LD267060 Kent ISD Dutton Asbestos Survey Report.pdf

PDF 7 MB Posted

Attached to
2026 Abatement and Hazmat Removal, Former Dutton Elementary
Solicitation number
RFP KSD 260000002248 1
Issued by
Michigan

About this file

This is an Asbestos Survey Report prepared by Terracon Consultants, Inc. for the Kent Intermediate School District regarding the former Dutton Elementary School located at 3820 68th Street, Caledonia, Michigan. The survey was conducted on April 1, 2, 3, and 8, 2026, by two Board for Global EHS Credentialing Certified Industrial Hygienists in accordance with USEPA 40 CFR Part 763, Subpart E (AHERA) protocols. The survey was performed in anticipation of future demolition of the approximately 60,000 square-foot building, which consists of a gymnasium, cafeteria, kitchen, library, restrooms, offices, and classrooms. Terracon collected a total of 339 bulk samples from 112 homogeneous areas of suspect asbestos-containing materials (ACMs) and submitted them to Scientific Analytical Institute for analysis by polarized light microscopy (PLM) using EPA Method 600/R-93/116.

The survey identified six homogeneous areas containing asbestos-containing materials: gray mortar associated with ceramic floor tiles in restrooms (0.25% chrysotile, Category II non-friable); gray mortar associated with red ceramic tile in Room 4109 (0.75% chrysotile, Category II non-friable); white interior wall expansion joint caulk in multiple rooms (2% chrysotile, Category II non-friable); gray exterior window frame caulk (2% chrysotile, Category II non-friable); and dark gray exterior wall expansion joint caulk at EIFS (2% chrysotile, Category II non-friable). Additionally, a tan and brown vinyl tile with yellow mastic in the corridor tested positive for asbestos (6% chrysotile tile, 2% chrysotile mastic). Estimated quantities of identified materials range from 2 square feet for caulk to 600 square feet for mortar. The report notes that contractor estimates regarding actual quantities present may vary significantly, particularly if ACMs exist in hidden or inaccessible areas not evaluated during the survey. Per Michigan regulations, notification to the Michigan Department of Licensing and Regulatory Affairs (LARA) must be provided at least 10 days prior to any abatement project exceeding 10 linear feet or 10 square feet.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asbestos Survey Report Former Dutton Elementary School

3820 68th Street | Caledonia, Michigan 49316

May 11, 2026 | Terracon Project Number: LD267060

Prepared for:

Kent Intermediate School District Grand Rapids, Michigan

Prepared by:

Terracon Consultants, Inc.

Grand Rapids, Michigan

400 Ann Street NW Suite 204

Grand Rapids, Michigan 49504 P (616) 226-8180

Terracon.com

Facilities | Environmental | Geotechnical | Materials

May 11, 2026

Kent Intermediate School District 2930 Knapp Street NE Grand Rapids, Michigan 49525

Attn: Mr. Russell Bray P: (616) 447-2444 E: russellbray@kentisd.org

Re: Asbestos Survey Report Former Dutton Elementary School 3820 68th Street Caledonia, Michigan 49316 Terracon Proposal No. LD267060

Dear Mr. Bray:

Terracon Consultants, Inc. (Terracon) is pleased to submit the attached asbestos survey report to Kent Intermediate School District (Client) regarding the former Dutton Elementary School at the above-referenced address. The purpose of this report is to present the results of an asbestos survey, which was performed on April 1, 2, 3, and 8, 2026. The asbestos survey was conducted in general accordance with our proposal number PLD267060, dated March 18, 2026. We understand that this survey was requested for the purpose of future demolition of the former elementary school located at 3820 68th Street, Caledonia, Michigan.

Asbestos-containing materials (ACMs) were identified as a result of this survey. Please refer to the attached report for details. Terracon appreciates the opportunity to provide this service to the Kent Intermediate School District. If you have any questions regarding this report or require additional services, please give us a call.

Sincerely, Terracon Consultants, Inc.

Jeff Fusee, CIH, CSP Joseph A. Tussey, CHMM Project Industrial Hygienist Principal

Former Dutton Elementary School | 3820 68th St., Caledonia, MI May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

TABLE OF CONTENTS

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

2.0 BUILDING DESCRIPTION

3.0 FIELD ACTIVITIES

3.1 Visual Assessment

3.2 Physical Assessment

3.3 Sample Collection

3.4 Sample Analysis

4.0 REGULATORY OVERVIEW

5.0 FINDINGS AND RECOMMENDATIONS

6.0 LIMITATIONS/GENERAL COMMENTS

APPENDIX A IDENTIFIED AND ASSUMED ASBESTOS-CONTAINING MATERIALS BY

HOMOGENEOUS AREA (HA)

APPENDIX B ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

APPENDIX C ASBESTOS ANALYTICAL LABORATORY DATA

APPENDIX D FLOOR PLAN

APPENDIX E PHOTOGRAPHS

APPENDIX F CIH CREDENTIALS

Facilities | Environmental | Geotechnical | Materials 1

ASBESTOS SURVEY REPORT

Former Dutton Elementary School

3820 68th Street Caledonia, Michigan 49316

Terracon Project No. LD267060 May 11, 2026

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) conducted an asbestos survey of the former Dutton Elementary School located at 3820 68th Street in Caledonia, Michigan. The asbestos survey was conducted on April 1, 2, 3, and 8, 2026, by two (2) Board for Global EHS Credentialing Certified Industrial Hygienists (CIH) in general accordance with Terracon’s proposal number PLD267060, dated March 18, 2026. Safely accessible building components were surveyed, and homogeneous areas of suspect accessible asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to inspect accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. Bulk samples from suspect ACM were collected in general accordance with the sampling protocols outlined in United States Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) Part 763, Subpart E, known as the Asbestos Hazard Emergency Response Act (AHERA). Collected bulk samples were delivered to an accredited laboratory for analysis of asbestos content by polarized light microscopy (PLM).

1.1 Project Objective

We understand that this survey was requested for planned demolition of the former Dutton Elementary School building. Asbestos inspections/surveys are required prior to renovation and demolition activities to satisfy requirements of the USEPA 40 CFR Part 61, Subpart M, the National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation and Michigan asbestos regulations.

1.2 Reliance

This report is for the exclusive use of Kent Intermediate School District (Client) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and the Client. Reliance on this report by the Client and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and the agreement between Terracon and the Client. The limitations of liability defined in the agreement is the aggregate limit of Terracon’s liability to the Client.

