J-2A MKG TRACON DWG.pdf

PDF 8 MB Posted

Attached to
MKG and GRR TRACON Realignment and Refurbishment Federal contract opportunity
Solicitation number
697DCK-24-R-00243
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document is a federal solicitation for the realignment and refurbishment of the TRACON facilities at the Muskegon County Airport (MKG) and the Gerald R. Ford International Airport (GRR). The scope of work includes removal of existing equipment, furniture, and finishes, and the provision of new partitions, carpets, ceilings, HVAC, and electrical systems as specified in the drawings and specifications. The solicitation is issued by the Department of Transportation Federal Aviation Administration Southwestern Region. Key details include the solicitation number (697DCK-24-R-00243), the requirement to remove and replace TRACON consoles, carpets, ceilings and other work, and the provision of new HVAC and electrical systems. The document provides drawings and specifications with the complete scope of work.

View the file

Other files for this federal contract opportunity

Other files attached to MKG and GRR TRACON Realignment and Refurbishment, newest first.
File Type Posted
J-2 MKG TRACON SPECSET_Updated 05.09.24.pdf PDF
J-1 GRR TRACON SPECSET_Updated 05.09.24.pdf PDF
697DCK-24-R-00243_Amendment 0002.pdf PDF
697DCK-24-R-00243_Amendment 0001.pdf PDF
J-7_Questions and Answers for MKG and GRR.pdf PDF
J-6_Contractor sign in sheet_1.pdf PDF
J-6A_Contractor sign in sheet_2.pdf PDF
J-3_ MI20240093 Wage Determination.pdf PDF
J-4_ MI20240088 Wage Determination.pdf PDF
J-5 Past Performance Questionnaire.pdf PDF
J-2 MKG TRACON SPEC.pdf PDF
697DCK-24-R-00243_MKG and GRR Solicitation.pdf PDF
J-1A GRR TRACON DWG transmittal.pdf PDF
J-1 GRR TRACON SPECSET.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

MKG

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DRAWING NO

DESIGNED

REVIEWED BY

/1

/2

:5

:4

P

M lo tt e d b y S

R V

-C

-E

O

APPROVED

m k g -1

-a

.d w

8 234567

TRACON

JANITOR CLOSET

MECHANICAL /

WOMEN MEN

NATCA OFFICE TELCO

112 118

WORK SPACE

CORRIDOR

4 4

CONFERENCE ROOM

OFFICE A

OFFICE B

D121

CORR.

D120

C C

IS

U

10/02/2023

MGR: ENGINEERING

AF

MUSKEGON

MKG-1701254-A101

BFS

JB

ATCT

TRACON REALIGNMENT

FIRST FLOOR PLAN

TERMINAL

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

N

T

IO

MUSKEGON COUNTY AIRPORT

THIS DRAWING PRODUCED ON THE AGL REGION CAD SYSTEM

PROJECT ENGINEER

1701254

MI

DESIGNATES DEMOLITION AREAS

LEGEND

NOTES

KEYNOTES ARE NOT SHOWN ON THIS SHEET, THEN NO WORK INTENDED.

SHEET FOR WORK TO BE ACCOMPLISHED FOR THIS PROJECT. IF THE

UNLESS DESIGNATED BY A KEYNOTE. REFER TO THE KEYNOTES ON THIS

STRICTLY FOR INFORMATION ONLY. NO WORK IS INTENDED TO BE DONE

ALL ITEMS IDENTIFIED ON THE FLOOR PLAN DRAWING ARE SHOWN -

CLEAN AND PREPARE SUB-FLOOR FOR NEW CARPET TILE

REMOVE DOTTED LINE ITEMS AND REMOVE EXISTING VINYL FLOOR,

(DEMOLITION)

KEYNOTES

REMOVE EXISTING DOOR AND FRAME.

(NEW WORK)

KEYNOTES

INSTALL NEW CARPET TILE

TO DOOR SCHEDULE SHEET A104.

INSTALL NEW HM DOOR, DOOR FRAME AND DOOR HARDWARE, REFER

FOR LIGHTING & POWER AND E031 FOR LUMINAIRE SCHEDULE.

INSTALL NEW CABINETS AND SINK, REFER TO 01,02,03-A103 AND E030

NOT USED

PROVIDE NEW METAL THRESHOLD AT FLOOR.

TYPE CONFIGURATION.

SYMBOL IMPLIES NEW WALL TYPE, REFER TO SHEET A005 FOR WALL

FOR NEW CARPET TILE.

REMOVE EXISTING CARPET FLOOR, CLEAN AND PREPARE SUB-FLOOR

REMOVE EXISTING GYP WALL INCLUDING SOFFITS.

REMOVE CARPET ON WALLS.

CORRIDOR HALL WAY UP TO DOOR ENCLOSURE.

PROVIDE FOR NEW DRYWALL TO CONTINUE 2 HR FIRE RATED ALONG

REMOVE EXISTING GRID, CEILING PANELS AND FIXTURES.

DESIGNATES NEW 2-HR WALL ADDITIONS

REMOVE EXISTING FIXTURES AND PIPE STUB

4' 0 4' 8'

SCALE: 1/4" = 1'-0"

EXISTING GROUND FLOOR PLAN

A101

GROUND FLOOR PLAN - NEW WORK

A101

X

NOT USED3

mkg-1701254-a101

2023-10-17T09:33:39-0500

DOUGLAS E WEAVER

2023-10-17T06:41:26-0500

CHUNSEI LEE FARREN

lo tt e

CORR.

MKG-1701254-A102

GROUND FLOOR RCP PLAN

KEYNOTES ARE NOT SHOWN ON THIS SHEET, THEN NO WORK INTENDED.

SHEET FOR WORK TO BE ACCOMPLISHED FOR THIS PROJECT. IF THE

UNLESS DESIGNATED BY A KEYNOTE. REFER TO THE KEYNOTES ON THIS

STRICTLY FOR INFORMATION ONLY. NO WORK IS INTENDED TO BE DONE

ALL ITEMS IDENTIFIED ON THE FLOOR PLAN DRAWING ARE SHOWN -

GROUND FLOOR RCP PLAN

A102

NEW (2' X 4') LED LIGHT FIXTURE INSTALLATION

LEGEND

INFORMATION

NOTE: REFER TO SHEETS M001 AND M002 FOR MORE MECHANICAL FIXTURES

NEW SUPPLY STEEL DIFFUSER

NEW STEEL GRILLED RETURN AIR INTAKE

NEW (2' X 2') LED LIGHT FIXTURE INSTALLATION

mkg-1701254-a102

2023-10-17T09:33:54-0500

DOUGLAS E WEAVER

2023-10-17T06:41:37-0500

CHUNSEI LEE FARREN

:0 lo tt e

MINI

FRIDGE

3030 3030

B36B30 B30

KNEE SPACE

OPEN

SLOPED TOP

CEILING

1/2" PLYWOOD

CORE EDGES

ADJUSTABLE 3/4" MDF

WITH STANDARD

MELAMINE FINISH

TYPICAL U.N.O.

3/4" MDF DOORS

DOOR PULLS

SOLID SURFACE

COUNTERTOP SIDE

SPLASH GUARD

COUNTERTOP WITH

4"CAULKED MOLDING

HARDWOOD TRIM

4" RUBBER BASE

(PLAM)

ADJUSTABLE 3/4" MDF

SHELF W/ STANDARD

MELAMINE FINISH

BACKSPLASH

GUARD

PROVIDE CONTINUOUS

STUD BRACING OR

10" FLAT PLATE

BACKING FOR CABINET

SUPPORT (TYPICAL)

EXIST CORRIDOR

FIRE RATED

SLOPED TOP

LED LIGHT

COUNTERTOP SIDE

SPLASH GUARD SOLID SURFACE

COUNTERTOP WITH

4"CAULKED MOLDING

BACKSPLASH

GUARD

PROVIDE CONTINUOUS

STUD BRACING OR

10" FLAT PLATE

BACKING FOR CABINET

SUPPORT (TYPICAL)

SINK

NEW SINGLE BOWL

DROP-IN ADA SINK

ANGLE PLYWOOD

SCORED TO PANEL

FACE BOARD

(PLASTIC LAMINATE PANEL

TO MATCH CABINETS)

4" RUBBER BASE

MKG-1701254-A103

CABINET DETAILS

1' 0 1' 2'

SCALE: 1" = 1'-0"

KITCHENETTE VIEW ELEVATION

A103

CABINET SECTION

CABINET SECTION AT SINK

mkg-1701254-a103

2023-10-17T09:34:22-0500

DOUGLAS E WEAVER

2023-10-17T06:41:59-0500

CHUNSEI LEE FARREN

:1 lo tt e

DOOR FRAME-RATED

SOLID CORE

GYP. BOARD

5/8" TYPE "X"

1 LAYER

INSULATION

3-1/2" BATT

LOCATIONS

DOOR JAMB

AT ALL

METAL STUDS

DOUBLE 3-5/8"

STUDS.

3-5/8" METAL

GYP. BOARD

5/8" TYPE "X"

1 LAYER

DOOR AS SCHED.

D112

DOOR

NO.

A 3'0"x 7'-0"

GLASS

1 1/2"

THICK

DOOR

JAMB

MAT'L

THRES.

HARDWARE

REMARKS

*CONTRACTOR TO VERIFY DIMENSIONS AND THICKNESS OF ALL DOORS

TYPE

FRAME

* DOORS TO MATCH EXISTING

4 7/8"

PANELS

HOLLOW METAL

(W x H)

3'0"x 7'-0" ---

DOOR SCHEDULE

SIZE

D113 A

ROOM

NUMBER

MATERIAL

ROOM FINISH SCHEDULE

113 CORRIDOR

ROOM NAME

FLOOR

BASE NORTH EAST SOUTH WEST MATERIAL

HEIGHT

WALLS

RUBBER ACT-1

CARPET PAINT ACT-1

TILE

RUBBER PAINT PAINT PAINT

PAINT 8'-0"

MATCH EXISTING

* 13'0"x 7'-0" ---D117 A

4 7/8" 13'0"x 7'-0" ---D120 A

CARPET

RUBBER

PAINT

PAINT PAINT ACT-1

4 7/8" 13'0"x 7'-0" ---D121 A

RUBBER ACT-1PAINTPAINT PAINT PAINT 8'-0"

8'-0"

8'-0"

* FIELD VERIFY HDWE TO

6" DOUBLE METAL

SCHEDULED

NEW DOOR, AS

DOOR FRAME-RATED

DOUBLE 3-5/8"

3-5/8" METAL

SCHEDULED

NEW DOOR, AS

FRAME-RATED

HOLLOW METAL DOOR

SCHED.

DOOR AS

IN HEIGHT ABOVE FIN. FLR.

NOT TO EXCEED 1/2"

TRANSITION STRIP

(BEYOND)

DOOR FRAME

CARPET FLOORING

FINISH MATERIAL

EXISTING FLOOR

MKG-1701254-A104

DOOR SCHEDULE AND DOOR DETAILS

3" 0 6" 9"

SCALE: 3" = 1'-0"

3"

JAMB DOOR DETAIL

A104

DOOR THRESHOLD DETAIL

FRAME DOOR DETAIL AT MAIN CORRIDOR 119 FIRE WALL

FRAME DOOR DETAIL

mkg-1701254-a104

2023-10-17T09:34:52-0500

DOUGLAS E WEAVER

2023-10-17T06:42:08-0500

CHUNSEI LEE FARREN

:2 lo tt e

CARPET FINISH

EXISTING MTL. STUDS

2 LAYER 5/8" GYP. BOARD ON

CONTINUOUS

NEW SUSPENDED ACT CEILING.TYP.

