J.02 Attachment 02 - Drawing [99 Pages].pdf
PDF 24 MB Posted
- Attached to
- (PROJ: 573-19-616) BB Correct Electrical Deficiencies (3-Year Test) Federal contract opportunity
- Solicitation number
- 36C24823R0042
About this file
This solicitation is for electrical deficiency corrective work at a Department of Veterans Affairs medical facility. The solicitation seeks proposals to correct electrical deficiencies through a three-year test contract at the Veterans Affairs Medical Center in Building 1. A site visit is scheduled for November 9th where attendees will park in a garage and meet in Conference Room EB59G-1 in the basement of the main building. Proposals for the work are due by November 28th and the work will be performed under the oversight of the Veterans Health Administration within Veterans Integrated Service Network 8.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| J.03 Attachment 03 - Specifications [23 Pages].pdf | ||
| J.11 Attachment 11 – Subcontractor Past Performance Consent Form [1 Page].pdf | ||
| J.07 Attachment 07 – Experience Modification Rate (EMR) [1 Page].docx | DOCX document | |
| J.10 Attachment 10 – Letter of Commitment Key Subcontractors [1 Page].pdf | ||
| J.01 Attachment 01 - Statement of Work [11 Pages].docx | DOCX document | |
| S02 - SF1449 - SOLICITATION - 36C24822R0167.pdf | ||
| J.08 Attachment 08 - Past Performance Questionnaire [5 Pages].docx | DOCX document | |
| J.09 Attachment 09 – Past Performance Survey [3 Pages].pdf | ||
| J.04 Attachment 04 - Wage Determination [5 Pages].pdf | ||
| J.06 Attachment 06 – Price Matrix [1 Page].xlsx | XLSX spreadsheet | |
| J.05 Attachment 05 - VHA Supplemental Contract Requirements for Combatting COVID-19 [1 Page].pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
SEE SHEET A001
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAG
T-3 T- 1A
T-7 T-
T-9
T-10
T-1
BLDG. 12
CLC
T-5
T-11 T-2
MEP
T-4
T-6
B30
G02
G03
G01
G1
WATER TANK
PUMP
HOUSE
B01
ACA
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Department of Veterans Affairs Medical Center
ABOVE GROUP
ENGINEERING
70 BIRCH ALLEY, SUITE 250
BEAVERCREEK OHIO, 45440
937.795.4440
ARCHITECTURE PLANNING INTERIOR DESIGN
524 FERNWOOD AVENUE
ALTAMONTE SPRINGS, FLORIDA 32701
407.830.6522 P
937.461.0260 F
RDC / JOHN POE ARCHITECTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:0
:5
P
M
Correct Electrical Deficiencies (3-Year Test)
12..2020
COVER SHEET
G001
MDMD
573-19-616
Gainesville, Florida
Correct Electrical Deficiencies (3-Year Test)
1601 SW Archer Rd Gainesville, FL 32608 PROJECT #: 573-19-616
100% CONSTRUCTION
DOCUMENTS
19019.00
G001 COVER SHEET
A101 B25 BATTERY CLOSET
S-101 STRUCTURAL SECTIONS & DETAILS MEP BUILDING ROOF
S-201 STRUCTURAL SECTIONS & DETAILS MEP BUILDING ROOF
M-000 MECHANICAL LEGENDS, SYMBOLS, & NOTES
MD101 MECHANICAL DEMO FLOOR/ROOF PLAN – BLDG. 25
MD102 MECHANICAL DEMO FLOOR/ROOF PLAN – MEP BLDG.
MD103 MECHANICAL DEMO FLOOR PLAN – ACA BLDG.
MH101 MECHANICAL NEW WORK FLOOR/ROOF PLAN – BLDG. 25
MH102 MECHANICAL NEW WORK FLOOR/ROOF PLAN – MEP BLDG.
MH103 MECHANICAL NEW WORK FLOOR PLAN – ACA BLDG.
M-201 MECHANICAL DETAILS
M-202 MECHANICAL DETAILS
M-301 MECHANICAL SCHEDULES
E-001 ELECTRICAL LEGENDS
E-002 ELECTRICAL GENERAL NOTES
E-003 ELECTRICAL SCHEDULES
ED101 ELECTRICAL DEMO FLOOR/ROOF PLAN - BLDG. 25
ED102 ELECTRICAL DEMO FLOOR/ROOF PLAN – MEP BLDG.
EP101 ELECTRICAL NEW WORK FLOOR/ROOF PLAN – BLDG. 25
EP102 ELECTRICAL NEW WORK FLOOR/ROOF PLAN – MEP BLDG.
EP103 ELECTRICAL NEW WORK FLOOR PLAN – ACA BLDG.
EP104 ELECTRICAL NEW WORK FLOOR PLAN – BED TOWER
EP105 ELECTRICAL NEW WORK FLOOR PLAN – BUILDING 1
GENERAL CONSTRUCTION NOTES
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO
BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE
SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT
THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,
HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS
AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT
DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL
WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS
SPECIFICALLY NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A
PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS
INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL
SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE
THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE
NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR
SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED
WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF
THE WALL.
12. CONTRACTOR TO COMPLY WITH VA CAMPUS COVID-19 REGULATIONS
INCLUDING DAILY SCREENING.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE
CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R.).
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,
INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA
PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE
ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,
TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND
DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13
WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS
TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT
EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED
WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH
ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT
ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF
NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO
REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW
MATERIALS.
DRAWING INDEX
GRAPHIC SYMBOLS
VICINITY MAP
Revisions Date
07.13.2021
305 EAST DR, SUITE H,
MELBOURNE, FLORIDA 32904
321.345.9026
10'-0"
1'-0" 1'-0"
B25-2
S1.0
Switchgear
B25-1
Battery Closet
B25-2
S1.0
4 7/8"
9.219.21
9.02
9.80
7.82
7.82
STRUCTURE ABOVE
FIN. CEILING
FLOOR SLAB
SEE SCHED.
S E
E S
C H
E D
U L E
F
2"
SEE
SCHED. 2"
S E
E S
C H
E D
U L E
SEE PLAN
1/2" 1/2"
H1
J1
8.02
9.21
9.80
8.02
9.09
9.21
9.80
9.08
7.82
7.82 1/2" 1/2"
ST
A
T E O F F L O R
ID
A
RE
G
IS
T E R E D A R C H
IT
EC
T
ROGE
R A R E P
ST
IEN
A R
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:0
:5
P
M
Correct Electrical Deficiencies (3-Year Test)
12..2020
B25 BATTERY CLOSET
A101
MDMD
573-19-616
Gainesville, Florida
100% CONSTRUCTION
DOCUMENTS
19019.00
Scale: 1/4" = 1'-0"1 B25 - Floor Plan
Scale: 1" = 1'-0"
Wall Types
A. All dimensions are taken to face of gypsum wallboard or unit masonry.
B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.
C. All wood blocking to be fire retardent treated.
D. All partitions shall be type 'S1.0' unless noted otherwise.
7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.
8.02 Hollow metal frame.
9.02 3 5/8" non-structural metal framing @ 16" o.c.
9.08 Metal framing box header.
9.09 Double metal framing at jambs, typ.
9.21 5/8" Type X gypsum board.
9.80 Acoustic insulation
NOTES
GENERAL NOTES
DOOR SCHEDULE
DOOR
BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION
FIRE
RATING
HDWE
SET REMARKSRM RM TYPE MAT'L
SIZE
TYPE MAT'L HEAD JAMB# W H T
ACA ACA EXT. F HM 2 3'-0" 7'-0" 1 3/4" 1 HM EXST. EXST. - 1 Existing HM frame to remain. See Mechanical ACA plan for door location.
