Jefferson MG Site - 1800T Salt Storage Building Drawings_100 CD_04-15-26.pdf
PDF 6 MB Posted
- Solicitation number
- 645-RFP-3022-2027
- Issued by
- Taylor County, Alburnett City, Iowa
About this file
This document consists of architectural construction drawings for a salt storage building project located at 610 N Pinet Street, Jefferson, Iowa 50129, prepared by the Iowa Department of Transportation's Resources & Acquisitions Bureau in collaboration with Shive Hattery engineering firm. The project involves construction of a new 7,200 square-foot salt storage and 50/50 mix building with two primary storage compartments: a 1,500-ton salt storage section measuring 5,040 square feet and a 300-ton 50/50 mix storage section measuring 2,160 square feet. The drawings detail floor plans, exterior elevations, building sections, and construction details specifying precast concrete T-wall construction, metal pole-frame building components, fabric door systems, and engineered concrete slabs with reinforcement. Site preparation requires excavation and compacted granular fill to meet frost-susceptible soil conditions, with minimum 6.5-inch reinforced concrete slabs and precast T-wall foundations designed for lateral loads of 87 pounds per cubic foot for salt storage and 130 pounds per cubic foot for 50/50 material. The project includes bollard safety barriers, downspout and drainage systems, translucent wall panels for natural lighting, and overhead accordion fabric doors on both storage compartments.
The drawings, dated April 15, 2026, were prepared under project number BG-5J25 (000)--80-37 in Greene County and are sealed by licensed architect Steve A. Trost with license renewal through June 30, 2027. Construction specifications incorporate Iowa Department of Transportation standards and the 2024 International Building Code as adopted by Iowa, with additional compliance required for the 2024 International Fire Code, 2012 International Energy Conservation Code, 2012 NFPA 101 Life Safety Code, Americans with Disabilities Act standards, and other applicable Iowa administrative rules. The precast concrete T-walls must be designed by an Iowa-licensed professional engineer with shop drawings submitted for review prior to construction. Contractors are required to verify utility locations through Iowa One Call, maintain positive drainage throughout construction, provide barricades and safety signage, and comply with detailed geotechnical requirements including third-party soil testing and proof-rolling of excavated areas. Material specifications include hot-dipped galvanized structural steel, stainless steel cables, high-density polyethylene fabric doors with ten to twelve-year service life, Bridge-Con surface coating for interior precast surfaces, and three applications of concrete defender treatment on floor slabs.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REGIONAL PLAN
SITE LOCATION
4 5
GREENE
OSCEOLALYON
DICKENSON
CRAWFORD
OBRIEN
CHEROKEE
SIOUX
EMMET
KOSSUTH
WINNEBAGO WORTH MITCHELL HOWARD
CLAY
MONONA
PLYMOUTH
BUENA VISTA POCAHONTAS
PALO ALTO
HUMBOLT WRIGHT FRANKLIN
FLOYD CHICKASAW
WINNESHIEK ALLAMAKEE
FAYETTE CLAYTON
BREMER
BUTLER
BLACK HAWK
CARROL
WOODBURY IDA SAC CALHOUN
HANCOCK CERRO GORDO
GREENE BOONE STORY MARSHALL
TAMA
GRUNDYHARDINHAMILTONWEBSTER
POWESHIEKJASPERPOLK
SCOTT
CLINTON
JACKSON
DUBUQUEDELAWAREBUCHANAN
JONES
CEDAR
LINN
BENTON
IOWA
JOHNSONHARRISON
POTTAWATTAMIE
MILLS
FREMONT
MADISON
DALLAS
GUTHRIEAUDUBON
SHELBY
CASS
ADAIR
UNIONADAMS
MONTGOMERY
PAGE TAYLOR RINGGOLD
WAREN MARION
LUCASCLARKE
DECATUR WAYNE
LEE
DES MOINES
LOUISA
MUSCATINE
WASHINGTONKEOKUKMAHASKA
HENRY
JEFFERSONWAPELLOMONROE
APPANOOSE DAVIS VAN BUREN
IOWA COUNTY AND DISTRICT KEY
ARCHITECTURAL
NO: NAME:
A001 PROJECT COVER
A102 FLOOR PLAN
A103 EXTERIOR ELEVATIONS
A104 BUILDING SECTIONS
A105 BUILDING DETAILS
A106 BUILDING DETAILS AND SITE DIAGRAM
PROJECT:
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
/1
/2
:5
:1
A
M
JEFFERSON 1800 TON TOTAL, 1500 TON SALT
STORAGE & 300 TON 50/50 BUILDING
BG-5J25 (000)--80-37
610 N Pinet St, Jefferson, IA 50129
ARCHITECTURE
SIGNATURE
I HEREBY CERTIFY THAT THE PORTION OF THIS TECHNICAL SUBMISSION
DESCRIBED BELOW WAS PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF IOWA.
DATE
MY LICENSE RENEWAL DATE IS:
LICENCE NUMBER:
PRINTED OR TYPED NAME: STEVE A. TROST
A-SHEETSPAGES OR SHEETS COVERED BY THIS SEAL:
JUNE 30, 2027
FOR REFERENCE ONLY
SHOWN AS AN EXAMPLE OF THE TYPE AND SCOPE
OF CONSTRUCTION ANTICIPATED IN ALTON, IA
A103 3
A103
A104
A A
F F
C C
E E
D D
A104
8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"4' - 0"
14' - 0" (APPROACH)128' - 0" (GRAVEL COVER)14' - 0" (APPROACH)
1' - 0"39' - 0"40' - 0"39' - 0"1' - 0"
A1032
A105
O
V E
R A
L L B
L D
G (D
E T
E R
M
IN
E D
B Y
B U
IL
D
IN
G
S U
P P
L
IE
R
O
V E
R A
L L B
L D
G (D
E T
E R
M
IN
E D
B Y
B U
IL
D
IN
G
S U
P P
L
IE
R
1' - 0" 39' - 0" 40' - 0" 39' - 0" 1' - 0"
300 TON 50/50 MIX
B B
4' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"8' - 0"4' - 0"
0' - 0"
4' - 0"80' - 0" CENTER OF PRECAST T36' - 0"
P
R E
C A
S T
O
P E
N
IN
G
G G
T WALL C.L.T WALL C.L.
T WALL C.L.
T W
A L L C
.L
4' - 0"80' - 0" SALT SORAGE (CENTER OF PRECAST T'S)32' - 0" 50/50 MIX (CENTER OF PRECAST T'S)4' - 0"
T W
A L L C
.L
PRECAST T
WALL TOE, TYP.
PRECAST T
WALL, TYP.
DOWNSPOUT & SPLASH BLOCK NOTE:
DOWNSPOUT ELBOW AND 24" LEADER W/ 36' X 12' X 3"
CONCRETE SPLASH BLOCK AT EACH LOCATION TYP.
(C
E N
T E
R O
F P
R E
C A
S R
T 'S
(C
E N
T E
R O
F C
O N
C R
E T
E T
'S
1500 TON SALT
STORAGE
60 X 84, BLDG. SIZE
52' X 80', CENTER OF T'S
1500 TONS MIN.
60 X 36, BLDG. SIZE
52' X 32', CENTER OF T'S
300 TONS MIN.
T WALL C.L.
