TECHNICAL EXHIBIT-1, Performance Requirements Summary (PRS).
| PERFORMANCE OBJECTIVE |
| STANDARD |
| PERFORMANCE THRESHOLD |
| METHOD OF SURVEILLANCE |
| REMEDY |
| Para 5.2. Sampling and analysis of treated water |
| Sampling and analysis IAW Monitoring Frequency |
| All required work has to be |
met
| 100% Inspection |
| The Contractor shall provide corrective plan, take corrective action and re-perform the analysis |
| Para 5.3.2. Sampling and analysis of waste water |
| Sampling and analysis IAW Monitoring Frequency |
| All required work has to be |
met
| 100% Inspection |
| The Contractor shall provide corrective plan, take corrective action and re-perform the analysis |
| Para 5.4.1. Preventive Maintenance |
| The Contractor shall submit a detailed PM schedule to the COR for approval 30 calendar days prior to the start date of each Contract year. |
| All reports submitted to COR prior to 30 calendar days of the new contract year. |
| 100% Inspection |
| Contractor shall perform Re-work within 1 day notification of the COR |
Para 5.4.5.
Heat Pumps
Perform all Preventive Maintenance (PM) checks within periodic cycle
No more than 1% of PMs shall be performed out of cycle
Random Inspection
Contractor shall perform Re-work within 2 hours notification of the COR
Para 5.12 Control System
Restore system failures within 24hrs.
All system failures shall meet the standard
| 100% Inspection |
| Contractor shall perform Re-work within 4 hours notification of the COR |
Para 5.5.1. Emergency Calls
Contractor shall respond to emergency calls within 2 hours working until the emergency condition is fixed.
All emergency calls shall meet the standard
| 100% Inspection |
| Contractor shall perform Re-work within 2 hours notification of the COR |
Para 5.5.1. Routine Calls Respond and begin work on routine service calls within 24 hours after receipt of the call, and complete all repairs within 7 calendar days.
No more than 1% of total calls shall exceed response time.
Random/ Customer Complaint
Contractor shall perform Re-work within 2 hours notification of the COR
Para 5.5.1.1. Service Call Record and Report
Maintain all service call records and Report to COR prior to 8:30 a.m. each workday.
0 defects
Periodic
Contractor shall perform Re-work within 120 minutes notification of the COR