ITB 25-45SS Plans.pdf
PDF 3 MB Posted
- Solicitation number
- 25-45SS
- Issued by
- Sarasota County, Florida
About this file
This document is a comprehensive set of construction drawings for the City of Sarasota Utilities Administration Building Men's Locker Room Remodeling project, located at 1750 12th Street in Sarasota, Florida. The project involves a renovation of the men's locker room and restroom area, with work spanning architectural, mechanical, plumbing, and electrical disciplines. The project is designed to update and modernize the existing facilities, with specific focus on replacing fixtures, updating finishes, and improving the overall functionality of the space. The project is being overseen by Hall Darling Design Studio as the Architect of Record and Genesis Engineering Group as the MEP Engineer of Record.
The renovation includes replacing existing plumbing fixtures such as toilets, urinals, and shower components, installing new tile work, updating lighting and electrical systems, and modifying mechanical ventilation. The project documents indicate a total renovation area of approximately 654 square feet, encompassing the men's restroom (340 SF) and locker room (314 SF). The drawings provide detailed specifications for new fixtures, finishes, and equipment, including Scranton Products 'Hiny Hiders' toilet partitions, new lockers, tile from Alpha Tile and DAL Tile, and LED lighting fixtures. The project appears to be funded by the City of Sarasota Utilities department, with work to be completed under the COSUD Project 002616, and is scheduled for bid in December 2023.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ITB 25-45SS Electronic Bid Form.xlsx | XLSX spreadsheet | |
| ITB 25-45SS Exhibit A - Required Forms.pdf | ||
| ITB 25-45SS Technical Specifications.pdf | ||
| ITBCON.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RANGE 18E, TOWNSHIP 36S, SECTIONS 18
COSUD PROJECT 002616
VICINITY MAP
ADMINISTRATION BUILDING MEN'S
LOCKER ROOM REMODELING
PROJECT INFO
CALL 2 FULL
BUSINESS DAYS
BEFORE YOU DIG
IT'S THE LAW!
DIAL 811
SUNSHINE STATE ONE CALL OF FLORIDA, INC.
Know what's below.
Call before you dig.
CITY OF SARASOTA UTILITIES - SARASOTA, FLORIDA
ISSUED FOR BID
G-01
SHEET LIST TABLE
SHEET
NUMBER SHEET TITLE
1-COVER SHEET
CS0.0 COVER SHEET
6-ARCHITECTURAL
A2.0 FIRST FLOOR PLAN
A5.0 INTERIOR ELEVATIONS
8-MECHANICAL
MO.1 MECHANICAL - LEGENDS & GENERAL NOTES
M1.0 MECHANICAL - OVERALL PLAN
M2.0 MECHANICAL - DEMOLITION & RENOVATION PLANS
M3.0 MECHANICAL - SCHEDULES AND DETAILS
11-ELECTRICAL
E0.1 ELECTRICAL - LEGENDS & GENERAL NOTES
E1.0 ELECTRICAL - OVERALL PLAN
E2.0 ELECTRICAL - DEMOLITION & PROPOSED FLOOR PLAN
E3.0 ELECTRICAL - SCHEDULE
E4.0 ELECTRICAL - ENERGY COMPLIANCE
PROJECT MANAGER:
EMIGDIO R. ISERN, P.E.
CITY OF SARASOTA UTILITIES
1750 12TH STREET
SARASOTA, FLORIDA 34236
941-263-6884 x36115
Tallahassee
Tampa
Miami
Jacksonville
Orlando
Pensacola
Fruitville Rd
U S
U S
41 U S
John Ringling Blvd
UTILITIES PROVIDERS LIST
1. GREG COKER
FLORIDA POWER AND LIGHT
1253 12TH AVENUE EAST
PALMETTO, FLORIDA 34221
(941) 723-4430
2. RANDY ALFORD
FRONTIER COMMUNICATIONS
1701 RINGLING BLVD.
SARASOTA, FLORIDA 34236
(941) 773-0077
3. ALEX MCFARLANE
TECO - PEOPLES GAS
8261 VICO COURT
SARASOTA, FLORIDA 34240
(813) 557-6134
4. ASHLEY WOODS
COMCAST CABLEVISION OF FLORIDA
5205 FRUITVILLE ROAD
SARASOTA, FLORIDA 34232
(941) 356-1489
5. DANNY HASKETT
CROWN CASTLE FIBER
9250 W. FLAGLER STREET
MIAMI, FLORIDA 33174
(941) 552-2931
6. KELLI WHITEHEAD
LEVEL 3 COMMUNICATIONS, LLC.
1025 ELDORADO BLVD.
BROOMFIELD, COLORADO 80021
(941) 888-4988
7. JOSH WELCH
CITY OF SARASOTA UTILITIES
1750 12TH STREET
SARASOTA, FLORIDA 34236
(941) 263-6884
8. ROBERT BRESCIANI
SARASOTA COUNTY STORMWATER
1001 SARASOTA CENTER BLVD.
SARASOTA, FLORIDA 34240
(941) 861-0908
SARASOTA CITY COMMISSION
COMMISSIONER
COMMISSIONER
COMMISSIONER
VICE MAYOR
ERIK ARROYO
KYLE BATTIE
LIZ ALPERT
JEN AHEARN-KOCH
DEBBIE TRICE
MAYOR
MEP ENGINEER OF RECORD:
GENESIS ENGINEERING GROUP
2601 CATTLEMEN ROAD
SARASOTA, FL 34232
941.444.2189
ARCHITECT OF RECORD:
HALL DARLING DESIGN STUDIO, PA
2168 MAIN STREET
SARASOTA, FL 34237
941.941.0883
AREA OF WORK
A5.0
A5.0
340 SF
MENS RESTROOM
314 SF
LOCKER ROOM
100A
EXISTING SERVICE LOCATIONS TO REMAIN
ADA
SHOWER
REPLACE SHOWER FLOOR
DRAINS IN EXISTING HUB, TYP
FLOOR SINK, DRAIN AND
FAUCET TO REMAIN
LOCKERS (23) 2-TIER LOCKERS
LOCKERS (17) 2-TIER LOCKERS
CORRIDOR - PROTECT DURING CONSTRUCTION
1' - 3"
2' - 8" 3' - 0" 3' - 1 1/2" 3' - 1" 3' - 1" 3' - 0" 3' - 0" 3' - 0"
/4
EX. DOOR
EX. DOOR
EX. DOOR
8 8 8
EXIST. ADA TOILET
ROOM
JANITOR
9 13
2' - 0" 2' - 6" 2' - 6" 2' - 6" 2' - 6" 2' - 0"
44 4
4 4 4
THRESHOLD
2 4
10 10 88
NO WORK
EX. DOOR
EX. DOOR
EX. DOOR
MENS RESTROOM
LOCKER ROOM
6 6 6
5 5
NO WORK
340 SF
MENS RESTROOM
314 SF
LOCKER ROOM
100A
7' - 6"
7' - 6"
8' - 0"
SS
S
7' - 10"
EXPOSED
CONC. BEAM,
PAINT
2' X 2' LAY-IN LED LIGHT FIXTURE
PAINTED GYPSUM
M.R. WALLBOARD
CEILING
2'x2'x5/8" ACOUSTIC TILE CEILING IN
SUSPENDED GRID
ARMSTRONG DUNE 1774 TEGULAR TILE
w/ CHICAGO METALLIC 1200 SERIES
GRID
RCP LEGEND
CEILINGS
LIGHTING
1' X 4' SUSPENDED LED
UTILITY FIXTURE
2' X 2' RETURN AIR GRILLE
2' X 2' SUPPLY AIR DIFFUSER
EXIT SIGN
FIRE ALARM HORN WITH STROBE
HEAT DETECTOR
OPEN TO UNDERSIDE OF STRUCTURE
CEILING TYPES
8'-0"
2'X2' ACOUSTIC CEILING TILE SYSTEM (ACT-1)
7'-6"
GENERAL RCP NOTES
1. REFER TO MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDITIONAL COORDINATION.
MECHANICAL
FIRE PROTECTION / LIFE SAFETY
S
5/8" MR GYPSUM WALL BOARD ON METAL FRAMING
7'-10"
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2023 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GLENN DARLING, AIA AR 97844
ARCHITECT OF RECORD
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
A2.0
FIRST FLOOR PLAN
CITY OF SARASOTA UTILITIES
DEPARTMENT LOCKER ROOM
RENOVATION
DECEMBER 20, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
ISSUED FOR PERMIT
23-025
N
1/4" = 1'-0"A2.0
5 REFLECTED CEILING PLAN
1/4" = 1'-0"A2.0
3 DEMOLITION PLAN
1/4" = 1'-0"A2.0
2 ENLARGED FLOOR PLAN
N
1/4" = 1'-0"A2.0
4 CEILING DEMOLITION PLAN - ENLARGED
N
DEMOLITION KEYNOTES
NO. DESCRIPTION
1 REMOVE FLOOR TILE TO EXPOSE EXISTING SUBSTRATE.
2 REMOVE WALL TILE TO EXPOSE EXISTING SUBSTRATE.
3 REMOVE TOILET PARTITIONS, URNIAL SCREENS AND
FASTENERS.
