ITB_25-021_Final_S&S_Plans_2024-11-06_.PDF
PDF 13 MB Posted
- Attached to
- Crystal River Airport (CGC) Fuel Farm Project
- Solicitation number
- ITB 25-021
- Issued by
- Citrus County, Florida
About this file
The provided file is a comprehensive set of mechanical and electrical engineering drawings for the Aviation Fuel Farm Replacement Project at Crystal River Airport (KCGC) in Citrus County, Florida. The project involves a complete replacement of the existing fuel farm infrastructure, including the removal and installation of two 12,000-gallon aboveground storage tanks (one for Jet A and one for AVGAS), associated pumps, filters, piping, electrical systems, and supporting infrastructure. The project is funded by the Florida Department of Transportation (FDOT) under Project Number 22-154 and is advertised through Invitation to Bid (ITB) #25-021.
The project encompasses extensive technical specifications for mechanical and electrical systems, including a new electrical service with a 30kW Generac generator, automatic transfer switch, site lighting, emergency fuel shut-off (EFSO) systems, ground verification systems, and comprehensive grounding infrastructure. The drawings detail precise technical requirements for tank installation, piping configurations, electrical connections, and safety systems, with specific attention to compliance with NFPA, NEC, and other relevant safety standards. The project will require a contractor to provide all labor, materials, engineering, and installation services to completely replace the existing fuel farm infrastructure while maintaining operational standards for airport fuel handling and distribution.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS
C O
V E
R
IN
D
E X
D R
A W
IN
G
C&I-1
DRAWING INDEX
C&I - 1 COVER & INDEX DRAWING
G - 1 MECHANICAL LEGEND, ABBREVIATIONS & SYMBOLS
G - 2 GENERAL PROJECT NOTES
G - 3 MECHANICAL MAJOR EQUIPMENT SCHEDULES
G - 4 DEMOLITION PLAN
G - 5 SITE PLAN
G - 6 SITE ELEVATIONS
M - 1 MECHANICAL TANK FARM LAYOUT PLAN
M - 2 MECHANICAL TANK & EQUIPMENT PLAN
M - 3 MECHANICAL EQUIPMENT DETAILS
M - 4 MECHANICAL EQUIPMENT SECTIONS
M - 5 MECHANICAL DETAILS
M - 6 MECHANICAL DETAILS
M - 7 MECHANICAL ISOMETRIC
M - 8 MECHANICAL DETAILS
M - 9 MECHANICAL SIGNAGE
AVIATION FUEL FARM REPLACEMENT
FOR
CITRUS COUNTY TECHNICAL SERVICES
CRYSTAL RIVER AIRPORT (KCGC)
CRYSTAL RIVER, FLORIDA
PROJECT FUNDING: (FDOT)
PROJECT NUMBER 22-154
ITB# 25-021
BID SET
CRYSTAL RIVER AIRPORT
718 N LINDBERG TER
CRYSTAL RIVER, FL 34429
(352) 795-6868
AVIATION FUEL FARM
REPLACEMENT SITE
U S
H W
Y
DRAWING INDEX
E - 1 ELECTRICAL LEAD - IN SHEET
E - 2 ELECTRICAL SITE PLAN
E - 3 ELECTRICAL POWER PLAN
E - 4 ELECTRICAL SCHEDULES & DETAILS
E - 5 ELECTRICAL CONTROLS
E - 6 ELECTRICAL DETAILS
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR
THE FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004‚ F.A.C.
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
)3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR
THE FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004‚ F.A.C.
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY RHETT R. JACKSON, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
AutoCAD SHX Text N
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION DESCRIPTION
AutoCAD SHX Text
BY
AutoCAD SHX Text
SYMBOL
Rhett Jackson RRJ Digital Seal_FL2
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L L
E G
E N
D
A B
B R
E V
IA
T
IO
N
S
S Y
M B
O L
S
G-1
NEW FUEL PIPE
VALVE
REDUCER
ELBOW DOWN
BALL VALVE
LEGEND ABBREVIATIONS
APPROX.
BFV
BLDG.
B.O.P.
COMM.
C
CLR.
CONT.
DET.
DIA. Ø
DWG.
EA.
E.F.
ELEC.
ELL.
EXIST.
FLG.
GALV.
HPV
I.D.
I.E.
JFP
LPD
MAX.
MECH.
MH.
MIN.
MNPT.
N.
NPT.
NTS
PAVMT.
PL.
R/C
APPROXIMATE
BUTTERFLY VALVE
BUILDING
BOTTOM OF PIPE
COMMUNICATION
CENTER LINE
CLEARANCE
CONTINUOUS
DETAIL
DIAMETER
DRAWING
EACH
EACH FACE
ELECTRICAL
ELBOW
EXISTING
FLANGE
GALVANIZED
HIGH POINT VENT
IDENTIFICATION
INVERT ELEVATION
JET-A FUEL PIPE
LOW POINT DRAIN
MAXIMUM
MECHANICAL
MANHOLE
MINIMUM
MALE NATIONAL PIPE THREAD
NORTH
NATIONAL PIPE THREAD
NOT TO SCALE
PAVEMENT
RELAXATION CHAMBER
PLATE
FUEL PIPE
EXPLOSION PROOF
WELD NECK FLANGE
WITHOUT
WITH
UNDERGROUND
TYPICAL
TOP OF PIPE
THICK
THREADED
TEMPORARY
STEEL
SHEET
STORM DRAIN
SCHEDULE
SANITARY
REQUIRED
REINFORCED
REFERENCE
REDUCER
XP.
WNF.
W/O
W/
U.G.
TYP.
T.O.P.
THK.
THD.
TEMP.
STL.
SHT.
SD.
SCH.
SAN.
REQ'D.
REINF.
REF.
RED.
STRUCT. STRUCTURE
VERT. VERTICAL
L
L.
O.C.
F.S.
E.W.
STA.
EACH WAY
FIRE SAFE
LONG
ON CENTER
STATION
CONC. CONCRETE
I.F. INSULATING FLANGE
NC. NORMALLY CLOSED
FNPT. FEMALE NATIONAL PIPE THREAD
DN. DOWN
A.O.A. AIR OPERATIONS AREA
ABOVE GROUNDA.G.
MOTOR GASOLINEMOGAS
NIC. NOT IN CONTRACT
BF BLIND FLANGE
LT. LEFT
RT. RIGHT
GAL. GALLON
PSI POUND PER SQUARE INCH
CHECK VALVE
OR
BUTTERFLY VALVEOR
F.E. FIRE EXTINGUISHER
ECC. ECCENTRIC
DIM. DIMENSION
FUEL
TANKER
F.O.T. FLAT ON TOP
ELBOW UP
ABOVE FINISHED PAVEMENTAFP.
AUTOMATIC AIR VENTAAV
AIR ELIMINATORA/E
CV CONTROL VALVE
EQ. EQUAL
FM FLOW METER
F/S FILTER SEPARATOR
OTRTT OVER THE ROAD TRANSPORT TRUCK
PIV. POST INDICATOR VALVE
TRV THERMAL RELIEF VALVE
VA. VALVE
FSP FUEL SAMPLING PROBE
CON. CONCENTRIC
SURGE SUPPRESSORSS
AST ABOVEGROUND STORAGE TANK
AVGAS AVIATION GASOLINE
ED. EDITION
EL. ELEVATION
EFSO EMERGENCY FUEL SHUT OFF
FLEX FLEXIBLE
GA. GAUGE
LB. POUND
QTY. QUANTITY
PS PIPE SUPPORT
SQUARESQ.
WELDED WIRE FABRICWWF.
WATERWTR.
ADDITIIONALADD'L
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
G E
N E
R A
L
PR
O
JE
C T
N O
T E
S
G-2
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L M
A
JO
R E
Q U
IP
M
E N
T
SC
H E
D U
L E
G-3
DEMOLITION PLAN
SCALE:
EXIST 24" x 24" SUMP WITH
BAR GRATING
EXIST CONTAINMENT
CURB AND AST SLAB
(6" WIDE x 12" HIGH CURB
FROM AST SLAB) 30
'-1 0"
46'-3"
3' -7
15'-0"
'-0
'-0
EXIST 8" WIDE CURB SLOPES
DOWN WITH RAMP, BOTH
SIDES OF DRIVEWAY
SLOPE
SLOPE
3' -7
EXIST DRAIN VALVES,
TYP OF 5
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
D E
M O
L
IT
IO
N
PL
A
N
G-4
NOTES:
1. REMOVE FUEL FROM EXIST ASTs AND TRANSFER TO REFFUELERS.
2. COMMENCE WITH DEMOLITION OF EXISTING FUEL FACILITY.
3. RELOCATE AST SUMP COLLECTORS TO NEW FUEL FACILITY.
RELOCATE EXISTING 17 GAL.
AST SUMP COLLECTORS
CONNECT
AAVs & TRVs
18"x18"x12" TYP.
36" HIGH
TYP.
REMOVE EXIST JET A AST
12,000 GAL.
REMOVE EXIST AVGAS AST
12,000 GAL.
