Lompoc_Salts_Mgt_Plan_010611.pdf
PDF 4 MB Posted
- Solicitation number
- 2025-RFP-015DW
- Issued by
- Santa Barbara County, Long Beach City, California
About this file
This is a Salinity Management Study and Plan document prepared by Larry Walker Associates for the City of Lompoc Regional Wastewater Reclamation Facility in January 2011, submitted to the Central Coast Regional Water Quality Control Board to comply with NPDES Permit requirements. The study addresses salt management for total dissolved solids (TDS), chloride, boron, sodium, and sulfate in wastewater discharges to San Miguelito Creek and the Santa Ynez River. The facility operates under NPDES Permit No. CA0048127 (Order No. R3-2006-0037) and serves the City of Lompoc, Vandenberg Air Force Base, and Vandenberg Village Community Services District with an average dry weather flow design capacity of 5.5 million gallons per day (MGD). The study includes monitoring data analysis, source identification through mass balance calculations, and evaluation of control strategy options. Key findings indicate that water supply accounts for the majority of salt loading (ranging from 34 to 107 percent by constituent), with "other activities" (residential and commercial) and industrial users contributing lesser amounts. The analysis demonstrates that reduction percentages needed to meet effluent limits range from 0 to 7 percent for TDS and established limits, while surface water quality objectives require reductions of 15 to 61 percent depending on the constituent.
The study identifies both controllable and uncontrollable salt sources, with water supply representing the primary uncontrollable source. Recommended implementation actions include partnering with VVCSD to evaluate water softener reduction mechanisms by end of 2011, examining feasibility of VVCSD water treatment process modifications, conducting targeted source identification for boron and chloride by mid-2012, implementing education and outreach for borax-free detergent use by end of 2013, evaluating water softener ban ordinance effectiveness by mid-2013, adopting such ordinances by mid-2014, and implementing a recycled water system by end of 2015. The study notes that City of Lompoc voters have twice rejected State Water Project water as an alternative source (1979 and 1991), making alternative water supplies infeasible. Capital-intensive options such as microfiltration/reverse osmosis treatment ($9.5 to $10+ million per MGD capacity with $730,000-plus annual operation and maintenance), ocean outfall discharge ($20-30 million capital cost), or groundwater discharge with advanced treatment (exceeding $50 million capital cost) are identified as cost-prohibitive with significant implementation barriers.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J A N U A R Y 2 0 1 1
C I T Y O F L O M P O C
Salinity Management Study and Plan
Submitted to:
CENTRAL COAST REGIONAL WATER QUALITY CONTROL BOARD
Prepared by:
LARRY WALKER ASSOCIATES
Lompoc Salinity Management Study and Plan i January 2011
TABLE OF CONTENTS
Executive Summary…………………………………………………………………………. iii
1.0 Introduction ……………………………………………………………………………... 1-1
Regulatory Background and Requirements….……………………………...………… 1-1 Overview of Service Area and Hydrology…………………………………………… 1-2
Salinity Management Plan Organization……………………………………………… 1-2
2.0 Effluent and Receiving Water Quality Data…………………………………………… 2-1 Facility Effluent and Receiving Water Quality Results………..……………………... 2-1
Total Dissolved Solids……................................................................................ 2-1 Chloride……..………………………………………….................................... 2-3 Sodium…………..…………………………………………………………….. 2-5 Sulfate………………………..………………………………………………... 2-7
Boron………………………………………………………………………….. 2-8
3.0 Source Identification…………………………………………………………………….. 3-1
Existing Data Collection……………………………………………………………… 3-1 Additional Data Collection…………………………………………………………... 3-2 Summary by Constituent……………………………………………………………... 3-7
Total Dissolved Solids………………………………………………………… 3-9 Chloride……………………………………………………………………….. 3-12 Sodium………………………………………………………………………… 3-15 Sulfate…………………………………………………………………………. 3-18 Boron…………………………………………………………………………. 3-21
Summary of Common Findings………………………………………………………. 3-24
4.0 Source Reduction Options……………………………………………………………... 4-1
Water Supply Options………………………………………………………………… 4-1
Water Treatment Plant Modifications………………………………………… 4-1 Source Water Alternatives…………………………………………………….. 4-3
Other Activities Options………………………………………………………………. 4-4 Conduct Boron Source ID…………………………………………………….. 4-4
Industrial Options…………………………………………………………………….. 4-5 Significant Industrial Users Outreach………………………………………… 4-5
Water Softener Options………………………………………………………………. 4-5 Public Education and Outreach……………………………………………….. 4-6 Water Softener Ban Ordinance……………………………………………….. 4-6
Facility Options………………………………………………………………………. 4-6 MF/RO Wastewater Treatment……………………………………………….. 4-6 Ocean Outfall Discharge……………………………………………………… 4-6 Groundwater Discharge………………………………………………………. 4-7 Water Recycling………………………………………………………………. 4-7
Summary of Options…………………………………………………………………. 4-8
Lompoc Salinity Management Study and Plan ii January 2011
5.0 Proposal to Proceed…….……………………………………………………………….. 5-1
6.0 References……………………………………………………………………………….. 6-1
Appendices Appendix A: Summary of Existing and Additional Data Appendix B: Additional Data Collection Results Appendix C: Water Softener Calculation
Lompoc Salinity Management Study and Plan iii January 2011
Executive Summary The City is required under Provision VI.C.6 of its current NPDES permit (Order No. R3-2006- 0037) to conduct a Salt Management Study for total dissolved solids (TDS), chloride, boron, sodium, and sulfate. The purpose of this document is to meet the requirements of Provision VI.C.6 by summarizing effluent and receiving water monitoring data, characterizing source water supply and wastewater quality, and evaluating and identifying feasible source control strategies.
As part of the effluent data summary, a Reasonable Potential Analysis (RPA) was conducted.
Results indicated that all five salts constituents have a reasonable potential to cause or contribute to an exceedance of effluent limits and/or surface water quality objectives. Additionally, the percent reduction needed to meet effluent limits and surface water quality objectives was evaluated and is summarized in Table E-1. As indicated in Table E-1, no reductions are needed for sodium and chloride to meet effluent limits.
Table E-1. Estimated % Reductions Needed
Constituent Estimated % Reduction
Needed to Meet Effluent Limit
Estimated % Reduction Needed to Meet Surface Water
Quality Objective
TDS 7% 15%
Chloride 0% 61%
Sodium 0% 54%
Sulfate n/a 43%
Boron n/a 17%
Receiving water data revealed that water quality upstream and downstream of Facility effluent exceeds surface water quality objectives. This indicates that background levels of salt are elevated prior to contributions from Facility effluent.