B25-2 B25-2 B25-1 F WD 4 2'-3" 7'-0" 1 1/2" 1 HM 1 1 - 2
N.T.S.Scale:
DOOR TYPES
N.T.S.Scale:
H.M. FRAME TYPES
Scale: 1 1/2" = 1'-0"
H.M. FRAME DETAILS
Revisions Date
07.13.2021
20.1 19.1 18.3 18.1 17.6
W.1
U
V
T.1
T
17.1
S
AHU-66
MEP BUILDING ROOF PLAN
SCALE: 3/16" = 1'-0"
A S201
REF: ABOVE GROUP SHEET MH102
VA FORM 08 - 6231
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS
BI
M
- C or re ct E le ct ric al
D ef ic ie nc ie s/
C or re ct E le ct ric al
D ef ic ie nc ie s R
M
EP
FP
.rv t
/1
1/
:1 8:
P
M
573-19-616
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
0119039
Revisions Date
STRUCTURAL SECTIONS & DETAILS
MEP BUILDING ROOF
07/13/2021 AJN RP
S-101
SHEET LIST
Sheet Number Sheet Name
S-101 STRUCTURAL NOTES & MEP BLDG ROOF PLAN
S-201 STRUCTURAL SECTIONS & DETAILS MEB BLDG ROOF
GENERAL
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS IN THE FIELD AND
NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH FABRICATION AND
CONSTRUCTION.
2. ALL STRUCTURAL SHEETS SHALL BE USED IN CONJUNCTION WITH THE CIVIL, MECHANICAL, ELECTRICAL, AND PROJECT SPECIFICATIONS.
3. GOVERNING BUILDING CODES::
a. 2017 FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE LOCAL CODES
b. ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
4. DESIGN WIND LOADS ARE IN ACCORDANCE WITH ASCE 7-16 USING THE FOLLOWING CRITERIA:
a. RISK CATEGORY = III
b. ULTIMATE WIND SPEED, V ULT = 135 MPH
c. NOMINAL WIND SPEED, V ASD = 105 MPH
d. IMPORTANCE FACTOR = 1.15
e. EXPOSURE CATEGORY = B
f. INTERNAL PRESSURE COEFF. = +/-0.18 (ENCLOSED)
5. ALL DETAILS APPLY TO SIMILAR SITUATIONS UNLESS SPECIFICALLY NOTED OTHERWISE ELSEWHERE.
POST-INSTALLED AND ADHESIVE ANCHORS
1. ANCHORS AND ADHESIVE ANCHORING SYSTEMS MUST BE TESTED AND APPROVED USING ICC
EVALUATION SERVICE ACCEPTANCE CRITERIA,, INCLUDING ICC-ES AC193 "MECHANICAL ANCHORS IN CONCRETE ELEMENTS" OR ICC-ES AC308 'POST-INSTALLED ADHESIVE ANCHORS IN CONCRETE
ELEMENTS". CONCRETE SHALL BE CONSIDERED CRACKED. SUBMIT MANUFACTURER'S DATA AND
EVALUATION REPORT (ESR) FOR PROPOSED ANCHORS.
2. MECHANICAL ANCHORS TO CONCRETE SHALL BE AS SHOWN IN THE STRUCTURAL DETAILS, UNLESS
NOTED OTHERWISE. USE ONE OF THE FOLLOWING:
a. HILTI KWIK BOLT TZ EXPANSION ANCHORS
b. HILTI HDA UNDERCUT ANCHORS
c. POWERS POWER-STUD+ SD2 WEDGE EXPANSION ANCHORS
d. SIMPSON STRONG-BOLT 2 WEDGE ANCHORS
3. ADHESIVE ANCHORING OF RODS AND REINFORCING BAR TO CONCRETE SHALL BE AS SHOWN IN
THE STRUCTURAL DETAILS, UNLESS NOTED OTHERWISE. PROVIDE STANDARD HAS-E RODS AND
USE ONE OF THE FOLLOWING:
a. HILTI HY-200 HYBRID ADHESIVE ANCHORING SYSTEM
b. HILTI RE-500-SD EPOXY ADHESIVE ANCHORING SYSTEM
c. POWERS PE-1000+ EPOXY ADHESIVE ANCHORING SYSTEM
d. SIMPSON SET-XP EPOXY ANCHORING ADHESIVE
4. MINIMUM EMBEDMENT, UNLESS OTHERWISE NOTED, SHALL BE AS FOLLOWS:
a. 1/2" DIA OR #4 REBAR = 4 1/2" EMBED
b. 5/8" DIA OR #5 REBAR = 5 5/8" EMBED
c. 3/4" DIA OR #6 REBAR = 6 3/4" EMBED
d. 1" DIA OR #8 REBAR = 9" EMBED
5. ALL ANCHORS AND RELATED HARDWARE SHALL BE GALVANIZED OR STAINLESS STEEL.
AHU-66 ROOF SECTIONA
S-201 SCALE: 3/4" = 1'-0"
RTU-1
RTU-1 ROOF ATTACHMENT
SEE SECTION 1/S-201
AHU-66 ROOF UNIT ATTACHMENTB
S-201 SCALE: 1 1/2" = 1'-0"
EXISTING INSULATION
EXISTING ROOF
MEMBRANE
NEW 4x4 CANT STRIP
NEW RIGID INSULATION
#14x3
4" SELF DRILLING
SCREWS @ 24" O.C.
NEW 24 GA FLASHING
EQUIPMENT
BASE PANEL
RTU-1 EQUIPMENT
SEE MECHANICAL DRAWINGS
EXISTING CAST IN
PLACE ROOF SLAB
16 GA GALVINIZED
STRAP 18" O.C. MAX
#12 SELF DRILLING SCREWS S.S.
ADHESIVE ANCHORS
2"Ø STAINLESS STEEL
TOTAL 8 BOLTS REQUIRED
NOTE:
ALL ANCHORS SHALL BE LOCATED OVER
CIP RIBS AS SHOWN
#12 SELF DRILLING SCREWS S.S.