REMOVE EXIST JET A
PUMP & EQUIPMENT
REMOVE EXIST AVGAS
PUMP & EQUIPMENT
EXIST 8" WIDE CURB
BOTH SIDES OF DRIVEWAY
EXIST 12" WIDE x 8" HIGH
DRIVE-OVER CURB
END OF DRIVEWAY
CONNECT
AAVs & TRVs
EXIST AVGAS TANK AND EQUIPMENT EXIST JET A TANK AND EQUIPMENT EXIST JET A CABINET
(TYPICAL)
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
SI
T
E P
L A
N
G-5
U S
H W
U S
H W
GODFREY LN
N L
IN
D
BE
R
G T
ER
N LINDBERG TER
U S
H W
LANDSIDE GATE
AIRSIDE GATE
AIRSIDE GATE
CONTRACTOR
STAGING AREA
APPROXIMATELY
55' x 100'
PROJECT AREA
APPROXIMATELY
55' x 45'
CONTRACTOR'S ACCESS ROUTE
U S
H W
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
SI
T
E E
L E
V A
T
IO
N S
G-6
EXIST
EXIST
SEE NOTE 24 ON DWG G-2.
FUEL FARM LAYOUT PLAN
EXIST 24" x 24" SUMP WITH
BAR GRATING
EXIST CONTAINMENT
CURB AND AST SLAB
(6" WIDE x 12" HIGH CURB
FROM AST SLAB)
'-1
0"
46'-3"
3' -7
15'-0"
'-0
'-0
EXIST 12" WIDE x 8" HIGH
DRIVE-OVER CURB
END OF DRIVEWAY
EXIST 8" WIDE CURB
BOTH EAST & WEST SIDES
OF DRIVEWAY
EXIST 8" WIDE CURB SLOPES
DOWN WITH RAMP, BOTH
EAST & WEST SIDES OF
DRIVEWAY
NEW AST 2 AVGAS 12,000 GAL
ABOVEGROUND STORAGE TANK
ON STEEL SKID, 10'Ø x 20'-6" LONG
NEW AST 1 JET A 12,000 GAL
ABOVEGROUND STORAGE TANK
ON STEEL SKID, 10'Ø x 20'-6" LONG
EXISTING AVGAS CURBED
EQUIPMENT PAD
SLOPE
SLOPE
3' -7
5'-0" 10'-0"Ø 3'-4"
10'-0"Ø
5' -2
5'
-2
17'-11"
(15'-0" CLR REQ'D)
31'-3"
(25'-0" CLR REQ'D)
PROVIDE PIPE CAPS AND
REMOVE EXIST DRAIN VALVES,
TYP OF 4
NEW PIV
NEW ELEVATED PUMP
PLATFORM (6'-0" HIGH
TOP OF AST SLAB TO
TOP OF PUMP
PLATFORM), TYP OF 2
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L
FU
E L
F A
R M
L A
Y O
U T
P L
A N
M-1
EXISTING JET A CURB
EQUIPMENT PAD
NEW LADDER WITH CAGE AND SAFETY CLIMB
NEW LADDER WITH CAGE AND SAFETY CLIMB
RELOCATED JET A
SUMP COLLECTOR
NEW SCULLY UNIT
NOTE:
THE CONTRACTOR TO PROVIDE THE DESIGN FOR ALL FOUNDATIONS, PLATFORMS AND STAIRS
CONFORMING TO ALL APPLICABLE CODES AND OSHA REQUIREMENTS. SUBMIT DESIGN AND
SHOP DRAWINGS SIGNED AND SEALED BY A STATE OF FLORIDA PROFESSIONAL ENGINEER.
15'-8"
NEW AVGAS REMOTE SELF
SERVICE DISPENSER.
PROVIDE CONCRETE SLAB
UNDERNEATH.
NEW 6"Ø BOLLARD, TYP OF 9.
SEE DETAIL 1/M-9
A M4
A
B M4
B
TOP OF NEW TANK WITH
ANTISKID COATING AND HANDRAILS,
TYPICAL BOTH TANKS
RELOCATED AVGAS
SUMP COLLECTOR
NEW GROUND REEL
NEW SCULLY UNIT
NEW GROUND REEL
NEW 1 1/2" AVGAS
ABOVEGROUND PIPING
NEW STAIR OVER FUEL PIPING
W/ STAIR FOOTING
NEW STAIR OVER FUEL PIPING
W/ STAIR FOOTING
HAND RAILS AROUND NORTH,
SOUTH & EAST SIDES OF AST 1
& AST 2 OF ANTISKID TOP
SURFACE
NEW STAIR TO
ELEVATED PUMP
PLATFORM W/
STAIR FOOTING
PIV
PIPE SUPPORT
SEE DWG M-5
REPAINT TOP OF CURB SAFETY YELLOW
PROVIDE CONCRETE COATING PER SPECIFICATIONS
PROVIDE CONCRETE
COATING PER
SPECIFICATIONS
FUEL FARM PLAN
NEW AVGAS CURBED
EQUIPMENT PAD
REFER TO DETAIL D/M-4
3"Ø ISSUE & SUCTION PIPING
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L
FU
E L
F A
R M
PL
A
N
M-2
NEW 6"Ø BOLLARDS, SEE DETAIL 1/M-9
NEW STAIR TO
ELEVATED PUMP
PLATFORM W/ STAIR
FOOTING
NEW AVGAS REMOTE SELF SERVICE DISPENSER
KEYED NOTES ( NOTES 1 - 16 AND 25 TYPICAL FOR BOTH TANKS #1 AND #2, EXCEPT AS NOTED:
1 4"X2" FILL FLANGE ON TOP ℄ WITH 3" BFV EXTERNAL, DROP TUBE INTERNAL (TERMINATE 6" ABOVE AST
BOTTOM AND ATTACH TO TANK BOTTOM BRACKET). PROVIDE 2" REMOTE PRESSURE FILL CUT-OFF FLOAT
SET AT 95% TANK CAPACITY INTERNAL. PROVIDE ANTI-SIPHON DEVICE. SEE DET 2/M-6
2 AVGAS - 8" SUCTION FLANGE ON TOP ℄ WITH 3" EXTERNAL BFV, DROP TUBE INTERNAL (TERMINATE 6" ABOVE AST BOTTOM). PROVIDE 3" FOOT VALVE. PROVIDE ANTISYPHON DEVICE. SUBMIT SHOP DRAWINGS FOR
APPROVAL.
2A JET A - 3" SUCTION FLANGE ON TOP ℄ WITH 3" EXTERNAL BFV, INTERNAL FLOATING SUCTION, RETENTION CABLE AND EXTERNAL TARGET INDICATOR. PROVIDE ANTISYPHON DEVICE. SUBMIT SHOP DRAWINGS FOR
APPROVAL.
2B INTERNAL FLOATING SUCTION. PROVIDE SUPPORTS TO MAINTAIN INLET 1'-6" ABOVE AST BOTTOM WHEN SUCTION PIPE IS IN DOWN POSITION. PROVIDE PIVOTED FLOATING SUCTION FLOAT ASSEMBLY: 10 GA.
ROLLED STEEL PLATE, WITH 3/4" DIA. 3000LB., TEST PLUGS AND COUPLINGS. PROVIDE FLOATS AS REQ'D TO ENSURE FLOTATION OF SUCTION PIPE IN JET FUEL, WITH MEANS TO COMPENSATE FOR INCREASED BUOYANCY FORCE OF WATER DURING HYDROSTATIC TEST. INDICATE MINIMUM AND MAXIMUM INLET SUBMERGENCE VS FLOATING SUCTION PIPE ANGLE. SUBMIT CALCULATIONS. PROVIDE SUCTION INLET WITH
ANTIVORTEX PLATE DESIGN FOR MAX. VELOCITY
3.5 FPS AT 130 GPM.
2C SUCTION PIPE RETENTION CABLE. 5/16" DIA. - TYPE 316 S.S. COIL-PROOF CABLE, SHALL LIMIT FLOATING SUCTION TRAVEL TO 60°. CONNECT TO UNDERSIDE OF FLOATING SUCTION. ATTACHCABLE WITH CAMPS TO
2'-6" SQ X 3/8" THK. STEEL PLATE CONTINUOUS WELD TO AST BOTTOM.
2D EXTERNAL SUCTION TARGET INDICATOR. 3/16" DIA. - TYPE 316 S.S. COIL-PROOF NONSPARKING CABLE WITH SWIVEL SHEAVES. CONNECT TO UNDERSIDE OF FLOATING SUCTION. CABLE SHALL NOT CONTACT TANK INTERNALS. PROVIDE EXTERNAL CABLE GUIDES AT TANK ROOF. PROVIDE SUPPORT BRACKETS AND TANK SHELL. PROVIDE TARGET PLATE RIGGED TO RISE AND FALL WITH OF FLOATING SUCTION POSITION. PROVIDE
1-1/2" NOZZLE FOR EXTERNAL SUCTION TARGET INDICATOR 1-1/2" 3000LB COUPLING.
3 3" VENT FLANGE ON TOP ℄ WITH VENT STACK (16'-0" AFP). PROVIDE PRESSURE/VACUUM VENT CAP
EXTERNAL.
4 8" EMERGENCY VENT FLANGE ON TOP ℄ (MAIN TANK VESSEL). PROVIDE EMERGENCY VENT EXTERNAL.