4 REMOVE TOILET AND URINAL FIXTURES. STONE SINK /
HANDWASH TO REMAIN.
5 REMOVE CEILING TILE AND SUPPORTING GRID.
6 REMOVE LIGHT FIXTURES.
7 REMOVE HVAC SERVICE AND RETURN DIFFUSERS. DUCT
TO REMAIN.
8 REMOVE AND REPLACE PLUMBING SERVICE VALVES.
9 REMOVE AND REPLACE GYP. BOARD CEILING.
10 REMOVE AND SALVAGE RESTROOM ACCESSORIES.
N
BULLNOSE EDGE TO WALL FACE
TYPICAL BOTH JAMBS
OPEN
OPEN
WALL TILE,SEE TILE
PATTERN, TYP.
PAINT
WALL TILE,SEE TILE
PATTERN, TYP.
PAINT
EXISTING DOOR TO REMAIN, PAINT
PAINT
WALL TILE, SEE TILE PATTERN, TYP.
1313 13137
4 4 4
13 13
PROVIDE PROTECTIVE ADA
PIPE WRAP, TYP. ALL SINKS
PROVIDE PROTECTIVE ADA
PIPE WRAP, TYP. ALL SINKS
WALL TILE,SEE TILE
PATTERN, TYP.
PAINT
EXISTING DOOR
TO REMAIN,
PAINT
TILE BASE CT-2
PAINT
9 9
H C
P
N O
N
H C
P
EQ. - 36" +/-
4 MIRROR
6 URINAL SCREEN 7 TOILET PARTITION
8 TOILET TISSUE
DISPENSER
9 PAPER TOWEL DISPENSER
13 SOAP DISPENSER
22 ROBE HOOK (HCP)
N O
N
H C
P
M A
X
16 SHOWER SEAT
17 SHOWER ROD,
CURTAIN, AND HOOKS
18 SHOWER GRAB BARS
FINISH FLOOR
FINISH FLOOR
WALL MOUNTED TOILET
URINAL AND URINAL SCREEN SHOWER
ACCESSORIES
2' - 0"
TOILET PARTITIONS AND URINAL SCREENS
SCRANTON PRODUCTS 'HINY HIDERS'
FLOOR MOUNTED OVERHEAD BRACED
8" ALUMINUM WRAP AROUND HINGE
STAINLESS STIRRUP BRACKETS.
COLOR SELECTED BY OWNER FROM STD.
COLOR CHOICES
PROVIDE SHOP DRAWINGS FOR APPROVAL
PRIOR TO FABRICATION
No. DESCRIPTION
TOILET FIXTURE & ACCESSORY KEYNOTE LEGEND
NOTE: PROVIDE BLOCKING AT WALL MOUNT FIXTURE ACCESSORIES
4 30" H x 42" W MIRROR - BOBRICK B-165 SERIES
6 URINAL SCREEN, 24" W - SCRANTON PRODUCTS STD. COLOR SELECTION
7 TOILET PARTITION (FLOOR ANCHORED, OVERHEAD BRACED)
8 TOILET TISSUE DISPENSER - BOBRICK B265
9 PAPER TOWEL DISPENSER - BOBRICK B-262
13 SOAP DISPENSER - BOBRICK B-2111
16 SHOWER SEAT (HCP) - BRADLEY 9593 FOLDING SEAT
17 SHOWER ROD, CURTAIN, AND HOOKS - BOBRICK B-207, B-204-2, B-204-1
18 SHOWER GRAB BARS (HCP) - BOBRICK B-5806 SERIES
21 ROBE HOOK - BOBRICK B-6717
22 SOAP DISH - BOBRICK B-680 (SHOWER)
23 TOWEL BAR - BOBRICK B-6747
24 MIRROR - BOBRICK B-2908 1830
SCHED. CT-1
FLOOR TILE.
SCHLUTER STRIP
RENO-U EU125 .
EXISTING
FLOORING
SCHED. CT-2
SHOWER TILE
SCHED. THRESHOLD
SCHED. CT-1
FLOOR TILE
8"
SHOWER THRESHOLD
DOOR THRESHOLD
EXISTING
DOOR
PAINT
PAINT
LOCKERS
TILE BASE CT-2
TILE BASE CT-2
SHOWER WALL TILE,
SEE TILE PATTERN,
TYP.
CLOSURE PANEL
TO MATCH
LOCKERS
SLOPED TOP
SHOWER WALL TILE,
SEE TILE PATTERN,
TYP.
PAINT
16 16
22 22
OPEN
OPEN
LOCKERS
SHOWER WALL TILE,
SEE TILE PATTERN,
TYP.
PAINT
TILE BASE, CT-2 TILE BASE, CT-2
PAINT
SLOPED TOP
PAINT
TILE BASE, CT-2
EXISTING DOOR TO REMAIN, PAINT
"3
SCHLUTER QUADEC-K (TOP)
T-3
T-4
T-5
T-3
T-4
T-5
T-4
T-5
T-3 T-3
WALL TILE CT-4
"3
SCHLUTER QUADEC-K (TOP)
T-3
T-4
T-5
T-3
T-4
T-5
T-4
T-5
T-3
T-3
REPEATING PATTERN CT-4, TYPICAL
REPEATING PATTERN CT-4, TYPICAL
TYPICAL RESTROOM
TYPICAL SHOWERS
BASE CT-2
WALL TILE CT-3
WALL TILE CT-3
T-4
T-5
INTERIOR FINISH LEGEND
FLOORING BASE CEILING PAINT
ACT-1 Acoustic Lay-In Tile Manufaturer: Armstrong Style: Dune #1774 Tegular Edge Profile: Angled Tegular Size: 2'-0" x 2'-0" Color: White Grid: 15/16" Chicago Metallic 1200 Exposed Tee Grid Color: White
GWB Painted Gypsum Board Smooth Finish
P2 Low VOC Latex Paint Manufacturer: Sherwin Williams Color:
Finish: Semi-Gloss Location: Interior Doors and Frames
P4 Low VOC Latex Paint Manufacturer: Sherwin Williams Color:
Finish: Flat Location: All CMU Walls (Interior Exposed)
CT-1 Porcelain Tile Manufaturer: Alpha Tile and Stone Style: Kone Series Color: Grey VR03 Size: 12" x 24"
CT-2 Ceramic Tile Manufaturer: DAL Tile Style: Valor Cove Base P36C9T Color: Gallant Gray VR03 Size: 6" x 12"
WALL - TILE
CT-3 FIELD Porcelain Tile Manufacturer: Alpha Tile and Stone Style: Loop Series Color: Grey Size: 12" x 24"
CT-4 WAINSCOT Ceramic Tile Manufaturer: DalTile Style: Color Wheel Classics Color: Key Lime / 1098 Ocean Blue / 1049 Electric Blue / 1194 Size: 3" x 6" Random Pattern
CT-2 Shower Porcelain Tile Manufaturer: Alpha Tile and Stone Style: Onix Mosaic Color: Gray Size: 3"
SHOWER THRESHOLD
ST-1 Marble Stone Slab Manufaturer: DAL Tile Style: Stormy Mist M048 Size: 8" x 36"
Grout: Mapei Ultracolor Plus FA Cobblestone / 103 Sealer: Custom Building Products Red Guard
Grout: Mapei Ultracolor Plus FA Cobblestone / 103 Sealer: Custom Building Products Red Guard
Grout: Mapei Ultracolor Plus FA Cobblestone / 103
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2023 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GLENN DARLING, AIA AR 97844
ARCHITECT OF RECORD
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
DIGITAL CERTIFICATION
CERTIFICATION BY ARCHITECT IS FOR THE
BUILDING’S ARCHITECTURAL COMPONENTS
ONLY. PLEASE REFER TO INDIVIDUAL
ENGINEER’S DRAWINGS FOR CERTIFICATION
BY THOSE DESIGN PROFESSIONALS.
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
AND SEALED BY GLENN DARLING, AIA, AS
NOTED BELOW, USING A DIGITAL SIGNATURE.
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SIGNATURE MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
A5.0
INTERIOR ELEVATIONS
CITY OF SARASOTA UTILITIES
DEPARTMENT LOCKER ROOM
RENOVATION
DECEMBER 20, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
ISSUED FOR PERMIT
23-025
1/4" = 1'-0"A5.0
4 I.E. - D
1/4" = 1'-0"A5.0
3 I.E. - C
1/4" = 1'-0"A5.0
1 I.E. - A
1/4" = 1'-0"A5.0
2 I.E. - B
1/4" = 1'-0"A5.0
5 I.E. - F
1/4" = 1'-0"A5.0
6 I.E. - G
1/4" = 1'-0"A5.0
7 I.E. - I
1/4" = 1'-0"A5.0
8 I.E. - H
1 1/2" = 1'-0"
TYPICAL THRESHOLDS
1/2" = 1'-0"A5.0
9 WALL TILE LAYOUTS
ROOM FINISH SCHEDULE
WT ROOM NAME
FLOOR WALLS CEILING
REMARKSFINISH BASE NORTH EAST SOUTH WEST FINISH
FIRST FLOOR
100 MENS RESTROOM CT-1 CT-3 CT-3 / CT-4 CT-3 / CT-4 P4 CT-3 / CT-4 ACT-1 CT-3 SOUTH WALL ONLY
100A LOCKER ROOM CT-1 CT-3 P4 P4 P4 P4 ACT-1
101 JANITOR NO WORK
FSD
SD
RD
FD
RETURN AIR
SMOKE DETECTOR
SQUARE FEET)
REQUIRED INDICATED IN
DOOR LOUVER (FREE AREA
UNDERCUT DOOR
L
UC
S
SINGLE LINE
SUPPLY AIR
RADIUS ELBOW (R=1.5)
CONTROL DAMPER-
AIR REGISTER (R)
SUPPLY AIR GRILLE (G) OR SUPPLY
FLEXIBLE CONNECTION (FXC)
AIR FLOW
RISE OR DROP DIRECTION OF
REC. BRANCH DUCT TAKE-OFF W/ VD
ELBOW W/ TURNING VANES
DIFFUSER
RD
TO BE REMOVED.
EXISTING EQUIPMENT OR DUCTWORK
ACCESS DOOR
MOTOR OPERATED DAMPER (MOD)
MANUAL VOLUME DAMPER (MVD)
NEW DUCTWORK
AD
VD
AD
DOUBLE LINE
D R
AD
VD
# KEYED NOTE NUMBER
X
X
X
X INDICATES DRAWING ON WHICH
DETAIL APPEARS
INDICATES SECTION NUMBER
INDICATES ON WHICH DRAWING
SECTION APPEARS
INDICATES REVISION & NUMBER
MECHANICAL SYMBOL LEGEND
INDICATES DETAIL, PLAN, SECTION, AND/OR
DIAGRAM(APPLIES ONLY WHERE INDICATED
TYP
X
X
INDICATES TYPICAL DETAIL
(APPLIES TO ALL CONTRACT
ON DRAWINGS)
INDICATES DRAWING ON WHICH
DETAIL APPEARS
DRAWINGS)
M
DUCT SYMBOLSGENERAL SYMBOLS
ROUND BRANCH DUCT TAKE-OFF W/ VD
T THERMOSTAT
PIPE RISING UP
PIPE DROPPING DOWN
DIRECTION OF FLOW
AUTOMATIC CONTROL VALVE (3-WAY)
PRESSURE REDUCING VALVE (PSI)
AUTOMATIC CONTROL VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
GATE VALVE
PRESSURE GAUGE
PIPE WELL
F.S.
FLOW SWITCH
THERMOMETER
STRAINER
PIPING SYMBOLS
SMOKE DAMPER W/ ACCESS
DOOR
FIRE SMOKE DAMPER W/ ACCESS
DOOR
RADIATION DAMPER W/ ACCESS
THROUGH DEVICE
EXHAUST AIR
FIRE DAMPER W/ ACCESS
DOOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFR ABOVE FINISHED ROOF
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AO ANALOG OUTPUT
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C COMMON
CD CONDENSATE
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CO2 CARBON DIOXIDE
COP COEFFICIENT OF PERFORMANCE
CU CONDENSING UNIT
DAC DEHUMIDIFICATION AHU
DB DRY BULB
DCU DEHUMIDIFICATION CU
DDC DIRECT DIGITAL CONTROL
DEGF DEGREE FAHRENHEIT
DI DIGITAL INPUT
DN DOWN
DO DIGITAL OUTPUT
DWG DRAWING
DP DIFFERENTIAL PRESSURE
EA EXHAUST AIR
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EAT ENTERING AIR TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
ERV ENERGY RECOVERY VENTILATOR
FC FAIL CLOSED
FC FAN COIL (EXISTING)
FCU FAN COIL UNIT
FD FIRE DAMPER
FF FLOW FEEDBACK/STATUS SIGNAL
FLA FULL LOAD AMPS
FO FAIL OPEN
FPM FEET PER MINUTE
FT FEET
GPM GALLONS PER MINUTE
H HUMIDITY
HS HUMIDISTAT
HP HEAT PUMP
HP HORSEPOWER
HWS HOT WATER SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
IAQ INDOOR AIR QUALITY
IN INCH
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LPS LOW PRESSURE STEAM
LPR LOW PRESSURE RETURN
LWT LEAVING WATER TEMPERATURE
M MOTORIZED
MBH THOUSAND BTUH
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVER CURRENT PROTECTION
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OBD OPPOSED BLADE DAMPER
OA OUTDOOR AIR
P PRESSURE
PF PROPORTIONAL FEEDBACK
PRV PRESSURE REDUCING VALVE
PRS PRESSURE REDUCING STATION
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
RA RETURN AIR
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RL REFRIGERANT LIQUID
RTU ROOFTOP PACKAGED UNIT
SA SUPPLY AIR
SF SQUARE FEET
SS START/STOP SIGNAL
S.S. STAINLESS STEEL
SP STATIC PRESSURE
T TEMPERATURE
V-PH VOLTAGE-PHASE
TD TIME DELAY
TS TEMPERATURE SENSOR
TSP TOTAL STATIC PRESSURE
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
WB WET BULB
WG WATER GAUGE
WR CHILLED WATER RESET
W/ WITH
W/O WITHOUT
MECHANICAL ABBREVIATIONS LEGEND
GENERAL NOTES
1. DO NOT SCALE FROM THESE DRAWINGS. EXACT DIMENSIONS SHALL BE TAKEN FROM ARCHITECTURAL
DRAWINGS.
2. ALL INDICATED WORK SHALL BE PERFORMED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE
NOTED.
3. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND
REGULATIONS INCLUDING, BUT NOT LIMITED TO, NATIONAL, CITY, STATE, AND LOCAL ORDINANCES WHICH
MAY BE IN EFFECT. ALL MECHANICAL MATERIALS, INSTALLATION PROCEDURES, AND SYSTEM LAYOUTS SHALL
BE APPROVED BY ALL APPLICABLE CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION, AND IT SHALL
BE THE MECHANICAL CONTRACTOR'S RESPONSIBILITY TO PAY FOR ALL NECESSARY PERMITS AND
APPROVALS FOR THIS INSTALLATION.
4. IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO REVIEW THESE PLANS AND SPECIFICATIONS
AS WELL AS THE RELATED PLUMBING, FIRE PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS TO BECOME FAMILIAR WITH THE FULL PROJECT SCOPE.
IN ADDITION, THIS CONTRACTOR MUST COORDINATE WITH THE OWNER OR OWNER'S REPRESENTATIVE TO
FULLY UNDERSTAND ALL REQUIREMENTS WHICH MAY NOT BE SPECIFIED HEREIN AND WHICH THE OWNER
MAY CONSIDER PART OF THIS CONTRACT. DURING THE COURSE OF CONSTRUCTION COORDINATION AND
ACTUAL CONSTRUCTION, IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO WORK CLOSELY WITH ALL
ACCOMPANYING CONTRACTORS AND TRADESMEN IN ORDER TO ENSURE A SMOOTH RUNNING AND
CAREFULLY COORDINATED INSTALLATION.
5. ANY DISCREPANCIES OR INADEQUACIES WITHIN THESE BID DOCUMENTS OR BETWEEN THESE BID
DOCUMENTS AND THE RELATED PLUMBING, FIRE PROTECTION, ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR DECOR, AND SITE ENGINEERING DRAWINGS, OR BETWEEN THESE BID DOCUMENTS AND FIELD
CONDITIONS MUST BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT, AND ENGINEER PRIOR TO
BID SUBMISSION.
6. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN THESE DRAWINGS, BETWEEN
INFORMATION PROVIDED IN THESE DRAWINGS AND THE PROJECT SPECIFICATIONS, AND/OR WITHIN THE
PROJECT SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST COST REQUIREMENTS SHALL APPLY.
SHOULD THIS CONTRACTOR REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR
CLARIFICATION. WHERE CONFLICTS DO EXIST, THE PROJECT ENGINEER OF RECORD SHALL HAVE THE SOLE
DISCRETION AND RIGHT TO PROVIDE INTERPRETATION OF INTENT OF THE CONTRACT DOCUMENTS AS
REQUIRED. THIS INTERPRETATION SHALL SERVE TO DIRECT THE CONTRACTOR IN ACCORDANCE WITH THE
IMPLIED INTENT OF THE CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE PROJECT.
7. THE MECHANICAL CONTRACTOR SHALL PROVIDE A COMPLETE SET OF RECORD "AS-BUILT" DRAWINGS, INDICATING THE PRECISE LOCATION OF ALL SYSTEMS, EQUIPMENT, CONCEALED OR EMBEDDED PIPING, PIPING CONNECTIONS, AND ACCESS DOORS. THESE DRAWINGS SHALL ALSO INCLUDE ALL CHANGES AND
DEVIATIONS FROM THE BID DOCUMENTS.
8. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW MECHANICAL EQUIPMENT WITH NEW LIGHT
LOCATIONS AND TILE LOCATIONS. REFER TO THE ARCHITECT'S REFLECTED CEILING PLAN LAYOUT.
9. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
10. RUN ALL DUCTWORK AND PIPING WITH AS FEW OFFSETS AS POSSIBLE THROUGHOUT THE ENTIRE BUILDING.
COORDINATE AND VERIFY WITH OTHER CONTRACTORS SO AS NOT TO INTERFERE WITH PLUMBING, FIRE
PROTECTION PIPING, LIGHTING SYSTEMS, ETC.
11. ALL REQUIRED OFFSETS, RISES, AND DROPS DUE TO POSSIBLE OBSTRUCTIONS OF DUCT AND PIPE RUNS ARE
NOT NECESSARILY SHOWN. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK, PIPING, SUPPORTS, ETC. NECESSARY FOR PROPER INSTALLATION AND OPERATION OF
NEW HVAC SYSTEM. THIS CONTRACTOR SHALL INCLUDE A CONTINGENCY IN HIS/HER BID TO OFFSET ANY
COST REQUIRED FOR ADDITIONAL FITTINGS AND LABOR THAT MAY BE REQUIRED.
12. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH VOLUME DAMPER IN THE BRANCH
CONNECTION UNLESS NOTED OTHERWISE. ALL ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED
WITH CONICAL SPIN-IN FITTING WITH INTEGRAL VOLUME DAMPER.
13. CONDENSATE SHALL BE PIPED FULL SIZE TO THE NEAREST APPROVED STORM WATER DRAINAGE SYSTEM
OR LANDSCAPED/GRASS AREA VIA AN INDIRECT CONNECTION. CONDENSATE SHALL NOT BE ALLOWED TO
DRAIN ONTO ANY WALKWAY.
14. MOUNT ALL THERMOSTATS ABOVE FINISHED FLOOR AT HEIGHT APPROVED BY ARCHITECT. COORDINATE
LOCATION WITH ARCHITECTURAL INTERIOR ELEVATIONS.
A CFM
A CFM
A CFM
A CFM
15. TEST AND BALANCE BY A THIRD PARTY SHALL BE REQUIRED FOR ALL SUPPLY, RETURN, OA, VENTILATION, STAIR PRESSURIZATION AND SMOKE REMOVAL SYSTEMS FOR THIS FACILITY.
APPLICABLE CODES
BUILDING CODE:
EXISTING CODE:
ACCESSIBILITY:
MECHANICAL CODE:
ELECTRICAL CODE:
PLUMBING CODE:
ENERGY CODE:
FUEL GAS CODE:
FIRE SAFETY CODE:
FLORIDA BUILDING CODE, 7TH EDITION (FBC), (2020) BUILDING
FLORIDA BUILDING CODE, 7TH EDITION (2020) EXISTING BUILDING
FLORIDA BUILDING CODE, 7TH EDITION (2020) ACCESSIBILITY
FLORIDA BUILDING CODE, 7TH EDITION (2020) MECHANICAL
FLORIDA BUILDING CODE, 7TH EDITION (2020) - CHAPTER 27; NFPA 70 (N.E.C.)
FLORIDA BUILDING CODE, 7TH EDITION (2020) PLUMBING
FLORIDA BUILDING CODE, 7TH EDITION (2020) ENERGY CONSERVATION
FLORIDA BUILDING CODE, 7TH EDITION (2020) FUEL GAS
FLORIDA FIRE PREVENTION CODE 7TH EDITION, BASED ON NFPA 1, NFPA 101, & LIFE SAFETY CODE
CONNECT NEW TO EXISTING
DEMOLISH TO THIS POINT
AUTO AUTOMATIC
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING ASHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U genesis engineering
2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.
project #16-014coa #29304
M0.1
MECHANICAL - LEGENDS &
GENERAL NOTES
CITY OF SARASOTA PUBLIC
WORKS ADMINISTRATION
BUILDING
DECEMBER 1, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
LOCKER RM RENOVATION -
INTERIOR BUILDOUT
21-024
MENS RESTROOM
LOCKER ROOM
M2.0
M2.0
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING ASHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U genesis engineering
2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.
project #16-014coa #29304
M1.0
MECHANICAL - OVERALL PLAN
CITY OF SARASOTA PUBLIC
WORKS ADMINISTRATION
BUILDING
DECEMBER 1, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
LOCKER RM RENOVATION -
INTERIOR BUILDOUT
21-024
N
1/8" = 1'-0"
MECHANICAL - PROPOSED FLOOR PLAN
LOCKER ROOM
T
A
150 CFM
M
200 CFM
M
200 CFM
A
150 CFM
M
150 CFM
A
250 CFM
L
680 CFM
M
150 CFM
A
250 CFM
EF-1
T
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING ASHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U genesis engineering
2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.
project #16-014coa #29304
M2.0
MECHANICAL - DEMOLITION &
RENOVATION FLOOR PLANS
CITY OF SARASOTA PUBLIC
WORKS ADMINISTRATION
BUILDING
DECEMBER 1, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
LOCKER RM RENOVATION -
INTERIOR BUILDOUT
21-024
1/4" = 1'-0"M2.0
2 MECHANICAL - ENLARGED PROPOSED FLOOR PLAN
KEYED NOTESGENERAL NOTES PROPOSED KEYED NOTESGENERAL NOTES
N
1. CONTRACTOR SHALL INSTALL MECHANICAL EQUIPMENT IN ACCORDANCE
WITH ALL STATE AND LOCAL CODES.CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL TRANSITIONS, FITTINGS, ELBOWS, DUCTWORK,
PIPING, SUPPORTS, ETC. NECESSARY FOR A PROPER INSTALLATION
AND OPERATION OF NEW HVAC SYSTEM.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
INSTALLATION WORK WITH OTHER TRADES TO AVOID CONFLICTS.
3. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW
MECHANICAL EQUIPMENT WITH NEW LIGHT LOCATIONS, AND CEILING
TILE LOCATIONS. REFER TO ARCHITECT'S REFLECTED CEILING PLAN
LAYOUT.
4. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE
DIMENSIONS.
5. WHERE CONFLICTS EXIST BETWEEN THE INFORMATION INCLUDED IN
THESE DRAWINGS OR BETWEEN INFORMATION PROVIDED IN THESE
DRAWINGS AND THE PROJECT SPECIFICATIONS OR WITHIN THE
PROJECT SPECIFICATIONS, THE MORE STRINGENT AND/OR HIGHEST
COST REQUIREMENTS SHALL APPLY. SHOULD THE CONTRACTOR
REQUIRE FURTHER CLARIFICATION, AN RFI SHALL BE SUBMITTED FOR
CLARIFICATION. WHERE CONFLICTS DO EXIST, THE PROJECT ENGINEER
OF RECORD SHALL HAVE THE SOLE DISCRETION AND RIGHT TO PROVIDE
INTERPRETATION OF INTENT OF THE CONTRACT DOCUMENTS, AS
REQUIRED, AND THIS INTERPRETATION SHALL SERVE TO DIRECT THE
CONTRACTOR IN ACCORDANCE WITH THE IMPLIED INTENT OF THE
CONSTRUCTION DOCUMENTS WITHOUT ADDITIONAL COST TO THE
PROJECT.
6. ALL BRANCH DUCTS TO AIR DEVICES SHALL BE PROVIDED WITH VOLUME
DAMPER IN THE BRANCH CONNECTION UNLESS NOTED OTHERWISE. ALL
ROUND BRANCH DUCT CONNECTIONS SHALL BE PROVIDED WITH
CONICAL SPIN-IN FITTING WITH INTEGRAL VOLUME DAMPER.
7. ALL AIR DEVICE COLORS AND FINISHES SHALL BE COORDINATED WITH
THE ARCHITECT BY MECHANICAL CONTRACTOR.
8. CONTRACTOR SHALL BALANCE THE EXISTING DIFFUSERS TO MATCH THE
CFM DISPLAYED ON THE DRAWINGS.
1 PROVIDE NEW SUPPLY DIFFUSER IN THIS APPROXIMATE LOCATION. SEE
SCHEDULES FOR MORE INFORMATION. COORDINATE FINAL LOCATION
WITH ARCHITECT AND GENERAL CONTRACTOR.
PROVIDE NEW EXHAUST GRILLE IN THIS APPROXIMATE LOCATION. SEE
SCHEDULES FOR MORE INFORMATION. COORDINATE FINAL LOCATION
WITH ARCHITECT AND GENERAL CONTRACTOR.
EXISTING THERMOSTAT TO REMAIN. CONTRACTOR SHALL CLEAN,
INSPECT, AND TEST UNIT FOR PROPER OPERATION. REPAIR OR REPLACE
UNIT IF FOUND TO BE DEFECTIVE.
RECONNECT EXISTING SUPPLY DUCTWORK TO NEW DIFFUSER. PROVIDE
NEW FLEX DUCTWORK AS REQUIRED. COORDINATE FINAL LOCATION
WITH NEW CEILING LAYOUT.
RECONNECT EXISTING EXHAUST DUCTWORK TO NEW GRILLE. PROVIDE
NEW FLEX DUCTWORK AS REQUIRED. COORDINATE FINAL LOCATION
WITH NEW CEILING LAYOUT.
PROVIDE NEW FILTER RETURN GRILLE IN THIS APPROXIMATE LOCATION.
SEE SCHEDULE FOR MORE INFORMATION. COORDINATE FINAL LOCATION
WITH NEW CEILING LAYOUT.
NEW WALL MOUNTED EXHAUST FAN TO BE INSTALLED IN THIS
APPROXIMATE LOCATION. EXHAUST FAN MUST MAINTAIN A MINIMUM 10'-0"
FROM ALL MECHANICAL AIR INTAKES. VERIFY FINAL LOCATION IN FIELD.
EXISTING DOOR GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN AND
INSPECT GRILLE AND REPLACE IF DAMAGED OR DEFECTIVE. COORDINATE
WITH ARCHITECT AND GENERAL CONTRACTOR.
4 1
1/4" = 1'-0"M2.0
1 MECHANICAL - ENLARGED DEMOLITION PLAN
DEMOLITION KEY NOTES DEMOLITION NOTES
1 REMOVE EXISTING EXHAUST GRILLE.
CONTRACTOR SHALL CLEAN AND INSPECT DUCTWORK. RETAIN EXISTING
DUCTWORK FOR RECONNECTION TO NEW AIR DEVICE.
REMOVE EXISTING SUPPLY DIFFUSER
EXISTING THERMOSTAT TO REMAIN. CONTRACTOR SHALL CLEAN,
INSPECT, AND TEST UNIT FOR PROPER OPERATION. REPAIR OR REPLACE
UNIT IF FOUND TO BE DEFECTIVE.
CONTRACTOR SHALL REMOVE EXISTING FLEX DUCTWORK UP TO EXISTING
SHEETMETAL SUPPLY DUCT.
REMOVE EXISTING FILTER RETURN GRILLE. EXISTING DUCTWORK AND AIR
HANDLING UNIT ON MEZZANINE LEVEL ABOVE TO REMAIN.
REMOVE EXISTING WALL-MOUNTED EXHAUST FAN ABOVE ROOF LEVEL.
RETAIN EXISTING DUCTWORK FOR RECONNECTION TO NEW FAN.
CONTRACTOR SHALL CLEAN AND INSPECT DUCTWORK. PREPARE
DUCTWORK FOR RECONNECTION TO NEW EXHAUST FAN.
EXISTING DOOR GRILLE TO REMAIN. CONTRACTOR SHALL CLEAN AND
INSPECT GRILLE AND REPLACE IF DAMAGED OR DEFECTIVE. COORDINATE
WITH ARCHITECT AND GENERAL CONTRACTOR.
1. COORDINATE HVAC DEMOLITION WITH OTHER TRADES AND GENERAL
CONTRACTOR. DO NOT DEMOLISH EQUIPMENT OR COMPONENTS
WITHOUT APPROVAL.
2. UNDER NO CIRCUMSTANCE SHALL DEMOLITION CAUSE DAMAGE OR
REMOVAL IN WHOLE OR IN PART OF ANY STRUCTURAL MEMBER
WITHOUT EXPRESS APPROVAL OF THE GENERAL CONTRACTOR.
3. CAP AND PROTECT ANY EXPOSED EQUIPMENT, DUCT, PIPE OR
ELECTRICAL CABLE / CONDUIT THAT RESULTS FROM DEMOLITION.
UNDER NO CIRCUMSTANCE WILL DEMOLITION RESULT IN THE
PERMANENT EXPOSURE OF ANY CHARGED OR LIVE COMPONENT OF
ANY EQUIPMENT TO BE RE-USED.
4. PROTECT ANY EQUIPMENT, SYSTEM, OR COMPONENT THEREOF THAT
SHALL BE RE-USED.
5. COORDINATE DISPOSAL OF ALL REMOVED ITEMS WITH THE GENERAL
CONTRACTOR. TURN OVER ANY COMPONENTS TO THE OWNER AS
DESIGNATED IN CLEAN CONDITION, WITHOUT DAMAGE, AND WITH
OPENING SEALED. FURNISH RECEIPTS OF PROPER DISPOSAL OF ALL
ITEMS REMOVED TO THE GENERAL CONTRACTOR UPON REQUEST.
RECEIPTS SHALL INDICATE DISPOSAL IN ACCORDANCE WITH ALL LOCAL,
STATE, AND FEDERAL REGULATIONS.
6. PRIOR TO START OF CONSTRUCTION, CONTRACTOR SHALL PERFORM
MAINTENANCE SERVICE TO EXISTING EQUIPMENT TO BE REUSED IN THE
NEW LAYOUT (TO REMAIN OR TO BE RELOCATED). NOTIFY ARCHITECT,
OWNER, AND ENGINEER OF ANY DEFICIENCY FOUND DURING PRE-
CONSTRUCTION MAINTENANCE SERVICE.
3 3
5 5
VENTILATION CALCULATIONS - 2020 FBC-M
ROOM # ROOM NAME
# OF PEOPLE
(1)
PEOPLE OUTDOOR
AIR RATE
(CFM/PERSON)
AREA (FT 2)
AREA OUTDOOR
AIR RATE (CFM/FT2)
Ez
VALUE
OA
REQUIRED
(CFM) (2)
OA
PROVIDED
(CFM)
PROVIDED
SUPPLY
AIRFLOW
UNIT TAGS
EXHAUST
RATE (CFM/FT2)
EXHAUST
REQUIRED
(CFM)
EXHAUST
PROVIDED
(CFM)
UNIT TAGS
LOCKER ROOM 0 0 293 0 0.8 0 60 500 EXISTING AHU-1 0.25 114 (4) 300 EF-1
MENS RESTROOM 0 0 424 0 0.8 0 60 300 EXISTING AHU-1 400 (3) 400 400 EF-1
JANITOR 0 0 44 0 0.8 0 0 0 EXISTING AHU-1 0 0 0
ZONE TOTALS = 0 761 0 120 800 514 700
NET EXFILTRATION RATE (5) = 0.13
AHU-1 0 0 0 120 800 UNIT OA 15.0% 0 0 0
NOTES:
1. SEE ARCHITECTURAL PLANS FOR ACTUAL OCCUPANCY LOADS.
2. OUTSIDE AIR REQUIRED = (PEOPLE * (CFM/PERSON) + AREA * (CFM/SF))/Ez.
3. EXHAUST VENTILATION REQUIRED AT 50 CFM PER WATER CLOSET OR
OPPOSED BLADE DAMPER
SUPPLY DUCT
MAIN
CEILING
COLLAR
CEILING DIFFUSER
TYPICAL DIFFUSER CONNECTION
(BOTTOM OF DUCT CONNECTION)
NOT TO SCALE
MANUFACTURER PROVIDED
(FACE ADJUSTABLE)
NOT TO SCALE
CENTRIFUGAL WALL EXHAUST FAN DETAIL
NOTE:
INSTALLATION PROCEDURES
WITH MANUFACTURER'S
WALL IN ACCORDANCE
MOUNT AND SECURE TO
AIR DEVICE SCHEDULE
TAG DIFFUSER
SIZE
NECK
SIZE
MANUFACTURER NOTESMODELMAX. FLOW
(CFM)
FINISH
24X24 6"∅ 130 WHITE TITUS TDC 1, 2
A
24X24 8"∅ 240 WHITE TITUS TDC
24X24 10"∅ 330 WHITE TITUS TDC
24X24 12"∅ 470 WHITE TITUS TDC
1, 2
1, 2
1, 2
GENERAL NOTES:
KEY NOTES:
1 FLEX DUCT SIZE TO MATCH NECK SIZE. MAXIMUM LENGTH OF FLEX SHALL BE 5'-0", BALANCE OF DUCT SHOWN ON
PLAN SHALL BE STEEL DUCT SAME SIZE AS NECK SIZE, EXTERNALLY INSULATED.
PROVIDE RUNOUT BRANCH DUCT TO AIR DEVICE SAME SIZE AS AIR DEVICE NECK UNLESS OTHERWISE NOTED ON
PLANS. PROVIDE 18" X 18" BACKPAN SIZE WITH 24" X 24" MODULE.
ALUMINUM 1/2" X 1/2" X 1/2" GRID
FILTER RETURN GRILLE FOR 1" FILTER - PROVIDE 1/4 TURN FASTENER AND 1" FILTER SET SIZED TO FIT GRILLE
INCLUDING NEW FILTER AT COMPLETION OF CONSTRUCTION AND SPARE FILTER.
1. BORDER TYPE SHALL BE SELECTED AS COORDINATED WITH ARCHITECTS REFLECTED CEILING PLAN.
2. PROVIDE SQUARE TO ROUND TRANSITIONS AS REQUIRED FOR COORDINATION OF DUCT AND AIR DEVICE NECK.
3. INSULATE THE TOPS OF ALL SUPPLY AIR DEVICES WITH 2" FIBERGLASS DUCT WRAP. SEAL AIR TIGHT AROUND EDGES
TO PREVENT CONDENSATION.
4. ALL DEVICES ARE TO BE ALUMINUM UNLESS OTHERWISE NOTED.
FAN SCHEDULE
TAG
NOTES:
CFM
E.S.P.
(IN. W.G.)
MOTOR
WATTS RPM V / PH
MANUFACTURER NOTESMODEL
HP
SONES
EF-1 700 0.5 --- 1624 120 / 18.8GREENHECK CUE-095-VG 1, 2, 3, 4, 51/6
1. PROVIDE FLEXIBLE CONNECTORS AT ALL DUCT CONNECTIONS TO FAN.
2. PROVIDE FAN WITH GRAVITY BACKDRAFT DAMPER. REFER TO STANDARD MECHANICAL DETAILS FOR FURTHER DETAILS.
3. PROVIDE WITH FACTORY MOUNTED DISCONNECT SWITCH.
4. PROVIDE FAN WITH SPEED CONTROLLER. MOUNT SPEED CONTROLLER IN 2X4 METALLIC BOX ADJACENT TO FAN IN CEILING. TEST AND
BALANCE CONTRACTORS SHALL ADJUST FAN PERFORMANCE THROUGH USE OF SPEED CONTROLLER.
5. FAN SHALL BE ECM-DRIVEN. TEST AND BALANCE CONTRACTOR SHALL ADJUST SPEED USING SET SCREW ON FAN CONTROLS. PROVIDE FAN
WITH INTEGRAL GRAVITY BACKDRAFT DAMPER, ALUMINUM GRILLE, AND FACTORY MOUNTED DISCONNECT SWITCH. FAN SHALL RUN
CONTINUOUSLY AND SHALL BE INTERLOCKED WITH BATHROOM LIGHT SWITCH.
M 24X24 22X22 1600 WHITE TITUS 50F 3
L 24X24 22X22 1600 WHITE TITUS 350FLF1 4
EXTERIOR WALL
CAULK / SEAL WEATHER TIGHT
EXHAUST FAN
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING ASHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U genesis engineering
2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.
project #16-014coa #29304
M3.0
MECHANICAL - SCHEDULES AND
DETAILS
CITY OF SARASOTA PUBLIC
WORKS ADMINISTRATION
BUILDING
DECEMBER 1, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
LOCKER RM RENOVATION -
INTERIOR BUILDOUT
21-024
URINAL FOR CONTINUOUS EXHAUST CONTROL.
4. EXHAUST VENTILATION PROVIDED INCLUDES 0.25 CFM/SF FOR LOCKER AREA AND 20 CFM PER SHOWER HEAD FOR SHOWER AREA.
5. NET EXFILTRATION RATE = (OUTSIDE AIR PROVIDED - EXHAUST AIR PROVIDED) / SF AREA.
PLUMBING GENERAL NOTES
SPRINKLER HEAD
FLEXIBLE-CONNECTION
STRAINER WITH
BLOW OFF VALVE
STRAINER
TP
S
RELIEF VALVE
TEMPERATURE AND PRESSURE
RELIEF/SAFETY VALVE
GAS PRESSURE REGULATOR
GAS COCK
SOLENOID VALVE
GLOBE VALVE, ANGLE
THREE WAY CONTROL VALVE
TWO WAY CONTROL VALVE
VALVE IN RISE OR DROP
SWING CHECK VALVE
LIFT CHECK VALVE
GATE VALVE, ANGLE
BALL VALVE
GLOBE VALVE
PLUG VALVE
VALVE (PRV)
BUTTERFLY VALVE
PRESSURE REDUCING
GATE VALVE
(REDUCED PRESSURE ZONE)
WALL CLEAN OUT
CO
WCO
BACKFLOW PREVENTER
WATER HAMMER ARRESTER
CIRCUIT SETTING
BALANCING VALVE
(DOUBLE CHECK VALVE ASSEMBLY)
OPEN SITE DRAIN
ADR
FD
CO
OS
RD
AREA DRAIN
CLEANOUT
FLOOR DRAIN
ROOF DRAIN
CBV
HB
SA
HOSE BIBB
PIPE RISING UP
PIPE DROPPING DOWN
TEMPERATURE TRANSMITTER
PRESSURE TRANSMITTER OR
PRESSURE SWITCH
UNION - SCREWED OR FLANGED
GAUGE WITH GAUGE COCK/
PRESSURE INDICATOR
BACKFLOW PREVENTER
THERMOMETER/TEMPERATURE
PI/GA
TH/TI
PT/PS
INDICATOR
TT
FS
FLOW SWITCH
- GREASE WASTE PIPING (GW) BELOW FLOORGW
AFF
CFH
CO
CONT
CW
DN
DWG
°F
FD
G
GPM
HW
HWC
KW
LBS
NTS
PSI
PVC
SS
SF
V
VTR
- ABOVE FINISH FLOOR
- CUBIC FEET PER HOUR
- CLEANOUT
- CONTINUATION
- DOMESTIC COLD WATER
- DOWN
- DRAWING
- DEGREE FAHRENHEIT
- FLOOR DRAIN
- GAS
- GALLONS PER MINUTE
- DOMESTIC HOT WATER
- DOMESTIC HOT WATER CIRCULATION
- KILOWATT
- POUNDS
- NOT TO SCALE
- POUNDS PER SQUARE INCH
- POLYVINYL CHLORIDE PIPE
- SANITARY SEWER
- SQUARE FEET
- VENT
- VENT THRU ROOF
- DOMESTIC COLD WATER PIPING (CW)
- DOMESTIC HOT WATER PIPING (HW)
- SANITARY SEWER PIPING (SS) ABOVE FLOOR
- SANITARY VENT PIPING (V)
(E) - EXISTING
P-1
BOTTOM-DRAWING# SHOWN ON
- ENLARGED PLAN REFERENCE: TOP-PLAN#,
FCO - FLOOR CLEANOUT
WCO - WALL CLEANOUT
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
- DOMESTIC HOT WATER CIRCULATION PIPING (HWC)
- LOW PRESSURE GAS PIPING (G)G
- MEDIUM PRESSURE GAS PIPING (MG)MG
- POINT OF CONNECTION TO EXISTING
UNO - UNLESS NOTED OTHERWISE
MG - MEDIUM PRESSURE GAS
V
SS
SD - STORM DRAIN
AP - ACCESS PANEL
RPBP - REDUCED PRESSURE BACKFLOW PREVENTER
IE - INVERT ELEVATION
- STORM DRAINSD
- OVERFLOW STORM DRAINOSD
- EXISTING PIPING TO BE REMOVED
PIPING ELEMENTS / VALVING
PLUMBING SYMBOL LEGEND
PLUMBING ABBREVIATIONS
BFF - BELOW FINISHED FLOOR
- STORM DRAIN BELOW FLOORSD
- SANITARY SEWER PIPING (SS) BELOW FLOORSS
A/C - ABOVE CEILING
FLOOR CLEANOUT
- GREASE WASTE PIPING (GW) ABOVE FLOORGW
- PUMP DISCHARGE PIPING (PD) ABOVE FLOORPD
- PUMP DISCHARGE PIPING (PD) BELOW FLOORPD
- CONDENSATE PIPING (CD) ABOVE FLOORCD
- CONDENSATE PIPING (CD) BELOW FLOORCD
- POINT OF DEMOLITION EXTENTS
CD - CONDENSATE DRAIN
OSD - OVERFLOW STORM DRAIN
PD - PUMP DISCHARGE
- FILTERED WATER PIPING (F)F
1. DO NOT SCALE FROM THESE DRAWINGS. EXACT
DIMENSIONS SHALL BE TAKEN FROM ARCHITECTURAL
DRAWINGS.
2. ALL INDICATED WORK SHALL BE PERFORMED BY THE
PLUMBING CONTRACTOR UNLESS OTHERWISE NOTED.
3. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES AND
REGULATIONS INCLUDING BUT NOT LIMITED TO
NATIONAL, CITY, STATE AND LOCAL ORDINANCES
WHICH MAY BE IN EFFECT. ALL PLUMBING MATERIALS,
INSTALLATION PROCEDURES AND SYSTEM LAYOUTS
SHALL BE APPROVED BY ALL APPLICABLE CODE
ENFORCEMENT AUTHORITIES HAVING JURISDICTION,
AND IT SHALL BE THE PLUMBING CONTRACTOR'S
RESPONSIBILITY TO PAY FOR ALL NECESSARY PERMITS
AND APPROVALS FOR THIS INSTALLATION.
4. IT IS THE RESPONSIBILITY OF THE PLUMBING
CONTRACTOR TO REVIEW THESE PLANS AND
SPECIFICATIONS, AS WELL AS THE RELATED HVAC,
FIRE PROTECTION, ELECTRICAL, STRUCTURAL,
ARCHITECTURAL, INTERIOR DECOR AND SITE
ENGINEERING DRAWINGS TO BECOME FAMILIAR WITH
THE FULL PROJECT SCOPE. IN ADDITION, THIS
CONTRACTOR MUST COORDINATE WITH AN OWNER
REPRESENTATIVE TO FULLY UNDERSTAND ALL
REQUIREMENTS WHICH MAY NOT BE SPECIFIED HEREIN
AND WHICH THE OWNER MAY CONSIDER PART OF THIS
CONTRACT. DURING THE COURSE OF CONSTRUCTION
COORDINATION AND ACTUAL CONSTRUCTION, IT IS THE
RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO
WORK CLOSELY WITH ALL ACCOMPANYING
CONTRACTORS AND TRADESMEN IN ORDER TO
ENSURE A SMOOTH RUNNING AND CAREFULLY
COORDINATED INSTALLATION.
