Larger-Volume_NaOCl_Crocks_Storage_Buildings_Attachment_E.pdf
PDF 655 KB Posted
- Solicitation number
- 250033
- Issued by
- Pima County, Tucson City, Arizona
About this file
This document is an attachment (Attachment A) from the City of Tucson and Tucson Water, detailing specifications for larger-volume sodium-hypochlorite (NaOCl) storage buildings. The City of Tucson seeks to establish a contract with a supplier to provide 7'W x 7'L storage buildings designed specifically for safely housing and managing larger chemical containers. The buildings must meet precise dimensional requirements, including a maximum height of 84", a foundation and structure width of 78" x 78", and a door width of 48" with a maximum height of 74".
The storage buildings must be constructed from fiberglass or wood siding capable of withstanding continuous exposure to sodium hypochlorite and direct sunlight. Specific design requirements include white or light-colored exterior, metal or fiberglass roof with a slope not exceeding 4/12 pitch, two 16" x 8" vents on side walls, linear roof ridge ventilation, and an open floor design of 49 sq ft to accommodate potential product overflow. Additional specifications mandate that all materials must withstand exposure to corrosive airborne materials for a minimum of 5 years, with electrical conduit anchored externally and a 2" circular hole for pump cord accommodation. No insulation is required by the vendor.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A
Larger-Volume NaOCl Crocks – Storage Buildings (Attachment E)
1. H1: Bldg height: 84” max
2. W1: Foundation width: 78” x78”
3. W2: Structure width: 78” x 78”
4. W3: Door width: 48” max
5. H2: Door height: 74” max
6. Must have two 16” x 8” vents on the left and right wall.
The City of Tucson intends to establish a contract with a supplier to provide 7'W x 7'L storage buildings that accommodate larger-volume sodium-hypochlorite crocks. The buildings should provide adequate ventilation and allow Tucson Water staff to safely and comfortably work with larger chemical containers.
Building
• Size: 78 “ W X 78” L maximum dimensions to match concrete foundation.
• Material: Fiberglass or wood siding. Must be able to withstand 24/7 exposure to NaOCl and direct sunlight.
Door Size
• 4’ W X 6’ H
• Left or right side hinge must be optional based on location.
• Rain guard over door. (not shown)
Color Selection
• White or light-colored options
Roof Design
• Metal or fiberglass
• Slope not to exceed 4/12 pitch
• Surface Area not to exceed 60 sq ft.
Ventilation
• Two 16” W x 8” H vents on the bottom of the left and right side walls. (Not to exceed 20” x 10” ).
• Linear roof ridge ventilation must cross the entire roof.
Floor
• 49 sq ft (max) open-floor design required to accommodate product overflow.
Miscellaneous
• Exposed nails or screws shall be clipped to avoid corrosion.
• Electrical conduit must be anchored to the exterior of the building for pump equipment.
• A 2” circular hole must be drilled through the side to accommodate the pump cord.
• No insulation is required by the vendor.
• All materials used must be able to withstand exposure to airborne corrosive materials for a minimum of 5+ years.