In order to characterize source water supply and wastewater quality, existing data was compiled and data gaps were identified. Data gaps included boron concentrations in industrial and facility influent; chloride concentrations in industrial effluent; and TDS, chloride, sodium, sulfate and boron concentrations in residential and commercial effluent. To fill these gaps, additional monitoring was conducted in May and June 2010.
Using existing data and monitoring data collected as part of this study, a mass balance was developed to determine contributions to Facility influent. The mass balance found that there are elevated loadings of all salt constituents before any anthropogenic contributions (i.e., industrial, commercial, residential) from the City were included. For example, 88% of the TDS to the facility was found to be attributable to the water supply. These elevated contributions from source water were also seen for chloride (69%), sodium (75%), sulfate (107%), and boron (34%).
A summary of mass balance findings is provided in Table E-2.
Lompoc Salinity Management Study and Plan iv January 2011
Table E-2. Summary of Mass Balance Findings by Constituent
Source Constituent
TDS Chloride Sodium Sulfate Boron
Water Supply 88% 69% 75% 107% 34%
City, VVCSD, and VAFB Activities
Residential Water Softeners 2% 5% 7% n/a n/a
Industrial 7% 9% 9% 6% 2%
Other Activities 10% 46% 26% 24% 45%
Lastly, an analysis was conducted to evaluate the potential for source control to address necessary reductions and the main sources of salts loadings. The analysis ranked several implementation efforts from low to high efficacy by ease of implementation/feasibility. The source reduction analysis found that capital improvements (i.e., microfiltration/reverse osmosis, source water changes) are cost prohibitive and significant hurdles exist for implementation. The City identified modifications to the VVCSD water treatment plant, borax-free detergent outreach, significant industrial user outreach, a residential water softener removal program, and water recycling as effective as potential options for the Facility to reduce influent salinity loading.
Lompoc Salinity Management Study and Plan 1-1 January 2011
Section 1
Introduction The City of Lompoc Regional Wastewater Reclamation Facility (Facility) operates under the National Pollutant Discharge Elimination System (NPDES) Permit No. CA0048127, Order No.
R3-2006-0037. Provision VI.C.6 of the NPDES permit requires the Facility to conduct a Salt Management Study for the following constituents:
total dissolved solids (TDS) chloride boron sodium sulfate
The goals of the Salts Management Study, as defined by Provision VI.C.6 of Order No. R3- 2006-0037, are to control “levels of salts in discharges from the wastewater treatment facility to San Miguelito Creek and the Santa Ynez River and [attain] applicable water quality objectives for salts in the Lompoc Plain Sub-basin of the Santa Ynez Drainage Basin.” The NPDES permit further specifies that the Salt Management Study:
summarize effluent and receiving water monitoring data characterize source water supply and wastewater quality evaluate alternative control strategies develop a Salt Management Plan
REGULATORY BACKGROUND AND REQUIREMENTS
For the Salts Management Study, several regulatory requirements come into play. According to the NDPES permit, the Facility is subject to effluent limitations for TDS, chloride, and sodium.
Similarly, the Facility’s NPDES permit specifies that “discharges shall not cause receiving water to exceed the following water quality objectives.” Table 1-1 displays effluent limits and surface water quality objectives in comparison with the Facility’s maximum effluent concentrations based on a 12-month running mean.
Table 1-1. Effluent Limitations and Surface Water Quality Objectives
Parameter Effluent Limitation Average Monthly1
(mg/L)
Surface Water Quality Objective2
(mg/L)
Maximum Effluent Concentration
12-Month Running Mean (mg/L)
TDS 1,100 1,000 1,181
Chloride 250 100 216 Sodium 270 100 258 Sulfate n/a 350 420 Boron n/a 0.4 0.7 1: Compliance is based on 12-month running means 2: Annual mean values
Lompoc Salinity Management Study and Plan 1-2 January 2011
OVERVIEW OF SERVICE AREA AND HYDROLOGY
The Facility is a tertiary treatment plant with an average dry weather flow design capacity of 5.5 million gallons per day (MGD). Influent is received from the City of Lompoc, Vandenberg Air Force Base (VAFB), and the Vandenberg Village Community Services District (VVCSD).
VAFB and VVCSD contribute 0.63 and 0.5 MGD1, respectively to the Facility. Source water to the City primarily consists of well water with a small portion coming from Frick Springs. Frick Springs water is treated at the Frick Springs Water Treatment Plant which provides water to several residences in Miguelito Canyon and Miguelito County Park. VVCSD obtains its source water from wells while VAFB utilizes well water and State Water Project water (approximately 25% well water and 75% state water). It is estimated that approximately 5 – 10% of the City’s residents have water softeners compared to 40 – 60% of VVCSD’s residents. For the purposes of the study, it was assumed that VAFB has little to no water softeners.
The Santa Ynez River flows east to west through the Santa Ynez Valley, reaching the Pacific Ocean near VAFB and the City. Upstream of the Facility, the Santa Ynez River is generally dry during from June through October with the exception of water releases from the Bradbury Dam at Lake Cachuma. The major tributary to the Santa Ynez River in the City is San Miguelito Creek. San Miguelito Creek is spring fed, originates in the Lompoc Hills and approaches the City from the south. The Facility discharges to San Miguelito Creek approximately 1,000 feet upstream of the confluence with the Santa Ynez River. During dry months, the combined flow of San Miguelito Creek (if any) and the Facility effluent are the only flow in the Santa Ynez River downstream of the discharge point. These features are depicted in Figure 1-1.
SALINITY MANAGEMENT PLAN ORGANIZATION
As required by the NPDES permit, the major elements of this Plan include the following:
Section 1: Introduction
Section 2: Effluent and Receiving Water Quality Data
Section 2: Source Identification
Section 3: Source Reduction Options
Section 4: Proposal to Proceed
1 VVCSD and VAFB contributions include dry and wet weather flows
Lompoc Salinity Management Study and Plan 1-3 January 2011
Figure 1-1. City of Lompoc Locator Map
Lompoc Salinity Management Study and Plan 2-1 January 2011
Section 2
Effluent and Receiving Water Quality Data The purpose of this section is to provide a summary of effluent and receiving water quality data as required by NPDES permit Provision VI.C.6. Existing data was obtained from the Facility, Central Coast Conditional Agricultural Waiver Program (Ag Waiver Program), and Lompoc Molybdenum Study (Mo Study). At a minimum, the Facility monitors levels of TDS, chloride, sodium, sulfate and boron in the Facility on a quarterly basis. The Facility also monitors receiving waters (San Miguelito Creek) upstream and downstream of the Facility effluent. The Facility’s receiving water quality data was supplemented with data from the Ag Waiver Program and the Mo Study which monitored TDS levels in the Santa Ynez River at Floradale Ave (downstream of effluent) and in San Miguelito Creek. A description of the monitoring sites is provided in Table 2-1 followed by a summary of available data in Table 2-2.