0' - 0" 0' - 4"
E L
E V
A T
IO
N
V
E R
IF
Y
W C
IV
IL
(A
P P
R O
A C
H
E L
E V
A T
IO
N
V
E R
IF
Y
W C
IV
IL
(A
P P
R O
A C
H
84' - 0" (CENTER OF DIVIDER TO OUTSIDE OF BLDG)36' - 0" (CENTER OF DIVIDER TO OUTSIDE OF BLDG)
14' - 0" (APPROACH)4' - 0"124' - 0" (GRAVEL COVER)14' - 0" (APPROACH)
4' - 0"80' - 0" SALT STORAGE (CENTER OF PRECAST T'S)32' - 0" SALT STORAGE (CENTER OF PRECAST T'S)4' - 0"
T W
A L L C
.L
T W
A L L C
.L
T W
A L L C
.L
THICKENED
SLAB, TYP.
3' - 0" 3' - 0"
3' - 0" 3' - 0"
3' - 0" 3' - 0"
0' - 4"
B
U
IL
D
IN
G O
P E
N
IN
G
B
U
IL
D
IN
G O
P E
N
IN
G
B O
L L A
R D
(S
T Y
P
P
R E
C A
S T
O
P E
N
IN
G
C
E N
T E
R O
F B
O L A
R D
S
BLDG. C.L. BLDG. C.L.
1, 2
T W
A L L C
.L
DOWNSPOUT NOTE:
BOOT CONNECTION TO
DOWNSPOUTS ON THIS SIDE TO
CONNECT TO UNDERGROUND
DRAIN SYSTEM. SEE CIVIL. TYP.
BOLLARD C.L.
15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.15' - 0" BOLLARD C.L.
DIVIDER WALL TO BE LOCATED
TO ACHIEVE MIN. STORAGE
TONNAGE AS NOTED.
S S
S S
ELEVATION,
VERIFY W/ CIVIL
ELEVATION, VERIFY
W/ CIVIL
CONCRETE FLOOR SLOPE CONCRETE FLOOR SLOPE
1' - 3"
1' - 3"
(C
E N
T E
R O
F B
O L
L A
R D
S
1. CONTRACTOR TO LOCATE UTILITIES BEFORE STARTING EXCAVATION: IOWA ONE CALL
811 OR CONTACT UTILITY COMPANY TO STAKE.
2. PROVIDE POSITIVE DRAINAGE AWAY FROM BUILDING WITH FINAL GRADING OR PAVING
3. “C.J.” REPRESENTS LOCATIONS OF SAWCUT CONTROL JOINTS. PROVIDE CONTROL
JOINTS IN SLAB AT 12' MAX SPACING.
4. THE CONTRACTOR SHALL REVIEW PLANS AND THE AREA OF CONSTRUCTION
CAREFULLY TO ENSURE FULL UNDERSTANDING OF EXACT SCOPE OF WORK.
5. PROVIDE POSITIVE DRAINAGE AT ALL TIMES WITHIN THE CONSTRUCTION AREA. DO
NOT ALLOW WATER TO POND IN EXCAVATION AREAS, AND MAINTAIN ALL EXISTING
DRAINAGE PATTERNS.
6. THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS IN THE FIELD AND NOTIFY THE PROJECT MANAGER OF ANY
DISCREPANCIES BEFORE PROCEEDING WITH ANY WORK. NO CHANGES SHALL BE
MADE TO ANY PLAN WITHOUT PRIOR WRITTEN APPROVAL OF THE DESIGNER.
7. THE LOCATION OF ALL AERIAL AND UNDERGROUND UTILITY LINES ARE NOT INDICATED
IN THESE PLANS. UNDERGROUND FACILITIES, WHETHER INDICATED OR NOT, WILL BE
LOCATED AND FLAGGED BY THE UTILITY COMPANY. THE OWNER WILL ASSIST IN
IDENTIFYING LOCATIONS FOR ON SITE, INTERNAL INFRASTRUCTURE UTILITIES
BETWEEN BUILDING AND OTHER OWNER EQUIPMENT. CONTRACTOR TO PROCEED
WITH WORK CAUTIOUSLY AS NOT ALL LOCATIONS ARE KNOW OR ACCURATELY
PROVIDED.
8. HAUL ALL DEBRIS RESULTING FROM CONSTRUCTION OPERATIONS OFF-SITE AND
DISPOSE OF PROPERLY.
9. FURNISH AND MAINTAIN ALL NECESSARY BARRICADES, WARNINGS, SIGNS AND LIGHTS
AS NECESSARY FOR CONSTRUCTION OPERATIONS.
10. INCLUDE 8" YELLOW PAINT LINE AT THE TOP OF THE PRECAST PANELS TO INDICATE
THE MAX FILL HEIGHT.
11. SEE SITE PLAN FOR EXCAVATION AND FILL REQUIREMENT RELATED TO THE BUILDING
FOOTPRINT AREA. PROVIDE A MINIMUM OF 8" INCHES COMPACTED GRANULAR SUB-
BASE MEETING IDOT 4121 SPEC BELOW CONCRETE SLAB. SEE SITE INCLUSION OR
EXCLUSION OF CONCRETE SLABS AND/OR PAVING.
12. SIZE OF BUILDING SHOWN IS BASED ON A MINIMUM CLEARANCE OF 4' - 0" FROM
CENTER OF PRECAST T WALL TO OUTSIDE OF WOOD POSTS. VERIFY POLE BUILDING
POST LOCATION CLEARANCE WITH SUPPLIERS PROPOSED PRE-CAST "T" WALL
FOOTING WIDTH AND/OR "T" WALL EXTENSIONS AT CORNERS. ADJUST SIZE OF WOOD
POST FRAME BUILDING TO PROVIDE ADEQUATE CLEARANCE OF 4 FEET OR GREATER
TO PROVIDE THE MOST COST EFFECTIVE STRUCTURAL CONFIGURATION.
13. BUILDING SUPPLIER TO VERIFY THE COLUMN LOCATIONS AND SPACING MOST
ADVANTAGEOUS TO MEET THE BUILDING COST REQUIREMENTS. COLUMN LOCATION,
SPACING AND SIZE ONLY SHOWN FOR ILLUSTRATION PURPOSES.
14. BARRIERS:
A. PROVIDE BARRIERS TO PREVENT UNAUTHORIZED ENTRY TO CONSTRUCTION
AREAS, TO PREVENT ACCESS TO AREAS THAT COULD BE HAZARDOUS TO
WORKERS OR THE PUBLIC, TO ALLOW FOR OWNER'S USE OF SITE AND TO
PROTECT EXISTING FACILITIES AND ADJACENT PROPERTIES FROM DAMAGE
FROM CONSTRUCTION OPERATIONS .
B. PROVIDE BARRICADES AND COVERED WALKWAYS REQUIRED BY GOVERNING
AUTHORITIES FOR PUBLIC RIGHTS-OF-WAY AND FOR PUBLIC ACCESS TO
EXISTING BUILDING.
C. PROTECT NON-OWNED VEHICULAR TRAFFIC, STORED MATERIALS, SITE, AND
STRUCTURES FROM DAMAGE.
