J-7 Specifications Vol II.pdf
PDF 7 MB Posted
- Attached to
- B2619 Dorm Construction Renovations
- Solicitation number
- FA448425R0003
About this file
This document appears to be the 100% Design Specifications Volume II for the B2619 Dorm Renovations project at Joint Base McGuire-Dix-Lakehurst in New Jersey. The project is a new construction requirement under Contract No. FA8903-21-D-0004, Task Order FA4484-23-F-0172.
The renovation work includes demolition, construction, and incidental related work for 63 bedrooms and 24,530 sq ft. Key aspects include relocation of existing hot water systems, installation of new chilled water system, fan coil units, HVAC controls, bathroom and bedroom refurbishment, telecom room relocation, hallway/public space refurbishments, new electrical service, LED lighting, fire alarm upgrades, and hazardous material remediation. There is one bid option that encompasses the entire dorm renovation. The project is an 8(a) competitive set-aside being procured by the Department of the Air Force's Air Mobility Command.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
100% Design Submission Specifications Volume II: Div. 23 – Div. 33
B2619 Dorm Renovations Title I A&E Services
Joint Base McGuire-Dix-Lakehurst, NJ
CONTRACT NO: FA8903-21-D-0004
TASK ORDER: FA4484-23-F-0172
100 Airside Drive Moon Township, PA 15108
WWW.MBAKERINTL.COM
22 March 2024
This Page Intentionally Left Blank
B2619 Dorm Renovations Joint Base McGuire-Dix-Lakehurst, NJ FA8903-21-D-0004 100% Design Submission
B2619 Dorm Renovations Joint Base McGuire-Dix-Lakehurst, NJ FA8903-21-D-0004 100% Design Submission
FA8903-21-D-0004
Joint Base McGuire-Dix-Lakehurst, NJ 100% Design Submission
DOCUMENT PROJECT Page 1
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 STATEMENT OF WORK
AF FORM 813
01 01 20 SPECIAL CONDITIONS
01 33 00 08/18, CHG 4: 02/21 SUBMITTAL PROCEDURES
01 33 29 02/21 SUSTAINABILITY REQUIREMENTS AND
REPORTING
01 35 26 11/20, CHG 4: 08/23 GOVERNMENTAL SAFETY REQUIREMENTS
01 35 60 STORM WATER POLLUTION PREVENTION
01 45 00 08/23 QUALITY CONTROL
01 54 00 AFFIRMATIVE PROCUREMENT
ENVIRONMENTAL COMPLIANCE
01 57 19 08/22 TEMPORARY ENVIRONMENTAL CONTROLS
HAZARDOUS MATERIALS REPORT
01 74 19 02/19, CHG 3: 11/21 CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL
01 78 00 05/19, CHG 1: 08/21 CLOSEOUT SUBMITTALS
01 78 23 05/23 OPERATION AND MAINTENANCE DATA
01 91 00.15 05/23, CHG 2: 11/23 BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 08/22 DEMOLITION AND DECONSTRUCTION
02 81 00 11/18 TRANSPORTATION AND DISPOSAL OF
HAZARDOUS MATERIALS
02 82 00 11/18, CHG 1: 11/19 ASBESTOS REMEDIATION
02 83 00 11/18 LEAD REMEDIATION
02 84 16 11/22 HANDLING OF LIGHTING BALLASTS AND
LAMPS CONTAINING PCBs AND MERCURY
02 85 00 11/18, CHG 1: 05/22 MOLD REMEDIATION
DIVISION 03 - CONCRETE
03 01 30.71 04/06 CONCRETE REHABILITATION
03 01 30.72 04/18 STRENGTHENING OF CAST-IN-PLACE CONCRETE
03 30 53 05/14 MISCELLANEOUS CAST-IN-PLACE CONCRETE
DIVISION 05 - METALS
05 12 00 08/18, CHG 2: 05/21 STRUCTURAL STEEL
05 40 00 05/15, CHG 1: 08/18 COLD-FORMED METAL FRAMING
05 51 33 02/16, CHG 2: 02/18 METAL LADDERS
05 52 00 08/23 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 08/16, CHG 2: 11/18 ROUGH CARPENTRY
06 41 16.00 10 08/10, CHG 1: 11/18 PLASTIC-LAMINATE-CLAD ARCHITECTURAL
CABINETS
06 61 16 08/20 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 84 00 05/10, CHG 1: 08/13 FIRESTOPPING
07 92 00 08/23 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 08/20 STEEL DOORS AND FRAMES
Joint Base McGuire-Dix-Lakehurst, NJ
DOCUMENT PROJECT Page 2
08 14 00 08/16, CHG 1: 08/18 WOOD DOORS
08 31 00 05/17, CHG 1: 08/18 ACCESS DOORS AND PANELS
08 71 00 02/16, CHG 4: 02/22 DOOR HARDWARE
08 87 23.13 08/09 SAFETY FILMS
DIVISION 09 - FINISHES
09 22 00 02/10, CHG 2: 08/18 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 08/16, CHG 4: 02/20 GYPSUM BOARD
09 30 10 08/20 CERAMIC TILING
09 51 00 08/20 ACOUSTICAL CEILINGS
09 62 38 08/17, CHG 1: 08/18 STATIC-CONTROL FLOORING
09 65 00 08/10, CHG 3: 08/18 RESILIENT FLOORING
09 90 00 02/21 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.20 08/20 INTERIOR SIGNAGE
10 26 00 08/20 WALL PROTECTION
10 28 13 08/20 TOILET ACCESSORIES
10 44 16 11/19 FIRE EXTINGUISHERS
DIVISION 12 - FURNISHINGS
12 21 00 08/17, CHG 2: 11/18 WINDOW BLINDS
DIVISION 22 - PLUMBING
22 00 00 11/15, CHG 4: 05/21 PLUMBING, GENERAL PURPOSE
22 07 19.00 40 02/23 PLUMBING PIPING INSULATION
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
COMMON PIPING FOR HVAC
VIBRATION AND SEISMIC CONTROLS FOR
HVAC PIPING AND EQUIPMENT
TESTING, ADJUSTING, AND BALANCING FOR
HVAC
THERMAL INSULATION FOR MECHANICAL
SYSTEMS
COMMISSIONING OF MECHANICAL AND
PLUMBING SYSTEMS
INSTRUMENTATION AND CONTROL FOR HVAC
INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC
CONTROL VALVES, SELF-CONTAINED
BACNET DIRECT DIGITAL CONTROL FOR HVAC
AND OTHER BUILDING CONTROL SYSTEMS
ELECTRIC AND ELECTRONIC CONTROL SYSTEM
FOR HVAC
SPACE TEMPERATURE CONTROL SYSTEMS
SEQUENCES OF OPERATION FOR HVAC CONTROL
FACILITY GAS PIPING
LOW TEMPERATURE WATER (LTW) HEATING
SYSTEM
HYDRONIC PUMPS
REFRIGERANT PIPING
HVAC AIR DISTRIBUTION
METAL DUCTS
23 05 15 05/22 23 05 48.00 40 05/22
23 05 93 11/15
23 07 00 02/13, CHG 7: 05/20
23 08 00 05/23
23 09 00 02/19, CHG 3: 05/21
23 09 13 11/15, CHG 2: 05/21
23 09 13.34 40 02/17
23 09 23.02 02/19, CHG 1: 02/20
23 09 33.00 40 11/20
23 09 53.00 20 02/10, CHG 2: 08/17
23 09 93 11/15
23 11 20 05/20
23 21 13.00 20 04/06, CHG 2: 11/19
23 21 23 08/17
23 23 00 08/21
23 30 00 05/20, CHG 1: 02/22
23 31 13.00 40 08/22
Joint Base McGuire-Dix-Lakehurst, NJ
DOCUMENT PROJECT Page 3
23 37 13.00 40 08/22 DIFFUSERS, REGISTERS, AND GRILLES
23 52 43.00 20 05/15, CHG 2: 08/18 LOW PRESSURE WATER HEATING BOILERS
23 82 19.00
05/17
(UNDER 800,000 BTU/HR OUTPUT)