Table 2-1. Description of Receiving Water Quality Monitoring Sites
Site Name Site ID Site Description
San Miguelito Creek at V St R-001 San Miguelito Creek located upstream of Facility Effluent
San Miguelito Creek, downstream of Effluent
R-002 San Miguelito Creek located just downstream of Facility Effluent
Santa Ynez River at Floradale Ave
SYR-2 Santa Ynez River located below confluence with San Miguelito
Table 2-2. Summary of Available Receiving Water Quality Data
Site Constituent(s) Monitored Data
Source TDS Chloride Sodium Sulfate Boron
San Miguelito Creek at V St (R-001)
2001 – 2010 2006 – 2010 2006 – 2010 2006 – 2010 2006 – 2010 Facility, Mo Study
San Miguelito Creek, downstream of Effluent
(R-002) 2001 – 2010 2006 – 2010 2006 – 2010 2006 – 2010 2006 – 2010
Facility, Ag Waiver, Mo Study
Santa Ynez River at Floradale Ave (SYR-2)
2006 – 2009 n/a n/a n/a n/a Ag Waiver, Mo Study n/a: data not available
FACILITY EFFLUENT AND RECEIVING WATER QUALITY RESULTS
Total Dissolved Solids (TDS)
Facility Effluent
The Facility’s TDS effluent limit is 1,100 mg/L and compliance is based on a 12-month running mean. Figure 2-1 shows the Facility’s TDS 12-month running mean in comparison with the
Lompoc Salinity Management Study and Plan 2-2 January 2011 effluent limit and illustrates the Facility’s ability to comply with the limit over time. The average 12-month running mean is 1,071 mg/L which is less than the effluent limit.
A Reasonable Potential Analysis (RPA) was also conducted to determine whether or not TDS has a reasonable potential to cause or contribute to an exceedance of the effluent limit and the surface water quality objective. According to the RPA, TDS show reasonable potential to exceed both the effluent limit and the surface water objective. In comparison with the maximum 12-month running mean (1,181 mg/L), approximately a 7% reduction in TDS levels is needed to achieve compliance with the effluent limit.
Figure 2-1. Facility TDS 12-Month Running Mean in Comparison with the Effluent Limit
Receiving Waters
As illustrated in Figure 2-2, both upstream (R-001) and downstream (R-002 and SYR-2) locations exceed the surface water quality objective of 1,000 mg/L. TDS concentrations are lower downstream of the Facility effluent. Concentrations at R-001 (San Miguelito Creek at V St., upstream of Facility effluent) indicate that background TDS levels in receiving waters are elevated prior to the contribution from the Facility’s effluent.
Lompoc Salinity Management Study and Plan 2-3 January 2011
Figure 2-2. TDS Concentrations in Receiving Waters
(Error bars are one standard error)
Chloride
Facility Effluent
The Facility’s average 12-month running mean is 203 mg/L and as Figure 2-3 illustrates, the Facility’s chloride 12-month running mean is able to comply with the 250 mg/L effluent limit.
The maximum 12-month running mean was 216 mg/L so no reduction is needed for compliance.
In contrast, an RPA was conducted and determined that chloride shows reasonable potential to cause or contribute to an exceedance of the effluent limit.
Lompoc Salinity Management Study and Plan 2-4 January 2011
Figure 2-3. Facility Chloride 12-Month Running Mean in Comparison with the Effluent Limit
As illustrated in Figure 2-4, both upstream (R-001) and downstream (R-002) locations exceed the surface water quality objective of 100 mg/L. On average, downstream concentrations are approximately 4% greater than upstream concentrations. Similar to TDS, concentrations at R- 001 (San Miguelito Creek at V St., upstream of Facility effluent) indicate that background chloride levels in Lompoc receiving waters are elevated prior to contribution from the Facility’s effluent.
Lompoc Salinity Management Study and Plan 2-5 January 2011
Figure 2-4. Chloride Concentrations in Receiving Waters
Sodium
Facility Effluent
The Facility’s effluent average 12-month running mean for sodium is 209 mg/L with a maximum 12-month running mean of 258 mg/L. The Facility’s sodium effluent limit is 270 mg/L and as illustrated in Figure 2-5, the Facility is able to meet this limit. Therefore no reduction is needed to achieve compliance. However, an RPA was conducted and determined that sodium shows a reasonable potential to cause or contribute to an exceedance of the effluent limit.
Lompoc Salinity Management Study and Plan 2-6 January 2011
Figure 2-5. Facility Sodium 12-Month Running Mean in Comparison with the Effluent Limit
As illustrated in Figure 2-6, both upstream (R-001) and downstream (R-002) locations exceed the surface water quality objective of 100 mg/L. On average, downstream concentrations are approximately 20% higher than upstream concentrations. Concentrations at R-001 (San Miguelito Creek at V St., upstream of Facility effluent) indicate that background levels of sodium in Lompoc receiving waters are elevated prior to the contribution from the Facility’s effluent.
Lompoc Salinity Management Study and Plan 2-7 January 2011
Figure 2-6. Sodium Concentrations in Receiving Waters
Sulfate
The Facility’s effluent average 12-month running mean for sulfate is 372 mg/L and the maximum 12-month running mean is 420 mg/L. Effluent limits do not exist for sulfate, however Order No. R3-2006-0037 indicates that Facility discharges should not cause receiving water to exceed a sulfate surface water quality objective of 350 mg/L (annual mean value). In order to meet the surface water quality objective, Facility effluent would have to be reduced by 17%. The RPA confirmed that sulfate shows reasonable potential to exceed surface water quality objectives.