Former Dutton Elementary School | | 3820 68th St., Caledonia, MI May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials 2

2.0 BUILDING DESCRIPTION

The abandoned, former Dutton Elementary School is approximately 60,000 square feet consisting of a gymnasium, cafeteria, kitchen, library, restrooms, offices, and classrooms.

The original date of construction was unknown to Terracon. The building was reported to have a library/office addition and a gym addition added later after the original construction (construction dates of the additions were also unknown to Terracon). As reference, Appendix D includes a general floor plan diagram (not to scale) of the building.

3.0 FIELD ACTIVITIES

The asbestos survey was conducted by Mr. Jeff Fusee, CIH, CSP (CIH Credential No. 10961 CP) and Mr. Joshua Schroedter, CIH (CIH Credential No. 12641 CP). A copy of their CIH credential is included in Appendix F.

The survey was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86 - AHERA. A summary of survey activities is provided below.

3.1 Visual Assessment

Survey activities were initiated with visual observation of the safely accessible interior and exterior areas of the building to identify homogeneous areas of accessible suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.

3.2 Physical Assessment

A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

3.3 Sample Collection

Based on results of the visual observation, bulk samples from suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release.

Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials 3

The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.

Terracon collected a total of 339 bulk samples from 112 homogeneous areas of suspect ACM. A summary table of samples collected from homogenous areas of suspect ACM is included in Appendix B.

3.4 Sample Analysis

Bulk samples were submitted under chain of custody to Scientific Analytical Institute (SAI) of Greensboro, North Carolina for analysis by PLM via the USEPA Methods 600/R-93/116.

The percentage of asbestos, where applicable, was determined by microscopic visual estimation using PLM. When applicable, the additional point count method (400 points) was utilized for samples identified to contain asbestos by PLM at low concentrations. SAI is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 200664-0.

A summary of results is included with the summary of collected samples in Appendix B.

The laboratory analytical reports are included in Appendix C.

4.0 REGULATORY OVERVIEW

The asbestos National Emission Standards for Hazardous Air Pollutants (NESHAP) regulation (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos-containing material (RACM).

The asbestos NESHAP regulation classifies ACM as either RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials other than Category I non-friable ACM that contain more than 1% asbestos. Category II non-friable ACM generally includes but is not limited to cementitious material such as cement pipes, cement siding, cement panels, glazing, mortar, and grouts.

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials 4

The Michigan Department of Environment, Great Lakes, and Energy (EGLE), Air Quality Division (AQD), enforces the asbestos NESHAP as adopted by 10 CSR 10-6.080. The owner or operator must provide EGLE with written notification at least ten working days prior to the commencement of asbestos abatement activities that will disturb RACM in amounts greater than or equal to 160 square feet, 250 linear feet, or 35 cubic feet.

In Michigan, asbestos regulations are also enforced by the Michigan Department of Licensing and Regulatory Affairs (LARA), Michigan Occupational Safety and Health Administration (MIOSHA). The LARA/MIOSHA Asbestos Program is responsible for the enforcement of most Michigan asbestos regulations. This program has the following six major areas of responsibility: 1) approval of asbestos training courses, 2) accreditation of workers, 3) licensing of asbestos abatement contractors, 4) processing of asbestos abatement project notifications (requires project notification at least 10 days prior to any non-emergency abatement project exceeding 10 linear feet or 10 square feet or both), 5) compliance investigations, and 6) EPA AHERA management plan review.

The U.S. Occupational Safety and Health Administration (OSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work. The standard also specifies requirements for handling materials containing asbestos in concentrations less than or equal to one percent.

5.0 FINDINGS AND RECOMMENDATIONS

Based on the laboratory analytical report, the presence of asbestos was identified in samples collected from the former Dutton Elementary. A summary of identified asbestos-containing materials is included in Appendix A.

An asbestos survey sample summary is included in Appendix B. The laboratory analytical report are included in Appendix C. Photos of identified ACMs are included in Appendix E.

Please note that suspect materials other than those identified during the survey (e.g., materials concealed/hidden in walls; materials not listed in Appendix A and Appendix B) may exist. Should suspect materials other than those which were identified during this survey be uncovered prior to or during demolition activities, those materials should be assumed asbestos-containing until sampling and analysis can confirm or refute their asbestos content.

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials 5

6.0 LIMITATIONS/GENERAL COMMENTS

The asbestos survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the subject building. The information contained in this report is relevant to the dates on which this survey was performed and may not be representative of conditions at a later date. This report has been prepared on behalf of and exclusively for use by Kent Intermediate School District. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding quantities of ACM and any further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.

Facilities | Environmental | Geotechnical | Materials

APPENDIX A

Former Dutton Elementary School

3820 68th Street Caledonia, Michigan 49316

Terracon Project No. LD267060

IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)

HA No. ACM Description Material Location

Percent and Type Asbestos

EPA NESHAP

Classification

Condition Estimated Quantity*

260401-22 Gray Mortar Associated with Blue and White 1”x1” Ceramic Floor Tile

Restroom 3 0.25% Chrysotile by Point

Count

Not Regulated by

EPA NESHAP (<1%

Asbestos by Point Count); However, Regulated by MIOSHA and Federal

OSHA

Good 180 square feet (sf)

260401-24 Gray Mortar Associated with Tan and Yellow 1”x1” Ceramic Floor Tile

Restroom 4 0.50% Chrysotile by Point

Count Good 100 sf

260401-41

Tan with Brown Streaks 9”x9” Vinyl Floor Tile and

Black Mastic (Under Carpet)

Room 4101 Room 4102 Room 4103 Room 4104

6% Chrysotile (Tile) 2% Chrysotile (Mastic)

Category I Non-Friable ACM

Good 4,000 total sf

260401-46 Joint Compound within the Drywall System – Ceiling

Restroom 7 Restroom 8

Mechanical Room (Concealed Above

Non-ACM Acoustical Drop Ceiling Tile in Restrooms)_

0.75% Chrysotile by Point Count (1 Sample Result);

However, Only 1 Sample was Identified with a Joint

Compound Layer;

Therefore, Assumed >1% in the Absence of a 2nd

Joint Compound Layer Sample Result Reported)

RACM Good 600 total sf

260401-53 Gray Mortar Associated with Red 6”x6” Ceramic Tile Floor Tile

Room 4109 0.75% Chrysotile by Point

Count Category II

Non-Friable ACM Good 425 sf

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials 7

*Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document; contractors would be responsible for drawing their own conclusions regarding quantities present. See the appendix documents for a summary of samples collected, laboratory analytical reports and photo examples of the above identified materials.

