This is a Request for Proposal (RFP) for firefighting and personal protective equipment maintenance services at three Marine Corps installations: MCB Camp Pendleton, MCLB Barstow, and MCAS Miramar. The RFP outlines requirements for a firm-fixed-price contract with a 12-month base period and four 12-month option periods, with potential 6-month extension, beginning January 15, 2025. Proposals are due by 2:00 PM PST on January 22, 2025.
The scope includes on-site inspection, testing, cleaning, certification, calibration, repair and maintenance of firefighting equipment and personal protective equipment across 15 fire stations. Key requirements include annual flow testing of SCBA equipment, hydrostatic testing of cylinders, air compressor maintenance, structural ensemble inspections, ladder testing, hose testing, and maintenance of various rescue tools and medical equipment. The solicitation is set aside for small businesses under NAICS code 811310 with a size standard of $12.5M. Technical capability and past performance are significantly more important than price in the evaluation criteria. Contractors must possess various certifications including Scott Air Pack, Bauer Factory Training, Hurst, Zoll, NFPA, and Stryker certifications to perform the required services.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEE ADDENDUM
(No Collect Calls)
M0068125R0002 17-Dec-2024
b. TELEPHONE NUMBER
760-725-8450
8. OFFER DUE DATE/LOCAL TIME
02:00 PM 22 Jan 2025
5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
STANDARD FORM 1449 (REV. 2/2012)
Prescribed by GSA – FAR (48 CFR) 53.212
(TYPE OR PRINT)
(SIGNATURE OF CONTRACTING OFFICER)
ADDENDA X ARE
26. TOTAL AWARD AMOUNT (For Gov t. Use Only )
23.
CODE 10. THIS ACQUISITION IS
SUCH ADDRESS IN OFFER
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT
BELOW IS CHECKED
TELEPHONE NO.
M006819. ISSUED BY
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a. UNLESS BLOCK
7. FOR SOLICITATION
INFORMATION CALL:
a. NAME
JUNE LEEPER
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NUMBER
(TYPE OR PRINT)
30b. NAME AND TITLE OF SIGNER 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a.UNITED STATES OF AMERICA
1 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1. 52.212-4. FAR 52.212-3. 52.212-5 ARE ATTACHED.X
25. ACCOUNTING AND APPROPRIATION DATA
1. REQUISITION NUMBER
20.
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED.
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, AND 30
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
M331204629517
ARE NOT ATTACHED
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
SET FORTH HEREIN, IS ACCEPTED AS TO ITEMS:
. YOUR OFFER ON SOLICITATION
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN
% FOR:SET ASIDE:UNRESTRICTED OR X
SMALL BUSINESSX
17a.CONTRACTOR/ CODE FACILITY
OFFEROR CODE
REGIONAL CONTRACTING OFFICE-MCIWEST
BLDG 22180 REGIONAL CONTRACTS
CAMP PENDLETON CA 92055-5027
18a. PAYMENT WILL BE MADE BY CODE
RATED ORDER UNDER
DPAS (15 CFR 700)
13a. THIS CONTRACT IS A
13b. RATING
CODE15. DELIVER TO CODE 16. ADMINISTERED BY
SEE SCHEDULE
12. DISCOUNT TERMS11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
14. METHOD OF SOLICITATION
RFQ IFB RFPX
FAX:
TEL: SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
8(A)
HUBZONE SMALL
BUSINESS
SIZE STANDARD:
$12,500,000
NAICS:
811310
X
OFFER DATED
29. AWARD OF CONTRACT: REF.
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND
EMAIL:
TEL:
31c. DATE SIGNED
SEE SCHEDULE
SCHEDULE OF SUPPLIES/ SERVICESITEM NO. QUANTITY UNIT UNIT PRICE AMOUNT
24.22.21.19.
WOMEN-OWNED SMALL BUSINESS (WOSB)
ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
(CONTINUED)
PAGE 2 OF86
ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED: ______________________________________________________
32a. QUANTITY IN COLUMN 21 HAS BEEN
RECEIVED INSPECTED
32b. SIGNATURE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32c. DATE 32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE 32f . TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE
37. CHECK NUMBER
FINALPARTIALCOMPLETE
36. PAYMENT35. AMOUNT VERIFIED
CORRECT FOR
34. VOUCHER NUMBER
FINAL
33. SHIP NUMBER
PARTIAL
38. S/R ACCOUNT NUMBER 39. S/R VOUCHER NUMBER 40. PAID BY
41a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR PAYMENT
41b. SIGNATURE AND TITLE OF CERTIFYING OFFICER 41c. DATE
42a. RECEIVED BY (Print)
42b. RECEIVED AT (Location)
42c. DATE REC'D (YY/MM/DD) 42d. TOTAL CONTAINERS
STANDARD FORM 1449 (REV. 2/2012) BACK
Prescribed by GSA – FAR (48 CFR) 53.212
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
SEE SCHEDULE
20.
SCHEDULE OF SUPPLIES/ SERVICES
21.
QUANTITY UNIT
22. 23.
UNIT PRICE
24.
AMOUNT
19.
ITEM NO.
M0068125R0002
Section A - Solicitation/Contract Form
SECTION A
A1. TYPE OF CONTRACT:
This will be a Single award Firm Fixed Price (FFP) Contract.
A2. SERVICE REQUIREMENTS:
Under this Contract, the Contractor will provide all management, tools, supplies, equipment, and labor necessary to inspect, test, clean, certify, calibrate, repair, and maintain Firefighting Equipment and Personal Protective Equipment as set forth in the remainder of this document in support of the Fire and Emergency Services (F&ES) departments. Services will be required at the following regional bases:
Marine Corps Base (MCB) Camp Pendleton (CPEN), California (CA);
Marine Corps Air Station (MCAS) Miramar, CA;
Marine Corps Logistics Base (MCLB) Barstow, CA;
All parts, supplies, labor, and transportation required to properly service the Government’s equipment, to include inspections, minor/major repairs, and preventative maintenance on the contractor’s equipment used for this requirement shall be supplied by the contractor and be at no additional cost to the Government.
Specific tasks and services to be performed under this contract are stated in the Performance Work Statement (PWS) under Section C of this document.
A3. COMPETITION ENVIRONMENT:
This procurement has been set-aside as total small business.
A4. NORTH AMERICAN INDUSTRY CLASSIFICATION SYSTEM (NAICS) CODE:
The appropriate NAICS code for this procurement is 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance with a small business size of $12.5M.
Section B - Supplies or Services and Prices
ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
0001 4 Lot Equipment Compliance Support - CPEN
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and Personal Protective Equipment (PPE) for Fire and Emergency Services (F&ES), Marine Corps Base Camp Pendleton (CPEN), CA in accordance with (IAW) the Performance Work Statement (PWS). Pricing for specific items to be provided via ELIN worksheet.
FOB: Destination
PURCHASE REQUEST NUMBER: M331204629517
PSC CD: J042
NET AMT
0002 4 Lot Equipment Compliance Support - Barstow
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Logistics Base Barstow, CA IAW the PWS. Pricing for specific items to be provided via ELIN worksheet.
FOB: Destination
0003 4 Lot Equipment Compliance Support - Miramar
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Air Station Miramar, CA IAW with the PWS. Pricing for specific items to be provided via ELIN worksheet.
Over and Above Services for 3 Locations
FFP
Provides for additional services outside the base contract scope across three locations (Marine Corps Base CPEN, Marine Corps Logistics Base Barstow, and Marine Corps Air Station Miramar) IAW the PWS.
Labor Rate: TBD / per hour
1001 4 Lot OPTION Equipment Compliance Support - CPEN
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and Personal Protective Equipment (PPE) for Fire and Emergency Services (F&ES), Marine Corps Base Camp Pendleton (CPEN), CA in accordance with (IAW) the Performance Work Statement (PWS). Pricing for specific items to be provided via ELIN worksheet.
1002 4 Lot OPTION Equipment Compliance Support - Barstow
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Logistics Base Barstow, CA IAW the PWS. Pricing for specific items to be provided via ELIN worksheet.
1003 4 Lot OPTION Equipment Compliance Support - Miramar
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Air Station Miramar, CA IAW with the PWS. Pricing for specific items to be provided via ELIN worksheet.
OPTION Over and Above Services for 3 Locations
FFP
Provides for additional services outside the base contract scope across three locations (Marine Corps Base CPEN, Marine Corps Logistics Base Barstow, and Marine Corps Air Station Miramar) IAW the PWS.
2001 4 Lot OPTION Equipment Compliance Support - CPEN
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and Personal Protective Equipment (PPE) for Fire and Emergency Services (F&ES), Marine Corps Base Camp Pendleton (CPEN), CA in accordance with (IAW) the Performance Work Statement (PWS). Pricing for specific items to be provided via ELIN worksheet.
2002 4 Lot OPTION Equipment Compliance Support - Barstow
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Logistics Base Barstow, CA IAW the PWS. Pricing for specific items to be provided via ELIN worksheet.
2003 4 Lot OPTION Equipment Compliance Support - Miramar
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Air Station Miramar, CA IAW with the PWS. Pricing for specific items to be provided via ELIN worksheet.
OPTION Over and Above Services for 3 Locations
FFP
Provides for additional services outside the base contract scope across three locations (Marine Corps Base CPEN, Marine Corps Logistics Base Barstow, and
3001 4 Lot OPTION Equipment Compliance Support - CPEN
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and Personal Protective Equipment (PPE) for Fire and Emergency Services (F&ES), Marine Corps Base Camp Pendleton (CPEN), CA in accordance with (IAW) the Performance Work Statement (PWS). Pricing for specific items to be provided via ELIN worksheet.
3002 4 Lot OPTION Equipment Compliance Support - Barstow
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Logistics Base Barstow, CA IAW the PWS. Pricing for specific items to be provided via ELIN worksheet.
3003 4 Lot OPTION Equipment Compliance Support - Miramar
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Air Station Miramar, CA IAW with the PWS. Pricing for specific items to be provided via ELIN worksheet.
OPTION Over and Above Services for 3 Locations
FFP
Provides for additional services outside the base contract scope across three locations (Marine Corps Base CPEN, Marine Corps Logistics Base Barstow, and
4001 4 Lot OPTION Equipment Compliance Support - CPEN
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and Personal Protective Equipment (PPE) for Fire and Emergency Services (F&ES), Marine Corps Base Camp Pendleton (CPEN), CA in accordance with (IAW) the Performance Work Statement (PWS). Pricing for specific items to be provided via ELIN worksheet.
4002 4 Lot OPTION Equipment Compliance Support - Barstow
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Logistics Base Barstow, CA IAW the PWS. Pricing for specific items to be provided via ELIN worksheet.
4003 4 Lot OPTION Equipment Compliance Support - Miramar
FFP
Inspect, test, clean, certify, calibrate, repair, and maintain Firefighting and PPE for F&ES, Marine Corps Air Station Miramar, CA IAW with the PWS. Pricing for specific items to be provided via ELIN worksheet.
OPTION Over and Above Services for 3 Locations
FFP
Provides for additional services outside the base contract scope across three locations (Marine Corps Base CPEN, Marine Corps Logistics Base Barstow, and
Section C - Descriptions and Specifications
PERFORMANCE WORK STATEMENT
PERFORMANCE WORK STATEMENT
C1. BACKGROUND. Marine Corps Installations West (MCIWEST) Fire and Emergency Services (F&ES) is a regional fire department covering Marine Corps Base Camp Pendleton (MCB CPEN), Marine Corps Logistics Base Barstow (MCLB) and Marine Corps Air Station Miramar (MCASM). F&ES encompasses 15 Fire Stations geographically separated providing for effective response capability to each base population to include automatic and mutual aid partnerships surrounding the installations. Changes may occur to the emergency vehicle fleet in accordance with paragraph 12. The USMC Fire and Emergency Services through policy letter requires Marine Corps fire departments to utilize the Center of Public Safety Excellence, Center of Fire Accreditation International model to assess and align the fire department. Category VI: Physical Resources outlines the following: a system is in place to ensure the regular inspection, testing, fueling, preventive maintenance, and emergency repair for all fire apparatus and equipment.