Receiving Waters
Sulfate concentrations in receiving waters were obtained from Facility monitoring. As illustrated in Figure 2-7, both upstream (R-001) and downstream (R-002) locations exceed the surface water quality objective of 350 mg/L. Sulfate concentrations are lower downstream of the Facility effluent. Elevated concentrations at R-001 (San Miguelito Creek at V St., upstream of Facility
Lompoc Salinity Management Study and Plan 2-8 January 2011 effluent) indicate that background levels of sulfate in Lompoc receiving waters are elevated prior to the contribution from the Facility’s effluent.
Figure 2-7. Sulfate Concentrations in Receiving Waters
Boron
The average and maximum 12-month running mean for boron in Facility effluent are 0.6 and 0.7 mg/L, respectively. While there is no effluent limit for boron, Order No. R3-2006-0037 indicates that Facility discharges should not cause receiving water to exceed a boron surface water quality objective of 0.4 mg/L (annual running mean). An approximate 42% reduction is needed in order to meet surface water quality objectives. The RPA confirmed that boron shows reasonable potential to exceed the surface water quality objective.
Receiving Waters
Boron concentrations in receiving waters were obtained from Facility monitoring. As illustrated in Figure 2-8, both upstream (R-001) and downstream (R-002) locations exceed the surface water quality objective of 0.4 mg/L. Boron concentrations are lower downstream of the Facility effluent. Elevated concentrations at R-001 (San Miguelito Creek at V St., upstream of Facility
Lompoc Salinity Management Study and Plan 2-9 January 2011 effluent) indicate that background levels of boron in Lompoc receiving waters are elevated prior to the contribution from the Facility’s effluent.
Figure 2-8. Boron Concentrations in Receiving Waters
Lompoc Salinity Management Study and Plan 3-1 January 2011
Section 3
Source Identification Existing data for source water and industries was compiled as a first step to identifying sources of salts to the Facility’s influent. This data was used to conduct a preliminary mass balance which highlighted data gaps. To fill these gaps, additional monitoring was conducted in May and June 2010.
Next, a source identification was conducted to examine the relative contributions of three primary sources to the Facility influent: water supply, collection systems (i.e., residential and commercial source), and significant industrial users. Water supply data was obtained from municipal water treatment facilities in Frick Springs, City of Lompoc, VVCSD and VAFB.
Additional data was collected to characterize collection systems and included the VVCSD and VAFB trunk lines and homogenous commercial and residential drainage areas. Additionally, significant industrial user2 monitoring data was reviewed and included Fagerdala, the City of Lompoc Aquatic Center, In-Shape City, Raytheon, and Culligan. A description of each site is provided in Table 3-1.
This section identifies existing data, describes additional data collected, and provides a summary of sources by constituent.
EXISTING DATA COLLECTION
Municipal supply water, collection systems, industrial and Facility water quality data was compiled from a number of sources and included the following:
Frick Springs Water Treatment Plant (Frick Springs WTP)
City of Lompoc Water Treatment Plant (City WTP)
VAFB Water Supply
VVCSD Water Supply
City of Lompoc Regional Wastewater Reclamation Facility (Facility)
City of Lompoc Molybdenum Study (Mo Study)
Significant Industrial User data (SIU), excluding VAFB
Table 3-1 provides a description of all the sites with salts data. This table encompasses both existing data and additional data collected. Table 3-2 summarizes the data collected and identifies the general timeline of data collection and the source of data for each site. As shown in Table 3-2, data is available for the salts constituents (TDS, chloride, sodium, sulfate, boron) at the majority of sites. Additional data collected as part of this Salt Management Plan is referred to
2 According to the City of Lompoc Wastewater Ordinance, a “Significant Industrial User (SIU) means any IU that:
a. is subject to federal categorical pretreatment standards; or
b. discharges 25,000 gal/d or more of process wastewater (average annual daily flow); or
c. contributes a process wastestream which makes up five percent (5%) or more of the average dry weather hydraulic or organic loading capacity of the Wastewater Treatment Plant; or
d. has a reasonable potential, in the opinion of the Director, to adversely affect the Wastewater Treatment Plant (e.g., cause Interference, Pass-Through, or endangerment to employees of the Wastewater System).”
Lompoc Salinity Management Study and Plan 3-2 January 2011 as “Salts Study” in the following tables. A summary of existing and additional data collected is provided in Appendix A.
ADDITIONAL DATA COLLECTION
Data gaps were identified once the existing data was compiled and analyzed. Data gaps included:
Boron concentrations in VAFB and VVCSD water supply, industrial user effluent, and
Facility influent;
Chloride concentrations in industrial user effluent; and TDS, chloride, sodium, sulfate, boron concentrations in residential and commercial effluent.
To fill these gaps, wastewater was sampled from the Facility’s influent and effluent, collection system focus areas (including VAFB and VVCSD), residential and commercial areas, and select significant industrial users. A residential site and commercial site were selected to represent and characterize these contributions to the wastewater stream. Table 3-3 summarizes the additional sampling sites and methods that were conducted in May and June of 2010. The locations of sites are provided in Figure 3-1 and a summary of monitoring results is provided in Appendix B.
