This document is a specifications and notes file for ITB-W-1528, issued by the City of Warren for City Hall Library Meeting Room Improvements, specifically focusing on A/V and electrical specifications for a viewing room upgrade. The project involves installing an LG 86" monitor mounted above a faux fireplace, with a fully automated audio-visual system utilizing a ScreenBeam 1100 Plus wireless interface and six JBL ceiling tile replacement speakers. The system will automatically power on when a signal is detected from a laptop, tablet, phone, or direct HDMI connection, and power down after approximately 25 minutes of inactivity.
The electrical specifications outline comprehensive requirements for conduit, wiring, switches, receptacles, and circuit breakers, emphasizing compliance with the National Electric Code, local and state regulations, and U.L. standards. The contractor is responsible for pulling permits (with fees waived by the city), providing all materials and labor, maintaining a set of as-built drawings, and offering a 3-year parts and labor warranty. System training will be provided to library staff upon project completion, with the overall goal of creating a seamless, technologically integrated meeting room space that blends new equipment with existing architectural elements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ITB-W-1528 Corrected.pdf | ||
| ITB-W-1528 A-2_Plan-22x34.pdf | ||
| ITB-W-1528.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A-100
AS NOTED
SPECIFICATIONS
AND NOTES
SPECIFICATIONS:
GENERAL REQUIREMENTS:
1. CONTRACTOR SHALL COORDINATE ALL WORK PRIOR TO INSTALLATION OR
FABRICATION OF ANY COMPONENTS. ALL OPENINGS SHALL ALSO BE
COORDINATED WITH REFERENCE DRAWINGS.
2. ALL WORK MUST CONFORM TO ALL STATUTES OF THE MICHIGAN BUILDING
CODE (EDITION IN EFFECT AT THE TIME OF PERMIT), ALL STATE, COUNTY AND
LOCAL ORDINANCES, CURRENT BARRIER FREE REGULATIONS, MIOSHA
STRUCTURAL GUIDELINES, ASTM STANDARD TESTING PROCEDURES, OWNER'S
PRACTICES AND GENERALLY ACCEPTED DESIGN PRACTICES. IF
DISCREPANCIES IN DRAWING APPEAR, WORK MUST BE DONE PER CODE.
3. EXISTING CONDITIONS OF BUILDING SHOWN ON CONSTRUCTION DOCUMENTS
ARE ILLUSTRATIVE OF CONDITIONS VISIBLE TO ARCHITECT AND BASED ON
EXISTING DRAWINGS. ALL EXISTING DIMENSIONS, CONDITIONS, SIZES &
LOCATIONS ARE TO BE FIELD VERIFIED.
4. THE CONTRACTOR SHALL KEEP THE SITE IN A NEAT AND ORDERLY CONDITION
AND SHALL REMOVE RUBBISH DAILY OR AS DIRECTED BY OWNER. DUST
CONTROL MEASURES ARE TO BE ERECTED BY THE CONTRACTOR TO PROTECT
PATRONS AND VEHICLES DURING DEMOLITION AND CONSTRUCTION ACTIVIES.
ALL STAGING AND MATERIALS STORAGE IS TO BE COORDINATED WITH THE
OWNER. THE CONTRACTOR SHALL TAKE PRECAUTIONS TO ISOLATE
CONSTRUCTION ACTIVITIES FROM ADJACENT AREAS THAT ARE TO REMAIN IN
OPERATION DURING CONSTRUCTION - CONFIRM SCHEDULE AND REQUIRED
BARRICADES WITH OWNER PRIOR TO COMMENCEMENT.
5. CONTRACTOR SHALL PROVIDE NEW OPENINGS AND SUPPORTS AS NOTED.
FINAL OPENING DIMENSIONS, CONNECTION SIZES, CLEARANCES, ETC. MUST BE
COORDINATED DURING CONSTRUCTION WITH APPROVED COMPONENTS. SEAL
TIGHT ALL OPENINGS (ROOF, WALL AND CEILING), EQUIPMENT AND/OR
PENETRATIONS - FROM AIR AND MOISTURE. MATCH EXISTING FINISHES. FIRE
CAULK AND SEAL ALL NEW RATED PENETRATIONS.
6. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND APPROVED
MANUFACTURERS.
7. ALL INSTALLATIONS TO BE COORDINATED WITH EXISTING CONDITIONS FOR
PROPER SIZE, LOCATION AND PROVISIONS REQUIRED TO INSTALL
COMPONENTS.
8. PIPING & CONDUIT HANGERS AND SUPPORT LOCATION ARE NOT SHOWN ON
DRAWINGS. THE CONTRACTOR SHALL PROVIDE THE PIPING AND CONDUIT
HANGERS AND SUPPORTS NECESSARY AS REQUIRED PER CODE.
9. PATCH AND REPAIR EXISTING WALLS, FLOORS, & CEILINGS FOR SEAMLESS,
LIKE NEW APPEARANCE. THIS ALSO APPLIES TO DAMAGES THAT OCCUR AS
PART OF THE CONSTRUCTION PROCESS - RETURN AFFECTED AREAS TO
ORIGINAL CONDITIONS. CAREFULLY CUT HOLES IN CEILINGS AND WALLS TO
ACCOMMODATE INSTALLATION OF PIPING - REPAIR OPENINGS TO SEAMLESS,
LIKE NEW APPEARANCE AND PAINT TO MATCH ADJACENT SURFACES.
10. EXTEND CONDUIT AND PIPING AS REQUIRED TO ACCOMMODATE NEW WORK -
PROVIDE NEW & REPAIR EXISTING AS REQUIRED.
11. PROVIDE ADDITIONAL BLOCKING TO MATCH EXISTING AT WALLS/ CEILINGS TO
ACCOMMODATE NEW INSTALLATIONS. MAINTAIN FIRE RATED ASSEMBLIES AND
FIRE STOPPING PER LOCAL GOVERNING CODES AND ORDINANCES.
12. CONTRACTOR SHALL PROVIDE ALL REQUIRED TRANSITIONS, FITTINGS AND
APPURTENANT CONNECTIONS.
13. CONFIRM ANY COLOR SELECTIONS WITH OWNER.
14. SHOP DRAWINGS AND PRODUCT DATA - THE CONTRACTOR SHALL SUBMIT TO
THE OWNER AND PROJECT ENGINEER, SHOP DRAWINGS & PRODUCT DATA
SUBMITTALS FOR ALL PRODUCTS AND COMPONENTS TO BE USED ON THIS
PROJECT. MAINTAIN ONE COPY OF ALL APPROVED SUBMITTALS AT THE SITE
FOR THE OWNER'S REFERENCE.
15. "RECORD" DRAWINGS - THE CONTRACTOR SHALL MAINTAIN A SET OF
"AS-BUILT" PRINTS, MARKED UP AT THE SITE, CONTAINING ALL "AS-BUILT"
INFORMATION. TURN SET OVER TO OWNER UPON COMPLETION OF THE WORK.
16. INSTALL ALL MATERIALS IN COMPLIANCE W/ MFR. RECOMMENDATIONS AND
CODE REQUIREMENTS.
17. WORKING HOURS AT BUILDINGS ARE BE DETERMINED WITH OWNER AT START
OF PROJECT.
18. ALL REMAINING WALLS ARE TO BE PATCHED SMOOTH PRIOR TO PAINTING FOR
A SMOOTH, UNBLEMISHED APPEARANCE.
19. CONTRACTOR MUST VERIFY ALL EXISTING UTILITY LOCATIONS PRIOR TO
START OF DEMOLITION AND MAKE EVERY EFFORT TO PROTECT THEM OR
RELOCATE AS REQUIRED.
20. CONTRACTORS TO REFER TO ENTIRE SET OF DRAWINGS AND SPECIFICATIONS
FOR FULL SCOPE OF WORK. CROSS COORDINATION BETWEEN CIVIL,
PROCESS, MECHANICAL, ELECTRICAL, STRUCTURAL AND ARCHITECTURAL
DRAWINGS IS REQUIRED.
APPROVED
CHECKED
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF WARREN
CITY HALL LIBRARY
MEETING ROOM
IMPROVEMENTS
ITB - W - 1528
MCM
AMM
QR
AMM
AFFECTED
AREA
04-08-25 ISSUED FOR BID
A/V SPECIFICATIONS:
SCOPE OF WORK: VIEWING ROOM
VIDEO MONITOR: INSTALL AN LG 86UL3J-B 86 MONITOR JUST ABOVE THE FAUX
FIREPLACE UTILIZING A SANUS VLF628-B1 WALL MOUNT CAPABLE OF BEING
POSITIONED APPROXIMATELY 24 FORWARD OF THE WALL JUST IN FRONT OF THE
EXISTING BOOKCASE. THE MONITOR WILL BE CENTERED ON THE MANTLE BELOW.
EQUIPMENT LOCATION: THE EQUIPMENT WILL BE LOCATED DIRECTLY BEHIND THE
LG MONITOR ON A COMPONENT MOUNTING PLATE. PLENUM RATED18/2 SPEAKER
WIRE WILL RUN INTO THE CEILING PLENUM SPACE DIRECTLY OVERHEAD OF THE
ROOM TO BE DAISY CHAINED WITH SIX (6) JBL LCT-81C/T 2X2 TILE REPLACEMENT
SPEAKERS TAPPED AT 5 WATTS EACH, WHICH WILL PROVIDE SUPERIOR
INTELLIGIBILITY AT EVEN LOW VOLUME LEVELS WHILE BLENDING SEAMLESSLY INTO
THE SURROUNDING CEILING TILES.
SYSTEM OPERATIONAL OVERVIEW:
THE SYSTEM OPERATION WILL BE FULLY AUTOMATED AS FOLLOWS.
POWER ON THIS WILL OCCUR WHEN:
1. THE SYSTEM SENSES A SOURCE INPUT SIGNAL WIRELESSLY AT THE
SCREENBEAM 1100 PLUS WIRELESS INTERFACE USING A LAPTOP, TABLET OR
APPLE / ANDROID PHONE.
2. THE SYSTEM SENSES AN INPUT SIGNAL FROM A DIRECT HDMI CONNECT AT THE
WALL INPUT LOCATION.
IN EITHER SCENARIO, THE SYSTEM INCLUDING VIDEO MONITOR WILL
AUTOMATICALLY POWER UP WHEN A SIGNAL IS SENSED.
VOLUME AND ANY INTERACTION WITH THE VIDEO ON DISPLAY ARE CONTROLLED
FROM THE SOURCE DEVICE.
POWER OFF THIS WILL OCCUR WHEN:
THE SYSTEM TIMER HAS NOT RECEIVED A SIGNAL IN APPROXIMATELY 25 MINUTES,
THE ENTIRE SYSTEM WILL POWER DOWN.
VOLUME CONTROL, PLAY PAUSE, FFWD, RWND
THESE FUNCTIONS ARE CONTROLLED FROM THE USER (PRESENTERS) SOURCE
DEVICE (COMPUTER, TABLET OR PHONE) VOLUME UP /DOWN MAY ALSO BE
CONTROLLED WITH LG DISPLAY MONITORS REMOTE CONTROL (INCLUDED)
PROJECT FINISH:
THE SPACE SHALL BE CLEANED AND ANY FURNITURE MOVED SHALL BE RETURNED
TO ORIGINAL PLACEMENT UPON PROJECT COMPLETION.
WARRANTY:
THE COMPLETE INSTALLATION WILL BE COVERED BY A 3 YEAR PARTS & LABOR
WARRANTY.
SYSTEM TRAINING:
TRAINING WILL BE PROVIDED AT PROJECT FINISH WITH LIBRARY STAFF.
GENERAL NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PULLING ALL PERMITS
NECESSARY FOR THE PROJECT. THE PERMIT FEES SHALL BE WAIVED BY THE
CITY.
2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE
(N.E.C.), N.F.P.A., O.S.H.A., LOCAL AND STATE CODES, ORDINANCES AND
REGULATIONS.
3. ALL POWER WIRING 120 VOLTS AND GREATER SHALL BE INSTALLED IN CONDUIT
AND SHALL BE NEW. UNLESS NOTED OTHERWISE, ELECTRICAL METALLIC TUBING
(EMT) SHALL BE USED WHERE CONDUIT IS EXPOSED. CONDUIT ABOVE CEILING
OR IN WALLS MAY BE EMT OR METAL CLAD (MC) CABLE.
4. ALL CONDUITS SHALL BE ROUTED TO AVOID OPENINGS IN FLOORS, ROOFS, AND
WALLS. LADDERS UP WALLS SHALL NOT BE CROSSED BY EXPOSED CONDUIT
RUNS. PROVIDE THE MINIMUM CLEAR SPACE REQUIRED BY ALL GOVERNING
CODES BETWEEN HANDRAILS AND ALL ELECTRICAL ENCLOSURES AND
RACEWAYS, WHICH IN NO CASE SHALL BE LESS THAN 1 1/2" CLEAR.
5. WHERE NEW WALLS ARE TO BE INSTALLED, NEW CONDUIT SHALL BE RUN
CONCEALED IN THE WALL. RECEPTACLES AND SWITCHES SHALL BE FLUSH
MOUNTED. WHERE RECEPTACLES AND SWITCHES ARE INSTALLED ON EXISTING
WALLS OR AREAS, DEVICES SHALL BE SURFACE MOUNTED, AND CONDUIT SHALL
BE RUN SURFACE MOUNTED.
6. PROVIDE A GREEN GROUND CONDUCTOR IN ALL SYSTEMS CONDUITS. GROUND
CONDUCTOR SIZING SHALL BE PER NEC TABLE 250.122 WHERE NOT SIZED ON
THE DRAWINGS.
7. ALL MATERIALS USED SHALL BE NEW AND BEAR THE U.L. LABEL WHERE SUCH
SERVICE AND LABEL ARE REGULARLY PROVIDED AND BE OF THE APPROPRIATE
NEMA STANDARD.
8. THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR AS INDICATED ON
PLANS AND AS REQUIRED FOR A COMPLETE, REVISED ELECTRICAL SYSTEM.
9. COORDINATE EXACT LOCATION OF ALL LIGHTING FIXTURES AND OTHER
ELECTRICAL DEVICES WITH MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK
BEFORE INSTALLATION.
10. ALL THREADED ELECTRICAL EQUIPMENT (CONDUIT, FITTINGS, BOLTS, SCREWS,
ETC.) SHALL BE COATED WITH ANTI-SEIZE COMPOUND PRIOR TO INSTALLATION.
ALL HARDWARE SHALL BE STAINLESS STEEL.
11. EACH OF THE SPECIFIED EQUIPMENT SHALL BE SUBMITTED FOR APPROVAL BY
REFERENCE TO MANUFACTURER AND SPECIFIC CATALOG AND MODEL NUMBER.
12. THE CONTRACTOR SHALL VISIT THE JOB SITE, THOROUGHLY CHECK THE
EXISTING FIELD CONDITIONS AND EXISTING ELECTRICAL INSTALLATIONS, AND
CLARIFY ALL DISCREPANCIES WITH THE ENGINEER BEFORE SUBMITTING A BID,
AS NO EXTRAS WILL BE ALLOWED FOR OMITTED WORK DUE TO FAILURE TO
INSPECT THE PREMISES.
13. ON COMPLETION OF WORK AND BEFORE FINAL PAYMENT IS MADE, THIS
CONTRACTOR SHALL PREPARE "AS-BUILT DRAWINGS". CLEARLY INDICATE ON A
SET OF CONTRACT DRAWINGS ALL THE CHANGES MADE DURING
CONSTRUCTION, DUE TO FIELD CONDITIONS, ADDENDA, BULLETINS, ETC.
DRAWINGS SHALL INDICATE THE INSTALLED LOCATION OF ALL EQUIPMENT,
OUTLETS, ETC.
14. WHEN THE JOB IS COMPLETE, CONTRACTOR SHALL PROVIDE THE OWNER WITH
CERTIFICATE OF APPROVAL FROM THE ELECTRICAL INSPECTION AUTHORITY
AND SHALL PROVIDE THE OWNER WITH A ONE YEAR WRITTEN GUARANTEE ON
ALL NEW MATERIALS AND LABOR.
15. RE-SUPPORT EXISTING CONDUIT, BOXES, ETC. WHERE CEILING OR SUPPORT
REVISIONS NECESSITATES NEW SUPPORTS. ALL WORK SHALL BE COORDINATED
WITH OTHER DISCIPLINES.
16. ALL DEMOLISHED ITEMS SHALL BE DISPOSED OF AWAY FROM THE SITE.
BASIC MATERIALS AND METHODS
1. WIRE FOR GENERAL USE SHALL BE COPPER, TYPE THHN/THWN, 90 DEGREES C.
ALUMINUM WIRE SHALL NOT BE USED. ALL WIRE SHALL BE RATED AT 600 VOLTS,
WET AND DRY LOCATION, MINIMUM SIZE NO. 12 A.W.G. INSTALLED IN CONDUIT,
SIZED AS SHOWN ON THE DRAWINGS, MINIMUM SIZE 3/4".
2. BOXES SHALL BE GALVANIZED STEEL, CODE THICKNESS, A MINIMUM OF 1" DEEP
AND OF SUFFICIENT SIZE TO ACCOMMODATE THE DEVICES THEY SERVE,
ACCORDING TO N.E.C. REQUIREMENTS. PULL BOXES FOR ALL CONDUIT RUNS
FOR ALL SYSTEMS SHALL BE INSTALLED AT INTERVALS NOT EXCEEDING 100
FEET OR AFTER 270 DEGREES OF BENDS.
3. CONDUITS SHALL NOT BE SUPPORTED FROM MECHANICAL DUCTS, PIPE, OR PIPE
AND DUCT SUPPORTS.
4. ELECTRIC SYSTEM GROUNDING SHALL IN ALL INSTANCES COMPLY WITH THE
MINIMUM REQUIREMENTS OF THE N.E.C. ALL CONDUITS SERVING WIRING OF 120
VOLTS OR GREATER SHALL INCLUDE A GROUND WIRE.
5. ELECTRICAL ENCLOSURES, CONDUIT SYSTEMS, ETC., SHALL BE THOROUGHLY
GROUNDED IN ACCORDANCE WITH THE N.E.C. AND ALL LOCAL CODES.
6. ALL CONDUITS SHALL BE ROUTED TO AVOID OPENINGS IN FLOORS, ROOFS, AND
WALLS. LADDERS UP WALLS SHALL NOT BE CROSSED BY EXPOSED CONDUIT
RUNS. PROVIDE THE MINIMUM CLEAR SPACE REQUIRED BY ALL GOVERNING
CODES BETWEEN HANDRAILS AND ALL ELECTRICAL ENCLOSURES AND
RACEWAYS, WHICH IN NO CASE SHALL BE LESS THAN 1 1/2" CLEAR.
7. FOR ALL 120 VAC LIGHTING AND RECEPTACLE CIRCUITS, RUN 2-#12 (MINIMUM) +
#12 GRD., 1/2"C. TO THE LIGHTING PANELBOARD INDICATED, UNLESS NOTED
OTHERWISE.
8. GFI DUPLEX RECEPTACLES SHALL BE 125 VOLT, 3 WIRE GFCI TYPE WITH FACE
MOUNTED TEST AND RESET BUTTONS AND MATCHING STAINLESS STEEL COVER
PLATE, HUBBELL HBL GF-5362-I, LEVITON 6898-I, OR EQUAL. ALL SWITCHES AND
RECEPTACLES SHALL BE PROVIDED WITH STAINLESS STEEL COVER PLATES.
9. DUPLEX RECEPTACLES SHALL BE 20 AMP, 125 VOLT, 3 WIRE, GROUNDING TYPE
BY HUBBELL, GE, COOPER, OR EQUAL.
10. SWITCHES AND RECEPTACLES SHALL BE PROVIDED WITH COVER PLATES -
CONFIRM COLOR/FINISH WITH OWNER, MATCH EXISTING AS NOTED. SWITCHES
AND RECEPTACLES TO BE SURFACE MOUNTED SHALL BE INSTALLED IN METAL
BOXES.
11. CIRCUIT BREAKERS FOR PANELBOARDS SHALL BE OF THE BOLT-IN-PLACE OR
STAB-IN TYPE USING SINGLE POLE OR COMMON TRIP, TWO OR THREE POLE AS
INDICATED ON THE DRAWINGS. CIRCUIT BREAKERS SHALL BE ON MOLDED CASE
TYPE WITH THERMAL MAGNETIC TRIP AND BREAKER HANDLES INDICATING "ON" -
"OFF" AND "TRIP" POSITIONS. GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
TYPE BREAKERS SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS.
BREAKERS SHALL HAVE 22,000 AMPERE INTERRUPTING CAPACITY MINIMUM AND
SHALL BE APPROVED FOR "SWITCHING DUTY." ALL CIRCUIT BREAKERS SHALL BE
LOCKABLE. CIRCUIT BREAKERS SHALL BE EATON-CUTLER-HAMMER, SQUARE D
BY SCHNEIDER ELECTRIC, OR ABB.
12. WHERE INDICATED ON THE DRAWINGS, PROVIDE MODIFICATIONS TO EXISTING
PANELBOARDS AS REQUIRED. PANELBOARDS SHALL BE MODIFIED BY THE
ADDITION OF NEW DEVICES, CONNECTIONS TO EXISTING DEVICES, AND/OR
DISCONNECTION FROM EXISTING DEVICES. CIRCUIT BREAKERS FOR ADDITION
TO EXISTING PANELBOARDS SHALL BE THE PANELBOARD MANUFACTURER'S
COMPATIBLE REPLACEMENT PARTS AND SHALL MATCH THE PANELBOARD'S
EXISTING BREAKER INTERRUPTING RATINGS. BREAKER TRIP RATINGS AND
NUMBER OF POLES SHALL BE INDICATED ON THE DRAWINGS.
13. SWITCHES SHALL BE QUIET, QUICK MAKE, SLOW BREAK DESIGN WITH TOTALLY
ENCLOSED CASE, FLUSH TYPE, TOGGLE SWITCHES, 20 AMPERE CAPACITY AT
120/277 VOLTS, SINGLE POLE OR 3-WAY AS INDICATED ON THE DRAWINGS.
LIGHTING SWITCHES SHALL BE HUBBELL SERIES HBL 1220, LEVITON SERIES 1220,
GENERAL ELECTRIC GE5951, COOPER WIRING DEVICES OR EQUAL.
14. ALL CONDUIT RUNS (POWER AND CONTROL) SHALL BE LABELED IN ACCORDANCE
WITH ANSI 13.1 WITH LABELS THAT ARE WATER-RESISTANT. CIRCUIT NUMBER
MARKERS SHALL CONSIST OF SELF-ADHESIVE VINYL CLOTH OR POLYVINYL
FLOURIDE FILM MARKERS WITH 1/8" HIGH (MINIMUM), BLACK LETTERING ON A
YELLOW BACKGROUND, W.H. BRADY CO. MARKERS MAY ALSO CONSIST OF
COMPUTER GENERATED, VINYL CLOTH, PERMANENT, NON-SMEARING,
SELF-ADHESIVE MARKERS SUCH AS BRADY DATAB, BRADYMARKER XC PLUS, 3M
SCOTCHCODE SCS OR STS, OR EQUAL. CIRCUIT NUMBER MARKERS FOR
PANELBOARD CIRCUIT BREAKERS MAY BE THE MANUFACTURER'S STANDARD.
ELECTRICAL SPECIFICATIONS:
AutoCAD SHX Text 2025 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202402\20240248\A\Sheets\A-1_Specs and Details.dwg
AutoCAD SHX Text Reed, Qetuwrah
AutoCAD SHX Text
AutoCAD SHX Text
4/15/2025 8:52 AM
AutoCAD SHX Text 20240248
AutoCAD SHX Text April 2025
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
| Sheets and Views |
| 22x34 |
File details come from the government source that posted it. Updated .