5 8" EMERGENCY VENT FLANGE ON TOP ℄ (SECONDARY CONTAINMENT). PROVIDE EMERGENCY VENT
EXTERNAL.
6 3" GAUGE HATCH FLANGE ON TOP ℄ WITH 1/4" THICK STRIKER PLATE ON TANK BOTTOM INTERNAL. PROVIDE SLOTTED DROP TUBE. INTERNAL TERMINATE 3" ABOVE AST BOTTOM AND SELF CLOSING HATCH EXTERNAL.
7 24" MANHOLES ON TOP ℄
8 4" LEVEL ALARM FLANGE ON TOP ℄ SET ALARM AT 90% TANK CAPACITY. (VISUAL AND AUDIBLE) SET PUMP CUT-OFF AT 95% TANK CAPACITY. SET LOW SUCTION CUT-OFF AT 2' -0" ABOVE AST BOTTOM.
9 3" DRAIN PUMP FLANGE ON TOP ℄ WITH DRAIN PUMP AND DROP TUBE. TERMINATE 2" ABOVE AST BOTTOM.
10 2" INTERSTITIAL MONITOR ON TOP ℄. CONNECT TO ALARM.
11 GROUNDING TABS ON VESSEL SIDE BOTTOM (QTY. 4). CONNECT TO GROUNDING GRID.
12 NEW STAIRS, PLATFORM AND HANDRAILS.
13 PRESSURE TEST CERTIFICATE 3 PSI FOR 1 HOUR, INTERNAL VESSEL AND SECONDARY CONTAINMENT.
14 LINE TANK INTERIOR WITH FUEL RESISTANT EPOXY "INTERLINE 850" (MANUFACTURER). COAT ASTs &
EQUIPMENT PER SPECIFICATIONS.
15 UL142 & UL2085, DOUBLE WALLED, 20,000 GALLON CAPACITY SKID-MOUNTED AS SPECIFIED 10'-0"Ø X 20'-6"L.
LABEL PRODUCT & TANK # ON TANK HEADS. COAT TANK INTERIOR AND EXTERIOR (MANUFACTURER).
16 NFPA 704 DECAL.
17 SIGNAGE - "EFSO" INSTRUCTIONS AND EFSO STATION. SEE DWG M-9 .
18 SIGNAGE - "NO SMOKING". SEE DWG M-9.
19 SIGNAGE - TANK STRAPPING CHART. EMERGENCY PROCEDURES
AND TELEPHONE NUMBERS. SEE DWG M-9.
20 SIGNAGE - "VALVE INSTRUCTIONS (LOAD/OFFLOAD)". SEE DWG M-9.
21 SIGNAGE - "AVGAS TANK #2 FILL". SEE DWG M-9.
22 SIGNAGE - "AVGAS TANK #2 SUCTION". SEE DWG M-9.
23 SIGNAGE - "JET A TANK #1 FILL". SEE DWG M-9.
24 SIGNAGE - "JET A TANK #1 SUCTION". SEE DWG M-9.
25 SIGNAGE - "FIRE EXTINGUISHER". PROVIDE NEW FIRE EXTINGUISHER
SEE DWG M-9.
26 SIGNAGE - "AVGAS VAPOR RECOVERY". SEE DWG M-9.
27 3" VAPOR RECOVERY FLANGE ON TOP ℄ WITH 3" BFV EXTERNAL.
28 PAINT EXTERIOR OF NEW PIPING AND EQUIPMENT. PAINT FLOW
DIRECTION ARROWS ON PIPES.
29 AVGAS REMOTE SELF SERVICE DISPENSER. SEE DETAIL E/M-4.
30 SIGNAGE - "AVGAS AST". SEE DETAIL 5/M-8.
31 SIGNAGE - "JET A AST". SEE DETAIL 6/M-8.
TRV
17 25
150# REFER TO SPEC
SECTION FS 231505
EQUIPMENT
31 13 14 15 16 18 19
30 13 14 15 16 18 19
10 1111 10 1111
1111 1111
2D
2A
2C
NEW AST 2 AVGAS 12,000 GAL
ABOVEGROUND STORAGE TANK
ON STEEL SKID, 10'Ø x 20'-6" LONG
NEW AST 1 JET A 12,000 GAL
ABOVEGROUND STORAGE TANK
ON STEEL SKID, 10'Ø x 20'-6" LONG
30 13 14 15 16
31 13 14 15 16
NEW LADDER WITH CAGE
AND SAFETY CLIMB
NEW LADDER WITH CAGE
AND SAFETY CLIMB
6'-0"
NEW STAIR OVER FUEL
PIPING W/ STAIR FOOTING
HAND RAILS AROUND NORTH,
SOUTH & EAST SIDES OF AST 1
& AST 2 OF ANTISKID TOP
SURFACE
NEW JET A CURBED
EQUIPMENT PAD
REFER TO DETAIL C/M-4
3"Ø ISSUE & SUCTION PIPING
1-1/2" BALL VALVE
1-1/2" AVGAS
ABOVEGROUND PIPING
HPV & LPD
AAV
AAV & TRV
TRV
HPV & LPD
AAV
HPV
LPD
HPV
HPV & LPD
AAV
TRV
HPV
FSP
LPD
HPV
AAV
LPD
HPV
LPD
TRV
AAV
AAV & TRV
HPV & LPD
AAV & TRV
HPV & LPD
HPV & LPD
AAV
TRV
HPV
AAV
TRV
HPV
LPD
LPD
FSP
POST
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L E
Q U
IP
M
E N
T D
E T
A
IL
S
M-3
AVGAS CURBED EQUIPMENT
PAD PLAN
SCALE:
M-3
JET A CURBED EQUIPMENT
PAD PLAN
SCALE:
M-3
SCULLY UNIT
NOTES:
1. AVGAS & JET A EQUIPMENT PADS ARE
SEPARATED FOR GRAPHIC CLARITY. REFER TO
LAYOUT PLAN DWG M-1 & M-2 FOR LOCATIONS.
2. AVGAS & JET A PIPING DIAGRAMS ON DWG M-7.
GROUND REEL, SEE DET 1/M-6. REFER TO
ELECTRICAL DWGS FOR ADD'L GROUND
VERIFICATION UNIT.
3" SWIVEL AND 4"x3" REDUCER
3" BFV TRV
3" CHECK VALVE AND
SURGE SUPPRESSOR
3" BFV
2-3" 90° ELLS
TRV2-3" 45° ELLS
PS-CFLEX CONN.
PS-C
FLEX CONN.
2-3" 90° ELLS
3" BASKET STRAINER
JET A LOAD/OFFLOAD PUMP
PS-C
3" JET A FROM AST #1 SUCTION
PUMP AIR RELEASE W/
AAV CHECK VALVE
3" JET A FROM AST #1 FILL
3" TEE
FLEX CONN.
PS-C
3" BFV
RELOCATED JET A
SUMP COLLECTOR
SEE DWG G-4
TRV
3" CONTROL VALVE, FM, AND A/E.
CONTROL VALVE HYDRAULIC SIGNAL
FROM FM AND A/E
PS-C2- 3" 45° ELLS
3" SWIVEL
2-3" 90° ELLS
RELAXATION VESSEL
PUMP FLOW SWITCH
CONTROL VALVE HYDRAULIC SIGNAL
FROM F/S FLOAT CONTROL
CONTROL VALVE HYDRAULIC SIGNAL
FROM F/S FLOAT CONTROL
3"x2-1/2" REFUELER TRUCK NOZZLE 3"x12' LOAD HOSE, SEE DET 4/M-5
DEADMAN SWITCH (HYDRAULIC)
PROVIDE POST ON TOP OF THE
CONCRETE SLAB
4" OVER THE ROAD
TRANSPORT TRUCK NOZZLE
4"x12' OFFLOAD HOSE, SEE DET 4/M-5
3" TEE
CURBED EQUIPMENT PAD
F/S
SCULLY UNIT
GROUND REEL, SEE DET 1/M-6. REFER TO
ELECTRICAL DWGS FOR ADD'L GROUND
VERIFICATION UNIT.
3" SWIVEL AND 4"x3" REDUCER
2-3" 45° ELLS
TRV
3" CHECK VALVE AND
SURGE SUPPRESSOR
3" BFV
2-3" 90° ELL
TRV
PS-CFLEX CONN.
PS-C
4-3" 90° ELLS
3" BASKET STRAINER
AVGAS LOAD/OFFLOAD PUMP
3" AVGAS FROM AST #2 SUCTION
3" TEE
PS-C
3" BFVRELOCATED AVGAS SUMP COLLECTOR
SEE DWG G-4
TRV
3" CONTROL VALVE, FM, AND A/E.
CONTROL VALVE HYDRAULIC SIGNAL
FROM FM AND A/E
1-1/2" 90° ELL, PIT W/ 1-1/2" BV & I.F. KIT
2- 3" 90° ELLS3" SWIVEL 2-1-1/2" 90° ELLS
CONTROL VALVE HYDRAULIC SIGNAL
FROM FILTER FLOAT CONTROL
3"x2-1/2" REFUELER TRUCK NOZZLE 3"x12' LOAD HOSE, SEE DET 4/M-5
DEADMAN SWITCH (HYDRAULIC)
PROVIDE POST ON TOP OF THE CONCRETE SLAB
4" OVER THE ROAD
TRANSPORT TRUCK NOZZLE
4"x12' OFFLOAD HOSE, SEE DET 4/M-5
3" TEE
CURBED EQUIPMENT PAD
FILTER
3" AVGAS FROM AST #2 FILL
3" AVGAS FROM AST #2 VAPOR RECOVERY
PUMP AIR RELEASE W/ AAV CHECK VALVE
FLEX CONN.