Lompoc Salinity Management Study and Plan 3-3 January 2011
Table 3-1. Description of Sites with Salts Data
Type Site Site Description
Water Supply
Frick Springs Water Treatment Plant Municipal water supply from Frick Springs; provided to several residences in Miguelito Canyon and Miguelito County Park
VVCSD (Well) VVCSD source water obtained from 3 groundwater wells; samples are taken directly from wells, prior to water treatment processes
VAFB State Water VAFB source water consists of a combination of State Water Project water and groundwater. State water makes up apx. 75% of water supply
VAFB Well Groundwater makes up apx. 25% of VAFB’s water supply
City of Lompoc Water Treatment Plant Effluent Effluent from Water Treatment Plant; water supply is obtained from groundwater wells
Wastewater:
Collection Systems
VAFB trunk sewer Wastewater from VAFB
VVCSD trunk sewer Wastewater from VVCSD
Residential sewer Wastewater from a typical Lompoc residential neighborhood
Commercial sewer Wastewater from a typical Lompoc commercial area
Wastewater:
Industrial
Fagerdala World Foams Plastic and molding manufacturer; periodic process water discharges to sewer system
City of Lompoc Aquatic Center Includes backwash water discharges from the therapy, competition, and activity pools
In-Shape City Includes discharges from spa, pool, and laundry facilities
Raytheon Includes process discharges and domestic waste from restrooms
Culligan Water Conditioning Discharge includes water used to clean water softening tanks and brine water generated through the addition of concentrated brine; facility also serves Buellton
Wastewater:
Facility
Facility Influent Influent to the City of Lompoc Regional Wastewater Reclamation Facility
Facility Effluent (data presented in Section 2) Effluent to the City of Lompoc Regional Wastewater Reclamation Facility
Lompoc Salinity Management Study and Plan 3-4 January 2011
Table 3-2. Summary of Available Data (includes both existing data and additional data collection)
Type Site Constituent(s) Monitored
Data Source TDS Chloride Sodium Sulfate Boron
Water Supply
Frick Spring Water Treatment Plant 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 Frick Springs WTP
VVCSD (Well) 2002 – 2008 2002 – 2008 2002 – 2008 2002 – 2008 2002 – 2008 VVCSD
VAFB State Water 2006 –2009 2006 –2009 2006 –2009 2006 –2009 2007 –2009 VAFB
VAFB Well 2004 –2007 2004 –2007 2004 –2007 2004 –2007 2007 VAFB
City of Lompoc Water Treatment Plant (Well)
2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 City WTP
Wastewater:
Collection Systems
VAFB trunk sewer 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 Facility, Mo Study, Salts Study
VVCSD trunk sewer 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 Facility, Mo Study, Salts Study
Residential sewer 2010 2010 2010 2010 2010 Salts Study
Commercial sewer 2010 2010 2010 2010 2010 Salts Study
Wastewater:
Industrial
Fagerdala World Foams 2008 – 2009 2008 – 2009 2008 – 2009 n/a n/a SIU
City of Lompoc Aquatic Center 2009 – 2010 2009 – 2010 2009 – 2010 2010 2010 SIU, Salts Study
In-Shape City 2008 – 2010 2008 – 2010 2008 – 2010 2010 2010 SIU, Salts Study
Raytheon 2007 – 2010 2007 – 2010 2007 – 2010 2010 2010 SIU, Salts Study
Culligan Water Conditioning 2000 – 2010 2000 – 2010 2000 – 2010 2010 2010 SIU, Salts Study
Wastewater:
Facility
Facility Influent 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 2010 Facility, Mo Study, Salts Study
Facility Effluent (data presented in Section 2)
2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 2000 – 2010 Facility, Mo Study, Salts Study n/a: data not available
Lompoc Salinity Management Study and Plan 3-5 January 2011
Table 3-3. Salts Study Sampling Sites and Monitoring Frequency
Type Site Name Site ID Sampling Method
Months Sampled
Wastewater:
Collection Systems
VAFB trunk sewer VAFB 24-hour
Composite May & June
VVCSD trunk sewer VVCSD 24-hour
Composite May & June
Residential sewer RES 24-hour
Composite May & June
Commercial sewer COM 24-hour
Composite May & June
Wastewater:
Industrial
Aquatic Center - Therapy Pool AQC-TP Grab May & June
Aquatic Center - Activity Pool AQC-AP Grab May & June
Aquatic Center - Competition Pool AQC-CP Grab May & June
In-Shape City - Spa ISC-S Grab May & June
In-Shape City - Laundry ISC-L Grab May & June
In-Shape City - Pool ISC-P Grab May & June
Raytheon RAY Business hour
Composite May & June
Culligan Water Conditioning CUL Business hour
Composite May & June
Wastewater:
Facility*
Facility Influent WW-I 24-hour
Composite April & May
Facility Effluent WW-E 24-hour
Composite April & May
*Monitoring of the Facility effluent and influent occurred in April and May.
Lompoc Salinity Management Study and Plan 3-6 January 2011
Figure 3-1. Additional Data Collection for the Salts Management Plan
Lompoc Salinity Management Study and Plan 3-7 January 2011
SUMMARY BY CONSTITUENT
A mass balance was conducted for TDS, chloride, sodium, sulfate and boron in order to estimate salt contributions to the Facility influent. As illustrated in Figure 3-2, the primary inputs to the Facility include:
municipal water supply (source water) from VVCSD, VAFB, and the City.
residential water softeners. The mass balance assumes that approximately 8% of City of Lompoc residents and 40% of VVCSD residents have water softeners. An example water softener calculation is provided in Appendix C.
industrial activities. Industrial concentrations may include source water contributions in addition to industrial processes.
“other” commercial and residential activities. This encompasses activities that may contribute to salts levels to the Facility influent beyond water supply and water softener discharges. This could include use of detergents by businesses and residents, etc.
It should be emphasized that several assumptions were made with respect to flows and concentrations for the different sources. Therefore, the loading contributions shown in the mass balance tables should be considered useful for planning purposes and identifying potentially significant versus insignificant sources.
Lompoc Salinity Management Study and Plan 3-8 January 2011
Figure 3-2. Flow Chart Illustrating the Major Inputs to the Facility
Lompoc Salinity Management Study and Plan 3-9 January 2011
Total Dissolved Solids (TDS)
A mass balance was conducted to determine primary sources of TDS loads to the Facility influent using available data. As indicated in Table 3-4 and Figure 3-3, the primary contributor is water supply which makes up 88% of the load to the Facility influent. Contributions are further discussed in the sections below.
Water Supply
Water supply is the largest contributor to TDS loads in Facility influent. The City of Lompoc, which obtains its water supply through groundwater wells, makes up more than 68% of the total load to Facility influent. Figure 3-4 provides a breakdown of the contributors to TDS within water supply.
Water Softeners
Water softener use by City and VVCSD residents make up approximately 2% of the Facility influent. VVCSD water softeners make up the majority of this load (Figure 3-5).
Industrial
Cumulatively, industries comprise approximately 7% of the total loading to the Facility influent.
Culligan is the largest contributor, making up 5% of the total load.
Other Activities
Ten percent (10%) of the loading is accounted for by “other” contributions to the Facility influent from residential and businesses activities in VVCSD, and VAFB.
Table 3-4. TDS Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Water Supply - - 22,738 88%
VVCSD, Well 0.5 798 3,357 13%
VAFB, Well 0.2 494 654 3%
VAFB, State Water Project Water 0.5 291 1,156 4%
City of Lompoc, Well [c] 2.5 842 17,571 68%
Residential Water Softeners [a], [e] - - 596 2%
VVCSD, Water Softeners 0.2 305 509 2%
City of Lompoc Water Softeners 0.2 62 87 0.3%
City of Lompoc (Sum of Industrial, Res, Comm) - - 1,919 7%
Industrial [g] - - 1,919 7%
Fagerdala 0.01 3,571 312 1%
Aquatic Center 0.008 1,931 136 0.5%
Raytheon 0.02 953 131 0.5%
Lompoc Salinity Management Study and Plan 3-10 January 2011
Table 3-4. TDS Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Culligan 0.2 1,081 1,315 5%
In-Shape City 0.002 1,297 25 0.1%
Commercial, Other [d], [f] 0.4 - 0 0%
Residential, Other [d], [f] 1.9 - 0 0%
Other - - 2,553 10%
VAFB, Other 0.3 206 1,102 4%
VVCSD, Other 0.6 576 1,471 6%
Total Identified Sources - - 27,806 107%
Facility Influent [b] 3.1 1,014 25,936 -
[a] Estimated that 8% of Lompoc residents and 40% of VVCSD residents have a water softener [b] Wastewater effluent data from Frick Springs community into the Facility not available [c] Water deliveries estimated using 2005 City of Lompoc Urban Water Management Plan. Water deliveries adjusted for losses (e.g. irrigation) per report studying water consumption habits for City of Lompoc (Source:
Heaney et al. "Nature of Residential Water Use and Effectiveness of Conservation Programs”)
[d] 0 loading denotes that the source water is the primary source of this constituent [e] Estimated value. See Appendix C for water softener calculations [f] Flows were estimated using best professional judgment and limited water delivery data [g] Industrial concentrations may include source water contributions in addition to industrial processes
Lompoc Salinity Management Study and Plan 3-11 January 2011
Figure 3-3. Relative Contributions of TDS to Facility Influent
Figure 3-4. Sources of TDS within Water Supply
Figure 3-5. Sources of TDS from Residential Water Softeners
Lompoc Salinity Management Study and Plan 3-12 January 2011
A mass balance was conducted to determine the primary sources of chloride loads to the Facility influent using available data. As indicated in Table 3-5 and Figure 3-6, the largest contributor of chloride loads is water supply.
Water Supply
Water supply makes up almost 70% of the chloride in Facility influent. Of the water supply sources, the City’s supply accounts for 62% of the total water supply contribution to chloride loading (Figure 3-7).
Water Softeners
Water softeners account for approximately 5% of chloride loads to Facility influent. As illustrated in Figure 3-8, VVCSD water softeners make up more than 85% of the water softener loading.
Industrial
Industries contribute less than 10% of chloride to the Facility influent. Culligan makes up the majority of this loading and contributes approximately 6% of the total chloride loading to Facility influent.
Other Activities
Residential and commercial activities in the City, VVCSD and VAFB are accounted as “Other.”
These activities comprise more than 40% of the chloride loading.
Table 3-5. Chloride Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Water Supply - - 3,233 69%
VVCSD, Well 0.5 157 756 16%
VAFB, Well 0.2 103 136 3%
VAFB, State Water Project Water 0.5 87 347 7%
City of Lompoc, Well [c] 2.5 96 1,995 43%
Residential Water Softeners [a], [d] - - 234 5%
VVCSD, Water Softeners 0.2 120 200 4%
City of Lompoc, Water Softeners 0.2 24 34 1%
City of Lompoc(Sum of Industrial, Res, Comm) - - 1,537 33%
Industrial [f] - - 441 9%
Fagerdala 0.01 1033 90 2%
Aquatic Center 0.008 620 44 0.9%
Raytheon 0.02 119 16 0.3%
Lompoc Salinity Management Study and Plan 3-13 January 2011
Table 3-5. Chloride Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Culligan 0.2 234 285 6%
In-Shape City 0.002 287 6 0.1%
Commercial, Other 0.4 79 245 5%
Residential, Other 1.9 53 862 18%
Other - - 1,067 23%
VAFB, Other 0.3 319 804 17%
VVCSD, Other 0.6 20 263 6%
Total Identified Sources - - 6,082 130%
Facility Influent [b] 3.1 183 4,681 -
[a] Estimated that 8% of Lompoc residents and 40% of VVCSD residents have a water softener [b] Wastewater effluent data from Frick Springs community into the Facility not available [c] Water deliveries estimated using 2005 City of Lompoc Urban Water Management Plan. Water deliveries adjusted for losses (e.g. irrigation) per report studying water consumption habits for City of Lompoc (Source:
Heaney et al. "Nature of Residential Water Use and Effectiveness of Conservation Programs”
[d] Estimated value. See Appendix C for water softener calculations [e] Flows were estimated using best professional judgment and limited water delivery data [f] Industrial concentrations may include source water contributions in addition to industrial processes
Figure 3-6. Relative Contributions of Chloride to Facility Influent
Lompoc Salinity Management Study and Plan 3-14 January 2011
Figure 3-7. Sources of Chloride within Water Supply
Figure 3-8. Sources of Chloride from Residential Water Softeners
Lompoc Salinity Management Study and Plan 3-15 January 2011
Sodium
Similar to TDS and chloride, water supply is identified as the largest contributor of sodium to Facility influent. Relative contributions of sodium to Facility influent are provided in Table 3-6 and Figure 3-9.
Water Supply
Water supply is the largest contributor of sodium to Facility influent. The City’s water supply makes up 77% of the total water supply sodium loading (Figure 3-10).
Water Softeners
Water softeners make up approximately 7% of the total sodium loading to the Facility influent.
As indicated in Figure 3-11, VVCSC water softeners comprise 85% of the total water softener sodium load.
Industrial
Industries comprise less than 10% of the total load to the Facility influent. Culligan makes up the majority of the load, contributing 7% of sodium to the total load to the Facility influent.
Other Activities
Other City, VAFB, and VVCSD activities are estimated to contribute approximately a fourth (25%) of the total sodium load to Facility influent.