HA No. ACM Description Material Location

Percent and Type Asbestos

EPA NESHAP

Classification

Condition Estimated Quantity*

260401-55 White Interior Wall

Expansion Joint Caulk

Room 4108 Room 4110A Room 4106

2% Chrysotile Category II

Non-Friable ACM Good 2 sf

260401-61 Gray Exterior Window

Frame Caulk Exterior (At Windows)

2% Chrysotile Category II

Non-Friable ACM Good 25 sf

260401-67 Dark Gray Exterior Wall Expansion Joint Caulk at

EIFS

Exterior (At EFIS) 2% Chrysotile

Category II Non-Friable ACM

Good 50 sf

Facilities | Environmental | Geotechnical | Materials

APPENDIX B

Former Dutton Elementary School

3820 68th Street, Caledonia, Michigan 49316 Terracon Project No. LD267060

ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

Original Building (260401)

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

2’x4” Ceiling Tile

Room 4121

Room 4121

Restroom 1 Restroom 2

4117A 4123B Office 1

Corridor

Ceiling Tile: None Detected

(ND)

02 Room 4117A Ceiling Tile: ND

03 Room 4102 Ceiling Tile: ND

Tan 8”x8” Ceramic Tile with Tan

Grout and Tan Mortar

Room 4121 Room 4121

4117A

Ceramic Tile: ND Grout: ND

02 Room 4118 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Room 4117A Ceramic Tile: ND

Grout: ND Mortar: ND

Gray Undersink Coating

Room 4121 Room 4121

4117A

Undersink Coating: ND

02 Room 4119 Undersink Coating: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

03 Room 4123

Undersink Coating: ND

Gray 4” Cove Base and Yellow Mastic

Room 4121

Room 4121 4117A 4108A

Corridor

Cove Base: ND Mastic: ND

02 Room 4119 Cove Base: ND

Mastic: ND

Corridor Outside

Room 4116 Cove Base: ND

Mastic: ND

Yellow Carpet Glue

Room 4121

Room 4121 4117A

Office 1 Office 2 Office 5

Corridor

Carpet Glue: ND

02 Room 4119 Carpet Glue: ND

Corridor Outside

Room 4116 Carpet Glue: ND

01 White Wall Board Room 4121

Room 4121

Wall Board: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

02 Room 4123

Wall Board: ND

03 Room 4116 Wall Board: ND

Wall Board Brown Glue Pod

Room 4121

Room 4121

Glue Pod: ND

02 Room 4123 Glue Pod: ND

03 Room 4116 Glue Pod: ND

Brown 4” Cove Base and yellow mastic (1) and brown mastic (2)

Room 4120

Room 4120 Room 4110C

Cove Base: ND Mastic 1: ND Mastic 2: ND

02 Room 4120 Cove Base: ND

Mastic: ND

03 Room 4120 Cove Base: ND Mastic 1: ND Mastic 2: ND

2’x4’ Pinholes and Craters Ceiling Tile

Room 4120 Room 4120

Office 1 Corridor

Ceiling Tile: ND

02 Room 4116 Ceiling Tile: ND

03 Office 1 Ceiling Tile: ND

Tan, Brown, and

White 1”x1” Ceramic Tile and tan grout, yellow adhesive, and beige paper

Restroom 2

Restroom 1 Restroom 2

Ceramic Tile: ND Grout: ND

Adhesive: ND Paper: ND

02 Restroom 1

Ceramic Tile: ND Grout: ND

Adhesive: ND Paper: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

03 Restroom 2

Ceramic Tile: ND Grout: ND

Adhesive: ND Paper: ND

Brown 1”x1” Ceramic Tile with tan grout, white adhesive, and gray mortar

Restroom 2

Restroom 1 Restroom 2

Ceramic Tile: ND Grout: ND

Adhesive: ND Mortar: ND

02 Restroom 1

Ceramic Tile: ND Grout: ND

Adhesive: ND Mortar: ND

03 Restroom 2

Ceramic Tile: ND Grout: ND

Adhesive: ND

2’x2’ Rough

Texture Ceiling Tile

Room 4119 Room 4119

Ceiling Tile: ND

02 Room 4117 Ceiling Tile: ND

03 Room 4123 Ceiling Tile: ND

Gray Duct Sealant

Room 4118 Room 4118 4110B

Duct Sealant: ND

02 Room 4117 Duct Sealant: ND

03 Room 4117 Duct Sealant: ND

Black Vibration Dampener

Room 4113 Room 4118

Room 4110B

Vibration Dampener: ND 02 Room 4110B Vibration Dampener: ND 03 Room 4110B Vibration Dampener: ND

Red Fire Caulk

Room 4118 Room 4118

Office 1 Office 2 Office 5 Corridor

Fire Caulk: ND

02 Room 4117 Fire Caulk: ND

03 Office 2 Fire Caulk: ND

16 01 Room 4117B Room 4177B Room 4113J

Cove Base: ND Mastic: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Black 4” Cove

Base and Yellow Mastic

Room 4123A Room 4123A Room 4123B Room 4109B Room 4109C Room 4110B

Corridor

Cove Base: ND Mastic: ND

Corridor Near Main

Entrance Cove Base: ND

Mastic: ND

01 Gray with White and Gray Feather Pattern 12”x12” Vinyl Tile and Yellow Mastic

Room 4117B Room 4177B Room 4113J Room 4123A Room 4123B

4108A 4110B

Tile: ND Mastic: ND

02 Room 4123A Tile: ND

Mastic: ND

03 Room 4108 Tile: ND

Mastic: ND

01 Gray/Blue 4” Cove

Base and Yellow Mastic

Room 4116 Room 4116

Office 1

Cove Base: ND Mastic: ND

02 Room 4114 Cove Base: ND

Mastic: ND

2’x4’ Pinholes

Ceiling Tile

Room 4113 Room 4113

Room 4109B

Ceiling Tile: ND

02 Room 4108 Ceiling Tile: ND

03 Room 4109 Ceiling Tile: ND

2’x4’ Pinholes and

Small Fissures Ceiling Tile

Room 4113 Room 4113

Corridor

Ceiling Tile: ND

Corridor Outside

Room 4108 Ceiling Tile: ND

Corridor Outside

Room 4102 Ceiling Tile: ND

01 Warnock Hersey Metal Fire Door –

Brown Core Material

Room 4123A Room 4113J Room 4123A Room 4108A

Fire Door: ND 02 Room 4113 Fire Door: ND

03 Room 4113 Fire Door: ND

Blue and White 1”x1” Ceramic Floor Tile with Gray Grout and

Gray Mortar

Restroom 3

Restroom 3

Ceramic Tile: ND Grout: ND

Mortar: 0.25% Chrysotile by Point

Count

02 Restroom 3

Ceramic Tile: ND Grout: ND

Mortar: 0.0% by Point Count

03 Restroom 3

Ceramic Tile: ND Grout: ND

Mortar: 0.0% by Point Count

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Light Blue 6”x4” Ceramic Tile with Gray Grout and

