This document is a technical specification for storage buildings, issued by the City of Tucson Water Department in Arizona, detailing requirements for storage buildings designed to house larger-volume sodium hypochlorite (NaOCl) chemical crocks. The City intends to establish a contract with a supplier to provide standardized storage buildings that measure 78" x 78" with a maximum height of 8'6", featuring specific design parameters such as fiberglass or wood siding, metal or fiberglass roofing with a slope not exceeding 4/12 pitch, and a surface area not surpassing 60 square feet.
The storage buildings must include critical functional specifications, including two 16" x 8" wall vents, linear roof ridge ventilation, a 49 square foot open floor design, a 4' wide by 6' high door with optional side hinging, and provisions for electrical conduit and pump cord accommodation. Materials must be capable of withstanding continuous exposure to NaOCl and direct sunlight for a minimum of 5 years, with color options limited to white or light tones. The buildings will be deployed at well sites, boosters, and reservoirs where standard storage solutions are insufficient, with the primary goal of enabling Tucson Water staff to safely and comfortably manage larger chemical containers.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Larger-Volume NaOCl Crocks – Storage Buildings (Attachment A) The City of Tucson intends to establish a contract with a supplier to provide 7'W x 7'L storage buildings that accommodate larger-volume sodium-hypochlorite crocks. The buildings should provide adequate ventilation and allow Tucson Water staff to safely and comfortably work with larger chemical containers.
Attachment A
1. H1: Bldg height: 8’6” max
2. W1: Foundation width: 78” x78”Building
· Size: 78 “ W X 78” L maximum dimensions to match concrete foundation.
· Material: Fiberglass or wood siding. Must be able to withstand 24/7 exposure to NaOCl and direct sunlight.
Door Size
· 4’ W X 6’ H
· Left or right side hinge must be optional based on location.
· Rain guard over door. (not shown)
Color Selection
· White or light-colored options Roof Design
· Metal or fiberglass
· Slope not to exceed 4/12 pitch
· Surface Area not to exceed 60 sq ft.
· Roof vent required
3. W2: Structure width: 78” x 78”H1
4. W3: Door width: 48” max
5. H2: Door height: 74” maxH2 Ventilation
· Two 16” W x 8” H vents on the bottom of the left and right side walls. (Not to exceed 20” x 10” ).
· Linear roof ridge ventilation must cross the entire roof.
Floor
· 49 sq ft (max) open-floor design required to accommodate product overflow.
Miscellaneous
· Exposed nails or screws shall be clipped to avoid corrosion.
· Electrical conduit must be anchored to the exterior of the building for pump equipment.
· A 2” circular hole must be drilled through the side to accommodate the pump cord.
· No insulation is required by the vendor.
· All materials used must be able to withstand exposure to airborne corrosive materials for a minimum of 5+ years.
6. V1/V2: Must have two 16” x 8” vents on the left and right wall.*The buildings shown in the pictures are used for illustration purposed only and are not intended to prevent any vendor from providing a storage building that meets the required dimensions.
V1 V2 W2 W1 W3 image2.jpeg image3.jpg image1.png