FAN COIL UNITS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.01 05/21, CHG 1: 08/23 CYBERSECURITY FOR HVAC
FACILITY-RELATED CONTROL SYSTEMS
25 05 11.02 05/21, CHG 1: 08/23 CYBERSECURITY FOR FIRE PROTECTION
FACILITY-RELATED CONTROL SYSTEMS
25 05 11.03 05/21, CHG 1: 08/23 CYBERSECURITY FOR ELECTRICAL
FACILITY-RELATED CONTROL SYSTEMS
25 08 10 05/21 UTILITY MONITORING AND CONTROL SYSTEM
TESTING
25 10 10 02/19, CHG 1: 05/21 UTILITY MONITORING AND CONTROL SYSTEM
(UMCS) FRONT END AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 05 00.00 40 11/20 COMMON WORK RESULTS FOR ELECTRICAL
26.00
40 08/19
08/23
GROUNDING AND BONDING FOR ELECTRICAL
SYSTEMS
POWER SYSTEM STUDIES
26 20 00 08/23 INTERIOR DISTRIBUTION SYSTEM
26 24 16.00 40 08/19 PANELBOARDS
26 27 14.00 20 02/21, CHG 1: 05/21 ELECTRICITY METERING
02/20, 08/23
CHG 1: 05/21 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS
UNDER 600 VOLTS
LIGHTNING PROTECTION SYSTEM
26 51 00 05/20, CHG 2: 11/21 INTERIOR LIGHTING
26 56 00 08/21 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 10 00 08/11 BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 08/20 INTERIOR FIRE ALARM AND MASS
NOTIFICATION SYSTEM, ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00 08/23 EARTHWORK
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 31 19 DECORATIVE METAL FENCES AND GATES
32 92 19 08/17, CHG 1: 08/21 SEEDING
DIVISION 33 - UTILITIES
33 82 00 04/06 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents --
B2619 Dor m Renovat i ons Joi nt Base McGui r e- Di x- Lakehur st , NJ FA8903- 21- D- 0004 100% Desi gn Submi ssi on
SECTI ON 22 00 00
PLUMBI NG, GENERAL PURPOSE
11/ 15, CHG 4: 05/ 21
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )
ANSI Z21. 10. 1/ CSA 4. 1 ( 2019) Gas Wat er Heat er s Vol . I , St or age Wat er Heat er s wi t h I nput Rat i ngs of 75, 000 Bt u Per Hour or Less
ANSI Z21. 10. 3/ CSA 4. 3 ( 2019) Gas- Fi r ed Wat er Heat er s Vol . I I I , St or age Wat er Heat er s Wi t h I nput Rat i ngs Above 75, 000 Bt u Per Hour , Ci r cul at i ng and I nst ant aneous
ANSI Z21. 22/ CSA 4. 4 ( 2015; R 2020) Rel i ef Val ves f or Hot Wat er Suppl y Syst ems
AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG
ENGI NEERS ( ASHRAE)
ASHRAE 90. 1 - I P ( 2019) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs
AMERI CAN SOCI ETY OF MECHANI CAL ENGI NEERS ( ASME)
ASME A112. 1. 2 ( 2012; R 2017; R 2022) Ai r Gaps i n Pl umbi ng Syst ems ( For Pl umbi ng Fi xt ur es and Wat er - Connect ed Recept or s)
ASME A112. 6. 1M ( 1997; R 2017) Fl oor Af f i xed Suppor t s f or Of f - t he- Fl oor Pl umbi ng Fi xt ur es f or Publ i c Use
ASME A112. 6. 3 ( 2019) St andar d f or Fl oor and Tr ench Dr ai ns
ASME A112. 14. 1 ( 2003; R 2017; R 2022) Backwat er Val ves
ASME A112. 19. 2/ CSA B45. 1 ( 2018; ERTA 2018) St andar d f or Vi t r eous Chi na Pl umbi ng Fi xt ur es and Hydr aul i c Requi r ement s f or Wat er Cl oset s and Ur i nal s
ASME A112. 19. 3/ CSA B45. 4 ( 2022) St ai nl ess St eel Pl umbi ng Fi xt ur es
ASME A112. 36. 2M ( 1991; R 2017) Cl eanout s
ASME B1. 20. 1 ( 2013; R 2018) Pi pe Thr eads, Gener al Pur pose ( I nch)
SECTI ON 22 00 00 Page 1
ASME B16. 3 ( 2021) Mal l eabl e I r on Thr eaded Fi t t i ngs, Cl asses 150 and 300
ASME B16. 4 ( 2021) Gr ay I r on Thr eaded Fi t t i ngs;
Cl asses 125 and 250
ASME B16. 5 ( 2020) Pi pe Fl anges and Fl anged Fi t t i ngs NPS 1/ 2 Thr ough NPS 24 Met r i c/ I nch St andar d
ASME B16. 12 ( 2019) Cast I r on Thr eaded Dr ai nage Fi t t i ngs
ASME B16. 15 ( 2018) Cast Copper Al l oy Thr eaded Fi t t i ngs Cl asses 125 and 250
ASME B16. 18 ( 2021) Cast Copper Al l oy Sol der Joi nt Pr essur e Fi t t i ngs
ASME B16. 21 ( 2021) Nonmet al l i c Fl at Gasket s f or Pi pe Fl anges
ASME B16. 22 ( 2021) Wr ought Copper and Copper Al l oy Sol der Joi nt Pr essur e Fi t t i ngs
ASME B16. 23 ( 2021) Cast Copper Al l oy Sol der Joi nt Dr ai nage Fi t t i ngs - DWV
ASME B16. 24 ( 2022) Cast Copper Al l oy Pi pe Fl anges, Fl anged Fi t t i ngs, and Val ves Cl asses 150, 300, 600, 900, 1500, and 2500
ASME B16. 29 ( 2017) Wr ought Copper and Wr ought Copper Al l oy Sol der - Joi nt Dr ai nage Fi t t i ngs - DWV
ASME B16. 34 ( 2021) Val ves - Fl anged, Thr eaded and Wel di ng End
ASME B16. 39 ( 2020) St andar d f or Mal l eabl e I r on Thr eaded Pi pe Uni ons; Cl asses 150, 250, and 300
ASME B16. 50 ( 2021) Wr ought Copper and Copper Al l oy Br aze- Joi nt Pr essur e Fi t t i ngs
ASME B16. 51 ( 2013) Copper and Copper Al l oy Pr ess- Connect Pr essur e Fi t t i ngs
ASME B31. 1 ( 2022) Power Pi pi ng
ASME B31. 5 ( 2022) Ref r i ger at i on Pi pi ng and Heat Tr ansf er Component s
ASME B40. 100 ( 2022) Pr essur e Gauges and Gauge At t achment s
ASME BPVC SEC I V ( 2017) BPVC Sect i on I V- Rul es f or Const r uct i on of Heat i ng Boi l er s
ASME BPVC SEC I X ( 2017; Er r at a 2018) BPVC Sect i on I X- Wel di ng, Br azi ng and Fusi ng
SECTI ON 22 00 00 Page 2
Qual i f i cat i ons
ASME CSD- 1 ( 2021) Cont r ol and Saf et y Devi ces f or Aut omat i cal l y Fi r ed Boi l er s
AMERI CAN SOCI ETY OF SANI TARY ENGI NEERI NG ( ASSE)
ASSE 1001 ( 2021) Per f or mance Requi r ement s f or At mospher i c Type Vacuum Br eaker s
ASSE 1003 ( 2020) Per f or mance Requi r ement s f or Wat er Pr essur e Reduci ng Val ves f or Domest i c Wat er Di st r i but i on Syst ems - ( ANSI appr oved 2010)
ASSE 1010 ( 2021) Per f or mance Requi r ement s f or Wat er Hammer Ar r est er s
ASSE 1011 ( 2017) Per f or mance Requi r ement s f or Hose Connect i on Vacuum Br eaker s
ASSE 1012 ( 2023) Per f or mance Requi r ement s f or Backf l ow Pr event er wi t h an I nt er medi at e At mospher i c Vent
ASSE 1013 ( 2021) Per f or mance Requi r ement s f or Reduced Pr essur e Pr i nci pl e Backf l ow Pr event i on Assembl i es