Gray Mortar

Restroom 3

Restroom 3

Ceramic Tile: ND Grout: ND Mortar: ND

02 Restroom 3 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Restroom 3 Ceramic Tile: ND

Grout: ND Mortar: ND

Tan and Yellow 1”x1” Ceramic Floor Tile with Gray Grout and

Gray Mortar

Restroom 4

Restroom 4

Ceramic Tile: ND Grout: ND

02 Restroom 4

Ceramic Tile: ND Grout: ND

Mortar: 0.25% Chrysotile by Point

Count

03 Restroom 4

Ceramic Tile: ND Grout: ND

Mortar: 0.50% Chrysotile by Point

Count

Light Tan 6”x4” Ceramic Tile with Gray Grout and

Gray Mortar

Restroom 4

Restroom 4

Ceramic Tile: ND Grout: ND Mortar: ND

02 Restroom 4 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Restroom 4 Ceramic Tile: ND

Grout: ND Mortar: ND

Blue 1”x1” Ceramic Tile with Gray Grout and White Mortar

Restroom 4

Restroom 4

Ceramic Tile: ND Grout: ND Mortar: ND

02 Restroom 4 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Restroom 4 Ceramic Tile: ND

Grout: ND Mortar: ND

01 Gray Mudded Pipe Insulation Fitting

Joints on Fiberglass

Insulated Lines

Restroom 1 Restroom 1 Restroom 2 Room 4108A Room 4108

Office 7 Room 4109

Corridor

Mudded Fitting: ND

02 Room 4108 Mudded Fitting: ND

03 Room 4109 Mudded Fitting: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Drywall (Unfinished, no joint compound)

Office 5 Room 4108

Office 5 Office 7

Room 4105 4109B 4109C

Drywall: ND

02 Room 4105 Drywall: ND

03 Room 4106 Drywall: ND

2’x2’ Pinholes and Crates Ceiling Tile

Office 2 Office 2 Office 5

Ceiling Tile: ND

02 Office 5 Ceiling Tile: ND

03 Office 5 Ceiling Tile: ND

Navy Blue 4” Cove Base with Yellow

Mastic

Office 2 Office 2

Restroom 7 Corridor

Cove Base: ND Mastic: ND

Corridor Outside

Office 1 Cove Base: ND

Mastic: ND

03 Restroom 7 Cove Base: ND

Mastic: ND

Black Window Sill

– 3 Layers (1 – black, 2 - gray, and 3 – brown/white)

Room 4108

Room 4108

Layer 1: ND Layer 2: ND Layer 3: ND

02 Room 4105 Layer 1: ND Layer 2: ND Layer 3: ND

03 Room 4107 Layer 1: ND Layer 2: ND

Dark Gray 4” Cove Base and Yellow

Mastic

Room 4108 Room 4108

Office 5 Room 4101

Cove Base: ND Mastic: ND

02 Room 4106 Cove Base: ND

Mastic: ND

03 Room 4101 Cove Base: ND

Mastic: ND

01 Gray with Green, Red, and Blue Specs 12”x12” Vinyl Tile and Black Mastic

Room 4108

Room 4108

Tile: ND Mastic: ND

02 Room 4108 Tile: ND

Mastic: ND

03 Room 4108 Tile: ND

34 01 Room 4108 Room 4108 Drywall: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Drywall and White Joint Compound

Corridor Joint Compound: ND

02 Room 4108 Drywall: ND

Joint Compound: ND

03 Corridor Drywall: ND

Joint Compound: ND

White 6”x4” Ceramic Tile with

Tan Grout and Whtie Adhesive

Room 4108

Room 4108

Ceramic Tile: ND Grout: ND

Adhesive: ND

02 Room 4108 Ceramic Tile: ND

Grout: ND Adhesive: ND

03 Room 4108 Ceramic Tile: ND

Grout: ND Adhesive: ND

Black Undersink

Coating

Room 4108 Room 4108

Undersink Coating: ND

02 Room 4101 Undersink Coating: ND

03 Room 4105 Undersink Coating: ND

Black 4” Cove

Base and Brown Mastic

Corridor Outside Restroom `

Office 7 Corridor

Cove Base: ND Mastic: ND

Corridor Outside

Room 4110 Cove Base: ND

Mastic: ND

Corridor Outside

Room 4108 Cove Base: ND

Mastic: ND

1’x1’ Paper Ceiling Tile

Room 4101 Room 4101

Ceiling Tile: ND 02 Room 4102 Ceiling Tile: ND 03 Room 4102 Ceiling Tile: ND

1’x1’ Holes Ceiling Tile

Room 4101 Room 4101

Ceiling Tile: ND 02 Room 4102 Ceiling Tile: ND 03 Room 4102 Ceiling Tile: ND

White 4”x4” Ceramic Tile with White Grout and White Adhesive

Room 4101 Room 4101

Ceramic Tile: ND Grout: ND

Adhesive: ND

02 Room 4102 Ceramic Tile: ND

Grout: ND Adhesive: ND

03 Room 4105 Ceramic Tile: ND

Grout: ND Adhesive: ND

01 Yellow Carpet Mastic (top layer), Tan with Brown Streaks 9”x9” Vinyl Tile

Corridor Outside Room 4103 Room 4101

Mastic 1: ND Tile: 6% Chrysotile

Mastic: 2% Chrysotile

02 Room 4101 Mastic 1: ND

Tile: Not Analyzed – 1st

Sample Positive

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

and Black Tile Mastic

Corridor (Outside 4101, 4102, 4103)

