RFI Set 2.pdf

PDF 46 KB Posted

Attached to
TMB ATCT Rehabilitation Federal contract opportunity
Solicitation number
697DCK-22-R-00166
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document contains a request for information and responses regarding repairs to the Miami Executive Airport Air Traffic Control Tower located in Miami, Florida. The Federal Aviation Administration is seeking proposals to repair the tower in accordance with specifications provided. A superintendent may serve as quality control manager but cannot fill the roles of project manager, superintendent, and quality control manager simultaneously. A LEED-certified coordinator is not required provided all specification and code requirements are met. Site photos from four years ago are provided for reference but may not reflect current conditions. Proposals are due by the date specified in the solicitation of record number 697DCK-22-R-00166. Questions regarding the request for information must be submitted to the contact provided by March 9, 2022.

View the file

Other files for this federal contract opportunity

Other files attached to TMB ATCT Rehabilitation, newest first.
File Type Posted
RFI Set 2 Photos.pdf PDF
697DCK-22-R-00166 Amend 0002.pdf PDF
RFI Set 1.pdf PDF
697DCK-22-R-00166 0001.pdf PDF
697DCK-22-R-00166 Final.pdf PDF
J4. Wage Rate.pdf PDF
J1. TMB ATCT Facility Rehab Final Specifications 12.01.20.pdf PDF
J1a. TMB - Addendum #1 - 031721.pdf PDF
J2. Operational Risk Management Plan.pdf PDF
L1. BidBond.pdf PDF
L2. TMB Past Performance Questionnaire.pdf PDF
J1b. TMB ATCT Facility Rehab Final Drawings 12.01.20.pdf PDF
L3. Price Proposal - TMB ATCT Rehab.xlsx XLSX spreadsheet
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Response Set #2 TMB ATCT Rehabilitation

697DCK-22-R-00166

Q1. As per spec 01 40 00, section 3.3. are we required to hire an independent QC organization?

R1. No an independent QC organization is not required

Q2. Can the superintendent performs the duties of the QCM?

R2. A superintendent may serve as QC manager; however, they may not serve the role of Project Manager, Superintendent and QC manager. If the superintendent becomes the QC manager, they assume all responsibilities of the QC manager as well.

Q3. Spec 017419 section 1.7. are we required to employ at LEED coordinator for this project?

R3. No, a LEED certified coordinator is not required as long as all requirements of the specification section are met and in compliance with local code, whichever is more stringent.

Q4. Do you have any photos of the roof that you can provide?

R4. Please see document entitled, “RFI Set 2 Photos”. Please note these photos are from four years ago and may not represent the most current condition.