VA FORM 08 - 6231
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS
BI
M
- C or re ct E le ct ric al
D ef ic ie nc ie s/
C or re ct E le ct ric al
D ef ic ie nc ie s R
M
EP
FP
.rv t
/1
1/
:1 8:
P
M
573-19-616
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
0119039
Revisions Date
STRUCTURAL SECTIONS & DETAILS
MEP BUILDING ROOF
07/13/2021 AJN RP
S-101
SHEET LIST
Sheet Number Sheet Name
S-101 STRUCTURAL NOTES & MEP BLDG ROOF PLAN
S-201 STRUCTURAL SECTIONS & DETAILS MEB BLDG ROOF
DUCTWORK SYMBOLS
SYMBOL DESCRIPTION ABBR. DESCRIPTION
A/E ARCHITECT / ENGINEER
AHU AIR-HANDLING UNIT
AMP AMPERGE
BTUH BRITISH THERMAL UNIT PER HOUR
CD CONDENSATE
CD CONSTRUCTION DOCUMENTS
CFM CUBIC FEET PER MINUTE
CU CONDENSING UNIT
DD DESIGN DOCUMENTS
DEG DEGREE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
ENT ENTERING
(E) EXISTING
F FAHRENHEIT
FLA FULL LOAD AMPS
HOA HAND/OFF/AUTOMATIC
IN WG INCH WATER GAUGE
kW KILOWATT
LAT LEAVING AIR TEMPERATURE
MIN MINIMUM
NC NOISE CRITERIA
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
RA RETURN AIR
RLA RUN LOAD AMPERE
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
SUPPLY TOP REGISTER OR GRILLE (WALL
TYPE)
EXHAUST OR RETURN CEILING REGISTER OR
GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR
GRILLE (WALL TYPE)
EXHAUST OR RETURN REGISTER OR TOP
GRILLE (WALL TYPE)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-
OFF
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
DNUP RETURN DUCT (UP & DOWN)
FC
10x8
FLEXIBLE CONNECTION,
EQUIPMENT, VIBRATION, OR SEISMIC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x
DEPTH)
EXISTING DUCT TO REMAIN
VD
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
SUPPLY
RETURN45°
STANDARD BRANCH SUPPLY
OR RETURN, NO SPLITTER(45° TAP)
45°
MOTORIZED DAMPER
M
SYMBOL DESCRIPTION
PIPING SYMBOLS
CONDENSATECD
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
RISE OR DROP IN PIPE
CAPPED OUTLET
PIPE UP
PIPE DOWN
ABBREVIATIONS
WELDED STAINLESS STEEL DUCTWORK
SYMBOL DESCRIPTION
CONTROL SYMBOLS
ECC
IT CURRENT TRANSMITTER
INTEGRATE CONTROL POINT ON REMOTE GRAPHICS
WORKSTATION AT ENERGY CONTROL CENTER
T THERMOSTAT
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION.
COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH AS OFFSETS IN
PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR
INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC DUCT
CONSTRUCTION STANDARD.
4. PROVIDE 1.5R ELBOWS IN DUCTWORK AS INDICATED. IF 1.5R ELBOWS DO NOT FIT, PROVIDE 1.0R ELBOWS.
IF 1.0R ELBOWS DO NOT FIT, PROVIDE 90 DEGREE RECTANGULAR DUCT ELBOWS WITH TURNING VANES.
5. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT FURNISHED.
6. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER EQUIPMENT, FURNITURE, AND DOOR SWINGS.
7. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
8. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
9. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
PAINTED FLAT BLACK.
10. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
11. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR PROPER
DRAINAGE TO SUIT EQUIPMENT FURNISHED.
12. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
13. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS.
14. COORDINATE SIZE REQUIREMENTS OF ALL CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR-MOUNTED
EQUIPMENT.
15. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS AND
OTHER AIR DISTRIBUTION DEVICES.
16. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO FANS, AIR HANDLING UNITS, AND FAN COIL UNITS.
17. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CONNECTED.
18. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
GENERAL NOTES
DRAWING SYMBOLS
BASIC MATERIALS
EXISTING TO BE REMOVED (HEAVY, DASHED)
EXISTING TO REMAIN (THIN, HALFTONED LINE)
NEW (HEAVY, SOLID LINE)
26-SF 3
26-TU-I-I
DETAIL NUMBER DRAWING
DRAWING NUMBER WHERE SHOWN
SECTIONLETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN). AN "(E)" SHOWN IN FRONT OF
EQUIPMENT TAGS NOTIFIES THAT EQUIPMENT IS EXISTING
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
BUILDING NO. WHERE EQUIPMENT IS LOCATED
H4
H7
A
NUMBER WHERE DRAWN
TT TEMPERATURE TRANSMITTER
UC UNIT CONTROLLER
DUCT SMOKE DETECTOR
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:2
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL LEGENDS,
SYMBOLS, & NOTES
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
M-000
0119039
SHEET LIST
Sheet Number Sheet Name
M-000 MECHANICAL LEGENDS, SYMBOLS, & NOTES
MD101 MECHANICAL DEMO FLOOR/ROOF PLAN - BLDG. 25
MD102 MECHANICAL DEMO FLOOR/ROOF PLAN - MEP BLDG.
MD103 MECHANICAL DEMO FLOOR PLAN - ACA BLDG.
MH101 MECHANICAL NEW WORK FLOOR/ROOF PLAN - BLDG. 25
MH102 MECHANICAL NEW WORK FLOOR/ROOF PLAN - MEP BLDG.
MH103 MECHANICAL NEW WORK FLOOR PLAN - ACA BLDG.
M-201 MECHANICAL DETAILS
M-202 MECHANICAL DETAILS
M-301 MECHANICAL SCHEDULES
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SI
VAD.JELYK
MD101
MD101
KEY PLAN
SCOPE OF
WORK
(E)EF-11
B25 - FIRST FLOOR
47' - 9"
BLDG 25 ROOF
63' - 5"
2 2
B25 - FIRST FLOOR
47' - 9"
BLDG 25 ROOF
63' - 5"
2 3
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS 25
NOT SPRINKLERED
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:3
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL DEMO FLOOR/ROOF
PLAN - BLDG. 25
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
MD101
0119039
1/4" = 1'-0"MD101
1 MECHANICAL DEMO FLOOR PLAN - BLDG. 25
0 2' 4' 8' 12'
1/4" = 1'-0" N
CODED NOTES:
1. DEMOLISH EXISTING EXHAUST FAN, MESH SCREEN, AND DAMPER. DEMOLISH ASSOCIATED
ACCESSORIES AND CONTROLS. CAP EXISTING ROOF CURB UNTIL NEW FAN INSTALLATION.
2. PROVIDE SHEET METAL PANEL AND BLANK OFF EXISTING LOUVER. FIELD VERIFY EXACT LOUVER
DIMENSIONS FOR BLANK OFF PANEL.
3. EXISTING LOUVER ABOVE DOOR SHALL REMAIN.
XX
1/4" = 1'-0"MD101
4 MECHANICAL DEMO ROOF PLAN - BLDG. 25
1/4" = 1'-0"MD101
2 BLDG. 25 SECTION 1
1/4" = 1'-0"MD101
3 BLDG. 25 SECTION 2
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SI
KEY PLAN
SCOPE OF WORK
20.1 19.1 18.3 18.1 17.6
W.1
U
V
T.1
T
17.1
S
(E)EF-21
(E)EF-13
MD102
20.1 19.1 18.3 18.1 17.6
W.1
U
V
T.1
T
17.1
S
MD102
7 7
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS MEP
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:4
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL DEMO FLOOR/ROOF
PLAN - MEP BLDG.
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
MD102
0119039
0 2' 4' 8' 12'
1/4" = 1'-0" N
CODED NOTES:
1. DEMOLISH EXISTING EXHAUST FAN AND DAMPER. DEMOLISH ASSOCIATED ACCESSORIES AND
CONTROLS. CAP EXISTING ROOF CURB - REFER TO DETAIL.
2. PROVIDE SHEET METAL PANEL AND BLANK OFF EXISTING LOUVER. FIELD VERIFY EXACT LOUVER
DIMENSIONS FOR BLANK OFF PANEL.
3. DEMOLISH EXISTING EXHAUST FAN AND DAMPER. DEMOLISH ASSOCIATED ACCESSORIES AND
CONTROLS. EXISTING ROOF CURB SHALL REMAIN.
4. EXISTING HOOD TO REMAIN.
5. EXISTING TO REMAIN EXHAUST DUCTWORK ROUTED ON ROOF.
6. EXISTING LOUVER TO REMAIN.
7. EXISTING UNIT HEATER TO REMAIN.
XX
1/8" = 1'-0"MD102
3 MECHANICAL DEMO ROOF PLAN - MEP BLDG.
1/8" = 1'-0"MD102
1 MECHANICAL DEMO FLOOR PLAN - MEP BLDG.
N.T.S.MD102
2 MEP BLDG. PHOTO 1
N.T.S.MD102
4 MEP BLDG. PHOTO 2
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SCOPE OF
WORK
33 32 31
K.3
M
M.6
N
MD103
MD103
MD103
MD103
4 4
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS ACA
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:4
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL DEMO FLOOR PLAN -
ACA BLDG.