PS-C
3" VAPOR OFFLOAD CONN. W/2-3" 90° ELLS
PUMP FLOW SWITCH
PS-C
1-1/2" FROM AVGAS
SELF SERVE DISPENSER
1-1/2" BALL VALVE W/ 3"x1-1/2" REDUCER
3" TEE
2-3" 90° ELLS
2-3" 90° ELLS
PROVIDE FIRE EXTINGUISHER
SEE DWG M-9
TANK SECTION B-B
M-4
NEW 12,000
GALLON TANK
TYP AST 1 & AST 2
TANK SKIDS OR
SADDLES AS
REQ. PER MFR.
EXIST CONC. SLAB (TYP.)
WITH NEW PROTECTIVE COATINGS
PROVIDE SHIM UNDER SKIDS TO MAINTAIN
CONTAINMENT FLOOR SLOPE TO DRAIN
WATER TO TRENCH DRAIN. (TYP.)
10' Ø INNER DIA.
10' Ø INNER DIA.
JET A
ABOVE
STORAGE
TANK 1
AVGAS
ABOVE
STORAGE
TANK 2
TOP OF SLAB
EL.= 5.0 6'
-0
TOP OF SLAB
EL.=5.0
SCALE:
TOP OF PUMP
PLATFORM12
TANK SECTION A-A
M-4
20'-6" INNER
LENGTH
SCALE:
AVGAS LOAD / OFFLOAD
SECTION D
M-4
JET A LOAD / OFFLOAD
SECTION C
M-4 SCALE:SCALE:
METER SUPPORT (BEYOND)
SEE DET 8/M-5
4'-0"
PUMP PAD
FOUNDATION
SEE NOTE 23 ON
DWG G-2
6' -0
3'-4" 5'-0" 46'-3"
3 2D 1091
6 7
2A2B2C
PUMP
PLATFORM 12
JET A PUMP CONCRETE
FOUNDATION
INTERNAL
STRIKER
PLATE
AVGAS
PUMP CONCRETE
FOUNDATION
TOP
OF
SLAB
AST
SKIDS
JET A AST-1
SLOPE 1"/ 20'
NEW LADDER
WITH CAGE
AND SAFETY
CLIMB
RELAXATION CHAMBER
SEE DET 10/M-5SURGE SUPPRESSOR
FILTER SEPARATOR
SEE DET 9/M-5 & 3/M-6
LOAD HOSE
OFFLOAD HOSE
TOP
OF
SLAB
HOSE RACK
SEE DET 4/M-5
JET A PUMP
SURGE SUPPRESSOR
FILTER
SEE DET 9/M-5 & 3/M-6
LOAD HOSE
OFFLOAD HOSE
TOP
OF
SLAB
METER SUPPORT (BEYOND)
SEE DET 8/M-5
HOSE RACK
SEE DET 4/M-5
AVGAS PUMP
VAPOR RECOVERY
HANDRAILS AROUND NORTH, SOUTH, EAST
SIDES OF AST 1 & AST 2 OF ANTISKID TOP
26 23
11 11
'-0
HANDRAILS AROUND NORTH, SOUTH, EAST
SIDES OF AST 1 & AST 2 OF ANTISKID TOP
31 13 30 13
18 19
18 19
11 11 11 11
NEW STAIRS OVER
FUEL PIPES
PROVIDE
PUMP PAD
25 25
NEW REMOTE SELF SERVICE
DISPENSER E
M-4SCALE: NOT TO SCALE
NOTE:
REFER TO SPECIFICATION SECTION FS 231505 EQUIPMENT FOR DISPENSER.
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L E
Q U
IP
M
E N
T
SE
C T
IO
N
M-4
AVGAS FILTER & JET A
FILTER SEPARATOR DETAIL
SCALE: NTS
M-5
RELAXATION CHAMBER
DETAIL
SCALE: NTS
M-5
S
3/4"Ø 3/4"Ø
TRV
SEE DET 6/M-9
AAV
SEE DET 8/M-9
INSTALL FLOAT CONTROL
CONNECT TO CV
SEE DET 4/M-6 & DWG M-7
FOR DRAIN PIPING DIAGRAM
ANCHOR BOLT TO SLAB
(TYP 4)
EQUIPMENT SLAB
ANCHOR BOLT TO SLAB
(TYP 4)
EQUIPMENT SLAB
SUMP DRAIN W/ SPRING
LOADED VALVE
1-1/2"Ø DRAIN LINE
HIGH POINT VENT (HPV)
DETAIL
SCALE: NTS
M-5
ABOVEGROUND LOW POINT
DRAIN (LPD) DETAIL
SCALE: NTS
M-5
TYPICAL BUTTERFLY VALVE
(BFV) INSTALLATION DETAIL
SCALE: NTS
M-5
HOSE RACK DETAIL
SCALE: NTS
M-5
PIPE SUPPORT (PS-A) DETAIL
SCALE: NTS
M-5
PIPE SUPPORT (PS-B) DETAIL
SCALE: NTS
M-5
METER SUPPORT DETAIL
SCALE: NTS
M-5
PIPE SUPPORT (PS-C) DETAIL
SCALE: NTS
M-5
PIPE SUPPORT SPACING
SCHEDULE
SUPPORT PIPES AT LOCATIONS INDICATED.
MAXIMUM SPACING OF SUPPORTS IS BASED ON
PIPE SIZE AND SHALL BE AS FOLLOWS:
NOMINAL PIPE
SIZE
MAXIMUM
SPACING
1 1/2" 9'-0" 2" 10'-0" 3" 12'-0" 4" 14'-0"
2" SOCKET WELD
BALL VALVE
2"Ø SOCKET
WELD NIPPLE
DRY DISCONNECT
AND CAP,
COORDINATE W/
THE SYSTEM
OPERATOR FOR
SIZE AND TYPE.
2" SOCKET WELD
BRANCH
CONNECTION
FUEL PIPE
B.O.P.
FUEL PIPE
B.O.P.
2"Ø SOCKET WELD NIPPLE
2" SOCKET WELD BRANCH
CONNECTION
2" SOCKET WELD
BALL VALVE
DRY DISCONNECT
AND CAP,
COORDINATE W/
THE SYSTEM
OPERATOR FOR
SIZE AND TYPE.
DIRECTION
OF FLOW
OPEN
CLOSED
FUEL PIPE
BFV
DISC IS SHOWN IN
CLOSED POSITION.
OPEN DISC AS
INDICATED. WELD NECK FLANGES
DISC SHAFT
IN VERTICAL
PROVIDE ADEQUATE CLEARANCE IN EACH
DIRECTION TO PERMIT OPERATION OF
GEAR OPERATOR HANDLE.
14'-0" 2'-0"
EQ. SPACE EQ. SPACE EQ. SPACE
TOP OF
CHANNEL LEG
BOTTOM OF
HOSE CHANNEL
AND END PLATE
TO BE EVEN
6" X 3/8" THK
SQUARE
BASE PLATE.
ATTACH TO
SLAB.
END VIEW
RADIUS CUT ENDS
ATTACH TO
SLAB.
RADIUS CUT ENDS AND CUT FRONT OF 8" CHANNEL DOWN TO
WEB FOR HOSE ENTRY CLOSE TO SWIVEL JOINT.
1/2"Ø DRAIN HOLES (TYP OF 4)
NOTE:
ALL WELDED CONSTRUCTION SUBMIT SHOP DRAWINGS.
FIELD
VERIFY
5/8"Ø ANCHOR BOLT
TO CONCRETE BASE.
MIN 3" DEPTH (TYP 2
PER SUPPORT)
6" MIN
NOTE:
FOR HORIZONTAL INSTALLATION ONLY.
PRECAST CONCRETE
SLEEPER OR TANK
CONCRETE SLAB
BUNA-N PAD UNDER
PIPE AND BETWEEN
PIPE AND PIPE
CLAMP
6" AND SMALLER
FUEL PIPE
UNISTRUT
PIPE CLAMP
UNISTRUT
CHANNEL
1/4"Ø U BOLT
SEE PIPING PLAN
FOR PIPE SIZES
BUNA-N PAD UNDER
PIPE AND BETWEEN
PIPE AND U BOLT
GRINNELL HEAVY
WELDED STEEL
BRACKET FIGURE
199, BRACKET No.2
OR APPROVED
EQUAL
ATTACH TO
TANK SKID
5/8"Ø
ANCHOR
BOLT
VA
R
IE
S
(F
IE
LD
V
ER
IF
Y)
4" OR 6" PIPE
VARIES. SEE MECH
DWGS.
BUNA-N PAD
UNDER PIPE
ADJUSTABLE PIPE
SADDLE SUPPORT
FIGURE 264 AND
STANCHION FIGURE
62. SIZE VARIES.
GRINNELL OR
APPROVED EQUAL.
