ITB 25-45SS Plans.pdf

PDF 3 MB Posted

Attached to
Utilities Administration Building Men’s Locker Room Remodeling
Solicitation number
25-45SS
Issued by
Sarasota County, Florida

About this file

This document is a comprehensive set of construction drawings for the City of Sarasota Utilities Administration Building Men's Locker Room Remodeling project, located at 1750 12th Street in Sarasota, Florida. The project involves a renovation of the men's locker room and restroom area, with work spanning architectural, mechanical, plumbing, and electrical disciplines. The project is designed to update and modernize the existing facilities, with specific focus on replacing fixtures, updating finishes, and improving the overall functionality of the space. The project is being overseen by Hall Darling Design Studio as the Architect of Record and Genesis Engineering Group as the MEP Engineer of Record.

The renovation includes replacing existing plumbing fixtures such as toilets, urinals, and shower components, installing new tile work, updating lighting and electrical systems, and modifying mechanical ventilation. The project documents indicate a total renovation area of approximately 654 square feet, encompassing the men's restroom (340 SF) and locker room (314 SF). The drawings provide detailed specifications for new fixtures, finishes, and equipment, including Scranton Products 'Hiny Hiders' toilet partitions, new lockers, tile from Alpha Tile and DAL Tile, and LED lighting fixtures. The project appears to be funded by the City of Sarasota Utilities department, with work to be completed under the COSUD Project 002616, and is scheduled for bid in December 2023.

View the file

Other files

File Type Posted
ITB 25-45SS Electronic Bid Form.xlsx XLSX spreadsheet
ITB 25-45SS Exhibit A - Required Forms.pdf PDF
ITB 25-45SS Technical Specifications.pdf PDF
ITBCON.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RANGE 18E, TOWNSHIP 36S, SECTIONS 18

COSUD PROJECT 002616

VICINITY MAP

ADMINISTRATION BUILDING MEN'S

LOCKER ROOM REMODELING

PROJECT INFO

CALL 2 FULL

BUSINESS DAYS

BEFORE YOU DIG

IT'S THE LAW!

DIAL 811

SUNSHINE STATE ONE CALL OF FLORIDA, INC.

Know what's below.

Call before you dig.

CITY OF SARASOTA UTILITIES - SARASOTA, FLORIDA

ISSUED FOR BID

G-01

SHEET LIST TABLE

SHEET

NUMBER SHEET TITLE

1-COVER SHEET

CS0.0 COVER SHEET

6-ARCHITECTURAL

A2.0 FIRST FLOOR PLAN

A5.0 INTERIOR ELEVATIONS

8-MECHANICAL

MO.1 MECHANICAL - LEGENDS & GENERAL NOTES

M1.0 MECHANICAL - OVERALL PLAN

M2.0 MECHANICAL - DEMOLITION & RENOVATION PLANS

M3.0 MECHANICAL - SCHEDULES AND DETAILS

11-ELECTRICAL

E0.1 ELECTRICAL - LEGENDS & GENERAL NOTES

E1.0 ELECTRICAL - OVERALL PLAN

E2.0 ELECTRICAL - DEMOLITION & PROPOSED FLOOR PLAN

E3.0 ELECTRICAL - SCHEDULE

E4.0 ELECTRICAL - ENERGY COMPLIANCE

PROJECT MANAGER:

EMIGDIO R. ISERN, P.E.

CITY OF SARASOTA UTILITIES

1750 12TH STREET

SARASOTA, FLORIDA 34236

941-263-6884 x36115

Tallahassee

Tampa

Miami

Jacksonville

Orlando

Pensacola

Fruitville Rd

U S

U S

41 U S

John Ringling Blvd

UTILITIES PROVIDERS LIST

1. GREG COKER

FLORIDA POWER AND LIGHT

1253 12TH AVENUE EAST

PALMETTO, FLORIDA 34221

(941) 723-4430

2. RANDY ALFORD

FRONTIER COMMUNICATIONS

1701 RINGLING BLVD.

SARASOTA, FLORIDA 34236

(941) 773-0077

3. ALEX MCFARLANE

TECO - PEOPLES GAS

8261 VICO COURT

SARASOTA, FLORIDA 34240

(813) 557-6134

4. ASHLEY WOODS

COMCAST CABLEVISION OF FLORIDA

5205 FRUITVILLE ROAD

SARASOTA, FLORIDA 34232

(941) 356-1489

5. DANNY HASKETT

CROWN CASTLE FIBER

9250 W. FLAGLER STREET

MIAMI, FLORIDA 33174

(941) 552-2931

6. KELLI WHITEHEAD

LEVEL 3 COMMUNICATIONS, LLC.

1025 ELDORADO BLVD.

BROOMFIELD, COLORADO 80021

(941) 888-4988

7. JOSH WELCH

CITY OF SARASOTA UTILITIES

1750 12TH STREET

SARASOTA, FLORIDA 34236

(941) 263-6884

8. ROBERT BRESCIANI

SARASOTA COUNTY STORMWATER

1001 SARASOTA CENTER BLVD.

SARASOTA, FLORIDA 34240

(941) 861-0908

SARASOTA CITY COMMISSION

COMMISSIONER

COMMISSIONER

COMMISSIONER

VICE MAYOR

ERIK ARROYO

KYLE BATTIE

LIZ ALPERT

JEN AHEARN-KOCH

DEBBIE TRICE

MAYOR

MEP ENGINEER OF RECORD:

GENESIS ENGINEERING GROUP

2601 CATTLEMEN ROAD

SARASOTA, FL 34232

941.444.2189

ARCHITECT OF RECORD:

HALL DARLING DESIGN STUDIO, PA

2168 MAIN STREET

SARASOTA, FL 34237

941.941.0883

AREA OF WORK

A5.0

A5.0

340 SF

MENS RESTROOM

314 SF

LOCKER ROOM

100A

EXISTING SERVICE LOCATIONS TO REMAIN

ADA

SHOWER

REPLACE SHOWER FLOOR

DRAINS IN EXISTING HUB, TYP

FLOOR SINK, DRAIN AND

FAUCET TO REMAIN

LOCKERS (23) 2-TIER LOCKERS

LOCKERS (17) 2-TIER LOCKERS

CORRIDOR - PROTECT DURING CONSTRUCTION

1' - 3"

2' - 8" 3' - 0" 3' - 1 1/2" 3' - 1" 3' - 1" 3' - 0" 3' - 0" 3' - 0"

/4

EX. DOOR

EX. DOOR

EX. DOOR

8 8 8

EXIST. ADA TOILET

ROOM

JANITOR

9 13

2' - 0" 2' - 6" 2' - 6" 2' - 6" 2' - 6" 2' - 0"

44 4

4 4 4

THRESHOLD

2 4

10 10 88

NO WORK

EX. DOOR

EX. DOOR

EX. DOOR

MENS RESTROOM

LOCKER ROOM

6 6 6

5 5

NO WORK

340 SF

MENS RESTROOM

314 SF

LOCKER ROOM

100A

7' - 6"

7' - 6"

8' - 0"

SS

S

7' - 10"

EXPOSED

CONC. BEAM,

PAINT

2' X 2' LAY-IN LED LIGHT FIXTURE

PAINTED GYPSUM

M.R. WALLBOARD

CEILING

2'x2'x5/8" ACOUSTIC TILE CEILING IN

SUSPENDED GRID

ARMSTRONG DUNE 1774 TEGULAR TILE

w/ CHICAGO METALLIC 1200 SERIES

GRID

RCP LEGEND

CEILINGS

LIGHTING

1' X 4' SUSPENDED LED

UTILITY FIXTURE

2' X 2' RETURN AIR GRILLE

2' X 2' SUPPLY AIR DIFFUSER

EXIT SIGN

FIRE ALARM HORN WITH STROBE

HEAT DETECTOR

OPEN TO UNDERSIDE OF STRUCTURE

CEILING TYPES

8'-0"

2'X2' ACOUSTIC CEILING TILE SYSTEM (ACT-1)

7'-6"

GENERAL RCP NOTES

1. REFER TO MECHANICAL, AND ELECTRICAL

DRAWINGS FOR ADDITIONAL COORDINATION.

MECHANICAL

FIRE PROTECTION / LIFE SAFETY

S

5/8" MR GYPSUM WALL BOARD ON METAL FRAMING

7'-10"

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2023 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GLENN DARLING, AIA AR 97844

ARCHITECT OF RECORD

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

A2.0

FIRST FLOOR PLAN

CITY OF SARASOTA UTILITIES

DEPARTMENT LOCKER ROOM

RENOVATION

DECEMBER 20, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

ISSUED FOR PERMIT

23-025

N

1/4" = 1'-0"A2.0

5 REFLECTED CEILING PLAN

1/4" = 1'-0"A2.0

3 DEMOLITION PLAN

1/4" = 1'-0"A2.0

2 ENLARGED FLOOR PLAN

N

1/4" = 1'-0"A2.0

4 CEILING DEMOLITION PLAN - ENLARGED

N

DEMOLITION KEYNOTES

NO. DESCRIPTION

1 REMOVE FLOOR TILE TO EXPOSE EXISTING SUBSTRATE.

2 REMOVE WALL TILE TO EXPOSE EXISTING SUBSTRATE.

3 REMOVE TOILET PARTITIONS, URNIAL SCREENS AND

FASTENERS.

4 REMOVE TOILET AND URINAL FIXTURES. STONE SINK /

HANDWASH TO REMAIN.

5 REMOVE CEILING TILE AND SUPPORTING GRID.

6 REMOVE LIGHT FIXTURES.

7 REMOVE HVAC SERVICE AND RETURN DIFFUSERS. DUCT

TO REMAIN.

8 REMOVE AND REPLACE PLUMBING SERVICE VALVES.

9 REMOVE AND REPLACE GYP. BOARD CEILING.

10 REMOVE AND SALVAGE RESTROOM ACCESSORIES.

N

BULLNOSE EDGE TO WALL FACE

TYPICAL BOTH JAMBS

OPEN

OPEN

WALL TILE,SEE TILE

PATTERN, TYP.

PAINT

WALL TILE,SEE TILE

PATTERN, TYP.

PAINT

EXISTING DOOR TO REMAIN, PAINT

PAINT

WALL TILE, SEE TILE PATTERN, TYP.

1313 13137

4 4 4

13 13

PROVIDE PROTECTIVE ADA

PIPE WRAP, TYP. ALL SINKS

PROVIDE PROTECTIVE ADA

PIPE WRAP, TYP. ALL SINKS

WALL TILE,SEE TILE

PATTERN, TYP.

PAINT

EXISTING DOOR

TO REMAIN,

PAINT

TILE BASE CT-2

PAINT

9 9

H C

P

N O

N

H C

P

EQ. - 36" +/-

4 MIRROR

6 URINAL SCREEN 7 TOILET PARTITION

8 TOILET TISSUE

DISPENSER

9 PAPER TOWEL DISPENSER

13 SOAP DISPENSER

22 ROBE HOOK (HCP)

N O

N

H C

P

M A

X

16 SHOWER SEAT

17 SHOWER ROD,

CURTAIN, AND HOOKS

18 SHOWER GRAB BARS

FINISH FLOOR

FINISH FLOOR

WALL MOUNTED TOILET

URINAL AND URINAL SCREEN SHOWER

ACCESSORIES

2' - 0"

TOILET PARTITIONS AND URINAL SCREENS

SCRANTON PRODUCTS 'HINY HIDERS'

FLOOR MOUNTED OVERHEAD BRACED

8" ALUMINUM WRAP AROUND HINGE

STAINLESS STIRRUP BRACKETS.

COLOR SELECTED BY OWNER FROM STD.

COLOR CHOICES

PROVIDE SHOP DRAWINGS FOR APPROVAL

PRIOR TO FABRICATION

No. DESCRIPTION

TOILET FIXTURE & ACCESSORY KEYNOTE LEGEND

NOTE: PROVIDE BLOCKING AT WALL MOUNT FIXTURE ACCESSORIES

4 30" H x 42" W MIRROR - BOBRICK B-165 SERIES

6 URINAL SCREEN, 24" W - SCRANTON PRODUCTS STD. COLOR SELECTION

7 TOILET PARTITION (FLOOR ANCHORED, OVERHEAD BRACED)

8 TOILET TISSUE DISPENSER - BOBRICK B265

9 PAPER TOWEL DISPENSER - BOBRICK B-262

13 SOAP DISPENSER - BOBRICK B-2111

16 SHOWER SEAT (HCP) - BRADLEY 9593 FOLDING SEAT

17 SHOWER ROD, CURTAIN, AND HOOKS - BOBRICK B-207, B-204-2, B-204-1

18 SHOWER GRAB BARS (HCP) - BOBRICK B-5806 SERIES

21 ROBE HOOK - BOBRICK B-6717

22 SOAP DISH - BOBRICK B-680 (SHOWER)

23 TOWEL BAR - BOBRICK B-6747

24 MIRROR - BOBRICK B-2908 1830

SCHED. CT-1

FLOOR TILE.

SCHLUTER STRIP

RENO-U EU125 .

EXISTING

FLOORING

SCHED. CT-2

SHOWER TILE

SCHED. THRESHOLD

SCHED. CT-1

FLOOR TILE

8"

SHOWER THRESHOLD

DOOR THRESHOLD

EXISTING

DOOR

PAINT

PAINT

LOCKERS

TILE BASE CT-2

TILE BASE CT-2

SHOWER WALL TILE,

SEE TILE PATTERN,

TYP.

CLOSURE PANEL

TO MATCH

LOCKERS

SLOPED TOP

SHOWER WALL TILE,

SEE TILE PATTERN,

TYP.

PAINT

16 16

22 22

OPEN

OPEN

LOCKERS

SHOWER WALL TILE,

SEE TILE PATTERN,

TYP.

PAINT

TILE BASE, CT-2 TILE BASE, CT-2

PAINT

SLOPED TOP

PAINT

TILE BASE, CT-2

EXISTING DOOR TO REMAIN, PAINT

"3

SCHLUTER QUADEC-K (TOP)

T-3

T-4

T-5

T-3

T-4

T-5

T-4

T-5

T-3 T-3

WALL TILE CT-4

"3

SCHLUTER QUADEC-K (TOP)

T-3

T-4

T-5

T-3

T-4

T-5

T-4

T-5

T-3

T-3

REPEATING PATTERN CT-4, TYPICAL

REPEATING PATTERN CT-4, TYPICAL

TYPICAL RESTROOM

TYPICAL SHOWERS

BASE CT-2

WALL TILE CT-3

WALL TILE CT-3

T-4

T-5

INTERIOR FINISH LEGEND

FLOORING BASE CEILING PAINT

ACT-1 Acoustic Lay-In Tile Manufaturer: Armstrong Style: Dune #1774 Tegular Edge Profile: Angled Tegular Size: 2'-0" x 2'-0" Color: White Grid: 15/16" Chicago Metallic 1200 Exposed Tee Grid Color: White

GWB Painted Gypsum Board Smooth Finish

P2 Low VOC Latex Paint Manufacturer: Sherwin Williams Color:

Finish: Semi-Gloss Location: Interior Doors and Frames

P4 Low VOC Latex Paint Manufacturer: Sherwin Williams Color:

Finish: Flat Location: All CMU Walls (Interior Exposed)

CT-1 Porcelain Tile Manufaturer: Alpha Tile and Stone Style: Kone Series Color: Grey VR03 Size: 12" x 24"

CT-2 Ceramic Tile Manufaturer: DAL Tile Style: Valor Cove Base P36C9T Color: Gallant Gray VR03 Size: 6" x 12"

WALL - TILE

CT-3 FIELD Porcelain Tile Manufacturer: Alpha Tile and Stone Style: Loop Series Color: Grey Size: 12" x 24"

CT-4 WAINSCOT Ceramic Tile Manufaturer: DalTile Style: Color Wheel Classics Color: Key Lime / 1098 Ocean Blue / 1049 Electric Blue / 1194 Size: 3" x 6" Random Pattern

CT-2 Shower Porcelain Tile Manufaturer: Alpha Tile and Stone Style: Onix Mosaic Color: Gray Size: 3"

SHOWER THRESHOLD

ST-1 Marble Stone Slab Manufaturer: DAL Tile Style: Stormy Mist M048 Size: 8" x 36"

Grout: Mapei Ultracolor Plus FA Cobblestone / 103 Sealer: Custom Building Products Red Guard

Grout: Mapei Ultracolor Plus FA Cobblestone / 103 Sealer: Custom Building Products Red Guard

Grout: Mapei Ultracolor Plus FA Cobblestone / 103

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2023 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GLENN DARLING, AIA AR 97844

ARCHITECT OF RECORD

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

DIGITAL CERTIFICATION

CERTIFICATION BY ARCHITECT IS FOR THE

BUILDING’S ARCHITECTURAL COMPONENTS

ONLY. PLEASE REFER TO INDIVIDUAL

ENGINEER’S DRAWINGS FOR CERTIFICATION

BY THOSE DESIGN PROFESSIONALS.

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED

AND SEALED BY GLENN DARLING, AIA, AS

NOTED BELOW, USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT

CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY

ELECTRONIC COPIES.

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

A5.0

INTERIOR ELEVATIONS

CITY OF SARASOTA UTILITIES

DEPARTMENT LOCKER ROOM

RENOVATION

DECEMBER 20, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

ISSUED FOR PERMIT

23-025

1/4" = 1'-0"A5.0

4 I.E. - D

1/4" = 1'-0"A5.0

3 I.E. - C

1/4" = 1'-0"A5.0

1 I.E. - A

1/4" = 1'-0"A5.0

2 I.E. - B

1/4" = 1'-0"A5.0

5 I.E. - F

1/4" = 1'-0"A5.0

6 I.E. - G

1/4" = 1'-0"A5.0

7 I.E. - I

1/4" = 1'-0"A5.0

8 I.E. - H

1 1/2" = 1'-0"

TYPICAL THRESHOLDS

1/2" = 1'-0"A5.0

9 WALL TILE LAYOUTS

ROOM FINISH SCHEDULE

WT ROOM NAME

FLOOR WALLS CEILING

REMARKSFINISH BASE NORTH EAST SOUTH WEST FINISH

FIRST FLOOR

100 MENS RESTROOM CT-1 CT-3 CT-3 / CT-4 CT-3 / CT-4 P4 CT-3 / CT-4 ACT-1 CT-3 SOUTH WALL ONLY

100A LOCKER ROOM CT-1 CT-3 P4 P4 P4 P4 ACT-1

101 JANITOR NO WORK

FSD

SD

RD

FD

RETURN AIR

SMOKE DETECTOR

SQUARE FEET)

REQUIRED INDICATED IN

DOOR LOUVER (FREE AREA

UNDERCUT DOOR

L

UC

S

SINGLE LINE

SUPPLY AIR

RADIUS ELBOW (R=1.5)

CONTROL DAMPER-

AIR REGISTER (R)

SUPPLY AIR GRILLE (G) OR SUPPLY

FLEXIBLE CONNECTION (FXC)

AIR FLOW

RISE OR DROP DIRECTION OF

REC. BRANCH DUCT TAKE-OFF W/ VD

ELBOW W/ TURNING VANES

DIFFUSER

RD

TO BE REMOVED.

EXISTING EQUIPMENT OR DUCTWORK

ACCESS DOOR

MOTOR OPERATED DAMPER (MOD)

MANUAL VOLUME DAMPER (MVD)

NEW DUCTWORK

AD

VD

AD

DOUBLE LINE

D R

AD

VD

# KEYED NOTE NUMBER

X

X

X

X INDICATES DRAWING ON WHICH

DETAIL APPEARS

INDICATES SECTION NUMBER

INDICATES ON WHICH DRAWING

SECTION APPEARS

INDICATES REVISION & NUMBER

MECHANICAL SYMBOL LEGEND

INDICATES DETAIL, PLAN, SECTION, AND/OR

DIAGRAM(APPLIES ONLY WHERE INDICATED

TYP

X

X

INDICATES TYPICAL DETAIL

(APPLIES TO ALL CONTRACT

ON DRAWINGS)

INDICATES DRAWING ON WHICH

DETAIL APPEARS

DRAWINGS)

M

DUCT SYMBOLSGENERAL SYMBOLS

ROUND BRANCH DUCT TAKE-OFF W/ VD

T THERMOSTAT

PIPE RISING UP

PIPE DROPPING DOWN

DIRECTION OF FLOW

AUTOMATIC CONTROL VALVE (3-WAY)

PRESSURE REDUCING VALVE (PSI)

AUTOMATIC CONTROL VALVE

BUTTERFLY VALVE

BALL VALVE

CHECK VALVE

GATE VALVE

PRESSURE GAUGE

PIPE WELL

F.S.

FLOW SWITCH

THERMOMETER

STRAINER

PIPING SYMBOLS

SMOKE DAMPER W/ ACCESS

DOOR

FIRE SMOKE DAMPER W/ ACCESS

DOOR

RADIATION DAMPER W/ ACCESS

THROUGH DEVICE

EXHAUST AIR

FIRE DAMPER W/ ACCESS

DOOR

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFR ABOVE FINISHED ROOF

AHU AIR HANDLING UNIT

AI ANALOG INPUT

AO ANALOG OUTPUT

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BHP BRAKE HORSE POWER

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C COMMON

CD CONDENSATE

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHWS CHILLED WATER SUPPLY

CHWR CHILLED WATER RETURN

CO2 CARBON DIOXIDE

COP COEFFICIENT OF PERFORMANCE

CU CONDENSING UNIT

DAC DEHUMIDIFICATION AHU

DB DRY BULB

DCU DEHUMIDIFICATION CU

DDC DIRECT DIGITAL CONTROL

DEGF DEGREE FAHRENHEIT

DI DIGITAL INPUT

DN DOWN

DO DIGITAL OUTPUT

DWG DRAWING

DP DIFFERENTIAL PRESSURE

EA EXHAUST AIR

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EAT ENTERING AIR TEMPERATURE

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

ERV ENERGY RECOVERY VENTILATOR

FC FAIL CLOSED

FC FAN COIL (EXISTING)

FCU FAN COIL UNIT

FD FIRE DAMPER

FF FLOW FEEDBACK/STATUS SIGNAL

FLA FULL LOAD AMPS

FO FAIL OPEN

FPM FEET PER MINUTE

FT FEET

GPM GALLONS PER MINUTE

H HUMIDITY

HS HUMIDISTAT

HP HEAT PUMP

HP HORSEPOWER

HWS HOT WATER SUPPLY

HPS HIGH PRESSURE STEAM

HWR HOT WATER RETURN

IAQ INDOOR AIR QUALITY

IN INCH

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LPS LOW PRESSURE STEAM

LPR LOW PRESSURE RETURN

LWT LEAVING WATER TEMPERATURE

M MOTORIZED

MBH THOUSAND BTUH

MCA MINIMUM CIRCUIT AMPACITY

MOCP MAXIMUM OVER CURRENT PROTECTION

NC NORMALLY CLOSED

NO NORMALLY OPEN

NTS NOT TO SCALE

OBD OPPOSED BLADE DAMPER

OA OUTDOOR AIR

P PRESSURE

PF PROPORTIONAL FEEDBACK

PRV PRESSURE REDUCING VALVE

PRS PRESSURE REDUCING STATION

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

RA RETURN AIR

RH RELATIVE HUMIDITY

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RL REFRIGERANT LIQUID

RTU ROOFTOP PACKAGED UNIT

SA SUPPLY AIR

SF SQUARE FEET

SS START/STOP SIGNAL

S.S. STAINLESS STEEL

SP STATIC PRESSURE

T TEMPERATURE

V-PH VOLTAGE-PHASE

TD TIME DELAY

TS TEMPERATURE SENSOR

TSP TOTAL STATIC PRESSURE

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

WB WET BULB

WG WATER GAUGE

WR CHILLED WATER RESET

W/ WITH

W/O WITHOUT

MECHANICAL ABBREVIATIONS LEGEND

GENERAL NOTES

1. DO NOT SCALE FROM THESE DRAWINGS. EXACT DIMENSIONS SHALL BE TAKEN FROM ARCHITECTURAL

DRAWINGS.

2. ALL INDICATED WORK SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE

NOTED.

3. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND

REGULATIONS INCLUDING, BUT NOT LIMITED TO, NATIONAL, CITY, STATE, AND LOCAL ORDINANCES WHICH

MAY BE IN EFFECT. ALL MECHANICAL MATERIALS, INSTALLATION PROCEDURES, AND SYSTEM LAYOUTS SHALL

BE APPROVED BY ALL APPLICABLE CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION, AND IT SHALL

BE THE MECHANICAL CONTRACTOR'S RESPONSIBILITY TO PAY FOR ALL NECESSARY PERMITS AND

APPROVALS FOR THIS INSTALLATION.

4. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW THESE PLANS AND SPECIFICATIONS

AS WELL AS THE RELATED PLUMBING, FIRE PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS TO BECOME FAMILIAR WITH THE FULL PROJECT SCOPE.

IN ADDITION, THIS CONTRACTOR MUST COORDINATE WITH THE OWNER OR OWNER'S REPRESENTATIVE TO

FULLY UNDERSTAND ALL REQUIREMENTS WHICH MAY NOT BE SPECIFIED HEREIN AND WHICH THE OWNER

MAY CONSIDER PART OF THIS CONTRACT. DURING THE COURSE OF CONSTRUCTION COORDINATION AND

ACTUAL CONSTRUCTION, IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO WORK CLOSELY WITH ALL

ACCOMPANYING CONTRACTORS AND TRADESMEN IN ORDER TO ENSURE A SMOOTH RUNNING AND

CAREFULLY COORDINATED INSTALLATION.

5. ANY DISCREPANCIES OR INADEQUACIES WITHIN THESE BID DOCUMENTS OR BETWEEN THESE BID

DOCUMENTS AND THE RELATED PLUMBING, FIRE PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS, OR BETWEEN THESE BID DOCUMENTS AND FIELD

CONDITIONS MUST BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT, AND ENGINEER PRIOR TO

BID SUBMISSION.

6. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN THESE DRAWINGS, BETWEEN

INFORMATION PROVIDED IN THESE DRAWINGS AND THE PROJECT SPECIFICATIONS, AND/OR WITHIN THE

PROJECT SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST COST REQUIREMENTS SHALL APPLY.

SHOULD THIS CONTRACTOR REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR

CLARIFICATION. WHERE CONFLICTS DO EXIST, THE PROJECT ENGINEER OF RECORD SHALL HAVE THE SOLE

DISCRETION AND RIGHT TO PROVIDE INTERPRETATION OF INTENT OF THE CONTRACT DOCUMENTS AS

REQUIRED. THIS INTERPRETATION SHALL SERVE TO DIRECT THE CONTRACTOR IN ACCORDANCE WITH THE

IMPLIED INTENT OF THE CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE PROJECT.

7. THE MECHANICAL CONTRACTOR SHALL PROVIDE A COMPLETE SET OF RECORD "AS-BUILT" DRAWINGS, INDICATING THE PRECISE LOCATION OF ALL SYSTEMS, EQUIPMENT, CONCEALED OR EMBEDDED PIPING, PIPING CONNECTIONS, AND ACCESS DOORS. THESE DRAWINGS SHALL ALSO INCLUDE ALL CHANGES AND

DEVIATIONS FROM THE BID DOCUMENTS.

8. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW MECHANICAL EQUIPMENT WITH NEW LIGHT

LOCATIONS AND TILE LOCATIONS. REFER TO THE ARCHITECT'S REFLECTED CEILING PLAN LAYOUT.

9. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.

10. RUN ALL DUCTWORK AND PIPING WITH AS FEW OFFSETS AS POSSIBLE THROUGHOUT THE ENTIRE BUILDING.

COORDINATE AND VERIFY WITH OTHER CONTRACTORS SO AS NOT TO INTERFERE WITH PLUMBING, FIRE

PROTECTION PIPING, LIGHTING SYSTEMS, ETC.

11. ALL REQUIRED OFFSETS, RISES, AND DROPS DUE TO POSSIBLE OBSTRUCTIONS OF DUCT AND PIPE RUNS ARE

NOT NECESSARILY SHOWN. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK, PIPING, SUPPORTS, ETC. NECESSARY FOR PROPER INSTALLATION AND OPERATION OF

NEW HVAC SYSTEM. THIS CONTRACTOR SHALL INCLUDE A CONTINGENCY IN HIS/HER BID TO OFFSET ANY

COST REQUIRED FOR ADDITIONAL FITTINGS AND LABOR THAT MAY BE REQUIRED.

12. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH VOLUME DAMPER IN THE BRANCH

CONNECTION UNLESS NOTED OTHERWISE. ALL ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED

WITH CONICAL SPIN-IN FITTING WITH INTEGRAL VOLUME DAMPER.

13. CONDENSATE SHALL BE PIPED FULL SIZE TO THE NEAREST APPROVED STORM WATER DRAINAGE SYSTEM

OR LANDSCAPED/GRASS AREA VIA AN INDIRECT CONNECTION. CONDENSATE SHALL NOT BE ALLOWED TO

DRAIN ONTO ANY WALKWAY.

14. MOUNT ALL THERMOSTATS ABOVE FINISHED FLOOR AT HEIGHT APPROVED BY ARCHITECT. COORDINATE

LOCATION WITH ARCHITECTURAL INTERIOR ELEVATIONS.

A CFM

A CFM

A CFM

A CFM

15. TEST AND BALANCE BY A THIRD PARTY SHALL BE REQUIRED FOR ALL SUPPLY, RETURN, OA, VENTILATION, STAIR PRESSURIZATION AND SMOKE REMOVAL SYSTEMS FOR THIS FACILITY.

APPLICABLE CODES

BUILDING CODE:

EXISTING CODE:

ACCESSIBILITY:

MECHANICAL CODE:

ELECTRICAL CODE:

PLUMBING CODE:

ENERGY CODE:

FUEL GAS CODE:

FIRE SAFETY CODE:

FLORIDA BUILDING CODE, 7TH EDITION (FBC), (2020) BUILDING

FLORIDA BUILDING CODE, 7TH EDITION (2020) EXISTING BUILDING

FLORIDA BUILDING CODE, 7TH EDITION (2020) ACCESSIBILITY

FLORIDA BUILDING CODE, 7TH EDITION (2020) MECHANICAL

FLORIDA BUILDING CODE, 7TH EDITION (2020) - CHAPTER 27; NFPA 70 (N.E.C.)

FLORIDA BUILDING CODE, 7TH EDITION (2020) PLUMBING

FLORIDA BUILDING CODE, 7TH EDITION (2020) ENERGY CONSERVATION

FLORIDA BUILDING CODE, 7TH EDITION (2020) FUEL GAS

FLORIDA FIRE PREVENTION CODE 7TH EDITION, BASED ON NFPA 1, NFPA 101, & LIFE SAFETY CODE

CONNECT NEW TO EXISTING

DEMOLISH TO THIS POINT

AUTO AUTOMATIC

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING ASHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U genesis engineering

2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.

project #16-014coa #29304

M0.1

MECHANICAL - LEGENDS &

GENERAL NOTES

CITY OF SARASOTA PUBLIC

WORKS ADMINISTRATION

BUILDING

DECEMBER 1, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

LOCKER RM RENOVATION -

INTERIOR BUILDOUT

21-024

MENS RESTROOM

LOCKER ROOM

M2.0

M2.0

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING ASHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U genesis engineering

2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.

project #16-014coa #29304

M1.0

MECHANICAL - OVERALL PLAN

CITY OF SARASOTA PUBLIC

WORKS ADMINISTRATION

BUILDING

DECEMBER 1, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

LOCKER RM RENOVATION -

INTERIOR BUILDOUT

21-024

N

1/8" = 1'-0"

MECHANICAL - PROPOSED FLOOR PLAN

LOCKER ROOM

T

A

150 CFM

M

200 CFM

M

200 CFM

A

150 CFM

M

150 CFM

A

250 CFM

L

680 CFM

M

150 CFM

A

250 CFM

EF-1

T

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING ASHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U genesis engineering

2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.

project #16-014coa #29304

M2.0

MECHANICAL - DEMOLITION &

RENOVATION FLOOR PLANS

CITY OF SARASOTA PUBLIC

WORKS ADMINISTRATION

BUILDING

DECEMBER 1, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

LOCKER RM RENOVATION -

INTERIOR BUILDOUT

21-024

1/4" = 1'-0"M2.0

2 MECHANICAL - ENLARGED PROPOSED FLOOR PLAN

KEYED NOTESGENERAL NOTES PROPOSED KEYED NOTESGENERAL NOTES

N

1. CONTRACTOR SHALL INSTALL MECHANICAL EQUIPMENT IN ACCORDANCE

WITH ALL STATE AND LOCAL CODES.CONTRACTOR SHALL BE

RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK,

PIPING, SUPPORTS, ETC. NECESSARY FOR A PROPER INSTALLATION

AND OPERATION OF NEW HVAC SYSTEM.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF

INSTALLATION WORK WITH OTHER TRADES TO AVOID CONFLICTS.

3. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW

MECHANICAL EQUIPMENT WITH NEW LIGHT LOCATIONS, AND CEILING

TILE LOCATIONS. REFER TO ARCHITECT'S REFLECTED CEILING PLAN

LAYOUT.

4. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE

DIMENSIONS.

5. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN

THESE DRAWINGS OR BETWEEN INFORMATION PROVIDED IN THESE

DRAWINGS AND THE PROJECT SPECIFICATIONS OR WITHIN THE

PROJECT SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST

COST REQUIREMENTS SHALL APPLY. SHOULD THE CONTRACTOR

REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR

CLARIFICATION. WHERE CONFLICTS DO EXIST, THE PROJECT ENGINEER

OF RECORD SHALL HAVE THE SOLE DISCRETION AND RIGHT TO PROVIDE

INTERPRETATION OF INTENT OF THE CONTRACT DOCUMENTS, AS

REQUIRED, AND THIS INTERPRETATION SHALL SERVE TO DIRECT THE

CONTRACTOR IN ACCORDANCE WITH THE IMPLIED INTENT OF THE

CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE

PROJECT.

6. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH VOLUME

DAMPER IN THE BRANCH CONNECTION UNLESS NOTED OTHERWISE. ALL

ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED WITH

CONICAL SPIN-IN FITTING WITH INTEGRAL VOLUME DAMPER.

7. ALL AIR DEVICE COLORS AND FINISHES SHALL BE COORDINATED WITH

THE ARCHITECT BY MECHANICAL CONTRACTOR.

8. CONTRACTOR SHALL BALANCE THE EXISTING DIFFUSERS TO MATCH THE

CFM DISPLAYED ON THE DRAWINGS.

1 PROVIDE NEW SUPPLY DIFFUSER IN THIS APPROXIMATE LOCATION. SEE

SCHEDULES FOR MORE INFORMATION. COORDINATE FINAL LOCATION

WITH ARCHITECT AND GENERAL CONTRACTOR.

PROVIDE NEW EXHAUST GRILLE IN THIS APPROXIMATE LOCATION. SEE

SCHEDULES FOR MORE INFORMATION. COORDINATE FINAL LOCATION

WITH ARCHITECT AND GENERAL CONTRACTOR.

EXISTING THERMOSTAT TO REMAIN. CONTRACTOR SHALL CLEAN,

INSPECT, AND TEST UNIT FOR PROPER OPERATION. REPAIR OR REPLACE

UNIT IF FOUND TO BE DEFECTIVE.

RECONNECT EXISTING SUPPLY DUCTWORK TO NEW DIFFUSER. PROVIDE

NEW FLEX DUCTWORK AS REQUIRED. COORDINATE FINAL LOCATION

WITH NEW CEILING LAYOUT.

RECONNECT EXISTING EXHAUST DUCTWORK TO NEW GRILLE. PROVIDE

NEW FLEX DUCTWORK AS REQUIRED. COORDINATE FINAL LOCATION

WITH NEW CEILING LAYOUT.

PROVIDE NEW FILTER RETURN GRILLE IN THIS APPROXIMATE LOCATION.

SEE SCHEDULE FOR MORE INFORMATION. COORDINATE FINAL LOCATION

WITH NEW CEILING LAYOUT.

NEW WALL MOUNTED EXHAUST FAN TO BE INSTALLED IN THIS

APPROXIMATE LOCATION. EXHAUST FAN MUST MAINTAIN A MINIMUM 10'-0"

FROM ALL MECHANICAL AIR INTAKES. VERIFY FINAL LOCATION IN FIELD.

EXISTING DOOR GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN AND

INSPECT GRILLE AND REPLACE IF DAMAGED OR DEFECTIVE. COORDINATE

WITH ARCHITECT AND GENERAL CONTRACTOR.

4 1

1/4" = 1'-0"M2.0

1 MECHANICAL - ENLARGED DEMOLITION PLAN

DEMOLITION KEY NOTES DEMOLITION NOTES

1 REMOVE EXISTING EXHAUST GRILLE.

CONTRACTOR SHALL CLEAN AND INSPECT DUCTWORK. RETAIN EXISTING

DUCTWORK FOR RECONNECTION TO NEW AIR DEVICE.

REMOVE EXISTING SUPPLY DIFFUSER

EXISTING THERMOSTAT TO REMAIN. CONTRACTOR SHALL CLEAN,

INSPECT, AND TEST UNIT FOR PROPER OPERATION. REPAIR OR REPLACE

UNIT IF FOUND TO BE DEFECTIVE.

CONTRACTOR SHALL REMOVE EXISTING FLEX DUCTWORK UP TO EXISTING

SHEETMETAL SUPPLY DUCT.

REMOVE EXISTING FILTER RETURN GRILLE. EXISTING DUCTWORK AND AIR

HANDLING UNIT ON MEZZANINE LEVEL ABOVE TO REMAIN.

REMOVE EXISTING WALL-MOUNTED EXHAUST FAN ABOVE ROOF LEVEL.

RETAIN EXISTING DUCTWORK FOR RECONNECTION TO NEW FAN.

CONTRACTOR SHALL CLEAN AND INSPECT DUCTWORK. PREPARE

DUCTWORK FOR RECONNECTION TO NEW EXHAUST FAN.

EXISTING DOOR GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN AND

INSPECT GRILLE AND REPLACE IF DAMAGED OR DEFECTIVE. COORDINATE

WITH ARCHITECT AND GENERAL CONTRACTOR.

1. COORDINATE HVAC DEMOLITION WITH OTHER TRADES AND GENERAL

CONTRACTOR. DO NOT DEMOLISH EQUIPMENT OR COMPONENTS

WITHOUT APPROVAL.

2. UNDER NO CIRCUMSTANCE SHALL DEMOLITION CAUSE DAMAGE OR

REMOVAL IN WHOLE OR IN PART OF ANY STRUCTURAL MEMBER

WITHOUT EXPRESS APPROVAL OF THE GENERAL CONTRACTOR.

3. CAP AND PROTECT ANY EXPOSED EQUIPMENT, DUCT, PIPE OR

ELECTRICAL CABLE / CONDUIT THAT RESULTS FROM DEMOLITION.

UNDER NO CIRCUMSTANCE WILL DEMOLITION RESULT IN THE

PERMANENT EXPOSURE OF ANY CHARGED OR LIVE COMPONENT OF

ANY EQUIPMENT TO BE RE-USED.

4. PROTECT ANY EQUIPMENT, SYSTEM, OR COMPONENT THEREOF THAT

SHALL BE RE-USED.

5. COORDINATE DISPOSAL OF ALL REMOVED ITEMS WITH THE GENERAL

CONTRACTOR. TURN OVER ANY COMPONENTS TO THE OWNER AS

DESIGNATED IN CLEAN CONDITION, WITHOUT DAMAGE, AND WITH

OPENING SEALED. FURNISH RECEIPTS OF PROPER DISPOSAL OF ALL

ITEMS REMOVED TO THE GENERAL CONTRACTOR UPON REQUEST.

RECEIPTS SHALL INDICATE DISPOSAL IN ACCORDANCE WITH ALL LOCAL,

STATE, AND FEDERAL REGULATIONS.

6. PRIOR TO START OF CONSTRUCTION, CONTRACTOR SHALL PERFORM

MAINTENANCE SERVICE TO EXISTING EQUIPMENT TO BE REUSED IN THE

NEW LAYOUT (TO REMAIN OR TO BE RELOCATED). NOTIFY ARCHITECT,

OWNER, AND ENGINEER OF ANY DEFICIENCY FOUND DURING PRE-

CONSTRUCTION MAINTENANCE SERVICE.

3 3

5 5

VENTILATION CALCULATIONS - 2020 FBC-M

ROOM # ROOM NAME

# OF PEOPLE

(1)

PEOPLE OUTDOOR

AIR RATE

(CFM/PERSON)

AREA (FT 2)

AREA OUTDOOR

AIR RATE (CFM/FT2)

Ez

VALUE

OA

REQUIRED

(CFM) (2)

OA

PROVIDED

(CFM)

PROVIDED

SUPPLY

AIRFLOW

UNIT TAGS

EXHAUST

RATE (CFM/FT2)

EXHAUST

REQUIRED

(CFM)

EXHAUST

PROVIDED

(CFM)

UNIT TAGS

LOCKER ROOM 0 0 293 0 0.8 0 60 500 EXISTING AHU-1 0.25 114 (4) 300 EF-1

MENS RESTROOM 0 0 424 0 0.8 0 60 300 EXISTING AHU-1 400 (3) 400 400 EF-1

JANITOR 0 0 44 0 0.8 0 0 0 EXISTING AHU-1 0 0 0

ZONE TOTALS = 0 761 0 120 800 514 700

NET EXFILTRATION RATE (5) = 0.13

AHU-1 0 0 0 120 800 UNIT OA 15.0% 0 0 0

NOTES:

1. SEE ARCHITECTURAL PLANS FOR ACTUAL OCCUPANCY LOADS.

2. OUTSIDE AIR REQUIRED = (PEOPLE * (CFM/PERSON) + AREA * (CFM/SF))/Ez.

3. EXHAUST VENTILATION REQUIRED AT 50 CFM PER WATER CLOSET OR

OPPOSED BLADE DAMPER

SUPPLY DUCT

MAIN

CEILING

COLLAR

CEILING DIFFUSER

TYPICAL DIFFUSER CONNECTION

(BOTTOM OF DUCT CONNECTION)

NOT TO SCALE

MANUFACTURER PROVIDED

(FACE ADJUSTABLE)

NOT TO SCALE

CENTRIFUGAL WALL EXHAUST FAN DETAIL

NOTE:

INSTALLATION PROCEDURES

WITH MANUFACTURER'S

WALL IN ACCORDANCE

MOUNT AND SECURE TO

AIR DEVICE SCHEDULE

TAG DIFFUSER

SIZE

NECK

SIZE

MANUFACTURER NOTESMODELMAX. FLOW

(CFM)

FINISH

24X24 6"∅ 130 WHITE TITUS TDC 1, 2

A

24X24 8"∅ 240 WHITE TITUS TDC

24X24 10"∅ 330 WHITE TITUS TDC

24X24 12"∅ 470 WHITE TITUS TDC

1, 2

1, 2

1, 2

GENERAL NOTES:

KEY NOTES:

1 FLEX DUCT SIZE TO MATCH NECK SIZE. MAXIMUM LENGTH OF FLEX SHALL BE 5'-0", BALANCE OF DUCT SHOWN ON

PLAN SHALL BE STEEL DUCT SAME SIZE AS NECK SIZE, EXTERNALLY INSULATED.

PROVIDE RUNOUT BRANCH DUCT TO AIR DEVICE SAME SIZE AS AIR DEVICE NECK UNLESS OTHERWISE NOTED ON

PLANS. PROVIDE 18" X 18" BACKPAN SIZE WITH 24" X 24" MODULE.

ALUMINUM 1/2" X 1/2" X 1/2" GRID

FILTER RETURN GRILLE FOR 1" FILTER - PROVIDE 1/4 TURN FASTENER AND 1" FILTER SET SIZED TO FIT GRILLE

INCLUDING NEW FILTER AT COMPLETION OF CONSTRUCTION AND SPARE FILTER.

1. BORDER TYPE SHALL BE SELECTED AS COORDINATED WITH ARCHITECTS REFLECTED CEILING PLAN.

2. PROVIDE SQUARE TO ROUND TRANSITIONS AS REQUIRED FOR COORDINATION OF DUCT AND AIR DEVICE NECK.

3. INSULATE THE TOPS OF ALL SUPPLY AIR DEVICES WITH 2" FIBERGLASS DUCT WRAP. SEAL AIR TIGHT AROUND EDGES

TO PREVENT CONDENSATION.

4. ALL DEVICES ARE TO BE ALUMINUM UNLESS OTHERWISE NOTED.

FAN SCHEDULE

TAG

NOTES:

CFM

E.S.P.