ASSE 1018 ( 2001; R 2021) Per f or mance Requi r ement s f or Tr ap Seal Pr i mer Val ves - Pot abl e Wat er Suppl i ed ( ANSI Appr oved 2002
ASSE 1019 ( 2011; R 2016) Per f or mance Requi r ement s f or Wal l Hydr ant wi t h Backf l ow Pr ot ect i on and Fr eeze Resi st ance
ASSE 1020 ( 2020) Per f or mance Requi r ement s f or Pr essur e Vacuum Br eaker Assembl i es
ASSE 1037 ( 2015; R 2020) Per f or mance Requi r ement s f or Pr essur i zed Fl ushi ng Devi ces f or Pl umbi ng Fi xt ur es
AMERI CAN WATER WORKS ASSOCI ATI ON ( AWWA)
AWWA B300 ( 2018) Hypochl or i t es
AWWA B301 ( 2018) Li qui d Chl or i ne
AWWA C203 ( 2020) Coal - Tar Pr ot ect i ve Coat i ngs and Li ni ngs f or St eel Wat er Pi pel i nes - Enamel and Tape - Hot - Appl i ed
AWWA C606 ( 2022) Gr ooved and Shoul der ed Joi nt s
AWWA C651 ( 2014) St andar d f or Di s i nf ect i ng Wat er Mai ns
SECTI ON 22 00 00 Page 3
AWWA C652 ( 2019) Di s i nf ect i on of Wat er - St or age Faci l i t i es
AWWA C700 ( 2020) Col d- Wat er Met er s - Di spl acement Type, Met al Al l oy Mai n Case
AWWA C701 ( 2019) Col d- Wat er Met er s - Tur bi ne Type f or Cust omer Ser vi ce
AWWA D100 ( 2021) Wel ded St eel Tanks f or Wat er St or age
AMERI CAN WELDI NG SOCI ETY ( AWS)
AWS A5. 8/ A5. 8M ( 2019) Speci f i cat i on f or Fi l l er Met al s f or Br azi ng and Br aze Wel di ng
AWS B2. 2/ B2. 2M ( 2016) Speci f i cat i on f or Br azi ng Pr ocedur e and Per f or mance Qual i f i cat i on
ASTM I NTERNATI ONAL ( ASTM)
ASTM A47/ A47M ( 1999; R 2022; E 2022) St andar d Speci f i cat i on f or Fer r i t i c Mal l eabl e I r on Cast i ngs
ASTM A53/ A53M ( 2022) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess
ASTM A74 ( 2021) St andar d Speci f i cat i on f or Cast I r on Soi l Pi pe and Fi t t i ngs
ASTM A105/ A105M ( 2021) St andar d Speci f i cat i on f or Car bon St eel For gi ngs f or Pi pi ng Appl i cat i ons
ASTM A183 ( 2014; R 2020) St andar d Speci f i cat i on f or Car bon St eel Tr ack Bol t s and Nut s
ASTM A193/ A193M ( 2023) St andar d Speci f i cat i on f or Al l oy- St eel and St ai nl ess St eel Bol t i ng Mat er i al s f or Hi gh- Temper at ur e Ser vi ce and Ot her Speci al Pur pose Appl i cat i ons
ASTM A515/ A515M ( 2017; R2022) St andar d Speci f i cat i on f or Pr essur e Vessel Pl at es, Car bon St eel , f or I nt er medi at e- and Hi gher - Temper at ur e Ser vi ce
ASTM A516/ A516M ( 2017) St andar d Speci f i cat i on f or Pr essur e Vessel Pl at es, Car bon St eel , f or Moder at e-and Lower - Temper at ur e Ser vi ce
ASTM A518/ A518M ( 1999; R 2022) St andar d Speci f i cat i on f or Cor r osi on- Resi st ant Hi gh- Si l i con I r on Cast i ngs
ASTM A536 ( 1984; R 2019; E 2019) St andar d Speci f i cat i on f or Duct i l e I r on Cast i ngs
SECTI ON 22 00 00 Page 4
ASTM A733 ( 2016; R 2022) St andar d Speci f i cat i on f or Wel ded and Seaml ess Car bon St eel and Aust eni t i c St ai nl ess St eel Pi pe Ni ppl es
ASTM A888 ( 2021a) St andar d Speci f i cat i on f or Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
ASTM B32 ( 2020) St andar d Speci f i cat i on f or Sol der Met al
ASTM B42 ( 2020) St andar d Speci f i cat i on f or Seaml ess Copper Pi pe, St andar d Si zes
ASTM B43 ( 2020) St andar d Speci f i cat i on f or Seaml ess Red Br ass Pi pe, St andar d Si zes
ASTM B75/ B75M ( 2020) St andar d Speci f i cat i on f or Seaml ess Copper Tube
ASTM B88 ( 2022) St andar d Speci f i cat i on f or Seaml ess Copper Wat er Tube
ASTM B88M ( 2020) St andar d Speci f i cat i on f or Seaml ess Copper Wat er Tube ( Met r i c)
ASTM B117 ( 2019) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us
ASTM B152/ B152M ( 2019) St andar d Speci f i cat i on f or Copper Sheet , St r i p, Pl at e, and Rol l ed Bar
ASTM B306 ( 2020) St andar d Speci f i cat i on f or Copper Dr ai nage Tube ( DWV)
ASTM B370 ( 2022) St andar d Speci f i cat i on f or Copper Sheet and St r i p f or Bui l di ng Const r uct i on
ASTM B584 ( 2022) St andar d Speci f i cat i on f or Copper Al l oy Sand Cast i ngs f or Gener al Appl i cat i ons
ASTM B813 ( 2016) St andar d Speci f i cat i on f or Li qui d and Past e Fl uxes f or Sol der i ng of Copper and Copper Al l oy Tube
ASTM B828 ( 2016) St andar d Pr act i ce f or Maki ng Capi l l ar y Joi nt s by Sol der i ng of Copper and Copper Al l oy Tube and Fi t t i ngs
ASTM C564 ( 2020a) St andar d Speci f i cat i on f or Rubber Gasket s f or Cast I r on Soi l Pi pe and Fi t t i ngs
ASTM C920 ( 2018) St andar d Speci f i cat i on f or El ast omer i c Joi nt Seal ant s
ASTM C1053 ( 2000; R 2010) St andar d Speci f i cat i on f or
SECTI ON 22 00 00 Page 5
Bor osi l i cat e Gl ass Pi pe and Fi t t i ngs f or Dr ai n, Wast e, and Vent ( DWV) Appl i cat i ons
ASTM D638 ( 2014) St andar d Test Met hod f or Tensi l e Pr oper t i es of Pl ast i cs
ASTM D1004 ( 2013) I ni t i al Tear Resi st ance of Pl ast i c Fi l m and Sheet i ng
ASTM D1785 ( 2015; E 2018) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) , Pl ast i c Pi pe, Schedul es 40, 80, and 120
ASTM D2000 ( 2018) St andar d Cl assi f i cat i on Syst em f or Rubber Pr oduct s i n Aut omot i ve Appl i cat i ons
ASTM D2235 ( 2004; R 2016) St andar d Speci f i cat i on f or Sol vent Cement f or Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) Pl ast i c Pi pe and Fi t t i ngs
ASTM D2239 ( 2012) St andar d Speci f i cat i on f or Pol yet hyl ene ( PE) Pl ast i c Pi pe ( SI DR- PR) Based on Cont r ol l ed I nsi de Di amet er
ASTM D2241 ( 2015) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) Pr essur e- Rat ed Pi pe ( SDR Ser i es)
ASTM D2464 ( 2015) St andar d Speci f i cat i on f or Thr eaded Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pe Fi t t i ngs, Schedul e 80
ASTM D2466 ( 2017) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pe Fi t t i ngs, Schedul e 40