3 5/8" MTL STUDS

5/8" GYP. BOARD ON

NEW 4 INCH VINYL BASE

NEW CARPET FINISH

4 INCH VINYL BASE

4 INCH VINYL BASE, TYP.

ON EX. 6" METAL STUDS.

2 LAYER 5/8" GYP. BOARD

EX. 6" MTL STUD

NEW 3 5/8" MTL STUD

5/8" GYP. BOARD PAINT TBD

NEW 4 INCH VINYL BASE

CEILING.TYP.

NEW SUSPENDED ACT

CEILING.TYP.

NEW SUSPENDED ACT

IN BETWEEN WALLS

SOUND BATT INSULATION

ACT CEILING.TYP.

NEW SUSPENDED

ON EX. 6" MTL STUDS

2 LAYER 5/8" GYP. BOARD

CEILING ANGLECEILING ANGLE

CEILING ANGLE

CEILING ANGLE

STEEL TRACK

WALL STEEL JOISTS

EXIST. 10" STEEL JOISTS

STEEL TRACK

WALL STEEL JOISTS

WALL

REMOVING CARPET ON

OR CLEAN UP GLUE AFTER

1/4" GYP. BD LAMINATED

EXIST. 10" STEEL JOISTS

ROOF DECK ABOVE ROOF DECK ABOVE ROOF DECK ABOVE

EX. 6" MTL STUD

EXIST.

EXIST.

ROOF DECK ABOVE

MKG-1701254-A105

WALL TYPES

1' 0 1' 2'

WALL TYPE "A"

A105

WALL TYPE "B"

WALL TYPE "C"

WALL TYPE "D"

OF WALL.

BASIS AND TO BE MATCHED TO EXISTING CONDITIONS IN NEW EXTENSIONS

REPAIRS ON EXISTING WALLS IS TO BE CONDUCTED IN AN AS-NEEDED

CURRENT WALL CONFIGURATION ACCORDING TO AS BUILT INFORMATION;

- ITEMS IDENTIFIED ON EXISTING WALL SECTIONS ARE SHOWN TO DEPICT

mkg-1701254-a105

2023-10-17T09:35:06-0500

DOUGLAS E WEAVER

2023-10-17T06:42:18-0500

CHUNSEI LEE FARREN

:3 lo tt e

-e

BLE

MKG-1701254-E128

JR

ELECTRICAL NOTES, LEGEND

AND ABBREVIATIONS

ELECTRICAL ABBREVIATION

AWG

GND

RGS

EMT

FT

J-BOX

NEC

PVC

SER

GEC

SLD

MDP

GFCI

GFE

LFMC

SCH

TYP

MAIN-GP

COMM

MLO

SUPP-GP

WP

BSC

FRWK

MPGP

OSHA

NFPA

MULTI-POINT GROUND PLATE

MAIN GROUND PLATE

GROUND CONDUCTOR

FRAMEWORK

BARE STRANDED COPPER

AMERICAN WIRE GAGE

SUPPLEMENTAL GROUND PLATE

MAIN LUG ONLY

POLYVINYL CHLORIDE CONDUIT

LIQUIDTIGHT FLEXIBLE METAL CONDUIT

COMMUNICATION

NATIONAL ELECTRIC CODE (NFPA 70)

NATIONAL FIRE PROTECTION ASSOCIATION

OPERATIONAL SAFETY AND HEALTH ADMINISTRATION

SERVICE ENTRANCE RATED

SINGLE LINE DIAGRAM

GROUNDING ELECTRODE CONDUCTOR

FEET

ELECTRICAL METALLIC TUBING

JUNCTION BOX

RIGID GALVANIZED STEEL CONDUIT

SCHEDULE

GROUND FAULT CIRCUIT INTERRUPTER

TYPICAL

GOVERNMENT FURNISHED EQUIPMENT

MAIN DISTRIBUTION PANEL

CONDUIT

DIA DIAMETER

APPLICABLE CONSTRUCTION CODES:

WEATHERPROOF

TBD TO BE DETERMINED

AVG

ELECTRICAL LEGEND

AVERAGE

COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

DP-1

DUPLEX RECEPTACLE

RECESSED/FLUSH MOUNTED

QUAD RECEPTACLE

SURFACE MOUNTED

CONDUIT, FLEXIBLE

CONDUIT, CAPPED

CONDUIT STUB UP

CONDUIT STUB DOWN

SOLID WHETHER CONCEALED OR EXPOSED

HOME RUN TO PANEL DP BREAKER, SHOWN

SAME AS BRANCH CIRCUIT - BUT CONCEALED

EES (BURIED) GROUND CONDUCTOR

DOWN CONDUCTOR

WITH (2)-12 AWG CONDUCTOR(S) PLUS (1)-12 AWG GROUND

BRANCH CIRCUIT, SURFACE MOUNTED 3/4" RACEWAY,

WHEN MORE THAN 3 IN 3/4" RACEWAY

CROSS MARKS DENOTE NUMBER OF 12 AWG CONDUCTOR(S)

RECESSED CEILING MOUNTED LED LIGHTING FIXTURE

ABOVE GROUND, CONDUCTOR

SYMBOL DESCRIPTION

OH OVERHEAD CONDUCTORS

DESCRIPTIONSYMBOL

AIR CONDITIONER CONTROLS / THERMOSTAT

120V, 20A, SPECIFICATION GRADE

SINGLE POLE SWITCH

120V, 20A, SPECIFICATION GRADE

DIMMER SWITCH

SINGLE RECEPTACLE

(GFCI)

DUPLEX RECEPTACLE (GFCI)

DISTRIBUTION PANELBOARD

SURFACE-MOUNTED ELECTRICAL

DISTRIBUTION PANELBOARD

RECESSED ELECTRICAL

EXISTING STEPLIGHT FIXTURE

DUPLEX RECEPTACLE

SINGLE RECEPTACLE

QUAD RECEPTACLE

PCB POLYCHLORINATED BIPHENYLS

AGL ABOVE GRADE LEVEL

AT AIR TRAFFIC

ATCT AIR TRAFFIC CONTROL TOWER

DIST DISTRIBUTION

ELEV ELEVATOR

PNL PANEL

DEMOLITION

TELEPHONE

JB JUNCTION BOX

HORN/STROBE

WALL SWITCH W/DIMMER

OCCUPANCY SENSOR

WORK AREA

MAY BE USED IN THIS PROJECT

NOT ALL SYMBOLS AND ABBREVIATION

RCPT RECEPTACLE

EMERG LT EMERGENCY LIGHT

MAY BE USED IN THIS PROJECT

NOT ALL SYMBOLS AND ABBREVIATION

LED EXIT LIGHT W/EMERGENCY LIGHT, WALL MOUNTED

F. NFPA 70E

E. IEEE C2

D. FAA-C-1217

C. FAA-C-1391

B. FAA-STD-019

A. NFPA 70 (NEC)

CODES AND STANDARDS:

STANDARDS. THESE DRAWINGS WERE COMPLETED IN ACCORDANCE WITH THE LATEST EDITION OF THE FOLLOWING

DOCUMENTS, DRAWINGS, ALL APPLICABLE CODES, LOCAL AUTHORITIES HAVING JURISDICTION, REGULATIONS, AND

ALL WORK MUST BE PERFORMED IN COMPLIANCE WITH DIVISION 26 OF THE SPECIFICATIONS, CONTRACT 1.

EMERGENCY LIGHT (DUAL)

ETHERNET PORT BOX

L LINE (UNGROUNDED CONDUCTOR)

THWN, UNLESS OTHERWISE SPECIFIED.

ALL BRANCH CIRCUIT CONDUCTORS ARE # 12

CROSS MARKS INDICATE NEUTRAL CONDUCTORS.

MARKS INDICATE PHASE CONDUCTORS. SHORT

IN PANEL FOR HOME RUN CIRCUIT. LONG CROSS

INDICATE NUMBER OF BRANCH POLES REQUIRED

HOME RUN CIRCUITRY. NUMBER OF ARROW HEADS

BRANCH CIRCUIT RUNS. ARROWS HEADS INDICATE

TO BE REMOVED AND REPLACED.

EXISTING RECESSED FLOURESCENT LIGHT FIXTURE

TOGGLE SWITCH, 120/227V, 20A, SPECIFICATION GRADE.

TOGGLE SWITCH, 3 WAY, 120/227V, 20A, SPECIFICATION

FLUORESCENT DIMMER SWITCH

EXIT

LOUVER NO. H419.

75W. PAR-38 LAMP. K.A.S. : HALO CAT. NO. 4108 WITH

LIGHT FIXTURE, RECESSED, INCANDESCENT, WITH LOUVER,

BE REMOVED AND REPLACED.

EXISTING FLOURESCENT LIGHT FIXTURE, WALL MOUNT TO

EMERGENCY LIGHTING

RE

RECEPTACLE

E : EXISTING TO REMAIN R : EXISTING TO BE REMOVED

S SMOKE DETECTOR

ALARM LAMP

STROBE

R TRACK LIGHTING

G LOUVER FACEPLATE

STEPLIGHT FIXTURE, INCANDESCENT, ALUMINUM

ISD

4'-6" ABOVE FINISHED FLOOR.

KNOB AND COVER PLATE, 120V, 600W. MOUNTED DIMMER

INCANDESCENT DIMMER, SINGLE POLE, ROTARY, WHITE

R SURFACE MOUNTED ETHERNET PORT BOX

BE REMOVED AND REPLACED.

EXISTING SELF - CONTAINED EMERGENCY EXIT SIGN TO

GENERAL GROUNDING NOTES:

GROUNDING AND BONDING IN ACCORDANCE WITH SPECIFICATION DIV.26, NEC, AND FAA-STD-019 (LATEST EDITION).1.

GENERAL ELECTRICAL NOTES:

POSSIBILITY OF GALVANIC ACTION.

CONNECTIONS. DISSIMILAR METALS IN CONTACT ANYWHERE IN THE SYSTEM MUST BE AVOIDED TO ELIMINATE THE

PROVIDE WEATHER RESISTANT ENCLOSURES AND CORROSION RESISTANT, WATERTIGHT FITTINGS FOR OUTDOOR 11.

OCCUPANTS DURING THE PERFORMANCE OF THE WORK A THE FACILITY WILL BE OCCUPIED AND IN OPERATION.

COORDINATE AND SCHEDULE WORK WITH RE AND FACILITY MANAGER TO AVOID DISRUPTIONS TO THE EQUIPMENT AND10.

DIRECTORIES FOR NEW OR AFFECTED PANELBOARDS.

RE-IDENTIFY AND MARKUP ANY CHANGES TO THE PANEL DIRECTORIES AFFECTED BY THE NEW WORK. PROVIDE NEW TYPED

FIELD VERIFY THE ACCURACY OF THE EXISTING BRANCH CIRCUITS AND MARK UP THE DRAWINGS WITH ANY DIFFERENCES.9.

UPGRADED/MODIFIED BEFORE ORDERING NEW MATERIALS.

FIELD VERIFY LOCATION OF EXISTING CABLE TRAYS, WIREWAYS, PANELBOARDS AND DEVICE/MATERIALS TO BE

VISIT THE JOB SITE TO BECOME COMPLETELY FAMILIAR WITH THE EXISTING CONDITIONS PRIOR TO BEGINNING WORK.8.