15. PROTECT NON-OWNED VEHICULAR TRAFFIC, STORED MATERIALS, AND SITE FROM
DAMAGE. PROTECT BY WHATEVER MEANS REQUIRED FOR ALL STRUCTURES,
UTILITIES, STREETS, BUSHES, TREES, FENCES, SIGNS, ETC. WHICH ARE NOT
DESIGNED FOR REMOVAL; OR WHICH ARE OUTSIDE THE CONTRACT AREA. SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/1
/2
:5
:2
A
M
J E
F F
E R
S O
N
T
O N
T O
T A
L T
O N
S A
L T
S T
O R
A G
E
T
O N
/5
B
U
IL
D
IN
G
F L O
O R
P L A
N
N
P in e t S t, J e ff e rs o n
IA
15 APR 26
A102
BG-5J25 (000)--80-37
GREENE 11/8" = 1'-0"A102
1 FLOOR PLAN
GEOTECHNICAL BASIS OF DESIGN
1. SEE TERRACON GEOTECHNICAL REPORT AB245049-01 DATED OCTOBER 14, 2024 FOR SITE ANALYSIS, SOIL BEARING PRESSURES AND RECOMMENDATIONS.
2. EXCAVATE 18" BELOW THE BOTTOM OF ALL PROPOSED BUILDING SLABS AND APPROACHES. PROOF ROLL THESE LOCATIONS WITH THE THIRD PARTY GEOTECHNICAL TESTING AGENCY PRESENT. REMOVE AND REPLACE SOILS DEEMED UNACCEPTABLE TO THE TESTING ENGINEER.
3. PROVIDE A MINIMUM 18" OF ENGINEERED FILL AS DESCRIBED IN THE GEOTECHNICAL REPORT TO SUPPORT NEW CONSTRUCTION. OF SLABS AND APPROACH PAVING IN A LEVEL PAD READY TO RECEIVE CONCRETE TEES ON THAT BASE. VERIFY WITH THE CONCRETE TEE ENGINEER THAT THIS SUB-BASE CONDITION
IS ACCEPTABLE FOR THE PROPOSED LOADS OF STORED SALT AND 50/50 MATERIAL.
4. FOR SLOPED SLABS INSIDE THE BUILDINGS PROVIDE A COMPACTED GRANULAR BASE ABOVE THE ENGINEERED FILL TO PRODUCE THE REQUIRED SLOPE.
5. INSTALL A MINIMUM OF 6 1/2" REINFORCED CONCRETE SLABS IN THE BUILDINGS. ENSURE THE CONCRETE SLABS OVERLAP THE FOOT OF THE PRECAST
CONCRETE TEES BY A MINIMUM OF 3" AS SHOWN ON THE DRAWINGS.
6. EXCAVATE PAD AND TRENCH FOOTINGS TO DEPTHS LISTED ON THE DRAWINGS. IF EXISTING FILL SOILS ARE STILL PRESENT OVER-EXCAVATE THESE LOCATIONS TO GET TO NATIVE SOILS. HAVE THE THIRD PARTY TESTING AGENCY NOTE THE DEPTHS OF OVER-EXCAVATION FOR CALCULATION OF ADDITIONAL WORK TO BE COMPENSATED BY UNIT PROCESS REQUESTED IN THE SPECIFICATION. FILL THE EXCAVATION TO FOOTING BEARING HEIGHTS WITH
LEAN CONCRETE TO PROVIDE APPROPRIATE BEARING FOR THE FOUNDATION SYSTEM.
7. REFERENCE CIVIL ENGINEERING DRAWINGS FOR FINISH FLOOR ELEVATIONS.
PERFORMANCE CRITERIA FOR PRECAST "T" WALLS
1. PRECAST T WALLS SHALL BE DESIGNED TO RESIST ALL APPLIED LOADS INCLUDING:
A. A. FOR STRUCTURAL CONSIDERATIONS, LATERAL AND VERTICAL LOADS FROM THE SALT PILE ON THE INTERIOR OF CONCRETE "T" WALLS IN THE SALT STORAGE PORTION OF THE BUILDING SHALL USE 87 LBS PER CUBIC FOOT.
B. FOR STRUCTURAL CONSIDERATION, LATERAL AND VERTICAL LOADS FROM THE 50/50 MATERIAL PILE ON THE INTERIOR OF THE CONCRETE "T" WALL IN THE 50/50 STORAGE PORTION OF THE BUILDING SHALL USE 130 LBS PER CUBIC FOOT.
C. PRE-CAST PANEL ENGINEER TO DESIGN REQUIRED SLAB THICKNESS AND WIDTH AT INTERIOR "T" WALL PANEL TOE TO PROVIDE REQUIRED RESISTANCE TO PROVIDE SALT STORAGE SUPPORT WITHOUT A BERM AT THE EXTERIOR OF THE PRE-CAST "T" WALL. DETAILS AND PLAN INDICATE AN EXAMPLE OF POTENTIAL CONFIGURATION, DIMENSIONS ARE TO BE
DETERMINED BY PANEL ENGINEER.
2. PROVIDE DETAILS OF ANY REQUIRED PANEL TO PANEL CONNECTIONS
3. PRECAST FOUNDATION PANELS SHALL BE DESIGNED BY AN IOWA LICENSED PROFESSIONAL ENGINEER FOR SALT LOADS, SHOP
DRAWINGS AND LAYOUT FOR REVIEW PRIOR TO CONSTRUCTION.
4. SHOP DRAWINGS SHALL INCLUDE A FULLY DIMENSIONED PLAN VIEW, A SECTION THROUGH THE FOUNDATION PANELS INCLUDING DIMENSIONS AND REINFORCING, CONNECTION DETAILS BETWEEN ADJACENT PANELS AND ANY ADDITIONAL
INFORMATION NEEDED TO REVIEW AND CONSTRUCT THE SYSTEM.
APPLICABLE BUILDING CODE:
STANDARD BASIS OF DESIGN
GENERAL NOTES
PROJECT DESCRIPTION
PROJECT CONSISTS OF A NEW 7200 SQFT. SALT STORAGE AND 50/50 MIX BUILDING.
1500 TON SALT STORAGE = 5040 SQFT.
300 TON 50/50 MIX = 2160 SQFT.
ARCHITECT:
RESOURCES AND ACQUISITIONS BUREAU, ARCHITECTURAL SERVICES
IOWA DEPARTMENT OF TRANSPORTATION
800 LINCOLN WAY, AMES, IA, 50010
ENGINEER:
SHIVE HATTERY (CIVIL AND ELECTRICAL)
4125 WESTOWN PKWY #100, WEST DES MOINES, IA 50266
SUBMISSION FOR PERMITTING
1. THE BUILDING PLANS AND SPECIFICATIONS ARE SUBMITTED BY THE
ARCHITECT/ENGINEER TO THE STATE OF IOWA BUILDING CODE BUREAU ONLY FOR
DESIGN REVIEW.
2. THE CONTRACTOR IS RESPONSIBLE FOR ARRANGING BUILDING
PERMITS/INSPECTIONS WITH THE STATE OF IOWA FOR ALL WORK.
