTED SPACE WITH CLEARANCE
COMMENSURABLE TO THESE SHOWN ON THE DRAWINGS WILL NOT BE CONSIDERED.
ALL WORK IS TO BE SCHEDULED, PLANNED AND EXECUTED SO AS NOT TO INTERFERE WITH OR DELAY THE WORK OF ANY OTHER
CONTRACTOR.
IF, AFTER ANY OF THE WORK IS INSTALLED, AND THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, OR STRUCTURAL DESIGN CANNOT BE FOLLOWED IN ACCORDANCE WITH THE DRAWINGS, THE CONTRACTOR WILL, AT HIS OWN EXPENSE, MAKE SUCH CHANGES AS DIRECTED BY THE OWNER IN THE WORK HEREUNDER AS WILL PERMIT THE PROPER INSTALLATION OF ALL OTHER WORK AS SHOWN ON THE DRAWINGS.
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-002
MECHANICAL
LEGEND,
ABBREVIATION,
AND NOTES
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
28' 29 30 31 32
Y
Z
AA
BB
CC
DD
EE
AHU-02 AHU-01
AHU-04 AHU-03
AHU-06 AHU-05
UH-1
AHU-08 AHU-07
AHU-10 AHU-09
UH-2
01 M-102
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-101
DEMOLITION PLAN
- BASEMENT
NORTH
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
1/4" = 1'-0"01 BASEMENT MECHANICAL ROOM DEMOLITION- NORTH
A.
B.
C.
GENERAL SHEET NOTES:
DEMOLISH AND REMOVE EXISTING AIR HANDLERS
INDICATED. REMOVE ALL ACCESSORIES AND
APPURTENANCES. DEMOLISH EXISTING
DUCTWORK AS REQUIRED TO INSTALL AND
CONNECT TO NEW AIR HANDLING UNITS.
NO EQUIPMENT OR MATERIALS SHALL BE
ABANDONED IN PLACE.
FOR AIR HANDLERS TO BE DEMOLISHED, REMOVE
EXISTING HEATING WATER PIPING BACK TO
EXISTING BRANCH ISOLATION VALVES. PREP FOR
NEW PIPING INSTALLATION.
Q
R
S
T
U
V
W
X
AHU-10 AHU-09
AHU-12 AHU-11
AHU-14
AHU-13
AHU-15AHU-16
AHU-18 AHU-17
AHU-19AHU-20
EXISTING RETURN
AIR TUNNEL FROM
CONSERVATORY
EXISTING RETURN
AIR TUNNEL FROM
CONSERVATORY
UH-3
EXISTING ELECTRICAL MCCEXISTING ELECTRICAL MCC
3"ø F
01 M-101
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-102
DEMOLITION PLAN
- BASEMENT SOUTH
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
1/4" = 1'-0"01 BASEMENT MECHANICAL ROOM DEMOLITION - SOUTH
A.
B.
C.
GENERAL SHEET NOTES:
DEMOLISH AND REMOVE EXISTING AIR HANDLERS
INDICATED. REMOVE ALL ACCESSORIES AND
APPURTENANCES. DEMOLISH EXISTING
DUCTWORK AS REQUIRED TO INSTALL AND
CONNECT TO NEW AIR HANDLING UNITS.
NO EQUIPMENT OR MATERIALS SHALL BE
ABANDONED IN PLACE.
FOR AIR HANDLERS TO BE DEMOLISHED, REMOVE
EXISTING HEATING WATER PIPING BACK TO
EXISTING BRANCH ISOLATION VALVES. PREP FOR
NEW PIPING INSTALLATION.
Y
Z
AA
BB
CC
DD
EE
AHU-02 AHU-01
AHU-05
UH-1
AHU-08
AHU-10 AHU-09
UH-2
AHU-07
AHU-06
AHU-04
AHU-03
6" ø
C H
W S
6" ø
C H
W R
8"ø CHWS
8"ø CHWR
01 M-302
7 8
LOCATE NEW CHWS/R PIPING
NEAR THIS STRUT LOCATION
FOR STRUCTURAL SUPPORT.
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-301
HVAC PIPING
PLAN - BASEMENT
NORTH
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
1/4" = 1'-0"01 BASEMENT MECHANICAL ROOM - NORTH
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
GENERAL NOTES:
NEW AIR HANDLING UNITS HAVE BEEN PRE-
PURCHASED BY OWNER THROUGH MC.
COORDINATE ALL PIPE AND DUCT INSTALLATION
WITH FINAL EQUIPMENT CONNECTIONS.
INSTALL EQUIPMENT AND MATERIALS TO ALLOW
FOR MAINTENANCE ACCESS AND SERVICE
CLEARANCE WHERE REQUIRED BY
MANUFACTURER.
WHEN ROUTING NEW CHILLED WATER PIPING,
MAINTAIN MINIMUM 6'-0" FOR HEADROOM.
EXISTING HEATING WATER PIPING NOT SHOWN.
PROVIDE NEW HEATING WATER PIPING AS
REQUIRED AND CONNECT TO NEW AIR
HANDLERS. REFER TO DETAIL 1 / M-501.
EXISTING HVAC DUCTWORK NOT SHOWN.
CONNECT NEW AIR HANDLING UNITS TO EXISTING
DUCTWORK. PROVIDE FLEXIBLE CONNECTORS AT
DUCT CONNECTIONS.
PROVIDE MOUNTING SUPPORTS FOR AIR
HANDLING UNITS SIMILAR TO EXISTING UNITS
USING SQUARE TUBE STRUCTURAL STEEL.
FOR EXISTING AIR HANDLERS TO REMAIN,
EXISTING HEATING WATER IS ALREADY
CONNECTED. ONLY CHILLED WATER
CONNECTIONS ARE IN SCOPE OF WORK.
FOR EXISTING TO REMAIN AHU'S, PREVIOUS
DESIGN INFO INDICATES 2.5" COIL CONNECTION
SIZE. CONTRACTOR TO VERIFY.
CONTRACTOR SHALL NOT CUT OR CORE
THROUGH ANY STRUCTURAL MEMBERS OF THE
EXISTING BUILDING, INCLUDING BUT NOT LIMITED
TO WALLS, COLUMNS, BEAMS, SLAB, OR STRUTS.
NOTIFY ENGINEER OF MAJOR DEVIATIONS OF
PIPE ROUTING TO EVALUATE STRUCTURAL
IMPACTS.
NO. KEYED NOTES:
1. ROUTE NEW NEW 8"Ø CHWS AND CHWR PIPING
THROUGH WEST WALL AND UP THROUGH RETURN
GRATE IN FLOOR.
2. INSTALL NEW UTILITY METER IN THIS APPROXIMATE
LOCATION. METER IS FURNISHED BY OTHERS,
INSTALLED IN PIPING BY MC.
3. EXISTING SPRINKLER PIPING.
4. ROUTE CHWS/R PIPING UP HIGH TIGHT TO CONDUIT
MOUNTED ON UNDERSIDE OF DECK ABOVE.
5. ROUTE NEW CHILLED WATER PIPING LOW APPROX. 12"
AFF UNDER EXISTING RA DUCTWORK SERVING AHU-02.
6. ROUTE NEW CHILLED WATER PIPING UP HIGH TIGHT
TO CEILING.
7. MODIFY EXISTING RETURN AIR DUCTWORK
CONNECTING TO AHU-04 TO ALLOW ROOM FOR NEW
CHILLED WATER PIPING AND UTILITY METER.
8. PROVIDE MANUAL AIR VENTS IN THIS APPROXIMATE
LOCATION.
Q
R
S
T
U
V
W
X AHU-10 AHU-09
AHU-12
AHU-14
AHU-17
AHU-20
EXISTING RETURN
AIR TUNNEL FROM
CONSERVATORY
EXISTING RETURN
AIR TUNNEL FROM
CONSERVATORY
UH-3
EXISTING ELECTRICAL MCCEXISTING ELECTRICAL MCC
3"ø F
AHU-19
AHU-18
AHU-15AHU-16
AHU-13
AHU-11
01 M-301
6"ø CHWS 6"ø CHWS 6"ø CHWR6"ø CHWR
4"ø CHWS 4"ø CHWR
4"ø CHWR 4"ø CHWS
4"ø CHWR 4"ø CHWS
4"ø CHWR 4"ø CHWS
1/4" = 1'-0"01 BASEMENT MECHANICAL ROOM - SOUTH
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-302
HVAC PIPING
PLAN - BASEMENT
SOUTH
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
NO. KEYED NOTES:
1. ROUTE CHWS/R PIPING AROUND EXISTING DDC
CABINET.
2. ROUTE CHWS/R PIPING DOWN UNDERNEATH
STUCTURAL BEAM TO LOWER CEILING AREA.
3 PROVIDE 1" END OF LINE BYPASS WITH AUTOFLOW
LIMITING VALVE.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
GENERAL NOTES:
NEW AIR HANDLING UNITS HAVE BEEN PRE-
PURCHASED BY OWNER THROUGH MC.
COORDINATE ALL PIPE AND DUCT INSTALLATION
WITH FINAL EQUIPMENT CONNECTIONS.
INSTALL EQUIPMENT AND MATERIALS TO ALLOW
FOR MAINTENANCE ACCESS AND SERVICE
CLEARANCE WHERE REQUIRED BY
MANUFACTURER.
WHEN ROUTING NEW CHILLED WATER PIPING,
MAINTAIN MINIMUM 6'-0" FOR HEADROOM.
EXISTING HEATING WATER PIPING NOT SHOWN.
PROVIDE NEW HEATING WATER PIPING AS
REQUIRED AND CONNECT TO NEW AIR
HANDLERS. REFER TO DETAIL 1 / M-501.
EXISTING HVAC DUCTWORK NOT SHOWN.
CONNECT NEW AIR HANDLING UNITS TO
EXISTING DUCTWORK. PROVIDE FLEXIBLE
CONNECTORS AT DUCT CONNECTIONS.
PROVIDE MOUNTING SUPPORTS FOR AIR
HANDLING UNITS SIMILAR TO EXISTING UNITS
USING SQUARE TUBE STRUCTURAL STEEL.
FOR EXISTING AIR HANDLERS TO REMAIN,
EXISTING HEATING WATER IS ALREADY
CONNECTED. ONLY CHILLED WATER
CONNECTIONS ARE IN SCOPE OF WORK.
FOR EXISTING TO REMAIN AHU'S, PREVIOUS
DESIGN INFO INDICATES 2.5" COIL CONNECTION
SIZE. CONTRACTOR TO VERIFY.
CONTRACTOR SHALL NOT CUT OR CORE
THROUGH ANY STRUCTURAL MEMBERS OF THE
EXISTING BUILDING, INCLUDING BUT NOT LIMITED
TO WALLS, COLUMNS, BEAMS, SLAB, OR STRUTS.
NOTIFY ENGINEER OF MAJOR DEVIATIONS OF
PIPE ROUTING TO EVALUATE STRUCTURAL
IMPACTS.
MAV
COIL DESIGNATION A B
TYP. AHU CHW COIL
TYP. AHU HW COIL
3" 2-1/2"
2-1/2" 2"
RETURN
SUPPLY
"D"
"A"
MAV
C
2-1/2"
2"
D
3"
2-1/2"
"B"
"C"
"B"
"C"
P/T PORT
UNION OR FLANGE CONNECTION
3/4" DRAIN VALVE
BUTTERFLY VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
TWO-WAY PRESSURE INDEPENDENT
CONTROL VALVE. REFER TO
SCHEDULES FOR VALVE.
3/4" CAPPED TEE FOR FLUSHING
THERMOMETER
NOTE:
NEW HEATING WATER PIPING & CONNECTIONS ONLY APPLICABLE TO
NEW AIR HANDLING UNITS.
P
1/4"
1/4"
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-501
MECHANICAL
DETAILS AND
SCHEDULES
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
NTS1 COIL CONNECTION DETAIL (AHU STACKED COIL - TWO WAY)
CONTROL VALVE SCHEDULE
MARK SERVES FLUID CONFIGURATION SIZE TYPE
DESIGN FLOW
(GPM)
MAX PRESSURE
DIFF (PSID) CHARACTERISTIC
ACTUATOR INFORMATION BASIS OF DESIGN
NOTESACTUATOR TYPE FAILSAFE VOLTAGE MANUFACTURER VALVE ACTUATOR
AHU CHW VALVE CHILLED WATER WATER - 55°F TWO-WAY 2-1/2" PICV 101 116 EQUAL PERCENTAGE MODULATING - PROPORTIONAL FC 24V BRAY SSM-250-A-L-102 GASEX24-450 1,3 AHU HW VALVE HEATING WATER WATER - 170°F TWO-WAY 2" PICV 55 58 EQUAL PERCENTAGE MODULATING - PROPORTIONAL FIP 24V BRAY SS-2-N-S-56.1 PAM24-27 2,3
1.
2.
3.
NOTES:
VALVE IS TYPICAL FOR ALL AHU CHILLED WATER COILS.
VALVE IS TYPICAL FOR ALL AHU HEATING WATER COILS. ONLY PROVIDE VALVES FOR AIR HANDLERS BEING REPLACED.
FAILSAFE NOMENCLATURE: FO = FAIL OPEN, FC = FAIL CLOSED, FIP = FAIL IN PLACE.
P
8" CHWS
8" CHWR
AHU-01
42.3 TONS
101 GPM
AHU-02
42.3 TONS
101 GPM
AHU-03
42.3 TONS
101 GPM
AHU-04
42.3 TONS
101 GPM
AHU-05
42.3 TONS
101 GPM
AHU-06
42.3 TONS
101 GPM
AHU-07
42.3 TONS
101 GPM
AHU-08
42.3 TONS
101 GPM
AHU-09
42.3 TONS
101 GPM
AHU-10
42.3 TONS
101 GPM
AHU-11
42.3 TONS
101 GPM
AHU-12
42.3 TONS
101 GPM
AHU-13
42.3 TONS
101 GPM
AHU-14
42.3 TONS
101 GPM
AHU-15
42.3 TONS
101 GPM
AHU-16
42.3 TONS
101 GPM
AHU-17
42.3 TONS
101 GPM
AHU-18
42.3 TONS
101 GPM
AHU-19
42.3 TONS
101 GPM
AHU-20
42.3 TONS
101 GPM
BYPASS VALVE
8"
M
MIN. 5 FT LENGTH
MIN. 2 1/2 FT LENGTH
8 FT
MIN
6"
3"
3"
3"
3"
8"
8"
8"
8"
8"
6" CHWR
6" CHWS
6" CHWR
6" CHWS
4"
4"
4"
4"
GROUND LEVEL
BASEMENT LEVEL
PENETRATE EXISTING
GREENHOUSE PLASTIC
WINDOW MATERIAL.
COORDINATE WITH
ARCHITECT FOR
PENETRATION
REQUIREMENTS.
ROUTE NEW PIPING
THROUGH EXISTING
RETURN AIR FLOOR GRATE.
EXISTING
GREENHOUSE
CRYSTAL BRIDGE
WEST RETURN
AIR TUNNEL
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
3"
MAV
MAV
MAV
MAV
8" C
H W
S
8" C
H W
R
A
COPYRIGHT 2025 OLSSON ALL RIGHTS RESERVED.
THIS DRAWING IS PROPERTY OF OLSSON. ANY MODIFICATION OR USE OF THIS DRAWING
WITHOUT EXPRESS WRITTEN AUTHORIZATION OF OLSSON IS PROHIBITED.
DC# 24155 / OLSSON# 025-00948SHEET SIZE: 30X42
OK COA #: 2483 EXPIRES 2027-06-30
Date:
ADGB Project:
Sheet No.
Revisions:
C op yr ig ht A
D G
B
LA
TT
, P
C
920 W. Main St.
Oklahoma City, OK 73106
Phone-Edmond: 405.340.8552 Web: www.adgblatt.com
101 S. Broadway, Suite 200 Edmond, OK 73034 Phone-OKC: 405.232.5700
8/ 4/
:2
7:
P M
M-601
CHILLED WATER
PIPING DIAGRAM
23-113
AUGUST 04, 2025
M B-
M
YR
IA
D
G A
RD
EN
S C
HI
LL
ED
W
A
TE
R
IN
ST
A
LL
A
TIO
N
301 W. Reno Ave, Oklahoma City, OK 73102
IS
SU
ED
F
O R
BI
D
NTS1 CHILLED WATER PIPING SCHEMATIC
A.
B.
C.
GENERAL NOTES:
REFER TO TYPICAL AHU COIL CONNECTION DETAIL
1/M-501 FOR ALL COMPONENTS BETWEEN AHU
COIL'S AND ISOLATION VALVES.
PREVIOUS DESIGN INFORMATION INDICATE
EXISTING AHU CHILLED WATER COIL
CONNECTIONS TO BE 2.5" FLANGE. CONTRACTOR
TO FIELD VERIFY.
CONTRACTOR SHALL NOT CUT OR CORE
THROUGH ANY STRUCTURAL MEMBERS OF THE
EXISTING BUILDING, INCLUDING BUT NOT LIMITED
TO WALLS, COLUMNS, BEAMS, SLAB, OR STRUTS.
NO. KEYED NOTES:
1. CHILLED WATER CUSTOMER CONNECTION. CONNECT
NEW CHILLED WATER PIPING TO EXISTING PIPING BY
UTILITY SUPPLIER.
2. PENETRATE RETURN AIR TUNNEL IN NORTHWEST
CORNER THROUGH WEST GYP WALL.
3. PROVIDE TWO THERMAL WELLS IN PIPING. WELLS
SHALL HAVE A 3/4 INCH THREADOLET AND BE 6" - 12"
APART.
4. PROVIDE 1" AUTOFLOW LIMITING VALVE. VALVE SHALL
BE SET AT 10 GPM.
| M-001-MECHANICAL LEGEND, ABBREVIATIONS, AND NOTES |
| M-002-MECHANICAL LEGEND, ABBREVIATION, AND NOTES |
| M-101-DEMOLITION PLAN - BASEMENT NORTH |
| M-102-DEMOLITION PLAN - BASEMENT SOUTH |
| M-301-HVAC PIPING PLAN - BASEMENT NORTH |
| M-302-HVAC PIPING PLAN - BASEMENT SOUTH |
| M-501-MECHANICAL DETAILS AND SCHEDULES |
| M-601-CHILLED WATER PIPING DIAGRAM |
File details come from the government source that posted it. Updated .