ALL ELECTRICAL EQUIPMENT MUST BE LISTED AND LABELED.7.

OF 72 HOURS ADVANCE NOTICE.

REVIEW THESE PROCEDURES PRIOR TO EACH ELECTRICAL OUTAGE. COORDINATE ANY POTENTIAL OUTAGES WITH A MINIMUM

STRICTLY ENFORCE LOCKOUT/TAGOUT (LOTO) PROCEDURES PER NFPA 70E, LATEST EDITION THROUGHOUT THIS PROJECT.6.

DRAWINGS.

INCLUDE ANY ADDITIONAL APPURTENANCE NECESSARY FOR PROPER FUNCTION OF THE SYSTEM EVEN IF NOT SHOWN ON THE5.

APPLY ANTI-SEIZE COMPOUND TO ALL THREADS ON BOLTS AND SCREWS.4.

MANUFACTURER INSTRUCTIONS, NEC, NEMA AND FAA STANDARDS AND ORDERS.

FOR EACH PIECE OF EQUIPMENT INSTALLED UNDER THE CONTRACT. INSTALLATION SHALL BE IN ACCORDANCE WITH

PROVIDE ALL REQUIRED CONDUITS, CABLES, JUNCTION BOXES, FITTINGS, SUPPORTS, ETC. TO COMPLETE BRANCH CIRCUITS3.

SPACE ACCORDING TO THE NEC CODE AND OSHA.

TO AVOID SPACE CONFLICT. INSTALLATION OF THE EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF THE WORKING

ALL EQUIPMENT DIMENSIONS SHOWN ARE NOMINAL. FIELD VERIFY ALL DIMENSIONS AND COORDINATE WITH EQUIPMENT2.

FOR GROUND CONDUCTORS OR BURIED CONDUIT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

THREADED TYPE ONLY. SET SCREW TYPE CONDUIT FITTINGS ARE NOT ALLOWED. PVC CONDUIT MUST ONLY BE PERMITTED

SUBJECT TO PHYSICAL DAMAGE. USE ONLY COMPRESSION TYPE FITTINGS FOR EMT. RGS CONDUIT FITTINGS MUST BE

PERMITTED CONDUIT TYPES ARE EMT, RGS AND PVC. EMT MAY ONLY BE USED I DRY INTERIOR LOCATIONS WHERE NOT1.

mkg-1701254-e128

2023-10-17T09:35:26-0500

DOUGLAS E WEAVER

2023-10-17T06:42:36-0500

CHUNSEI LEE FARREN

SEE NOTE 2

DEMOLITION

20 20

225A

SPARE

HALL PLUGS

HALL WATER COLLER

EXHAUST FAN

MECH RM PLUGS (NOT OUTLET BY WATER)

WOMENS BATH RM ON COMMON WALL W/MECH RM

HALL LIGHTS, EAST SECURITY LIGHT

BATH & MECH ROOM LIGHTS

HUMIDIFIER

EXIT LIGHTS (A.F. WORK SHOP & TELCO)

TELCO PLUGS

TRACON PLUGS

A.F. SHOP & WORK SPACE PLUGS

TRACON WEST OUTSIDE LIGHTS

TELCO A.F. TRACON RM LIGHTS,

TRACON CEILING LIGHTS

TRACON WALK LIGHTS

A.F. WORK SPACE CENTER LIGHTS

TRACON WATER COOLER

LADIE'S RM HEATER

ROOF OUTLET)

RECEPTACLE ON ROOF (TRACON HVAC

EXIT LITE EAST DOORWAY E

(CARD READER)

ACCESS CONTROL (1ST FLOOR SECURITY RM)

MEN'S RM HEATER40

S/N

TO PANEL "MDP"

LPN-C2

PANEL

EXISTING

EXISTING WOMEN MEN

CLOSET

JANITOR

MECHANICAL

IT

3S

AREA

WORK

WORK AREA

NATCA OFFICE

TELCO

R R

LPN-C

LPN-CRECPT

EMERG LT

RECPT

EXITR

RECPT

LPE-C

DASR

R R

EE

LIGHT

TO HALL

LPE-B2

POWER

LPE-B2

ISD

(NOT OUTLET IN WOMENS BATH ON COMMON WALL W/ MEN RM

MECH RM OUTLET BY WATER, N/E SECURITY LITE, BATH PLUGS

CABLE TRAY

ASR-11

UPS

NO. 1

CB

30A

2P/

EXISTING FEEDER

MDP

lo tt e

GENERAL NOTES:

CONDUIT AND CABLE TO THE MAXIMUM EXTENT POSSIBLE.

VERIFY ALL CONDUIT RUNS AND EQUIPMENT BEFORE DEMOLITION REMOVE ALL 21.

NOT USED20.

ALL THE TOOLS.

MAINTAIN A CLEAN CONSTRUCTION AREA BY CLEANING DAILY, REMOVE ALL DEBRIS AND PROPERLY STORE 19.

DO NOT OBSTRUCT THE MEANS OF EGRESS FOR THE FACILITY AT ANY TIME THROUGHT THE PERIOD OF THE WORK.18.

COORDINATE DEMOLITION WORK AND NOTES ON THIS DRAWING WITH ARCHITECTURAL DRAWINGS.17.

TO ORIGINAL WORKING CONDITION.

IF FIRE ALARM DEVICES ARE DISTURBED DURING THE PERFORMANCE OF THE WORK, RELOCATE AND REINSTATE 16.

TO AVOID DISRUPTIONS TO THE OCCUPANTS AND AIR TRAFFIC OPERATIONS.

THE BUILDING WILL BE OCCUPIED DURING THE PERFORMANCE OF WORK. COORDINATE AND SCHEDULE WORK 15.

ACCORDANCE WITH THE SCHEDULE DESCRIBED IN "SEQUENCE OF WORK" UNDER GENERAL REQUIREMENTS.

ELECTRICAL WORK DESCRIBED IN THIS DOCUMENT MUST BE COORDINATED WITH GENERAL WORK IN 14.

RELOCATE ANY EXISTING EQUIPMENT TO NEW WALL AS INDICATED.13.

EXISTING CONDUITS MAY BE MODIFIED AND REUSED FOR NEW WORK.12.

RESIDENT ENGINEER.

LIGHTING MAY BE USED AS A TEMPORARY LIGHT IF IT IS APPROVED BY THE PART OF THE EXISTING

PROVIDE TEMPORARY POWER, AND LIGHT AND MAINTAIN BUILDING POWER DURING DEMOLITION. ALL OR 11.

REPAIRED TO MATCH EXISTING.

FINISHES AND SURFACES DAMAGED BY THE DEMOLITION OR CONSTRUCTION MUST BE PATCHED AND 10.

NOT USED9.

MAINTAIN ALL SIGNAL, POWER, LIGHTING AND ALARMS CIRCUITS DURING ALL PHASES OF CONSTRUCTION.8.

FROM THE TRACON ROOM PER DETAILS 1/E029 AND 2/E029.

REMOVE EXISTING LIGHTS, THEIR CONTROLS, EXISTING RECEPTACLES, AND THEIR ASSOCIATED WIRING7.

ASR-11 PANEL.

AND CONDUCTORS FROM ASR-11 TO DASR. PROVIDE CONDUIT AND CONDUCTORS FROM ASR-11 UPS TO

REMOVE TRACON DASR PANEL LOCATED AT THE BASE BUILDING FIRST FLOOR CORRIDOR. REMOVE CONDUIT 6.

STORE SMOKE DETECTORS TO BE REINSTALLED BELOW NEW CEILING.

BOX. WHERE CONDUITS ARE INACCESSIBLE TO REMOVE AND/OR CAN BE REUSED, LEAVE THEM IN PLACE.

ASSOCIATED WIRING AND CONDUITS BACK TO THE POWER SOURCE OR NEAREST OUTLET BOX/JUNCTION

DISCONNENCT AND REMOVE LIGHTING FIXTURES, EXIT SIGNS, WIRING, WIRING DEVICES, SWITCHES AND 5.

FIXTURE AND DISPOSE OF BALLAST IN ACCORDANCE WITH FEDERAL AND STATE REQUIREMENTS.EACH

IF FLUORESCENT LIGHTS HAVE BALLASTS THAT MAY CONTAIN PCB MATERIAL, REMOVE EACH BALLAST FROM 4.

SUBCONTRACTOR MUST NOT OPEN OR CLOSE ANY BREAKERS AT ANY TIME.

OPERATION TO THE FAA IN WRITING AT LEAST 48 HOURS IN ADVANCE TO THE WORK BEING PERFORMED.

ONLY FAA PERSONNEL MAY OPERATE CIRCUIT BREAKERS. SUBMIT REQUEST FOR CIRCUIT BREAKER3.

DEMOLITION.

DISCONNECT EQUIPMENT AND APPLY LOCK-OUT/TAG-OUT PROCEDURE PER NFPA 70E BEFORE COMMENCING 2.

MUST BE COORDINATED WITH THE RE AND FAA PERSONNEL IN ADVANCE.

FIELD VERIFY EXISTING CONDITIONS PRIOR TO DEMOLITION OF ELECTRICAL SYSTEM. ALL DEMOLITION WORK1.

EXISTING BASE BUILDING FIRST FLOOR LIGHTING PLAN

SCALE: 1/4" = 1'-0"E129

1 EXISTING BASE BUILDING FIRST FLOOR POWER PLAN

SCALE: 1/4" = 1'-0"E129

ONE-LINE DIAGRAM BREAKER NO. 1 EXISTING CONNECTIONS

NOT TO SCALEE129

EXISTING PANEL LPN-C2, FED FROM MDP

NOT TO SCALEE129

MKG-1701254-E129

ELECTRICAL DEMOLITION

THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM

mkg-1701254-e129

2023-10-17T09:35:39-0500

DOUGLAS E WEAVER

2023-10-17T06:42:54-0500

CHUNSEI LEE FARREN

ITEXISTING EXISTING EXISTING EXISTING

B B

B B e e e a c c

5 7

D 14 aS g g g g

DS

f

5 9

12 12 fff

E E

3S g

LIGHT

TO HALL

5 6 cD

5 8 d d

F F5 8

5 7

GFCI GFCI

2020 21

LPN-C2-27

LPN-C2-8

WOMEN

MEN

LPN-C2-29

LPN-C2-10

LPN-C2-6

LPN-C2-19

LPN-C2-37

LPN-C2-35

LPN-C2-12

LPN-C2-31 LPN-C2-23

:4 lo tt e

KEY NOTES

KEY NOTES (cont.)

NOT USED.

CONNECTIONS.

ETHERNET PORT BOX AND USE THE NEAREST ETHERNET PORT FOR

PROVIDE NEW DUPLEX RECEPTACLES.

PROVIDE A NEW TYPED UPDATED PANEL BOARD DIRECTORY.

OR ENCLOSURES ON EACH SIDE OF FLEXIBLE CONNECTION.

FLEXIBLE CONDUITS AND FASTENED TO TERMINAL WITHIN THE FIRST JUNCTION BOXES

EQUIPMENT GROUND CONDUCTOR GREREN MUST BE EXTENDED THROUGH ALL

METAL CONDUIT. LENGTH OF FLEXIBLE CONDUIT MUST NOT EXCEED 6 FEET. AN

FINAL BRANCH CIRCUIT CONNECTION TO LIGHT FIXTURES MAY BE IN 3/4" FLEXIBLE

NOT USED.

INFORMATION.

