ITB_25-021_Final_S&S_Plans_2024-11-06_.PDF

PDF 13 MB Posted

Attached to
Crystal River Airport (CGC) Fuel Farm Project
Solicitation number
ITB 25-021
Issued by
Citrus County, Florida

About this file

The provided file is a comprehensive set of mechanical and electrical engineering drawings for the Aviation Fuel Farm Replacement Project at Crystal River Airport (KCGC) in Citrus County, Florida. The project involves a complete replacement of the existing fuel farm infrastructure, including the removal and installation of two 12,000-gallon aboveground storage tanks (one for Jet A and one for AVGAS), associated pumps, filters, piping, electrical systems, and supporting infrastructure. The project is funded by the Florida Department of Transportation (FDOT) under Project Number 22-154 and is advertised through Invitation to Bid (ITB) #25-021.

The project encompasses extensive technical specifications for mechanical and electrical systems, including a new electrical service with a 30kW Generac generator, automatic transfer switch, site lighting, emergency fuel shut-off (EFSO) systems, ground verification systems, and comprehensive grounding infrastructure. The drawings detail precise technical requirements for tank installation, piping configurations, electrical connections, and safety systems, with specific attention to compliance with NFPA, NEC, and other relevant safety standards. The project will require a contractor to provide all labor, materials, engineering, and installation services to completely replace the existing fuel farm infrastructure while maintaining operational standards for airport fuel handling and distribution.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

© 2023 Microsoft Corporation © 2023 Maxar ©CNES (2023) Distribution Airbus DS

C O

V E

R

IN

D

E X

D R

A W

IN

G

C&I-1

DRAWING INDEX

C&I - 1 COVER & INDEX DRAWING

G - 1 MECHANICAL LEGEND, ABBREVIATIONS & SYMBOLS

G - 2 GENERAL PROJECT NOTES

G - 3 MECHANICAL MAJOR EQUIPMENT SCHEDULES

G - 4 DEMOLITION PLAN

G - 5 SITE PLAN

G - 6 SITE ELEVATIONS

M - 1 MECHANICAL TANK FARM LAYOUT PLAN

M - 2 MECHANICAL TANK & EQUIPMENT PLAN

M - 3 MECHANICAL EQUIPMENT DETAILS

M - 4 MECHANICAL EQUIPMENT SECTIONS

M - 5 MECHANICAL DETAILS

M - 6 MECHANICAL DETAILS

M - 7 MECHANICAL ISOMETRIC

M - 8 MECHANICAL DETAILS

M - 9 MECHANICAL SIGNAGE

AVIATION FUEL FARM REPLACEMENT

FOR

CITRUS COUNTY TECHNICAL SERVICES

CRYSTAL RIVER AIRPORT (KCGC)

CRYSTAL RIVER, FLORIDA

PROJECT FUNDING: (FDOT)

PROJECT NUMBER 22-154

ITB# 25-021

BID SET

CRYSTAL RIVER AIRPORT

718 N LINDBERG TER

CRYSTAL RIVER, FL 34429

(352) 795-6868

AVIATION FUEL FARM

REPLACEMENT SITE

U S

H W

Y

DRAWING INDEX

E - 1 ELECTRICAL LEAD - IN SHEET

E - 2 ELECTRICAL SITE PLAN

E - 3 ELECTRICAL POWER PLAN

E - 4 ELECTRICAL SCHEDULES & DETAILS

E - 5 ELECTRICAL CONTROLS

E - 6 ELECTRICAL DETAILS

THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR

THE FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004‚ F.A.C.

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

)3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

THE ABOVE NAMED PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR

THE FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004‚ F.A.C.

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY RHETT R. JACKSON, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

AutoCAD SHX Text N

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

SYMBOL

Rhett Jackson RRJ Digital Seal_FL2

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L L

E G

E N

D

A B

B R

E V

IA

T

IO

N

S

S Y

M B

O L

S

G-1

NEW FUEL PIPE

VALVE

REDUCER

ELBOW DOWN

BALL VALVE

LEGEND ABBREVIATIONS

APPROX.

BFV

BLDG.

B.O.P.

COMM.

C

CLR.

CONT.

DET.

DIA. Ø

DWG.

EA.

E.F.

ELEC.

ELL.

EXIST.

FLG.

GALV.

HPV

I.D.

I.E.

JFP

LPD

MAX.

MECH.

MH.

MIN.

MNPT.

N.

NPT.

NTS

PAVMT.

PL.

R/C

APPROXIMATE

BUTTERFLY VALVE

BUILDING

BOTTOM OF PIPE

COMMUNICATION

CENTER LINE

CLEARANCE

CONTINUOUS

DETAIL

DIAMETER

DRAWING

EACH

EACH FACE

ELECTRICAL

ELBOW

EXISTING

FLANGE

GALVANIZED

HIGH POINT VENT

IDENTIFICATION

INVERT ELEVATION

JET-A FUEL PIPE

LOW POINT DRAIN

MAXIMUM

MECHANICAL

MANHOLE

MINIMUM

MALE NATIONAL PIPE THREAD

NORTH

NATIONAL PIPE THREAD

NOT TO SCALE

PAVEMENT

RELAXATION CHAMBER

PLATE

FUEL PIPE

EXPLOSION PROOF

WELD NECK FLANGE

WITHOUT

WITH

UNDERGROUND

TYPICAL

TOP OF PIPE

THICK

THREADED

TEMPORARY

STEEL

SHEET

STORM DRAIN

SCHEDULE

SANITARY

REQUIRED

REINFORCED

REFERENCE

REDUCER

XP.