ASTM D2467 ( 2015) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pe Fi t t i ngs, Schedul e 80
ASTM D2564 ( 2020) St andar d Speci f i cat i on f or Sol vent Cement s f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pi ng Syst ems
ASTM D2657 ( 2007; R 2015) Heat Fusi on Joi ni ng Pol yol ef i n Pi pe and Fi t t i ngs
ASTM D2661 ( 2014; E 2018) St andar d Speci f i cat i on f or Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) Schedul e 40, Pl ast i c Dr ai n, Wast e, and Vent Pi pe and Fi t t i ngs
ASTM D2665 ( 2014) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Dr ai n, Wast e, and Vent Pi pe and Fi t t i ngs
ASTM D2672 ( 2014) Joi nt s f or I PS PVC Pi pe Usi ng Sol vent Cement
SECTI ON 22 00 00 Page 6
ASTM D2683 ( 2020) St andar d Speci f i cat i on f or Socket - Type Pol yet hyl ene Fi t t i ngs f or Out si de Di amet er - Cont r ol l ed Pol yet hyl ene Pi pe and Tubi ng
ASTM D2737 ( 2012a) Pol yet hyl ene ( PE) Pl ast i c Tubi ng
ASTM D2822/ D2822M ( 2005; R 2011; E 2011) St andar d Speci f i cat i on f or Asphal t Roof Cement , Asbest os- Cont ai ni ng
ASTM D2846/ D2846M ( 2019) St andar d Speci f i cat i on f or Chl or i nat ed Pol y( Vi nyl Chl or i de) ( CPVC) Pl ast i c Hot - and Col d- Wat er Di st r i but i on Syst ems
ASTM D2855 ( 2015) St andar d Pr act i ce f or Maki ng Sol vent - Cement ed Joi nt s wi t h Pol y( Vi nyl Chl or i de) ( PVC) Pi pe and Fi t t i ngs
ASTM D2996 ( 2017) St andar d Speci f i cat i on f or Fi l ament - Wound " Fi ber gl ass" ( Gl ass- Fi ber - Rei nf or ced Ther moset t i ng- Resi n) Pi pe
ASTM D3035 ( 2015) Pol yet hyl ene ( PE) Pl ast i c Pi pe ( DR- PR) Based on Cont r ol l ed Out si de Di amet er
ASTM D3122 ( 1995; R 2009) Sol vent Cement s f or St yr ene- Rubber ( SR) Pl ast i c Pi pe and Fi t t i ngs
ASTM D3138 ( 2004; R 2016) St andar d Speci f i cat i on f or Sol vent Cement s f or Tr ansi t i on Joi nt s Bet ween Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) and Pol y( Vi nyl Chl or i de) ( PVC) Non- Pr essur e Pi pi ng Component s
ASTM D3139 ( 2019) Joi nt s f or Pl ast i c Pr essur e Pi pes Usi ng Fl exi bl e El ast omer i c Seal s
ASTM D3212 ( 2020) St andar d Speci f i cat i on f or Joi nt s f or Dr ai n and Sewer Pl ast i c Pi pes Usi ng Fl exi bl e El ast omer i c Seal s
ASTM D3261 ( 2016) St andar d Speci f i cat i on f or But t Heat Fusi on Pol yet hyl ene ( PE) Pl ast i c Fi t t i ngs f or Pol yet hyl ene ( PE) Pl ast i c Pi pe and Tubi ng
ASTM D3311 ( 2017) St andar d Speci f i cat i on f or Dr ai n, Wast e, and Vent ( DWV) Pl ast i c Fi t t i ngs Pat t er ns
ASTM D4101 ( 2017) St andar d Cl assi f i cat i on Syst em and Basi s f or Speci f i cat i on f or Pol ypr opyl ene I nj ect i on and Ext r usi on Mat er i al s
SECTI ON 22 00 00 Page 7
ASTM D4551 ( 2017) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Fl exi bl e Conceal ed Wat er - Cont ai nment Membr ane
ASTM E1 ( 2014) St andar d Speci f i cat i on f or ASTM Li qui d- i n- Gl ass Ther momet er s
ASTM E96/ E96M ( 2022a; E 2023) St andar d Test Met hods f or Gr avi met r i c Det er mi nat i on of Wat er Vapor Tr ansmi ssi on Rat e of Mat er i al s
ASTM F437 ( 2021) St andar d Speci f i cat i on f or Thr eaded Chl or i nat ed Pol y( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe Fi t t i ngs, Schedul e 80
ASTM F438 ( 2017) St andar d Speci f i cat i on f or Socket - Type Chl or i nat ed Pol y( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe Fi t t i ngs, Schedul e 40
ASTM F439 ( 2019) St andar d Speci f i cat i on f or Chl or i nat ed Pol y( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe Fi t t i ngs, Schedul e 80
ASTM F441/ F441M ( 2023) St andar d Speci f i cat i on f or Chl or i nat ed Pol y( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe, Schedul es 40 and 80
ASTM F442/ F442M ( 2023) St andar d Speci f i cat i on f or Chl or i nat ed Pol y( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe ( SDR- PR)
ASTM F477 ( 2014; R 2021) St andar d Speci f i cat i on f or El ast omer i c Seal s ( Gasket s) f or Joi ni ng Pl ast i c Pi pe
ASTM F493 ( 2022) St andar d Speci f i cat i on f or Sol vent Cement s f or Chl or i nat ed Pol y ( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe and Fi t t i ngs
ASTM F628 ( 2022) St andar d Speci f i cat i on f or Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) Schedul e 40 Pl ast i c Dr ai n, Wast e, and Vent Pi pe wi t h a Cel l ul ar Cor e
ASTM F877 ( 2023) St andar d Speci f i cat i on f or Cr ossl i nked Pol yet hyl ene ( PEX) Pl ast i c Hot - and Col d- Wat er Di st r i but i on Syst ems
ASTM F891 ( 2016) St andar d Speci f i cat i on f or Coext r uded Pol y ( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pe wi t h a Cel l ul ar Cor e
ASTM F1290 ( 2019) St andar d Pr act i ce f or El ect r of usi on Joi ni ng Pol yol ef i n Pi pe and Fi t t i ngs
ASTM F1760 ( 2016; R 2020) St andar d Speci f i cat i on f or
SECTI ON 22 00 00 Page 8
Coext r uded Pol y( Vi nyl Chl or i de) ( PVC) Non- Pr essur e Pl ast i c Pi pe Havi ng Repr ocessed- Recycl ed Cont ent
ASTM F2389 ( 2023) St andar d Speci f i cat i on f or Pr essur e- r at ed Pol ypr opyl ene ( PP) Pi pi ng Syst ems
CAST I RON SOI L PI PE I NSTI TUTE ( CI SPI )
CI SPI 301 ( 2018) Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
CI SPI 310 ( 2012) Coupl i ng f or Use i n Connect i on wi t h Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
COPPER DEVELOPMENT ASSOCI ATI ON ( CDA)
CDA A4015 ( 2016; 14/ 17) Copper Tube Handbook
I NTERNATI ONAL ASSOCI ATI ON OF PLUMBI NG AND MECHANI CAL OFFI CI ALS
( I APMO)
I APMO PS 117 ( 2005b) Pr ess Type Or Pl ai n End Rub Gasket ed W/ Nai l CU & CU Al l oy Fi t t i ngs 4 I nst al l On CU Tubi ng
I NTERNATI ONAL CODE COUNCI L ( I CC)
I CC A117. 1 ( 2017) St andar d And Comment ar y Accessi bl e and Usabl e Bui l di ngs and Faci l i t i es
I CC I PC ( 2021) I nt er nat i onal Pl umbi ng Code
MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS
I NDUSTRY ( MSS)
MSS SP- 25 ( 2018) St andar d Mar ki ng Syst em f or Val ves, Fi t t i ngs, Fl anges and Uni ons
MSS SP- 44 ( 2019) St eel Pi pel i ne Fl anges
MSS SP- 58 ( 2018) Pi pe Hanger s and Suppor t s - Mat er i al s, Desi gn and Manuf act ur e, Sel ect i on, Appl i cat i on, and I nst al l at i on
MSS SP- 67 ( 2022) But t er f l y Val ves
MSS SP- 70 ( 2011) Gr ay I r on Gat e Val ves, Fl anged and Thr eaded Ends
MSS SP- 71 ( 2018) Gr ay I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
MSS SP- 72 ( 2010a) Bal l Val ves wi t h Fl anged or But t - Wel di ng Ends f or Gener al Ser vi ce
SECTI ON 22 00 00 Page 9
MSS SP- 78 ( 2011) Cast I r on Pl ug Val ves, Fl anged and Thr eaded Ends
MSS SP- 80 ( 2019) Br onze Gat e, Gl obe, Angl e and Check Val ves
MSS SP- 83 ( 2014) Cl ass 3000 St eel Pi pe Uni ons Socket Wel di ng and Thr eaded
MSS SP- 85 ( 2011) Gr ay I r on Gl obe & Angl e Val ves Fl anged and Thr eaded Ends
MSS SP- 110 ( 2010) Bal l Val ves Thr eaded, Socket - Wel di ng, Sol der Joi nt , Gr ooved and Fl ar ed Ends
NACE I NTERNATI ONAL ( NACE)
NACE SP0169 ( 2013) Cont r ol of Ext er nal Cor r osi on on Under gr ound or Submer ged Met al l i c Pi pi ng Syst ems
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
NEMA 250 ( 2020) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)
NEMA MG 1 ( 2021) Mot or s and Gener at or s
NEMA MG 11 ( 1977; R 2012) Ener gy Management Gui de f or Sel ect i on and Use of Si ngl e Phase Mot or s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 31 ( 2020) St andar d f or t he I nst al l at i on of Oi l - Bur ni ng Equi pment
NFPA 54 ( 2021) Nat i onal Fuel Gas Code
NFPA 90A ( 2024) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
NSF I NTERNATI ONAL ( NSF)
NSF 372 ( 2016) Dr i nki ng Wat er Syst em Component s - Lead Cont ent
NSF/ ANSI 14 ( 2022) Pl ast i cs Pi pi ng Syst em Component s and Rel at ed Mat er i al s
NSF/ ANSI 61 ( 2022) Dr i nki ng Wat er Syst em Component s - Heal t h Ef f ect s
PLASTI C PI PE AND FI TTI NGS ASSOCI ATI ON ( PPFA)
PPFA Fi r e Man ( 2016) Fi r est oppi ng: Pl ast i c Pi pe i n Fi r e Resi st i ve Const r uct i on
SECTI ON 22 00 00 Page 10
PLUMBI NG AND DRAI NAGE I NSTI TUTE ( PDI )
PDI WH 201 ( 2010) Wat er Hammer Ar r est er s St andar d
SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)
SAE J1508 ( 2023) Hose Cl amp Speci f i cat i ons
U. S. DEPARTMENT OF ENERGY ( DOE)
Ener gy St ar ( 1992; R 2006) Ener gy St ar Ener gy Ef f i c i ency Label i ng Syst em ( FEMP)
U. S. ENVI RONMENTAL PROTECTI ON AGENCY ( EPA)
EPA SM 9223 ( 2004) Enzyme Subst r at e Col i f or m Test
PL 93- 523 ( 1974; A 1999) Saf e Dr i nki ng Wat er Act
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
10 CFR 430 Ener gy Conser vat i on Pr ogr am f or Consumer Pr oduct s
21 CFR 175 I ndi r ect Food Addi t i ves: Adhesi ves and Component s of Coat i ngs
40 CFR 141. 80 Nat i onal Pr i mar y Dr i nki ng Wat er Regul at i ons; Cont r ol of Lead and Copper ;
Gener al Requi r ement s
UNDERWRI TERS LABORATORI ES ( UL)
UL 1951 ( 2011; Repr i nt Jun 2020) UL St andar d f or Saf et y El ect r i c Pl umbi ng Accessor i es
1. 2 SUBMI TTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Pl umbi ng Syst em; G
Det ai l dr awi ngs consi st i ng of schedul es, per f or mance char t s, i nst r uct i ons, di agr ams, and ot her i nf or mat i on t o i l l ust r at e t he r equi r ement s and oper at i ons of syst ems t hat ar e not cover ed by t he Pl umbi ng Code. Det ai l dr awi ngs f or t he compl et e pl umbi ng syst em i ncl udi ng pi pi ng l ayout s and l ocat i ons of connect i ons; di mensi ons f or r oughi ng- i n, f oundat i on, and suppor t poi nt s; schemat i c di agr ams and wi r i ng di agr ams or connect i on and i nt er connect i on di agr ams. Det ai l dr awi ngs shal l i ndi cat e c l ear ances r equi r ed f or mai nt enance and oper at i on. Wher e pi pi ng and equi pment ar e t o be suppor t ed ot her t han as i ndi cat ed, det ai l s shal l i ncl ude l oadi ngs and pr oposed suppor t met hods. Mechani cal dr awi ng pl ans, el evat i ons, v i ews, and det ai l s, shal l be dr awn t o scal e.
SECTI ON 22 00 00 Page 11
SD- 03 Pr oduct Dat a
Recycl ed Cont ent f or St eel Pi pe
Recycl ed Cont ent f or Cast I r on Pi pe
Backf l ow Pr event i on Assembl i es
Shower Faucet s; G
Wat er Sense Label f or Shower head
Fi xt ur es
Li st of i nst al l ed f i x t ur es wi t h manuf act ur er , model , and f l ow r at e.
Fl ush Tank Wat er Cl oset s
Fl ush Val ve Wat er Cl oset s
Wat er Sense Label f or Fl ush Tank Wat er Cl oset
Wat er Sense Label f or Fl ush Val ve Wat er Cl oset
Wal l Hung Lavat or i es
Count er t op Lavat or i es
Ser vi ce Si nks
Wat er Heat er s
Ener gy St ar Label f or Gas St or age Wat er Heat er
Pumps
Wel di ng
A copy of qual i f i ed pr ocedur es and a l i s t of names and i dent i f i cat i on symbol s of qual i f i ed wel der s and wel di ng oper at or s.
Vi br at i on- Absor bi ng Feat ur es; G
Det ai l s of v i br at i on- absor bi ng f eat ur es, i ncl udi ng ar r angement , f oundat i on pl an, di mensi ons and speci f i cat i ons.
Pl umbi ng Syst em
Di agr ams, i nst r uct i ons, and ot her sheet s pr oposed f or post i ng.
Manuf act ur er ' s r ecommendat i ons f or t he i nst al l at i on of bel l and spi got and hubl ess j oi nt s f or cast i r on soi l pi pe.
SD- 06 Test Repor t s
Test s, Fl ushi ng and Di si nf ect i on
Test r epor t s i n bookl et f or m showi ng al l f i el d t est s per f or med
SECTI ON 22 00 00 Page 12 t o adj ust each component and al l f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l i ndi cat e t he f i nal posi t i on of cont r ol s.
Test of Backf l ow Pr event i on Assembl i es; G.
Cer t i f i cat i on of pr oper oper at i on shal l be as accompl i shed i n accor dance wi t h st at e r egul at i ons by an i ndi v i dual cer t i f i ed by t he st at e t o per f or m such t est s. I f no st at e r equi r ement exi st s, t he Cont r act or shal l have t he manuf act ur er ' s r epr esent at i ve t est t he devi ce, t o ensur e t he uni t i s pr oper l y i nst al l ed and per f or mi ng as i nt ended. The Cont r act or shal l pr ovi de wr i t t en document at i on of t he t est s per f or med and si gned by t he i ndi v i dual per f or mi ng t he t est s.
SD- 07 Cer t i f i cat es
Mat er i al s and Equi pment
Wher e equi pment i s speci f i ed t o conf or m t o r equi r ement s of t he ASME Boi l er and Pr essur e Vessel Code, t he desi gn, f abr i cat i on, and i nst al l at i on shal l conf or m t o t he code.
Bol t s
Wr i t t en cer t i f i cat i on by t he bol t manuf act ur er t hat t he bol t s f ur ni shed compl y wi t h t he speci f i ed r equi r ement s.
SD- 10 Oper at i on and Mai nt enance Dat a
Pl umbi ng Syst em; G
1. 3 STANDARD PRODUCTS
Speci f i ed mat er i al s and equi pment shal l be st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of such pr oduct s.
Speci f i ed equi pment shal l essent i al l y dupl i cat e equi pment t hat has per f or med sat i sf act or i l y at l east t wo year s pr i or t o bi d openi ng.
St andar d pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year use shal l i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been f or sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2 year per i od.
1. 3. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a t wo- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er ' s f act or y or l abor at or y t est s, can be shown.
1. 3. 2 Ser vi ce Suppor t
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons. Submi t a cer t i f i ed l i s t of qual i f i ed per manent ser vi ce or gani zat i ons f or suppor t of t he equi pment whi ch i ncl udes t hei r addr esses and qual i f i cat i ons. These ser vi ce or gani zat i ons shal l be r easonabl y conveni ent t o t he equi pment
SECTI ON 22 00 00 Page 13 i nst al l at i on and abl e t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 3. 3 Manuf act ur er ' s Namepl at e
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be accept abl e.
1. 3. 4 Modi f i cat i on of Ref er ences
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on" , or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer .
1. 3. 4. 1 Def i ni t i ons
For t he I nt er nat i onal Code Counci l ( I CC) Codes r ef er enced i n t he cont r act document s, advi sor y pr ovi s i ons shal l be consi der ed mandat or y, t he wor d " shoul d" shal l be i nt er pr et ed as " shal l . " Ref er ence t o t he " code of f i c i al " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " For Navy owned pr oper t y, r ef er ences t o t he " owner " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " For l eased f aci l i t i es, r ef er ences t o t he " owner " shal l be i nt er pr et ed t o mean t he " l essor . " Ref er ences t o t he " per mi t hol der " shal l be i nt er pr et ed t o mean t he " Cont r act or . "
1. 3. 4. 2 Admi ni st r at i ve I nt er pr et at i ons
For I CC Codes r ef er enced i n t he cont r act document s, t he pr ovi s i ons of Chapt er 1, " Admi ni st r at or , " do not appl y. These admi ni st r at i ve r equi r ement s ar e cover ed by t he appl i cabl e Feder al Acqui s i t i on Regul at i ons ( FAR) i ncl uded i n t hi s cont r act and by t he aut hor i t y gr ant ed t o t he Of f i cer i n Char ge of Const r uct i on t o admi ni st er t he const r uct i on of t hi s pr oj ect . Ref er ences i n t he I CC Codes t o sect i ons of Chapt er 1, shal l be appl i ed appr opr i at el y by t he Cont r act i ng Of f i cer as aut hor i zed by hi s admi ni st r at i ve cogni zance and t he FAR.
1. 4 DELI VERY, STORAGE, AND HANDLI NG
Handl e, st or e, and pr ot ect equi pment and mat er i al s t o pr event damage bef or e and dur i ng i nst al l at i on i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons, and as appr oved by t he Cont r act i ng Of f i cer . Repl ace damaged or def ect i ve i t ems.
1. 5 PERFORMANCE REQUI REMENTS
1. 5. 1 Wel di ng
Pi pi ng shal l be wel ded i n accor dance wi t h qual i f i ed pr ocedur es usi ng per f or mance- qual i f i ed wel der s and wel di ng oper at or s. Pr ocedur es and wel der s shal l be qual i f i ed i n accor dance wi t h ASME BPVC SEC I X. Wel di ng pr ocedur es qual i f i ed by ot her s, and wel der s and wel di ng oper at or s qual i f i ed by anot her empl oyer , may be accept ed as per mi t t ed by ASME B31. 1.
The Cont r act i ng Of f i cer shal l be not i f i ed 24 hour s i n advance of t est s, and t he t est s shal l be per f or med at t he wor k s i t e i f pr act i cabl e. Wel der s or wel di ng oper at or s shal l appl y t hei r assi gned symbol s near each wel d
SECTI ON 22 00 00 Page 14 t hey make as a per manent r ecor d.
1. 6 REGULATORY REQUI REMENTS
Unl ess ot her wi se r equi r ed her ei n, pl umbi ng wor k shal l be i n accor dance wi t h I CC I PC.
1. 7 PROJECT/ SI TE CONDI TI ONS
The Cont r act or shal l become f ami l i ar wi t h det ai l s of t he wor k, ver i f y di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng any wor k.
1. 8 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
When speci f i ed i n ot her sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o t he desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance, i ncl udi ng per t i nent saf et y r equi r ement s, of t he speci f i ed equi pment or syst em.
I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal oper at i on and mai nt enance wor k.
I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual sect i on.
When mor e t han 4 man- days of i nst r uct i on ar e speci f i ed, use appr oxi mat el y hal f of t he t i me f or c l assr oom i nst r uct i on. Use ot her t i me f or i nst r uct i on wi t h t he equi pment or syst em.
When si gni f i cant changes or modi f i cat i ons i n t he equi pment or syst em ar e made under t he t er ms of t he cont r act , pr ovi de addi t i onal i nst r uct i on t o acquai nt t he oper at i ng per sonnel wi t h t he changes or modi f i cat i ons.
1. 9 ACCESSI BI LI TY OF EQUI PMENT
I nst al l al l wor k so t hat par t s r equi r i ng per i odi c i nspect i on, oper at i on, mai nt enance, and r epai r ar e r eadi l y accessi bl e. I nst al l conceal ed val ves, expansi on j oi nt s, cont r ol s, damper s, and equi pment r equi r i ng access, i n l ocat i ons f r eel y accessi bl e t hr ough access door s.
PART 2 PRODUCTS
2. 1 MATERI ALS
Mat er i al s f or var i ous ser vi ces shal l be i n accor dance wi t h TABLES I and I I .
St eel pi pe shal l cont ai n a mi ni mum of 25 per cent r ecycl ed cont ent , wi t h a mi ni mum of 16 per cent post - consumer r ecycl ed cont ent . Pr ovi de dat a i dent i f y i ng per cent age of r ecycl ed cont ent f or st eel pi pe. Pi pe schedul es shal l be sel ect ed based on ser vi ce r equi r ement s. Pi pe f i t t i ngs shal l be compat i bl e wi t h t he appl i cabl e pi pe mat er i al s. Pl ast i c pi pe, f i t t i ngs, and sol vent cement shal l meet NSF/ ANSI 14 and shal l be NSF l i st ed f or t he ser vi ce i nt ended. Pl ast i c pi pe, f i t t i ngs, and sol vent cement used f or pot abl e hot and col d wat er ser vi ce shal l bear t he NSF seal " NSF- PW. " Pol ypr opyl ene pi pe and f i t t i ngs shal l conf or m t o di mensi onal r equi r ement s of Schedul e 40, I r on Pi pe si ze and shal l compl y wi t h NSF/ ANSI 14, NSF/ ANSI 61 and ASTM F2389. Pol ypr opyl ene pi pi ng t hat wi l l be exposed t o UV l i ght shal l be pr ovi ded wi t h a Fact or y appl i ed UV r esi st ant coat i ng.
SECTI ON 22 00 00 Page 15
Pi pe t hr eads ( except dr y seal ) shal l conf or m t o ASME B1. 20. 1. Gr ooved pi pe coupl i ngs and f i t t i ngs shal l be f r om t he same manuf act ur er . Mat er i al or equi pment cont ai ni ng a wei ght ed aver age of gr eat er t han 0. 25 per cent l ead shal l not be used i n any pot abl e wat er syst em i nt ended f or human consumpt i on, and shal l be cer t i f i ed i n accor dance wi t h NSF/ ANSI 61, Annex G or NSF 372. I n l i ne devi ces such as wat er met er s, bui l di ng val ves, check val ves, met er st ops, val ves, f i t t i ngs and back f l ow pr event er s shal l compl y wi t h PL 93- 523 and NSF/ ANSI 61, Sect i on 8. End poi nt devi ces such as dr i nki ng wat er f ount ai ns, l avat or y f aucet s, k i t chen and bar f aucet s, r esi dent i al i ce maker s, suppl y st ops and end poi nt cont r ol val ves used t o di spense wat er f or dr i nki ng must meet t he r equi r ement s of NSF/ ANSI 61, Sect i on 9. Hubl ess cast - i r on soi l pi pe shal l not be i nst al l ed under gr ound, under concr et e f l oor s l abs, or i n cr awl spaces bel ow ki t chen f l oor s. Cast - i r on pi pe shal l cont ai n a mi ni mum of 95 per cent r ecycl ed cont ent . Pr ovi de dat a i dent i f y i ng per cent age of r ecycl ed cont ent f or cast i r on pi pe. Pl ast i c pi pe shal l not be i nst al l ed i n ai r pl enums. Pl ast i c pi pe shal l not be i nst al l ed i n a pr essur e pi pi ng syst em i n bui l di ngs gr eat er t han t hr ee st or i es i ncl udi ng any basement l evel s.
2. 1. 1 Pi pe Joi nt Mat er i al s
Gr ooved pi pe and hubl ess cast - i r on soi l pi pe shal l not be used under gr ound. Sol der cont ai ni ng l ead shal l not be used wi t h copper pi pe.
Cast i r on soi l pi pe and f i t t i ngs shal l be mar ked wi t h t he col l ect i ve t r ademar k of t he Cast I r on Soi l I nst i t ut e. Joi nt s and gasket mat er i al s shal l conf or m t o t he f ol l owi ng:
a. Coupl i ng f or Cast - I r on Pi pe: f or hub and spi got t ype ASTM A74, AWWA C606. For hubl ess t ype: CI SPI 310
b. Coupl i ng f or St eel Pi pe: AWWA C606.
c. Coupl i ngs f or Gr ooved Pi pe: Duct i l e I r on ASTM A536 ( Gr ade 65- 45- 12) Mal l eabl e I r on ASTM A47/ A47M, Gr ade 32510.
d. Fl ange Gasket s: Gasket s shal l be made of non- asbest os mat er i al i n accor dance wi t h ASME B16. 21. Gasket s shal l be f l at , 1/ 16 i nch t hi ck, and cont ai n Ar ami d f i ber s bonded wi t h St yr ene But adi ene Rubber ( SBR) or Ni t r o But adi ene Rubber ( NBR) . Gasket s shal l be t he f ul l f ace or sel f cent er i ng f l at r i ng t ype. Gasket s used f or hydr ocar bon ser vi ce shal l be bonded wi t h NBR.
e. Br azi ng Mat er i al : Br azi ng mat er i al shal l conf or m t o AWS A5. 8/ A5. 8M, BCuP- 5.
f . Br azi ng Fl ux: Fl ux shal l be i n past e or l i qui d f or m appr opr i at e f or use wi t h br azi ng mat er i al . Fl ux shal l be as f ol l ows: l ead- f r ee; have a 100 per cent f l ushabl e r esi due; cont ai n s l i ght l y aci di c r eagent s;
cont ai n pot assi um bor i des; and cont ai n f l uor i des.
g. Sol der Mat er i al : Sol der met al shal l conf or m t o ASTM B32.
h. Sol der Fl ux: Fl ux shal l be l i qui d f or m, non- cor r osi ve, and conf or m t o ASTM B813, St andar d Test 1.
i . PTFE Tape: PTFE Tape, f or use wi t h Thr eaded Met al or Pl ast i c Pi pe.
j . Rubber Gasket s f or Cast - I r on Soi l - Pi pe and Fi t t i ngs ( hub and spi got t ype and hubl ess t ype) : ASTM C564.
SECTI ON 22 00 00 Page 16
k. Rubber Gasket s f or Gr ooved Pi pe: ASTM D2000, maxi mum t emper at ur e 230 degr ees F.
l . Fl exi bl e El ast omer i c Seal s: ASTM D3139, ASTM D3212 or ASTM F477.
m. Bol t s and Nut s f or Gr ooved Pi pe Coupl i ngs: Heat - t r eat ed car bon st eel , ASTM A183.
n. Sol vent Cement f or Tr ansi t i on Joi nt s bet ween ABS and PVC Nonpr essur e Pi pi ng Component s: ASTM D3138.
o. Pl ast i c Sol vent Cement f or ABS Pl ast i c Pi pe: ASTM D2235.
p. Pl ast i c Sol vent Cement f or PVC Pl ast i c Pi pe: ASTM D2564 and ASTM D2855.
q. Pl ast i c Sol vent Cement f or CPVC Pl ast i c Pi pe: ASTM F493.
r . Fl anged f i t t i ngs i ncl udi ng, but not l i mi t ed t o, f l anges, bol t s, nut s and bol t pat t er ns shal l be i n accor dance wi t h ASME B16. 5 c l ass 150 and shal l have t he manuf act ur er ' s t r ademar k af f i xed i n accor dance wi t h MSS SP- 25. Fl ange mat er i al shal l conf or m t o ASTM A105/ A105M. Bl i nd f l ange mat er i al shal l conf or m t o ASTM A516/ A516M col d ser vi ce and ASTM A515/ A515M f or hot ser vi ce. Bol t s shal l be hi gh st r engt h or i nt er medi at e st r engt h wi t h mat er i al conf or mi ng t o ASTM A193/ A193M.
s. Pl ast i c Sol vent Cement f or St yr ene Rubber Pl ast i c Pi pe: ASTM D3122.
t . Pr ess f i t t i ngs f or Copper Pi pe and Tube: Copper pr ess f i t t i ngs shal l conf or m t o t he mat er i al and si z i ng r equi r ement s of ASME B16. 51 and per f or mance cr i t er i a of I APMO PS 117. Seal i ng el ement s f or copper pr ess f i t t i ngs shal l be EPDM, FKM or HNBR. Seal i ng el ement s shal l be f act or y i nst al l ed or an al t er nat i ve suppl i ed f i t t i ng manuf act ur er .
Seal i ng el ement shal l be sel ect ed based on manuf act ur er ' s appr oved appl i cat i on gui del i nes.
u. Copper t ubi ng shal l conf or m t o ASTM B88, Type K, L or M.
v. Heat - f usi on j oi nt s f or pol ypr opyl ene pi pi ng: ASTM F2389.
2. 1. 2 Mi scel l aneous Mat er i al s
Mi scel l aneous mat er i al s shal l conf or m t o t he f ol l owi ng:
a. Wat er Hammer Ar r est er : PDI WH 201. Wat er hammer ar r est er shal l be di aphr agm t ype.
b. Copper , Sheet and St r i p f or Bui l di ng Const r uct i on: ASTM B370.
c. Asphal t Roof Cement : ASTM D2822/ D2822M.
d. Hose Cl amps: SAE J1508.
e. Suppor t s f or Of f - The- Fl oor Pl umbi ng Fi xt ur es: ASME A112. 6. 1M.
f . Met al l i c Cl eanout s: ASME A112. 36. 2M.
g. Pl umbi ng Fi xt ur e Set t i ng Compound: A pr ef or med f l exi bl e r i ng seal
SECTI ON 22 00 00 Page 17 mol ded f r om hydr ocar bon wax mat er i al . The seal mat er i al shal l be nonvol at i l e nonasphal t i c and cont ai n ger mi ci de and pr ovi de wat er t i ght , gast i ght , odor pr oof and ver mi npr oof pr oper t i es.
h. Coal - Tar Pr ot ect i ve Coat i ngs and Li ni ngs f or St eel Wat er Pi pel i nes:
AWWA C203.
i . Hypochl or i t es: AWWA B300.
j . Li qui d Chl or i ne: AWWA B301.
k. Gauges - Pr essur e and Vacuum I ndi cat i ng Di al Type - El ast i c El ement :
ASME B40. 100.
l . Ther momet er s: ASTM E1. Mer cur y shal l not be used i n t her momet er s.
2. 1. 3 Pi pe I nsul at i on Mat er i al
I nsul at i on shal l be as speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON
FOR MECHANI CAL SYSTEMS.
2. 2 PI PE HANGERS, I NSERTS, AND SUPPORTS
Pi pe hanger s, i nser t s, and suppor t s shal l conf or m t o MSS SP- 58.
2. 3 VALVES
Val ves shal l be pr ovi ded on suppl i es t o equi pment and f i xt ur es. Val ves 2- 1/ 2 i nches and smal l er shal l be br onze wi t h t hr eaded bodi es f or pi pe and sol der - t ype connect i ons f or t ubi ng. Val ves 3 i nches and l ar ger shal l have f l anged i r on bodi es and br onze t r i m. Pr essur e r at i ngs shal l be based upon t he appl i cat i on. Gr ooved end val ves may be pr ovi ded i f t he manuf act ur er cer t i f i es t hat t he val ves meet t he per f or mance r equi r ement s of appl i cabl e MSS st andar d. Val ves shal l conf or m t o t he f ol l owi ng st andar ds:
Descr i pt i on St andar d
But t er f l y Val ves MSS SP- 67
Cast - I r on Gat e Val ves, Fl anged and Thr eaded Ends
MSS SP- 70
Cast - I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
MSS SP- 71
Bal l Val ves wi t h Fl anged But t - Wel di ng Ends f or Gener al Ser vi ce
MSS SP- 72
Bal l Val ves Thr eaded, Socket - Wel di ng, Sol der Joi nt , Gr ooved and Fl ar ed Ends
MSS SP- 110
Cast - I r on Pl ug Val ves, Fl anged and Thr eaded Ends
MSS SP- 78
SECTI ON 22 00 00 Page 18
Br onze Gat e, Gl obe, Angl e, and Check Val ves MSS SP- 80
St eel Val ves, Socket Wel di ng and Thr eaded Ends
ASME B16. 34
Cast - I r on Gl obe and Angl e Val ves, Fl anged and Thr eaded Ends
MSS SP- 85
Backwat er Val ves ASME A112. 14. 1
Vacuum Rel i ef Val ves ANSI Z21. 22/ CSA 4. 4
Wat er Pr essur e Reduci ng Val ves ASSE 1003
Wat er Heat er Dr ai n Val ves ASME BPVC SEC I V, Par t HLW- 810:
Requi r ement s f or Pot abl e- Wat er Heat er s Bot t om Dr ai n Val ve
Tr ap Seal Pr i mer Val ves ASSE 1018
Temper at ur e and Pr essur e Rel i ef Val ves f or Hot Wat er Suppl y Syst ems
ANSI Z21. 22/ CSA 4. 4
Temper at ur e and Pr essur e Rel i ef Val ves f or Aut omat i cal l y Fi r ed Hot Wat er Boi l er s
ASME CSD- 1
Saf et y Code No. , Par t CW, Ar t i c l e 5
2. 3. 1 Backwat er Val ves
Backwat er val ves shal l be ei t her separ at e f r om t he f l oor dr ai n or a combi nat i on f l oor dr ai n, P- t r ap, and backwat er val ve, as shown. Val ves shal l have cast - i r on bodi es wi t h c l eanout s l ar ge enough t o per mi t r emoval of i nt er i or par t s. Val ves shal l be of t he f l ap t ype, hi nged or pi vot ed, wi t h r evol v i ng di sks. Hi nge pi vot s, di sks, and seat s shal l be nonf er r ous met al . Di sks shal l be s l i ght l y open i n a no- f l ow no- backwat er condi t i on.
Cl eanout s shal l ext end t o f i ni shed f l oor and be f i t t ed wi t h t hr eaded count er sunk pl ugs.
2. 3. 2 Wal l Faucet s
Wal l f aucet s wi t h vacuum- br eaker backf l ow pr event er shal l be br ass wi t h 3/ 4 i nch mal e i nl et t hr eads, hexagon shoul der , and 3/ 4 i nch hose connect i on. Faucet handl e shal l be secur el y at t ached t o st em.
2. 3. 3 Wal l Hydr ant s ( Fr ost pr oof )
ASSE 1019 wi t h vacuum- br eaker backf l ow pr event er shal l have a ni ckel - br ass or ni ckel - br onze wal l pl at e or f l ange wi t h nozzl e and det achabl e key
SECTI ON 22 00 00 Page 19 handl e. A br ass or br onze oper at i ng r od shal l be pr ovi ded wi t hi n a gal vani zed i r on casi ng of suf f i c i ent l engt h t o ext end t hr ough t he wal l so t hat t he val ve i s i nsi de t he bui l di ng, and t he por t i on of t he hydr ant bet ween t he out l et and val ve i s sel f - dr ai ni ng. A br ass or br onze val ve wi t h coupl i ng and uni on el bow havi ng met al - t o- met al seat shal l be pr ovi ded. Val ve r od and seat washer shal l be r emovabl e t hr ough t he f ace of t he hydr ant . The hydr ant shal l have 3/ 4 i nch exposed hose t hr ead on spout and 3/ 4 i nch mal e pi pe t hr ead on i nl et .
2. 3. 4 Rel i ef Val ves
Wat er heat er s and hot wat er st or age t anks shal l have a combi nat i on pr essur e and t emper at ur e ( P&T) r el i ef val ve. The pr essur e r el i ef el ement of a P&T r el i ef val ve shal l have adequat e capaci t y t o pr event excessi ve pr essur e bui l dup i n t he syst em when t he syst em i s oper at i ng at t he maxi mum r at e of heat i nput . The t emper at ur e el ement of a P&T r el i ef val ve shal l have a r el i evi ng capaci t y whi ch i s at l east equal t o t he t ot al i nput of t he heat er s when oper at i ng at t hei r maxi mum capaci t y. Rel i ef val ves shal l be r at ed accor di ng t o ANSI Z21. 22/ CSA 4. 4. Rel i ef val ves f or syst ems wher e t he maxi mum r at e of heat i nput i s l ess t han 200, 000 Bt uh shal l have 3/ 4 i nch mi ni mum i nl et s, and 3/ 4 i nch out l et s. Rel i ef val ves f or syst ems wher e t he maxi mum r at e of heat i nput i s gr eat er t han 200, 000 Bt uh shal l have 1 i nch mi ni mum i nl et s, and 1 i nch out l et s. The di schar ge pi pe f r om t he r el i ef val ve shal l be t he s i ze of t he val ve out l et .
2. 3. 5 Ther most at i c Mi xi ng Val ves
Pr ovi de t her most at i c mi xi ng val ve f or l avat or y f aucet s. Mi xi ng val ves, t her most at i c t ype, pr essur e- bal anced or…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .