This is a Quality Assurance Plan (QAP) for the Little Back River Road Reconstruction project in Hampton, Virginia, administered by the City of Hampton Public Works in conjunction with the Virginia Department of Transportation (VDOT). The project, identified as VDOT Project No. U000-114-315/UPC 109304 with Federal Aid Project Numbers STP-5A03(997) and FHWA 534 No. 35004, involves installing pedestrian facilities on both sides of Little Back River Road, including an asphalt shared-use path on the West side between Lamington Road and Oakville Road and a concrete sidewalk on the East side between Riverchase Drive and the existing sidewalk between Rosewood Drive and Westphal Drive. The QAP establishes the quality control and assurance framework for materials testing, inspection frequencies, and acceptance procedures across all project phases, including clearing and grubbing, embankment work, aggregate base materials, asphalt and concrete pavement, structural elements, erosion control, and roadway appurtenances. The plan designates McCord Newsome as the Responsible Charge Engineer, Philippe Fenouil as the Locality Project Manager, and Cynthia Yager as the Locality Project Coordinator, with MBP serving as the Quality Assurance and Construction Management consultant and Terracon performing independent materials testing verification.
The QAP requires adherence to VDOT specifications and the Locally Administered Projects Manual (LAP MANUAL) standards, with all testing performed by qualified, certified personnel and accredited laboratories meeting LAP MANUAL Chapter 13.2 requirements. Independent Assurance testing tolerances must conform to LAP MANUAL Appendix 13.2E, with documented investigation and non-conformance reporting (NCR) procedures for testing results outside specified tolerances. Materials acceptance records and test data must be maintained in project notebooks for a minimum of three years following project completion and made available for inspection by the VDOT District LAP Construction Project Monitor. The plan establishes hold points requiring VDOT notification and approval prior to work proceeding, including ADA ramps and asphalt placement, and witness points for maintenance of traffic, traffic signals, concrete placement, flexible planning, and pavement markings. The City of Hampton agrees to VDOT's right to inspect all project items, with detailed inspection forms and daily reporting requirements provided for each work category to ensure comprehensive quality documentation throughout the construction process.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Quality Assurance Plan for
Little Back River Road Reconstruction
VDOT Project No.: U000-114-315 / UPC 109304
Federal Aid Project Numbers: STP-5A03(997)
FHWA 534 No. 35004
I. Date of Original QAP Submitted:
II. QAP Revision Date (if applicable)
III. Locality Name and Physical Address: City of Hampton
Public Works, Engineering
22 Lincoln St Hampton, Va 23669
IV. Responsible Charge Engineer: McCord Newsome
7) 727-8404 mnewsome@hampton.gov
V. Locality Project Manager Philippe Fenouil Contact Information (757) 506-6573 philippe.fenouil@hampton.gov
I.
Contact Information (757)727-6325
Cynthia Yager cayager@hampton.gov
Organizational Chart:
McCord Newsome
Responsible Charge Engineer
Contractor's Testing Firm
MBP
Quality Assurance Manager / Inspector
Independent Assurance (IA) for:
- Misc Roadway and Structure
- Soils and Aggregates
Philippe Fenouil
Locality Project Manager
Contractor QC Testing for:
- Asphalt and Asphalt Concrete
- Misc Roadway and Structure
Cynthia Yager
Locality Project Coordinator
Acceptance Testing for Soils and Aggregates
Independent Assurance (IA) for:
- Hydraulic Cement Concrete
- Asphalt and Asphalt Concrete
Acceptance Testing for Hydraulic Cement Concrete
Acceptance Testing for Asphalt and Asphalt Concrete
Terracon Testing Firm
QAP DOCUMENT
I. Mission Statement: The City of Hampton is dedicated to ensure only quality materials meeting Virginia Department of Transportation specifications and standards will be accepted and incorporated into this project as identified in the project plans and specifications. All materials shall be approved, sampled, and / or tested in conformance with contract specifications and the Locally Administered Projects Manual (LAP MANUAL). Submittal of this QAP designates a commitment by the City of Hampton to adhere to its contents as well as the LAP MANUAL. Any deviation from this Quality Assurance Plan shall not occur without a revision submittal of this QAP to the District Project Coordinator for approval.
II. The City of Hampton maintains a copy of Personnel Certifications and Licenses as required by the Contract Documents in a working file for this project. These copies are readily available to the VDOT DISTRICT Project Coordinator for review. All personnel performing materials testing will have the necessary certifications and experience /expertise required by the contract documents and the LAP Manual. The City of Hampton will not allow work to be performed by inexperience or non-certified personnel.
III. The materials testing laboratories used for this project by the City of Hampton will meet the requirements as outlined in the LAP MANUAL, Chapter 13.2 for “Qualified Laboratories”. No work shall be authorized otherwise. Independent Assurance sampling and testing will be defined within this QA Plan and is attached to this document. The Materials Notebook will be the mechanism to track independent assurance samples. All Independent Assurance Tolerances will be in accordance with the LAP MANUAL Appendix 13.2E Independent Assurance Tolerances. If IA testing is outside the specified tolerance the testing equipment for both the QC and IA testing shall be evaluated and if applicable, the calibrations checked. If either equipment is found to be out of calibration, then the equipment shall be re calibrated and the test repeated for the equipment meet calibrations standards and the equipment tolerances specified in the applicable test method, third party testing shall be used to verify the test data and an investigation will be conducted to resolve the discrepancy. The investigation and report will be documented through the NCR and AR process.
IV. Communications Channels: Once construction starts, City of Hampton will coordinate with the contractor regarding the inspection frequencies outlined in the QAP, ensuring that adequate inspections forces are available to meet the scheduled construction activities. The QA Inspector will interface daily with the Contractor and QC team. The QA Inspector’s primary point of contact on site is Cynthia Yager. The QC staff, including the technicians listed in this document, will submit all daily documentation to the QA Inspector for review and acceptance. The Project Inspector will review these documents routinely to assure they are accurate and complete. Any unacceptable work identified by the QC/QA staff will be scheduled for correction, to include additional inspections requirements.
The city of Hampton’s communications channels have been established to provide direction and Solve problems and are as follows:
V.
McCord Newsome, Represents the City of Hampton. He is the City Engineer and is the Responsible Engineer in Charge. Philippe Fenouil, Project Manager with the City of Hampton, reports to McCord Newsome. Philippe responds to design issues during construction and questions on technical aspects of the project, including design variance and/or material substitution requests. Cynthia Yager, Project Coordinator with the City of Hampton, reports to McCord Newsome.
MBP will perform the Quality Assurance and Construction Managment for the owner. They represent the City of Hampton and are responsible for quality of design, construction, project costs and deadlines. They will be monitoring and documenting of the on-site daily activities including oversight of the required field sampling, and will take on-site visual verification against reports, and will report to Cynthia Yager. They will work with Philippe Fenouil for Design issues and questions.
Terracon will perform the testing for the owner. They will verify all acceptance testing, ensures sample test results meets specifications, provides verification and oversight of activities that affect the quality of the work.
• Superintendent Name represents Contractor. He handles all field construction issues and ensures that products meet specifications. He will provide acceptance testing and contractor QC testing for material specified in the Quality Assurance Plan per the LAP Manual Appendix 13.2 pages G-2 through G-14.
Resolution Procedure: In the event of unclear contract specifications or published guidelines, the resolution procedure will be accomplished by:
MBP will call a meeting for resolution. Invited attendees will include:
a. Philippe Fenouil, Project Manager, City of Hampton
b. Cynthia Yager, Project Coordinator, City of Hampton
c. Contractor
MBP will document discussion. Once an agreement is reached, MBP will send out agreed upon resolution to all parties listed above.
VI. Progress reports as agreed upon will be provided to the VDOT District LAP Construction Project Monitor. A sample of a progress report is attached to this document for reference See attached Progress Report.
VII. The City of Hampton will keep Materials Acceptance records and test data in a project notebook and project file. This notebook and files will be readily available for inspection at all times by the VDOT DISTRICT Project Coordinator. These record shall be kept for a minimum of 3 years after project completion.
VIII. The City of Hampton agrees to the “right to inspect” by the VDOT'S District LAP Construction Project Monitor for any and all project items by the submittal of this Quality Assurance Program.
The following items shall be considered during an inspection as events that need to be hold points that must be witnessed by the DISTRICT PC and /or Engineering Consultant for the City of Hampton.
Hold Points (must notify VDOT, and work shall not proceed without VDOT):
o ADA Ramps o Asphalt placement
Witness Points (must notify VDOT, but work may proceed with or without VDOT) o Maintenance of Traffic o Traffic Signal o Concrete Placement Curb & Gutter o Flexible Planning o Pavement Markings/Striping
Type text here
IX. Non-Compliance to this QAP shall be promptly reported through the established communications process in the QAP. An example “Non- Compliance Report “and the “Recovery Plan “are attached to this document.
Attachments:
• Minimum Requirements for QA and QC
• Project item descriptions
• Progress Reports template
• Non – Compliance Report (NCR) template.
• Non- Conformance notification Log
• Audit and NCR Recovery Plan template
• Inspection logs for project items
• Lab Accreditaton.
Date
Date
Date
Submitted:
Philippe Fenouil, Locality Project Manager
Cynthia Yager, Locality Project Coordinator
Approved By:
VDOT Construction
9/25/2026
9/29/2026
9/29/26
OFFICE OF ADMINISTRATION & ENGINEERING SERVICES
(757) 727-6346 FAX (757) 727-6123
22 LINCOLN STREET, HAMPTON, VIRGINIA 23669
“Oldest Continuous English-Speaking Settlement in America – 1610”
Little Back River Road Reconstruction Project # UPC 109304
Quality Assurance Monthly Report
Period Ending:
Qam Activities This Period:
QC and QA Inspection and Testing this period:
• Approximate Quantities and testing this period.
CLEARING AND GRUBBING INSPECTION FORM
REPORT NO.: DATE OF WORK:
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
APPROVED
INTERMEDIATE
EROSION CONTROL INPLACE
CHECK CLEARING LIMITS
VERIFY AREA STAKED AND
MARKED IS IAW PLANS
CHECK FOR BURN PERMITS
IF BURNING PERMITTED
CHECK WEATHER FOR WINDS
AND DRY CONDITIONS
STUMPS LEFT IN PLACE
MAXIMUM 6” ABOVE EXISTING
GROUND SURFACE
STUMPS REMOVED IN
SHALLOW FILLS
CLEARED MATERIAL
DISPOSED OF PROPERLY
CHECK FOR DAMAGE OUTSIDE
R/W
AREA OF CLEARING
CALCULATED
DAMAGED EROSION CONTROL
ITEMS REPAIRED
TEMPORARY SEEDING WITHIN
15-DAYS (IF NECESSARY)
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL010
07/2018 Page 1of 1
BACKFILL OF STRUCTURES INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN APPROVED
BACKFILL MATERIAL APPROVED
& TESTING REQUIREMENTS
ESTABLISHED
STRUCTURES INSPECTED
PRIOR TO BACKFILL
INTERMEDIATE
PERIMETER FILLS PLACED IN 6”
LIFTS
FLOWABLE BACKFILL IN PLACE
IAW PLANS & SPECS
EACH LIFT COMPACTED AT
±20% OPTIMUM MOISTURE
EACH LIFT COMPACTED TO
MINIMUM 95% DENSITY
DENSITY TEST IAW
ESTABLISHED REQUIREMENTS
PROCTORS PERFORMED IAW
ESTABLISHED REQUIREMENTS
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE
TESTING AS REQUIRED
COMPLETION
VERIFY TESTING
DOCUMENTATION FOR
COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL020
PIPE AND DRAINAGE STRUCTURE INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
MATERIALS APPROVED AND
CERTIFICATIONS VERIFIED
QA/QC PLAN APPROVED
INTERMEDIATE
VERIFY LAYOUT
MINOR STRUCTURE EXCAVATION
CALCULATION (IF APPLICABLE)
CHECK TRENCH WITDTH/SHORING
CHECK FOUNDATION
DEWATERING
BEDDING MATERIAL (DEPTH AND SHAPING
IAW PLANS & SPECS)
VERIFY PIPE/STRUCTURE ALIGNMENT AND
GRADE
JOINING/SEALING OF PIPE
STRUCTURE INVERT
PIPE/STRUCTURE BACKFILL AND DENISTY
TESTING
WEEP HOLES
STRUCTURE TOP
COMPLETION
TL-124’S REVIEWED FOR COMPLETION AND
ACCURACY
FINAL FIELD INSPECTION PERFORMED
ADDITIONAL PIPE/STRUCTURE INFORMATION:
STRUCTURE TYPE:_______________________ PIPE SIZE:_______________________
STRUCTURE ID.: STR. #___________________ PIPE ID: STR#______________TO STR#_____________
ACTUAL INV. ELEVATION:__________________ PLAN LENGTH:___________________
FINAL DI HEIGHT:_________________________ ACTUAL LENGTH:_________________
DENSITY TESTS RECORD NO’S: _____________________________________________________
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL030
CAST-IN-PLACE STRUCTURES INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
APPROVED MATERIALS SOURCE
APPROVED MIX DESIGN
QA/QC PLAN APPROVED & TESTING
REQUIREMENTS ESTABLISHED
INTERMEDIATE
STRENGTH REQUIREMENTS IAW
PLANS & SPECS FOR PRECEDING
WORK
PROPER SUBSURFACE & BEDDING
IAW PLANS & SPECS
PROPER FORMWORK &
REINFORCING STEEL IAW PLANS &
SPECS
AREA FREE OF DEBRIS, WATER, &
MUD
2 INSPECTORS PRESENT DURING
ENTIRE PLACEMENT OF CONCRETE
PROPER TESTING METHODS
PERFORMED & RECORDED
PROPER PROTECTION & CURING
METHODS IAW PLANS & SPECS
CONTROL CYLINDERS CURED IN
SAME MANNER AS IN-PLACE
CONCRETE
VERIFY 28-DAY STRENGTH TESTS
RESULTS IAW PLANS & SPECS
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE TESTING
AS REQUIRED
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL040
EROSION & SILTATION CONTROL INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
VERIFY ALL APPLICABLE PERMITS
ARE ON FILE PER CONTRACT
DOCUMENTS
INTERMEDIATE
ARE ALL CONTROLS SHOWN ON
PLAN IN PLACE, & WITHIN
SPECIFICATIONS
DENUDED AREAS STABILIZED
DO SEEDED AREAS REQUIRE
MAINTENANCE FERTILIZER, SEED,
OR MULCH
IS SEDIMENT LEAVING SITE
PERIMETER TRAPS IN PLACE
CUT AND FILL SLOPES STABILIZED
EVIDENCE OF INCREASED OFF-SITE
EROSION SINCE BEGINNING OF JOB
CHANNELS AND OUTLETS
STABILIZED
INLETS PROTECTED FROM
SEDIMENT
WORK ONGOING IN LIVE STREAMS
THAT REQUIRES STABILIZATION
UTILITY TRENCHES BACKFILLED
AND STABILIZED
MUD ON PUBLIC ROADS
ANY CONTROLS THAT CAN BE
REMOVED
CONTROLS THAT REQUIRE REPAIR
OR CLEAN OUT
ANY DEFICIENCIES NOT
CORRECTED FROM LAST REPORT
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL050
EMBANKMENT INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN ACCEPTED
MATERIAL ACCEPTED & TESTING
REQUIREMENTS ESTABLISHED
INTERMEDIATE
VERIFY EMBANKMENT MATERIAL
BEING USED IS CONSISTENT
WITH APPROVED & TESTED
MATERIAL (CHECK FOR MUD,
MUCK, ROOT MAT, FROZEN
MATERIAL, BOULDERS.)
VERIFY INSTALLATION
PROCEDURES ARE ADEQUATE
(COMPACTION EQUIPMENT,
BENCHING, LIFT THICKNESS)
EACH LIFT COMPACTED AT ±20%
OPTIMUM MOISTURE
EACH LIFT COMPACTED TO
MINIMUM 95% DENSITY
FINAL GRADE AND SLOPES
FORMED IAW PLANS, SPECS &
TYPICAL SECTION
EROSION & SILTATION CONTROLS
MAINTAINED & TEMP OR FINAL
SEEDING IAW PLANS & SPECS
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE
TESTING AS REQUIRED
COMPLETION
VERIFY TESTING
DOCUMENTATION FOR
COMPLETION AND ACCURACY
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL060
UNDERCUT EXCAVATION INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATOTY
AREA OF UNDERCUT REVIEWED &
DOCUMENTED
INTERMEDIATE
VERIFY WITH CONTRACTOR THE
UNSUITABLE SOIL CONDITIONS
DICTATING UNDERCUT
EXCAVATION
MONITOR & RECORD LOCATIONS,
CONDITIONS, EQUIPMENT USED &
MANPOWER HOURS FOR
UNDERCUT OPERATIONS
INSPECT, MEASURE AND RECORD
EXCAVATED AREA PRIOR TO
PLACEMENT OF APPROVED
BACKFILL MATL
BACKFILL IAW PLANS & SPECS
PROPER DENSITY TESTS
PERFORMED AND RECORDED
MEASUREMENT & PAYMENT IAW
PLANS, SPECS & CONTRACT
PROVISIONS
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL070
AGGREGATE BASE MATERIAL INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
APPROVED MATERIALS
INTERMEDIATE
EXISTING SURFACE (SUBGRADE)
PREPARED IAW PLANS & SPECS
BASE COURSE MATL MIXED IAW
APPROVED METHODS
VERIFY INSTALLATION
PROCEDURES (USE OF SPREADER
BOX, WATER TRUCK, SMOOTH
DRUM ROLLERS)
CONTROL STRIP & TEST SECTION
PERFORMED IAW PLANS & SPECS
MAXIMUM 6” LIFT THICKNESS
OBSERVED (UNLESS OTHERWISE
APPROVED)
PROPER DEPTH & DENSITY TESTS
PERFORMED AND RECORDED
PROPER COMPACTION BETWEEN
LIFTS
FINAL SURFACE PROTECTION IAW
PLANS & SPECS
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE
TESTING AS REQUIRED
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL080
CEMENT TREATED AGGREGATE INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
APPROVED MATERIALS
INTERMEDIATE
EXISTING SURFACE (SUBGRADE)
PREPARED IAW PLANS & SPECS
BASE COURSE MATL MIXED IAW
APPROVED METHODS
VERIFY INSTALLATION
PROCEDURES (USE OF SPREADER
BOX, WATER TRUCK, SMOOTH
DRUM ROLLERS)
CONTROL STRIP & TEST SECTION
PERFORMED IAW PLANS & SPECS
MAXIMUM 6” LIFT THICKNESS
OBSERVED (UNLESS OTHERWISE
APPROVED)
PROPER DEPTH & DENSITY TESTS
PERFORMED AND RECORDED
PROPER COMPACTION BETWEEN
LIFTS
FINAL SURFACE PROTECTION IAW
PLANS & SPECS
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE
TESTING AS REQUIRED
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL081
STABILIZED OPEN-GRADED MATERIAL INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
APPROVED MATERIALS
INTERMEDIATE
PROPER SURFACE CONDITIONS
OBSERVED IAW SPECS
2 INSPECTORS PRESENT DURING
ENTIRE PLACEMENT
STABILIZATION MATL
PROPORTIONING APPLIED IAW
APPROVED PLANS, SPECS &
CONTRACT PROVISIONS
TEMPERATURE REQUIREMENTS IAW
PLANS & SPECS
EQUIPMENT USED IS ADEQUATE
PROPER TESTING PROCEDURE
PERFORMED AND RECORDED
CURING PROCEDURES OBSERVED
IAW PLANS & SPECS
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL090
SOIL STABILIZATION INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED & ACCEPTED
APPROVED MATERIALS
INTERMEDIATE
PREPARATION OF EXISTING SURFACE
IAW PLANS & SPECS
MATERIAL SCARIFIED & PULVERIZED
IAW PLANS & SPECS
CEMENT & OTHER APPROVED
ADMIXTURES APPLIED IAW
APPROVED PROCEDURES (MIX-IN-
PLACE OR CENTRAL PLANT METHOD)
COMPACTION AND FINISHING
PROCEDURES PERFORMED IAW
PLANS & SPECS
CONSTRUCTION JOINTS IAW PLANS &
SPECS
DENSITY & THICKNESS TESTING
PERFORMED AND RECORDED
PROPER PROTECTION & CURING
PROCEDURES OBSERVED IAW PLANS
& SPECS
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL110
ASPHALT SURFACE TREATMENT INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS FROM APPROVED
SOURCE
EQUIPMENT PROPERLY
CALIBRATED
INTERMEDIATE
SURFACE PREPARATION IAW
PLANS & SPECS
LIQUID ASPHALT APPLICATION
RATE IAW APPROVED PLAN,
SPECS & CONTRACT
PROVISIONS
COVER MATERIAL APPLICATION
RATE IAW APPROVED PLAN,
SPECS & CONTRACT
PROVISIONS
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL110
ASPHALT CONCRETE PAVEMENT INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
ASPHALT MIX DESIGN APPROVED
INTERMEDIATE
FINAL SUBBASE INSPECTION FOR
PROPER LINE, GRADE, AND
CONFORMITY IAW PLANS, SPECS
AND CONTRACT PROVISIONS
2 INSPECTORS PRESENT DURING
ENTIRE PLACEMENT OPERATIONS
EQUIPMENT CALIBRATION
OBSERVED AND APPROVED
CONTROL STRIPS PERFORMED,
OBSERVED, TESTED AND
APPROVED
ROLLER PATTERNS PERFORMED,
OBSERVED, TESTED AND
APPROVED
TACK PLACEMENT AND
APPLICATION RATE IAW PLANS &
SPECS
PROPER MATERIAL LIFTS
OBSERVED AND APPROVED
DENSITY TESTING PERFORMED
RE-TEST WHERE COMPACTION
TESTS VARY GREATER THAN 2%
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE
TESTING AS REQUIRED
COMPLETION
VERIFY TESTING AND MATERIALS
DOCUMENTATION FOR
COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL120
HYDRAULIC CEMENT CONC. PAVEMENT INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
APPROVED MIX DESIGN
INTERMEDIATE
FINAL SUBBASE INSPECTION
FOR PROPER LINE, GRADE AND
CONFORMITY IAW PLANS, SPECS
AND CONTRACT PROVISIONS
WHERE APPLICABLE, PROPER
REINFORCEMENT STEEL
PLACEMENT AND TIED IAW
PLANS & SPECS
2 INSPECTORS PRESENT
DURING ENTIRE PLACEMENT
OPERATIONS
PROPER FIELD TESTING BEING
PERFORMED AND RECORDED
JOINT CONSTRUCTION IAW
PLANS & SPECS
PROPER CURING PROCEDURES
OBSERVED
CONTROL CYLINDERS CURED IN
SAME MANNER AS IN-PLACE
CONCRETE
JOINT SEALS INSTALLED IAW
PLANS & SPECS
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE
TESTING AS REQUIRED
COMPLETION
VERIFY TESTING AND
MATERIALS DOCUMENTATION IS
COMPLETE AND ACCURATE
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL130
LOAD BEARING PILES INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED & ACCEPTED
MATERIALS APPROVED
EQUIPMENT APPROVED
INTERMEDIATE
VERIFY TYPE PILE TO BE USED IN STRUCTURE
FROM PLANS
ENSURE TESTING REQUIREMENTS OF PILING HAVE
BEEN MET. ( HEAT #’S, QA STAMPS, ETC)
VERIFY THAT DRIVING HAMMER IS APPROVED AND
REQUIRED HAMMER BLOWS FOR REFUSALS
CHECK ELEVATION OF EXCAVATION TO ENSURE
PROPER ELEVATION
CHECK PILING LOCATIONS AFTER CONTRACTOR
HAS PERFORMED LAYOUT
VERIFY LOCATIONS OF VERTICAL AND BATTERED
PILING
OBSERVE PILE DRIVING OPERATIONS TO VERIFY
BLOW COUNTS
ENSURE WELDING AT SPLICES ON STEEL PILES IS
PERFORMED BY CERTIFIED WELDER ( OBTAIN
CERTIFICATION)
VERIFY CORRECT NUMBER AND LENGTH OF
SPLICES
CALCULATE TOTAL LENGTH OF PILING DRIVEN
FROM CUTOFF ELEVATION
VERIFY CORRECT LOCATION OF PILINGS WHEN
DRIVING IS COMPLETE. COMPUTE CENTER OF
GRAVITY AS NEEDED.
COMPLETE
VERIFY TESTING AND MATERIALS
DOCUMENTATION IS COMPLETE AND ACCURATE
FINAL FIELD INSPECTION PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL140
BRIDGE H.C.C. OPERATIONS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED & ACCEPTED
OBTAIN AN APPROVED MIX DESIGN
FOR ALL CONCRETE MIXES TO BE
USED
EQUIPMENT APPROVED
INTERMEDIATE
VERIFY DIMENSIONS AND
ELEVATIONS OF FORM WORK
FORMWORK AND REINFORCEMENT
STEEL (CORRECT SIZE, TYPE, GRADE
AND PLACEMENT) IAW PLANS, SPECS
& CONTRACT PROVISIONS
SHOP DRAWINGS SUBMITTED AND
APPROVED FOR SIP METAL DECK
FORMS
CHECK DECK SCREED FOR PROPER
OPERATION AND GRADE
VERIFY WEATHER / TEMPERATURE
LIMITATION REQUIREMENTS ARE IAW
PLANS AND SPECS
ENSURE AUTHORIZATION FOR
PUMPING OF CONCRETE IS
APPROVED BY ENGINEER
VERIFY PLACEMENT SEQUENCE IAW
PLANS, SPEC, AND CONTRACT
PROVISIONS
2 INSPECTORS PRESENT DURING
ENTIRE PLACEMENT OF CONCRETE
OBSERVE PLACEMENT AND TESTING
OF CONCRETE DURING PLACEMENT
AND PERFORM INDEPENDENT
VERIFICATION TESTING AS REQUIRED
VERIFY LOCATION OF
CONSTRUCTION JOINTS ARE IAW
PLANS, SPECS, & CONTRACT
PROVISIONS
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL150
07/2018 Page 1of 2
BRIDGE H.C.C. OPERATIONS INSPECTION FORM
REPORT NO.:________________ DATE OF WORK:____________________ PAGE NO.:____2___
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
INTERMEDIATE - Continued
ENSURE PROPER BONDING AND
WATERPROOFING OF
CONSTRUCTION JOINTS
CHECK AND ENSURE REQUIREMENTS
FOR FORM REMOVAL ARE MET
ENSURE PROPER PROTECTION AND
CURING METHODS ARE USED
OBSERVE OVERDEPTH PROBES OF
DECK CONCRETE AND VERIFY
RECORDKEEPING OF SAME
CONTROL CYLINDERS CURED IN
SAME MANNER AS IN-PLACE
CONCRETE
VERIFY 28-DAY STRENGTH TESTS
RESULTS IAW PLANS & SPECS
CHECK DECK FOR IMPERFECTIONS
AND REPAIR IF NECESSARY
CHECK BRIDGE SEAT BEARING
AREAS FOR LIMITS OF TOLERANCE
COMPLETION
VERIFY TESTING DOCUMENTATION
FOR COMPLETION AND ACCURACY
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL150
07/2018 Page 2 of 2
HYDRAULIC CEMENT CONC ITEMS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED & ACCEPTED
MIX DESIGN APPROVED
INTERMEDIATE
PROPER SUBSURFACE & BEDDING
IAW PLANS & SPECS
PLACEMENT IAW PLANS & SPECS
1 INSPECTOR PRESENT DURING
ENTIRE PLACEMENT OF LESS THAN
25 CY
2 INSPECTORS PRESENT DURING
ENTIRE PLACEMENT OF GREATER
THAN 25 CY
REQUIRED ON-SITE TESTS TAKEN
AND RECORDED
PROPER CURING PRECEDURES
OBSERVED
CONTROL CYLINDERS CURED IN
SAME MANNER AS IN-PLACE
CONCRETE
PERFORM INDEPENDENT
VERIFICATION/ASSURANCE TESTING
AS REQUIRED
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL160
07/2018 Page 1 of 1
STRUCTURAL STEEL INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
AQCCEPTED
VERIFY APPROVED SHOP
DRAWINGS
MATERIALS APPROVED
INTERMEDIATE
ENSURE PROPER STORAGE
OF STRUCTURAL ITEMS ( 4”
ABOVE GROUND)
HOLES REAMED 1/8”
MAXIMUM DURING
ALIGNMENT
VERIFY PROPER STRENGTH
BOLTS USED
ENSURE PROPER TORQUE
OF BOLT TIGHTENING
SPOT CHECK WELDS,
BOLTED CONNECTIONS,
ETC. FOR COMPLIANCE
VERIFY PROPER PAINT
SYSTEM IS USED
COMPLETION
VERIFY ACCEPTANCE BY
QAM
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL170
PROTECTIVE COATINGS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
ENSURE THAT CONTRACTOR HAS
ALL REQUIRED CERTIFICATIONS
TO PERFORM PROTECTIVE
COATINGS AND COATING
REMOVAL OPERATIONS
VERIFY PE CERTIFICATIONS
REQUIREMENT FOR STRUCTURES
WITH CONTAINMENT
INTERMEDIATE
INSPECT STRUCTURAL MEMBERS
TO ENSURE PROPER REMOVAL
OF EXISTING COATINGS AS
REQUIRED
INSPECT STRUCTURAL MEMBERS
TO ENSURE PREP WORK IS
SUFFICIENT (CLEANING/REMOVAL
OF RESIDUE)
ENSURE PROPER COATING
SYSTEM AND COMPONENTS ARE
USED
VERIFY APPLICATION
LIMITATIONS (TEMPERATURE,
HUMIDITY, ETC.)
VERIFY APPLICATION
PROCEDURES IAW PLANS &
SPECS
CHECK MIL THICKNESS OF
COATING
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL180
UNDERDRAINS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPATATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
APPROVED MATERIALS
INTERMEDIATE
INSTALLED IAW PLANS, SPECS &
CURRENT STANDARDS
SLOPES CHECKED AFTER HEAVY
RAINFALL FOR SEEPAGE
CORRECTIONS TAKEN IF
NECESSARY
VERIFY UPSTREAM ENDS
RECEIVE PLUGS
CHECK GEOTEXTILE FABRIC FOR
PROPER INSTALLATION
VERIFY PROPER AGGREGATE
SIZE USED AND AGGREGATE
MATERIAL IS CLEAN & FREE OF
FOREIGN MATERIALS
OUTLET PIPES VISUALLY
CHECKED FOR CRUSHED,
CLOGGED OR DISPLACEMENT
VERIFY ENDWALL PLACEMENT
HAS CORRECT ALIGNMENT AND
IS BELOW FINAL SHOULDER
ELEVATION
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL190
GUARDRAIL INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS FROM APPROVED
SOURCE
INTERMEDIATE
GUARDRAIL INSTALLED IAW
PLANS, SPECS, CURRENT
STANDARDS, & SPECIAL
PROVISIONS
DAILY INSPECTION BY A GRIT
CERTIFIED INSPECTOR
VERIFY LON (LENGTH OF
NEED) CALCULATIONS FOR
END TREATMENTS
SPOT CHECK HEIGHT AND
ALIGNMENT
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL200
FENCING INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS FROM
APPROVED SOURCE
INTERMEDIATE
FENCE INSTALLED IAW
PLANS, SPECS,
STANDARDS & SPECIAL
PROVISIONS
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL210
RIGHT OF WAY MONUMENTS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIAL CONFORMS TO
THE SPECS
INTERMEDIATE
VERIFY LOCATION
STAKEOUT IS CORRECT
MONUMENTS PLACED IAW
PLANS OR AS DIRECTED BY
THE ENGINEER
PROPER BACKFILL
COMPACTION TO AVOID
DISPLACEMENT OF
MONUMENT
COMPLETION
FINAL FIELD INSPECTION
REVIEW PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL220
MAINTENANCE OF TRAFFIC INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
TRAFFIC CONTROLS APPROPRIATELY
DESIGNED TO MAINTAIN TRAFFIC
INTERMEDIATE
MATERIALS CONFORM TO THE SPECS
SIGNALIZATION, BARRICADES,
CHANNELIZING DEVICES, SAFETY
DEVICES & PAVEMENT MARKINGS
CONFORM TO SPECS, VIRGINIA WORK
AREA PROTECTION MANUAL & MUTCD
STANDARDS
SIGNS PLACED IAW VIRGINIA WORK
AREA PROTECTION MANUAL & MUTCD
STANDARDS
CERTIFIED FLAGGERS
CONTRACTOR PROPER MAINTENANCE
OF TRAFFIC CONTROL DEVICES
COMPLETION
FINAL FIELD INSPECTION PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL230
PAVEMENT MARKING INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS FROM
APPROVED SOURCE
INTERMEDIATE
INSTALLED IN LOCATIONS
SHOWN ON THE PLANS
INSTALLED IAW VIRGINIA
WORK AREA PROTECTION
PLAN
INSTALLED IAW
MANUFACTURER’S
RECOMMENDATIONS
CERTIFIED PAVEMENT
MARKING TECHNICIAN
PRESENT AND OBSERVING
APPLICATION
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL240
SOUND BARRIER WALLS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS
APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
SHOP DRAWING SUBMITTALS
REVIEWED AND APPROVED
INTERMEDIATE
PILE INSTALLATION IAW PLANS
& SPECS
BARRIER WALL INSTALLED IAW
PLANS, SPECS, & STANDARDS
FOR TYPE SPECIFIED
SPOT CHECK TOP FACE
ALIGNMENT IS WITHIN
DEVIATION ALLOWANCES
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL250
TOPSOIL AND SEEDING INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
INTERMEDIATE
SITE LOCATION IAW PLANS
TOPSOIL CLASSIFICATION IAW
THE PLANS & SPECS
BRUSH, ROOTS, STUMPS, LITTER
REMOVED
AREAS PROPERLY PREPARED TO
RECEIVE SEED (SLOPES ARE
COMPACTED AND GROOVED)
AREA SEEDING TIME LIMITS ARE
IAW PLANS, SPECS, CONTRACT
PROVISIONS, & VIRGINIA DCR
REQUIREMENTS
SEED MIXTURE APPLIED IAW
ROADSIDE DEVELOPMENT PLANS
(INCLUDING SEED, LIME,
FERTILIZER)
MULCH APPLIED IAW PLANS &
SPECS
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL260
PLANTING INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
INTERMEDIATE
PLANTS PROPERLY
IDENTIFIED AND INSPECTED
PRIOR TO PLANTING
INSTALLATION IAW PLANS,
SPECS, & CURRENT
STANDARDS
MULCHING, STAKING &
GUYING, WRAPPINGS,
WATERING, ETC. IAW PLANS,
SPECS, & CURRENT
STANDARDS
PROPER DOCUMENTATION &
CONTRACTOR NOTIFICATION
OF ESTABLISHMENT PERIOD
BEGIN AND END DATES IS
COMPLETE
AT THE END OF THE
ESTABLISHMENT PERIOD,
DEAD & DEFECTIVE PLANTS
ARE REPLACED IAW PLANS, &
SPECS
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL270
TRAFFIC SIGNS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
SHOP DRAWING SUBMITTALS
REVIEWED AND APPROVED
INTERMEDIATE
SIGN LOCATION LAYOUT IAW
PLANS
MESSAGES & SYMBOLS ARE
CORRECT AND IAW MUTCD
STANDARDS
SIGN FOUNDATIONS AND POSTS
INSTALLED IAW APPROVED SHOP
DRAWINGS
INSTALLATION IS IAW PLANS,
SPECS, CURRENT STANDARDS,
CONTRACT PROVISIONS & MUTCD
STANDARDS
SIGN PANELS ARE FREE OF
CRACKS, GAPS, STREAKS,
WRINKLES, BLISTERS,
DISCOLORATIONS, BUCKLES,
WARPS AND HAVE A SMOOTH
SURFACE OF UNIFORM COLOR
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL280
TRAFFIC SIGNALS INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
SHOP DRAWING SUBMITTALS
REVIEWED AND APPROVED
INTERMEDIATE
ENSURE ALL FOUNDATIONS,
DEVICES, ETC. ARE
CONSTRUCTED WITHIN THE R/W
SHOWN ON THE PLANS
FOUNDATIONS AND POLES
INSTALLED IAW APPROVED SHOP
DRAWINGS
INSTALLATION IS IAW PLANS,
SPECS, CURRENT STANDARDS,
CONTRACT PROVISIONS & MUTCD
STANDARDS
VERIFY TRAFFIC LOOP
DETECTORS INSTALLED IAW
PLANS & SPECS
SYSTEM TESTING IS COMPLETE
AND ACCEPTABLE
ALL SIGNALS ARE FUNCTIONING
AS DESIGNED
COMPLETION
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL290
WATER & SEWER FACILITIES INSPECTION FORM
PROJECT NO.: CONTRACTOR:
LOCATION:
PLAN PAGE: INSPECTOR: ______________________________
ITEM
INSPECTOR
(INITIAL) DATE REMARKS
PREPARATORY
DESIGN DOCUMENTS APPROVED
QA/QC PLAN REVIEWED &
ACCEPTED
MATERIALS APPROVED
SHOP DRAWING SUBMITTALS
REVIEWED AND APPROVED
INTERMEDIATE
WATER & SEWER HORIZONTAL &
VERTICAL MINIMUM SEPARATION
REQUIREMENTS IAW PLANS &
SPECS
TRENCH EXCAVATION IAW SECT.
PIPE & FITTINGS INSPECTED FOR
CRACKS AND DEFECTS BEFORE
LOWERED INTO TRENCH
FOUNDATION APPROVED &
BEDDING MATERIAL IAW PLANS &
SPECS
BACKFILL MATERIAL APPROVED
AND INSTALLED IAW PLANS,
SPECS & CURRENT STANDARDS
VERIFY DISINFECTING, LEAK
TESTING, AND SYSTEM TESTING IS
COMPLETE AND APPROVED BY
THE QAM
COMPLETION
PROPER DOCUMENTATION IS ON
FILE WITH LOCALITY (IF
APPLICABLE)
FINAL FIELD INSPECTION
PERFORMED
REMARKS:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-CL300
Date Page No: of
Contract No:
Contractor: Hours: From: To:
Weather: Low: High: Condition:
WORK CONDITIONS: GOOD FAIR POOR UNWORKABLE
VISITORS:
Communications and instructions given to the Contractor and its QA/QC Team:
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-DAILY RPT
07/2018 Page 1 of 2
WORK IN PROGRESS:
PLAN CHANGES:
REMARKS
Submittals Received
Independent Verification tests performed:
Independent Assurance performed:
Preparatory Inspections attended:
Intermediate Inspections performed :
Final Inspections performed :
Non-conformance reports received:
Reports of corrected and pending actions to correct Non-conformance Reports
Other Comments:
SIGNED
NAME TITLE
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-DAILY RPT
INSPECTOR’S DAILY REPORT REPORT NO:
Date
Contract No:
Page No: of
Contractor:
Inspector: Hours: From: To:
Weather: Low: High: Condition:
WORK ACCOMPLISHED
TESTING ACCOMPLISHED
ITEM TESTED LOCATION:
FROM
LOCATION:
TO
QUANTITY
TESTED/LOT
RESULT SPECIFICATION
MATERIALS RECEIVED TODAY:
MATERIAL SOURCE
CAR INVOICE
OR TICKET NO. QUANTITY IDENTIFICATION
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-INSP DAILY
07/2018 Page 1 of 2
INSPECTOR’S DAILY REPORT REPORT NO:
CONTRACTOR’S EQUIPMENT & MANPOWER
EQUIPMENT MANPOWER
REMARKS
Signed Approval
Name Title Name Title
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-INSP DAILY
NONCONFORMANCE NOTIFICATION LOG Page
PROJECT: PROJECT NO:
CONTRACTOR:
Notification Spec Accepted Number Date Section Defective/Rejected Work By Date
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-NCLOG
NONCONFORMANCE REPORT
TO CONTRACTOR: NOTIFICATION NO:
PROJECT: PROJECT NO:
OWNER: TIME: AM/PM
ENGINEER: OBSERVER:
Pursuant to the GENERAL CONDITIONS of the Contract, you are hereby notified of the following noncompliance violation:
Specification Section: Paragraph:
Violation:
Contract Requirement:
Violation Detected by: Test Inspection Observation
Noncompliance Work is: Defective Rejected
Contactor’s Proposed Recommendation
Received by:
Engineer:
Date:
Authorized Representative Contractor
Title
Date
Distribution:
1. Engineer
2. Owner
3. Field File
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-NCRPT
NOTICE OF CORRECTION OF NONCONFORMANCE WORK
TO PREVIOUS NOTIFICATION NO: DATE:
PROJECT: PROJECT NO:
OWNER:
ENGINEER:
The below listed nonconformance work has been re-inspected and the results of the Contractor’s corrective actions have placed the work in compliance with the Contract Documents.
Description of Violation:
Description of Correction:
Engineer:
Authorized Representative
Date:
Distribution:
1. Engineer
2. Owner
3. Field File
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-NCNOTICE
PUNCH LIST DATE
PAGE: OF
PROJECT: PROJECT NO:
CONTRACTOR:
INSPECTED BY:
Item Location Action Required Accepted
By Date
ALTERNATIVE PROJECT DELIVERY DIVISION FORM APD-PUNCHLIST
LAP Manual 13.2 - G-2 April 2025 Construction Administration
Acceptance/VST/IA Frequency - SOILS AND AGGREGATES Material and Test VDOT R&B Spec Test Method Acceptance (VST) IA
Soil/Embankment/Backfill – Classification, CBR, Proctor/One-Point Proctor
Special Provision, as determined by Engineer
VTM-1, VTM-7, VTM-12,
VTM-25
1/soil type during project development and 1/change in material during construction
System IA during construction
Embankment Density Test 303.04(h) VTM-10; for Nuclear use
Direct Transmission Method
For fills less than 2500 LF, one (1) test in each lift. For fills greater than 2500 LF, five (5) tests in each lift.
When tests cannot be run due to gravel, muck, rock, etc., give station and depth on report TL-124 in lieu of test, with reason. See Note 1 for reports.
System IA
Subgrade, finished (either cut or fill sections) Density Test
305.03 VTM-10; for Nuclear use
Direct Transmission Method One (1) test per 500 LF. See Note 1 for reports. System IA
Subgrade, stabilized, either in-situ or imported material other than aggregate base, subbase, or select material) Density Test by any method
306.03(f), 307.05(e)
VTM-10; for Nuclear use Direct Transmission Method
Five (5) tests per 0.5 mile per lane width. Tests shall be randomly located. See Note 1 for reports. System IA
Depth Test 306.03(g), 307.05(e) VTM-38A
One (1) test per 0.5 mile per lane width. Tests shall be randomly located. Deficient or excessive areas of depth shall be as defined in VTM-38A. See Note 1 for reports.
Tests in turning lanes, acceleration or deceleration lanes, ramps, connections, crossovers, etc., tested at discretion of Engineer.
System IA
Central Mix Aggregate Base, treated or untreated, Subbase, and Select Material Density Test by any method
305.03, 308.03, 309.05
VTM-10; for Nuclear use Backscatter Control Strip Method, set up roller pattern and control strip for each layer or lift placed.
One (1) test per 0.5 mile per lane width per layer, each test result being the average of five (5) readings. See Note 1 for reports. See Note 2 on related laboratory and plant testing of aggregate.
System IA
Depth Test 308.04, 309.05 VTM-38B
One (1) test per 0.5 mile per lane width. Maximum lot size is 2 miles for each lane width. Project divided into lots, each lot stratified, and location of each test within stratified section determined randomly. Tests in turning lanes, acceleration or deceleration lanes, ramps, connections, crossovers, etc., tested at discretion of Engineer, and shall not be taken at random, however, care shall be taken not to set up uniform patterns of tests; the tolerance for an individual test result shall be used. See Note 1 for reports.
System IA
LAP Manual 13.2 - G-3 April 2025
Shoulders Density Test by any method 305.03(a) Same as Central Mix Aggregate, alternating sides. Not required when shoulder is part of mainline pull. System IA
Depth 305.03(a) Same as Central Mix Aggregate, alternating sides. Not required when shoulder is part of mainline pull. System IA
Backfill, Pipe and Box Culverts 302.03, 303.04(g), 401.03(i)
VTM-10; for Nuclear use Direct Transmission Method
Minimum one (1) test per lift on alternating sides of structure for each 100 LF in structure length. Testing shall start after first 4-in compacted layer above bedding and continue to one (1) ft above the top of the structure.
See Note 1 for reports.
System IA
Backfill for Abutments, Gravity and Cantilever Retaining Walls
303.04(g), 401.03(i)
VTM-10; for Nuclear use Direct Transmission Method
Minimum of one (1) test per 150 CY. Tests shall be taken behind heel a distance of H+10 ft. See Note 1 for reports.
System IA
Mechanically Stabilized Earth Walls (MSE) Reinforced Zone material
303.04(g), 401.03(i)
VTM-10; for Nuclear use Direct Transmission Method
Minimum of one (1) test per 150 CY. The testing shall be conducted a minimum distance of three (3) ft away from the face of the wall, to within three (3) ft of the back edge of the zone of the reinforced fill area. See Note 1 for reports.
System IA
Backfill for Drop Inlets and Manholes 302.03, 303.04(g) VTM-10; for Nuclear use
Direct Transmission Method
Minimum one (1) test every other lift around the perimeter of each structure. To include drop inlets, junction boxes, etc. Testing shall start after first 4-in compacted layer above bedding and continue to the top of the structure. See Note 1 for reports.
System IA
Note 1. Report density tests on Forms TL-53, TL-54, TL-55, TL-124, TL-125 (Sand-Cone Method), and TL-136; report IA density and depth tests on Form TL- 105.
Note 2: CBR tests (VTM-8) are laboratory tests required for acceptance of subgrade and in some cases, aggregate Select Material, per VDOT Road and Bridge Specifications 207 and 305. A 75 to 100 lb sample of the material is typically gathered from borrow pits, borings, or plant stockpiles prior to project field work, but may also be gathered from the roadway after project field work has begun. Gradation (VTM-25) and Atterberg Limits (VTM-7) tests are also plant tests and are done on a system basis as described in Section 309 of the VDOT Materials Division MOI. Typically 4 samples of 30 to 40 lb each are collected in a stratified random sampling from each 2,000 or 4,000 ton lot of aggregate at a quarry, and one of these 4 samples is split for IA testing by the VDOT District Materials Section.
LAP Manual 13.2 - G-4 April 2025
Acceptance/VST/IA Frequency - HYDRAULIC CEMENT CONCRETE Material and Test 1 VDOT R&B Spec Test Method Acceptance (VST) IA
Structural/Miscellaneous/Pavemen t Concrete - “Wet” Tests Slump
217.08 ASTM C143 One (1) test per load (truck) per source System IA
Air Content 217.08 ASTM C231 or C173 One (1) test per load (truck) per source System IA Temperature 217.08 ASTM C1064 One (1) test per load (truck) per source System IA Unit Weight (Lightweight
Concrete only) 217.08 ASTM C138 One (1) test per load (truck) per source System IA
Structural Concrete Compressive Strength 217.08 ASTM C31 and C39 One (1) set of cylinders per load (truck) per mix design
- each set consists of three (3) 4-in by 8-in cylinders System IA with use of Qualified Laboratory
Permeability 217.08 ASTM C31, VTM- 112 One (1) set per 100 CY – per source each set consists of two (2) 4-in by 8-in cylinders
System IA with use of Qualified Laboratory
Miscellaneous Concrete Compressive Strength 217.08 ASTM C31 and C39
One (1) set per 250 CY per source, minimum 1 per day per mix design - - each set consists of three (3) 4-in by 8-in cylinders
System IA with use of Qualified Laboratory
Permeability 217.08 ASTM C31, VTM-112 One (1) set per 250 CY per source, minimum 1 per day per mix design - – each set consists of two (2) 4-in by 8-in cylinders
System IA with use of Qualified Laboratory
Pavement Concrete Compressive Strength 217.08 ASTM C31 and C39
One (1) set per 250 CY, minimum 1 set per day and 3 sets per project - - each set consists of three (3) 4-in by 8-in cylinders
System IA with use of Qualified Laboratory
Permeability 217.08 ASTM C31, VTM-112 One (1) set per 250 CY, minimum 1 set per day and 3 sets per project, only if specified for the project – each set consists of two (2) 4-in by 8-in cylinders
System IA with use of Qualified Laboratory
Flexural Strength 316.04(f) ASTM C78 and C31 and C293
As deemed necessary by DME to determine opening to traffic; this is not an acceptance test
System IA with use of Qualified Laboratory
Thickness 316.05 VTM-26 One (1) per 0.1 mile per lane System IA Structural/Miscellaneous Self Consolidating Concrete (SCC) Slump Flow
217.11 ASTM C1611,
Procedure B One (1) test per load (truck) per source System IA
J-Ring Flow 217.11 ASTM C1621 One (1) test per load (truck) per source System IA
1. For Self Consolidating Concrete (SCC), the slump flow and J-ring flow tests replace the slump test.
For latex-modified concrete or silica fume concrete bridge deck overlays, one set of five cylinders (3 for compressive strength testing and 2 for permeability testing) will be sampled for every day of placement with a minimum of one set per bridge. Any placement over 25 CY will require an additional set of cylinders at every 25 CY.
For temperature, slump, unit weight, and air content for bridge deck concrete, all miscellaneous concrete, and all pavement concrete, if the first 3 trucks have an air content all within 1% of each other, then only every third truck thereafter need be tested.
LAP Manual 13.2 - G-5 April 2025
QC/VST/IA Frequency - ASPHALT AND ASPHALT CONCRETE (applicable to each mix type)
Material and Test
Sample Location
VDOT R&B
Specification
Test Method QC VST IA
In-place Pavement Density by Nuclear Method (Control Strip) (Asphalt Pavement)
Location - Field 315.05 VTM-76, VTM-6
(This is acceptance test) Control Strip.
Establish Roller pattern according to VTM-76. Ten stratified random sample to establish target density. Verify minimum density achieved with cores per VTM-76.
QC technician shall be certified
None
Materials representative observe and witness QC testing to assure gauge is calibrated and accurate.
Materials representative observing bulking of cores/plug and percent density calculations.
1 plug/core per 10 project control strips verified in approved lab.
IA is not required for Control Strip acceptance.
IA technician shall be certified
In-place Pavement Density by Nuclear Method and/or VDOT cores (Test Section) (Asphalt Pavement)
Location - Field
315.05; VTM-
76 VTM-6
Test Section- Lot Size:
5000 ft per Lane width.
Test stratified random samples per lot for nuclear gauge and/or five stratified random plug/cores per lot QC technician shall be
VST on 20%*QC Lots Acceptance Options:
Coring/Saw plugs method Use VTM-6 Two (2) cores/plugs per VST lot. Preferably match to QC lot which translates to one core per sub lot for two sublots [1000 ft. (300
m) (QC sub lot)].
VST technician shall be certified as Field Level II
Materials representative observe and witness QC testing to assure testing is performed properly and equipment is calibrated on a system basis: minimum once per calendar year.
IA technician shall be
LAP Manual 13.2 - G-6 April 2025
In-Place Depth Check for
SM/IM/BM
Material
Location - Mainline 315.05 None
(This is acceptance test) Two tests for 24 ft.
pavement from 0 to 1/2 mile (0 – 800m), 3 tests for pavement from 1/2 to 3/4 mile (800 – 1200 m), and 4 tests for pavement from 3/4 to one mile (1200 – 1600 m).
Maximum lot size is one mile of 24 ft. (7 m) base course.
Project divided into lots, each lot stratified, and location of each test within stratified section determined randomly.
None
In-Place Depth Check for Base Material
Location - Shoulders 315.05 None
(This is acceptance test) Same as above, alternating sides if specific plan depths specified. Depth tests not required if plans specify rate of application.
None
Asphalt Tack Applications
Location - Roadway VTM-137 None
(This is acceptance test) One tack plate test per 5000 LF (per lane)per roadway within first 500 LF.
None
Grading and Binder Content (Asphalt Pavement)
Location - Processing or mixing plant from back of truck
211.08
Eight 10-LB samples per 4000- ton lot.
Samples taken in stratified random manner.
QC technician shall be certified
Same as IA frequency, results from IA testing are used in VST statistical analysis.
VST technician shall be certified
Target two samples per lot and Maintain a twenty percent sampling rate, as a percentage of the QC samples IA technician shall be certified
Temperature Measurements
Location –
QC –
Processing or mixing plant from back of truck QA - Field
211.08
(This is acceptance test) One temperature measurement initially on first and fifth loads, of each JMF, each production day, and thereafter minimum of one per hour of production time for each JMF, by
None
Project Inspector should take and record temperature measurements of the AC at the beginning of paving operations and thereafter at a rate of not less than one measurement every hour.
Inspector may increase the frequency of temperature measurements at any time.
LAP Manual 13.2 - G-7 April 2025
Producer's APT. If any test outside of tolerance, minimum of three additional tests made in different points of the load, and four tests averaged, and average used as temperature of load or batch.
The temperature should be checked using an appropriate heat- sensing device (e.g.
probe thermometer, infrared thermometer, etc.).N/A
Field
SUPERPAVE®
volumetric Test
Location - At processing or mixing plant or from project site
211.08
One per 1000 tons of production. A minimum of one per day if at least 300 tons produced.
Field Superpave tests are obtained at the same frequency as IA testing on Grading and Binder Content
Field Superpave volumetric tests are only used for verification.
Depth of pavement
Location – AC base course, surface and intermediate courses only if depth specified on plans
315.05(c), 315.07; MOI
503.07;
VTM-32B
See VDOT Materials Division MOI Sec.503.07
See VDOT Materials Division MOI Sec. 503.07
See VDOT Materials Division MOI Sec. 503.07
LAP Manual 13.2 - G-8 April 2025
QC/VST/IA Frequency - Misc Roadway and Structure
Material Type Spec Section
Test Reference QC Testing VST IA
Clearing and Grubbing Ensure activities are confined to limits and seeded within 30 days of disturbance
VDOT Section 301 N/A Daily Weekly
Erosion and Siltation Control
Monitor for correct installation and Maintenance
VDOT Section
303.03 & Current Virginia DCR Specifications
N/A Daily After rain event
Undercut
Review area to determine need for undercut
VDOT Section
30…