EXISTING SOURCE. REFER TO DRAWING E031 FOR MORE LED LIGHTING FIXTURES

LED EXIT LIGHT WITH EMERGENCY LIGHTS OVER THE DOOR AND CONNECT TO THE

LIGHTING FIXTURES INFORMATION.

DIMMER CONTROL SWITCH TO FIXTURES. REFER TO DRAWING E031 FOR MORE LED

LOCATION. PROVIDE CONTROL WIRING IN CONDUIT, AS REQUIRED FROM ASSOCIATED

AND WIRING FROM EXISTING JUNCTION BOX ABOVE CEILING TO NEW LIGHT FIXTURES

(LETTER INDICATES SWITCH DESIGNATION). PROVIDE NEW BRANCH CIRCUIT CONDUIT

2' X 2' RECESSED LED LIGHT FIXTURE WITH INDIVIDUAL DIMMING DRIVER

FIXTURES. REFER TO DRAWING E031 FOR MORE LED LIGHTING FIXTURES INFORMATION.

WIRING IN CONDUIT, AS REQUIRED FROM ASSOCIATED DIMMER CONTROL SWITCH TO

JUNCTION BOX ABOVE CEILING TO NEW LIGHT FIXTURES LOCATION. PROVIDE CONTROL

SWITCH DESIGNATION). PROVIDE NEW BRANCH CIRCUIT AND WIRING FROM EXISTING

ROOM ABOVE THE COUNTERTOP WITH INDIVIDUAL DIMMING DRIVER (LETTER INDICATES

6" RECESSED CAN LED LIGHT FIXTURE AT THE PRESENTER END OF THE

REFER TO DRAWING E031 FOR MORE LED LIGHTING FIXTURES INFORMATION.

CONDUIT, AS REQUIRED, FROM ASSOCIATED DIMMER CONTROL SWITCH TO FIXTURES.

ABOVE CEILING TO NEW LIGHT FIXTURES LOCATION. PROVIDE CONTROL WIRING IN

NEW BRANCH CIRCUIT CONDUIT AND WIRING FROM EXISTING JUNCTION BOX

WSXA PDT EZ D WH OR EQUIVALENT. (LETTER INDICATES SWITCH DESIGNATION).

OCCUPANCY SENSOR DIMMABLE WALL SWITCH, WATT STOPPER ACUITY BRANDS

2' X 4' RECESSED LED LIGHTING FIXTURE WITH WALL MOUNTED

FOR MORE LED LIGHTING FIXTURES INFORMATION.

ASSOCIATED DIMMER CONTROL SWITCH TO FIXTURES. REFER TO DRAWING E031

FIXTURES LOCATION. PROVIDE CONTROL WIRING IN CONDUIT, AS REQUIRED, FROM

CONDUIT AND WIRING FROM EXISTING JUNCTION BOX ABOVE CEILING TO NEW LIGHT

(LETTER INDICATES SWITCH DESIGNATION). PROVIDE NEW BRANCH CIRCUIT

NEW 2' X 2' RECESSED LED LIGHTING FIXTURE WITH DIMMING DRIVER

DIFFUSERS PRIOR TO INSTALLATION.

COORDINATE LIGHT FIXTURES LOCATIONS WITH MECHANICAL SYSTEMS AND

WITH THE COTR.

CONDUIT 6" IN CEILING SPACE. VERIFY EXACT LOCATION AND MOUNTING HEIGHT

3/4" CONDUIT TO A LAN JB W/2 PULL WIRES IN WALL FOR TV AND STUB UP

COORDINATE EXACT LOCATION WITH COTR.

CATV OUTLET AT 72" AFF AND 1" C FROM J-BOX TO 6" ABOVE CEILING.

REQUIREMENTS. VERIFY EXACT LOCATION AND MOUNTING WITH THE COTR.

AND INSTALL (4) ETHERNET PORT IN EACH SIDE OF THE TABLE AS PER FAA

CATV OUTLET CABLE, TABLE RECEPTACLES, COMMUNICATION CONNECTIONS

LPN-C2 PANEL BREAKER 23.

TABLE MOUNTED QUAD RECEPTACLE AND BOX. SUPPLY POWER FROM

PROVIDE HARDWIRE CONNECTION FOR HOT WATER HEATER.

LOCATION WITH COTR.

1" C FROM JUNCTION TO 6" ABOVE CEILING. COORDINATE EXACT

SWITCHES. COORDINATE EXACT LOCATION WITH RE.

RECONNECT THE EXISTING LIGHTS IN THE CORRIDOR TO THE NEW THREE WAY WALL

66 TO 75 INCHES AFF. COORDINATE THE EXACT LOCATION AND HEIGHT WITH RE.

RECEPTACLE FOR MICROWAVE AND INSTALL AT THE HEIGHT BETWEEN

TWO GFCI RECEPTACLES AT 42" AFF. COORDINATE EXACT LOCATION WITH RE.

SECURITY ROOM. COORDINATE EXACT LOCATION AND HEIGHT WITH RE.

COMMUNICATION CABLES INTO EXISTING CABLE TRAY FROM CORRIDOR TO

PROVIDE ON CORRIDOR WALL A TELEPHONE OUTLET ACCESS AT 48" AFF. RUN

REINSTALL PHOTOELECTRIC SMOKE DETECTORS CEILING MOUNTED.

SOURCE.

NEW HORN/STROBES WALL MOUNTED, CONNECT TO EXISTING

4' 8'04'

MKG-1701254-E130

LIGHTING AND POWER PLAN

BASE BUILDING

CONFERENCE ROOM LIGHTING PLAN

E130

CONFERENCE ROOM POWER PLAN

E130 mkg-1701254-e130

2023-10-17T09:36:10-0500

DOUGLAS E WEAVER

2023-10-17T06:43:05-0500

CHUNSEI LEE FARREN

LUMINAIRE SCHEDULE

LABEL QTY. MANUFACTURER CATALOG NUMBER DESCRIPTION LAMP VOLTS DRIVER MOUNTING

(4)

(1)

(2)

(3)

(3)

LIGHTING

LITHONIA

4000K LEDs

4000K LEDs 120

120 - - -

@ H = 8'-0"

RECESSED

WALL/SURFACE

FIXTURE (TYPICAL)

NEW RECESSED

(TYPICAL)

MAXIMUM LENGTH 6 FEET

CONDUIT FIXTURE WHIP

NEW FLEXIBLE METAL

NEW OR EXISTING

BUILDING STRUCTURE

SUPPORT SYSTEM OR

UNISTRUT - TYPE

WITH 5 TWISTS AT EACH END

AT 2 CORNERS OF FIXTUREWIRE

NEW GALV 12 GA SUSPENSION

SUSPENDED CEILING

CONDUIT EMT

NEW OR

F (2) 4000K LEDs 120

WR LSS EZ1

LDN6 40/30 LO6

WR LSS EZ1

LDN6 40/30 LO6

EQUIVALENT

EU2C HO OR

OR EQUIVALENT

LHQM LED R HO

LP840 OR EQUIVALENT

2AVL2 30LSE MDR EZ1

LP840 OR EQUIVALENT

2AVL4 30LSE MDR EZ1

TROFFER

2' X 4' REGRESSED

TROFFER

2' X 2' REGRESSED

EMERGENCY LIGHT

LED EXIT LIGHT W/

LED EMERGENCY LIGHT

6" ROUND DOWNLIGHT

6" ROUND DOWNLIGHT

DIMMING)

(0-10 VOLT

DIMS TO 1%

eldoLED

DIMMING)

(0-10 VOLT

DIMS TO 1%

eldoLED

DOWN TO 1%

PERFORMANCE

DEEP DIMMING

AND FLICKER-FREE

DRIVER W/ SMOOTH

0-10V eldoLED

DOWN TO 1%

PERFORMANCE

DEEP DIMMING

AND FLICKER-FREE

DRIVER W/ SMOOTH

0-10V eldoLED

COUNTERTOP

ABOVE

WALL/SURFACE

RED

BKL

BKL

VIO

PNK

GRN

L N

LOAD

GRY/PINK*

410.69 OF 2020 NEC

OTHERWISE INDICATED PER SECTION

FIXTURE MAY BE PINK OR AS

* 0-10V DIMMING COMMON FROM

PROJECT SPECIFICATIONS AND SEISMIC REQUIREMENTS.

INSTALL LIGHTING FIXTURES AND SUPPORTS TO MEET2.

CONDUIT RUNS TO A MAXIMUM OF 6 FEET.

BOXES TO SUPPORT NEW LIGHTING LAYOUT AND KEEP FLEXIBLE

PROVIDE NEW CONDUIT AND WIRING FROM EXISTING JUNCTION1.

DETECTION AND DAYLIGHT

DIMMING, OCCUPANCY

SWITCH SENSOR WITH

WSXA PDT EZ WH WALL

DETAIL NOTES

lo tt e

MKG-1701254-E131

LUMINAIRE SCHEDULE AND

FIXTURE DETAILS

AND/OR CLASS B DEVICES FOR LED LIGHT FIXTURES.

COMPLETE REQUIREMENTS OF CFR TITLE 47 PART 15 FOR CLASS AC

A SECURE AND COMPLETE ASSEMBLY.

AND COMPLIANCE WITH LIGHTING CONTROL SYSTEM, PROPER FIT, AND

MANUFACTURER) PRIOR TO INSTALLATION TO ENSURE COMPATIBILITY

ACCESSORIES MUST BE VERIFIED (CONSULT WITH LIGHTING

LUMINAIRE BALLASTS, DRIVERS, MOUNTING BRACKETS ANDB

COMPLIANCE AND APPROVAL.

SUBMITTED IN ADVANCE FOR ENGINEER OF RECORD FOR

AND PERFORMANCE THAT ANY SUBSTITUTED FIXTURES MUST BE

ON THIS DRAWINGS ESTABLISH A LEVEL OF QUALITY, APPEARANCE,

THE FIXTURES SPECIFIED IN THE LIGHTING FIXTURE SCHEDULEA

GENERAL NOTES

NOT TO SCALE

WALL SWITCH OCCUPANCY SENSOR DETAIL

E131

RECESSED FIXTURE MOUNTING DETAIL

E131 mkg-1701254-e131

2023-10-17T09:36:25-0500

DOUGLAS E WEAVER

2023-10-17T06:43:27-0500

CHUNSEI LEE FARREN

20 20

225A

DAMPER MD-1

MECH RM PLUGS (NOT OUTLET BY WATER)

WOMENS BATH RM ON COMMON WALL W/MECH RM

(CARD READER)

ACCESS CONTROL (1ST FLOOR SECURITY RM)

HALL PLUGS

HALL WATER COLLER

EXHAUST FAN

HALL LIGHTS, EAST SECURITY LIGHT

BATH & MECH ROOM LIGHTS

HUMIDIFIER

TELCO PLUGS

A.F. SHOP & WORK SPACE PLUGS

A.F. WORK SPACE CENTER LIGHTS

LADIE'S RM HEATER

ROOF OUTLET)

RECEPTACLE ON ROOF (TRACON HVAC

EXIT LITE EAST DOORWAY

MEN'S RM HEATER

S/N

TO PANEL "MDP"