(IN. W.G.)

MOTOR

WATTS RPM V / PH

MANUFACTURER NOTESMODEL

HP

SONES

EF-1 700 0.5 --- 1624 120 / 18.8GREENHECK CUE-095-VG 1, 2, 3, 4, 51/6

1. PROVIDE FLEXIBLE CONNECTORS AT ALL DUCT CONNECTIONS TO FAN.

2. PROVIDE FAN WITH GRAVITY BACKDRAFT DAMPER. REFER TO STANDARD MECHANICAL DETAILS FOR FURTHER DETAILS.

3. PROVIDE WITH FACTORY MOUNTED DISCONNECT SWITCH.

4. PROVIDE FAN WITH SPEED CONTROLLER. MOUNT SPEED CONTROLLER IN 2X4 METALLIC BOX ADJACENT TO FAN IN CEILING. TEST AND

BALANCE CONTRACTORS SHALL ADJUST FAN PERFORMANCE THROUGH USE OF SPEED CONTROLLER.

5. FAN SHALL BE ECM-DRIVEN. TEST AND BALANCE CONTRACTOR SHALL ADJUST SPEED USING SET SCREW ON FAN CONTROLS. PROVIDE FAN

WITH INTEGRAL GRAVITY BACKDRAFT DAMPER, ALUMINUM GRILLE, AND FACTORY MOUNTED DISCONNECT SWITCH. FAN SHALL RUN

CONTINUOUSLY AND SHALL BE INTERLOCKED WITH BATHROOM LIGHT SWITCH.

M 24X24 22X22 1600 WHITE TITUS 50F 3

L 24X24 22X22 1600 WHITE TITUS 350FLF1 4

EXTERIOR WALL

CAULK / SEAL WEATHER TIGHT

EXHAUST FAN

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING ASHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U genesis engineering

2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.

project #16-014coa #29304

M3.0

MECHANICAL - SCHEDULES AND

DETAILS

CITY OF SARASOTA PUBLIC

WORKS ADMINISTRATION

BUILDING

DECEMBER 1, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

LOCKER RM RENOVATION -

INTERIOR BUILDOUT

21-024

URINAL FOR CONTINUOUS EXHAUST CONTROL.

4. EXHAUST VENTILATION PROVIDED INCLUDES 0.25 CFM/SF FOR LOCKER AREA AND 20 CFM PER SHOWER HEAD FOR SHOWER AREA.

5. NET EXFILTRATION RATE = (OUTSIDE AIR PROVIDED - EXHAUST AIR PROVIDED) / SF AREA.

PLUMBING GENERAL NOTES

SPRINKLER HEAD

FLEXIBLE-CONNECTION

STRAINER WITH

BLOW OFF VALVE

STRAINER

TP

S

RELIEF VALVE

TEMPERATURE AND PRESSURE

RELIEF/SAFETY VALVE

GAS PRESSURE REGULATOR

GAS COCK

SOLENOID VALVE

GLOBE VALVE, ANGLE

THREE WAY CONTROL VALVE

TWO WAY CONTROL VALVE

VALVE IN RISE OR DROP

SWING CHECK VALVE

LIFT CHECK VALVE

GATE VALVE, ANGLE

BALL VALVE

GLOBE VALVE

PLUG VALVE

VALVE (PRV)

BUTTERFLY VALVE

PRESSURE REDUCING

GATE VALVE

(REDUCED PRESSURE ZONE)

WALL CLEAN OUT

CO

WCO

BACKFLOW PREVENTER

WATER HAMMER ARRESTER

CIRCUIT SETTING

BALANCING VALVE

(DOUBLE CHECK VALVE ASSEMBLY)

OPEN SITE DRAIN

ADR

FD

CO

OS

RD

AREA DRAIN

CLEANOUT

FLOOR DRAIN

ROOF DRAIN

CBV

HB

SA

HOSE BIBB

PIPE RISING UP

PIPE DROPPING DOWN

TEMPERATURE TRANSMITTER

PRESSURE TRANSMITTER OR

PRESSURE SWITCH

UNION - SCREWED OR FLANGED

GAUGE WITH GAUGE COCK/

PRESSURE INDICATOR

BACKFLOW PREVENTER

THERMOMETER/TEMPERATURE

PI/GA

TH/TI

PT/PS

INDICATOR

TT

FS

FLOW SWITCH

- GREASE WASTE PIPING (GW) BELOW FLOORGW

AFF

CFH

CO

CONT

CW

DN

DWG

°F

FD

G

GPM

HW

HWC

KW

LBS

NTS

PSI

PVC

SS

SF

V

VTR

- ABOVE FINISH FLOOR

- CUBIC FEET PER HOUR

- CLEANOUT

- CONTINUATION

- DOMESTIC COLD WATER

- DOWN

- DRAWING

- DEGREE FAHRENHEIT

- FLOOR DRAIN

- GAS

- GALLONS PER MINUTE

- DOMESTIC HOT WATER

- DOMESTIC HOT WATER CIRCULATION

- KILOWATT

- POUNDS

- NOT TO SCALE

- POUNDS PER SQUARE INCH

- POLYVINYL CHLORIDE PIPE

- SANITARY SEWER

- SQUARE FEET

- VENT

- VENT THRU ROOF

- DOMESTIC COLD WATER PIPING (CW)

- DOMESTIC HOT WATER PIPING (HW)

- SANITARY SEWER PIPING (SS) ABOVE FLOOR

- SANITARY VENT PIPING (V)

(E) - EXISTING

P-1

BOTTOM-DRAWING# SHOWN ON

- ENLARGED PLAN REFERENCE: TOP-PLAN#,

FCO - FLOOR CLEANOUT

WCO - WALL CLEANOUT

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

- DOMESTIC HOT WATER CIRCULATION PIPING (HWC)

- LOW PRESSURE GAS PIPING (G)G

- MEDIUM PRESSURE GAS PIPING (MG)MG

- POINT OF CONNECTION TO EXISTING

UNO - UNLESS NOTED OTHERWISE

MG - MEDIUM PRESSURE GAS

V

SS

SD - STORM DRAIN

AP - ACCESS PANEL

RPBP - REDUCED PRESSURE BACKFLOW PREVENTER

IE - INVERT ELEVATION

- STORM DRAINSD

- OVERFLOW STORM DRAINOSD

- EXISTING PIPING TO BE REMOVED

PIPING ELEMENTS / VALVING

PLUMBING SYMBOL LEGEND

PLUMBING ABBREVIATIONS

BFF - BELOW FINISHED FLOOR

- STORM DRAIN BELOW FLOORSD

- SANITARY SEWER PIPING (SS) BELOW FLOORSS

A/C - ABOVE CEILING

FLOOR CLEANOUT

- GREASE WASTE PIPING (GW) ABOVE FLOORGW

- PUMP DISCHARGE PIPING (PD) ABOVE FLOORPD

- PUMP DISCHARGE PIPING (PD) BELOW FLOORPD

- CONDENSATE PIPING (CD) ABOVE FLOORCD

- CONDENSATE PIPING (CD) BELOW FLOORCD

- POINT OF DEMOLITION EXTENTS

CD - CONDENSATE DRAIN

OSD - OVERFLOW STORM DRAIN

PD - PUMP DISCHARGE

- FILTERED WATER PIPING (F)F

1. DO NOT SCALE FROM THESE DRAWINGS. EXACT

DIMENSIONS SHALL BE TAKEN FROM ARCHITECTURAL

DRAWINGS.

2. ALL INDICATED WORK SHALL BE PERFORMED BY THE

PLUMBING CONTRACTOR UNLESS OTHERWISE NOTED.

3. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH

THE REQUIREMENTS OF ALL APPLICABLE CODES AND

REGULATIONS INCLUDING BUT NOT LIMITED TO

NATIONAL, CITY, STATE AND LOCAL ORDINANCES

WHICH MAY BE IN EFFECT. ALL PLUMBING MATERIALS,

INSTALLATION PROCEDURES AND SYSTEM LAYOUTS

SHALL BE APPROVED BY ALL APPLICABLE CODE

ENFORCEMENT AUTHORITIES HAVING JURISDICTION,

AND IT SHALL BE THE PLUMBING CONTRACTOR'S

RESPONSIBILITY TO PAY FOR ALL NECESSARY PERMITS

AND APPROVALS FOR THIS INSTALLATION.

4. IT IS THE RESPONSIBILITY OF THE PLUMBING

CONTRACTOR TO REVIEW THESE PLANS AND

SPECIFICATIONS, AS WELL AS THE RELATED HVAC,

FIRE PROTECTION, ELECTRICAL, STRUCTURAL,

ARCHITECTURAL, INTERIOR DECOR AND SITE

ENGINEERING DRAWINGS TO BECOME FAMILIAR WITH

THE FULL PROJECT SCOPE. IN ADDITION, THIS

CONTRACTOR MUST COORDINATE WITH AN OWNER

REPRESENTATIVE TO FULLY UNDERSTAND ALL

REQUIREMENTS WHICH MAY NOT BE SPECIFIED HEREIN

AND WHICH THE OWNER MAY CONSIDER PART OF THIS

CONTRACT. DURING THE COURSE OF CONSTRUCTION

COORDINATION AND ACTUAL CONSTRUCTION, IT IS THE

RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO

WORK CLOSELY WITH ALL ACCOMPANYING

CONTRACTORS AND TRADESMEN IN ORDER TO

ENSURE A SMOOTH RUNNING AND CAREFULLY

COORDINATED INSTALLATION.

5. ANY DISCREPANCIES OR INADEQUACIES WITHIN THESE

BID DOCUMENTS OR BETWEEN THESE BID DOCUMENTS

AND THE RELATED HVAC, FIRE PROTECTION,

ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR

DECOR AND SITE ENGINEERING DRAWINGS, OR

BETWEEN THESE BID DOCUMENTS AND FIELD

CONDITIONS MUST BE BROUGHT TO THE ATTENTION

OF THE OWNER, ARCHITECT AND ENGINEER PRIOR TO

BID SUBMISSION.

6. THE PLUMBING CONTRACTOR MUST VISIT THE SITE

AND NOTE ALL EXISTING CONDITIONS AS WELL AS

CONDITIONS TO BE MET PRIOR TO BID SUBMISSION.

LACK OF A THOROUGH UNDERSTANDING OF THE

PROJECT SCOPE AND CONDITIONS SHALL NOT

CONSTITUTE AN EXCUSE FOR ERRORS OR OMISSIONS,

NOR FOR A REQUEST FOR EXTRA COMPENSATION.

7. IT IS CRITICAL THAT THE PLUMBING CONTRACTOR

FIELD VERIFIES ALL EXISTING INVERT ELEVATIONS

PRIOR TO BID SUBMISSION. IF ANY CONFLICTS EXIST

BETWEEN THE NEW PLUMBING SYSTEMS AND THE

EXISTING SITE LEVEL SYSTEMS, THEY SHOULD BE

BROUGHT TO THE ATTENTION OF AN OWNER'S

REPRESENTATIVE AND THE ENGINEER PRIOR TO BID

SUBMISSION. EXTRA COMPENSATION WILL NOT BE

GRANTED FOR ANY EXTRA WORK OR MATERIAL WHICH

RESULTS FROM AN INABILITY TO MEET THE INVERTS OF

THE EXISTING SITE LEVEL PIPING SYSTEMS.

8. THE PLUMBING CONTRACTOR SHALL PROVIDE A

COMPLETE SET OF RECORD "AS-BUILT" DRAWINGS

INDICATING THE PRECISE LOCATION OF ALL SYSTEMS,

EQUIPMENT CONCEALED OR EMBEDDED PIPING, PIPING

CONNECTIONS AND ACCESS DOORS. THESE

DRAWINGS SHALL ALSO INCLUDE ALL CHANGES AND

DEVIATIONS FROM THE BID DOCUMENTS.

9. RUN ALL DOMESTIC WATER, WASTE, VENT AND GAS

PIPING AS HIGH AS POSSIBLE THROUGHOUT THE

ENTIRE BUILDING. INSTALL LONG RUNS OF PIPING

WITHIN STEEL JOIST SPACE AND OTHER PIPING TIGHT

TO BOTTOM OF STEEL. COORDINATE AND VERIFY WITH

OTHER CONTRACTORS AS NOT TO INTERFERE WITH

DUCTWORK, FIRE PROTECTION PIPING, LIGHTING

SYSTEMS, ETC.

10. ALL EXPOSED HORIZONTAL AND VERTICAL PIPING

SHALL BE INSTALLED IN A NEAT ARRANGEMENT IN

LOCATIONS WHICH ARE THE MOST INCONSPICUOUS.

VERTICAL DROPS SHALL BE KEPT TO AN ABSOLUTE

MINIMUM AND THEIR FINAL LOCATIONS SHALL BE

COORDINATED AND RUN WITHIN CHASES, WALLS,

SOFFITS WITH OTHER MECHANICAL/ ELECTRICAL

FEEDS. ALL SUCH LOCATIONS ARE TO BE REVIEWED

WITH AN OWNER REPRESENTATIVE AND ARCHITECT

PRIOR TO INSTALLATION.

11. ALL DOMESTIC WATER BRANCH LINES SHALL HAVE

THEIR OWN RESPECTIVE SHUT-OFF VALVES WHETHER

OR NOT SHOWN ON THE DRAWINGS.

12. DOMESTIC WATER HEATER TEMPERATURE / PRESSURE

RELIEF VALVES SHALL BE PIPED FULL SIZE TO THE

NEAREST APPROVED FLOOR DRAIN. THIS

REQUIREMENT SHALL BE APPLICABLE TO ALL

DOMESTIC WATER HEATING STORAGE VESSELS.

INSTANTANEOUS WATER HEATERS NOT STORING

WATER SHALL NOT REQUIRE TEMPERATURE OR

PRESSURE RELIEF VALVES.

13. THE PLUMBING CONTRACTOR SHALL RUN OUT ALL

BUILDING DRAINAGE AND WASTE LINES WHERE SHOWN

ON THE DRAWINGS AND MAKE ALL CONNECTIONS TO

SITE LEVEL SYSTEMS.

14. ALL EXPOSED PIPING BELOW LAVATORY'S DESIGNATED

AS HANDICAPPED SHALL BE TOTALLY INSULATED.

15. ALL NON-DRAINAGE PIPING SHALL BE RUN LEVEL AND

GENERALLY FREE OF TRAPS AND UNNECESSARY

BENDS, ARRANGED TO CONFORM TO THE BUILDING

REQUIREMENTS AND TO SUIT THE NECESSITIES OF

CLEARANCES FOR OTHER MECHANICAL WORK.

PROVIDE VALVED DRAINAGE OUTLETS IN AREAS OF

PIPING WHICH WOULD BE UNDRAINABLE DURING

MAINTENANCE OR REPAIRS.

16. ALL REQUIRED OFFSETS, RISES AND DROPS DUE TO

POSSIBLE OBSTRUCTIONS OF PIPE RUNS ARE NOT

NECESSARILY SHOWN. PLUMBING CONTRACTOR

SHALL PROVIDE ALL REQUIRED OFFSETS NECESSARY

FOR FINAL COORDINATION WITH OTHER TRADES AND

STRUCTURE.

17. THROUGH PENETRATIONS OF FIRE RESISTANCE RATED

HORIZONTAL ASSEMBLIES SHALL BE PROTECTED BY

AN APPROVED THROUGH- PENETRATION FIRESTOP

SYSTEM INSTALLED AND TESTED IN ACCORDANCE

WITH ASTM E 814 OR UL 1479, WITH A MINIMUM

POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF

WATER (2.49 PA). THE SYSTEM SHALL HAVE AN F

RATING/T RATING OF NOT LESS THAN 1 HOUR BUT NOT

LESS THAN THE REQUIRED RATING OF THE FLOOR

PENETRATED. SEE ARCHITECTURAL DRAWINGS FOR

RATED ASSEMBLY LOCATIONS, RATINGS AND DETAILS.

EXCEPTIONS:

A. FLOOR PENETRATIONS CONTAINED AND LOCATED

WITHIN THE CAVITY OF A WALL ABOVE THE FLOOR OR

BELOW THE FLOOR DO NOT REQUIRE A T RATING.

B. FLOOR PENETRATIONS BY FLOOR DRAINS, TUB

DRAINS OR SHOWER DRAINS CONTAINED AND

LOCATED WITHIN THE CONCEALED SPACE OF A

HORIZONTAL ASSEMBLY DO NOT REQUIRE A T RATING.

18. FLUSH LEVERS FOR ACCESSIBLE WATER CLOSETS

SHALL BE LOCATED ON THE APPROACH SIDE (WIDE

SIDE OF ROOM) OF THE FIXTURE.

19. CLEANOUTS SHALL BE PROVIDED IN ACCORDANCE

WITH LOCAL CODE REQUIREMENTS, INCLUDING AT THE

BASE OF ALL DRAINAGE STACKS.

20. ALL PLUMBING EQUIPMENT, INSULATION, PIPING, ETC.

INSTALLED IN HVAC RETURN AIR PLENUMS SHALL MEET

CODE REQUIREMENTS FOR FLAME SPREAD AND

SMOKE DEVELOPMENT RATINGS (FLAME 25 / SMOKE

50), WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR

UL 273.

21. ALL PLUMBING EQUIPMENT REQUIRING ELECTRICAL

POWER SHALL BE INSTALLED WITH DISCONNECT

SWITCHES AT EACH PIECE OF EQUIPMENT.

COORDINATE SWITCH TYPE (FUSED OR NON-FUSED)

WITH ELECTRICAL DRAWINGS.

22. ALL PLUMBING EQUIPMENT SHALL BE INSTALLED

ACCORDING TO MANUFACTURER'S REQUIREMENTS.

MANUFACTURER RECOMMENDATIONS ARE DEEMED

REQUIREMENTS.

23. WATER PIPING ROUTED ABOVE CEILINGS AND IN

EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE

(UNDERSIDE) OF CEILING INSULATION AND HEATED

SIDE (INSIDE) OF WALL INSULATION. DO NOT INSTALL

PIPING IN LOCATIONS SUBJECT TO FREEZING

CONDITIONS.

24. WATER HAMMER ARRESTORS, SIZED PER PDI, SHALL

BE PROVIDED ON THE SUPPLY PIPING TO EACH QUICK

CLOSING VALVE (E.G. WATER CLOSETS, URINALS,

SENSOR SENSOR OPERATED FAUCETS, ICE MACHINE

SUPPLY BOXES, WATER COOLERS, WASHING MACHINE

SUPPLY BOXES, DISHWASHERS, ETC). ARRESTORS

SHALL BE DOUBLE SEAL PISTON TYPE WITH THREADED

CONNECTIONS, LISTED FOR CONCEALED

INSTALLATIONS WITHOUT ACCESS PANELS.

25. WHERE REQUIRED FOR ACCESS TO VALVES AND

ACCESSORIES ABOVE HARD CEILINGS OR IN WALLS,

ACCESS PANELS SHALL BE PROVIDED BY THIS

CONTRACTOR. PANELS IN RATED ASSEMBLIES SHALL

HAVE LISTED RATINGS EQUAL TO OR GREATER THAN

THE ASSEMBLY THEY ARE INSTALLED IN.

26. ALL VALUE ENGINEERING OR DEVIATIONS FROM THE

CONTRACT DOCUMENTS SHALL BE SUBMITTED IN

WRITING TO THE DESIGN TEAM FOR REVIEW AND

APPROVAL PRIOR TO ACCEPTANCE OR

IMPLEMENTATION. ANY COST INCURRED AS A RESULT

OF ANY DEVIATIONS FROM THE BASIS OF DESIGN

INDICATED IN THE CONTRACT DOCUMENTS (E.G.

PLUMBING MODIFICATIONS TO ACCOMMODATE

ALTERNATE EQUIPMENT SELECTIONS, DESIGN

RELATED EXPENSES FOR REQUIRED DRAWING

MODIFICATIONS, ETC.) SHALL BE SOLE RESPONSIBILITY

OF THE CONTRACTOR. NO INCREASE IN CONTRACT

COST WILL BE GRANTED UNLESS BORNE BY AND

APPROVED IN WRITING BY THE OWNER. CONTRACT

DOCUMENTS ARE DEFINED TO INCLUDE ALL

DISCIPLINES AND DIVISIONS OF THE CONTRACT.

DO NOT SCALE DIMENSIONS FROM THESE

DRAWINGS. WHEN INFORMATION IS NOT CLEARLY

PROVIDED, OBTAIN EXACT INFORMATION FROM

THE ARCHITECT BEFORE PROCEEDING WITH THE

WORK.

THE ARCHITECT IS NOT RESPONSIBLE FOR

CONSTRUCTION THAT IS NOT CARRIED OUT IN

ACCORDANCE WITH THESE CONSTRUCTION

DOCUMENTS. THE ARCHITECT IS NOT

RESPONSIBLE FOR DECISIONS AND

INTERPRETATIONS MADE BY THE CONTRACTOR,

OWNER, OR OTHER PARTIES.

COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,

PA. DRAWINGS AND CONCEPTS MAY NOT BE

USED OR REPRODUCED WITHOUT THE WRITTEN

PERMISSION OF THE ARCHITECT.

GENERAL NOTES

MEPF ENGINEER

coa #29304

ORIGINALS PRINTED AT 24" x 36"

Project No.

Date

Revisions:

Genesis Engineering

2601 CATTLEMEN RD, Suite 501

Sarasota, FL 34232

P: 941.444.2189

SEAL

Hall Darling Design Studio, PA

AR97844

2168 MAIN STREET

Sarasota, FL 34231

P:941.917.0883

ARCHITECT'S STATEMENT

TO THE BEST OF THE ARCHITECT'S

KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS

COMPLY WITH THE APPLICABLE BUILDING CODES

AND APPLICABLE MINIMUM FIRE SAFETY

STANDARDS.

THIS ITEM HAS BEEN ELECTRONICALLY

SIGNED AND SEALED BY ANTHONY LUKASZ,

PE. ON THE DATE ADJACENT TO THE SEAL

USING ASHA AUTHENTICATION CODE.

PRINTED COPIES OF THIS DOCUMENT ARE

NOT CONSIDERED SIGNED AND SEALED AND

THE SHA AUTHENTICATION CODE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

G

STATE OF

ROL

F A

DI

EL

I C E N S

NAL EN

I

N

P R O F E

S I O

S

E E R

No. 94249

S A

KLNO

H T

N A

Z

Y U genesis engineering

2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.

project #16-014coa #29304

P0.1

PLUMBING - LEGENDS &

GENERAL NOTES

CITY OF SARASOTA PUBLIC

WORKS ADMINISTRATION

BUILDING

DECEMBER 1, 2023

1750 12th STREET

SARASOTA, FLORIDA 34237

LOCKER RM RENOVATION -

PLUMBING SPECIFICATIONS

11. EQUIPMENT CONNECTIONS: CONTRACTOR SHALL FURNISH

ALL REQUIRED VALVES, FITTINGS, VACUUM BREAKERS, TRAPS,

ETC., NECESSARY FOR THE COMPLETE HOOKUP TO PROVIDE

PROPER OPERATION OF EACH PIECE OF EQUIPMENT. IN

CONNECTING TO EQUIPMENT, MANUFACTURER'S

RECOMMENDATIONS AS TO SIZE AND ARRANGEMENT OF

CONNECTIONS SHALL BE FOLLOWED, BUT WITH SIZES SHOWN

ON PLAN BEING FOLLOWED.

12. VALVES: DOMESTIC HOT AND COLD WATER SHUT-OFF VALVES

SHALL BE BRASS QUARTER TURN BALL VALVES WITH INJECTION

MOLDED BRASS THREAD TO CPVC SOLVENT WELD ADAPTERS

AND SHALL BE FULL PORT. PROVIDE BRASS VALVE TAGS WITH

SCHEDULE IDENTIFYING VALVE SERVICE AND LOCATION.

13. INSULATION: PROVIDE PREFORMED FIBERGLASS INSULATION

ON ALL HOT, HOT WATER CIRCULATION AND COLD WATER

PIPING (COLD WATER PIPING TO HAVE VAPOR BARRIER),

VALVES, AND EQUIPMENT. ALL INSULATION, JACKETS,

ADHESIVES, ETC., SHALL HAVE A FLAME SPREAD RATING NOT

OVER 25 AND A SMOKE DEVELOPED RATING NOT OVER 50.

INSULATION 'R' VALUES SHALL BE AS REQUIRED BY PREVAILING

CODES AND ENERGY RELATED STANDARDS.

PROVIDE ELASTOMERIC INSULATION ON ALL CONDENSATE

PIPING, ARMSTRONG AP OR EQUAL.

FINISHES: EXPOSED PIPE INSULATION SHALL BE VINYL COATED

WITH AN EMBOSSED LAMINATE VAPOR BARRIER JACKET. LAPS

AND END STRIPS SHALL BE ADHERED WITH INSULCOUSTIC

IC-225. CONCEALED PIPE INSULATION SHALL HAVE A WHITE

VAPOR BARRIER JACKET SECURED WITH ALUMINUM BANDS.

INSULATED PIPE WITHIN MAIN MECHANICAL ROOMS AND

SIMILAR AREAS THAT IS BELOW 7'-0" SHALL BE PROVIDED WITH

ALUMINUM JACKETS AND BANDS FOR PROTECTION.

INSULATION SUPPORT (TO PREVENT COLLAPSE OF INSULATION)

SHALL BE PROVIDED BETWEEN PIPING AND PIPE HANGING

SHIELDS. RIGID POLYURETHANE FOAM OR NATURAL CORK

INSERTS MAY BE USED FOR SUPPORT. ALL PIPE SUPPORT

APPARATUS MUST BE MOUNTED ON THE OUTSIDE OF ALL

INSULATION.

INSULATION FOR DOMESTIC WATER PIPING SHALL BE

1"THICKNESS FOR 2" AND SMALLER PIPING AND 1-1/2"

THICKNESS FOR 2-1/2" AND LARGER PIPING.

INSULATION FOR STORM WATER AND CONDENSATE PIPING

SHALL BE 3/4" THICKNESS.

PROVIDE PREFORMED INSULATION GUARDS ON ALL EXPOSED

PLUMBING ELEMENTS UNDER ADA COMPLIANT LAVS AND SINKS

AS REQUIRED BY ADA REQUIREMENTS, TRUEBRO OR EQUAL.

14. PIPING IDENTIFICATION: ALL PIPING SHALL BE IDENTIFIED WITH

SEMI-RIGID PLASTIC PRESSURE-SENSITIVE IDENTIFICATION

MARKERS (NOTE PRESSURE-SENSITIVE VINYL PIPE MARKERS

WILL NOT BE ACCEPTED). DIRECTION OF FLOW ARROWS ARE

TO BE INCLUDED ON EACH MARKER AND SHALL BE IN

CONFORMANCE WITH "SCHEME FOR THE…