3. THE FACILITY IS A STATE OWNED AND STATE FUNDED PROJECT. AS SUCH, THE STATE
OF IOWA, DEPARTMENT OF INSPECTIONS, APPEALS AND LICENSING IS THE AUTHORITY
HAVING JURISDICTION OVER THE PROJECT FOR CODE COMPLIANCE, PERMITTING AND
INSPECTIONS. NO OTHER GOVERNMENTAL ENTITY IS THE AUTHORITY HAVING
JURISDICTION.
REFERENCE CODES, GUIDELINES AND ACTS
THE FOLLOWING CODES AND GUIDELINES, AS ADOPTED AND AMENDED BY THE STATE OF
IOWA AND THE IOWA DEPARTMENT OF INSPECTIONS, APPEALS AND LICENSING ARE
APPLICABLE TO THIS PROJECT:
IOWA CODE: CHAPTER 103A - STATE BUILDING CODE
2024 INTERNATIONAL BUILDING CODE -
AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 661-201 AND 661-301
2024 INTERNATIONAL FIRE CODE -
AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 661-201
2012 INTERNATIONAL ENERGY CONSERVATION CODE -
AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 661-301
2012 NFPA 101 LIFE SAFETY CODE -
AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 661-205
2010 AMERICANS WITH DISABILITIES ACT -
AS ADOPTED BY IOWA ADMINISTRATIVE RULE CHAPTERS 661-302
2021 INTERNATIONAL MECHANICAL CODE -
AS ADOPTED BY IOWA DEPARTMENT OF PUBLIC HEALTH IOWA ADMIN RULE 641-61
2021 UNIFORM PLUMBING CODE -
AS ADOPTED BY IOWA DEPARTMENT OF PUBLIC HEALTH IOWA ADMIN RULE 641-25
2020 NATIONAL ELECTRIC CODE -
AS ADOPTED BY THE STATE ELECTRICAL LICENSING BOARD IOWA ADMIN RULE 661-504
STATE OF IOWA HAS ADOPTED THE CODES LISTED. IT IS RECOMMENDED THAT APPLICANTS
REVIEW THE IOWA ADMINISTRATIVE CODE FOR ANY MODIFICATIONS OR AMENDMENTS. THE
ADMINISTRATIVE CODE CAN BE VIEWED AT:
WWW.LEGIS.IOWA.GOV
HTTPS://DIAL.IOWA.GOV/LICENSES/BUILDING/PLAN-REVIEW
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
TOP OF SLAB, FRONT & REAR
0"
TRUSS BEARING
20' - 0"
A
1' - 0"
CONTINUOUS RIDGE VENT PER BLDG. MFG.
1' - 0"
BOTTOM OF METAL PANEL
4' - 0"
G
FABRIC DOOR AND
TRACK SYSTEM
60' - 0" OVERALL BLDG. (DETERMINED BY BUILDING SUPPLIER)
PRECAST T WALL TYP.
METAL JAMB TRIM AT
OPENING PERIMETER PER
BLDG MFG. CONTRACTOR TO
PROVIDE 2X BLOCKING FOR
BARIC DOOR INSTALLATION.
WRAP W/ METAL TRIM TO
MATCH JAMB OPENING
BOLLARD(S)TYP.
P R
E C
A S
T T
C .L
P R
E C
A S
T T
C .L
METAL WALL PANELS PER BLDG. MFG.
WING WALLS TYP.
SS102
19' - 7 1/2" (DOOR)
20' - 0" BLDG. OPENING
18' - 8" CENTER OF BOLLARDS
TOP OF SLAB, FRONT & REAR
0"
TRUSS BEARING
20' - 0"
A
1' - 0"
CONTINUOUS RIDGE VENT PER BLDG. MFG.
METAL WALL
PANELS PER
BLDG. MFG.
BOTTOM OF METAL PANEL
4' - 0"
BOLLARD(S)TYP.
G
PRECAST T WALL TYP.
60' - 0" OVERALL BLDG. (DETERMINED BY BUILDING SUPPLIER)
FABRIC DOOR AND
TRACK SYSTEM
METAL JAMB TRIM AT
OPENING PERIMETER PER
BLDG MFG. CONTRACTOR TO
PROVIDE 2X BLOCKING FOR
BARIC DOOR INSTALLATION.
WRAP W/ METAL TRIM TO
MATCH JAMB OPENING
P R
E C
A S
T T
C .L
P R
E C
A S
T T
C .L
WING WALLS TYP.
SS101
19' - 7 1/2" (DOOR)
18' - 8" CENTER OF BOLLARDS
20' - 0" BLDG. OPENING
TOP OF SLAB, FRONT & REAR
0"
TOP OF SLAB, FRONT & REAR
0"
TRUSS BEARING
20' - 0"
TRUSS BEARING
20' - 0"
CONTINUOUS RIDGE VENT PER BLDG. MFG.
METAL ROOF PANELS PER BLDG. MFG. TYP.
BOLLARD(S) TYP.
120' - 0" OVERALL BLDG. (DETERMINED BY BUILDING SUPPLIER)
GUTTER TYP.
METAL WALL PANELS PER BLDG. MFG.
DOWNSPOUT NOTE:
BOOT CONNECTION TO DOWNSPOUTS ON THIS
SIDE TO CONNECT TO UNDERGROUND DRAIN
SYSTEM. SEE CIVIL. TYP.
TRANSLUCENT WALL PANELS PER BLDG. MFG. TYP.
PRECAST T WALL TYP.
BOTTOM OF METAL PANEL
4' - 0"
BOTTOM OF METAL PANEL
4' - 0"
1' - 0" 39' - 0" 40' - 0" 39' - 0" 1' - 0"
4' - 0"32' - 0" 50/50 STORAGE (CENTER OF PRECAST T'S)80' - 0" SALT SORAGE (CENTER OF PRECAST T'S)4' - 0"
BOLLARD(S) TYP.
P R
E C
A S
T T
C .L
P R
E C
A S
T T
C .L
P R
E C
A S
T T
C .L
T
Y P
EXT. ELEC. PANEL FOR
LIGHTS. VERIFY POWER
REQ'S, LOCATION AND
FEED SOURCE W/ ELEC.
WING WALL
20' - 0" 40' - 0" 40' - 0" 20' - 0"
15' - 0"15' - 0"15' - 0"15' - 0"15' - 0"15' - 0"15' - 0"15' - 0"
BOLLARD(S) TYP.
PROVIDE BLOCKING, ELECTRICAL
BOX AND CONDUIT FOR LIGHT
FIXTURE, VERIFY POWER
REQUIREMENTS W/ ELEC. TYP.
1' - 3"
1/8" = 1'-0"A103
3 NORTH ELEVATION
1/8" = 1'-0"A103
2 SOUTH ELEVATION
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/1
/2
:5
:2
A
M
J E
F F
E R
S O
N
T
O N
T O
T A
L T
O N
S A
L T
S T
O R
A G
E
T
O N
/5
B
U
IL
D
IN
G
E X
T E
R
IO
R E
L E
V A
T
IO
N S
N
P in e t S t, J e ff e rs o n
IA
15 APR 26
A103
BG-5J25 (000)--80-37
GREENE 1
1/8" = 1'-0"A103
1 EAST ELEVATION, OPPOSITE ELEVATION SIM
FABRIC DOOR SPECIFIATION
FABRIC: HIGH DENSITY POLYETHYLENE (HDPE) STRUCTURAL MESH.
1. WARP AND WEFT FILAMENTS: 100 PERCENT ROUND MONO-FILAMENT.
2. FINISHED WEIGHT: 12.5 OZ/SQ YD .
3. STRETCH PROPERTIES: DIMENSIONALLY STABLE IN WARP AND WEFT.
4. FLAME RETARDANCY: COMPLY WITH NFPA 701.
5. FLAME SPREAD INDEX: 25 OR LESS, WHEN TESTED IN ACCORDANCE WITH ASTM E84, CLASS A.
6. SEAMS: SUFFICIENT STRENGTH TO DEVELOP 90 PERCENT OF FULL STRENGTH OF FABRIC AT 140 DEGREES F IN DIRECT TENSION ACROSS
SEAM.
A. ACCEPTABLE SEAMS AND EDGES: OVERLOCK STITCHED INTO A POLYETHYLENE ROPE OF APPROPRIATE STRETCH AND
DURABILITY CHARACTERISTICS OR OTHER APPROVED MATERIAL.
B. PROHIBITED SEAMS AND EDGES: FRENCH-HEM SEAM AND EDGE DETAILS AROUND A STEEL CABLE ARE UNACCEPTABLE DUE TO
WEAR CHARACTERISTICS.
C. PREVENT FABRIC FROM COMING INTO CONTACT WITH STEEL SUPPORT MEMBERS OTHER THAN THROUGH POLYETHYLENE EDGE
ROPE OR OTHER CORNER TERMINATIONS; STRETCHED FABRIC OVER STEEL SUPPORT FRAME IS UNACCEPTABLE DUE TO WEAR
CHARACTERISTICS.
7. EXPECTED SERVICE LIFE: TEN TO TWELVE YEARS.
8. COLOR: WHITE.
SUPPORTING STEEL MEMBERS: AS SPECIFIED IN SECTION 05 12 00, UNLESS OTHERWISE SPECIFIED IN THIS SECTION; STEEL MEMBERS ARE HOT-
DIPPED GALVANIZED AFTER FABRICATION.
1. STRUCTURAL STEEL: ASTM A36/A36M.
2. STRUCTURAL PIPE: ASTM A53/A53M, TYPE E OR S, GRADE B.
3. STRUCTURAL TUBING: ASTM A500/A500M, GRADE B.
4. HIGH-STRENGTH BOLTS: ASTM F3125/F3125M.
5. COMMON BOLTS: ASTM A307.
6. THREADED ROD: ASTM A36/A36M.
7. ANCHOR BOLTS, THREADED ROD: ASTM A36/A36M.
8. BRIDGECON COATING ON STRUCTURAL CONNECTION AT TOP OF PRECAST TEES.
PAINT FOR STRUCTURAL STEEL MEMBERS, TENSIONING NUTS, AND FABRIC PLATES:
1. FINISH COAT: ALIPHATIC POLYURETHANE; MINIMUM DRY FILM THICKNESS (DFT) OF 10 MILS, 0.010 INCH.
CABLES AND END FITTINGS: PROVIDE STRUCTURAL CABLES OF SAME TYPE HAVING SAME MODULUS OF ELASTICITY.
1. CABLES: STAINLESS STEEL, TYPE 304 OR 316.
2. CABLES IN CONTACT WITH FABRIC: PVC SLEEVED.
3. CABLE LENGTH TOLERANCE: AS INDICATED ON DRAWINGS.
4. SWAGED AND SPELTERED FITTINGS: DESIGN AND INSTALL TO DEVELOP FULL BREAKING STRENGTH OF CABLE.
5. THIMBLE END FITTINGS: DESIGN AND INSTALL TO DEVELOP A MINIMUM OF 90 PERCENT OF BREAKING STRENGTH OF CABLE.
6. SWAGED END FITTINGS, PINS, NUTS, AND WASHERS: STAINLESS STEEL.
7. TENSIONING NUTS AND FABRIC PLATES: GALVANIZED STEEL, FINISHED WITH TWO COATS OF EPOXY PAINT.
SHACKLES, RIGGING SCREWS, CLAMPS, AND TENSIONING HARDWARE: STAINLESS STEEL ARCHITECTURAL FINISHED MATERIAL ONLY.
OVERHEAD ACCORDION DOOR: ROLL-UP FABRIC DOOR WITH SAME FABRIC AS HOOP COVER. PULLEY CABLE LIFT OF FABRIC DOOR WITH
FOLLOWING SUPPORT ACCESSORIES:
1. MANUFACTURER'S STANDARD HOT DIPPED GALVANIZED TRACKS AND ANCHOR PLATES.
2. GALVANIZED STEEL FABRIC SUPPORT BARS
3. STAINLESS STEEL LIFT CABLES WITH HEAVY DUTY ALUMINUM MANUAL CRANK WINCH AND ALUMINUM PULLEY WHEELS.
OVERHEAD ACCORDION DOOR: ROLL-UP FABRIC DOOR WITH SAME FABRIC AS HOOP COVER. PULLEY CABLE LIFT
OF FABRIC DOOR WITH FOLLOWING SUPPORT ACCESSORIES:
1. MANUFACTURER'S STANDARD HOT DIPPED GALVANIZED TRACKS AND ANCHOR PLATES.
2. GALVANIZED STEEL FABRIC SUPPORT BARS
3. STAINLESS STEEL LIFT CABLES WITH HEAVY DUTY ALUMINUM MANUAL CRANK WINCH AND ALUMINUM PULLEY WHEELS.
EXAMINATION
1. EXAMINE AREA TO RECEIVE STRUCTURE; NOTIFY ARCHITECT IF AREA IS NOT ACCEPTABLE, AND DO NOT BEGIN INSTALLATION UNTIL
UNACCEPTABLE CONDITIONS HAVE BEEN CORRECTED.
PREPARATION
1. PREPARE AN ERECTION PLAN FOR ALL STRUCTURAL AND FABRIC INSTALLATION ACTIVITY, INCLUDING A DETAILED
SEQUENCE OF THE WORK.
2. PREPARE A CLEAR, FLAT, SMOOTH, AND CLEAN LAYOUT AREA ON GROUND OF SUFFICIENT SIZE FOR ASSEMBLY OF FABRIC PANELS;
PREPARE AREA ADJACENT TO LOCATION OF STRUCTURE INSTALLATION.
3. CHECK CONTACT SURFACES TO REMOVE SHARP OBJECTS, DIRT, GREASE, OIL, AND OTHER CAUSES FOR RIPS, SCRATCHING, OR OTHER
DAMAGE TO FABRIC PANELS DURING INSTALLATION.
4. USE TEMPORARY GROUND SHEETS WHERE FABRIC PANELS ARE TO BE DRAGGED ACROSS A SURFACE TO PREVENT CHAFFING OR
OTHER DAMAGE TO FABRIC PANEL SURFACE.
INSTALLATION
1. COMPLY WITH PRE-ESTABLISHED ERECTION PLAN.
2. DO NOT UNDERTAKE ERECTION OF FABRIC DURING INCLEMENT WEATHER CONDITIONS; INSTALLER HAS SOLE RESPONSIBILITY TO
DETERMINE WHEN CONDITIONS ARE SAFE FOR ERECTION.
3. INSTALL STRUCTURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AT LOCATION INDICATED ON DRAWINGS.
4. STEEL SUPPORT
A. ERECT SUPPORT STEEL PLUMB, LEVEL, AND SQUARE, TO CORRECT LOCATION AND ELEVATION.
B. DO NOT PERFORM FIELD WELDING WITHOUT APPROVAL OF ARCHITECT; USE EXPERIENCED WELDERS.
5. INSTALL STRUCTURE IN NECESSARY SEQUENCE AND WITH SUFFICIENT BRACING TO ENSURE STABILITY THROUGHOUT INSTALLATION.
6. ARCHITECT WILL INSPECT INSTALLED, SUPPORT STEEL, CABLES, AND FITTINGS BEFORE INSTALLATION OF FABRIC ONLY TO ENSURE
COMPLIANCE WITH DATA SUBMITTALS.
7. INSTALL AND TENSION FABRIC IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
A. USE CARE IN INSTALLATION OF FABRIC TO AVOID DAMAGE TO BASE MATERIAL, COATING, AND SURFACE TREATMENT.
B. ENSURE SURFACES OF FABRIC ARE SMOOTH, UNIFORM, AND CLEAN, WITH EVEN CURVED EDGES AND INTERFACES, AND WITH NO
CUTS, SCRATCHES, ABRASIONS, STAINS, MARKS, BLEMISHES, OR WELDING IRREGULARITIES.
8. REPAIR OR REPLACE DEFECTIVE OR DAMAGED MATERIALS, COATINGS, AND FINISHES AS DIRECTED BY ARCHITECT.
ADJUSTING
1. MAKE FINAL ADJUSTMENTS TO DOOR AS REQUIRED FOR STRUCTURAL INTEGRITY, AND
2. FREE FROM OBJECTIONABLE WRINKLES WHEN VIEWED FROM THE NORMALLY OCCUPIED SPACE.
CLEANING
1. CLEAN STRUCTURE IN ACCORDANCE WITH FABRIC MANUFACTURER'S INSTRUCTIONS.
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
CONT. METAL DRIP EDGE TRIM
LAMINATED POST/COL PER BLDG MFG.
TREATED WOOD GIRTS, PER MFG.
METAL WALL PANELS, PER MFG.
METAL SOFFIT (VENTED @
OVERHANG, SOLID @ GABLES)
2X SUB-FASCIA W/
METAL FASCIA OVER
2 X FRAMING BOLTED TO
POST PER MANUFACTURER'S STRUCTURAL DESIGN
BRACE PER BLDG MFG. KEEP BRACING WITH IN
4'-0" OF OUTSIDE WALL
METAL GUTTER
METAL FASCIA
METAL DRIP EDGE
TRUSS TIES, (HI), TYP. PER MFG'S STRUCTURAL DESIGN
ENGINEERED ROOF TRUSS PER MFG'S STRUCTURAL DESIGN
PURLIN SIZING & SPACING PER MANUFACTURER REQUIREMENTS
METAL ROOF PANELS
BRIDGING/BRACING PER BLDG. MFG.
TRANSLUCENT WALL PANELS SEE
ELEVATIONS, CONT. SEALS TOP & BTM.
COMPACTED GRANULAR FILL
EXTERIORINTERIOR
T R
A N
S L
U C
E N
T W
A L L
P A
N E
L
CONT. METAL DRIP EDGE
SEE SITE SPECIFIC SOIL NOTES
4' - 0" MIN.
A
0' - 0"
TOP OF SLAB, FRONT, VERIFY
-0' - 8"
BOTTOM OF T, FRONT, VERIFY
+20' - 0"
TRUSS BEARING
FOOTING PER BLDG. MFG.
T T
W A
L L
H E
IG
H
T
8" PAINTED YELLOW SAFETY LINE
(PAVING PAINT)
T WALL REINFORCING PER MFG.
15' - 0"
MAX SALT PILE
BRIDGE-CON SURFACE COATING AS
MANUFACTURED BY RHOMAR INDUSTRIES.
APPLY AT 50 SQFT/GAL., APPLY AT ALL
INTERIOR SURFACES, APPLY TO JAMB
OPENINGS AND RETURN TO EXTERIOR OF
PANEL FACES AT JAMBS FOR 4' - 0"
BITUMINOUS CAULK OVER
BITUMINOUS JOINT FOAM AT
INTERIOR OF ALL PRECAST JOINTS
VERIFY POLE BUILDING POST LOCATION
CLEARANCE WITH SUPPLIERS PROPOSED PRE-
CAST "T" WALL FOOTING WIDTH AND/OR "T" WALL
EXTENSIONS AT CORNERS. ADJUST SIZE OF
WOOD POST FRAME BUILDING TO PROVIDE
ADEQUATE CLEARANCE OF 4 FEET OR GREATER
TO PROVIDE THE MOST COST EFFECTIVE
STRUCTURAL CONFIGURATION
M
IN
M
IN
M
IN
/2
3" MIN OVERLAP ON THE
FACE OF T-WALL TOE, TO
PROVIDE MIN. 2" COVER
TOP AND BTM. OF REBAR
SHADED AREA TO HAVE THICKENED SLAB AT
INSIDE FACE OF PRECAST FOOTING TOE OF "T"
WALL PANEL. VERIFY DIMENSIONS REQUIRED
WITH PRE-CAST PANEL STRUCTURAL
ENGINEER. SLAB FIELD TO HAVE MINIMUM 6 1/2"
CONCRETE SLAB, C3-WR WITH #5 EPOXY
COATED REBAR AT 12" O.C. EACH WAY.
SURFACE TO BE TREATED WITH T"CONCRETE
DEFENDER" PER SPEC
REBAR SIZE, LENGTH AND
SPACING WHERE THICKENED
SLAB TIES INTO TOE OF PRE-
CAST "T" WALL PANEL TO BE
DETERMINED BY PRE-CAST "T"
WALL PANEL ENGINEER
3' - 0"
COMPACTED IN SITU EARTH COMPACTED IN SITU EARTH
COMPACTED GRANULAR FILL FOR
SLAB SLOPE, THICKNESS VARIES
SEE GEOTECHNICAL BASIS OF DESIGN
NOTE #6 FOR UNDER FOOTING CONDITIONS
50/50 SIDE
0' - 4"
TOP OF SLAB
-0' - 4"
BOTTOM OF T
CONC. FLOOR SLOPE
SEE SITE SPECIFIC SOIL NOTES
SALT STORAGE SIDE
0'- 4"0'- 4"
4' - 0" 4' - 0"
M
IN
M
IN
" 8
8" PAINTED YELLOW SAFETY LINE (PAVING
PAINT) BOTH SIDES TYP.
T WALL REINFORCING PER MFG.
BRIDGE-CON SURFACE COATING AS
MANUFACTURED BY RHOMAR INDUSTRIES.
APPLY AT 50 SQFT/GAL., APPLY AT ALL INTERIOR
SURFACES, APPLY TO JAMB OPENINGS AND
RETURN TO EXTERIOR OF PANEL FACES AT
JAMBS FOR 4' - 0" BOTH SIDES TYP.
BITUMINOUS CAULK OVER BITUMINOUS
JOINT FOAM AT INTERIOR OF ALL PRECAST
JOINTS, BOTH SIDES TYP.
3" MIN OVERLAP ON THE FACE
OF T-WALL TOE, TO PROVIDE
MIN. 2" COVER TOP AND BTM.
OF REBAR BOTH SIDES TYP.
REBAR SIZE, LENGTH AND SPACING
WHERE THICKENED SLAB TIES INTO
TOE OF PRE-CAST "T" WALL PANEL
TO BE DETERMINED BY PRE-CAST "T"
WALL PANEL ENGINEER, BOTH SIDES
TYP.
M
IN
/2
CONC. FLOOR SLOPE
COMPACTED GRANULAR FILL
SHADED AREA TO HAVE THICKENED SLAB AT
INSIDE FACE OF PRECAST FOOTING TOE OF "T"
WALL PANEL. VERIFY DIMENSIONS REQUIRED WITH
PRE-CAST PANEL STRUCTURAL ENGINEER. SLAB
FIELD TO HAVE MINIMUM 6 1/2" CONCRETE SLAB,
C3-WR WITH #5 EPOXY COATED REBAR AT 12" O.C.
EACH WAY. SURFACE TO BE TREATED WITH THREE
APPLICATIONS OF "CONCRETE DEFENDER", TYP.
3' - 0"3' - 0"
M
IN
COMPACTED IN SITU EARTH
M
IN
/2 " 5
M
IN
0' - 4"
TOP OF SLAB
-0' - 4"
BOTTOM OF T
COMPACTED GRANULAR FILL FOR SLAB SLOPE
PRECAST CONCRETE "T" PANEL NOTES:
1. PRE-CAST PANEL ENGINEER TO DESIGN REQUIRED SLAB
THICKNESS AND WIDTH AT INTERIOR "T" WALL PANEL TOE
TO PROVIDE REQUIRED RESISTANCE TO PROVIDE SALT
STORAGE SUPPORT WITHOUT A BERM AT THE EXTERIOR
OF THE PRE-CAST "T" WALL OR PROVIDE EXTERIOR BERM
DESIGN. DETAILS AND PLAN INDICATE AN EXAMPLE OF
POTENTIAL CONFIGURATION, DIMENSIONS ARE TO BE
DETERMINED BY PANEL ENGINEER.
2. BOTTOM OF PRE-CAST "T" WALL PANEL ELEVATION TO BE
DETERMINED BY PANEL ENGINEER BASED ON REQUIRED
INTERIOR SLAB OVERLAP THICKNESS FOR LOAD
RESISTANCE. THIS DIMENSION IS TO BE A MINIMUM OF 3
INCHES PER WALL SECTION. ELEVATION SHOWN HERE IS
BASED ON THE MINIMUM OVERLAP THICKNESS.
SUB-BASE FOR PRECAST CONCRETE "T" PANEL NOTES:
1. EXCAVATE 18" BELOW THE BOTTOM OF ALL PROPOSED
BUILDING SLABS AND APPROACHES. PROOF ROLL THESE
LOCATIONS WITH THE THIRD PARTY GEOTECHNICAL
TESTING AGENCY PRESENT. REMOVE AND REPLACE SOILS
DEEMED UNACCEPTABLE TO THE TESTING ENGINEER.
2. SEE SITE SPECIFIC SOILS INFO FOR SLABS AND APPROACH
PAVING IN A LEVEL PAD READY TO RECEIVE CONCRETE
TEES ON THAT BASE. VERIFY WITH THE CONCRETE TEE
ENGINEER THAT THIS SUB-BASE CONDITION IS
ACCEPTABLE FOR THE PROPOSED LOADS OF STORED SALT
AND 50/50 MATERIAL.
8" MIN COMPACTED GRANULAR FILL,
TYPICAL ON ALL PROJECTS
COMPACTED IN SITU EARTH,
TYPICAL ON ALL PROJECTS
M
IN
/2
M
IN
M
IN
USE (NFS) FILL FOR THIS SITE
SITE SPECIFIC SOILS INFO:
THE SOILS ON THIS SITE ARE FROST SUSCEPTIBLE. SMALL AMOUNTS OF WATER CAN
AFFECT THE PERFORMANCE OF SLAB ON-GRADE CONSTRUCTION, AS SUCH SLABS IN
NON-HEATED STRUCTURES SHOULD BE ANTICIPATED TO HEAVE DURING WINTER
MONTHS. THE USE OF EITHER LOW FROST SUSCEPTIBLE (LFS) FILL MATERIAL OR NON-
FROST SUSCEPTIBLE (NFS) FILL PLACED TO CONVENTIONAL FROST DEPTH OF 4 FEET
IS RECOMMEND.
(NFS) MATERIAL: SHOULD CONSIST OF A WELL-GRADED, CLEAN GRANULAR
MATERIAL WITH LESS THAN 3% PASSING THE NO. 200 SIEVE.
(NFS) LOW-FROST SUSCEPTIBLE MATERIAL: SHOULD CONSIST OF A WELL-
GRADED, CLEAN GRANULAR MATERIAL WITH LESS THAN 6% PASSING THE NO.
200 SIEVE
CONCRETE SLAB
3/4" = 1'-0"A105
1 WALL SECTION SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/1
/2
:5
:2
A
M
J E
F F
E R
S O
N
T
O N
T O
T A
L T
O N
S A
L T
S T
O R
A G
E
T
O N
/5
B
U
IL
D
IN
G
B U
IL
D
IN
G
D E
T A
IL
S
N
P in e t S t, J e ff e rs o n
IA
15 APR 26
A105
BG-5J25 (000)--80-37
GREENE 1
3/4" = 1'-0"A105
2 DIVIDING PRECAST T WALL DETAIL
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
TOP OF SLAB, FRONT & REAR
0"
TOP OF SLAB, FRONT & REAR
0"
TRUSS BEARING
20' - 0"
TRUSS BEARING
20' - 0"
CONTINUOUS RIDGE VENT PER BLDG. MFG.
20' - 0" (APPROACH) 120' - 0" OVERALL BLDG. (DETERMINED BY BUILDING SUPPLIER) 20' - 0" (APPROACH)
BOTTOM OF T, FRONT & REAR
-8"
BOTTOM OF T, FRONT & REAR
-8"
TRANSLUCENT WALL PANEL PER BLDG. MFG. TYP.
A105
BOTTOM OF METAL PANEL
4' - 0"
TRUSSES PER BLDG. MFG. TYP.
4' - 0" 80' - 0" SALT SORAGE (CENTER OF PRECAST T'S) 32' - 0" 50/50 (CENTER OF PRECAST T'S) 4' - 0"
TOP OF SLAB 0' - 4"
CONCRETE T DIVIDER
P R
E C
A S
T C
.L
P R
E C
A S
T C
.L
P R
E C
A S
T C
.L
BOLLARD(S)
CS102
300 TON 50/50 MIX
1500 TON SALT
STORAGE
CS101
36' - 0"84' - 0"
BOLLARD(S)
TOP OF SLAB 0' - 0"
-0' -1", VERIFY W/ EXISTING SITE CONDITIONS
TOP OF SLAB 0' - 4"
TOP OF SLAB 0' - 0"
1' - 3"
TOP OF SLAB, FRONT & REAR
0"
TRUSS BEARING
20' - 0"
A
1' - 0"1' - 0"
CONTINUOUS RIDGE VENT PER BLDG. MFG.
BOTTOM OF T, FRONT & REAR
-8"
4' - 0" 52' - 0" CENTER OF PRECAST T (VERIFIED BY PRECAST SUPPLIER) 4' - 0"
BOTTOM OF METAL PANEL
4' - 0"
G
A105
P R
E C
A S
T T
C .L
P R
E C
A S
T T
C .L
1500 TON SALT
STORAGE
SS101
FABRIC DOOR AND
TRACK SYSTEM
METAL JAMB TRIM AT
OPENING PERIMETER PER
BLDG MFG. CONTRACTOR TO
PROVIDE 2X BLOCKING FOR
BARIC DOOR INSTALLATION.
WRAP W/ METAL TRIM TO
MATCH JAMB OPENING
19' - 7 1/2" (DOOR)
19' - 4" PRECAST OPENING
20' - 0" BUILDING OPENING
60' - 0" OVERALL BLDG. (DETERMINED BY BUILDING SUPPLIER)
1' - 3"
TOP OF SLAB, FRONT & REAR
0"
TRUSS BEARING
20' - 0"
ACONTINUOUS RIDGE VENT PER BLDG. MFG.
BOTTOM OF T, FRONT & REAR
-8"
4' - 0" 52' - 0" CENTER OF PRECAST T (VERIFIED BY PRECAST SUPPLIER) 4' - 0"
A105
1 SIM.
BOTTOM OF METAL PANEL
4' - 0"
G
P R
E C
A S
T T
C .L
P R
E C
A S
T T
C .L
300 TON 50/50 MIX
SS102
FABRIC DOOR AND
TRACK SYSTEM
METAL JAMB TRIM AT
OPENING PERIMETER PER
BLDG MFG. CONTRACTOR TO
PROVIDE 2X BLOCKING FOR
BARIC DOOR INSTALLATION.
WRAP W/ METAL TRIM TO
MATCH JAMB OPENING
19' - 7 1/2" (DOOR)
20' - 0" BUILDING OPENING
60' - 0" OVERALL BLDG. (DETERMINED BY BUILDING SUPPLIER)
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/1
/2
:5
:2
A
M
J E
F F
E R
S O
N
T
O N
T O
T A
L T
O N
S A
L T
S T
O R
A G
E
T
O N
/5
B
U
IL
D
IN
G
B U
IL
D
IN
G
S E
C T
IO
N
S
N
P in e t S t, J e ff e rs o n
IA
15 APR 26
A104
BG-5J25 (000)--80-37
GREENE 1
1/8" = 1'-0"A104
1 LONG. BLDG. SECT.
1/8" = 1'-0"A104
2 BLDG. SECT. LOOKING AT SALT STORAGE
1/8" = 1'-0"A104
3 BLDG. SECT. LOOKING AT 50/50 MIX
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
CONCRETE FLOOR SLAB
ISOLATION JOINT W/
SEALANT OVER, TYP.
EXTERIOR INTERIOR
SLOPE APPROACH -2" OVERALL AWAY FROM BLDG.
4' - 0"
0' - 0"
TOP OF SLAB, FRONT
-0' - 8"
BOTTOM. OF T, FRONT
SLOPE SLAB 6" OVERALL TO BLDG. OPENING
COMPACTED GRANULAR FILL
CONCRETE APPROACH
OPEN SPACE BETWEEN PRECAST
"T" AND BLDG. STRUCTURE
COMPACTED GRANULAR FILL
PRECAST
T WALL
BLDG. OPENING
COMPACTED EARTH IN SITU
1' - 3"
6" DIA. GALV. STEEL PIPE
BOLLARD. FILL W/ CONC. SET
IN 15" DIA. HOLE 4' - 0" BELOW
GRADE. CONTRACTOR TO
PROVIDE AND INSTALL
PLASTIC COVER
3' - 0" 2' - 6"
/2
M
IN
M
IN
0'-0" ORIGIN POINT
THICKENED EDGE AT
PERIMETER (SEE PLAN)
CENTER OF "T" WALL
TO OUTSIDE OF TOE
FACE OF
BLDG. TO C.L.
/2
M
IN
M
I N
VERIFY POLE BUILDING POST
LOCATION CLEARANCE WITH
SUPPLIERS PROPOSED PRE-
CAST "T" WALL FOOTING
WIDTH AND/OR "T" WALL
EXTENSIONS AT CORNERS.
ADJUST SIZE OF WOOD POST
FRAME BUILDING TO PROVIDE
ADEQUATE CLEARANCE OF 4
FEET MINIMUM OR MOST
COST ECONOMICALLY
EFFECTIVE POLE BUILDING
POST CONFIGURATION
BLDG. OPENING, JAMB TRIM PER BLDG. MFG.
FABRIC DOOR TRACK / HARDWARE
FABRIC DOOR TO TOP OF WING WALL
CONTRACTOR TO PROVIDE 2X BLOCKING
FOR BARIC DOOR INSTALLATION. WRAP W/
METAL TRIM TO MATCH JAMB OPENING
SEE SITE SPECIFIC
SOILS INFO EARTH
SHEET
DATE:
x
S h e e t Io w a D
O T
R E
V
IS
IO
N
S
Resources & Acquisitions Bureau 800 Lincoln Way Ames, Iowa 50010
(515) 239-1299
COUNTY: DISTRICT:
PROJECT NUMBER:
/1
/2
:5
:2
A
M
J E
F F
E R
S O
N
T
O N
T O
T A
L T
O N
S A
L T
S T
O R
A G
E
T
O N
/5
B
U
IL
D
IN
G
B U
IL
D
IN
G
D E
T A
IL
S
A N
D S
IT
E
D
IA
G R
A M
N
P in e t S t, J e ff e rs o n
IA
15 APR 26
A106
BG-5J25 (000)--80-37
GREENE 1
N O
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
3/4" = 1'-0"A106
1 DOOR THRESHOLD DETAIL AT BLDG. OPENING, OPP. SIDE SIM.
DIAGRAM NOTES:
BUILDING NOT SHOWN FOR CLARITY
SALT STORAGE DIAGRAMS
BOLLARD(S)
CONCRETE APPROACH
SEE PLAN, TYP.
BOLLARD(S), TYP.
GRAVEL COVER SEE PLAN
GRAVEL COVER SEE PLAN
8" SAFETY STRIPE
BRIDGE-CON AT PANEL TOP, TYP.
DIVIDING PANEL, SEE PLAN.
BRIDGE-CON AT
PANEL INTERIOR, TYP.
WRAP BRIDGE-CON
COATING TO THE OUTSIDE
OF THE T OPENING 4'-0"
AS SHOWN, TYP. AT ALL
OPENINGS.
PRECAST T'S SEE PLAN
File details come from the government source that posted it. Updated .