5. ANY DISCREPANCIES OR INADEQUACIES WITHIN THESE
BID DOCUMENTS OR BETWEEN THESE BID DOCUMENTS
AND THE RELATED HVAC, FIRE PROTECTION,
ELECTRICAL, STRUCTURAL, ARCHITECTURAL, INTERIOR
DECOR AND SITE ENGINEERING DRAWINGS, OR
BETWEEN THESE BID DOCUMENTS AND FIELD
CONDITIONS MUST BE BROUGHT TO THE ATTENTION
OF THE OWNER, ARCHITECT AND ENGINEER PRIOR TO
BID SUBMISSION.
6. THE PLUMBING CONTRACTOR MUST VISIT THE SITE
AND NOTE ALL EXISTING CONDITIONS AS WELL AS
CONDITIONS TO BE MET PRIOR TO BID SUBMISSION.
LACK OF A THOROUGH UNDERSTANDING OF THE
PROJECT SCOPE AND CONDITIONS SHALL NOT
CONSTITUTE AN EXCUSE FOR ERRORS OR OMISSIONS,
NOR FOR A REQUEST FOR EXTRA COMPENSATION.
7. IT IS CRITICAL THAT THE PLUMBING CONTRACTOR
FIELD VERIFIES ALL EXISTING INVERT ELEVATIONS
PRIOR TO BID SUBMISSION. IF ANY CONFLICTS EXIST
BETWEEN THE NEW PLUMBING SYSTEMS AND THE
EXISTING SITE LEVEL SYSTEMS, THEY SHOULD BE
BROUGHT TO THE ATTENTION OF AN OWNER'S
REPRESENTATIVE AND THE ENGINEER PRIOR TO BID
SUBMISSION. EXTRA COMPENSATION WILL NOT BE
GRANTED FOR ANY EXTRA WORK OR MATERIAL WHICH
RESULTS FROM AN INABILITY TO MEET THE INVERTS OF
THE EXISTING SITE LEVEL PIPING SYSTEMS.
8. THE PLUMBING CONTRACTOR SHALL PROVIDE A
COMPLETE SET OF RECORD "AS-BUILT" DRAWINGS
INDICATING THE PRECISE LOCATION OF ALL SYSTEMS,
EQUIPMENT CONCEALED OR EMBEDDED PIPING, PIPING
CONNECTIONS AND ACCESS DOORS. THESE
DRAWINGS SHALL ALSO INCLUDE ALL CHANGES AND
DEVIATIONS FROM THE BID DOCUMENTS.
9. RUN ALL DOMESTIC WATER, WASTE, VENT AND GAS
PIPING AS HIGH AS POSSIBLE THROUGHOUT THE
ENTIRE BUILDING. INSTALL LONG RUNS OF PIPING
WITHIN STEEL JOIST SPACE AND OTHER PIPING TIGHT
TO BOTTOM OF STEEL. COORDINATE AND VERIFY WITH
OTHER CONTRACTORS AS NOT TO INTERFERE WITH
DUCTWORK, FIRE PROTECTION PIPING, LIGHTING
SYSTEMS, ETC.
10. ALL EXPOSED HORIZONTAL AND VERTICAL PIPING
SHALL BE INSTALLED IN A NEAT ARRANGEMENT IN
LOCATIONS WHICH ARE THE MOST INCONSPICUOUS.
VERTICAL DROPS SHALL BE KEPT TO AN ABSOLUTE
MINIMUM AND THEIR FINAL LOCATIONS SHALL BE
COORDINATED AND RUN WITHIN CHASES, WALLS,
SOFFITS WITH OTHER MECHANICAL/ ELECTRICAL
FEEDS. ALL SUCH LOCATIONS ARE TO BE REVIEWED
WITH AN OWNER REPRESENTATIVE AND ARCHITECT
PRIOR TO INSTALLATION.
11. ALL DOMESTIC WATER BRANCH LINES SHALL HAVE
THEIR OWN RESPECTIVE SHUT-OFF VALVES WHETHER
OR NOT SHOWN ON THE DRAWINGS.
12. DOMESTIC WATER HEATER TEMPERATURE / PRESSURE
RELIEF VALVES SHALL BE PIPED FULL SIZE TO THE
NEAREST APPROVED FLOOR DRAIN. THIS
REQUIREMENT SHALL BE APPLICABLE TO ALL
DOMESTIC WATER HEATING STORAGE VESSELS.
INSTANTANEOUS WATER HEATERS NOT STORING
WATER SHALL NOT REQUIRE TEMPERATURE OR
PRESSURE RELIEF VALVES.
13. THE PLUMBING CONTRACTOR SHALL RUN OUT ALL
BUILDING DRAINAGE AND WASTE LINES WHERE SHOWN
ON THE DRAWINGS AND MAKE ALL CONNECTIONS TO
SITE LEVEL SYSTEMS.
14. ALL EXPOSED PIPING BELOW LAVATORY'S DESIGNATED
AS HANDICAPPED SHALL BE TOTALLY INSULATED.
15. ALL NON-DRAINAGE PIPING SHALL BE RUN LEVEL AND
GENERALLY FREE OF TRAPS AND UNNECESSARY
BENDS, ARRANGED TO CONFORM TO THE BUILDING
REQUIREMENTS AND TO SUIT THE NECESSITIES OF
CLEARANCES FOR OTHER MECHANICAL WORK.
PROVIDE VALVED DRAINAGE OUTLETS IN AREAS OF
PIPING WHICH WOULD BE UNDRAINABLE DURING
MAINTENANCE OR REPAIRS.
16. ALL REQUIRED OFFSETS, RISES AND DROPS DUE TO
POSSIBLE OBSTRUCTIONS OF PIPE RUNS ARE NOT
NECESSARILY SHOWN. PLUMBING CONTRACTOR
SHALL PROVIDE ALL REQUIRED OFFSETS NECESSARY
FOR FINAL COORDINATION WITH OTHER TRADES AND
STRUCTURE.
17. THROUGH PENETRATIONS OF FIRE RESISTANCE RATED
HORIZONTAL ASSEMBLIES SHALL BE PROTECTED BY
AN APPROVED THROUGH- PENETRATION FIRESTOP
SYSTEM INSTALLED AND TESTED IN ACCORDANCE
WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF
WATER (2.49 PA). THE SYSTEM SHALL HAVE AN F
RATING/T RATING OF NOT LESS THAN 1 HOUR BUT NOT
LESS THAN THE REQUIRED RATING OF THE FLOOR
PENETRATED. SEE ARCHITECTURAL DRAWINGS FOR
RATED ASSEMBLY LOCATIONS, RATINGS AND DETAILS.
EXCEPTIONS:
A. FLOOR PENETRATIONS CONTAINED AND LOCATED
WITHIN THE CAVITY OF A WALL ABOVE THE FLOOR OR
BELOW THE FLOOR DO NOT REQUIRE A T RATING.
B. FLOOR PENETRATIONS BY FLOOR DRAINS, TUB
DRAINS OR SHOWER DRAINS CONTAINED AND
LOCATED WITHIN THE CONCEALED SPACE OF A
HORIZONTAL ASSEMBLY DO NOT REQUIRE A T RATING.
18. FLUSH LEVERS FOR ACCESSIBLE WATER CLOSETS
SHALL BE LOCATED ON THE APPROACH SIDE (WIDE
SIDE OF ROOM) OF THE FIXTURE.
19. CLEANOUTS SHALL BE PROVIDED IN ACCORDANCE
WITH LOCAL CODE REQUIREMENTS, INCLUDING AT THE
BASE OF ALL DRAINAGE STACKS.
20. ALL PLUMBING EQUIPMENT, INSULATION, PIPING, ETC.
INSTALLED IN HVAC RETURN AIR PLENUMS SHALL MEET
CODE REQUIREMENTS FOR FLAME SPREAD AND
SMOKE DEVELOPMENT RATINGS (FLAME 25 / SMOKE
50), WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR
UL 273.
21. ALL PLUMBING EQUIPMENT REQUIRING ELECTRICAL
POWER SHALL BE INSTALLED WITH DISCONNECT
SWITCHES AT EACH PIECE OF EQUIPMENT.
COORDINATE SWITCH TYPE (FUSED OR NON-FUSED)
WITH ELECTRICAL DRAWINGS.
22. ALL PLUMBING EQUIPMENT SHALL BE INSTALLED
ACCORDING TO MANUFACTURER'S REQUIREMENTS.
MANUFACTURER RECOMMENDATIONS ARE DEEMED
REQUIREMENTS.
23. WATER PIPING ROUTED ABOVE CEILINGS AND IN
EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE
(UNDERSIDE) OF CEILING INSULATION AND HEATED
SIDE (INSIDE) OF WALL INSULATION. DO NOT INSTALL
PIPING IN LOCATIONS SUBJECT TO FREEZING
CONDITIONS.
24. WATER HAMMER ARRESTORS, SIZED PER PDI, SHALL
BE PROVIDED ON THE SUPPLY PIPING TO EACH QUICK
CLOSING VALVE (E.G. WATER CLOSETS, URINALS,
SENSOR SENSOR OPERATED FAUCETS, ICE MACHINE
SUPPLY BOXES, WATER COOLERS, WASHING MACHINE
SUPPLY BOXES, DISHWASHERS, ETC). ARRESTORS
SHALL BE DOUBLE SEAL PISTON TYPE WITH THREADED
CONNECTIONS, LISTED FOR CONCEALED
INSTALLATIONS WITHOUT ACCESS PANELS.
25. WHERE REQUIRED FOR ACCESS TO VALVES AND
ACCESSORIES ABOVE HARD CEILINGS OR IN WALLS,
ACCESS PANELS SHALL BE PROVIDED BY THIS
CONTRACTOR. PANELS IN RATED ASSEMBLIES SHALL
HAVE LISTED RATINGS EQUAL TO OR GREATER THAN
THE ASSEMBLY THEY ARE INSTALLED IN.
26. ALL VALUE ENGINEERING OR DEVIATIONS FROM THE
CONTRACT DOCUMENTS SHALL BE SUBMITTED IN
WRITING TO THE DESIGN TEAM FOR REVIEW AND
APPROVAL PRIOR TO ACCEPTANCE OR
IMPLEMENTATION. ANY COST INCURRED AS A RESULT
OF ANY DEVIATIONS FROM THE BASIS OF DESIGN
INDICATED IN THE CONTRACT DOCUMENTS (E.G.
PLUMBING MODIFICATIONS TO ACCOMMODATE
ALTERNATE EQUIPMENT SELECTIONS, DESIGN
RELATED EXPENSES FOR REQUIRED DRAWING
MODIFICATIONS, ETC.) SHALL BE SOLE RESPONSIBILITY
OF THE CONTRACTOR. NO INCREASE IN CONTRACT
COST WILL BE GRANTED UNLESS BORNE BY AND
APPROVED IN WRITING BY THE OWNER. CONTRACT
DOCUMENTS ARE DEFINED TO INCLUDE ALL
DISCIPLINES AND DIVISIONS OF THE CONTRACT.
DO NOT SCALE DIMENSIONS FROM THESE
DRAWINGS. WHEN INFORMATION IS NOT CLEARLY
PROVIDED, OBTAIN EXACT INFORMATION FROM
THE ARCHITECT BEFORE PROCEEDING WITH THE
WORK.
THE ARCHITECT IS NOT RESPONSIBLE FOR
CONSTRUCTION THAT IS NOT CARRIED OUT IN
ACCORDANCE WITH THESE CONSTRUCTION
DOCUMENTS. THE ARCHITECT IS NOT
RESPONSIBLE FOR DECISIONS AND
INTERPRETATIONS MADE BY THE CONTRACTOR,
OWNER, OR OTHER PARTIES.
COPYRIGHT 2022 HALL DARLING DESIGN STUDIO,
PA. DRAWINGS AND CONCEPTS MAY NOT BE
USED OR REPRODUCED WITHOUT THE WRITTEN
PERMISSION OF THE ARCHITECT.
GENERAL NOTES
MEPF ENGINEER
coa #29304
ORIGINALS PRINTED AT 24" x 36"
Project No.
Date
Revisions:
Genesis Engineering
2601 CATTLEMEN RD, Suite 501
Sarasota, FL 34232
P: 941.444.2189
SEAL
Hall Darling Design Studio, PA
AR97844
2168 MAIN STREET
Sarasota, FL 34231
P:941.917.0883
ARCHITECT'S STATEMENT
TO THE BEST OF THE ARCHITECT'S
KNOWLWEDGE, SAID PLANS AND SPECIFICATIONS
COMPLY WITH THE APPLICABLE BUILDING CODES
AND APPLICABLE MINIMUM FIRE SAFETY
STANDARDS.
THIS ITEM HAS BEEN ELECTRONICALLY
SIGNED AND SEALED BY ANTHONY LUKASZ,
PE. ON THE DATE ADJACENT TO THE SEAL
USING ASHA AUTHENTICATION CODE.
PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
G
STATE OF
ROL
F A
DI
EL
I C E N S
NAL EN
I
N
P R O F E
S I O
S
E E R
No. 94249
S A
KLNO
H T
N A
Z
Y U genesis engineering
2601 cattlemen rd., ste 501 sarasota, fl 34232 www.geneng.net group, llc.
project #16-014coa #29304
P0.1
PLUMBING - LEGENDS &
GENERAL NOTES
CITY OF SARASOTA PUBLIC
WORKS ADMINISTRATION
BUILDING
DECEMBER 1, 2023
1750 12th STREET
SARASOTA, FLORIDA 34237
LOCKER RM RENOVATION -
PLUMBING SPECIFICATIONS
11. EQUIPMENT CONNECTIONS: CONTRACTOR SHALL FURNISH
ALL REQUIRED VALVES, FITTINGS, VACUUM BREAKERS, TRAPS,
ETC., NECESSARY FOR THE COMPLETE HOOKUP TO PROVIDE
PROPER OPERATION OF EACH PIECE OF EQUIPMENT. IN
CONNECTING TO EQUIPMENT, MANUFACTURER'S
RECOMMENDATIONS AS TO SIZE AND ARRANGEMENT OF
CONNECTIONS SHALL BE FOLLOWED, BUT WITH SIZES SHOWN
ON PLAN BEING FOLLOWED.
12. VALVES: DOMESTIC HOT AND COLD WATER SHUT-OFF VALVES
SHALL BE BRASS QUARTER TURN BALL VALVES WITH INJECTION
MOLDED BRASS THREAD TO CPVC SOLVENT WELD ADAPTERS
AND SHALL BE FULL PORT. PROVIDE BRASS VALVE TAGS WITH
SCHEDULE IDENTIFYING VALVE SERVICE AND LOCATION.
13. INSULATION: PROVIDE PREFORMED FIBERGLASS INSULATION
ON ALL HOT, HOT WATER CIRCULATION AND COLD WATER
PIPING (COLD WATER PIPING TO HAVE VAPOR BARRIER),
VALVES, AND EQUIPMENT. ALL INSULATION, JACKETS,
ADHESIVES, ETC., SHALL HAVE A FLAME SPREAD RATING NOT
OVER 25 AND A SMOKE DEVELOPED RATING NOT OVER 50.
INSULATION 'R' VALUES SHALL BE AS REQUIRED BY PREVAILING
CODES AND ENERGY RELATED STANDARDS.
PROVIDE ELASTOMERIC INSULATION ON ALL CONDENSATE
PIPING, ARMSTRONG AP OR EQUAL.
FINISHES: EXPOSED PIPE INSULATION SHALL BE VINYL COATED
WITH AN EMBOSSED LAMINATE VAPOR BARRIER JACKET. LAPS
AND END STRIPS SHALL BE ADHERED WITH INSULCOUSTIC
IC-225. CONCEALED PIPE INSULATION SHALL HAVE A WHITE
VAPOR BARRIER JACKET SECURED WITH ALUMINUM BANDS.
INSULATED PIPE WITHIN MAIN MECHANICAL ROOMS AND
SIMILAR AREAS THAT IS BELOW 7'-0" SHALL BE PROVIDED WITH
ALUMINUM JACKETS AND BANDS FOR PROTECTION.
INSULATION SUPPORT (TO PREVENT COLLAPSE OF INSULATION)
SHALL BE PROVIDED BETWEEN PIPING AND PIPE HANGING
SHIELDS. RIGID POLYURETHANE FOAM OR NATURAL CORK
INSERTS MAY BE USED FOR SUPPORT. ALL PIPE SUPPORT
APPARATUS MUST BE MOUNTED ON THE OUTSIDE OF ALL
INSULATION.
INSULATION FOR DOMESTIC WATER PIPING SHALL BE
1"THICKNESS FOR 2" AND SMALLER PIPING AND 1-1/2"
THICKNESS FOR 2-1/2" AND LARGER PIPING.
INSULATION FOR STORM WATER AND CONDENSATE PIPING
SHALL BE 3/4" THICKNESS.
PROVIDE PREFORMED INSULATION GUARDS ON ALL EXPOSED
PLUMBING ELEMENTS UNDER ADA COMPLIANT LAVS AND SINKS
AS REQUIRED BY ADA REQUIREMENTS, TRUEBRO OR EQUAL.
14. PIPING IDENTIFICATION: ALL PIPING SHALL BE IDENTIFIED WITH
SEMI-RIGID PLASTIC PRESSURE-SENSITIVE IDENTIFICATION
MARKERS (NOTE PRESSURE-SENSITIVE VINYL PIPE MARKERS
WILL NOT BE ACCEPTED). DIRECTION OF FLOW ARROWS ARE
TO BE INCLUDED ON EACH MARKER AND SHALL BE IN
CONFORMANCE WITH "SCHEME FOR THE…