STEEL BASE PLATE,
MIN 6" SQ 3/8" THK
1/2"Ø ANCHOR
BOLT MIN
ATTACH TO EQUIP PAD SUMP
SLAB OR TANK PLATFORM
GRATING
VA
R
IE
S
(F
IE
LD
V
ER
IF
Y)
METER SUPPORTING CHAIR AND ANCHOR
BOLT SIZE VARIES. SEE PIPING PLAN24"x24"x1/2" PLATE
COORDINATE W/
EQUIP PER ANCHOR
BOLT LOCATION
3/4"Ø ANCHORS
BOLT (TYP 4)
ATTACH TO EQUIP PAD SLAB
ADJUSTABLE PIPE
SUPPORT
STEEL BASE PLATE,
MIN 8" SQ 3/8" THK
TO AST FILL TO AST FILL
SEE DWG M-7
3/4"Ø 3/4"Ø
TRV
SEE DET 6/M-9
AAV
SEE DET 10/M-5
TO AST FILL TO AST FILL
SEE DWG M-7
TOP OF
SLAB
NOTE:
CONTRACTOR TO PROVIDE SHOP DWGS AND
PIPE SUPPORT LOCATIONS PLAN.
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L D
E T
A
IL
M-5
GROUNDING REEL DETAIL
SCALE: NTS
M-6
AST FILL CONNECTION DETAIL
SCALE: NTS
M-6
AVGAS FILTER & JET A
FILTER/SEPARATOR DIAGRAM
SCALE: NTS
M-6
CONNECT TO
GROUND GRID AND
TO GROUNDING REEL
GROUND ROD
3/4"x10'L COPPER
CLAD STEEL.
CONNECT TO
ADDITIONAL RODS AS
REQUIRED TO
MAINTAIN A MINIMUM
OF 15 OHMS
RESISTANCE
SECURE TO SLAB
WITH "HILTI"
FASTENER. 2
REQUIRED.
TOP OF SLAB
GROUND REEL W/
CABLE AND CLIP
PLAN
SECTION A
A A4" RISER PIPE
4" INLET OR FILL
DROP TUBE W/ CUT OUT
6" LOCKABLE TIGHT FILL
CAP
6" RISER PIPE
REMOTE PRESSURE FILL
TYPE DROP TUBE W/ 6"
SLC (SOR TYPE)
4" FILL
6" THD CONNECTION
AST
4" OVERFILL
PREVENTION VALVE AND
DROP TUBE
DOUBLE WALL STORAGE
TANK
AST
6"
MARK TOP OF DROP
TUBE W/ LOCATION OF
INLET TEE AND ALIGN
PER MANUF.
INSTRUCTIONS
OVERFILL PREVENTION
VALVE. (REMOTE
PRESSURE FILL TYPE)
DROP TUBE
STRIKER PLATES -
UNDER EQUIPMENT
OPENINGS BY TANK
MANUF.
3/4" AAV, SEE DET 8/M-9
3/4" MAV (BALL VALVE NIPPLE AND CAP)
VESSEL HEAD LIFT AND PIVOT
LOCATE PER PLAN
DIFFERENTIAL PRESSURE
GAUGE
1/4" INSTRUMENT VALVES (TYP
OF 2)
FUEL WATER CONTROL PROBE
CONNECTIONCV
CONTROL VALVE
OUTLET
INLET
FUEL SAMPLING PROBE, SEE DET 7/M-9
3/4" SPRING LOADED TO CLOSE BALL VALVES
TO AST FILL
3/4" TRV, SEE DET 9/M-5
3/4" AAV CHECK VALVE
CAP
1" UNION LOCATED AT
VESSEL HEAD CLOSURE
SIGHT FLOW INDICATOR
FSP
1-1/2" VESSEL DRAIN
DRY DISCONNECT
WHITE BUCKET TEST
DRAIN
NOTES:
1. CONTRACTOR SHALL CONNECT THE CONTROL
VALVE TO THE FUEL WATER CONTROL PROBE IN
STRICT ACCORDANCE W/ MANUF INSTRUCTIONS
WITH S.S. TUBING.
2. CONTRACTOR TO SUBMIT
SHOP DWG. FOR APPROVAL.
WELD 4X4 TEE
SEE DETAIL 9/M-5
PROVIDE ANTI-SIPHON DEVICE
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L D
E T
A
IL
M-6
AVGAS & JET A PIPING
ISOMETRIC DIAGRAM
SCALE: NTS
M-7
AVGAS EQUIPMENT PAD
JET A EQUIPMENT PAD
AVGAS AST 2
JET A AST 1
AAV, TYP. OF 7
SEE DTL 8/M-9
TRV
AVGAS FILTER
SEE DTL 9/M-5
RELOCATED AVGAS
SUMP COLLECTOR
JET A FILTER /
SEPARATOR, SEE
DTL 9/M-5
RELAXATION VESSEL
SEE DTL 10/M-5
AAV
NOTE:
CONTRACTOR TO SUBMIT SHOP DWG
FOR APPROVAL.
SURGE SUPPRESSOR
LPD
HPV
HPV TYP. OF 10
SEE DTL 1/M-5
FLOW METER
LPD
HPV
A/E
HPV
AVGAS VAPOR RECOVERY
SURGE
SUPPRESSOR
LPD
HPV
HPV
FLOW METER
LPD
HPV
A/E
HPV
TRV AND PUMP AAV
DISCHARGE INTO
AVGAS AST FILL
TRV
TRV AAV
SPRING LOADED
BALL VALVE
TRV, TYP. OF 12
SEE DTL 6/M-9
LPD TYP. OF 10
SEE DTL 2/M-5
LPD
TRV
TRV
AAV
TRV
TRVAAV
LPD
TRV
RELOCATED JET A
SUMP COLLECTOR
SPRING LOADED
BALL VALVE
LPD
JET A
ELEVATED
PUMP PAD
AVGAS
ELEVATED
PUMP PAD
AAV
AAV
TRV AND PUMP AAV
DISCHARGE INTO
JET A AST FILL
LPD
HPV
LPD
HPV
STRAINER
STRAINER
AVGAS DRAIN W/
BALL VALVE TYP OF 5
JET A DRAIN W/ BALL
VALVE, TYP OF 5
AST
VAPOR
RECOVERY
AST
FILL
HPV
TRV
AAV
HPV
TRV
AAV
AST
SUCTION
HPV
LPD
TRV
AAV
FSP, TYP. OF 4
SEE DTL 7/M-9
HPV
AST
SUCTION
HPV, TYP. OF 5
SEE DTL 1/M-5 AST
FILL
AAV, TYP OF 5
SEE DTL 8/M-9
TRV, TYP OF 5
SEE DTL 6/M-9
AAV
TRV
AVGAS SELF SERVICE
DISPENSER
LPD
LPD, TYP OF 5
SEE DTL 2/M-5
FSP
FSP
1-1/2" BALL VALVE
LPD ON FUEL PIPE
SEE DTL 4/M-6
LPD ON FUEL PIPE
SEE DTL 4/M-6
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L
IS
O M
E T
R
IC
M-7
A static electric spark can occur when filling portable containers sitting on truck bed liners, or on any vehicle's carpeting or matting.
This spark will explosively ignite a fuel vapor fire and cause SERIOUS INJURY or DEATH.
NEVER fill portable containers that are in or on vehicle.
STATIC ELECTRIC SPARK
EXPLOSION HAZARD
ALWAYS place containers on ground.
Keep nozzle in contact with container while filling.
STATIC ELECTRICITY
WARNING
SCALE: NTS
M-8
NOTE:
PLACE ONE ON EACH SIDE OF EACH FUEL
DISPENSER (PLACE IN A CONSPICUOUS AREA)
COLOR "BLACK"
(UNLESS LABELED OTHERWISE)
COLOR "RED"
COLOR "ORANGE"
COLOR "ORANGE"
INDUSTRY STANDARD STICKER
JET A
FUEL
AVGAS
100 LL
AVGAS AST & EQUIPMENT
LABEL
SCALE: NTS
M-8
JET A AST & EQUIPMENT
LABEL
SCALE: NTS
M-8
COLOR "WHITE"
3"
6"
COLOR "BLACK"
1/8"
COLOR "WHITE"
3"
6"
COLOR "RED"
1/8"
HELVETICA BLACK FONTHELVETICA RED FONT
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L D
E T
A
IL
M-8
THERMAL RELIEF VALVE (TRV)
DETAIL
SCALE: NTS
M-9
NEW 3/4" RELIEF VALVE
W/FLANGED ENDS
(SET AT 150-PSI)
NEW 1" CS
RELIEF PIPING
NEW 3/4" BLIND FLANGE
NEW 3/4" SOCKET WELD TEE (TYP)
NEW 3/4" SOCKET WELD FLANGE
NEW 3/4" BALL VALVE (NORMALLY
OPEN) W/LOCKABLE HANDLE.
ROTATE AS REQUIRED FOR
HANDLE TO CLEAR TEE AND PIPE.