Table 3-6. Sodium Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Water Supply - - 3,660 75%
VVCSD, Well 0.5 127 535 11%
VAFB, Well 0.2 68 89 2%
VAFB, State Water Project Water 0.5 57 227 5%
City of Lompoc, Well [c] 2.5 135 2,808 57%
Residential Water Softeners [a] - - 361 7%
VVCSD, Water Softeners 0.2 185 309 6%
City of Lompoc, Water Softeners 0.2 37 52 1%
City of Lompoc (Sum of Industrial, Res, Comm) - - 1,031 21%
Industrial [g] - - 474 10%
Fagerdala 0.01 877 77 2%
Aquatic Center 0.008 457 32 0.7%
Raytheon 0.02 239 33 0.7%
Culligan 0.2 270 328 7%
Lompoc Salinity Management Study and Plan 3-16 January 2011
Table 3-6. Sodium Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
In-Shape City 0.002 215 4 0.1%
Commercial, Other [d] [f] 0.4 0 0 0%
Residential, Other [f] 1.9 34 557 11%
Other - - 730 15%
VAFB, Other 0.6 25 329 7%
VVCSD, Other 0.3 159 401 8%
Total Identified Sources - - 5,782 118%
Facility Influent [b] 3.1 191 4,885 -
[a] Estimated that 8% of Lompoc residents and 40% of VVCSD residents have a water softener [b] Wastewater effluent data from Frick Springs community into the Facility not available [c] Water deliveries estimated using 2005 City of Lompoc Urban Water Management Plan. Water deliveries adjusted for losses (e.g. irrigation) per report studying water consumption habits for City of Lompoc (Source:
Heaney et al. "Nature of Residential Water Use and Effectiveness of Conservation Programs”)
[d] 0 loading denotes that the source water is the primary source of this constituent [e] Estimated value. See Appendix C for water softener calculations [f] Flows were estimated using best professional judgment and limited water delivery data [g] Industrial concentrations may include source water contributions in addition to industrial processes
Figure 3-9. Relative Contributions of Sodium to Facility Influent
Lompoc Salinity Management Study and Plan 3-17 January 2011
Figure 3-10. Sources of Sodium within Water Supply
Figure 3-11. Sources of Sodium from Residential Water Softeners
Lompoc Salinity Management Study and Plan 3-18 January 2011
The mass balance indicates that water supply is the primary source of sulfate to Facility influent.
The mass balance is detailed in Table 3-7 and relative contributions are depicted in Figure 3-12.
Water Supply
Nearly all of the sulfate loading can be attributed to water supply. The mass balance estimates that 107% of the loading comes from municipal water sources with 101% coming from the City’s groundwater supply.
Industrial
Industrial sulfate contributions add up to 7% of the total sulfate load. Culligan makes up more than 85% of the total industrial contribution.
Other Activities
Residential and commercial activities conducted in the City, VAFB, and VVCSD contributed close to a quarter (22%) of the sulfate loading. Residential activities in the City comprise the majority of this loading.
Table 3-7. Sulfate Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Water Supply - - 8,947 107%
VVCSD, Well 0.5 157 171 2%
VAFB, Well 0.2 88 117 1%
VAFB, State Water Project Water 0.5 50 198 2%
City of Lompoc, Well [b] 2.5 406 8,462 101%
Residential Water Softeners - - - -
VVCSD, Water Softeners n/a n/a n/a n/a
City of Lompoc, Water Softeners n/a n/a n/a n/a
City of Lompoc (Sum of Industrial, Res, Comm) - - 1,666 7%
Industrial [e] - - 542 7%
Fagerdala 0.01 n/a - -
Aquatic Center 0.008 527 37 0.4%
Raytheon 0.02 460 63 0.8%
Culligan 0.2 355 432 5%
In-Shape City 0.002 532 10 0.1%
Commercial, Other [c] [d] 0.4 - 0 0%
Residential, Other [d] 1.9 69 1,124 13%
Lompoc Salinity Management Study and Plan 3-19 January 2011
Table 3-7. Sulfate Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Other - - 729 9%
VAFB, Other 0.6 19 102 1%
VVCSD, Other 0.3 249 627 8%
Total Identified Sources - - 11,342 136%
Facility Influent [a] 3.1 326 8,338 -
[a] Wastewater effluent data from Frick Springs community into the Facility not available [b] Water deliveries estimated using 2005 City of Lompoc Urban Water Management Plan. Water deliveries adjusted for losses (e.g. irrigation) per report studying water consumption habits for City of Lompoc (Source:
Heaney et al. "Nature of Residential Water Use and Effectiveness of Conservation Programs”)
[c] 0 loading denotes that the source water is the primary source of this constituent [d] Flows were estimated using best professional judgment and limited water delivery data [e] Industrial concentrations may include source water contributions in addition to industrial processes
Figure 3-12. Relative Contributions of Sulfate to Facility Influent
Lompoc Salinity Management Study and Plan 3-20 January 2011
Figure 3-13. Sources of Sulfate within Water Supply
Lompoc Salinity Management Study and Plan 3-21 January 2011
Boron
The largest contributor to boron loading is other activities followed by water supply. Table 3-8 and Figure 3-14 provide a detailed breakdown of contributors to boron in Facility influent.
Water Supply
Unlike the other constituents, water supply is the second highest contributor of boron to Facility influent. Water supply makes up approximately a third of the boron loading. A little less than 25% of the water supply loading can be attributed to the City’s groundwater supply.
Industrial
Industries make up a very small portion of the overall loading. The mass balance estimates that industries contribute 2% to the overall boron load. Culligan comprises the majority of this loading.
Other Activities
The majority of boron loading to Facility influent can be attributed to other activities. Other activities make up approximately 45% of the boron load.
Table 3-8. Boron Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Water Supply - - 5.1 34%
VVCSD, Well 0.5 0.3 1.2 8%
VAFB, Well 0.2 0.1 0.2 1%
VAFB, State Water Project Water 0.5 0.1 0.2 1%
City of Lompoc, Well [b] 2.5 0.2 3.5 23%
Residential Water Softeners - - 0 0%
VVCSD, Water Softeners 0.2 n/a n/a n/a
City of Lompoc, Water Softeners 0.2 n/a n/a n/a
City of Lompoc (Sum of Industrial, Res, Comm) - - 4 28%
Industrial [d] - - 0.4 2%
Fagerdala 0.01 n/a - -
Aquatic Center 0.008 0.3 0.02 0.1%
Raytheon 0.02 0.2 0.02 0.1%
Culligan 0.2 0.3 0.3 2%
In-Shape City 0.002 0.3 0.005 0.03%
Commercial, Other [c] 0.4 0.1 0.3 2%
Residential, Other [c] 1.9 0.04 3.6 24%
Lompoc Salinity Management Study and Plan 3-22 January 2011
Table 3-8. Boron Mass Balance
Source Flow
(MGD)
Conc.
(mg/L)
Loading
(lbs/day)
% of Facility Influent
Other - - 2.9 19%
VAFB, Other 0.3 0.6 1.6 10%
VVCSD, Other 0.6 0.1 1.4 9%
Total Identified Sources - n/a 12.4 81%
Facility Influent [a] 3.1 0.6 15 -
[a] Wastewater effluent data from Frick Springs community into the Facility not available [b] Water deliveries estimated using 2005 City of Lompoc Urban Water Management Plan. Water deliveries adjusted for losses (e.g. irrigation) per report studying water consumption habits for City of Lompoc (Source:
Heaney et al. "Nature of Residential Water Use and Effectiveness of Conservation Programs”)
[c] Flows were estimated using best professional judgment and limited water delivery data [d] Industrial concentrations may include source water contributions in addition to industrial processes
Figure 3-14. Relative Contributions of Boron to Facility Influent
Lompoc Salinity Management Study and Plan 3-23 January 2011
Figure 3-15. Sources of Boron within Water Supply
Figure 3-16. Sources of Boron within Other Activities
Lompoc Salinity Management Study and Plan 3-24 January 2011
Summary of Common Findings
Several conclusions can be drawn across constituents:
As illustrated Table 3-9, water supply is consistently the largest contributor of salt loading to the Facility, with the exception of boron.
Table 3-9. Summary of Mass Balance Findings by Constituent
Source Constituent
TDS Chloride Sodium Sulfate Boron
Water Supply 88% 69% 75% 107% 34%
City, VVCSD, and VAFB Activities
Residential Water Softeners 2% 5% 7% n/a n/a
Industrial 7% 9% 9% 6% 2%
Other Activities 10% 46% 26% 24% 45% n/a: not applicable
“Other Activities” (e.g., undefined contributions from residential and commercial activities) is consistently the second largest contributor of salts to the Facility influent with the exception of boron.
Water softeners in the City make up a small percentage of loading (7% or less).
Industries contribute less than 10% of salts loading.
Lompoc Salinity Management Study and Plan 4-1 January 2011
Section 4
Source Reduction Options This section builds on the previous sections which laid out the reductions needed to meet effluent limits and surface water quality objectives and identified the relative sources to salts loading in Facility influent. A summary of necessary reductions is provided in Table 4-1. As indicated in the previous section, the water supply is estimated to be the most significant source of salts to the Facility followed by other activities, industries, and VVCSD water softeners.
Table 4-1. Estimated % Reductions Needed
Constituent Estimated % Reduction
Needed to Meet Effluent Limit
Estimated % Reduction Needed to Meet Surface Water
Quality Objective
TDS 7% 15%
Chloride 0% 61%
Sodium 0% 54%
Sulfate n/a 43%
Boron n/a 17% n/a: not applicable
Source reduction options that address necessary reductions and the main sources of salts loadings are discussed below.
WATER SUPPLY OPTIONS
Several options that address water supply’s contribution to salts are reviewed below for their applicability and feasibility.
Water Treatment Plant Modifications
City of Lompoc
The current source of drinking water for the City of Lompoc is groundwater that contains high levels of hardness (greater than 700 mg/L). To make this water supply suitable for potable uses the City treats the water using a lime-soda softening process to reduce the hardness to approximately 300 mg/L. The soda-lime process involves addition of chemical salts, most, but not all of which, are precipitated and removed in the process. Thus some additional salt is added to the water supply during treatment. The average TDS concentration in Lompoc final drinking water is approximately 800 mg/L.
Converting water treatment from the soda-lime hardness removal process to reverse osmosis (RO) would reduce both the salts and hardness concentrations in the drinking water. A portion of the water supply could be treated by RO and blended with the remainder to achieve a desired level of salts and hardness in the final product water. The water treatment plant currently produces approximately 5 MGD at an O&M cost of approximately $1.4 million per year, including chemicals and sludge disposal. The resulting cost per million gallon treated is
Lompoc Salinity Management Study and Plan 4-2 January 2011 approximately $767/MG To produce final water with a hardness of 300 mg/L and a TDS of 400 mg/L using RO would require RO treatment of approximately 3.2 MGD. The annual O&M cost for 3.2 MGD of RO treatment would be approximately $1,400/mg or $2.55 million per year. The amortized cost of construction for 3.2 MGD of RO treatment for 20 years at 5% interest would be approximately $1.3 million per year. Thus the total cost for RO water treatment would be approximately $3.85 million/year, which would be approximately 2.75 times the cost of current chemical water treatment.
Another option may be to reduce or eliminate soda-lime water softening process. The disadvantage of this approach may be an increase in water softener installation.
Vandenberg Village Community Service District (VVCSD)
VVCSD’s well water data reflects the quality of the water prior to treatment. Part of VVCSD’s well water treatment includes the addition of sodium hypochlorite as a disinfectant (Personal communication, Martin Damwyk, VVCSD Operations and Maintenance). This may partially account for the contribution of VVCSD’s “other” contribution to chloride and sodium loading.
The hardness of VVCSD’s source water is fairly high at more than 300 mg/L. As a result, it is estimated that between 40 – 60% of VVCSD residents own a water softener. To address the hardness of water supplied to residents, VVCSD recently contracted with Procorp Enterprises LLC (Procorp) to perform a pilot test of Crystalactor (Pellet Reactor) water softening technology on VVCSD’s source water. Pilot testing included two trials: one trial with soda ash as the chemical treatment and the second trial with sodium hydroxide (Procorp Enterprises, 2010).
Table 4-2 summarizes these results of the trials which generally resulted in a decrease in hardness and increase in salts.
Table 4-2. Pilot Test Results
Constituent Soda Ash (Trial 1)
% Change
Sodium Hydroxide (Trial 2)
% Change
Hardness - 73% - 64%
Calcium - 90% - 77%
Manganese - 88% --
Iron - 47% - 27%
TDS + 3% - 5%
Sodium + 42% + 50% --: reduced to non-detectable levels
To determine the overall potential benefit of this technology, the mass balance described in Section 2 was modified to account for a hypothetical decrease in water softener use and changes in TDS and sodium levels in VVCSD’s water supply. In this scenario, water softener use was decreased from 40% to 10%. Tables 4-3 and4-4 provides the results of the mass balance scenarios for TDS and sodium, respectively.
Lompoc Salinity Management Study and Plan 4-3 January 2011
Table 4-3. Projected TDS Levels in Response to Pilot Test Results
Source Current Scenario With Soda Ash
With Sodium Hydroxide
Conc.
(mg/L)
Loading lbs/day Conc.
(mg/L)
Loading lbs/day Conc.
(mg/L)
Loading lbs/day
Water Softener 305 509 76 32 76 32
Well Water 798…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .