J1b. TMB ATCT Facility Rehab Final Drawings 12.01.20.pdf
PDF 11 MB Posted
- Attached to
- TMB ATCT Rehabilitation Federal contract opportunity
- Solicitation number
- 697DCK-22-R-00166
About this file
This solicitation is for repairs to the Air Traffic Control Tower at Miami Executive Airport in Miami, Florida. The Federal Aviation Administration requires repairs to the existing ATCT facility and is seeking proposals in response to solicitation number 697DCK-22-R-00166. Offerors must be registered in the System for Award Management and submit proposals in accordance with Sections L and M of the solicitation by the specified due date. Questions regarding the solicitation are due by March 9th, 2022 and must be submitted in writing to the identified point of contact. A site visit date has not yet been set but information will be provided through an amendment posted on SAM.gov once scheduled. Only direct costs will be considered for payment and the Government is not liable for any costs associated with proposal preparation or submission.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFI Set 2 Photos.pdf | ||
| RFI Set 2.pdf | ||
| 697DCK-22-R-00166 Amend 0002.pdf | ||
| RFI Set 1.pdf | ||
| 697DCK-22-R-00166 0001.pdf | ||
| L3. Price Proposal - TMB ATCT Rehab.xlsx | XLSX spreadsheet | |
| 697DCK-22-R-00166 Final.pdf | ||
| J4. Wage Rate.pdf | ||
| L2. TMB Past Performance Questionnaire.pdf | ||
| J1. TMB ATCT Facility Rehab Final Specifications 12.01.20.pdf | ||
| J1a. TMB - Addendum #1 - 031721.pdf | ||
| J2. Operational Risk Management Plan.pdf | ||
| L1. BidBond.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Croft & Associates
0 2020-12-01 100% SUBMITTAL
11/25/202011/25/5///202222222 20// /////
A 2019-12-20 CHECK SET
B 2020-01-10 95% CHECK SET
0 2020-11-30 100% SUBMITTAL
11/30/2020
B 2020-01-10 95% CHECK SET
B 2020-01-10 95% CHECK SET
B 2020-01-10 95% CHECK SET
GENERAL REQUIREMENTS:
1. ALL WORK SHALL CONFORM TO THE 2017 EDITION
OF THE NATIONAL ELECTRICAL CODE (NFPA 70),
ALL STATE AND LOCAL CODES, RULES, AND
REGULATIONS, AND PROJECT SPECIFICATIONS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
FEES, PERMITS, AND LICENSES FOR THE
COMPLETE INSTALLATION OF THE WORK
OUTLINED IN THESE CONTRACT DOCUMENTS.
3. THE CONTRACT DOCUMENTS ARE
DIAGRAMMATIC IN NATURE AND NOT EVERY
DETAIL OR EXACT LOCATION OF EQUIPMENT
AND/OR CONDUIT IS SHOWN. VERIFY ALL
CONDITIONS AND DIMENSIONS PRIOR TO
ORDERING ANY MATERIAL OR PERFORMING ANY
WORK. NOTIFY THE ENGINEER OF RECORD OF
ANY CONDITIONS OR DIMENSIONS WHICH WOULD
AFFECT PERFORMANCE OF WORK IN
ACCORDANCE WITH THE CONTRACT DRAWINGS
AND/OR SPECIFICATIONS.
4. CONTRACTOR IS TO COORDINATE W/ GENERAL
CONTRACTOR IN REGARDS TO PROJECT
TIMELINE, WORK HOURS, AS WELL AS ANY
BONDING OR INSURANCE REQUIREMENTS.
5. HANDLE, STORE AND PROTECT EQUIPMENT AND
MATERIALS IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
REPLACE DAMAGED OR DEFECTIVE ITEMS WITH
NEW ITEMS.
COORDINATION:
1. CONTRACTOR SHALL COORDINATE LOCATIONS
AND ELECTRICAL REQUIREMENTS OF
MECHANICAL/PLUMBING EQUIPMENT WITH THE
MECHANICAL/PLUMBING CONTRACTORS PRIOR
TO ORDERING ANY MATERIAL OR PERFORMING
ANY WORK ASSOCIATED WITH SUCH EQUIPMENT.
2. CONTRACTOR SHALL COORDINATE LOCATION OF
LIGHT FIXTURES WITH MECHANICAL
CONTRACTOR, PLUMBING CONTRACTOR, AND
FIRE PROTECTION CONTRACTOR PRIOR TO
INSTALLATION TO AVOID CONFLICT WITH
DUCTWORK, PIPING, AND SPRINKLER SYSTEM
COMPONENTS.
3. EXACT DEVICE LOCATIONS (RECEPTACLES,
DATA/TELEPHONE OUTLETS, LIGHT FIXTURES,
ETC.) SHALL BE COORDINATED WITH
ARCHITECTURAL PLANS.
4. TRACK LIGHTS, FLOOD LIGHTS, AND WALL
WASHERS SHALL HAVE THEIR AIMING ANGLES
ADJUSTED PER GOVERNMENT REQUIREMENTS
PRIOR TO FINALIZATION OF LIGHTING WORK.
MATERIALS:
1. OUTLET BOXES
1.1. GENERAL USE BOXES: GALVANIZED,
PRESSED STEEL UNITS OF PROPER DEPTH
AND GAUGE REQUIRED BY THE OUTLET
LOCATION. EQUIP WITH PLASTER RING OR
COVER AS NECESSARY.
1.2. SPECIAL BOXES: GALVANIZED SHEET METAL
OR CAST CONSTRUCTION AND SIZED IN
ACCORDANCE WITH NFPA 70. FOR SPECIAL
SYSTEM, USE BOXES AS RECOMMENDED BY
THE EQUIPMENT MANUFACTURER.
2. CONDUIT
2.1 RIGID METALLIC CONDUIT (RMC): HOT
DIPPED GALVANIZED STEEL CONFORMING
TO (FS) WW-C581E AND UL 6.
2.2 ELECTRICAL METALLIC TUBING (EMT):
GALVANIZED STEEL CONFORMING TO ASA
C80.3, (FS) WW-C563 AND ULF 797.
2.3 FLEXIBLE METAL CONDUIT (FMC): SPIRAL
WOUND,SQUARE LOCKED, HOT DIPPED
GALVANIZED STEEL CONFORMING TO UL 1
2.4 METAL-CLAD CABLE (MC): INTERLOCKING
STEEL SHEATH, CONFORMING TO UL
1569. ALUMINUM IS PROHIBITED.
3. CONDUIT FITTINGS
3.1 RMC: HOT DIPPED GALVANIZED OR CADMIUM
PLATED. FITTINGS USED WITH COATED RMC
SHALL HAVE A SIMILAR COATING.
3.2 EMT: COMPRESSION TYPE, MADE OF
CADMIUM PLATED STEEL OR HOT DIPPED
GALVANIZED MALLEABLE IRON.
3.3 MC: TWO SCREW, DOUBLE CLAMP
MALLEABLE IRON, HOT DIPPED GALVANIZED
OR CADMIUM PLATED.
4. WIRING
4.1 ALL WIRING SHALL BE COPPER UNLESS
NOTED OTHERWISE.
4.2 INSULATION: HEAT AND MOISTURE
RESISTANT WITH A TEMPERATURE RATING
OF AT LEAST 75 DEGREES THERMAL HIGH
HEAT NYLON (THHN), THERMAL HIGH WATER
RESISTANT NYLON (THWN) AND A 600 VOLT
RATING UNLESS OTHERWISE INDICATED.
4.3 USE STRANDED CONDUCTOR ON ALL
WIRING #8 AWG AND LARGER. ALL OTHER
WIRING MAY BE SOLID.
5. USE ANCHORS AND FASTENERS OF A TYPE
DESIGNED AND INTENDED FOR USE IN THE BASE
MATERIAL TO WHICH THE MATERIAL OR SUPPORT
IS TO BE ATTACHED, AND CAPABLE OF
SUPPORTING THE INTENDED LOAD AND WITH
STANDING ANY ASSOCIATED STRESSES AND
VIBRATIONS. DO NOT USE WOODEN PLUGS FOR
FASTENING.
6. ALL MATERIALS USED FOR CONSTRUCTION SHALL
BE INSTALLED IN A NEAT AND WORK-LIKE MANNER.
7. ALL WIRING DEVICES SHALL BE SPECIFICATION
GRADE AND MATCH BASE BUILDING STANDARD
DEVICE STYLE, COLOR, AND MOUNTING HEIGHT
UNLESS REQUIRED TO BE IN COMPLIANCE WITH
ADA.
8. CONTRACTOR SHALL PROVIDE ALL COMPONENTS
NECESSARY TO INSTALL LIGHT FIXTURES PER
MANUFACTURER'S RECOMMENDATIONS. THIS
INCLUDES, BUT IS NOT LIMITED TO, MOUNTING
HARDWARE, SLOPED-CEILING ADAPTORS, GYP
BOARD TRIM KITS, ETC.
9. FOR ALL TELEPHONE/DATA OUTLETS, PROVIDE AN
OUTLET BOX WITH 3/4” CONDUIT AND A PULL
STRING TO THE ACCESSIBLE CEILING SPACE.
10. ALL MATERIALS AND EQUIPMENT FURNISHED AND
INSTALLED BY THE CONTRACTOR SHALL BE NEW,
UL LISTED OR LABELED, AND CONFORM TO NEMA
ANS/ANSI STANDARDS WHERE APPLICABLE.
11. FURNISH AND INSTALL PULL BOXES, JUNCTION
BOXES, AND DEVICE BOXES OF SUITABLE GAUGE
AND SIZE AS NECESSARY TO PROVIDE A FULLY
FUNCTIONAL AND CODE COMPLIANT SYSTEM.
EXECUTION:
1. MAINTAIN THE INTEGRITY OF ALL EXISTING
CIRCUITS IN SERVICE THAT MAY BE AFFECTED BY
THIS WORK. IDENTIFY ALL SOURCES OF POWER
AND DE-ENERGIZE REQUIRED CIRCUITS BEFORE
BEGINNING WORK.
2. PERFORM ALL CUTTING AND DRILLING TO PROVIDE
PENETRATIONS THROUGH WALLS AND FLOORS
FOR ELECTRICAL INSTALLATION WORK.
3. WHERE CONDUITS PASS THROUGH FIRE RATED
OR SMOKE RATED ASSEMBLIES, CONTRACTOR
SHALL FOLLOW UL GUIDELINES FOR
SEALING/STOPPING PENETRATIONS TO MAINTAIN
FIRE AND/OR SMOKE RATING OF WALL ASSEMBLY.
4. ALL DEVICES AND JUNCTION BOXES SHALL BE
ACCESSIBLE. PROVIDE ACCESS PANELS AS
REQUIRED TO ENSURE ACCESS TO DEVICES.
COORDINATE ACCESS PANEL LOCATIONS AND
TYPES WITH RESIDENT ENGINEER PRIOR TO
ORDERING AND INSTALLATION.
5. DISCONNECT SWITCHES SHALL BE MOUNTED ON
INDIVIDUAL STRUCTURAL SUPPORTS, OR
OTHERWISE DIRECTLY ON EQUIPMENT, PROVIDED
NO MODIFICATION TO EQUIPMENT IS NECESSARY.
ALL STRUCTURAL SUPPORTS FOR ELECTRICAL
EQUIPMENT SHALL BE PROVIDED AND INSTALLED
BY CONTRACTOR.
6. ALL ELECTRICAL DEVICE CONNECTIONS SHALL BE
TIGHTENED TO THE TORQUE VALUES
RECOMMENDED BY THE DEVICE MANUFACTURER.
IF THESE VALUES ARE NOT LISTED, TIGHTEN TO
POUND INCH OR POUND FOOT VALUES
RECOMMENDED BY UL STANDARD 486A-B.
7. GROUNDING
7.1 ALL ELECTRICAL EQUIPMENT, WIRING,
CONDUITS, AND BUILDING ELEMENTS SHALL
BE GROUNDED PER THE REQUIREMENTS OF
NFPA 70 AND FAA STANDARD 019F.
7.2 THE BUILDING GROUNDING ELECTRODE
SYSTEM SHALL BE INSTALLED TO MAINTAIN A
RESISTANCE TO EARTH OF 25 OHMS OR LESS.
IF A SINGLE GROUNDING ELECTRODE CAN
NOT MEET THIS REQUIREMENT, THE
CONTRACTOR IS REQUIRED TO INSTALL
SUPPLEMENTAL ELECTRODES PER SECTION
250.53 OF NFPA 70.
7.3 PROVIDE AN EQUIPMENT CONDUCTOR IN ALL
RACEWAYS SIZED IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 70. CONDUITS ARE
NOT PERMITTED TO BE USED IN LIEU OF A
GROUND WIRE.
7.4 BOND ALL BRANCH CIRCUIT DEVICES TO THE
BUILDING GROUND SYSTEM BY MEANS OF
THE GROUNDING CONDUCTOR INSTALLED IN
EACH RACEWAY.
8. CABLE INSTALLED OUTSIDE OF RACEWAYS SHALL
BE SUPPORTED INDEPENDENTLY AND NOT FROM
OTHER SYSTEMS. SECURING CABLES TO OR FROM
WATERLINES, ELECTRICAL RACEWAYS, OR ANY
OTHER MECHANICAL SYSTEM IS NOT ACCEPTABLE.
CABLES SHALL BE SUPPORTED FROM BAR JOISTS,
CABLE TRAYS, UNI- STRUT TRAPEZE HANGERS, OR
OTHER HANGERS INSTALLED AND APPROVED FOR
THIS PURPOSE. MAXIMUM SPACING SHALL BE 10'
ON CENTER WITH A MAXIMUM 8” SAG. CABLES
SHALL MAINTAIN A MINIMUM 6” CLEARANCE FROM
ELECTRICAL EQUIPMENT.
9. IDENTIFICATION
9.1 REFER TO SPECIFICATION SECTION 26 05 53
"IDENTIFICATION FOR ELECTRICAL SYSTEMS"
FOR LABELING REQUIREMENTS.
9.2 IDENTIFICATION AND NAMEPLATES SHALL BE
IN ACCORDANCE WITH FAA 1217G
10. WIRING
10.1 ALL WIRING SHALL BE INSTALLED IN
APPROVED CONDUITS OR RACEWAYS UNLESS
NOTED OTHERWISE.
10.2 ALL BRANCH CIRCUITS SHALL HAVE
DEDICATED NEUTRAL CONDUCTORS UNLESS
NOTED OTHERWISE.
10.3 WIRES SHALL BE A MINIMUM #12 AWG IN SIZE.
10.4 COLOR CODE WIRING AS FOLLOWS:
10.4.1 120/240V, 1 PHASE: NEUTRAL - WHITE,
PHASE A - BLACK, PHASE B - RED,
GROUND - GREEN
10.4.2 120/208V, 3 PHASE: NEUTRAL - WHITE,
PHASE A - BLACK, PHASE B - RED,
PHASE C - BLUE, GROUND - GREEN
10.4.3 277/480V, 3 PHASE: NEUTRAL - GREY,
PHASE A - BROWN, PHASE B - ORANGE,
PHASE C -YELLOW, GROUND - GREEN
11. CONDUIT
11.1 ALL CONDUITS SHALL BE INSTALLED IN A
CONCEALED LOCATION WHERE POSSIBLE,
WITH THE EXCEPTION OF DEDICATED
MECHANICAL AND ELECTRICAL SPACES. IN
THOSE AREAS OUTSIDE OF THE EXCEPTION
WHERE IT IS NOT POSSIBLE TO INSTALL
CONDUITS IN A CONCEALED MANNER,
CONTRACTOR SHALL INSTALL
EXPOSED CONDUITS PARALLEL AND AT RIGHT
ANGLES TO THE NEARBY SURFACES AND
STRUCTURAL MEMBERS. IN THESE AREAS,
GROUP RACEWAYS IN MINIMUM GROUPS OF
THREE RACEWAYS ON A COMMON SUPPORT
SYSTEM.
11.2 PROVIDE PULL ROPE IN ALL EMPTY CONDUITS.
11.3 EXTERIOR LOCATIONS: USE RMC CONDUIT.
11.4 INTERIOR LOCATIONS, WHERE SUBJECT TO
DAMAGE BELOW 8' AFF: USE RMC CONDUIT.
11.5 INTERIOR LOCATIONS, WHERE NOT SUBJECT
TO DAMAGE, ABOVE 8' AFF, OR IN CONCEALED
LOCATIONS: USE RMC OR EMT CONDUIT.
11.6 TYPE MC CABLE FOR LIGHTING CIRCUITS IS
PERMITTED IN CONCEALED LOCATION UP TO A
MAXIMUM RUN OF 6'0” FEET AT THE END OF
RUN TO CONNECT LIGHT FIXTURES TO
SUPPLYING BRANCH CIRCUIT.
11.7 FMC IS PERMITTED TO BE USED IN FOR
RUNOUTS FOR EQUIPMENT SUBJECT TO
VIBRATION (MOTORS, HVAC EQUIP, ETC.).
RUNOUT LENGTHS FOR FMC MUST BE 6'0”
FEET OR LESS.
11.8 CONDUIT REQUIREMENTS IN THIS SECTION
ARE PROVIDED FOR GENERAL PRICING AND
INSTALLATION GUIDANCE. CONTRACTOR IS
RESPONSIBLE FOR FOLLOWING NFPA 70
REQUIREMENTS.
12. LIGHTING
12.1 CONTRACTOR SHALL COORDINATE LOCATION
OF LIGHT FIXTURES WITH MECHANICAL
CONTRACTOR, PLUMBING CONTRACTOR, AND
FIRE PROTECTION CONTRACTOR PRIOR TO
INSTALLATION TO AVOID CONFLICT WITH
DUCTWORK, PIPING, AND SPRINKLER SYSTEM
COMPONENTS.
12.2 MANUFACTURERS: SUBJECT TO COMPLIANCE
WITH REQUIREMENTS, MANUFACTURERS
OFFERING PRODUCTS WHICH MAY BE
INCORPORATED IN THE WORK INCLUDE BUT
ARE NOT LIMITED TO THOSE LISTED IN THE
FIXTURE SCHEDULE: LIGHT FIXTURES SHALL
BE SUPPORTED FROM BUILDING STRUCTURE
INDEPENDENT OF THE GRID SYSTEM (2 POINTS
MINIMUM).
12.3 ALL LIGHT FIXTURE LAMPS USED IN THIS
PROJECT SHALL BE BY ONE MANUFACTURER.
ALL LAMPS OF A PARTICULAR TYPE SHALL BE
FROM ONE PRODUCTION RUN. ANSI C78.
13. LIGHTING CONTROLS
13.1 WHERE MORE THAN ONE SWITCH OR DIMMER
OCCURS AT A LOCATION, GANG THE
SWITCHES TOGETHER WITH A COMMON
JUNCTION BOX AND FACEPLATE.
13.2 WHERE OCCUPANCY SENSORS ARE USED IN
OPEN CONFIGURATIONS, CONTRACTOR SHALL
MASK LAST SENSOR AT EACH END TO
PREVENT PASSER-BY ACTIVATION OF LIGHTS.
13.3 TIMEOUT ON OCCUPANCY SENSORS SHALL BE
SET TO 10 MINUTES UNLESS OTHERWISE
NOTED.
14. RECEPTACLES
14.1 ALL RECEPTACLES LOCATED WITHIN 6'-0”
OF A SINK OR LAVATORY SHALL BE GFCI
RATED.
15. CONTRACTOR SHALL BE RESPONSIBLE FOR
PROPERLY BALANCING ALL BRANCH CIRCUITS
AMONG THE PHASES OF THE SYSTEM
ACCORDING TO NFPA 70.
16. PRIOR TO ENERGIZING OF ALL NEW FEEDERS,
CHECK ALL WIRE AND CABLE FOR CONTINUITY
FOR CIRCUITRY AND FOR SHORT CIRCUITS.
CORRECT ANY DEFICIENCIES PRIOR TO
ENERGIZING.
17. RECORD DRAWINGS
17.1 MAINTAIN A SET OF DRAWINGS ON SITE.
THESE DRAWINGS SHALL BE UPDATED
WITH ALL FORMAL FIELD CHANGES AND
OTHER PORTIONS OF THE WORK THAT
VARY SIGNIFICANTLY FROM THE
CONTRACT DOCUMENTS. INDICATE
ACTUAL ROUTING OF ALL MAIN SERVICE,
TRANSFORMER, AND PANELBOARD
FEEDERS.
17.2 DELIVER RECORD DRAWINGS TO OWNER
PRIOR TO CLOSEOUT OF CONSTRUCTION.
18. ALL MATERIALS AND LABOR SHALL BE
UNCONDITIONALLY WARRANTED FOR A PERIOD
OF ONE (1) YEAR FROM DATE OF SUBSTANTIAL
COMPLETION. SPECIFIC MANUFACTURER'S
EQUIPMENT WARRANTIES IN EXCESS OF ONE (1)
YEAR SHALL TAKE PRECEDENCE.
MANUFACTURER'S WARRANTIES SHALL BE
PROVIDED WHENEVER AVAILABLE AND
POSSIBLE. ALL EQUIPMENT SHALL BE NEW AND
UNUSED FROM THE FACTORY AND SHALL NOT
BE MODIFIED OR REBUILT..
GENERAL ELECTRICAL NOTES:
A AMPS, AMPERES
AB AS-BUILT
AC ALTERNATING CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING
JURISDICTION
AIC AMPERE INTERRUPTING
CAPACITY
AL ALARM
AM AMMETER
AT ASTRONOMIC TIMER
ATS AUTOMATIC TRANSFER
SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT
TELEVISION
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
ELECTRICAL ABBREVIATIONS:
CLR CLEARANCE
CPVC CHLORINATED
POLYVINYL CHLORIDE
CT CURRENT
TRANSFORMER
CTR COUNTER
CU COPPER
DC DIRECT CURRENT
DIA DIAMETER
DS DISCONNECT SWITCH
EA EACH
ELEC ELECTRICAL
EMER EMERGENCY
EMT ELECTRICAL METALLIC
TUBING
ES EMERGENCY STOP
FA FIRE ALARM
FACP FIRE ALARM CONTROL
PANEL
FC FULLY CLOSED
FLA FULL LOAD AMPS
FO FULLY OPEN
FU FUSE
GC GENERAL CONTRACTOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTOR
GND GROUND
HP HORSEPOWER
HZ HERTZ
IMC INTERMEDIATE METAL
CONDUIT
JB JUNCTION BOX
KVA KILO-VOLT AMP(S)
KW KILO-WATT
KWH KILO-WATT HOUR(S)
LTG LIGHTING
LTS LIGHTS
LO LOCKOUT
MC METAL-CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL
CENTER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTR METER
MTS MANUAL TRANSFER
SWITCH
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATED
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OC OVERCURRENT
OCPD OVERCURRENT
PROTECTION DEVICE
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PUSHBUTTON
PH PHASE
PNL PANELBOARD
POE POWERED OVER
ETHERNET
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA REMOTE
ANNUNCIATOR
RCC RELAY CONTROL
CABINET
REF REFERENCE
REQD REQUIRED
RMC RIGID METAL CONDUIT
SW SWITCH
SWB SWITCHBOARD
SWGR SWITCHGEAR
UC UNDER COUNTER
UL UNDERWRITERS
LABORATORY
UNO UNLESS NOTED
OTHERWISE
V VOLT(S)
VA VOLT-AMPERE(S)
VFD VARIABLE FREQUENCY
DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S)
WP WATER PROOF
XFMR TRANSFORMER
120V DUPLEX RECEPTACLE
SECURITY CAMERA
ELECTRICAL SYMBOL LEGEND
OBSTRUCTION LIGHT
AIR TERMINAL
JUNCTION BOXJ
Croft & Associates 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftae.com
OWNER
SHEET NO.
PROJECT NUMBER
SHEET TITLE
DRAWN:
1 2
B
A
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
C
D
E
F
G
H
I
J
K
L
M
N
Co py rig ht by
C ro ft
As so cia te s, P
C.
A ll r ig ht s re se rv ed
Th is do cu m en t i s pr op er ty o f C ro ft
As so cia te s, P
C.
I t i s to b e us ed o nl y fo r t he s pe cif ic pr oj ec t r ef er re d to o r i de nt ifie d he re in a nd is n ot to b e us ed o n ot he r p ro je ct s, in w ho le o r i n pa rt, e xc ep t b y th e ex pr es s wr itt en a gr ee m en t o f C ro ft
As so cia te s, P C.
TH
IS
S H
EE
T
PL
O
TS
O
N
2" x
4"
A N
SI
D
CHECKED:
1" 2"
3"
1/ 2"
/3
0/
0:
:4
AM
\\1
0.
0.
.9
0\ Pr oj ec ts \C
O M
M
ER
C
IA
L\
P
R O
JE
C
T
IN
-B O
X\
-2
F
AA
M ia m i E xe cu tiv e
AT
C T\
2.
D ra w in g
In fo
\c . R ev it\
-2
_F
AA
M ia m i E xe cu tiv e
AT
C
T_ E2
0.
rv t
E-001
ELECTRICAL NOTES
2019-245
RER RER
MIAMI EXECUTIVE AIRPORT
AIRPORT TRAFFIC CONTROL
TOWER FACILITY
REHABILITATION
FEDERAL AVIATION ADMINISTRATION
CENTRAL ACQUISTION, AAQ-520
1010 HILLWOOD PARKWAY
FT. WORTH, TX 76177-2324
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL LAMP VOLTAGE WATTAGE COMMENTS
A SURFACE MOUNTED LED FIXTURE RATED FOR WET LOCATIONS HUBBELL LIGHTING LSQ SERIES OR APPROVED EQUIVALENT LSQ1-25 SERIES WITH SILVER FINISH LED, 4000K 120/277V 25 W
ISSUANCE
No. Date Description
A 2019-12-20 CHECK SET
B 2020-01-10 65% CHECK SET
Level 1 0' - 0"
LEVEL 1
0'-0"
LEVEL 2
9'-10"
LEVEL 3
19'-8"
LEVEL 4
29'-6"
LEVEL 5
39'-4"
LEVEL 6
49'-2"
LEVEL 7
59'-0"
LEVEL 8
68'-10"
T.O. WINDOW
81'-11"
T.O. TOWER ROOF
84'-1"
CONTROL ROOM
FLOOR
72'-2"
EG ROOM
ELEVATOR
MACHINE ROOM
STAIR
ELEVATOR
LINK
RECEPTION
MANAGER
STORAGE /
BREAK ROOM
CONFERENCE
ROOM
AREA
SUPERVISOR
CORRIDOR
RESTROOM
RESTROOM
E-101
A A A A
Croft & Associates 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftae.com
OWNER
SHEET NO.
PROJECT NUMBER
SHEET TITLE
DRAWN:
1 2
B
A
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
C
D
E
F
G
H
I
J
K
L
M
N
Co py rig ht by
C ro ft
As so cia te s, P
C.
A ll r ig ht s re se rv ed
Th is do cu m en t i s pr op er ty o f C ro ft
As so cia te s, P
C.
I t i s to b e us ed o nl y fo r t he s pe cif ic pr oj ec t r ef er re d to o r i de nt ifie d he re in a nd is n ot to b e us ed o n ot he r p ro je ct s, in w ho le o r i n pa rt, e xc ep t b y th e ex pr es s wr itt en a gr ee m en t o f C ro ft
As so cia te s, P C.
TH
IS
S H
EE
T
PL
O
TS
O
N
2" x
4"
A N
SI
D
CHECKED:
1" 2"
3"
1/ 2"
/3
0/
0:
:4
AM
\\1
0.
0.
.9
0\ Pr oj ec ts \C
O M
M
ER
C
IA
L\
P
R O
JE
C
T
IN
-B O
X\
-2
F
AA
M ia m i E xe cu tiv e
AT
C T\
2.
D ra w in g
In fo
\c . R ev it\
-2
_F
AA
M ia m i E xe cu tiv e
AT
C
T_ E2
0.
rv t
E-101
FLOOR PLANS -
LIGHTING & POWER
2019-245
RER RER
MIAMI EXECUTIVE AIRPORT
AIRPORT TRAFFIC CONTROL
TOWER FACILITY
REHABILITATION
FEDERAL AVIATION ADMINISTRATION
CENTRAL ACQUISTION, AAQ-520
1010 HILLWOOD PARKWAY
FT. WORTH, TX 76177-2324
0 5 10 FT
3/16" = 1'-0"
E-101
TOWER ELEVATION - REFERENCE ONLY
10 FT50
1/4" = 1'-0"
E-101
FLOOR PLAN LEVEL 1 - LIGHTING & POWER
GENERAL NOTES:
KEY NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
CAB EQUIPMENT FIXTURE AND EXTERIOR CANOPY
LOCATIONS.
1. ROUTE #1/0 TINNED COPPER DOWN CONDUCTOR IN
1" PVC CONDUIT MOUNTED TO EXTERIOR OF TOWER
DOWN TO GROUND ROD AT GRADE TO MATCH
EXISTING INSTALLATION. SEE DETAIL 2/E-201 FOR
MORE INFORMATION.
2. CONNECT TO EXISTING BRANCH SERVING AREA.
3. ROUTE CONDUIT IN TOP CORNER OF DECK FLUTE.
SEE CANOPY SECTION DETAIL G14 ON SHEET A-351
FOR MORE INFORMATION.
4. INSTALL NEW SURFACE MOUNTED LIGHT FIXTURE
UNDER CANOPY.
X
PLAN
NORTH
4 4 4 4
ISSUANCE
No. Date Description
A 2019-12-20 CHECK SET
B 2020-01-10 65% CHECK SET
J
J
MECHANICAL
ROOM
MENS
RESTROOM
WOMENS
RESTROOM
ELEVATOR
STAIR
EXISTING
PANEL H
CAB
Croft & Associates 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftae.com
OWNER
SHEET NO.
PROJECT NUMBER
SHEET TITLE
DRAWN:
1 2
B
A
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
C
D
E
F
G
H
I
J
K
L
M
N
Co py rig ht by
C ro ft
As so cia te s, P
C.
A ll r ig ht s re se rv ed
Th is do cu m en t i s pr op er ty o f C ro ft
As so cia te s, P
C.
I t i s to b e us ed o nl y fo r t he s pe cif ic pr oj ec t r ef er re d to o r i de nt ifie d he re in a nd is n ot to b e us ed o n ot he r p ro je ct s, in w ho le o r i n pa rt, e xc ep t b y th e ex pr es s wr itt en a gr ee m en t o f C ro ft
As so cia te s, P C.
TH
IS
S H
EE
T
PL
O
TS
O
N
2" x
4"
A N
SI
D
CHECKED:
1" 2"
3"
1/ 2"
/3
0/
0:
:0
AM
\\1
0.
0.
.9
0\ Pr oj ec ts \C
O M
M
ER
C
IA
L\
P
R O
JE
C
T
IN
-B O
X\
-2
F
AA
M ia m i E xe cu tiv e
AT
C T\
2.
D ra w in g
In fo
\c . R ev it\
-2
_F
AA
M ia m i E xe cu tiv e
AT
C
T_ E2
0.
rv t
E-102
FLOOR PLANS - POWER
2019-245
RER RER
MIAMI EXECUTIVE AIRPORT
AIRPORT TRAFFIC CONTROL
TOWER FACILITY
REHABILITATION
FEDERAL AVIATION ADMINISTRATION
CENTRAL ACQUISTION, AAQ-520
1010 HILLWOOD PARKWAY
FT. WORTH, TX 76177-2324
GENERAL NOTES:
KEY NOTES:
1. PROVIDE AND INSTALL WALL MOUNTED DOME
CAMERA MOUNTED 7'-6" AFF ADJACENT TO CAB
ENTRY DOOR. TIE INTO EXISTING MONITOR SYSTEM
LOCATED ON THE CAB FLOOR. CAMERA
MANUFACTURER TO MATCH EXISTING CAMERAS IN
SPACE. PROVIDE CABLING/CONDUIT PER
MANUFACTURERS RECOMMENDATIONS. ROUTE
BRANCH CIRCUIT TO 20A/1P SPARE BREAKER #23 IN
EXISTING LOCKED PANEL H LOCATED ON 7TH FLOOR
UTILIZING 2#12, 1#12G IN 3/4"C.
2. PROVIDE AND INSTALL (2) ADDITIONAL COPPER AIR
TERMINALS AS INDICATED TO MATCH EXISTING AIR
TERMINALS ON CAB ROOF. MOUNT AIR TERMINALS
ON RIGID 10'-0" SUPPORT. BOND TERMINAL TO
GUARD RAIL AND OBSTRUCTION LIGHT ON CAB ROOF
WITH #1/0 TINNED COPPER CONDUCTOR. ROUTE
ADDITIONAL #1/0 TINNED COPPER DOWN
CONDUCTOR FROM TERMINAL TO DRIVEN GROUND
ROD AT GRADE BELOW UTILIZING 1" PVC CONDUIT
MOUNTED TO EXTERIOR OF TOWER TO MATCH
EXISTING INSTALLATION. SEE DETAIL 1/E-201 FOR
MORE INFORMATION.
3. REMOVE EXISTING OBSTRUCTION LIGHTS AND
REPLACE WITH NEW STRUCTURE MOUNTED
OBSTRUCTION LIGHT TO MATCH EXISTING.
RECONNECT TO EXISTING BRANCH CIRCUIT AND
PROVIDE ALL REQUIRED CONTROLS AND
INTERFACES FOR A COMPLETE AND OPERABLE
SYSTEM. SEE DETAIL 3/E-201 FOR MORE
INFORMATION.
4. ROUTE #1/0 TINNED COPPER DOWN CONDUCTOR
FROM CAB ROOF ACROSS CATWALK AND ROUTE
DOWN BUILDING UTILIZING 1" PVC CONDUIT TO
MATCH EXISTING INSTALLATION.
5. MOUNT RECEPTACLES IN KICKPLATE OF EXISTING
CONSOLE. ROUTE BRANCH CIRCUIT TO 20A/1P SPARE
BREAKER #9 IN EXISTING PANEL H LOCATED ON 7TH
FLOOR UTLIZING 2#12, 1#12G IN 3/4"C.
6. PROVIDE AND INSTALL 120V/1PH BRANCH CIRCUIT
FOR AUTOMATIC WINDOW WASHING POWER
PANEL. ROUTE BRANCH CIRCUIT TO 20A/1P SPARE
BREAKER #26 IN EXISTING PANEL H LOCATED ON 7TH
FLOOR UTILIZING 2#12, 1#12G IN 3/4"C. VERIFY EXACT
LOCATION OF CONTROL PANEL IN FIELD. PROVIDE
AND INSTALL ALL CONTROL CONDUITS AS REQUIRED
FOR A COMPLETE AND OPERABLE SYSTEM. REFER
TO PLUMBING SHEETS P-201 THROUGH P-204 FOR
MORE INFORMATION AND CONDUIT REQUIREMENTS.
COORDINATE EXACT LOCATION OF PANEL IN FIELD.
7. ROUTE #4/0 TINNED COPPER CONDUCTOR FROM
NEW COPPER AIR TERMINAL TO EXISTING AIR
TERMINAL ON ROOF TO MATCH EXISTING
INSTALLATION. SEE DETAIL 1/E-201 FOR MORE
INFORMATION.
8. CAB WINDOW WASHING CONTROL PANEL LOCATION.
COORDINATE EXACT LOCATION IN FIELD.
9. INSTALL NEW #4/0 BARE COPPER CONDUCTOR
AROUND PERIMETER OF CAB ROOF.
X
10 FT50
1/4" = 1'-0"
E-102
FLOOR PLAN LEVEL 7 - POWER
10 FT50
1/4" = 1'-0"
E-102
FLOOR PLAN CAB - POWER
10 FT50
1/4" = 1'-0"
E-102
FLOOR PLAN CAB ROOF - POWER
1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
CAB EQUIPMENT FIXTURE AND EXTERIOR CANOPY
LOCATIONS.
1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
CAB EQUIPMENT FIXTURE AND EXTERIOR CANOPY
LOCATIONS.
2. DOWN CONDUCTORS SHALL BE TINNED COPPER,
THOMPSON LIGHTNING PROTECTION, ZEUS 506T.
PLAN
NORTH
PLAN
NORTH
PLAN
NORTH
ISSUANCE
No. Date Description
A 2019-12-20 CHECK SET
B 2020-01-10 65% CHECK SET
0 2020-12-01 100% SUBMITTAL
B 2020-01-10 65% CHECK SET