Mastic: Not Analyzed – 1st Sample Positive

03 Room 4104

Mastic 1: ND Tile: Not Analyzed – 1st

Sample Positive Mastic: Not Analyzed –

1st Sample Positive

Blue 7”x7” Ceramic Tile with Gray Grout and

Gray Mortar

Restroom 7

Restroom 7

Ceramic Tile: ND Grout: ND Mortar: ND

02 Restroom 7 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Restroom 7 Ceramic Tile: ND

Grout: ND Mortar: ND

2’x2’ Pinholes Ceiling Tile

Restroom 7 Restroom 7 Restroom 8

Ceiling Tile: ND 02 Restroom 8 Ceiling Tile: ND 03 Restroom 8 Ceiling Tile: ND

Maroon 7”x7” Ceramic Tile with Gray Grout and

Gray Mortar

Restroom 8

Restroom 8

Ceramic Tile: ND Grout: ND Mortar: ND

02 Restroom 8 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Restroom 8 Ceramic Tile: ND

Grout: ND Mortar: ND

Maroon 4” Cove Base and Yellow

Mastic

Restroom 8

Restroom 8

Cove Base: ND Mastic: ND

02 Restroom 8 Cove Base: ND

Mastic: ND

03 Restroom 8 Cove Base: ND

Mastic: ND

Painted Drywall

Ceiling and White Joint Compound

Restroom 7 Restroom 7 Restroom 8 Mechanical

Room (Above

Acoustical Drop Ceiling Tile in Restrooms)

Drywall: ND Joint Compound:

0.75%% Chrysotile 02 Restroom 8 Drywall: ND

03 Restroom 8 Drywall: ND

01 Drywall (No Joint Compound)

Between Wood Sheeting

Mechanical Room

Mechanical Room

Drywall: ND 02 Mechanical Room Drywall: ND

03 Mechanical Room Drywall: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Light Gray with Gray Feathering

12”x12” Vinyl Tile and Yellow Mastic

Room 4110

Room 4110 Room 4110B

Tile: ND Mastic: ND

02 Room 4110 Tile: ND

Mastic: ND

03 Room 4110 Tile: ND

Mastic: ND

Yellow, Orange, Purple 12” x 12” Vinyl Tile System and Yellow Mastic

Room 4110

Room 4110

Tile: ND Mastic: ND

02 Room 4110 Tile: ND

Mastic: ND

03 Room 4110 Tile: ND

Mastic: ND

Ceiling Tile Brown Glue Pod

Room 4110

Room 4110

Ceiling Tile: ND Glue Pod: ND

02 Room 4110 Ceiling Tile: ND Glue Pod: ND

03 Room 4110 Ceiling Tile: ND Glue Pod: ND

Tan/White 2’x2’ Fiber Board

Room 4110 Room 4110

Fiberboard: ND 02 Room 4110 Fiberboard: ND 03 Room 4110 Fiberboard: ND

Red 6”x6” Ceramic Floor Tile with Gray

Grout and White Mortar

Room 4109

Room 4109

Ceramic Tile: ND Grout: ND

Mortar: 0.75% Chrysotile by Point

Count

02 Room 4109

Ceramic Tile: ND Grout: ND

Mortar: 0.25% Chrysotile

03 Room 4109

Ceramic Tile: ND Grout: ND

Mortar: 0.25% Chrysotile

Hard Layered Plaster (White Skim Coat and Gray Plaster)

Room 4109

Room 4109

Skim Coat: ND Plaster: ND

02 Room 4109 Skim Coat: ND

Plaster: ND

03 Room 4109 Skim Coat: ND

Plaster: ND

01 White Building Caulk (Interior Wall Expansion

Joint Caulk)

Room 4108 Room 4108

Room 4110A Room 4106

Caulk: ND 02 Room 4110A Caulk: ND

03 Room 4106 Caulk: 2% Chrysotile

01 Wood Panel

Warnock Hersey Office 4

Office 4 Fire Door: ND

02 Office 4 Fire Door: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Fire Door – White

Core Material Office 4 Fire Door: ND

Brown 1”x1” Ceramic Tile with Gray Grout and Tan Adhesive

Corridor by Main Entry

Corridor

Ceramic Tile: ND Grout: ND

Adhesive: ND

Corridor by Main

Entry

Ceramic Tile: ND Grout: ND

Adhesive: ND

Corridor by Main

Entry

Ceramic Tile: ND Grout: ND

Adhesive: ND

Tan 2”x2” Ceramic Tile with Tan

Grout and Gray Mortar

Corridor by Main Entry

Corridor by Main Entry Corridor by

Main Entry

Ceramic Tile: ND Grout: ND

Adhesive: ND

Corridor by Main

Entry

Ceramic Tile: ND Grout: ND Mortar: ND

Corridor by Main

Entry

Ceramic Tile: ND Grout: ND Mortar: ND

Floor Leveling Compound (2

Layers: 1 – White and 2 – Gray)

Corridor Outside Room 4119

Corridor

Leveling 1: ND Leveling 2: ND

Corridor Outside

Room 4119 Leveling 1: ND Leveling 2: ND

Corridor Outside

Room 4119 Leveling 1: ND Leveling 2: ND

Gray/Red EFIS

Exterior, Outside Room 4108

Exterior

EFIS: ND

Exterior, Outside

Room 4103

EFIS: ND

Exterior, Outside

Room 4107

EFIS: ND

Gray Window Frame Caulk

(Exterior)

Exterior, Outside Room 4108

Exterior (On Windows)

Caulk: ND

Exterior, Outside

Room 4116 Caulk: 2%

Exterior, Outside

Room 4117

Caulk: Not Analyzed – Previous Sample

Positive

Roofing System (2

Felt on Foam Layers: 1 –

Brown/Yellow and 2 – Yellow/Gray)

North Roof, Middle

Exterior

Felt on Foam 1: ND Felt on Foam 2: ND

North Roof, North

Side Felt on Foam 1: ND Felt on Foam 2: ND

North Roof, West

Side Felt on Foam 1: ND Felt on Foam 2: ND

04 North Roof, East Felt on Foam 1: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Felt on Foam 2: ND

Gray/Yellow Roofing System

South Roof, Middle

Exterior

Roof: ND

02 South Roof, West Roof: ND

South Roof, Northwest

Roof: ND

04 Gym Roof Roof: ND

Black Roof Tar Patch

South Roof, West Roof Systems

(Exterior)

Roof Tar: ND 02 Middle, East Roof Tar: ND 03 North Roof, West Roof Tar: ND

Black Roof Caulk South Roof, West

Roof Systems (Exterior)

Roof Caulk: ND 02 Cafeteria Roof Roof Caulk: ND 03 North Roof, West Roof Caulk: ND

Gray Roof Caulk

North Roof, East

Roof Systems (Exterior)

Roof Caulk: ND

North Roof, Skylight Roof Caulk: ND

Cafeteria Roof, North Roof Caulk: ND

Dark Gray Wall Expansion Joint Caulk (Exterior) at EIFS

Exterior, SW Side

Exterior (at EFIS)

Caulk: ND

Exterior, South

Side Caulk: ND

Exterior, North

Side Caulk: 2% Chrysotile

White Building Caulk (Exterior)

Exterior, Outside Room 4322

Exterior

Caulk: ND

Exterior, Outside

Room 4323 Caulk: ND

Exterior, Outside

Room 4323 Caulk: ND

HA = Homogeneous Area ND = None Detected Bold indicates ACM

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

Library/Office Addition (260402)

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Drywall and White Joint Compound

Room 4111

Room 4111 Room 4322

Drywall: None Detected

(ND)

Joint Compound: ND

02 Room 4111 Drywall: ND

Joint Compound: ND

03 Room 4322 Drywall: ND

Joint Compound: ND

Fiberglass Panel Beige Glue Pod

Room 4111 Room 4111

Glue Pod: ND 02 Room 4111 Glue Pod: ND 03 Room 4111 Glue Pod: ND

Blue 4” Cove Base and Beige Mastic

Room 4111 Room 4111 Room 4111A Room 4111B Room 4111C

Cove Base: ND Mastic: ND

02 Room 4111 Cove Base: ND

Mastic: ND

03 Room 4111 Cove Base: ND

Mastic: ND

Clear Carpet Glue

Room 4111 Room 4111 Room 4111A Room 4111C Room 4320 Room 4322 Room 4323

Office Corridor

Carpet Glue: ND

02 Room 4320 Carpet Glue: ND

03 Room 4322 Carpet Padding: ND

Black Vibration Dampener

Room 4111A Room 4111A Room 4111B

Vibration Dampener: ND 02 Room 4111B Vibration Dampener: ND 03 Room 4111B Vibration Dampener: ND

Red Fire Caulk

Room 4111B Room 4111A Room 4111B Room 4320 Room 4320A Room 4322 Room 4323

Office Corridor Restroom 5 Restroom 6

Office 6

Fire Caulk: ND

02 Room 4111A Fire Caulk: ND

03 Office Corridor Fire Caulk: ND

Gray Undersink Coating

Room 4111C Room 4111C

Undersink Coating: ND 02 Room 4111C Undersink Coating: ND 03 Room 4111C Undersink Coating: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Large and Small Pinholes 2’x2’

Ceiling Tile

Room 4111 Room 4111 Room 4111C Room 4320 Room 4320A Room 4322 Room 4323

Office Corridor Restroom 5 Restroom 6

Office 6

Ceiling Tile: ND

02 Room 4320 Ceiling Tile: ND

03 Office 6 Ceiling Tile: ND

01 Gray with red, White, and Blue Specs 12”x12” Vinyl Tile and

Tan/Yellow Mastic

Room 4320A Room 4320A Office Corridor

Restroom 5 Restroom 6

Office 6

Vinyl Tile: ND Mastic: ND

02 Office 6 Vinyl Tile: ND

Mastic: ND

03 Office Corridor Vinyl Tile: ND

Mastic: ND

Gray 4” Cove Base and Beige Mastic

Room 4320A Room 4320 Room 4320A Room 4322 Room 4323

Office Corridor Restroom 5 Restroom 6

Office 6

Cove Base: ND Mastic: ND

02 Restroom 6 Cove Base: ND

Mastic: ND

03 Room 4322 Cove Base: ND

Mastic: ND

01 Beige/Gray Mudded Pipe

Fitting Insulation on Fiberglass

Insulated Water Lines

Room 4320 Room 4320 Room 4320A Restroom 5 Restroom 6

Fitting: ND

02 Room 4320A Fitting: ND

03 Restroom 6 Fitting: ND

White Marble Window Sill

Room 4320 Room 4320 Room 4322 Room 4323

Sill: ND 02 Room 4322 Sill: ND 03 Room 4323 Sill: ND

01 Beige/Gray

Mudded Roof Drain Insulation

Room 4320 Room 4320

Fitting: ND 02 Room 4320 Fitting: ND 03 Room 4320 Fitting: ND

01 Roof Deck Drywall

Board (No Joint Compound)

Room 4320 Room 4320 Room 4320A

Office Corridor

Drywall: ND 02 Office 6 Drywall: ND 03 Office Corridor Drywall: ND

01 Warnock Hersey Wood Panel Fire

Door – White/Gold Core Material

Room 4320A Room 4320 Room 4320A Room 4322 Room 4323

Fire Door: ND

02 Room 4322 Fire Door: ND

03 Room 4320 Fire Door: ND

01 Gray Hard Duct

Sealant Room 4111C Room 4111C

Restroom 5 Duct Sealant: ND

02 Room 4111C Duct Sealant: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

03 Room 4111C Restroom 6 Duct Sealant: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

Gym Addition (260408)

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

2’x2’ Rough Texture Ceiling

Tile

Room 4126

Room 4126 Room 4127 Room 4136

Ceiling Tile: None Detected

(ND)

02 Room 4127 Ceiling Tile: ND

03 Room 4135 Ceiling Tile: ND

Gray 4” Cove Base and Beige Mastic

Room 4126

Room 4126 Room 4127 Room 4128 Room 4129 Room 4130 Room 4131 Room 4132 Room 4133

South Corridor Room 4134 Room 4135 Room 4136

Locker Room Custodial Closet 2

North Corridor

Cove Base: ND Mastic: ND

02 Room 4131 Cove Base: ND

Mastic: ND

Corridor Outside

Room 4135 Cove Base: ND

Mastic: ND

Tan 4”x4” Ceramic Tile with Gray

Grout and Gray Mortar

Room 4126

Room 4126 Room 4128 Room 4129 Room 4130 Room 4131 Room 4132 Room 4133 Room 4134 Room 4135 Room 4136

Ceramic Tile: ND Grout: ND

02 Room 4130 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Room 4134 Ceramic Tile: ND

Grout: ND Mortar: ND

04 01 Yellow Carpet Glue Room 4126

Room 4126 Room 4127 Room 4128 Room 4129

Carpet Glue: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

02 Room 4131

Room 4130 Room 4131 Room 4132 Room 4133

South Corridor Room 4134 Room 4135 Room 4136

Custodial Closet 2 Room 4138

North Corridor

Carpet Glue: ND

03 Room 4135 Carpet Glue: ND

Large and Small Pinholes 2’x4’

Ceiling Tile

Corridor Outside Room 4126

Room 4128 Room 4129 Room 4130 Room 4131 Room 4132 Room 4133 Room 4134

Custodial Closet 2 North Corridor

Ceiling Tile: ND

02 Room 4131 Ceiling Tile: ND

Corridor Outside

Room 4134 Ceiling Tile: ND

White/Gray Wallboard and

Yellow Glue Pod (Mastic)

Room 4128 Room 4128 Room 4129 Room 4130 Room 4131 Room 4132 Room 4133 Room 4134 Room 4135 Room 4136

Wall Board: ND Mastic: ND

02 Room 4131 Wall Board: ND

Mastic: ND

03 Room 4134 Wall Board: ND

Mastic: ND

Black Undersink Coating

Room 4128 Room 4128 Room 4129 Room 4130 Room 4131 Room 4132 Room 4133 Room 4134 Room 4135 Room 4136

Undersink Coating: ND

02 Room 4130 Undersink Coating: ND

03 Room 4136 Undersink Coating: ND

Tan 4”x4” Ceramic

Tile with Gray Grout and Gray

Mortar

South Corridor Vestibule

South Corridor North Corridor

Coat Room

Ceramic Tile: ND Grout: ND Mortar: ND

North Corridor

Vestibule Ceramic Tile: ND

Grout: ND

Coat Room between Rooms 4135 and 4136

Ceramic Tile: ND Grout: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

Maroon 4” Cove Base and Tan

Mastic

Staff Restroom Staff Restroom

Girls Restroom 1 Girls Restroom 2

Cove Base: ND Mastic: ND

02 Girls Restroom 1 Cove Base: ND

Mastic: ND

03 Girls Restroom 2 Cove Base: ND

Mastic: ND

01 Maroon 6”x6” Ceramic Tile with Gray Grout (Same Gray Mortar as HA

13)

Staff Restroom Staff Restroom

Girls Restroom 1 Girls Restroom 2

Ceramic Tile: ND Grout: ND

02 Girls Restroom 1 Ceramic Tile: ND

Grout: ND

03 Girls Restroom 2 Ceramic Tile: ND

Grout: ND

Blue 4” Cove Base and Tan Mastic

Boys Restroom 1

Boys Restroom 1 Boys Restroom 2

Cove Base: ND Mastic: ND

02 Boys Restroom 1 Cove Base: ND

Mastic: ND

03 Boys Restroom 2 Cove Base: ND

Mastic: ND

Blue 6”x6” Ceramic Tile with Gray Grout and

Gray Mortar

Boys Restroom 1

Boys Restroom 1 Boys Restroom 2

Ceramic Tile: ND Grout: ND Mortar: ND

02 Boys Restroom 1 Ceramic Tile: ND

Grout: ND Mortar: ND

03 Boys Restroom 2 Ceramic Tile: ND

Grout: ND Mortar: ND

01 2’x4’ Large and Small Pinholes, Smooth Surface

Ceiling Tile

Girls Restroom 1 Girls Restroom 1 Girls Restroom 2 Boys Restroom 1

Ceiling Tile: ND

02 Boys Restroom 1 Ceiling Tile: ND

03 Girls Restroom 2 Ceiling Tile: ND

Tan Feathered

Pattern 12”x12” Vinyl Tile and Black Mastic

Custodial Closet 1 Custodial Closet 1

Room 4135 Room 4136 Room 4139

Floor Tile: ND Mastic: ND

02 Room 4135 Floor Tile: ND

Mastic: ND

03 Room 4136 Floor Tile: ND

Mastic: ND

Brown 4” Cove Base and Beige

Mastic

Custodial Closet 1 Custodial Closet 1

Room 4135 Room 4136 Room 4139

Cove Base: ND Mastic: ND

02 Room 4135 Cove Base: ND

Mastic: ND

03 Room 4136 Cove Base: ND

Mastic: ND

18 01 Red Fire Caulk Custodial Closet 1 Custodial Closet 1

South Corridor Fire Caulk: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

South Corridor Outside Room

Fire Caulk: ND

South Corridor

Outside Custodial Closet 1

Fire Caulk: ND

Dark Brown 4” Cove Base and Yellow Mastic

Room 4136A Room 4135 Room 4135A Room 4136A Room 4136

Cove Base: ND Mastic: ND

02 Room 4136A Cove Base: ND

Mastic: ND

03 Room 4136 Cove Base: ND

Mastic: ND

Tan 12”x12” Ceramic Tile with

Brown Grout, Gray Mortar, and Black

Mastic

Room 4136A

Room 4135 Room 4135A Room 4136A Room 4136

Ceramic Tile: ND Grout: ND Mortar: ND Mastic: ND

02 Room 4136A

Ceramic Tile: ND Grout: ND Mortar: ND Mastic: ND

03 Room 4135A

Ceramic Tile: ND Grout: ND Mortar: ND Mastic: ND

Gray 6”x6”

Ceramic Tile with Gray Grout and

Gray Mortar (Same Gray

Mortar as HA 2, 9, 11, 13, and 20)

Locker Room

Locker Room

Ceramic Tile: ND Grout: ND

Gray Mortar: ND

02 Locker Room Ceramic Tile: ND

Grout: ND

03 Locker Room Ceramic Tile: ND

Grout: ND

Black Angled Cove Base and Yellow

Mastic

Room 4139

Room 4139

Cove Base: ND Mastic: ND

02 Room 4139 Cove Base: ND

Mastic: ND

03 Room 4139 Cove Base: ND

23 01 Room 4138 Room 4138 Vibration Dampener: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% / Type of Asbestos)HA #

SEQ.

02 Black Vibration

Dampener Room 4138 Room 4139 Vibration Dampener: ND

03 Room 4138 Vibration Dampener: ND

White/Gray Duct Sealant

Room 4138 Room 4138 Room 4139

Duct Sealant: ND 02 Room 4138 Duct Sealant: ND 03 Room 4138 Duct Sealant: ND

Gray Tectum Board

Room 4138 Room 4138 Room 4139

Tectum Board: ND 02 Room 4138 Tectum Board: ND 03 Room 4138 Tectum Board: ND

Yellow Backsplash Adhesive

Room 4130 Room 4128 Room 4129 Room 4130 Room 4131 Room 4132 Room 4133 Room 4134 Room 4135 Room 4136

Adhesive: ND

02 Room 4132 Adhesive: ND

03 Room 4134 Adhesive: ND

Hard Layered Plaster (White Finish Coat and Gray Base Coat)

South Corridor Near Room 4127

South Corridor Exterior

Finish: ND Base: ND

South Corridor

Near Room 4127 Finish: ND Base: ND

South Corridor

Near Room 4127 Finish: ND Base: ND

Exterior

(Outside Room 4108)

Finish: ND Base: ND

White Perlite Block Filler Insulation

Room 4114 Girls Restroom 1

Room 4133 Room 4132 Room 4131 Room 4130 Room 4129 Room 4128 Room 4126 Room 4139

Perlite: ND

02 Room 4118 Perlite: ND

03 Room 4126 Perlite: ND

04 Room 4139 Perlite: ND

May 11, 2026 | Terracon Project No. LD267060

Facilities | Environmental | Geotechnical | Materials

APPENDIX C

ASBESTOS ANALYTICAL LABORATORY DATA

Bulk Asbestos Analysis By Polarized Light Microscopy EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10106268Customer: Terracon 400 Ann St. NW Suite 204 Grand Rapids, MI 49504

Analysis:

Date Received:

Jeff Fusee

PLM

04/16/2026

Project: LD267060 Date Reported: 04/23/2026

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

260401-01-01

10106268_0001

2'x4' Ceiling tile

None Detected 35% 35%

Cellulose Mineral Wool

30% Other

Fibrous

Teased

White

Homogeneous

260401-01-02

10106268_0002

2'x4' Ceiling tile

None Detected 35% 35%

Cellulose Mineral Wool

30% Other

Fibrous

Teased

White

Homogeneous

260401-01-03

10106268_0003

2'x4' Ceiling tile

None Detected 35% 35%

Mineral Wool Cellulose

30% Other

Fibrous

Teased

White

Homogeneous

260401-02-01 - A

10106268_0004

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Beige

Homogeneous ceramic tile

260401-02-01 - B

10106268_0208

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Tan

Homogeneous grout, no mortar

260401-02-02 - A

10106268_0005

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Beige

Homogeneous ceramic tile

260401-02-02 - B

10106268_0209

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Tan

Homogeneous grout

260401-02-02 - C

10106268_0210

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Tan

Homogeneous mortar

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Charmel Dozier (360)

Analyst Approved Signatory

Page 1 of 46P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10106268Customer: Terracon 400 Ann St. NW Suite 204 Grand Rapids, MI 49504

Analysis:

Date Received:

Jeff Fusee

PLM

04/16/2026

Project: LD267060 Date Reported: 04/23/2026

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

260401-02-03 - A

10106268_0006

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Beige

Homogeneous ceramic tile

260401-02-03 - B

10106268_0211

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Tan

Homogeneous grout

260401-02-03 - C

10106268_0212

8"x8" Ceramic tile

None Detected 100% Other

Non-Fibrous

Crushed

Tan

Homogeneous mortar

260401-03-01

10106268_0007

Undersink coating

None Detected 5% Cellulose 95% Other

Non-Fibrous

Dissolved

White

Homogeneous

260401-03-02

10106268_0008

Undersink coating

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous

260401-03-03

10106268_0009

Undersink coating

None Detected 5% Cellulose 95% Other

Non-Fibrous

Dissolved

White

Homogeneous

260401-04-01 - A

10106268_0010

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous cove base

260401-04-01 - B

10106268_0213

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Charmel Dozier (360)

Page 2 of 46P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10106268Customer: Terracon 400 Ann St. NW Suite 204 Grand Rapids, MI 49504

Analysis:

Date Received:

Jeff Fusee

PLM

04/16/2026

Project: LD267060 Date Reported: 04/23/2026

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

260401-04-02 - A

10106268_0011

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous cove base

260401-04-02 - B

10106268_0214

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

260401-04-03 - A

10106268_0012

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Gray

Homogeneous cove base

260401-04-03 - B

10106268_0215

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic

260401-05-01

10106268_0013

Carpet glue

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous

260401-05-02

10106268_0014

Carpet glue

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous

260401-05-03

10106268_0015

Carpet glue

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous

260401-06-01

10106268_0016

Wall board

None Detected 50% 25%

Mineral Wool Cellulose

25% Other

Fibrous

Teased

White

Homogeneous

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.

Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Charmel Dozier (360)

Page 3 of 46P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888

EPA Method: 600/R-93/116 and

40 CFR, Part 763, Subpart E, App.E

Lab Order ID:Attn: 10106268Customer: Terracon 400 Ann St. NW Suite 204 Grand Rapids, MI 49504

Analysis:

Date Received:

Jeff Fusee

PLM

04/16/2026

Project: LD267060 Date Reported: 04/23/2026

Sample ID

Lab Sample ID

Description

Lab Notes Asbestos

Fibrous Components

Non-Fibrous Components Treatment

Attributes

260401-06-02

10106268_0017

Wall board

None Detected 50% 25%

Mineral Wool Cellulose

25% Other

Fibrous

Teased

White

Homogeneous

260401-06-03

10106268_0018

Wall board

None Detected 50% 25%

Mineral Wool Cellulose

25% Other

Fibrous

Teased

White

Homogeneous

260401-07-01

10106268_0019

Glue pod

None Detected 100% Other

Non-Fibrous

Dissolved

Brown

Homogeneous

260401-07-02

10106268_0020

Glue pod

None Detected 100% Other

Non-Fibrous

Dissolved

Brown

Homogeneous

260401-07-03

10106268_0021

Glue pod

None Detected 100% Other

Non-Fibrous

Dissolved

Brown

Homogeneous

260401-08-01 - A

10106268_0022

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Brown

Homogeneous cove base

260401-08-01 - B

10106268_0216

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Yellow

Homogeneous mastic 1

260401-08-01 - C

10106268_0217

4" Cove base

None Detected 100% Other

Non-Fibrous

Dissolved

Brown

Homogeneous mastic 2

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request.