SWITCH

BYPASS

ISOLATION

ATS WITH

NO. 1

30A

2P/

NO. 5 NO. 4 NO. 6 NO. 3 NO. 2

UPS

100A

3RD FLR

BRK RM

EDP

NEDP

ASR - 11

NEW FEEDER SWITCH

SHUT - OFF

LPE-B

SPD

4TH FLOOR

ETVS

LPE-B

192019

BANK

LOAD

7 6

3P/100A

1P/20A

1P/20A

2P/50A

PANEL E / G

IN 1" C

1 #10 AWG GND

4-1/C #6 AWG

IN 1" C

1 AWG GND

4-1/C 4/0 AWG

IN 1 1/4" C

1 AWG GND

4 AWG

MUSKEGON COUNTY

PRIMARY FROM

CONFERENCE ROOM RECEPTACLES

CONFERENCE RM MICROWAVE RCPT

OFFICE "A" RECEPTACLES

CONFERENCE ROOM LIGHTS

CONFERENCE RM GFCI RCPT

OFFICE "A" LIGHTS

OFFICE "B" LIGHTS

OFFICE "B" RECEPTACLES

CORRIDOR LIGHTS

BATH ON COMMON WALL W/ MEN RM

BATH PLUGS (NOT OUTLET IN WOMENS

MECH RM OUTLET BY WATER, N/E SECURITY LITE,

DAY TANK PUMP

FUEL SOLENOIDS

LOUVER CONTROL

40A MAIN

20A

NOTES 1, 2, 3, 4

NOTE 3

IN 2" C

1 #2 AWG GND

NEW 4 #2 AWG

IN 1 1/2" C

1 NO.6 GRD

4 NO. 2 AND

STEEL CONDUIT

RIGID GALVANIZED

IN 2 4" UNDERGROUND

2 NO. 1/0 GND

8-500KCM AND

EXOTHERMICALLY WELDED

WITH NO. 1/0 MINIMUM,

GROUNDING ELECTRODE,

CONNECTED TON BUILDING

1 NO. 6 GRD

IN 2 4" C

8-500KCM AND

3P/700A

GND IN 4" C (EACH)

500KCMIL, 1/0 AWG

(2) SETS OF (4)

IN 2 4" C

6-500KCM AND

IN 3/4" C

1 NO. 12 GND

2 NO. 12 AND

1 NO. 10 GND

2 NO. 8 AND

1 NO. 12 GND

2 NO. 12 AND

IN 1" RIGID CONDUIT

22 NO. 14 CONTROL

TRANSFORMER LEADS

CURRENT SENSING

2 NO. 12 IN 3/4" C

2 NO. 12

1 NO. 8 GND

EXISTING NUMBERED LEGEND:

EMERGENCY ENGINE GENERATOR KOHLER MODEL #200ROZD (175KW).

BATTERY CHARGER FOR ENGINE GENERATOR.

LOAD BANK.

LOAD BANK CONTROL PANEL.

5 AUTOMATIC CLOSED TRANSITION TRANSFER WITH BY-PASS ISOLATION SWITCH.

START-UP BATTERY FOR ENGINE GENERATOR.

REMOTE EMERGENCY STOP SWITCH

FUSEHOLDERS, 1 S/N), GROUND BUS, ALL COPPER, 208V, NEMA TYPE 1. SQUARE 'D', CATALOG #H327.

BUILDING MAIN SERVICE ENTRANCE SWITCH, 800 AMP, WITH 800 AMP FUSES, 4 WIRE (3 BLADES AND

SURGE ARRESTER, LIGHTNING PROTECTION CORP, CATALOG #PLC-20308-3.

SURG ARRESTER, 120/208V, 3PHASE, 4 WIRE, LIGHTNING PROTECTION CORP, CATALOG #LPC-20308-3.

POWER PANEL "EDP", 120/208V, 3 PHASE, 4 WIRE, 3 POLE 225A MAIN CIRCUIT BREAKER.

POWER PANEL "NEDP", 120/208V, 3 PHASE, 4 WIRE, 3 POLE 225A MAIN LUG.

E/G POWER PANEL FOR DAYTANK, SOLENOID VALVE AND LOUVERS. CATALOG #ST Q06-12-6-1005.

300KVA PAD MOUNTED TRANSFORMER. (BY MUSKEGON COUNTY).

CURRENT TRANSFORMER AND METER ENCLOSURE, NEMA TYPE 3R.

18" X 24" PULL BOX, NEMA TYPE 1 WITH COVER, HOFFMAIN ENCLOSURE.

SQUARE 'D' 30A DISCONNECT SWITCH.

5KVA POWER TRANSFORMER. ACME CORP, CATALOG #T-1-53144-1.

RAYVOSS, SPD MODEL #120-3Y-N1-3-03-A-H.

RAYVOSS, SPD MODEL #120-3Y-M3-4-06-A-H.

OBSTRUCTION LIGHTS ON CAB ROOF.

RAYVOSS, SPD MODEL #120-3Y-M3-4-06-A-H ON DISTRIBUTION PANEL (6TH FLOOR) THAT FEEDS

SQUARE 'D', CATALOG #HCM.

MAIN DISTRIBUTION PANE "MDP" WITH 800 AMP MAIN CIRCUIT BREAKER, 12/208V, 3 PHASE, 4 WIRE.

CATALOG #NQOD.

PANEL "E/G" WITH 100 AMP MAIN CIRCUIT BREAKER, 120/208V, 3 PHASE, 4 WIRE. SQUARE 'D', SQUARE 'D' CATALOG #H323N (FRN-R-100 FUSE).

HEAVY DUTY DISCONNECT SWITCH WITH 100 AMP FUSES, 3 PHASE, 3 WIRE, 100 AMP, 208VAC, 250A

3P/

250A

200A

PANEL MDP

MAIN DISTRIBUTION

800A MAIN BREAKER

NEW WORK SHOWN IN CLOUD.4.

PROVIDE NEW BREAKERS AND BRANCH CIRCUITS FOR OFFICES AND CONFERENCE ROOM.3.

INSTALL NEW CONDUIT AND CABLES FROM ASR-11 UPS TO PANEL ASR-11.

REMOVE EXISTING PANEL DASR AND CONDUIT. REMOVE EXISTING CABLES BACK TO ASR-11 UPS.2.

AFTER INSTALLATION, UPDATE PANEL SCHEDULE IN PANEL LPN-C2 LOCATED IN THE MECHANICAL 1.

NOTE 1

HEATER BELOW SINK

CONFERENCE ROOM WATER

NOT SHOWN ON SLD 225

lo tt e

MKG-1701254-E132

ELECTRICAL ONE LINE DIAGRAM

AND PANEL SCHEDULE

EXISTING PANEL LPN-C2 FED FROM MDP

E132

ONE-LINE DIAGRAM

E132 mkg-1701254-e132

2023-10-17T09:36:43-0500

DOUGLAS E WEAVER

2023-10-17T06:43:40-0500

CHUNSEI LEE FARREN

:1 lo tt e

-f

STROBE

HORN/STROBE

LEGEND:

SMOKE DETECTOR, IONIZATION TYPE

MANUAL FIRE ALARM PULL STATION

FIRE ALARM CONTROL PANEL

REMOTE ALARM ANNUNCIATOR PANEL

FACP

RAAP

SMOKE DETECTOR, DUCT MOUNTED

I

AIM ADDRESSABLE INTERFACE MODULE

BASE BUILDING FIRST FLOOR PLAN

BASE BUILDING FIRST FLOOR PLAN

F2 F2

AR1

AR2

DD

AR3

CENTER

JANITORCLOSET

CABLE POST

POWER/SIGNAL

CABLE POST

POWER/SIGNAL

BOARD

STATUS

DESK

SUPERVISOR

JANITORCLOSET

EXISTING TO REMAIN SMOKE DETECTOR

EXISTING TO REMAIN PULL STATION

EXISTING TO REMAIN STROBE

EXISTING TO REMAIN HORN/STROBE

EXISTING TO REMAIN REMOTE ANNUNCIATOR

RELOCATED SMOKE DETECTOR

RELOCATED HORN/STROBE

REPLACE EXISTING STROBE WITH HORN/STROBE

REPLACE EXISTING STROBE WITH HORN/STROBE AND RELOCATE

EXISTING TO REMAIN DUCT SMOKE DETECTOR

EXISTING TO REMAIN RELAY

CONSTRUCTION NOTES:

ALL WORK TO COMPLY WITH NFPA 72 2019 ED.

ALL WORK TO BE CLASS A

PROVIDE SHOP AND AS-BUILT DRAWINGS

ALL SPLICES TO BE MADE WITH TERMINAL STRIPS IN 6" X 6" BOX

04' 4' 8'

04' 4' 8'

*7

*6

*5

*2

*1

*3

I1

DOWN

FAN SHUT

AIM

IM

3 1

I1

AIM

IM

3 1

7 7

MKG-1701254-F101

FIRE ALARM MODIFICATION

-f mkg-1701254-f101

2023-10-17T09:36:57-0500

DOUGLAS E WEAVER

2023-10-17T06:43:50-0500

CHUNSEI LEE FARREN

�\ Or TR-4111.

0'�

�«) 9P

0 z is �

� # st,4TEs Ot

/4��----------------v-

����L All 1"1

/1; � �/ // � 'a� Ill lJ.. lfi_jJ�"-\ "Ill -z_ \

* ---n�- •!lllllll"'rt'-- *

� � --------it----� '

�" IA; /STRP...� /

6 5 4

MKG ATCT

MUSKEGON CO TY AIRPORT

MUSKEGON, MICHIGAN

6 5 4

REV APPROVED

VICINITY MAP

SCALE: NOT TO SCALE

MUSKEGON COUNTY Jl,IRPORT

MUSKEGON, f�I

DESCRIPTION

JCN REDLINE Z

DATE tPVD � u

FEDERAL AVIATION ADMINISTRATION tnBz

CENTRAL SERVICE AREA 8 ATO - TECHNICAL OPERATIONS

SUBM ITTED BY

MKG ATCT

COVER SHEET

APPROVED BY

Ml a::

LL

w U) U)

PROJECT ENGINEER MGR ENGINEERING A i f---+----+D=Es=1GN=ED - -� -- I SS-UED-BY-----+=---cDAT=E --10/0-2/2-02 -3 �Jc=N - --170-12----154

DRAWN BFS ENGINEERING SERVICES

f---+----+c=HE=CKE�D - ---I TERMINAL f

MKG-1701254-G101

THIS DRAWlj..:i PRODUCED ON THE AGL REGION CAD SYSTEM

2023-10-17T06:40:57-0500

CHUNSEI LEE FARREN

2023-10-17T09:33:01-0500

DOUGLAS E WEAVER

:2 lo tt e

-g

SYMBOLS LEGEND

AXXX

SECTION VIEW SYMBOL

DESIGNATIONSYMBOL

DETAIL

SHEET

DIRECTION

VIEW

SECTION

ELEVATION VIEW SYMBOL

ELEVATION

DETAIL TITLE1

A100

SCALE:1"=1'-0"

DETAIL NUMBER

DETAIL NAME

SHEET REFERENCE

DETAIL DRAWING SCALE

SCALE: 1" = 1"

1" 2"01"

DRAWING SCALE

DISTANCE

SCALE REFERENCE

BAR SCALE

VIEW SYMBOL

PICTURE OR DRAWING

DRAWING

PICTURE OR

ENLARGED DETAIL LOCATION

INFORMATION

FOR FURTHER

WILL BE ENLARGED

AREA OF DETAIL THAT

DETAIL NUMBER

REFERENCE

KEYNOTE INDICATOR

DEMOLITION WORK

KEYNOTE

XX

XX

KEYNOTE

KEYNOTE INDICATOR

NEW WORK

CONDITIONS WHICH ARE REQUIRED TO MAINTAIN THE ORIGINAL QUALITY OF MATERIALS AND EQUIPMENT.

MATERIAL AND EQUIPMENT MANUFACTURER'S INSTRUCTIONS REGARDING TEMPERATURE LIMITATIONS AND OTHER ENVIRONMENTAL

INCLUDING DAMAGE WHICH MIGHT RESULT FROM INTRUSIONS OF FOREIGN MATTER OR MOISTURE FROM ANY SOURCE. COMPLY WITH

TRANSPORT, DELIVER, HANDLE AND STORE MATERIALS AND EQUIPMENT AT THE JOB SITE IN SUCH A MANNER AS TO PREVENT DAMAGE, 16.

ALL WORK SHALL BE PLUMB, SQUARE, LEVEL, IN PROPER ALIGNMENT, AND SECURELY FASTENED.15.

DO NOT ALLOW ADHESIVE ODOR AND OTHER FUMES FROM CONSTRUCTION ACTIVITY TO ENTER HVAC SYSTEM.14.

SATISFACTION OF THE RESIDENT ENGINEER.

INCLUDED IN THE SCOPE OF THIS PROJECT, SHALL BE REPAIRED AND CORRECTED AT SUBCONTRACTOR'S EXPENSE AND TO THE

FIREPROOFING ON STRUCTURAL ELEMENTS AND FIRE RATED ASSEMBLIES. ANY DAMAGE TO THE EXISTING BUILDING AND/OR SITE, NOT

DISTURBED AREAS TO MATCH ADJACENT MATERIALS AND FINISHES. EXTEND PATCH TO THE NEAREST NATURAL BREAK POINT. REPAIR

PROVIDE PROTECTION FOR ALL EXISTING FINISHES TO REMAIN, AND REPAIR ANY DAMAGE THAT OCCURS. PATCH AND FINISH 13.

RESIDENT ENGINEER PRIOR TO THE COMMENCEMENT OF ANY WORK.

TO DURING THE DEMOLITION AND CONSTRUCTION PHASES. A COPY OF SUCH INSURANCE COVERAGE SHALL BE FURNISHED TO THE

ADEQUATELY PROTECT PERSONS AND PROPERTY. COPIES OF ALL APPLICABLE PERMITS SHALL BE MAINTAINED ON-SITE AND ADHERED

COST OF PROPER INSURANCE AS REQUIRED BY STATE AND LOCAL LAWS, NATIONAL BUILDING REGULATIONS OR CODES TO

THE SUBCONTRACTOR SHALL APPLY FOR AND OBTAIN ALL PERMITS REQUIRED BY REGULATORY AGENCIES. COSTS SHALL INCLUDE THE 12.

AREAS CONCEAL PIPING, DUCTWORK WIRING AND CONDUITS.

THAT PIPING, WIRING, DUCTWORK AND CONDUITS ALLOW FOR MAXIMUM ACCESSIBILITY FOR MAINTENANCE AND REPAIRS. IN FINISHED

ESTABLISH ROUTING FOR ELECTRICAL, TELECOMMUNICATION, PLUMBING, MECHANICAL AND SECURITY SYSTEMS AS REQUIRED SO

THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF NEW CONSTRUCTION WITH EXISTING CONSTRUCTION TO REMAIN. 11.

WRITING FOR SERVICE INTERRUPTIONS A MINIMUM OF 14 BUSINESS DAYS PRIOR TO PLANNED INTERRUPTION.

OTHER CHANGE IN OPERATION TO THE SYSTEM. SERVICE OR UTILITY IN QUESTION. THE SUBCONTRACTOR WILL MAKE REQUESTS IN

WORK, CONSULT RESIDENT ENGINEER TO ARRIVE AT A MUTUALLY ACCEPTABLE SCHEDULE FOR THE INTERRUPTION, SWITCH OVER OR

PRIOR TO ANY TEMPORARY INTERRUPTION OF SERVICES DEEMED ABSOLUTELY NECESSARY BY THE CONTRACT TO PERFORM THE 10.

ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED. 9.

DISCREPANCY IN DIMENSIONS PRIOR TO BEGINNING NEW CONSTRUCTION.

ALL DIMENSIONS ARE FROM FINISHED WALL TO FINISHED WALL, UNLESS OTHERWISE NOTED. NOTIFY RESIDENT ENGINEER OF ANY 8.

SPECIFICATIONS.

PROVIDE AND INSTALL ALL MANUFACTURED ITEMS, MATERIALS AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S 7.

PROPERTY AND DISPOSED OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL CODES AND REGULATIONS.

BASIS. ALL WASTE, DEBRIS, UNUSED MATERIALS AND OTHER UNSATISFACTORY MATERIALS MUST BE REMOVED FROM THE PROJECT

THE WORK AREA IS TO BE KEPT CLEAN AND ORDERLY AT ALL TIMES. REFUSE AND DEBRIS SHALL BE LAWFULLY REMOVED ON A REGULAR 6.

ALL PHASES OF THE WORK AND WITHIN THE SCOPE OF THE CONTRACT DOCUMENTS.

REGULATIONS. SUBCONTRACTOR WILL OBTAIN AND BE RESPONSIBLE FOR ALL FEES AND PERMITS REQUIRED AND ASSOCIATED WITH

ALL WORK PERFORMED BY THE CONTRACTOR SHALL BE DONE IN ACCORDANCE WITH APPLICABLE CODES, ORDINANCES, AND 5.

DETERMINED BY THE CONTRACTING OFFICER) SHALL BE FURNISHED.

DETERMINED BY THE CONTRACTING OFFICER) SHALL GOVERN, AND THE GREATER QUANTITY AND THE HIGHER QUALITY ( AS

IN CASE OF CONFLICT BETWEEN OR WITHIN THE VARIOUS CONTRACT DOCUMENTS, THE MORE STRINGENT REQUIREMENTS (AS 4.

AREAS OF CONSTRUCTION.

PROTECTION AND SAFETY OF TENANTS AND GENERAL PUBLIC. IT IS THE RESPONSIBILITY OF THE SUBCONTRACTOR TO SECURE THE

AND MAINTAIN BARRICADES, DANGER SIGNALS AND MAINTAIN BARRICADES, DANGER SIGNALS AND SIGNS IN AREAS OF WORK FOR

MAINTAIN ALL BUILDING LIFE SAFETY, FIRE PROTECTION AND SECURITY SYSTEMS AT ALL TIMES. DO NOT BLOCK EXITS. PROVIDE, ERECT 3.

AREAS OF THE PROJECT SITE TO EMERGENCY AND SECURITY VEHICLES AT ALL TIMES AND WITHOUT DELAY DURING CONSTRUCTION.

CONTRACTOR MUST MAINTAIN ACCESS AND HAUL ROUTES IN A MANNER THAT ALLOWS UNOBSTRUCTED EMERGENCY ACCESS TO ALL

TRAFFIC ACCESS SHALL BE MAINTAINED DURING THE DEMOLITION AND CONSTRUCTION PHASES OF THIS PROJECT, IN ADDITION, THE

THE SUBCONTRACTOR SHALL VERIFY AND COORDINATE ALL SITE AND BUILDING ACCESS WITH THE RESIDENT ENGINEER. LOCAL 2.

THE WORK. ALLOW TIME FOR PROBLEM RESOLUTION WITHOUT DELAYING THE WORK.

RESIDENT ENGINEER OF ANY CONFLICTS BETWEEN FIELD CONDITIONS AND DRAWINGS PRIOR TO PROCEEDING WITH ANY PORTION OF

THE SUBCONTRACTOR SHALL VERIFY AND COORDINATE THE SCOPE OF WORK WITH EXISTING SITE AND BUILDING CONDITIONS. NOTIFY 1.

GENERAL ARCHITECTURAL NOTES:

A SMOOTH AND FLUSH TRANSITION.

PREP EXISTING WALLS TO RECEIVE NEW FINISHES AS REQUIRED AND ALIGN ALL NEW WALLS TO EXISTING WALLS TO PROVIDE 6.

ITEMS SALVAGED FOR RE-USE SHALL BE CLEANED, STORED AND RE-INSTALLED AS REQUIRED BY NEW WORK.5.

IMMEDIATELY TO THE RESIDENT ENGINEER ATTENTION.

ANY EVIDENCE OF HAZARDOUS MATERIALS (I.E ACM'S) PRIOR TO OR DURING CONSTRUCTION SHALL BE BROUGHT 4.

IN DIMENSIONS PRIOR TO BEGINNING DEMOLITION.

TO ACCOMMODATE NEW WORK. REFER TO NEW CONSTRUCTION PLANS. NOTIFY RESIDENT ENGINEER OF ANY DISCREPANCY

ALL DIMENSION ON DEMOLITION PLANS ARE FOR ROUGH OPENINGS TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED 3.

CONSTRUCTION AT NO ADDITIONAL COST TO THE OWNER.

AND NOT INDICATED TO BE REMOVED WILL BE REPAIRED TO "LIKE NEW" CONDITION AND WILL MATCH EXISTING ADJACENT

PROTECT ALL EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE DURING CONSTRUCTION ACTIVITIES. ANY AREA DAMAGED 2.

DISCARDED.

COORDINATE WITH RESIDENT ENGINEER ALL ITEMS THAT ARE TO BE REMOVED AND RETURNED TO THE OWNER OR 1.

GENERAL DEMOLITION NOTES

DRAWING INDEX

MKG-1701254-G102

SYMBOLS AND NOTES AND DRAWING INDEX

-g

DWG. LIST REV. DATE DESCRIPTION

GENERAL

ARCHITECTURAL

PLUMBING

ELECTRICAL

MKG-1701254-G102

MKG-1701254-G101

MKG-1701254-A105

MKG-1701254-A104

MKG-1701254-A103

MKG-1701254-A102

MKG-1701254-A101

MKG-1701254-M102

MKG-1701254-M101

MKG-1701254-P102

MKG-1701254-P101

MKG-1701254-E132

MKG-1701254-E131

MKG-1701254-E130

MKG-1701254-E129

MKG-1701254-E128

SYMBOLS AND NOTES AND DRAWING INDEX

COVER SHEET

WALL TYPES

DOOR SCHEDULE AND DOOR DETAILS

CABINET DETAILS

FIRST FLOOR RCP PLAN

MECHANICAL FIRST FLOOR PLAN DEMO/NEW CONSTRUCTION

MECHANICAL LEGEND, NOTES AND SCHEDULES

PLUMBING FIRST FLOOR PLAN DEMO/NEW CONSTRUCTION

PLUMBING LEGEND, NOTES AND SCHEDULES

ELETRICAL ONE LINE DIAGRAM AND PANEL SCHEDULE

LUMINAIRE SCHEDULE AND FIXTURE DETAILS

LIGHTING AND POWER PLAN BASE BUILDING

ELECTRICAL DEMOLITION FIRST FLOOR PLAN

ELECTRICAL LEGEND AND ABBREVIATIONS

FIRE PROTECTION

MKG-1701254-F101 FIRE PROTECTION CONSTRUCTION PLANS10/02/2023

mkg-1701254-g102

2023-10-17T09:33:20-0500

DOUGLAS E WEAVER

2023-10-17T06:41:10-0500

CHUNSEI LEE FARREN

lo t t e d b

BFEDERAL AVIATION ADMINISTRATION

ISSUED BY DATE

SYMBOLS BLADESMANUFACTURER MODEL # LINKAGE

DAMPER SCHEDULE

SIZE (WxH)

4. FACTORY PROVIDED THERMOSTAT TRANSFORMER

3. AUTOMATIC CHANGEOVER BETWEEN HEATING & COOLING

2. YOUNG DIGITAL THERMOSTAT

1. FACTORY INSTALLED ELECTRIC ACTUATOR

REMARKSTYPE

MD-1 YOUNG REGULATOR ROUNDMODULATING2075 EXPOSED 1,2,3,4

MECHANICAL LEGEND:

THERMOSTATT

DEVICE TYPE/AIRFLOW/NECK SIZE

SA

8"Ø

AIRFLOW DIRECTION

FLEX DUCT

MANUAL VOLUME DAMPER

2'x2' SUPPLY DIFFUSER

2'x2' RETURN GRILLE

ROOF ABOVE

SUPPLY DUCT UP TO FLOOR ABOVE/THRU

ROOF ABOVE

RETURN DUCT UP TO FLOOR ABOVE/THRU

MODULATING DAMPER

W/

TYP

TEMP

T-STAT

SA

RTU

RA

OA

MIN

MBH

INWC

FLR

FD

ESP

(ETBR)

(ETR)

(E)

DN

DEG F

COORD

CONT

CONN

CLG

CFM

ABV

WITH

TYPICAL

TEMPERATURE

THERMOSTAT

SUPPLY AIR

ROOFTOP UNIT

RETURN AIR

OUTSIDE AIR

MINIMUM

1,000 BRITISH THERMAL UNIT

H2O INCHES WATER PRESSURE

FIRE DAMPER

EXTERNAL STATIC PRESSURE

EXISTING TO BE REMOVED

EXISTING TO REMAIN

DEGREES FAHRENHEIT

COORDINATE

CONTINUATION

CONNECT

CUBIC FEET PER MINUTE AIRFLOR

ABOVE

FIRE DAMPER

AIR DEVICE SCHEDULE

SYMBOLS TYPE MATERIAL FINISH

S-1 SUPPLY DIFFUSER STEEL WHITE

1,2,3

& MODEL #

MANUFACTURER

SIZE

R-1 STEEL WHITE24x24

CEILING MOUNT3.

NC VALUE SHALL NOT EXCEED 302.

4-WAY ADJUSTABLE1.

RETURN GRILLE

PRICE #SCD

PRICE #PDDR

24X24

2,3

ROOM

SUPPLY

JAN CLOSET

RTU AIR BALANCE TABLE

OUTSIDE AIRFLOW (380 CFM)

UTILIZE OUTSIDE AIR AND EXHAUST DAMPERS AT ROOF TOP UNIT TO ACCOMMODATE REVISED MINIMUM 4.

UNIT HAS AN ECONOMIZER MODE 3.

SUBCONTRACTOR SHALL ADJUST EXISTING RTU TO ACCOMMODATE REVISED AIRFLOWS2.

EXISTING UNIT AIRFLOWS ARE BASED ON EXISTING CONDITION DRAWINGS1.

EXISTING AIRFLOW (CFM)

WOMEN 150

MEN 150

RETURN EXHAUST MIN OUTSIDE AIR

SUPPLY

REVISED AIRFLOW (CFM)

RETURN EXHAUST MIN OUTSIDE AIR

CORRIDOR #100

1,975 1,975TRACON

240 240NATCA OFFICE #104

300 300TELCO

--CORRIDOR #101

OFFICE A #102

OFFICE A #103

CONFERENCE RM #105

3,195 2,815TOTAL

UNKNOWN

240 240

300 300

1,970 1,590

100 100

100 100

400 400

EXISTING PACKAGE AIR CONDITIONING UNIT SCHEDULE

SCHEDULE BASED ON EXISTING CONDITION DRAWINGS2.

ECONOMIZER CYCLE1.

SYMBOLS AREA SERVED MAKE & MODEL

RTU

FLOW (CFM)

VERTICAL

DISCHARGE

ATCT BASE BUILDING CARRIER 48DP008 3,200

TOTAL (BTUH)

SUPPLY FAN

ESP (IN WC)

0.70

AIR (CFM)

OUTSIDE

UNKNOWN 98,000

COOLING MODE

SENSIBLE (BTUH)

73,000

TOTAL (MBH) # STAGES

2 (110/150)

GAS HEAT

1, 2

ADVANCE OF ANY AND ALL UTILITY/SYSTEM SHUTDOWNS.

SUBCONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE RESIDENT ENGINEER, IN WRITING, 10 WORKING DAYS IN 5.

NOTIFY THE RESIDENT ENGINEER PRIOR TO PROCEEDING WITH DEMOLITION.

WHERE DEMOLITION WOULD AFFECT THE STRUCTURAL INTEGRITY OF THE BUILDING, THE SUBCONTRACTOR SHALL 4.

INDICATED TO REMAIN.

DEMOLITION SHALL BE PERFORMED IN SUCH A MANNER THAT WILL NOT DAMAGE ADJOINING SURFACES OR EQUIPMENT 3.

REQUIRED TO BE REMOVED IN PREPARATION FOR INSTALLATION OF NEW CONSTRUCTION.

REMOVAL OF EQUIPMENT, DUCTWORK, CEILING DEVICES, DAMPERS, CONTROLS, ETC THAT MIGHT REASONABLY BE

RENOVATED CONSTRUCTION WHETHER OR NOT SPECIFICALLY NOTED. THIS SHALL INCLUDE BUT NOT LIMITED TO:

MECHANICAL SUBCONTRACTOR SHALL PROVIDE ALL DEMOLITION WORK INCIDENTAL TO OR REQUIRED FOR NEW AND

SPECIFIC DEMOLITION NOTES ARE NOT TO BE CONSIDERED ALL INCLUSIVE OR COMPLETE IN THEMSELVES. THE 2.

DEMOLITION WORK.

DOCUMENTS AND VERIFIED FIELD CONDITIONS SHALL BE REPORTED TO THE RESIDENT ENGINEER PRIOR TO STARTING

THE EXACT SIZES AND ROUTING OF EXISTING DUCTWORK, ETC. ANY DISCREPANCIES BETWEEN THE CONSTRUCTION

BEFORE DEMOLITION WORK BEGINS THE SUBCONTRACTOR SHALL VERIFY THE CONDITION OF ALL EXISTING EQUIPMENT, 1.

MECHANICAL DEMOLITION NOTES:

DIFFUSERS AND GRILLES.

PROVIDE MANUAL BALANCING/VOLUME DAMPERS AT ALL SUPPLY AND RETURN LOW PRESSURE BRANCH TAKE-OFFS TO 13.

ALL DIFFUSERS, GRILLES, AND REGISTERS SHALL BE IN ACCORDANCE WITH THE DIFFUSER/GRILLE/REGISTER SCHEDULE.12.

FLEXIBLE DUCT.

DIFFUSERS, GRILLES, AND REGISTERS CONNECTED TO FLEXIBLE DUCT SHALL BE SUPPORTED INDEPENDENTLY OF THE 11.

STAINLESS STEEL BANDS SHALL BE USED FOR FLEXIBLE DUCT CONNECTIONS.10.

SUPPORT ALL FLEXIBLE DUCTWORK AT AN INTERVAL NOT LESS THAN 5'-0" ON CENTER.9.

PULL FLEXIBLE DUCTWORK TAUGHT AND INSTALL AS STRAIGHT AS POSSIBLE.8.

TRIM FLEXIBLE DUCTWORK RUNS TO THE MINIMUM LENGTH NECESSARY TO MAKE CONNECTION.7.

THE USE OF DOVETAIL AND/OR SEAL TIGHT FACE MOUNTED TAP-INS ARE NOT ACCEPTABLE.6.

DO NOT CONSTRUCT OR INSTALL TAPS OUT OF REDUCERS, TEES, AND/OR ELBOWS.5.

LOW PRESSURE DUCTWORK SHALL USE SPIN-IN AND VOLUME DAMPERS FOR ROUND TAKE OFFS FROM SQUARE DUCT.4.

ALL SUPPLY AND RETURN AIR DUCTWORK SHALL BE INSULATED.3.

ALL OTHER TRADES AND EXISTING CONDITIONS.

INSTALL DUCTWORK AS HIGH AS POSSIBLE, UNLESS INDICATED OTHERWISE. COORDINATE DUCTWORK ELEVATIONS WITH 2.

REQUIREMENTS.

ALL DUCTWORK IS SHOWN AS FREE AREA INSIDE DIMENSIONS, REFER TO SPECIFICATIONS FOR INSULATION 1.

MECHANICAL DUCTWORK NOTES:

MECHANICAL SUBCONTRACTOR MUST PROVIDE ALL REQUIRED CONTROL WIRING AND CONDUIT.24.

OPERATION OF CONTROLS REPORT SHALL BE PROVIDED TO THE ENGINEER OF RECORD FOR REVIEW.

MECHANICAL SYSTEMS WITHIN THE SCOPE OF WORK. UPON COMPLETION OF WORK, A WRITTEN TEST & BALANCE AND

UPON COMPLETION OF WORK AN INDEPENDENT AND CERTIFIED T&B COMPANY SHALL TEST AND BALANCE ALL 23.

INSTALL ALL BALANCING DEVICES NEEDED TO ACHIEVE PROPER ADJUSTING AND BALANCING OF MECHANICAL SYSTEMS.22.

MOUNT THERMOSTATS WHERE INDICATED ON PLANS AT 4'-0" ABOVE FINISH FLOOR UNLESS NOTED OTHERWISE.21.

SUNLIGHT & SUPPLY AIR, & OBSTRUCTIONS THAT CREATE STAGNANT AIR AT THE THERMOSTAT.

LOCATE THERMOSTATS TO AVOID HALLWAYS, WINDOWS, EXTERIOR DOORS, EXTERIOR WALLS, DIRECT EXPOSURE TO 20.

DUCTWORK SHALL NOT RUN OVER ELECTRIC PANELS.19.

CEILING TILES OR CEILING STRUCTURE.

ALL DUCTWORK ABOVE GRADE SHALL BE PROPERLY SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST ON 18.

UNLESS OTHERWISE NOTED, GUARANTEE ALL PARTS AND LABOR FOR ONE YEAR FROM DATE OF FINAL ACCEPTANCE.17.

TYPE.

SENSORS, ETC IN CEILINGS AND WALLS. ACCESS PANELS IN RATED ASSEMBLIES SHALL BE LISTED AND SELF-CLOSING

SUBCONTRACTOR SHALL PROVIDE ACCESS PANELS WHERE REQUIRED FOR ACCESS TO VALVES, DAMPERS, ACTUATORS, 16.

ADDITIONAL EXPENSE TO THE FAA/PARSONS.

MAKE ALL NECESSARY DUCTWORK OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT 15.

PROVIDING SUFFICIENT SPACE TO MEET ALL OTHER TRADE CLEARANCE REQUIREMENTS.

TRADES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL, PLUMBING, AND GENERAL CARPENTRY. THIS SHALL INCLUDE

IT SHALL BE THE RESPONSIBILITY OF THIS SUBCONTRACTOR TO COORDINATE THEIR WORK WITH THAT OF ALL OTHER 14.

COMPONENTS AND ACCESSORIES IS PROHIBITED.

QUALITY. UNLESS INDICATED OTHERWISE, THE REUSE OF EXISTING DEVICES, MATERIALS, EQUIPMENT AND ASSOCIATED

ALL EQUIPMENT, DUCTWORK, DEVICES, DAMPERS, CONTROLS, VALVES, PIPING, INSULATION, ETC SHALL BE FIRST 13.

PRIOR TO STARTING WORK.

THE DESIGN DOCUMENTS AND MANUFACTURER'S REQUIREMENTS, THIS SUBCONTRACTOR SHALL NOTIFY THE ENGINEER

STARTING WORK. ALL WORK SHALL ADHERE TO THE MANUFACTURERS' REQUIREMENTS. IF A CONFLICT EXISTS BETWEEN

REVIEW ALL APPLICABLE MANUFACTURERS' INSTALLATION AND MAINTENANCE DOCUMENTS/REQUIREMENTS PRIOR TO 12.

PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURER'S RECOMMENDATIONS.11.

APPROVAL.

AND MATERIALS. SUBMIT LITERATURE FOR ALL EQUIPMENT AND MATERIALS TO THE ENGINEER OF RECORD FOR

MANUFACTURER'S MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY FOR PERFORMANCE 10.

INSTALLATION.

FURNISH ANY MISCELLANEOUS ITEMS NORMALLY USED, SPECIFICALLY MENTIONED OR NOT, TO RENDER A COMPLETE 9.

MAINTAIN INTEGRITY OF LISTED ASSEMBLY, PROVIDE SLEEVES WHERE REQUIRED.

SEAL ALL EXISTING AND NEW FLOOR/ROOF/WALL PENETRATIONS WITHIN THE SCOPE OF WORK AS REQUIRED TO 8.

ENGINEER'S REVIEW AND APPROVAL.

STRUCTURAL COMPONENTS SHALL NOT BE CUT, DRILLED OR MODIFIED IN ANY MANNER WITHOUT A STRUCTURAL 7.

VERIFY SIZES, LOCATIONS, INVERTS AND ELEVATIONS PRIOR TO RUNNING ANY DUCTWORK.6.

OFFSETTING EXISTING PIPING AND MODIFICATIONS REQUIRED FOR COORDINATION WITH ALL OTHER TRADES.

EXISTING CONDITIONS TO PERFORM WORK OF THIS SECTION. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, SYSTEMS/UTILITIES IN FIELD, WHETHER OR NOT SHOWN ON DRAWINGS. MAKE ALL NECESSARY MODIFICATIONS TO

COMPLETION OF LOCATIONS SHOWN ON DRAWINGS IS GUARANTEED. DETERMINE EXACT LOCATIONS OF EXISTING

ALL EXISTING CONDITIONS SHOWN ARE TAKEN FROM EXISTING DRAWINGS AND FIELD SURVEYS. NEITHER ACCURACY NOR 5.

RESOLVED PRIOR TO THE INSTALLATION OF THE WORK INVOLVED.

DRAWINGS WHICH IS IN VIOLATION SHALL BE BROUGHT TO THE ATTENTION OF THE RESIDENT ENGINEER AND SHALL BE

NO WORK SHALL BE INSTALLED IN VIOLATION OF ANY GOVERNING STANDARDS AND CODES. ANY WORK SHOWN ON THE 4.

RULES AND REGULATIONS. IN CASE OF DIFFERENCES THE MOST STRINGENT SHALL GOVERN.

ALL MECHANICAL WORK SHALL BE IN ACCORDANCE WITH FAA STANDARDS AND ALL APPLICABLE STATE AND LOCAL CODES, 3.

THE REQUIREMENTS OF THE CONTRACT.

MEANS TO BE PROVIDED FOR GETTING THE EQUIPMENT INTO PLACE, AND BECOME THOROUGHLY FAMILIAR WITH ALL OF

ANY EXISTING WORK. DETERMINE, IN ADVANCE, THE METHODS OF INSTALLING AND CONNECTING THE APPARATUS, THE

BEFORE SUBMITTING A BID CAREFULLY STUDY THE CONSTRUCTION DOCUMENTS. CAREFULLY EXAMINE THE PREMISES AND 2.

COMPONENTS. DO NOT SCALE THESE DRAWINGS.

THESE DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO DEPICT THE GENERAL LOCATION OF MECHANICAL SYSTEM 1.

HUMIDISTATH

SHEET METAL RUN OUT

WITH DUCT WRAP

PROVIDE 45° SHEET METAL

NECK WITH DUCT WRAP

ELBOW AT DIFFUSER

SUPPORT FROM STRUCTURE

WITH SHEET METAL STRIP

INSULATED

FLEXIBLE DUCT

HIGH EFFICIENCY TAKE-OFF

WITH VOLUME DAMPER

LOW PRESSURE

SUPPLY DUCT

EXTEND SHEET METAL RUN OUT TO WITHIN 5

LINEAR FEET OF DIFFUSER

FASTEN FLEXIBLE DUCT TO SHEET METAL WITH

PLASTIC CABLE TIES

TYPICAL DIFFUSION CONNECTION

M101

ABBREVIATIONS:

MECHANICAL GENERAL NOTES:

INSULATION

DIFFUSER WITH

ROUND NECK CEILING

MKG-1701254-M101

AK

MECHANICAL LEGEND, NOTES AND SCHEDULES

-m mkg-1701254-m101

2023-10-17T09:37:20-0500

DOUGLAS E WEAVER

2023-10-17T06:44:07-0500

CHUNSEI LEE FARREN

FROM RTU ABV

20x26 RA DROP

(ETR) 20x20 SA/

(300 CFM)

REGISTER

(ETR) SA

DUCT (150 CFM)

(ETR) 6" FLEX

(ETR) RA GRILLE (300 CFM)

(ETR) 22x16

CONN T-STAT TO RTU

PENETRATION (TYP)

CONN TO (E) DUCT

CAP RA OPENING

DUCT (80 CM)

(ETR) 12x12

DUCT (100

(ETR) 26x20

(TYP)

(ETR) FD

DUCT (240 CFM)

(ETR) 8" FLEX

GRILLE (240 CFM)

(ETR) RA

(ETR) 14x12

(ETR) 20x20

(ETR) 14x14 (TYP)

CAP RA OPENING

(ETR) 24x20

DUCT (100 CFM)

RTU ABV

DROP FROM

SA/ 20x26 RA

(TYP OF 4, 250 CFM)

(ETBR) 8" SA FLEXDUCT

(TYP OF 3, 325 CFM)

(ETBR) 10" SA FLEXDUCT

(ETBR) T-STAT

GRILLE (375 CFM)

(ETBR) RA

(ETBR) HUMIDISTAT

(ETR) 14x14

(375 CFM)

(ETBR) RA GRILLE

REGISTER (TYP)

(ETBR) SA (ETR) 20x16

(ETR) 20x16

(1,225 CFM)

(ETBR) RA GRILLE

(ETR) 14x14

(ETR) 14x12(ETR) FD (TYP)

(ETR) 26x20

ETR 24x20

(ETR) 12x12

DUCT (80 CFM)

DUCT (150 CFM)

(240 CFM)

(ETBR) GRILLE

REGISTER

(ETR) SA

RA GRILLE(ETR)

S-1

(ETR) 14x12(ETR) 8x8

(ETR) 10x10 (ETR) 10x10

(ETR) 20x16

R-1

10"Ø

MECHANICAL JANITOR

MD-1

(ETR) 14x12(ETR) 8x8

(ETR) 10x10 (ETR) 10x10

DUCT (240 CFM)

(ETR) 8" FLEX

(ETR) RA GRILLE

(100 CFM)

(ETR) 6" FLEX DUCT

DUCT (100 CFM)

MECHANICAL JANITOR CLOSET

FD FD

lo tt e

DEMOLITION LEGEND:

DEMO TO THIS POINT

NEW CONSTRUCTION LEGEND:

NEW CONSTRUCTION

CONNECT TO EXISTING

DEMOLITION SHEET NOTES:

SPACE. THIS EQUIPMENT HAS BEEN ABANDONED IN PLACE AND SHALL REMAIN ABANDONED IN PLACE.

THERE IS AN EXISTING STEAM HUMIDIFIER IN THE 24x20 SUPPLY AIR DUCT SERVING THE TRACON 3.

EXISTING ROOFTOP UNIT IS TO REMAIN AS IS.2.

CEILING SPACE WORK (8'-2" AND HIGHER ABOVE FINISH FLOOR) IS TO BE MINIMIZED.

FOUND ASBESTOS IN THE BUILDING'S DRYWALL JOINT COMPOUND. TO MITIGATE THE ABATEMENT, AN ASBESTOS-CONTAINING MATERIAL (ACM) INSPECTION OF THE AIR TRAFFIC CONTROL TOWER 1.

NEW CONSTRUCTION SHEET NOTES:

FIELD COORDINATE FINAL LOCATION OF ALL THERMOSTATS.2.

MECHANICAL BASE BUILDING FIRST FLOOR PLAN - DEMOLITION

M102

MECHANICAL BASE BUILDING FIRST FLOOR PLAN - NEW CONSTRUCTION

M102

DO

NOT

SI

GN

MKG-1701254-M102

MECHANICAL FIRST FLOOR PLAN

DEMOLITION/NEW CONSTRUCTION

mkg-1701254-m102

2023-10-17T09:37:36-0500

DOUGLAS E WEAVER

2023-10-17T06:44:17-0500

CHUNSEI LEE FARREN

TOP OF COUNTER

TO FAUCET CONNECTIONS

SINK

COLD WATER

1/2"CW

1/2"HW

FLOW LIMITER

WATER HEATER

INSTANT ELECT

SYMBOL

TRAPSUPPLY

SIZETYPE MANUFACTURER TYPEMODEL FAUCET

C.W H.W.

CARRIER

MOUNTED

WASTE (MIN)

PLUMBING FIXTURE SCHEDULE

FITTINGFIXTURE

McGUIRE NA NA#8912 1-1/2" P-TRAP 1-1/2"1/2" 1/2"P-1

SINK-HAND

ELKAY

LUSTERTONE LR1517 8" FAUCET CENTERS

FULLY UNDERCOATED

SELF RIMMING

STAINLESS STEEL

CENTER MOUNTED

MANUALLY OPERATED

5-1/4" RIGID GOOSENECK

CHICAGO- #201-AGN2AE3

#LFH-2165#151 BASKET STRAINER

PLUMBING LEGEND & ABBREVIATIONS:

SYMBOL

SANITARY UNDERSLAB

PIPE TURNED UP

PIPE TURNED DOWN

PIPE BREAK

P-1 FIXTURE IDENTIFICATION

SYMBOL REMARKS

kW

TEMP RISE (DEG F)

MODEL #

MANUFACTURER/

V PH

FLOW (GPM)

ELECTRIC TANKLESS WTR HTR SCHEDULE

ELECTRICAL

IWH-1 38EEMAX #8208 1.5 8.3 208 1 MOUNT IN CABINET BELOW SINK

HEATER SHALL BE LEAD FREE (MEET REQUIREMENTS OF ANSI 372)4.

REPLACEABLE FILTER SHALL BE PROVIDED IN INLET CONNECTION3.

HEATING ELEMENT SHALL BE REPLACEABLE CARTRIDGE2.

MINIMUM WORKING PRESSURE SHALL BE 150 PSI1.

PLUMBING DEMOLITION NOTES:

ADVANCE OF ANY AND ALL UTILITY/SYSTEM SERVICE INTERRUPTIONS.

THIS SUBCONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE RESIDENT ENGINEER IN WRITING 10 DAYS IN 5.

AND CAP AT NEAREST VALVE OR MAIN LINE.

FLOOR, ABOVE CEILING AND/OR IN WALLS AS REQUIRED. REMOVE ALL PIPING NOT REQUIRED FOR RENOVATION

DRAWINGS. UNLESS OTHERWISE NOTED, CAP AND CONCEAL ALL SANITARY,…