AVGAS FILTER OR JET A FILTER
SEPARATOR, RELAXATION VESSEL, OR
FUEL PIPE DEAD END FLOW
FUEL PIPE
OPEN FLOW
TO AST
ISOLATION VALVE OMITTED FOR
GRAPHIC CLARITY
3/4" SOCKET WELDING
BRANCH CONN. (TYP)
AUTOMATIC AIR VENT (AAV)
DETAIL
SCALE: NTS
M-9
SOCKET WELD
BRANCH CONNECTION
AND PIPE NIPPLE
NIPPLE AND CAP
SOCKET WELD
BALL VALVE
MANUAL VENT
AAV
3/4" AAV CHECK VALVE
DISCHARGE OPEN
FLOW PIPING
SEE DWGS M-3 & M-7
GUARD POST DETAIL
SCALE: NTS
M-9
NO SMOKING AND DANGER
SIGN
SCALE: NTS
M-9
FIRE EXTINGUISHER SIGN
SCALE: NTS
M-9
EFSO SIGN POST DETAIL
SCALE: NTS
M-9
OTHER SIGNAGE
SCALE: NTS
M-9
4'-0"
5'-0"
3"
18"
CONCRETE DOME
6"Ø SCHEDULE 40 STEEL
PIPE. FILL W/ CONCRETE
PAINT YELLOW
FINISH GRADE
CONCRETE BASE
9" 3"
18"
7'- 6"
A
BO
VE
F
IN
IS
H
GR
AD
E
PIPE CAP GALVANIZED
(WELD ALL AROUND)
TYPICAL FOR ALL SIGNAGE.
SIGN MOUNTING HOLES
(TYP)
2" HIGH RED LETTERS W/
WHITE BACKGROUND
EFSO SIGN. 18"Lx9"W
EFSO PULL TYPE OR BREAK
GLASS STATION. (SEE
ELECTRICAL DRAWINGS &
SPECIFICATIONS)
2" GALVANIZED PIPE OR
STRUCTURAL STEEL TUBE
INSTALL 5 FEET INTO GRADE
W/ CONCRETE BASE SIMILAR
TO GUARD POST DETAIL.NOTE:
COORDINATE LOCATION W/ ELECTRICAL DRAWINGS.
9"
18"
4' MIN FROM
FINISHED FLOOR
NOTE:
SECURE TO 2" GALVANIZED PIPE POST.
RED
BACKGROUND
WHITE
LETTERING
WHITE
BACKGROUND
2" HEIGHT
BLACK LETTERS
9"
18" TYP
WHITE
BACKGROUND
RED LETTERS
2" HIGH MIN
TYP OF ALL
SIGNAGE
SECURE TO
2"Ø GALVANIZED
POST TO
HAND RAIL
PROVIDE FIRE
EXTINGUISHER W/
BRACKET (AT
LOCATIONS NOTED
ON PLANS)
NOTE:
1. SECURE SIGN TO 2"Ø GALVANIZED PIPE POST.
2. ALL SIGNS SHALL BE 18"Lx9"W FIBERGLASS.
3. THESE SIGNS SHALL HAVE A WHITE BACKGROUND WITH 2"
BLACK LETTERS.
4. CONTRACTOR SHALL CONTACT OPERATOR FOR
PROCEDURES AND EMERGENCY INFORMATION FOR SIGNS.
5. TERMINATE 4'Lx2"Ø GALVANIZED POST WITH FLANGE. BOLT
TO EQUIPMENT PAD SUPPORT PLATE.
6. TERMINATE 9'Lx2"Ø GALVANIZED POST 5 FEET INTO GRADE
WITH CONCRETE BASE SIMILAR TO GUARD POST DETAIL.
7. SECURE SIGNS TO PIPE WITH STRAP.
22 23 24
19 20 21
FUEL SAMPLING POINT
CONNECTION DETAIL
SCALE: NTS
M-9
1/2 D
D FUEL PIPECL
1/4" S.S. QUICK DISCONNECT
COUPLER, MNPT END.
3/4"x1/4" REDUCING BUSHING
3/4" BRANCH CONNECTION
1/4" S.S. SAMPLE PROBE.
45° CUT IN DIRECTION OF FLOW
1/4" BALL VALVE
FNPT ENDS.
WELD
NOTES:
1. REFER TO FLOW DIAGRAM FOR QTY. AND LOCATION OF HIGH POINT VENTS, LOW
POINT DRAINS, AND FUEL SAMPLING PROBES.
2. INSTALL IN ACCORDANCE TO MANUFACTURER RECOMMENDATION.
PROVIDE ADDITIONAL SIGN
INSIDE OPS BLDG COORD /W
OPERATOR
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 4-29-2024
This document originally issued by TECS LLC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
B R
U C
E M
. K E
L L
Y , P
.E
M
EM
O R
IA
L
H W
Y
SU
IT
E
TA
M
PA
, F L
(8
) 3
-7
BID SET
THIS ITEM HAS BEEN DIGITALLY SIGNED AND
SEALED BY BRUCE M. KELLEY, PE ON THE DATE
ADJACENT TO THE SEAL. PRINTED COPIES OF
THIS DOCUMENT ARE NOT CONSIDERED SIGNED
AND SEALED AND THE SIGNATURE MUST BE
VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
M E
C H
A N
IC
A
L
SI
G N
A G
E
M-9
EL
EC
TR
IC
AL
LE
AD
-IN
S
HE
ET
E-1
A V
IA
T
IO
N
FU
E
L F
A R
M R
E
PL
A C
E M
E N
T
PR
O
JE
C T
2-
Dwg. No.
DATE: 04-29-2024
This document originally issued by PHOENIX ENGINEERING GROUP, INC.
This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN
100% SUBMITTAL
Su ite w w w .p ho en ix en g.
us t.8
.9
.0 f.8
.3
.0
En gi ne er in g
Li ce ns e
N o.
N
. D al e M ab ry
Ta m pa , F
L
8PH
O
EN
IX
EN
G
IN
EE
RI
N G
G
RO
UP
M ec ha ni ca l
El ec tri
Pl um bi ng
F ire
P ro te ct io n
Pr oc es s on st ru ct io n Ad m in is tra tio n
T M
L I C EN S E
THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY RHETT R.
JACKSON, PE ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES
OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.
W . I
D
LE
W
IL
D A
V E, SU
IT
E
TA
M
PA
, F L
(8
) 3
-2
C
ER
T.
O
F A
U
TH
Z.
N
O .3
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION DESCRIPTION
AutoCAD SHX Text
BY
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text No. 53250
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text
%%UABBREVIATIONS
AutoCAD SHX Text
TERMINAL CABINET- SURFACE MTD.
AutoCAD SHX Text
PULL BOX
AutoCAD SHX Text
REVISION NUMBER
AutoCAD SHX Text
SHEET NOTE INDICATOR
AutoCAD SHX Text
INDICATES SECTION NUMBER SECTION REFERENCE TAG
AutoCAD SHX Text
INDICATES DRAWING IN WHICH SECTION APPEARS
AutoCAD SHX Text
CONNECTION POINT OF NEW TO EXISTING
AutoCAD SHX Text BRANCH CIRCUIT HOMERUN TO PANELBOARD PNL-1 IS PANEL DESIGNATION 10 IS CIRCUIT DESIGNATION EACH CIRCUIT CONSISTS OF (2)#12, (1)#12 EG, 3/4"C UNO
AutoCAD SHX Text UNLESS NOTED ON PLAN REFER TO STANDARD MOUNTING HEIGHTS BELOW. UNLESS OTHERWISE NOTED MOUNTING HEIGHTS ARE TO CENTERLINE OF BOX. UNLESS OTHERWISE NOTED, MOUNTING HEIGHTS FOR LIGHT FIXTURES ARE TO BOTTOM ON FIXTURE.
AutoCAD SHX Text
%%UMOUNTING HEIGHTS
AutoCAD SHX Text USE OF SYMBOLS AND ABBREVIATIONS: 1. NOT ALL SYMBOLS, ABBREVIATIONS AND EQUIPMENT ABBREVIATIONS INDICATED APPEAR ON THESE CONTRACT DRAWINGS. INDIVIDUAL DRAWINGS MAY HAVE SHEET LEGENDS OR SYMBOL DESCRIPTIONS FOR UNIQUE SYMBOLS AND/OR FOR CONVENIENCE. COMMISSIONING 1. COMMISSION ELECTRICAL SYSTEMS IN THE OWNER'S PRESENCE ACCORDING TO NECA 90 COMMISSION ELECTRICAL SYSTEMS IN THE OWNER'S PRESENCE ACCORDING TO NECA 90 STANDARDS/RECOMMENDATIONS. 2. VERY PHASE ROTATION FOR ALL THREE-PHASE OUTLETS AND DISCONNECTS PRIOR TO ENERGIZING VERY PHASE ROTATION FOR ALL THREE-PHASE OUTLETS AND DISCONNECTS PRIOR TO ENERGIZING EQUIPMENT. OWNER SHALL FURNISH TEST EQUIPMENT FOR SAID TESTING.