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
MD103
0119039
0 2' 4' 8' 12'
1/4" = 1'-0" N
1/4" = 1'-0"MD103
1 MECHANICAL DEMO FLOOR PLAN - ACA BLDG.
CODED NOTES:
1. PROVIDE SHEET METAL PANEL AND BLANK OFF EXISTING LOUVER. FIELD VERIFY EXACT LOUVER
DIMENSIONS FOR BLANK OFF PANEL.
2. PROVIDE SHEET METAL PANEL AND BLANK OFF EXISTING WALL GRILLE. FIELD VERIFY EXACT WALL
GRILLE DIMENSIONS FOR BLANK OFF PANEL.
3. EXISTING UNIT HEATER TO REMAIN.
4. REPLACE EXISTING LOUVERED METAL DOORS AND REPLACE WITH NEW, SOLID, INSULATED,
HOLLOW METAL DOORS. PROVIDE NEW HARDWARE TO MATCH EXISTING.
5. PROVIDE SHEET METAL PANEL AND BLANK OFF EXISTING LOUVER ABOVE DOUBLE DOORS. FIELD
VERIFY EXACT LOUVER DIMENSIONS FOR BLANK OFF PANEL.
XX
N.T.S.MD103
2 ACA BLDG. PHOTO 1
N.T.S.MD103
3 ACA BLDG. PHOTO 2
N.T.S.MD103
4 ACA BLDG. PHOTO 3
N.T.S.MD103
5 ACA BLDG. PHOTO 4
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SCOPE OF
WORK
AHU 67
CU 67
6ø EA
C 825 C 825
28x16 SA
T
C 100
C F
M
100 CFM 6
EXISTING ELECTRICAL GEAR
EXISTING ELECTRICAL GEAR
MH101
EXISTING BATTERIES
NEW BATTERY
STORAGE ROOM
C 825 C 825
2' - 10"
3' - 10"
MH101
24ø SA 22ø SA 18ø SA 14ø SA
EF 181
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS 25
NOT SPRINKLERED
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:4
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL NEW WORK
FLOOR/ROOF PLAN - BLDG. 25
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
MH101
0119039
0 2' 4' 8' 12'
1/4" = 1'-0" N
1/4" = 1'-0"MH101
1 MECHANICAL NEW WORK FLOOR PLAN - BLDG. 25
1/4" = 1'-0"MH101
2 MECHANICAL NEW WORK ROOF PLAN - BLDG. 25
CODED NOTES:
1. EQUIPMENT MOUNTED ON 4" CONCRETE PAD. CONCRETE PAD SHALL EXTEND 6" BEYOND
PERIMETER OF EQUIPMENT.
2. MANUFACTURER'S RECOMMENDED CLEARANCE.
3. EXPOSED SPIRAL DUCTWORK, DOUBLE-WALL INTERNALLY INSULATED. DUCTWORK SHALL BE
ROUTED TIGHT TO STRUCTURE ABOVE AND SHALL NOT BE ROUTED ABOVE ELECTRICAL
EQUIPMENT.
4. 3/4" CONDENSATE ROUTED FROM AHU-1 AND THRU WALL TO DISCHARGE 6" ABOVE SPLASHBLOCK.
CONDENSATE SHALL MAINTAIN A 1/8" SLOPE. SEAL WALL PENETRATION WATERTIGHT.
5. 6"Ø EA ROUTED UP TO EF 181 ON ROOF.
6. MAKEUP AIR THRU EXISTING LOUVER ABOVE DOOR. PROVIDE NEW 1" FILTER RACK ON BACK OF
EXISTING LOUVER AND PROVIDE WITH 1" GALVANIZED STEEL WASHABLE FILTER.
7. REFRIGERANT PIPING ROUTED TIGHT TO STRUCTURE. REFRIGERANT PIPING SHALL NOT BE ROUTED
OVER ELECTRICAL EQUIPMENT.
8. REFRIGERANT PIPING ROUTED TO AVOID ELECTRICAL EQUIPMENT.
9. EXISTING BATTERY ELECTRICAL EQUIPMENT. CONTRACTOR SHALL NOT INSTALL NEW UTILITIES
ABOVE EXISTING EQUIPMENT
10. EXISTING ELECTRICAL DISCONNECTS. CONTRACTOR SHALL NOT INSTALL NEW UTILITIES ABOVE
EXISTING DISCONNECTS.
11. ROUTED REFRIGERANT PIPING DOWN AND THRU WALL TO CU 67. SEAL WALL PENETRATION
WATERTIGHT.
12. EXHAUST DUCTWORK ROUTED AROUND EXISTING ELECTRICAL GEAR TO MAINTAIN PROPER
VERTICAL CLEARANCE FOR ELECTRICAL GEAR.
13. PROVIDE CURB ADAPTER FOR NEW EXHAUST FAN.
14. PROVIDE FLEXIBLE CONNECTION AT AHU DUCT CONNECTION.
XX
N.T.S.MH101
3 BLDG. 25 PHOTO 1
N.T.S.MH101
4 BLDG. 25 PHOTO 2
GENERAL NOTES:
1. BLDG. 25 PHOTO 2 SHOWN FOR REFERENCE FOR DUCTWORK ROUTING.
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SCOPE OF WORK
20.1 19.1 18.3 18.1 17.6
W.1
U
V
T.1
T
17.1
S
B 60002
T
IDU-1
IDU-2
MH102
T
MH102
20.1 19.1 18.3 18.1 17.6
W.1
U
V
T.1
T
17.1
S x3
S
A x3
R
A
AHU 66
ODU-1
M - MAIN FLOOR
88' - 9"
M - ROOF
108' - 1"
MEP Roof 66' - 1 1/32"
18.1
M - MAIN FLOOR
46' - 9 1/32"
36x18 SA 18x36 RA
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS MEP
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:4
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL NEW WORK
FLOOR/ROOF PLAN - MEP BLDG.
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
MH102
0119039
0 2' 4' 8' 12'
1/4" = 1'-0" N
1/8" = 1'-0"MH102
1 MECHANICAL NEW WORK FLOOR PLAN - MEP BLDG.
1/8" = 1'-0"MH102
2 MECHANICAL NEW WORK ROOF PLAN - MEP BLDG.
CODED NOTES:
1. UTILIZE EXISTING PENETRATION AND ROOF CURB. SEAL CURB WATER TIGHT.
2. NEW CONCENTRIC DIFFUSER. CONCENTRIC DIFFUSER SHALL BE MOUNTED TIGHT TO STRUCTURE
ABOVE ELECTRICAL CONDUIT, BUT SO THAT STRUCTURE DOES NOT AFFECT AIRFLOW.
3. MANUFACTURER'S RECOMMENDED CLEARANCE.
4. REFRIGERANT PIPING UP THRU EXISTING CAPPED ROOF CURB AND TO OUTDOOR UNIT.
5. ROUTE 3/4" CONDENSATE TO NEAREST ROOF DRAIN LOCATED PLAN EAST OF COLUMN LINE 17.1, ADJACENT TO EXISTING COOLING TOWER. SLOPE PIPING AT 1/8" AND PROVIDE PIPING SUPPORTS AS
REQUIRED.
6. INDOOR UNIT SHALL BE MOUNTED AT HEIGHT ABOVE ELECTRICAL GEAR BUT BELOW SUSPENDED
LIGHTING (APPROXIMATELY 9'-0" ABOVE FINISHED FLOOR).
7. 3/4" CONDENSATE ROUTED FROM IDU-2 ALONG WALL AND UNDER IDU-1. SLOPE PIPING AT 1/8".
8. REFRIGERANT PIPING ROUTED FROM IDU-2 ALONG WALL AND UNDER IDU-1.
9. REFRIGERANT PIPING ROUTED FROM IDU-1 ALONG WALL.
10. REFRIGERANT PIPING ROUTED UP WALL AND OVER TO EXISTING ROOF PENETRATION.
11. 3/4" CONDENSATE ROUTED FROM IDU-1 DOWN TO TIE INTO 3/4" CONDENSATE FROM IDU-2.
12. 3/4" CONDENSATE ROUTED DOWN AND THRU WALL TO DISCHARGE AT SPLASHBLOCK.
13. COORDINATE FINAL CONDENSATE ROUTING WITH EXISTING EQUIPMENT. PIPING SHALL NOT BE
ROUTED ABOVE ELECTRICAL EQUIPMENT.
14. EXISTING LOUVER TO REMAIN.
15. EXISTING TO REMAIN DUCTWORK ROUTED ON ROOF.
16. PROVIDE OUTDOOR RATED FLEXIBLE CONNECTION AT AHU DUCT CONNECTION AND SEALED WATER
TIGHT.
XX
1/4" = 1'-0"MH102
3 MECHANICAL SECTION - MEP BLDG.
N.T.S.MH102
4 MEP BLDG. PHOTO 1
GENERAL NOTES:
1. MEP BLDG. PHOTO 1 SHOWN FOR REFERENCE FOR ROUTING OF NEW CONDENSATE.
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SI
33 32 31
K.3
M
M.6
N
AHU 68
CU 68
C 900
C 900
C 900
C 900
C 900
2 1
EXISTING ELECTRICAL GEAR
EXISTING ELECTRICAL GEAR
18x30 SA
MH103
MH103
30x18 SA x1
S
A x1
S A x1
S
A x1
S A
T
5 6
KEY PLAN
SCOPE OF
WORK
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS ACA
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:5
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL NEW WORK FLOOR
PLAN - ACA BLDG.
CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
MH103
0119039
1/4" = 1'-0"MH103
1 MECHANICAL NEW WORK FLOOR PLAN - ACA BLDG.
0 2' 4' 8' 12'
1/4" = 1'-0" N
CODED NOTES:
1. EQUIPMENT MOUNTED ON 4" CONCRETE PAD. CONCRETE PAD SHALL EXTEND 6" BEYOND
PERIMETER OF EQUIPMENT.
2. MANUFACTURER'S RECOMMENDED CLEARANCE.
3. EXPOSED RECTANGULAR DUCTWORK, DOUBLE-WALL INTERNALLY INSULATED. DUCTWORK SHALL
NOT BE ROUTED ABOVE ELECTRICAL EQUIPMENT. DUCTWORK HEIGHT SHALL BE LOCATED ABOVE
ELECTRICAL GEAR AND ABOVE SUSPENDED LIGHTING. FINAL HEIGHT SHALL BE COORDINATED WITH
EXISTING SANITARY PIPING, SPRINKLER PIPING, AND ELECTRICAL CONDUIT.
4. 3/4" CONDENSATE AND REFRIGERANT PIPING ROUTED THRU EXISTING SHEET METAL/LOUVER.
CONDENSATE SHALL BE ROUTED AT 1/8" SLOPE AND SHALL DISCHARGE 6" ABOVE SPLASHBLOCK.
SEAL PENETRATION WATERTIGHT.
5. DUCTWORK SHALL BE ROUTED BELOW SANITARY PIPING.
6. DUCTWORK ROUTED UP AND ROUTED ACROSS ROOM ABOVE SANITARY PIPING AND BELOW FIRE
SPRINKLER PIPING.
7. PROVIDE FLEXIBLE CONNECTION AT AHU DUCT CONNECTION.
XX
N.T.S.MH103
4 ACA BLDG. PHOTO 1
GENERAL NOTES:
1. ACA PHOTO 3 & 4 SHOWN FOR REFERENCE FOR DUCTWORK ROUTING.
N.T.S.MH103
3 ACA BLDG. PHOTO 1
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
18 GAUGE STAINLESS STEEL STRAPS
1" WIDE MIN (DO NOT BLOCK ACCESS
PANELS) 2-MIN PER 4'0". WRAP
CONTINUOUS OVER CONDENSER AND
SECURE TO CONCRETE PAD WITH
1/4"X1-1/2" STAINLESS STEEL
CONCRETE SCREWS OR ANCHORS.
(EACH SIDE)
4" THK FIBERMESH
REINFORCED
CONCRETE PAD
6" MIN
ALL
SIDES
CONDENSING UNIT
PROVIDE 6" CLEAR GRAVEL
AROUND CONDENSER. SOD
THEREAFTER.
W
1/ 3W
R
1/ 3W1/2W
W
2/3W
R
W
R
VANE
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/6W.
NOTES:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS
ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS
RECOMMENDED BY SMACNA.
NOTES:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W
DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE
BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE TYPE.
W1
W
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON
FAN SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL
TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS
ON 12" [300mm]
CENTERS
RIVET ON 4"
[100mm]
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION OF
BOLT 1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL AS
SPECIFIED
1/2" 1 1/2"1/2"
CURB CAP
SEAL WITH APPROVED FIRE
STOPPING MATERIAL
GALV. SHEET METAL HOOD WITH
SOLDERED SEAMS.
SEAL OPENING WATER
TIGHT FOLLOWING
INSTALLATION OF
PIPING TWO PIECE PIPE CLAMP
INSULATED
REFRIGERANT PIPING
1-5/8", 16 GA. SPOT
WELDED CHANNELS
BACK TO BACK
PITCH
4"X4"X1/4" THICK ALUM. PLATE
ANCHORED TO ROOF DECK.
ANCHORS SHALL NOT
PENETRATE THE ROOF DECK
MORE THAN 3/4"
NOTES:
1. FLASH AROUND PIPING SUPPORT COLUMN
2. PIPING SHALL BE SLOPED TOWARD THE CONDENSING UNITS
EXISTING ROOF
TAPERED INSULATION
20 GAUGE GALVANIZED
SHEETMETAL COVER
SLOPE
1-1/2" LONG, ONE WAY
SECURITY SCREWS W/
WASHER, INSTALL EVERY 4" O.C.
SEAL WATERTIGHT
EXISTING ROOF
CURB
ROOF
SIZE CAPS TO FIT EXISTING ROOF CURBS; FIELD VERIFY
EXACT DIMENTIONS
6" R-19 FIBERGLASS BATT
INSULATION
22 GAIGE INSULATION
LINER
SILICONE CAULK SEAL-
CONTINUOUS BEAD
BETWEEN LINER CURB
EDGE & CAP
3/4" CDX PLYWOOD
1/4" THICK
WOOD SHIM
BAND
OVER 50"∅
HANGER RODS
BAND OF
SAME SIZE AS
HANGER STRAP
LOAD RATED
FASTENERS
50"∅ & UNDER
NOTE:
TABULATED DATA FROM SMACNA ALLOWS FOR DUCT
REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.
420ONE 1 x 18 GA STRAP36
TWO 1/2∅ RODS
TWO 3/8∅. RODS
ONE 1 x 16 GA STRAP
50 700
ONE 1 x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ∅
HANGER STRAPS OR RODS
MAX. LOAD
LBS.
MAX.
IN.
SPACING
IN. IN.
UNION
DRAIN PAN (FURNISHED
WITH UNIT)
PRIMER PLUG
CLEAN OUT
PITCH DOWN
TOWARD DRAIN
L DIMENSIONS:
L = H + J + PIPE DIAMETER
H = 1 INCH FOR EACH INCH OF NEGATIVE
PRESSURE (INTERNAL PLUS RETURN
STATIC PRESSURE) + 1 INCH
J = 1/2 H
H
J
EXTERIOR
BUILDING WALL
INSULATED PIPING
INSULATION
REFRIGERANT PIPING
FIRE RATED CAULK
7/8" MAX. ANNULAR SPACE
NOTE: NON-INSULATED PIPING SIMILAR.
REFER TO ARCHITECTURAL FOR
FLASHING AND SEALING
REQUIREMENTS OF PENETRATION
ON EXTERIOR SIDE OF WALL
INTERIOR
BUILDING WALL
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:3
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL DETAILS CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
M-201
0119039
N.T.S.
CU MOUNTED ON GRADE
N.T.S.
DUCTWORK RADIUS ELBOWS DETAIL
N.T.S.
DUCTWORK SQUARE VANE ELBOWS DETAIL
N.T.S.
FLEXIBLE DUCT CONNECTIONS DETAIL
N.T.S.
REGRIGERANT PIPING ROOF CAP DETAIL
N.T.S.
ROOF CURB CAP DETAIL
N.T.S.
ROUND DUCT HANGERS
N.T.S.
CONDENSATE DRAIN TRAP W/ FORMULA DETAIL
N.T.S.
PIPING PENETRATION DETAIL
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
PREFAB CURB BY EQUIP.
MFR.
12" MIN.
ROOF INSULATION
THICKNESS
VARIES
ROOF
SMOKE DETECTORS LOCATED IN AN
ACCESSIBLE LOCATION IN SA DUCT
J-BOX CONDUIT &
WIRE BY
DIV. 27
PACKAGED
A/C UNIT
ELECTRICAL
DISCONNECT AND
SERVICE
RECEPTACLE
RETURN AIR
CONNECTION
SUPPLY AIR
CONNECTION
NOTE: ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT HURRICANE
CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE.
MOTOR & DRIVE
U.L. APPROVED
ELECTRICAL DISCONNECT
BIRDSCREEN
SPONGE RUBBER PAD
(VIB. ISOL.)
EXISTING CURB
THERMAL &
ACOUSTICAL
INSULATION
BACKDRAFT
DAMPER
FLASHING
ROOF
CONSTRUCTION
EXHAUST
DUCTWORK
ALL ALUMINUM WHEEL
HUB & HOUSING
MOTOR DOME EXHAUST FAN
DISCHARGE
DOME
RING FLANGE. WELD
TO CURB CAP.
WEATHERPROOF GLASS
FAB. & MASTIC (2 LAYERS)
BETWEEN DUCT & RING
FLANGE COLLAR
GALV. METAL CURB
CAP. CROSS BREAK.
WELD CORNERS.
PRE-FAB ROOF CURB
CANT. (REF.)
ROOFING (REF.)
INSULATION (REF.)
STRUCTURAL DECK (REF.)
DUCT SUPPORT CLAMP
SECURE CURB TO
STRUCT. DECK.
8" M
IN
4" M
IN
WELDED STEEL ANGLE
SUPPORT. ATTACH TO CURB.
DUCT SUPPORT CLAMP
2" MIN.
DUCT
DUCT CLAMP
STEEL ANGLE
8" MIN.
NOTE:
1. ROUND DUCT SHOWN AS TYPICAL
2. SLOPE TOP OF DUCTWORK FROM PEAK
AT 10 DEGREESE FROM HORIZONTAL
ROOF SURFACE
PRE-FAB ROOF EQUIPMENT SUPPORT
(2) LAG SCREWS SILICONE CAULK
BENEATH HEAD BEFORE
TIGHTENING SIZE PER INSTALL
CLEARANCE REQUIREMENTS
FOR ROOFTOP EQUIPMENT
(DIMENSION A)
D
IM
E N
S
IO
N
A
WIDTH OF EQUIP.
(INCHES)
CLEARANCE
(INCHES)
UP TO 24
24 TO 36
37 TO 48
49 TO 60
61 & WIDER
SUPPLY AIR
RETURN AIR
PROVIDE FILTER SECTION WITH
HINGED ACCESS DOOR AND
LOCKS. PROVIDE 1" FILTER
RACK SECTION.
FLOOR SLAB
UNISTRUT P2481 PIPE
BRACKET ANCHOR UNISTRUT
SUPPORT TO FLOOR
CONDENSATE DRAIN
(INSULATED)
REFRIGERANT LINES
FLEX CONNECTION
4" CONCRETE HOUSEKEEPING
PAD. EXTEND 6" BEYOND
PERIMETER OF AHU
NOTE: AN OVERFLOW DEVICE SHALL
BE PROVIDED FOR CONDENSATE
CONTROL IN ACCORDANCE TO FBC -
MECHANICAL (2017) 307.2.3.
SIDE RETURN
SUPPLY DUCT
SINGLE CONTINUOUS
HANGER STRAP, ATTACH TO
STRUCTURE ABOVE.
LOUVERED SUPPLY
GRILLE WITH AIR
SCOOP
SUPPLY DUCT
SINGLE CONTINUOUS
HANGER STRAP, ATTACH
TO STRUCTURE ABOVE
LOUVERED SUPPLY
GRILLE WITH
OPPOSED BLADE
DAMPER.
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:3
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL DETAILS CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
M-202
0119039
N.T.S.
RTU INSTALLATION
N.T.S.
ROOF DOWNBLAST EXHAUST FAN DETAIL
N.T.S.
DUCT ROOF PENETRATION DETAIL
N.T.S.
ROOF DUCT SUPPORT DETIAL
N.T.S.
AHU INSTALL DETAIL
N.T.S.
EXPOSED DUCT SUPPLY GRILLE DETAIL
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
EF-1 SEQUENCE OF OPERATION
1. GENERAL
A. FAN IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. EF-1 SERVES BATTERY STORAGE IN
BLDG. 25.
B. FAN SHALL RUN CONTINUOUSLY.
2. GRAPHICAL USER INTERFACE
A. GRAPHIC DISPLAY: PROVIDE A COMPLETE GRAPHIC DISPLAY OF THE SYSTEM AT THE ECC. THE DISPLAY SHALL
SHOW ALARM CAPABILITIES FOR FAN STATUS AND AIRFLOW INTERRUPTION.
ECC
SST
IT
EF-1
FAN
C O
O
LI
N G
C O
IL
F
IL
T E
R
RA
ROOM TEMPERATURE SENSOR, WALL MOUNTED 48" AFF.
T
UC
AHU 66, 67, & 68 UNIT SEQUENCE OF OPERATION
E
LE
C T
R
IC
H
E A
T
IN
G C
O
IL
COMPRESSOR
IF APPLICABLE
TT
AHU 66, 67, & 68
ECC
SST
IT
SA
1. GENERAL
A. AIR HANDLING UNIT SHALL REMAIN OPERATIONAL AT ALL TIMES.
B. AIR HANDLING UNIT SHALL BE THERMOSTATICALLY CONTROLLED TO CYCLE WITH LOADS THRU ITS
FACTORY PROVIDED CONTROLLER.
C. ALARM IF SPACE TEMPERATURE IS OUTSIDE OF RANGES FOR MORE THAN 10 MINUTES (ADJUSTABLE).
2. GRAPHICAL USER INTERFACE
A. GRAPHIC DISPLAY: PROVIDE A COMPLETE GRAPHIC DISPLAY OF THE SYSTEM AT THE ECC. THE DISPLAY SHALL
SHOW ALARM CAPABILITIES FOR FAN STATUS AND AIRFLOW INTERRUPTION.
EXISTING
EXISTING ENGINEERING
CONTROL CENTER -
ECC
NETWORK
EXISTING COMMUNICATION NETWORK
CLOSEST
UPSTREAM DEVICE
TO AHU 66
BACNET
BUILDING
CONTROLLER
MSTP
COMMUNICATION
(TYPICAL)
NOTES:
1. REUSE EXISTING COMMUNICATION NETWORK.
2. EXISTING CONTROL SYSTEM SOFTWARE TO REMAIN.
UPGRADE GRAPHICS ACCORDINGLY.
3. CONTROL SYSTEM ARCHITECTURE SHOWN IS FOR
DESIGN INTENT OF CONTROL SYSTEM. CONTROLS
CONTRACTOR SHALL ALTER SYSTEM ARCHITECTURE
AS REQUIRED TO BEST FIT NEW CONTROL SYSTEM
AND TIE IN TO EXISTING SYSTEM.
4. ALL NEW EQUIPMENT SHALL BE BACNET COMPATIBLE.
5. ALL NEW CONTROL POINTS SHALL BE ABLE TO BE
MONITORED AND ADJUSTED FROM THE EXISTING
CONTROLS FRONT END.
AHU 66
(NEW)
CLOSEST
UPSTREAM DEVICE
TO AHU 67
1st DEVICE IN LINE
(EXISTING)
AHU 67
(NEW)
CLOSEST
UPSTREAM DEVICE
TO AHU 68
AHU 68
(NEW)
CLOSEST
UPSTREAM DEVICE
TO EF-1
EF-1
(NEW)
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VA Project No.
AG Project No.
Project Number
Building
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT Office of Construction and Facilities Management www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbounre, Florida 32904
PH: 321.345.9026
100% CONSTRUCTION
DOCUMENTS
B
IM
/0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s /0
C o rr e c t E le c tr ic a l D e fi c ie n c ie s R
M
E P
F P
.r v t
/1
/2
:2
:3
A
M
573-19-616
KYLE J .DAVIS, P.E.
FL License #84275
MECHANICAL SCHEDULES CORRECT ELECTRICAL
DEFICIENCIES
GAINESVILLE VA
07/13/2021 KJD MRK
M-301
0119039
MULTI-ZONE MINI-SPLIT DUCTLESS HEAT PUMP SCHEDULE
INDOOR UNIT OUTDOOR UNIT
MARK MODEL NO.
SA CFM
(MAX.)
TOTAL COOLING
CAPACITY (BTU/H)
TOTAL HEATING
CAPACITY (BTU/H)
UNIT ELECTRICAL
MARK MODEL NO.
NOM.
TONS
AMBIENT
TEMP. (°F)
UNIT ELECTRICAL
RATED
AMPS V/PH/HZ RATED AMPS MCA MOCP V/PH/HZ
IDU-1 ,2 LMN079HVT 250 7000 8100 0.4 208/1/60 ODU-1 LMU18CHV 1.3 95 11.1 13.3 20 208/1/60
AIR HANDLING UNIT SCHEDULE
MARK MODEL NO.
NOM.
TONS
SUPPLY FAN COOLING - DX HEATING COIL
WEIGHT
ELECTRICAL
SUPPLY
CFM
OUTSIDE AIR
CFM ESP (IN WG) MOTOR HP
EAT
(°F DB)
EAT
(°F WB)
MAX LAT
(°F DB)
TOT. CAP.
(MBH) REFRIGERANT TYPE
TOTAL CAP.
(KW) V/PH/HZ MCA MOP
AHU 67 TWE09044A 7.5 3300 NONE 1.0 3.0 76 63.7 55.0 89.8 R-410A ELETRIC 14.96 400 460/3/60 28 30
AHU 68 TWE12044A 10 4500 NONE 1.0 3.0 76 63.4 55.0 118.1 R-410A ELETRIC NONE 450 460/3/60 6 15
AIR-COOLED CONDENSING UNIT SCHEDULE
MARK MODEL NO. NOM. TONS
COMPRESSOR
QTY/RLA
FAN
QTY/FLA
REFRIGERANT
VOLTS/PH/HZ MCA MOP MIN. SEERTYPE GAS SIZE LIQUID SIZE
CU 67 TTA09044A 7.5 1/12.2 1/1.6 R-410A NOTE 2 NOTE 2 460/3/60 17 25 11.5
CU 68 TTA12044A 10 1/17.8 1/2.5 R-410A NOTE 2 NOTE 2 460/3/60 25 40 11.5
NOTES:
1. BASIS OF DESIGN MANUFACTURER IS TRANE.
2. SIZE REFRIGERANT LINES PER MANUFACTURER RECOMMENDATIONS. PROVIDE OVERSIZE LINES AND/OR REFRIGERATION LINE EXTENSION KIT BASED ON MANUFACTURERS RECOMMENDATIONS FOR EXTENDED
REFRIGERATION LINE RUNS.
3. AMBIENT DESIGN TEMPERATURE IS 95° F.
4. PROVIDE SINGLE POINT ELECTRICAL CONNECTION.
5. PROVIDE 5 YEAR COMPRESSOR WARRANTY.
6. PROVIDE ANTI-RECYCLE COMPRESSOR TIMER.
7. PROVIDE CONDENSER COIL GUARDS.
8. PROVIDE PROTECTIVE COATING ON CASING, BASE, FRAME AND CONDENSER COIL OF OUTSIDE CONDENSING UNIT. ACCEPTABLE PROVIDERS ARE GOLDFIN, BLYGOLD, LUVATA, AND BRONZ-GLOW. COIL COATING
SHALL BE APPLIED AFTER CONSTRUCTION OF THE COIL (COATED FIN STOCK IS NOT ACCEPTABLE). COATING SHALL BE DOCUMENTED TO ENDURE A MINIMUM OF 4,000 HOURS OF SALT SPRAY (ASTM B117).
COATING SHALL BE APPLIED BY THE FACTORY TRAINED AND CERTIFIED APPLICATOR.
NOTES:
1. BASIS OF DESIGN MANUFACTURER IS TRANE.
2. PROVIDE SIDE RETURN AND PROVIDE GRILLE AT RETURN INTAKE.
3. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. STARTER, RELAY, HEATING ELEMENT, AND CONTROLS SHALL BE PART OF PACKAGED UNIT.
4. PROVIDE WITH 30% EFFICIENCY FILTERS.
5. PROVIDE HEAD PRESSURE CONTROLLER FOR OPERATION IN AMBIENT TEMPERATURE DOWN TO 30° F.
6. SIZE REFRIGERANT LINES PER MANUFACTURER RECOMMENDATIONS FOR SPECIFIC REFRIGERANT LINE RUN.
7. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT. UNITS SHALL BE THERMOSTATICALLY CONTROLLED TO CYCLE WITH LOADS. NO ADDITIONAL CONTROLS ARE REQUIRED.
NOTES:
1. BASIS OF DESIGN MANUFACTURER IS LG.
2. INDOOR UNITS AND OUTDOOR UNITS POWERED INDIVIDUALLY. PROVIDE SINGLE POINT ELECTRICAL CONNECTION FOR EACH IDU AND ODU.
3. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.
4. PROVIDE LOW AMBIENT KIT FOR OPERATION IN AMBIENT TEMPERATURES DOWN TO 0° F.
5. SIZE REFRIGERANT LINES PER MANUFACTURER RECOMMENDATIONS. PROVIDE OVERSIZE LINES AND/OR REFRIGERATION LINE EXTENSION KIT BASED ON
MANUFACTURERS RECOMMENDATIONS FOR EXTENDED REFRIGERATION LINE RUNS.
6. PROVIDE 5 YEAR COMPRESSOR WARRANTY.
7. PROVIDE ANTI-RECYCLE COMPRESSOR TIMER.
8. PROVIDE CONDENSER COIL GUARDS.
9. PROVIDE PROTECTIVE COATING ON CASING, BASE, FRAME, AND CONDENSER COIL OF CONDENSING UNIT. ACCEPTABLE PROVIDERS ARE GOLDFIN, BLYGOLD, LUVATA, AND BRONZGLOW. COIL COATING SHALL BE APPLIED AFTER CONSTRUCTION OF THE COIL (COATED FIN STOCK IS NOT ACCEPTABLE). COATING SHALL BE DOCUMENTED TO ENDURE A MINIMUM OF 4,000 HOURS OF SALT SPRAY (ASTM B117). COATING SHALL BE APPLIED BY THE FACTORY TRAINED AND CERTIFIED
APPLICATOR.
10. PROVIDE 7 DAY PROGRAMMABLE THERMOSTAT. UNITS SHALL BE THERMOSTATICALLY CONTROLLED TO CYCLE WITH LOADS. NO ADDITIONAL CONTROLS ARE
REQUIRED.
AIR DISTRIBUTION SCHEDULE
MARK CFM NECK SIZE
FACE SIZE
LENGTH DESCRIPTION
A 0-950 18X12 18X12 SPIRAL DUCT SUPPLY GRILLE
BASIS OF DESIGN: PRICE - SDGE
COLOR: MATCH DUCTWORK
MATERIAL: ALUMINUM
AIR SCOOP: YES
B 0-6000 (2) 18X36 45.5X45.5 CONCENTRIC SUPPLY/RETURN DIFFUSER
BASIS OF DESIGN: RUSKIN - CDS-60
COLOR: WHITE
MATERIAL: ALUMINUM
OPPOSED BLADE DAMPER: NO
C 0-100 8X6 8X6 SIDEWALL EXHAUST GRILLE
BASIS OF DESIGN: PRICE - 80
COLOR: MATCH WALL
MATERIAL: ALUMINUM
OPPOSED BLADE DAMPER: NO
D 0-900 18X12 18X12 SUPPLY GRILLE
BASIS OF DESIGN: PRICE - 620DAL
COLOR: MATCH DUCT
MATERIAL: ALUMINUM
OPPOSED BLADE DAMPER: YES
EXHAUST FAN SCHEDULE
MARK BASIS OF DESIGN MODEL NO. TYPE CFM
ESP
(IN-WG)
FAN
RPM
ELECTRICAL DRIVE
TYPE
MAX
SONESHP NEC FLA V/PH/HZ
EF 181 GREENHECK G-097-VG CENTRIFUGAL
ROOF
100 0.3 917 1/4 2.85 115/1/60 DIRECT 3.0
NOTES:
1. PROVIDE FACTORY DISCONNECT SWITCH.
2. PROVIDE BACKDRAFT DAMPER.
3. EXHAUST FAN SHALL RUN CONTINUOUSLY.
4. PROVIDE MOTOR WITH SPEED CONTROL CAPABILITY.
5. PROVIDE SPARK PROOF FAN WITH EXPLOSION PROOF MOTOR.
6. PROVIDE ROOF CURB ADAPTOR.
7. EXHAUST FAN SHALL BE TIED INTO THE EXISTING ECC. REFER TO CONTROL DIAGRAM FOR CONTROL INFORMATION.
PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE
MARK
BASIS OF
DESIGN MODEL NO.
NOMINAL
TONS
SUPPLY FAN
OUTSIDE AIR
(CFM)
COOLING COIL - DX
ELECTRIC
HEAT
WEIGHT
(LBS)
ELECTRICAL
NOMINAL
CFM
ESP
(IN-WG)
MOTOR
HP
DRIVE
TYPE CFM
EAT
(F° DB)
EAT
(F° WB)
MAX. LAT
(F° DB)
GROSS TOTAL
MBH
GROSS
SENSIBLE MBH
AMBIENT TEMP.
(F°) REFRIGERANT
MIN. EFFICIENCY
(EER) V/PH/HZ MCA MOP
AHU 66 TRANE THD180 15.0 6000 1.0 3.0 BELT NONE 6000 76.0 62.8 54.9 165.8 136.9 100 R-410A 12.1 NONE 2500 460/3/60 33 45
NOTES:
1. PROVIDE SIDE SUPPLY DISCHARGE AND SIDE RETURN INTAKE CONNECTIONS.
2. PROVIDE FACTORY UNIT MOUNTED DISCONNECT WITH HOA SWITCH AND PILOT LIGHTS.
3. PROVIDE 115V DUPLEX GROUND FAULT PROTECTED ELECTRICAL OUTLET WITH POWER SUPPLY INDEPENDENT OF UNIT DISCONNECT.
4. PROVIDE PROTECTIVE COATING ON CASING, BASE, FRAME, AND CONDENSER COIL. ACCEPTABLE PROVIDERS ARE BLYGOLD, LUVATA AND BRONZ-GLOW. COIL COATING SHALL BE APPLIED AFTER CONSTRUCTION OF THE
COIL (COATED FIN STOCK IS NOT ACCEPTABLE). COATING SHALL BE DOCUMENTED TO ENDURE A MINIMUM OF 4,000 HOURS OF SALT SPRAY (ASTM B117). COATING SHALL BE APPLIED BY THE FACTORY OR BY A FACTORY
TRAINED AND CERTIFIED APPLICATOR.
5. PROVIDE MANUFACTURER'S INTEGRATED CONTROLS PACKAGE CAPABLE OF PROGRAMMABLE CONTROL.
6. PROVIDE PREFABRICATED ROOF CURB TO EXTEND A MINIMUM OF 8" ABOVE FINISHED ROOF.
7. PROVIDE PROTECTIVE COATING ON CASING, BASE, FRAME AND CONDENSER COIL OF OUTSIDE CONDENSING UNIT. ACCEPTABLE PROVIDERS ARE GOLDFIN, BLYGOLD, LUVATA, AND BRONZ-GLOW. COIL COATING SHALL
BE APPLIED AFTER CONSTRUCTION OF THE COIL (COATED FIN STOCK IS NOT ACCEPTABLE). COATING SHALL BE DOCUMENTED TO ENDURE A MINIMUM OF 4,000 HOURS OF SALT SPRAY (ASTM B117). COATING SHALL BE
APPLIED BY THE FACTORY TRAINED AND CERTIFIED APPLICATOR.
N.T.S.
EF-1 CONTROL DIAGRAM
3 N.T.S.
AIR HANDLING UNIT CONTROLS
2 N.T.S.
BACNET SYSTEM ARCHITECTURE
CODED NOTES:
1. CONTROLS PART OF "BID ALTERNATE NO. 1 - REMOVE AHU 66, 67, & 69 CONTROLS" INDICATED IN
SPECIFICATIONS.
XX
Revisions Date
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
ELECTRICAL ABBREVIATIONS
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND OR GENERATOR
GEN…