C2. DESCRIPTION OF SERVICES. The Contractor shall provide all management, tools, supplies, equipment and labor necessary to inspect, test, clean, certify, calibrate, repair and maintain Fire Fighting Equipment and Personal Protective Equipment. The Contractor shall provide services in support of MCB CPEN, MCLB, and MCASM F&ES, (hereafter referred to as the GOVERNMENT) and shall include all items listed below. All work shall be performed on-site, either at the fire stations or collected and returned to the fire stations, by certified/qualified technicians. The Contractor shall ensure all employees doing business with the GOVERNMENT have properly cleared the vetting process prior to arrival at MCB CPEN, MCLB, and MCASM, this includes access to the Naval Weapons Station Fallbrook (MCB CPEN Fire Station 9), and ACU-5 (Assault Craft Unit) (MCB CEPN Fire Station 2). This process can take up to 30 days. Work to be performed can be within any or all of the 15 Fire Stations aboard the installations. Coordination of locations of work performed shall be determined by the fire department program management representatives. When required by the GOVERNMENT, DoD, local or federal regulations, Contractor personnel shall wear any required safety equipment, including but not limited to safety glasses, safety shoes, hard hats, and earplugs. The GOVERNMENT will not be responsible for furnishing or paying for the cost of this safety equipment.
C3. PLACE OF PERFORMANCE. All work shall be completed on-site and shall take place as approved through scheduling that is mutually agreeable to both the GOVERNMENT and the contractor. Scheduling and work shall commence after a signed contract has been approved and provided to both parties. The Contractor shall provide a proposed schedule of dates that services will be performed throughout the year. Services shall be completed through the months of January through December. Should extensive repairs be required and/or additions to the Performance Work Statement become necessary, the Contractor may request an extension of time to complete the work, which may be granted or denied in the sole discretion of the Contracting Officer.
C4. APPLICABLE PUBLICATIONS. All work performed on F&ES Firefighting equipment and Personal Protective Equipment (PPE) shall be done in accordance with the current version of all applicable publications and standards (current edition) including, but not limited to the following:
a. National Fire Protection Association (NFPA) 1911: Standard for the Inspection, Maintenance, Testing, and Retirement of In-Service Emergency Vehicles
b. NFPA 1932: Standard on Use, Maintenance, and Service Testing of In-Service Fire Department
Ground Ladders
c. NFPA 1852: Standard on Selection, Care, and Maintenance of Open-Circuit Self-Contained Breathing
Apparatus (SCBA)
d. NFPA 1989: Standard on Breathing Air Quality for Emergency Services Respiratory Protection
e. Portable Air Cascade Manufacturers (Bauer and Oxygen Generating Systems Intl. (OGSI)) Suggested
Inspection, Testing, Servicing, Cleaning, and Certification (as applicable)
f. NFPA 1962: Standard for the Care, Use, Inspection, Service Testing, and Replacement of Fire Hose, Couplings, Nozzles, and Fire Hose Appliances
g. NFPA 1851: Standard on Selection, Care, and Maintenance of Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting
h. NFPA 1404: Standard for Fire Service Respiratory Protection Training
i. NFPA 1500: Fire Department Occupational Safety, Health and Wellness Program
j. Specialized Firefighting Equipment Manufacturers (Hurst, Holmatro, Scott Safety, Bauer Compressor, OGSI Oxygen Compressor, TSI PortaCount, Globe, Morning Pride, Fire Dex, Innotex Turn-Out Gear, Alco-Lite Ladders, Pierce Aerial Ladder, NFPA 1962 Fire Hose, Stryker Gurney, Stryker Lucas Device, and Zoll Monitors) Suggested Inspection, Testing, Servicing, Cleaning, and Certification (as applicable)
k. Extrication Equipment Manufacturers (Hurst and Holmatro) Suggested Inspection, Testing, Servicing, Cleaning, and Certification (as applicable)
l. Occupational Safety and Health Administration (OSHA) Standards, 29 Code of Federal Regulations (CFR) Part 1910 Occupational Safety and Health Standards
m. Manufacturer’s Suggested Standards
i. Scott Safety SCBAs and Bottles
ii. Bauer Compressor
iii. OGSI Oxygen Compressor
iv. TSI PortaCount
v. Globe, Morning Pride, Fire Dex, and Innotex Turn-Out Gear
vi. Alco-Lite Ladders
vii. Pierce Aerial Ladder
viii. NFPA 1962 Fire Hose
ix. Stryker Gurney and Lucas Device
x. Zoll Monitors
xi. Task Force Tips Nozzles
xii. Hurst Edraulics Rescue Tools
xiii. Holmatro Rescue Tools
xiv. Hale and Waterous Pumps on Pierce and KMEs Fire Apparatus
C5. GOVERNMENT RESPONSIBILITIES.
a. Utilities necessary to perform all inspections, tests, certifications, cleaning, calibrations, repairs, and maintenance will be provided by the Government.
b. The Government will provide a list of Fire Fighting Equipment and Personal Protective Equipment to be serviced and certified. The Government will also update the list as equipment is replaced due to unserviceable or out of life cycle.
C6. EQUIPMENT. The following equipment list may be modified by changes, additions, or deletions during the life of the contract in accordance with paragraph 12.
Description QTY
MCB
CPEN
MCLB
Barstow
MCAS
Miramar
Annual Flow Test Flow Test SCBA Harness (Standard and CBRNE) and SCBA Mask (Standard and Modified for CBRNE)
45 65
Flow Test additional SCBA Masks (Standard and Modified for
CBRNE)
20 0
Flow Test Confined Space Escape Pack 9 10 4 Flow Test RIC Drag Bag 14 5 3
Annual Fit Testing Fit Test SCBA Masks 159 0 50 Fit Test N-95 Masks 159 0 50
Hydrostatic Testing Cylinders Hydrostatic Test HM 60 Min Carbon Cylinders 91 15 8 Hydrostatic Test HM 45 Min Carbon Cylinders 0 0 64 Hydrostatic Test 30 Min Carbon Cylinders 259 60 0 Hydrostatic Test 10 Min Escape pack cylinders 9 10 0
Annual PM and servicing of Bauer Breathing Air Compressor (4 models)
4 4
Air Sampling/Testing and Analysis 4 4 4
Equipment Calibration TSI Porta Counters (2 units) 2 1 2
Structural Ensemble Inspection/Testing Advanced Inspection of structural ensemble each IAW NFPA 1851 (Set)
300 150 110
Second required advance cleaning and inspection IAW NFPA 1851 300 150 110
Annual Ladder Testing/Inspection/Certification/NDT Ground Ladder Testing 1400 650’ 264’ 75' Aerial 1 1 0 105' Aerial 1 0 0
Structure Hose Testing (feet) 45,000 27,000 16,800
Test Fire Hose Nozzles 60 0 20
Annual Pump Testing 26 0 8
Annual Maintenance Ambulance Gurneys Stryker EMS Gurney 7 3 3 Annual Maintenance Lucas Devices Stryker Lucas Devices 14 5 2 Annual Maintenance of Hydraulic Rescue Tools-eDraulic Spreader 5 0 2 Cutter 5 0 2 Combination 11 0 2 Ram 9 0 3 Strong Arm 1 0 1 EMS Cardiac Monitors Zoll EMS Monitors 10 5 5
C7. THE CONTRACTOR SHALL PROVIDE THE FOLLOWING SERVICES.
7.1 Annual Flow Test/Service: On-site inspection, testing, maintenance, repair and recertification of Self- Contained Breathing Apparatus (SCBA) will be completed by a certified technician. Proof of certification of each technician shall be provided to the Government prior to any work being started. Service shall be conducted on-site, be in accordance with all manufacturer’s recommendations and include an inventory of all systems, location and applicable dates recorded.
A breathing apparatus is a fully assembled breathing device that can be immediately used in a contaminated air environment and/or in firefighting by the operator. The components can include: backpack, regulator, air hoses, gauges and valves. This includes the SCBA Panther, Supplied Air Respirator (SAR)/Hip Pack and Rapid Intervention Crew (RIC) Bag.
Each Breathing Apparatus will be thoroughly inspected visually, and any necessary cleaning / repairs completed.
The breathing device will be placed on a test bench with the following tests completed: automatic positive pressure, opening pressure, positive pressure, relief valve pressure, by-pass function, and leakage test. Results will be recorded, and necessary repairs made to ensure device passes tests. Servicing of the breathing device includes: the positive pressure attachment, valve housing assembly, valve insert with breathing hose and adjustment of breathing valve.
The regulator unit is placed on the test bench with the following tests completed: secondary pressure, sealing pressure, relief valve, warning pressure, function and sealing tightness. Results will be recorded, and necessary repairs made to ensure the regulator passes tests. Additional servicing of the regulator unit includes: the cylinder valve connection, pressure regulator mechanism, supply hose, high-pressure hose, pressure gauge, quick-coupling connection and warning whistle. Servicing of the harness and backpack includes adjusting the cylinder strap assembly and the cylinder bracket assembly. Servicing of the cylinder assembly includes: the hand-wheel mechanism and pressure gauge safety device. The Contractor shall use all manufacturer-recommended tools and equipment, including Breathing Apparatus service kits and the PosiChek 3.
7.2 Annual Fit Testing: Certified/Qualified technicians will perform fit testing on all personnel’s assigned equipment to include: SCBA Face Piece. Proof of certifications / qualifications of technicians shall be provided to the Government prior to any work being started. All testing and test procedures will be carried out in accordance with all applicable guidance and regulation, including OSHA 1910.134, the current editions of NFPA Standards 1404 and 1500, and 42 CFR Part 84. OSHA 1910.134 mandates that fit testing shall be performed at least once annually or when major repairs have been performed to the face masks or respirator, or if there has been a major increase or decrease in body weight of the user (20%) or at any time personnel change. All fit testing will be carried out using the TSI PortaCount or Occupational Health Dynamics (OHD) QuantiFit.
7.3 Annual Hydrostatic Testing of Cylinders: Service for hydrostatic testing shall be conducted onsite with a DOT approved hydrostatic testing unit. Hydrostatic testing will be performed by a qualified/certified technician in accordance with the Department of Transportation (DOT) and Structural Composite Industries (SCI) recommendations for the hydrostatic testing of cylinders manufactured under DOT exemption. Proof of certification/qualification of technicians shall be provided to the Government prior to any work being started. All hydrostatic testing procedures shall complete in accordance with the current applicable DOT & NFPA Standards for air bottles. At the time of Hydrostatic testing an internal visual inspection of the cylinder will be completed. This will be carried out utilizing a borroscope in order to detect minor defects not visible to the naked eye.
7.4 Annual PM of Breathing Air Compressor and Servicing: A total of 4 Bauer breathing air compressors shall be inspected, serviced, and tested by a Bauer certified technician, in accordance with the manufacturer’s requirements and specifications. Proof of Bauer technician certification shall be provided to the Government prior to any work being started. The inspection, servicing, repair, and testing shall be done on–site.
The service includes: the recording of fill station preliminary data, pre-test data, check list, test check list, labels, instructions and appearance as well as the compressor preliminary data, pre-test data, check list tests, check list normal operational readings, accessories, monitors, compressor CO2 monitors, air test, labels and instructions and appearance. All servicing, repairs, calibrations and testing of compressors, refill stations, storage trailers and gas boosters or decanting systems shall be performed and carried out by a Bauer certified high pressure and ultra-high pressure breathing air compressor technician. A representative of the Government shall witness a functional operational test after each service or repair.
7.5 Quarterly Air Sampling/Testing and Analysis: It will be the responsibility of the Contractor to collect and process all air samples and provide the test result records to the Government.
7.6 Annual Structural Ensemble Inspection/Testing: The Contractor on an annual basis will inspect, clean, and disinfect up to three hundred sets of firefighter personal protective clothing to include hoods, boots, gloves and helmets, in accordance with NFPA 1851, Selection, Care, and Maintenance of Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting, Current edition. Contractor shall be third party verified to NFPA 1851 Standard on Selection, Care, and Maintenance of Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting. The Contractor shall provide the Camp Pendleton Fire Department with all data on testing, maintenance, and inspection activities in the form of a spreadsheet or pdf. that allows for monitoring the status of cleaning and inspection. This data shall be delivered either via email or through a database accessible to the Camp Pendleton Fire Department. Additionally, all data shall be turned over within (30) calendar days following the end of each period of performance.
7.7 Annual Ladder Testing/Inspection/Certification: Inspection, testing, maintenance, repair, and recertification of ladders will be tested by a qualified/certified technician. Proof of technician certification/qualification shall be provided to the Government prior to any work being started. All applicable NFPA regulations and manufacturer requirements will be utilized during ground ladder / aerial apparatus testing and repair. Prior to service testing, all ground ladders shall be visually inspected in accordance with the current edition NFPA Standard 1932 and in the case of aerial apparatus, the current edition of NFPA Standard 1911. 14’, 24’, 28’, and 35’ Extension Ladders will be inspected, tested, and all manufacturer’s recommended preventive maintenance shall be completed. 12’, 14’, and 16’ Roof Ladders will be inspected, tested, and all manufacture’s recommended preventive maintenance shall be completed. 10’ Folding Ladders will be inspected, tested, all manufacture’s recommended preventive maintenance completed, and repairs as needed. 10’ Attic Ladders will be inspected, tested, all manufacture’s recommended preventive maintenance shall be completed 100’and 75’ Aerial Apparatus apparatus will be inspected and tested, on an annual basis by a certified aerial apparatus technician in accordance with NFPA 1911. In the case of the 100’ and 75’ Aerial Apparatus a representative of the Government shall witness a functional operational test of aerial apparatus after all testing or servicing.
7.8 Annual Structure Hose Testing: Inspection, testing, maintenance, and recertification of a minimum of 88,800 feet of structure fire hose. Contractor shall inspect, test, service in accordance with the current edition of NFPA Standard 1962 and certify the condition of the hoses. In-service hose shall be unloaded, unracked, unreeled or unrolled and physically inspected. Contractor shall be reloaded, re-racked, re-reeled, or re-rolled hoses so that any folds do not occur at the same position on the hose. Physical inspection shall determine that the hose and couplings are free of physical damage and debris, do not exhibit evidence of mildew or rot, any signs of chemical damage, burns, cuts, abrasion, and vermin. Accurate hose records shall be established and maintained in accordance with the Standard. All hose identification numbers shall be re-stenciled on to the jacket or cover using ink or paint if necessary. The Contractor will utilize a computer-generated reporting system for recording all hose data. This information shall cover the following (where applicable): assigned identification number, manufacturer, part number, vendor, size i.e. internal diameter of water way, length, type of hose, construction, date received, date put in service, the date of each service test, the serviced test pressure, repairs and new length if shortened, actual damage, exposure to possible damage, reason removed from service, indication that the hose has been removed from service or condemned within the warranty. Pressure tests shall be performed utilizing calibrated digital gauges and documented for accountability.
7.9 Annual Testing of Fire Service Nozzles: Inspection, testing, maintenance, and recertification of department fire service nozzles.
7.10 Annual Pump Testing: Testing of fire pump systems on vehicles and apparatus will be conducted to the standards and procedures as outlined in the current edition of NFPA Standard 1911. These tests are to be conducted on an annual basis or when repairs or modifications to the pumps have been carried out. Technicians shall ensure that the test site is as outlined in the Standard. Should this not be the case and a testing pit is not available for use, then use of the Government’s Draft Commander Trailer is an acceptable alternate option. All environmental conditions shall be within required parameters. Contractor shall provide all required intake hoses, strainers, and suction hoses and a determination must be made that the intake gauge pressure is a minimum 20 psi. Discharge hose can be provided if required. This hose is to allow the correct flow to the measuring devices. Contractor will ensure that this does not exceed 35 ft. per second (approximately 500 gallons per minute for 2.5 in. hose) as a safety precaution. Technicians will ensure that hoses are marked to prevent coupling-hose separation going unnoticed. All flow measuring devices shall meet NFPA requirements and all gauges shall be grade A as defined in ASME B 40.1, or calibrated digital gauges shall be utilized. All test results shall be recorded along with ambient air temperatures, water temperatures, vertical lift, the elevation of test site and the atmospheric pressure at test site (converted to sea level). These readings shall also be recorded in increments of two hours to ensure uniformity and accuracy in test results. Vacuum tests shall also be conducted on all pumping units. Pressure control tests on all pumps shall also be conducted. Pressure gauges, vacuum gauges and flow meters on board pumping units, vehicles and fire apparatus shall be checked for accuracy and can be calibrated on site utilizing the dead weight testing system. Gauges which require repairs will be handled under the over and above CLIN. If apparatus is equipped with a water tank, then the tank to pump flow rate shall be checked as per the current Standard. Contractor will also ensure that the engines, pumps and transmissions on all vehicles and all pumping apparatus do not overheat or perform poorly, in any way during the period of time required to conduct these tests. The Contractor shall conduct testing of the pump at draft using the Draft Commander trailer unless the Contracting Officer, in his sole discretion, approves in advance the use of a hydrant or alternate sources. Due to the variables and parameters required for this kind of testing, the Contractor’s technicians shall establish communications with the Government prior to the commencement of testing.
A representative of the Government shall witness a functional operational test of all apparatus after testing or servicing.
7.11 Contract Data Requirements: Contractor shall provide a final report in a binder per installation, (6) binders and an electronic version to the Government containing: Annual Visual Inspection Certificate, Hydrostatic Test Certificate and results, Scott Test Results, SCBA Mask History and Maintenance Report, Backpack History and Maintenance Report, Air Bottle History Maintenance Report, Cylinder Failure Form, Cylinder Spec Sheet, Cylinder Visual Defects Report, SCBA Compressor and Refill Station Operational Inspection and Test Certificates, Fit Test Results, Air Test Results, Ladder Test Results, Pump Test Results, Suit Test Results, Hose Test Results, Nozzle and Appliance Test Results, Air Cart Certificates and Results, Calibration Certificates and a complete report of all repairs that were accomplished during the contract period of performance. The binders shall be delivered within 30 days following the completion of the period of performance.
7.12 Contractor will provide data-entry support to enter service/maintenance and testing information into the USMC Fire and Emergency Services Records Management data base (First Due). Testing data will be uploaded into the appropriate areas/modules of First Due. The department First Due system administrator will provide log on and password credentials via the Common Access Card (CAC) to the system once the Contractors are on the installation and keep those credentials active throughout the contract.
7.13 Annual Maintenance of Lucas Devices: Inspection, testing, maintenance, and recertification of department Lucas Devices.
7.14 Annual Maintenance of Ambulance Gurneys: Inspection, testing, maintenance, and recertification of department ambulance gurneys.
7.15 Annual Maintenance of Hydraulic Rescue Tools: Inspection, testing, maintenance, and recertification of department hydraulic power rescue tools.
7.16 Annual Maintenance of Heart Monitors: Inspection, testing, maintenance, and recertification of department heart monitors.
C8. REPORTS. The Contractor shall, at the time of completion of work prior to departure, ensure that a representative of the Government has been provided a copy of a complete, individualized and accurate report of all test / inspections records. The report shall include all test / inspection results for all services provided under this contract. The Government’s representative shall have 10 working days to review and accept the report as complete and accurate. This requirement does not relieve the Contractor of the requirements contained in section 7.11 Contract Data Requirements (CDR). The reports shall be uploaded in the WAWF invoice submission for approval and acceptance.
C9. QUALITY ASSURANCE. A Contracting Officer Representative (COR) will be assigned to this contract. The Contractor is responsible for Quality Control. The Government will conduct Quality Assurance in accordance with a Quality Assurance Surveillance Plan (QASP), which describes how Government personnel will evaluate and assess Contractor performance. The QASP will be revised or modified as circumstances warrant. An informational copy of the QASP will be furnished to the Contractor after award.
C10. OVER AND ABOVE WORK.
10.1 The Contractor shall provide all items necessary such as labor, transportation, equipment, tools, supervision, management, quality control, testing equipment, materials and parts required to perform over and above work repair, modification or replacement of equipment, parts, etc. in a timely manner. The Contractor shall substantiate the need for over and above work by describing the conditions that warrant the repair, and why minor repair measures accomplished as part of regular maintenance will not suffice. The Contractor shall report the need for over and above work repairs to the Contracting Officer Representative (COR).
10.2 General Requirements and Procedures for Over and Above work. As described in paragraph 252.217-7028 of the contract, Over and Above Work authorizes the Contractor to perform repairs to identified equipment that is outside of the standard inspection requirements to ensure equipment is sustained in good working order in accordance with manufacturer’s instructions. Work performed under this requirement will be billed under the Over and Above Work line item identified for each year’s period of performance.
10.3 Response Time. The Contractor shall notify the COR within one (1) hour for emergency work or by 8:00 A.M.
the following workday if other than emergency work and provide a description of the work with an estimate showing labor hours and material/parts. Each estimate shall be prepared by the Contractor and forwarded within five
(5) calendar days of receipt of the request under routine conditions, and within two (2) hours under emergency conditions.
10.4 Authority to Performance Over and Above Work. The Contracting Officer is the only person(s) with authority to authorize the Contractor to proceed with the work in accordance with the over and above work portion of the contract and work will be negotiated and approved in advance for each work request. All work requests will be ordered in writing. In the sole discretion of the Contracting Officer, the Government may elect not to make repairs or may replace items. Replacement items may be acquired either from the Contractor, or from any other source determined to be advantageous by the Government, in its sole discretion.
10.5 Over and Above Estimate, Preparation and Evaluation
a. The preparation of estimates is included in the price of the firm fixed-price portion of the contract.
b. Following equipment inspection, or if requested by the COR, the Contractor shall provide a written work estimate that will include the following minimum information:
(1) Contractor name and address.
(2) Contract number.
(3) Date inspection was performed/call placed.
(4) Itemized list of parts required to perform repair, including quantity and price for each item.
(5) Estimated number of labor hours required to complete repair.
(6) Number of hours charged for travel if the repair is not part of the scheduled maintenance inspection.
c. Materials and Parts.
(1) Material price and parts shall be the lowest price available considering the availability of materials and the time constraints of the job. It shall include any discounts and/or rebates accrued to or for the Contractor. Parts shall be provided to the Government at the Contractor’s cost without mark up.
(2) The Contractor shall provide quotations from three suppliers of the required materials exceeding
$2,500.00 per parts/material.
d. Estimate Evaluation. The Contractor’s estimate will be evaluated to determine if:
(1) The scope has been clearly and accurately identified.
(2) The number of hours has been accurately estimated.
(3) The cost of materials and parts are reasonable and properly documented. The material and parts shall include a detailed estimate of materials including such items as the name of the part, manufacturer of the part, the part number, the size, quality, quantity (number of units) and the unit prices.
(4) The estimated lead-time for the delivery of the part to the Contractor is included.
(5) The Contractor shall state the actual time it will take to perform the work from commencement to completion.
(6) The detailed estimate will be used to negotiate over and above work repairs and award of a firm fixed price modification to the contract. The Contractor shall not assume that a modification will be issued and shall not order materials or proceed with any work until receipt of the modification.
C11. WARRANTY. The Contractor guarantees that all items will be serviced or repaired in accordance with manufacturers’ specifications and applicable certification requirements as set forth by OSHA, NIOSH, and NFPA.
The Contractor guarantees all service and repairs for a period of one year unless damage is due to misusing, tampering, fire damage, or normal wear-and-tear. Determination of application of one of the exceptions to warranty is in the sole discretion of the contracting officer.
Units which require calibration will be marked so that tampering is evident to the Contractor; if certified units require re-calibration for any reason, the units will be shipped to the Contractor and returned to the Government at Contractor expense. Recalibration which is not the result of one of the exceptions to warranty will be done at no cost to the Government. Recalibration required due to an exception to warranty will be accomplished under the over and above repair CLINs.
C12. INCREASE OR DECREASE IN REQUIREMENTS. The equipment to be serviced under this contract may change at the discretion of the Government during the time the contract is in effect. Replacement of equipment with similar equipment shall not constitute grounds for request for equitable adjustment or claim by the Contractor. In addition, due to reorganization, restructuring, or to enhance efficiency, the Government reserves the right to add or delete requirements in this contract to include or exclude all or part of facilities in California. Such increased or decreased requirements may include Marine Corps installations or other Department of the Navy organizations not included herein.
C13. WORKING HOURS. Required inspections and repairs will be coordinated by the Contracting Officer’s Representative (COR). On-site service will be provided during normal working hours, 7:30 am through 4:30 pm, Monday through Friday, weekends and holidays excluded. The Contractor shall obtain prior approval of the COR for work that is to be done on evenings, weekends and holidays.
Section E - Inspection and Acceptance
INSPECTION AND ACCEPTANCE TERMS
Supplies/services will be inspected/accepted at:
CLIN INSPECT AT INSPECT BY ACCEPT AT ACCEPT BY
0001 Destination Government Destination Government 0002 Destination Government Destination Government 0003 Destination Government Destination Government 0004 Destination Government Destination Government 1001 Destination Government Destination Government 1002 Destination Government Destination Government 1003 Destination Government Destination Government 1004 Destination Government Destination Government 2001 Destination Government Destination Government 2002 Destination Government Destination Government 2003 Destination Government Destination Government 2004 Destination Government Destination Government 3001 Destination Government Destination Government 3002 Destination Government Destination Government 3003 Destination Government Destination Government 3004 Destination Government Destination Government 4001 Destination Government Destination Government 4002 Destination Government Destination Government 4003 Destination Government Destination Government 4004 Destination Government Destination Government
Section F - Deliveries or Performance
DELIVERIES OR PERFORMANCE
F1. CLIN – DELIVERIES OR PERFORMANCE.
The following are the period of performance (PoP) for the services to be provided over the life of this contract:
CLINs Period PoP
0001-0004 Base Period 15 January 2025 – 14 January 2026 1001-1004 Option Period One (1) 15 January 2026 – 14 January 2027 2001-2004 Option Period Two (2) 15 January 2027 – 14 January 2028 3001-3004 Option Period Three (3) 15 January 2028 – 14 January 2029 4001-4004 Option Period Four (4) 15 January 2029 – 14 January 2030
F2. CONTRACT TERM.
The anticipated contract start date is 3 February 2025. The contract will be awarded for a base period of twelve (12) months, with four (4) 12-month option periods. The entire duration of the contract shall not exceed sixty-six (66) months.
The additional six (6) months of performance reserved and modified into the contract in accordance with FAR 52.217-8, Option to Extend Service, and/or FAR 52.217-9, Option to Extend the Term of the Contract should it be determined at a later date that an extension of services is necessary. In the event of the extension being exercised, the contract will be modified to allow for the extension of services.
F3. Performance Requirements Summary
Outcome Performance Inspection Incentive
Stakeholder Outcome
PWS
Para.
No. Standard
Acceptable Quality Level Inspector
Method of Frequency
Performance Incentive
Flow Test SCBA Harness (Standard and CBRNE) and SCBA Mask (Standard and Modified for
CBRNE)
7.1
On-site inspection, testing, maintenance, repair and recertification of Breathing Apparatus will be completed by a certified technician.
Proof of certification shall be provided to the government prior to any work being started.
Compliancy 100%
COR
Review after testing is completed-validate tracking daily of work completed And customer complaints
CPAR, timely invoice approval, and exercise of option year.
Annual Fit Testing 7.2
All testing and test procedures will be carried out in accordance with OSHA 1910.134, the current editions NFPA Standards 1404 AND
1500, NIOSH, 42
CFR 84, and the manufacture’s fit testing procedures.
Compliancy 100%
COR
Validated daily and end of testing And customer complaints
CPAR, timely invoice approval, and option year
Annual Visual Inspection of Cylinders
7.3
IAW Department of Transportation (DOT).
DOT 49 CFR
Compliancy
COR
Validated daily and at end of testing
CPAR, timely invoice approval, and
Hydrostatic Testing of Cylinders 7.4
Hydrostatic testing will be performed by a qualified/certified technician in accordance with the DOT and EFIC recommendations for the hydrostatic testing of cylinders manufactured under DOT exemption.
Compliancy 100%
COR
Validated by inspection results and air bottle labeling
CPAR, timely invoice approval, and
Valve Rebuild (SCBA Cylinders) 7.5
Provide Rebuild Valve Kits for Cylinders, labor to remove, re-build, re-install and torque the valves onto the tanks within Manufacturer’s requirements
Compliancy 100%
COR
Validated through replacement per manufactures guidance
CPAR, timely invoice approval, and
Inspection, testing maintenance, repair and re-certification od supplied air breathing apparatus and hose carts 7.6
Services shall include batteries, full electronic testing of pressure sensitive alarm system, pressure gauges are tested and refilled (glycol) or replaced if necessary, all valves are operationally tested and serviced, hoses HP 6000 psi are checked for damage and replaced / repaired if necessary and regulators are performance tested per manufacturers specifications
Compliancy. COR
Validated on site through testing
CPAR, timely invoice approval, and
Annual PM of Breathing Air Compressor and Servicing 7.7
3 Bauer breathing air compressors shall be inspected, serviced, repaired and tested by a Bauer certified technician, in accordance with the manufacturer’s requirements and specifications.
100% Compliancy COR
Review of testing results on site
CPAR, timely invoice approval, and
Air Sampling/Testing and Analysis 7.8 will provide air sampling services of all Bauer compressor units to the client. All air sampling shall be completed
Contractor to complete, individualized and accurate report of all test / inspections records and a spreadsheet of all test / inspection results. COR
Validated that contractor process all samples collected and provide the test result records to the government.
CPAR, timely invoice approval, and
Visual Inspection and Testing of A- Level and B-Level Suits 7.9
Contractor will inspect, test, service in accordance with the applicable sections of the current edition of NFPA Standard 1991
A data log will be completed indicating the serial number, identification number, manufacturer, manufacture date, style and size of each suit tested. COR
Validated at time of testing
CPAR, timely invoice approval, and
Equipment Calibration 7.10
2-Magnahelic level A suit tester, 1-Draft Commander Pump Test Trailer, 1- Set Portable Pump Test Gauges, Haz Mat ID, 14- TIC’s, 6- Air Bag Controls, 2- Hose Testing Units moisture analyzers,
(1) fire finder (Thermal Imaging Cameras if applicable).
Contractor’s calibration equipment shall be in compliance with ISO 10012-1 and
ANSI/NCSL
Z540-1 standards. COR validate tracking daily of work completed
CPAR, timely invoice approval, and
F4. FEDERAL HOLIDAYS.
The following Federal Holidays are observed by Government personnel:
New Years Day Labor Day
Birthday of Martin Luther King, Jr. Columbus Day Washington’s Birthday Veterans Day Memorial Day Thanksgiving Day Juneteenth National Independence Day Christmas Day Independence Day
DELIVERY INFORMATION
CLIN DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /
CAGE
0001 POP 03-FEB-2025 TO
02-FEB-2026
N/A M33120
CHRISTOPHER HUBMER
22113 8TH AND D AVE WEST END
CAMP PENDLETON CA 92055
M33120
0002 POP 03-FEB-2025 TO
02-FEB-2026
N/A M93845
RYAN TWOREK
BLDG 236, EAST END
BARSTOW CA 92311-5050
760-577-6081
M93845
0003 POP 03-FEB-2025 TO
N/A MCAS MIRAMAR
BRIAN CATO
MCAS MIRAMAR BLDG 7117
SAN DIEGO CA 92145-2000
858 577-6660
M02203
0004 POP 03-FEB-2025 TO
N/A M33120
CHRISTOPHER HUBMER
22113 8TH AND D AVE WEST END
CAMP PENDLETON CA 92055
1001 POP 03-FEB-2026 TO
02-FEB-2027
N/A (SAME AS PREVIOUS LOCATION)
1002 POP 03-FEB-2026 TO
N/A M93845
RYAN TWOREK
BLDG 236, EAST END
BARSTOW CA 92311-5050
760-577-6081
1003 POP 03-FEB-2026 TO
N/A MCAS MIRAMAR
BRIAN CATO
MCAS MIRAMAR BLDG 7117
SAN DIEGO CA 92145-2000
858 577-6660
1004 POP 03-FEB-2026 TO
N/A M33120
CHRISTOPHER HUBMER
22113 8TH AND D AVE WEST END
CAMP PENDLETON CA 92055
FOB: N/A
2001 POP 03-FEB-2027 TO
02-FEB-2028
N/A (SAME AS PREVIOUS LOCATION)
2002 POP 03-FEB-2027 TO
N/A M93845
RYAN TWOREK
BLDG 236, EAST END
BARSTOW CA 92311-5050
760-577-6081
2003 POP 03-FEB-2027 TO
N/A MCAS MIRAMAR
BRIAN CATO
MCAS MIRAMAR BLDG 7117
SAN DIEGO CA 92145-2000
858 577-6660
2004 POP 03-FEB-2027 TO
N/A M33120
CHRISTOPHER HUBMER
22113 8TH AND D AVE WEST END
CAMP PENDLETON CA 92055
3001 POP 03-FEB-2028 TO
02-FEB-2029
N/A (SAME AS PREVIOUS LOCATION)
3002 POP 03-FEB-2028 TO
N/A M93845
RYAN TWOREK
BLDG 236, EAST END
BARSTOW CA 92311-5050
760-577-6081
3003 POP 03-FEB-2028 TO
N/A MCAS MIRAMAR
BRIAN CATO
MCAS MIRAMAR BLDG 7117
SAN DIEGO CA 92145-2000
858 577-6660
3004 POP 03-FEB-2028 TO
N/A M33120
CHRISTOPHER HUBMER
22113 8TH AND D AVE WEST END
CAMP PENDLETON CA 92055
4001 POP 03-FEB-2029 TO
02-FEB-2030
N/A (SAME AS PREVIOUS LOCATION)
4002 POP 03-FEB-2029 TO
N/A M93845
RYAN TWOREK
BLDG 236, EAST END
BARSTOW CA 92311-5050
760-577-6081
4003 POP 03-FEB-2029 TO
N/A MCAS MIRAMAR
BRIAN CATO
MCAS MIRAMAR BLDG 7117
SAN DIEGO CA 92145-2000
858 577-6660
4004 POP 03-FEB-2029 TO
N/A M33120
CHRISTOPHER HUBMER
22113 8TH AND D AVE WEST END
CAMP PENDLETON CA 92055