AutoCAD SHX Text
MOTOR RATED SWITCH SIZE (A)/POLES/ENCLOSURE RATING
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text X/X/X
AutoCAD SHX Text
MATCH EXISTING
AutoCAD SHX Text
EXISTING TO BE RELOCATED - NEW LOCATION
AutoCAD SHX Text
EXISTING TO BE RELOCATED - EXISTING LOCATION
AutoCAD SHX Text
EXISTING TO BE DEMOLISHED
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
TERMINATION POINT OF DEMOLITION
AutoCAD SHX Text
(ME)
AutoCAD SHX Text
(ERN)
AutoCAD SHX Text
(ERE)
AutoCAD SHX Text
(ED)
AutoCAD SHX Text
(EX)
AutoCAD SHX Text
INDICATES DRAWING IN WHICH DETAIL APPEARS
AutoCAD SHX Text
INDICATES DETAIL NUMBER DETAIL REFERENCE TAG
AutoCAD SHX Text
EQUIPMENT IDENTITY TAG
AutoCAD SHX Text
FUTURE ITEM
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
PNL-1/10
AutoCAD SHX Text
%%UREFERENCE
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
CONDUIT/WIRE UNDERSLAB OR UNDERGROUND
AutoCAD SHX Text LIGHT SWITCH FOR INDUSTRIAL APPLICATIONS SS COVER PLATE. WP=WATERPROOF INCL SS HINGED COVER, DP=DUSTPROOF WITH CLEAR RUBBER BOOT SHIELDING TOGGLE.
AutoCAD SHX Text
VOLTAGE TRANSFORMER WITH CONCRETE PAD
AutoCAD SHX Text
BRANCH CIRCUIT PANELBOARD-FLUSH MTD
AutoCAD SHX Text
POWER PANEL SURFACE MOUNTED
AutoCAD SHX Text
LIGHTING CONTACTOR
AutoCAD SHX Text
FOUR-WAY SWITCH 20 AMP, 125/277 VOLT
AutoCAD SHX Text
TWO-POLE SWITCH 20 AMP, 125/277 VOLT
AutoCAD SHX Text
SPECIAL PURPOSE LOCKING RECEPTACLE, IN FLOOR BOX NEMA CONFIGURATION AS INDICATED
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R SINGLE, IN FLOOR BOX
AutoCAD SHX Text RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R QUADRUPLEX, PEDESTAL OR LAB BENCHTOP MOUNTED
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX - SPLIT WIRED
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R SINGLE
AutoCAD SHX Text
PIS=PIN IN SLEEVE
AutoCAD SHX Text
TL=TWIST LOCK
AutoCAD SHX Text RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX, PEDESTAL OR LAB BENCHTOP MOUNTED
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UTILITY METER
AutoCAD SHX Text
MOTOR #=MOTOR HORSEPOWER
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
TERMINAL CABINET- RECESSED MTD.
AutoCAD SHX Text
ENCLOSED CIRCUIT BREAKER, SIZE/POLES/ENCLOSURE TYPE
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE CONTROLLER
AutoCAD SHX Text
JUNCTION BOX HP=MOTOR HORSEPOWER
AutoCAD SHX Text
MANUAL MOTOR STARTER WITH OVERLOAD AND PILOT LIGHT
AutoCAD SHX Text MOTOR STARTER/CONTROLLER, WITH LOCAL DISCONNECT, U.O.N. TYPE/NEMA STARTER SIZE/POLES/ENCLOSURE TYPE. DISCONNECTING MEANS: CB=CIRCUIT BREAKER F=FUSED SWITCH
AutoCAD SHX Text J
AutoCAD SHX Text
VFD
AutoCAD SHX Text
PB
AutoCAD SHX Text J
AutoCAD SHX Text X/X/X/X
AutoCAD SHX Text X/X/X
AutoCAD SHX Text
TC
AutoCAD SHX Text
TC
AutoCAD SHX Text
AutoCAD SHX Text
CP
AutoCAD SHX Text DISCONNECT SWITCH RATING/FUSING/POLES/ENCLOSURE TYPE. WHERE "F" IS SHOWN FOR FUSING RATING/FUSING/POLES/ENCLOSURE TYPE. WHERE "F" IS SHOWN FOR FUSING SIZE FUSE PER EQUIPMENT NAMEPLATE DATA. NF=NON-FUSED
AutoCAD SHX Text X/X/X/X
AutoCAD SHX Text
%%UPOWER
AutoCAD SHX Text
THREE-WAY SWITCH 20 AMP, 125/277 VOLT
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING EQUIPMENT OR FEEDER TO BE REMOVED
AutoCAD SHX Text
EXISTING EQUIPMENT OR FEEDER TO REMAIN
AutoCAD SHX Text
VOLTAGE TRANSFORMER
AutoCAD SHX Text
BRANCH CIRCUIT PANELBOARD-SURFACE MTD
AutoCAD SHX Text
DISTRIBUTION PANELBOARD SURFACE MOUNTED
AutoCAD SHX Text
DIMMER SWITCH, SEE PLANS FOR WATTAGE RATING, VOLTAGE TO MATCH APPLICATION.
AutoCAD SHX Text T
AutoCAD SHX Text
TIME CLOCK
AutoCAD SHX Text
TC
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text
%%UWIRING
AutoCAD SHX Text T
AutoCAD SHX Text
%%UPOWER DISTRIBUTION
AutoCAD SHX Text
WP
AutoCAD SHX Text S
AutoCAD SHX Text X
AutoCAD SHX Text
LC
AutoCAD SHX Text
SINGLE POLE SWITCH 20 AMP, 125/277 VOLT
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R QUADRUPLEX, IN FLOOR BOX
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX, IN FLOOR BOX
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
%%ULIGHTING
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text SPECIAL PURPOSE RECEPTACLE, 480V, NEMA TYPE CONFIGURATION OR ELECTRICAL REQUIREMENTS WITH CONFIGURATION TO MATCH APPLICATION.
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DOUBLE DUPLEX-QUADRUPLEX
AutoCAD SHX Text
RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX
AutoCAD SHX Text
WP=WATER/WEATHER PROOF
AutoCAD SHX Text
#=NUMBER INDICATES CIRCUIT NUMBER
AutoCAD SHX Text
GFI=GROUND FAULT CIRCUIT INTERRUPTER
AutoCAD SHX Text
AutoCAD SHX Text L6-30
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
30A/3P/TL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%URECEPTACLES
AutoCAD SHX Text
RECEPTACLE NOMENCLATURE:
AutoCAD SHX Text
CONDUIT CONCEALED IN WALL OR CEILING
AutoCAD SHX Text
EXPOSED CONDUIT
AutoCAD SHX Text
PANEL BOARDS - LIGHTING AND RECEPTACLE
AutoCAD SHX Text
NEW
AutoCAD SHX Text (N)
AutoCAD SHX Text
OCCUPANCY SENSOR LIGHTING CONTROLLER, WALL MOUNT
AutoCAD SHX Text S
AutoCAD SHX Text
OS
AutoCAD SHX Text
80" A.F.F. TO BOTTOM OF STROBE OR 6" BELOW CLG WHICHEVER IS LOWER
AutoCAD SHX Text 18" A.F.F.
AutoCAD SHX Text 48" A.F.F.
AutoCAD SHX Text
72" AFF TO TOP OF PANEL
AutoCAD SHX Text 48" A.F.F.
AutoCAD SHX Text
RECEPTACLE AND WALL COMM. JACKS - GENERAL
AutoCAD SHX Text
LIGHT SWITCHES - GENERAL
AutoCAD SHX Text
FIRE ALARM STROBE, HORN/STROBE
AutoCAD SHX Text
FIRE ALARM PULL STATION
AutoCAD SHX Text S
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text OCCUPANCY SENSOR LIGHTING CONTROLLER, CEILING MOUNT. NUMBER INDICATES ANGLE OF COVERAGE
AutoCAD SHX Text SPECIAL PURPOSE RECEPTACLE, 208V OR 240V, NEMA TYPE CONFIGURATION OR ELECTRICAL REQUIREMENTS WITH CONFIGURATION TO MATCH APPLICATION.
AutoCAD SHX Text AC ABOVE COUNTER ABOVE COUNTER AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFC ABOVE FINISHED GRADE ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIR HANDLING UNIT AIC AMPERE INTERRUPT CAPACITY AMPERE INTERRUPT CAPACITY AM AMMETER AMMETER ANN ANNUNCIATOR ANNUNCIATOR AS AMMETER SWITCH AMMETER SWITCH AT AMPERE(S) TRIP AMPERE(S) TRIP ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH AUX AUXILIARY AUXILIARY AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BAS BUILDING AUTOMATION SYSTEM BUILDING AUTOMATION SYSTEM BC BELOW COUNTER BELOW COUNTER BFC BELOW FINISHED CEILING BELOW FINISHED CEILING BFE BASE FLOOD ELEVATION BASE FLOOD ELEVATION BFG BELOW FINISHED GRADE BELOW FINISHED GRADE BKR BREAKER BREAKER C CONDUIT CONDUIT CAT CATEGORY CATEGORY CB CIRCUIT BREAKER CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CLOSED CIRCUIT TELEVISION CKT CIRCUIT CIRCUIT CL CURRENT LIMITING CURRENT LIMITING CMP COMMUNICATIONS CABLE PLENUM RATED COMMUNICATIONS CABLE PLENUM RATED CMR COMMUNICATIONS CABLE RISER RATED COMMUNICATIONS CABLE RISER RATED COMM COMMUNICATIONS COMMUNICATIONS CT CURRENT TRANSFORMER CURRENT TRANSFORMER DE DUAL ELEMENT DUAL ELEMENT DN DOWN DOWN DSW DISCONNECT SWITCH DISCONNECT SWITCH DT DOUBLE THROW DOUBLE THROW DWG DRAWING DRAWING EM EMERGENCY EMERGENCY EC ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR EF EXHAUST FAN EXHAUST FAN EFSO EMERGENCY FUEL SHUTOFF EMERGENCY FUEL SHUTOFF EG ELECTRICAL GROUND ELECTRICAL GROUND EMT ELECTRIC METALLIC TUBING ELECTRIC METALLIC TUBING EOL END OF LINE (RESISTOR) END OF LINE (RESISTOR) ES END SWITCH END SWITCH EVH ELECTRIC UNIT HEATER ELECTRIC UNIT HEATER EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER ELECTRIC WATER HEATER F FUSE, FUSED FUSE, FUSED FA FIRE ALARM FIRE ALARM FACP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL FARA FIRE ALARM REMOTE ANNUNCIATOR FIRE ALARM REMOTE ANNUNCIATOR FCU FAN COIL UNIT FAN COIL UNIT FLUOR FLUORESCENT FLUORESCENT FO FIBER OPTIC FIBER OPTIC FVNR FULL VOLTAGE NON-REVERSING FULL VOLTAGE NON-REVERSING FWE FURNISHED WITH EQUIPMENT FURNISHED WITH EQUIPMENT GA GAUGE GAUGE GFI GROUND FAULT (CIRCUIT) INTERRUPTER GROUND FAULT (CIRCUIT) INTERRUPTER GFP GROUND FAULT PROTECTION GROUND FAULT PROTECTION GND,GRD GROUND GROUND GRS GALVANIZED RIGID STEEL GALVANIZED RIGID STEEL HH HAND HOLE HAND HOLE HID HIGH INTENSITY DISCHARGE HIGH INTENSITY DISCHARGE HDA HAND-OFF-AUTO HAND-OFF-AUTO HP HORSEPOWER HORSEPOWER HT HEAT TRACE HEAT TRACE HTT HIGH TEMPERATURE HEAT TRACE HIGH TEMPERATURE HEAT TRACE HV HIGH VOLTAGE HIGH VOLTAGE HZ HERTZ HERTZ IAW IN ACCORDANCE WITH IN ACCORDANCE WITH IMC INTERMEDIATE METAL CONDUIT INTERMEDIATE METAL CONDUIT INC INCANDESCENT INCANDESCENT JB JUNCTION BOX JUNCTION BOX KV KILOVOLTS KILOVOLTS KVA KILOVOLTS-AMPERE KILOVOLTS-AMPERE KVAR KILOVAR KILOVAR KW KILOWATTS KILOWATTS KWH KILOWATT-HOUR KILOWATT-HOUR LC LIGHTING CONTACTOR LIGHTING CONTACTOR LTS LIGHT(S) LIGHT(S) mA MILLIAMPERE MILLIAMPERE MAX MAXIMUM MAXIMUM MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MOTOR CIRCUIT PROTECTOR MH MANHOLE MANHOLE MIN MINIMUM MINIMUM MLO MAIN LUG ONLY MAIN LUG ONLY MOA MULTI-OUTLET ASSEMBLY MULTI-OUTLET ASSEMBLY MTD MOUNT, MOUNTED MOUNT, MOUNTED MTS MANUAL TRANSFER SWITCH MANUAL TRANSFER SWITCH N NEUTRAL NEUTRAL N1 NEMA-1 NEMA-1 N3R NEMA-3R NEMA-3R N4X NEMA-4X NEMA-4X N4X SS NEMA-4X STAINLESS STEEL NEMA-4X STAINLESS STEEL N12 NEMA-12 NEMA-12 N.C. NORMALLY CLOSED NORMALLY CLOSED NAC NOTIFICATION APPLIANCE CIRCUIT NOTIFICATION APPLIANCE CIRCUIT NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NF NON-FUSED NON-FUSED NIC NOT IN CONTRACT NOT IN CONTRACT N.O. NORMALLY OPEN NORMALLY OPEN No. NUMBER NUMBER NTS NOT TO SCALE NOT TO SCALE OC ON CENTER ON CENTER OFNP OPTICAL FIBER NONCONDUCTIVE PLENUM OPTICAL FIBER NONCONDUCTIVE PLENUM OFNR OPTICAL FIBER NONCONDUCTIVE RISER OPTICAL FIBER NONCONDUCTIVE RISER OH OVERHEAD OVERHEAD OL OVERLOAD OVERLOAD P POLE POLE PA/E PROJECT ARCHITECT/ENGINEER PROJECT ARCHITECT/ENGINEER PB PULL BOX PULL BOX PH PHASE PHASE PNL PANEL/PANELBOARD PANEL/PANELBOARD PRI PRIMARY PRIMARY PT POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE POLYVINYL CHLORIDE RE REFERENCE REFERENCE RCP RECEPTACLE(S) RECEPTACLE(S) RGSC RIGID GALVANIZED STEEL CONDUIT RIGID GALVANIZED STEEL CONDUIT RMS ROOT MEAN SQUARE ROOT MEAN SQUARE RR REMOVE AND REPLACE REMOVE AND REPLACE SBJ SERVICE BONDING JUMPER SERVICE BONDING JUMPER SD SMOKE DETECTOR SMOKE DETECTOR SEC SECONDARY SECONDARY SF SUPPLY FAN SUPPLY FAN SLC SIGNAL LINE CIRCUIT SIGNAL LINE CIRCUIT SQFT SQUARE FOOT SQUARE FOOT SS STAINLESS STEEL STAINLESS STEEL STP SHIELDED TWISTED PAIR SHIELDED TWISTED PAIR ST SINGLE THROW SINGLE THROW SW SWITCH SWITCH SWBD SWITCHBOARD SWITCHBOARD SWGR SWITCHGEAR SWITCHGEAR TEL TELEPHONE TELEPHONE TL TWIST LOCK TWIST LOCK TS TIME SWITCH TIME SWITCH TTB TELEPHONE TERMINAL BOARD TELEPHONE TERMINAL BOARD TYP TYPICAL TYPICAL uM MICRON MICRON UNO UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE UON UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED UTP UNSHIELDED TWISTED PAIR UNSHIELDED TWISTED PAIR V VOLTS VOLTS VFD VARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE VIF VERIFY IN FIELD VERIFY IN FIELD W WATTS WATTS W/ WITH WITH WP WEATHERPROOF/WATER PROOF WEATHERPROOF/WATER PROOF XFMR TRANSFORMER TRANSFORMER 1P ONE POLE ONE POLE 2P TWO POLE TWO POLE 3P THREE POLE THREE POLE PHASE
AutoCAD SHX Text
XP=NEC CLASSIFIED UON: CLASS 1, DIV 1 GROUPS A,B,C,D,
AutoCAD SHX Text
GROUND
AutoCAD SHX Text GENERAL 1. THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE "CONTRACTOR" SHALL PROVIDE THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE "CONTRACTOR" SHALL PROVIDE COMPLETE AND PROPERLY FUNCTIONING ELECTRICAL SYSTEMS AS INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. 2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND INSPECTIONS REQUIRED TO CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND INSPECTIONS REQUIRED TO COMMENCE AND COMPLETE ELECTRICAL WORK. 3. CONTRACTOR SHALL CONDUCT A THOROUGH SITE INSPECTION TO FAMILIARIZE HIMSELF WITH CONTRACTOR SHALL CONDUCT A THOROUGH SITE INSPECTION TO FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS AND ALL ASPECTS OF HIS SCOPE OF WORK. SUCH AN INSPECTION SHALL BE CONDUCTED PRIOR TO BIDDING. 4. THIS CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO THIS CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PROCEEDING WITH ANY WORK. IF DISCREPANCIES OCCUR BETWEEN THESE DOCUMENTS AND EXISTING, THE CONTRACTOR SHALL REPORT SAID DISCREPANCY TO THE OWNER AND/OR ENGINEER FOR EXPEDITING AND RESOLUTION. CONTINUATION OF WORK BEFORE RESOLUTION IS GIVEN SHALL BE AT THE CONTRACTORS RISK. 5. THE CONTRACTOR SHALL PROVIDE DROP CLOTHS, RUBBER MATS AND, PLYWOOD COVERS TO THE CONTRACTOR SHALL PROVIDE DROP CLOTHS, RUBBER MATS AND, PLYWOOD COVERS TO PROTECT OWNER'S EQUIPMENT FROM DAMAGE DURING CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S REPRESENTATIVE. 6. ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE OWNER. SCHEDULE ALL ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE OWNER. SCHEDULE ALL WORK WITH THE OWNER'S REPRESENTATIVE BEFORE PROCEEDING. 7. ALL ACTIVITIES ASSOCIATED WITH CONSTRUCTION OF THIS FACILITY SHALL COMPLY WITH OSHA ALL ACTIVITIES ASSOCIATED WITH CONSTRUCTION OF THIS FACILITY SHALL COMPLY WITH OSHA GUIDELINES. 8.