WNF.

W/O

W/

U.G.

TYP.

T.O.P.

THK.

THD.

TEMP.

STL.

SHT.

SD.

SCH.

SAN.

REQ'D.

REINF.

REF.

RED.

STRUCT. STRUCTURE

VERT. VERTICAL

L

L.

O.C.

F.S.

E.W.

STA.

EACH WAY

FIRE SAFE

LONG

ON CENTER

STATION

CONC. CONCRETE

I.F. INSULATING FLANGE

NC. NORMALLY CLOSED

FNPT. FEMALE NATIONAL PIPE THREAD

DN. DOWN

A.O.A. AIR OPERATIONS AREA

ABOVE GROUNDA.G.

MOTOR GASOLINEMOGAS

NIC. NOT IN CONTRACT

BF BLIND FLANGE

LT. LEFT

RT. RIGHT

GAL. GALLON

PSI POUND PER SQUARE INCH

CHECK VALVE

OR

BUTTERFLY VALVEOR

F.E. FIRE EXTINGUISHER

ECC. ECCENTRIC

DIM. DIMENSION

FUEL

TANKER

F.O.T. FLAT ON TOP

ELBOW UP

ABOVE FINISHED PAVEMENTAFP.

AUTOMATIC AIR VENTAAV

AIR ELIMINATORA/E

CV CONTROL VALVE

EQ. EQUAL

FM FLOW METER

F/S FILTER SEPARATOR

OTRTT OVER THE ROAD TRANSPORT TRUCK

PIV. POST INDICATOR VALVE

TRV THERMAL RELIEF VALVE

VA. VALVE

FSP FUEL SAMPLING PROBE

CON. CONCENTRIC

SURGE SUPPRESSORSS

AST ABOVEGROUND STORAGE TANK

AVGAS AVIATION GASOLINE

ED. EDITION

EL. ELEVATION

EFSO EMERGENCY FUEL SHUT OFF

FLEX FLEXIBLE

GA. GAUGE

LB. POUND

QTY. QUANTITY

PS PIPE SUPPORT

SQUARESQ.

WELDED WIRE FABRICWWF.

WATERWTR.

ADDITIIONALADD'L

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

G E

N E

R A

L

PR

O

JE

C T

N O

T E

S

G-2

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L M

A

JO

R E

Q U

IP

M

E N

T

SC

H E

D U

L E

G-3

DEMOLITION PLAN

SCALE:

EXIST 24" x 24" SUMP WITH

BAR GRATING

EXIST CONTAINMENT

CURB AND AST SLAB

(6" WIDE x 12" HIGH CURB

FROM AST SLAB) 30

'-1 0"

46'-3"

3' -7

15'-0"

'-0

'-0

EXIST 8" WIDE CURB SLOPES

DOWN WITH RAMP, BOTH

SIDES OF DRIVEWAY

SLOPE

SLOPE

3' -7

EXIST DRAIN VALVES,

TYP OF 5

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

D E

M O

L

IT

IO

N

PL

A

N

G-4

NOTES:

1. REMOVE FUEL FROM EXIST ASTs AND TRANSFER TO REFFUELERS.

2. COMMENCE WITH DEMOLITION OF EXISTING FUEL FACILITY.

3. RELOCATE AST SUMP COLLECTORS TO NEW FUEL FACILITY.

RELOCATE EXISTING 17 GAL.

AST SUMP COLLECTORS

CONNECT

AAVs & TRVs

18"x18"x12" TYP.

36" HIGH

TYP.

REMOVE EXIST JET A AST

12,000 GAL.

REMOVE EXIST AVGAS AST

12,000 GAL.

REMOVE EXIST JET A

PUMP & EQUIPMENT

REMOVE EXIST AVGAS

PUMP & EQUIPMENT

EXIST 8" WIDE CURB

BOTH SIDES OF DRIVEWAY

EXIST 12" WIDE x 8" HIGH

DRIVE-OVER CURB

END OF DRIVEWAY

CONNECT

AAVs & TRVs

EXIST AVGAS TANK AND EQUIPMENT EXIST JET A TANK AND EQUIPMENT EXIST JET A CABINET

(TYPICAL)

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

SI

T

E P

L A

N

G-5

U S

H W

U S

H W

GODFREY LN

N L

IN

D

BE

R

G T

ER

N LINDBERG TER

U S

H W

LANDSIDE GATE

AIRSIDE GATE

AIRSIDE GATE

CONTRACTOR

STAGING AREA

APPROXIMATELY

55' x 100'

PROJECT AREA

APPROXIMATELY

55' x 45'

CONTRACTOR'S ACCESS ROUTE

U S

H W

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

SI

T

E E

L E

V A

T

IO

N S

G-6

EXIST

EXIST

SEE NOTE 24 ON DWG G-2.

FUEL FARM LAYOUT PLAN

EXIST 24" x 24" SUMP WITH

BAR GRATING

EXIST CONTAINMENT

CURB AND AST SLAB

(6" WIDE x 12" HIGH CURB

FROM AST SLAB)

'-1

0"

46'-3"

3' -7

15'-0"

'-0

'-0

EXIST 12" WIDE x 8" HIGH

DRIVE-OVER CURB

END OF DRIVEWAY

EXIST 8" WIDE CURB

BOTH EAST & WEST SIDES

OF DRIVEWAY

EXIST 8" WIDE CURB SLOPES

DOWN WITH RAMP, BOTH

EAST & WEST SIDES OF

DRIVEWAY

NEW AST 2 AVGAS 12,000 GAL

ABOVEGROUND STORAGE TANK

ON STEEL SKID, 10'Ø x 20'-6" LONG

NEW AST 1 JET A 12,000 GAL

ABOVEGROUND STORAGE TANK

ON STEEL SKID, 10'Ø x 20'-6" LONG

EXISTING AVGAS CURBED

EQUIPMENT PAD

SLOPE

SLOPE

3' -7

5'-0" 10'-0"Ø 3'-4"

10'-0"Ø

5' -2

5'

-2

17'-11"

(15'-0" CLR REQ'D)

31'-3"

(25'-0" CLR REQ'D)

PROVIDE PIPE CAPS AND

REMOVE EXIST DRAIN VALVES,

TYP OF 4

NEW PIV

NEW ELEVATED PUMP

PLATFORM (6'-0" HIGH

TOP OF AST SLAB TO

TOP OF PUMP

PLATFORM), TYP OF 2

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L

FU

E L

F A

R M

L A

Y O

U T

P L

A N

M-1

EXISTING JET A CURB

EQUIPMENT PAD

NEW LADDER WITH CAGE AND SAFETY CLIMB

NEW LADDER WITH CAGE AND SAFETY CLIMB

RELOCATED JET A

SUMP COLLECTOR

NEW SCULLY UNIT

NOTE:

THE CONTRACTOR TO PROVIDE THE DESIGN FOR ALL FOUNDATIONS, PLATFORMS AND STAIRS

CONFORMING TO ALL APPLICABLE CODES AND OSHA REQUIREMENTS. SUBMIT DESIGN AND

SHOP DRAWINGS SIGNED AND SEALED BY A STATE OF FLORIDA PROFESSIONAL ENGINEER.

15'-8"

NEW AVGAS REMOTE SELF

SERVICE DISPENSER.

PROVIDE CONCRETE SLAB

UNDERNEATH.

NEW 6"Ø BOLLARD, TYP OF 9.

SEE DETAIL 1/M-9

A M4

A

B M4

B

TOP OF NEW TANK WITH

ANTISKID COATING AND HANDRAILS,

TYPICAL BOTH TANKS

RELOCATED AVGAS

SUMP COLLECTOR

NEW GROUND REEL

NEW SCULLY UNIT

NEW GROUND REEL

NEW 1 1/2" AVGAS

ABOVEGROUND PIPING

NEW STAIR OVER FUEL PIPING

W/ STAIR FOOTING

NEW STAIR OVER FUEL PIPING

W/ STAIR FOOTING

HAND RAILS AROUND NORTH,

SOUTH & EAST SIDES OF AST 1

& AST 2 OF ANTISKID TOP

SURFACE

NEW STAIR TO

ELEVATED PUMP

PLATFORM W/

STAIR FOOTING

PIV

PIPE SUPPORT

SEE DWG M-5

REPAINT TOP OF CURB SAFETY YELLOW

PROVIDE CONCRETE COATING PER SPECIFICATIONS

PROVIDE CONCRETE

COATING PER

SPECIFICATIONS

FUEL FARM PLAN

NEW AVGAS CURBED

EQUIPMENT PAD

REFER TO DETAIL D/M-4

3"Ø ISSUE & SUCTION PIPING

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L

FU

E L

F A

R M

PL

A

N

M-2

NEW 6"Ø BOLLARDS, SEE DETAIL 1/M-9

NEW STAIR TO

ELEVATED PUMP

PLATFORM W/ STAIR

FOOTING

NEW AVGAS REMOTE SELF SERVICE DISPENSER

KEYED NOTES ( NOTES 1 - 16 AND 25 TYPICAL FOR BOTH TANKS #1 AND #2, EXCEPT AS NOTED:

1 4"X2" FILL FLANGE ON TOP ℄ WITH 3" BFV EXTERNAL, DROP TUBE INTERNAL (TERMINATE 6" ABOVE AST

BOTTOM AND ATTACH TO TANK BOTTOM BRACKET). PROVIDE 2" REMOTE PRESSURE FILL CUT-OFF FLOAT

SET AT 95% TANK CAPACITY INTERNAL. PROVIDE ANTI-SIPHON DEVICE. SEE DET 2/M-6

2 AVGAS - 8" SUCTION FLANGE ON TOP ℄ WITH 3" EXTERNAL BFV, DROP TUBE INTERNAL (TERMINATE 6" ABOVE AST BOTTOM). PROVIDE 3" FOOT VALVE. PROVIDE ANTISYPHON DEVICE. SUBMIT SHOP DRAWINGS FOR

APPROVAL.

2A JET A - 3" SUCTION FLANGE ON TOP ℄ WITH 3" EXTERNAL BFV, INTERNAL FLOATING SUCTION, RETENTION CABLE AND EXTERNAL TARGET INDICATOR. PROVIDE ANTISYPHON DEVICE. SUBMIT SHOP DRAWINGS FOR

APPROVAL.

2B INTERNAL FLOATING SUCTION. PROVIDE SUPPORTS TO MAINTAIN INLET 1'-6" ABOVE AST BOTTOM WHEN SUCTION PIPE IS IN DOWN POSITION. PROVIDE PIVOTED FLOATING SUCTION FLOAT ASSEMBLY: 10 GA.

ROLLED STEEL PLATE, WITH 3/4" DIA. 3000LB., TEST PLUGS AND COUPLINGS. PROVIDE FLOATS AS REQ'D TO ENSURE FLOTATION OF SUCTION PIPE IN JET FUEL, WITH MEANS TO COMPENSATE FOR INCREASED BUOYANCY FORCE OF WATER DURING HYDROSTATIC TEST. INDICATE MINIMUM AND MAXIMUM INLET SUBMERGENCE VS FLOATING SUCTION PIPE ANGLE. SUBMIT CALCULATIONS. PROVIDE SUCTION INLET WITH

ANTIVORTEX PLATE DESIGN FOR MAX. VELOCITY

3.5 FPS AT 130 GPM.

2C SUCTION PIPE RETENTION CABLE. 5/16" DIA. - TYPE 316 S.S. COIL-PROOF CABLE, SHALL LIMIT FLOATING SUCTION TRAVEL TO 60°. CONNECT TO UNDERSIDE OF FLOATING SUCTION. ATTACHCABLE WITH CAMPS TO

2'-6" SQ X 3/8" THK. STEEL PLATE CONTINUOUS WELD TO AST BOTTOM.

2D EXTERNAL SUCTION TARGET INDICATOR. 3/16" DIA. - TYPE 316 S.S. COIL-PROOF NONSPARKING CABLE WITH SWIVEL SHEAVES. CONNECT TO UNDERSIDE OF FLOATING SUCTION. CABLE SHALL NOT CONTACT TANK INTERNALS. PROVIDE EXTERNAL CABLE GUIDES AT TANK ROOF. PROVIDE SUPPORT BRACKETS AND TANK SHELL. PROVIDE TARGET PLATE RIGGED TO RISE AND FALL WITH OF FLOATING SUCTION POSITION. PROVIDE

1-1/2" NOZZLE FOR EXTERNAL SUCTION TARGET INDICATOR 1-1/2" 3000LB COUPLING.

3 3" VENT FLANGE ON TOP ℄ WITH VENT STACK (16'-0" AFP). PROVIDE PRESSURE/VACUUM VENT CAP

EXTERNAL.

4 8" EMERGENCY VENT FLANGE ON TOP ℄ (MAIN TANK VESSEL). PROVIDE EMERGENCY VENT EXTERNAL.

5 8" EMERGENCY VENT FLANGE ON TOP ℄ (SECONDARY CONTAINMENT). PROVIDE EMERGENCY VENT

EXTERNAL.

6 3" GAUGE HATCH FLANGE ON TOP ℄ WITH 1/4" THICK STRIKER PLATE ON TANK BOTTOM INTERNAL. PROVIDE SLOTTED DROP TUBE. INTERNAL TERMINATE 3" ABOVE AST BOTTOM AND SELF CLOSING HATCH EXTERNAL.

7 24" MANHOLES ON TOP ℄

8 4" LEVEL ALARM FLANGE ON TOP ℄ SET ALARM AT 90% TANK CAPACITY. (VISUAL AND AUDIBLE) SET PUMP CUT-OFF AT 95% TANK CAPACITY. SET LOW SUCTION CUT-OFF AT 2' -0" ABOVE AST BOTTOM.

9 3" DRAIN PUMP FLANGE ON TOP ℄ WITH DRAIN PUMP AND DROP TUBE. TERMINATE 2" ABOVE AST BOTTOM.

10 2" INTERSTITIAL MONITOR ON TOP ℄. CONNECT TO ALARM.

11 GROUNDING TABS ON VESSEL SIDE BOTTOM (QTY. 4). CONNECT TO GROUNDING GRID.

12 NEW STAIRS, PLATFORM AND HANDRAILS.

13 PRESSURE TEST CERTIFICATE 3 PSI FOR 1 HOUR, INTERNAL VESSEL AND SECONDARY CONTAINMENT.

14 LINE TANK INTERIOR WITH FUEL RESISTANT EPOXY "INTERLINE 850" (MANUFACTURER). COAT ASTs &

EQUIPMENT PER SPECIFICATIONS.

15 UL142 & UL2085, DOUBLE WALLED, 20,000 GALLON CAPACITY SKID-MOUNTED AS SPECIFIED 10'-0"Ø X 20'-6"L.

LABEL PRODUCT & TANK # ON TANK HEADS. COAT TANK INTERIOR AND EXTERIOR (MANUFACTURER).

16 NFPA 704 DECAL.

17 SIGNAGE - "EFSO" INSTRUCTIONS AND EFSO STATION. SEE DWG M-9 .

18 SIGNAGE - "NO SMOKING". SEE DWG M-9.

19 SIGNAGE - TANK STRAPPING CHART. EMERGENCY PROCEDURES

AND TELEPHONE NUMBERS. SEE DWG M-9.

20 SIGNAGE - "VALVE INSTRUCTIONS (LOAD/OFFLOAD)". SEE DWG M-9.

21 SIGNAGE - "AVGAS TANK #2 FILL". SEE DWG M-9.

22 SIGNAGE - "AVGAS TANK #2 SUCTION". SEE DWG M-9.

23 SIGNAGE - "JET A TANK #1 FILL". SEE DWG M-9.

24 SIGNAGE - "JET A TANK #1 SUCTION". SEE DWG M-9.

25 SIGNAGE - "FIRE EXTINGUISHER". PROVIDE NEW FIRE EXTINGUISHER

SEE DWG M-9.

26 SIGNAGE - "AVGAS VAPOR RECOVERY". SEE DWG M-9.

27 3" VAPOR RECOVERY FLANGE ON TOP ℄ WITH 3" BFV EXTERNAL.

28 PAINT EXTERIOR OF NEW PIPING AND EQUIPMENT. PAINT FLOW

DIRECTION ARROWS ON PIPES.

29 AVGAS REMOTE SELF SERVICE DISPENSER. SEE DETAIL E/M-4.

30 SIGNAGE - "AVGAS AST". SEE DETAIL 5/M-8.

31 SIGNAGE - "JET A AST". SEE DETAIL 6/M-8.

TRV

17 25

150# REFER TO SPEC

SECTION FS 231505

EQUIPMENT

31 13 14 15 16 18 19

30 13 14 15 16 18 19

10 1111 10 1111

1111 1111

2D

2A

2C

NEW AST 2 AVGAS 12,000 GAL

ABOVEGROUND STORAGE TANK

ON STEEL SKID, 10'Ø x 20'-6" LONG

NEW AST 1 JET A 12,000 GAL

ABOVEGROUND STORAGE TANK

ON STEEL SKID, 10'Ø x 20'-6" LONG

30 13 14 15 16

31 13 14 15 16

NEW LADDER WITH CAGE

AND SAFETY CLIMB

NEW LADDER WITH CAGE

AND SAFETY CLIMB

6'-0"

NEW STAIR OVER FUEL

PIPING W/ STAIR FOOTING

HAND RAILS AROUND NORTH,

SOUTH & EAST SIDES OF AST 1

& AST 2 OF ANTISKID TOP

SURFACE

NEW JET A CURBED

EQUIPMENT PAD

REFER TO DETAIL C/M-4

3"Ø ISSUE & SUCTION PIPING

1-1/2" BALL VALVE

1-1/2" AVGAS

ABOVEGROUND PIPING

HPV & LPD

AAV

AAV & TRV

TRV

HPV & LPD

AAV

HPV

LPD

HPV

HPV & LPD

AAV

TRV

HPV

FSP

LPD

HPV

AAV

LPD

HPV

LPD

TRV

AAV

AAV & TRV

HPV & LPD

AAV & TRV

HPV & LPD

HPV & LPD

AAV

TRV

HPV

AAV

TRV

HPV

LPD

LPD

FSP

POST

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L E

Q U

IP

M

E N

T D

E T

A

IL

S

M-3

AVGAS CURBED EQUIPMENT

PAD PLAN

SCALE:

M-3

JET A CURBED EQUIPMENT

PAD PLAN

SCALE:

M-3

SCULLY UNIT

NOTES:

1. AVGAS & JET A EQUIPMENT PADS ARE

SEPARATED FOR GRAPHIC CLARITY. REFER TO

LAYOUT PLAN DWG M-1 & M-2 FOR LOCATIONS.

2. AVGAS & JET A PIPING DIAGRAMS ON DWG M-7.

GROUND REEL, SEE DET 1/M-6. REFER TO

ELECTRICAL DWGS FOR ADD'L GROUND

VERIFICATION UNIT.

3" SWIVEL AND 4"x3" REDUCER

3" BFV TRV

3" CHECK VALVE AND

SURGE SUPPRESSOR

3" BFV

2-3" 90° ELLS

TRV2-3" 45° ELLS

PS-CFLEX CONN.

PS-C

FLEX CONN.

2-3" 90° ELLS

3" BASKET STRAINER

JET A LOAD/OFFLOAD PUMP

PS-C

3" JET A FROM AST #1 SUCTION

PUMP AIR RELEASE W/

AAV CHECK VALVE

3" JET A FROM AST #1 FILL

3" TEE

FLEX CONN.

PS-C

3" BFV

RELOCATED JET A

SUMP COLLECTOR

SEE DWG G-4

TRV

3" CONTROL VALVE, FM, AND A/E.

CONTROL VALVE HYDRAULIC SIGNAL

FROM FM AND A/E

PS-C2- 3" 45° ELLS

3" SWIVEL

2-3" 90° ELLS

RELAXATION VESSEL

PUMP FLOW SWITCH

CONTROL VALVE HYDRAULIC SIGNAL

FROM F/S FLOAT CONTROL

CONTROL VALVE HYDRAULIC SIGNAL

FROM F/S FLOAT CONTROL

3"x2-1/2" REFUELER TRUCK NOZZLE 3"x12' LOAD HOSE, SEE DET 4/M-5

DEADMAN SWITCH (HYDRAULIC)

PROVIDE POST ON TOP OF THE

CONCRETE SLAB

4" OVER THE ROAD

TRANSPORT TRUCK NOZZLE

4"x12' OFFLOAD HOSE, SEE DET 4/M-5

3" TEE

CURBED EQUIPMENT PAD

F/S

SCULLY UNIT

GROUND REEL, SEE DET 1/M-6. REFER TO

ELECTRICAL DWGS FOR ADD'L GROUND

VERIFICATION UNIT.

3" SWIVEL AND 4"x3" REDUCER

2-3" 45° ELLS

TRV

3" CHECK VALVE AND

SURGE SUPPRESSOR

3" BFV

2-3" 90° ELL

TRV

PS-CFLEX CONN.

PS-C

4-3" 90° ELLS

3" BASKET STRAINER

AVGAS LOAD/OFFLOAD PUMP

3" AVGAS FROM AST #2 SUCTION

3" TEE

PS-C

3" BFVRELOCATED AVGAS SUMP COLLECTOR

SEE DWG G-4

TRV

3" CONTROL VALVE, FM, AND A/E.

CONTROL VALVE HYDRAULIC SIGNAL

FROM FM AND A/E

1-1/2" 90° ELL, PIT W/ 1-1/2" BV & I.F. KIT

2- 3" 90° ELLS3" SWIVEL 2-1-1/2" 90° ELLS

CONTROL VALVE HYDRAULIC SIGNAL

FROM FILTER FLOAT CONTROL

3"x2-1/2" REFUELER TRUCK NOZZLE 3"x12' LOAD HOSE, SEE DET 4/M-5

DEADMAN SWITCH (HYDRAULIC)

PROVIDE POST ON TOP OF THE CONCRETE SLAB

4" OVER THE ROAD

TRANSPORT TRUCK NOZZLE

4"x12' OFFLOAD HOSE, SEE DET 4/M-5

3" TEE

CURBED EQUIPMENT PAD

FILTER

3" AVGAS FROM AST #2 FILL

3" AVGAS FROM AST #2 VAPOR RECOVERY

PUMP AIR RELEASE W/ AAV CHECK VALVE

FLEX CONN.

PS-C

3" VAPOR OFFLOAD CONN. W/2-3" 90° ELLS

PUMP FLOW SWITCH

PS-C

1-1/2" FROM AVGAS

SELF SERVE DISPENSER

1-1/2" BALL VALVE W/ 3"x1-1/2" REDUCER

3" TEE

2-3" 90° ELLS

2-3" 90° ELLS

PROVIDE FIRE EXTINGUISHER

SEE DWG M-9

TANK SECTION B-B

M-4

NEW 12,000

GALLON TANK

TYP AST 1 & AST 2

TANK SKIDS OR

SADDLES AS

REQ. PER MFR.

EXIST CONC. SLAB (TYP.)

WITH NEW PROTECTIVE COATINGS

PROVIDE SHIM UNDER SKIDS TO MAINTAIN

CONTAINMENT FLOOR SLOPE TO DRAIN

WATER TO TRENCH DRAIN. (TYP.)

10' Ø INNER DIA.

10' Ø INNER DIA.

JET A

ABOVE

STORAGE

TANK 1

AVGAS

ABOVE

STORAGE

TANK 2

TOP OF SLAB

EL.= 5.0 6'

-0

TOP OF SLAB

EL.=5.0

SCALE:

TOP OF PUMP

PLATFORM12

TANK SECTION A-A

M-4

20'-6" INNER

LENGTH

SCALE:

AVGAS LOAD / OFFLOAD

SECTION D

M-4

JET A LOAD / OFFLOAD

SECTION C

M-4 SCALE:SCALE:

METER SUPPORT (BEYOND)

SEE DET 8/M-5

4'-0"

PUMP PAD

FOUNDATION

SEE NOTE 23 ON

DWG G-2

6' -0

3'-4" 5'-0" 46'-3"

3 2D 1091

6 7

2A2B2C

PUMP

PLATFORM 12

JET A PUMP CONCRETE

FOUNDATION

INTERNAL

STRIKER

PLATE

AVGAS

PUMP CONCRETE

FOUNDATION

TOP

OF

SLAB

AST

SKIDS

JET A AST-1

SLOPE 1"/ 20'

NEW LADDER

WITH CAGE

AND SAFETY

CLIMB

RELAXATION CHAMBER

SEE DET 10/M-5SURGE SUPPRESSOR

FILTER SEPARATOR

SEE DET 9/M-5 & 3/M-6

LOAD HOSE

OFFLOAD HOSE

TOP

OF

SLAB

HOSE RACK

SEE DET 4/M-5

JET A PUMP

SURGE SUPPRESSOR

FILTER

SEE DET 9/M-5 & 3/M-6

LOAD HOSE

OFFLOAD HOSE

TOP

OF

SLAB

METER SUPPORT (BEYOND)

SEE DET 8/M-5

HOSE RACK

SEE DET 4/M-5

AVGAS PUMP

VAPOR RECOVERY

HANDRAILS AROUND NORTH, SOUTH, EAST

SIDES OF AST 1 & AST 2 OF ANTISKID TOP

26 23

11 11

'-0

HANDRAILS AROUND NORTH, SOUTH, EAST

SIDES OF AST 1 & AST 2 OF ANTISKID TOP

31 13 30 13

18 19

18 19

11 11 11 11

NEW STAIRS OVER

FUEL PIPES

PROVIDE

PUMP PAD

25 25

NEW REMOTE SELF SERVICE

DISPENSER E

M-4SCALE: NOT TO SCALE

NOTE:

REFER TO SPECIFICATION SECTION FS 231505 EQUIPMENT FOR DISPENSER.

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L E

Q U

IP

M

E N

T

SE

C T

IO

N

M-4

AVGAS FILTER & JET A

FILTER SEPARATOR DETAIL

SCALE: NTS

M-5

RELAXATION CHAMBER

DETAIL

SCALE: NTS

M-5

S

3/4"Ø 3/4"Ø

TRV

SEE DET 6/M-9

AAV

SEE DET 8/M-9

INSTALL FLOAT CONTROL

CONNECT TO CV

SEE DET 4/M-6 & DWG M-7

FOR DRAIN PIPING DIAGRAM

ANCHOR BOLT TO SLAB

(TYP 4)

EQUIPMENT SLAB

ANCHOR BOLT TO SLAB

(TYP 4)

EQUIPMENT SLAB

SUMP DRAIN W/ SPRING

LOADED VALVE

1-1/2"Ø DRAIN LINE

HIGH POINT VENT (HPV)

DETAIL

SCALE: NTS

M-5

ABOVEGROUND LOW POINT

DRAIN (LPD) DETAIL

SCALE: NTS

M-5

TYPICAL BUTTERFLY VALVE

(BFV) INSTALLATION DETAIL

SCALE: NTS

M-5

HOSE RACK DETAIL

SCALE: NTS

M-5

PIPE SUPPORT (PS-A) DETAIL

SCALE: NTS

M-5

PIPE SUPPORT (PS-B) DETAIL

SCALE: NTS

M-5

METER SUPPORT DETAIL

SCALE: NTS

M-5

PIPE SUPPORT (PS-C) DETAIL

SCALE: NTS

M-5

PIPE SUPPORT SPACING

SCHEDULE

SUPPORT PIPES AT LOCATIONS INDICATED.

MAXIMUM SPACING OF SUPPORTS IS BASED ON

PIPE SIZE AND SHALL BE AS FOLLOWS:

NOMINAL PIPE

SIZE

MAXIMUM

SPACING

1 1/2" 9'-0" 2" 10'-0" 3" 12'-0" 4" 14'-0"

2" SOCKET WELD

BALL VALVE

2"Ø SOCKET

WELD NIPPLE

DRY DISCONNECT

AND CAP,

COORDINATE W/

THE SYSTEM

OPERATOR FOR

SIZE AND TYPE.

2" SOCKET WELD

BRANCH

CONNECTION

FUEL PIPE

B.O.P.

FUEL PIPE

B.O.P.

2"Ø SOCKET WELD NIPPLE

2" SOCKET WELD BRANCH

CONNECTION

2" SOCKET WELD

BALL VALVE

DRY DISCONNECT

AND CAP,

COORDINATE W/

THE SYSTEM

OPERATOR FOR

SIZE AND TYPE.

DIRECTION

OF FLOW

OPEN

CLOSED

FUEL PIPE

BFV

DISC IS SHOWN IN

CLOSED POSITION.

OPEN DISC AS

INDICATED. WELD NECK FLANGES

DISC SHAFT

IN VERTICAL

PROVIDE ADEQUATE CLEARANCE IN EACH

DIRECTION TO PERMIT OPERATION OF

GEAR OPERATOR HANDLE.

14'-0" 2'-0"

EQ. SPACE EQ. SPACE EQ. SPACE

TOP OF

CHANNEL LEG

BOTTOM OF

HOSE CHANNEL

AND END PLATE

TO BE EVEN

6" X 3/8" THK

SQUARE

BASE PLATE.

ATTACH TO

SLAB.

END VIEW

RADIUS CUT ENDS

ATTACH TO

SLAB.

RADIUS CUT ENDS AND CUT FRONT OF 8" CHANNEL DOWN TO

WEB FOR HOSE ENTRY CLOSE TO SWIVEL JOINT.

1/2"Ø DRAIN HOLES (TYP OF 4)

NOTE:

ALL WELDED CONSTRUCTION SUBMIT SHOP DRAWINGS.

FIELD

VERIFY

5/8"Ø ANCHOR BOLT

TO CONCRETE BASE.

MIN 3" DEPTH (TYP 2

PER SUPPORT)

6" MIN

NOTE:

FOR HORIZONTAL INSTALLATION ONLY.

PRECAST CONCRETE

SLEEPER OR TANK

CONCRETE SLAB

BUNA-N PAD UNDER

PIPE AND BETWEEN

PIPE AND PIPE

CLAMP

6" AND SMALLER

FUEL PIPE

UNISTRUT

PIPE CLAMP

UNISTRUT

CHANNEL

1/4"Ø U BOLT

SEE PIPING PLAN

FOR PIPE SIZES

BUNA-N PAD UNDER

PIPE AND BETWEEN

PIPE AND U BOLT

GRINNELL HEAVY

WELDED STEEL

BRACKET FIGURE

199, BRACKET No.2

OR APPROVED

EQUAL

ATTACH TO

TANK SKID

5/8"Ø

ANCHOR

BOLT

VA

R

IE

S

(F

IE

LD

V

ER

IF

Y)

4" OR 6" PIPE

VARIES. SEE MECH

DWGS.

BUNA-N PAD

UNDER PIPE

ADJUSTABLE PIPE

SADDLE SUPPORT

FIGURE 264 AND

STANCHION FIGURE

62. SIZE VARIES.

GRINNELL OR

APPROVED EQUAL.

STEEL BASE PLATE,

MIN 6" SQ 3/8" THK

1/2"Ø ANCHOR

BOLT MIN

ATTACH TO EQUIP PAD SUMP

SLAB OR TANK PLATFORM

GRATING

VA

R

IE

S

(F

IE

LD

V

ER

IF

Y)

METER SUPPORTING CHAIR AND ANCHOR

BOLT SIZE VARIES. SEE PIPING PLAN24"x24"x1/2" PLATE

COORDINATE W/

EQUIP PER ANCHOR

BOLT LOCATION

3/4"Ø ANCHORS

BOLT (TYP 4)

ATTACH TO EQUIP PAD SLAB

ADJUSTABLE PIPE

SUPPORT

STEEL BASE PLATE,

MIN 8" SQ 3/8" THK

TO AST FILL TO AST FILL

SEE DWG M-7

3/4"Ø 3/4"Ø

TRV

SEE DET 6/M-9

AAV

SEE DET 10/M-5

TO AST FILL TO AST FILL

SEE DWG M-7

TOP OF

SLAB

NOTE:

CONTRACTOR TO PROVIDE SHOP DWGS AND

PIPE SUPPORT LOCATIONS PLAN.

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L D

E T

A

IL

M-5

GROUNDING REEL DETAIL

SCALE: NTS

M-6

AST FILL CONNECTION DETAIL

SCALE: NTS

M-6

AVGAS FILTER & JET A

FILTER/SEPARATOR DIAGRAM

SCALE: NTS

M-6

CONNECT TO

GROUND GRID AND

TO GROUNDING REEL

GROUND ROD

3/4"x10'L COPPER

CLAD STEEL.

CONNECT TO

ADDITIONAL RODS AS

REQUIRED TO

MAINTAIN A MINIMUM

OF 15 OHMS

RESISTANCE

SECURE TO SLAB

WITH "HILTI"

FASTENER. 2

REQUIRED.

TOP OF SLAB

GROUND REEL W/

CABLE AND CLIP

PLAN

SECTION A

A A4" RISER PIPE

4" INLET OR FILL

DROP TUBE W/ CUT OUT

6" LOCKABLE TIGHT FILL

CAP

6" RISER PIPE

REMOTE PRESSURE FILL

TYPE DROP TUBE W/ 6"

SLC (SOR TYPE)

4" FILL

6" THD CONNECTION

AST

4" OVERFILL

PREVENTION VALVE AND

DROP TUBE

DOUBLE WALL STORAGE

TANK

AST

6"

MARK TOP OF DROP

TUBE W/ LOCATION OF

INLET TEE AND ALIGN

PER MANUF.

INSTRUCTIONS

OVERFILL PREVENTION

VALVE. (REMOTE

PRESSURE FILL TYPE)

DROP TUBE

STRIKER PLATES -

UNDER EQUIPMENT

OPENINGS BY TANK

MANUF.

3/4" AAV, SEE DET 8/M-9

3/4" MAV (BALL VALVE NIPPLE AND CAP)

VESSEL HEAD LIFT AND PIVOT

LOCATE PER PLAN

DIFFERENTIAL PRESSURE

GAUGE

1/4" INSTRUMENT VALVES (TYP

OF 2)

FUEL WATER CONTROL PROBE

CONNECTIONCV

CONTROL VALVE

OUTLET

INLET

FUEL SAMPLING PROBE, SEE DET 7/M-9

3/4" SPRING LOADED TO CLOSE BALL VALVES

TO AST FILL

3/4" TRV, SEE DET 9/M-5

3/4" AAV CHECK VALVE

CAP

1" UNION LOCATED AT

VESSEL HEAD CLOSURE

SIGHT FLOW INDICATOR

FSP

1-1/2" VESSEL DRAIN

DRY DISCONNECT

WHITE BUCKET TEST

DRAIN

NOTES:

1. CONTRACTOR SHALL CONNECT THE CONTROL

VALVE TO THE FUEL WATER CONTROL PROBE IN

STRICT ACCORDANCE W/ MANUF INSTRUCTIONS

WITH S.S. TUBING.

2. CONTRACTOR TO SUBMIT

SHOP DWG. FOR APPROVAL.

WELD 4X4 TEE

SEE DETAIL 9/M-5

PROVIDE ANTI-SIPHON DEVICE

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L D

E T

A

IL

M-6

AVGAS & JET A PIPING

ISOMETRIC DIAGRAM

SCALE: NTS

M-7

AVGAS EQUIPMENT PAD

JET A EQUIPMENT PAD

AVGAS AST 2

JET A AST 1

AAV, TYP. OF 7

SEE DTL 8/M-9

TRV

AVGAS FILTER

SEE DTL 9/M-5

RELOCATED AVGAS

SUMP COLLECTOR

JET A FILTER /

SEPARATOR, SEE

DTL 9/M-5

RELAXATION VESSEL

SEE DTL 10/M-5

AAV

NOTE:

CONTRACTOR TO SUBMIT SHOP DWG

FOR APPROVAL.

SURGE SUPPRESSOR

LPD

HPV

HPV TYP. OF 10

SEE DTL 1/M-5

FLOW METER

LPD

HPV

A/E

HPV

AVGAS VAPOR RECOVERY

SURGE

SUPPRESSOR

LPD

HPV

HPV

FLOW METER

LPD

HPV

A/E

HPV

TRV AND PUMP AAV

DISCHARGE INTO

AVGAS AST FILL

TRV

TRV AAV

SPRING LOADED

BALL VALVE

TRV, TYP. OF 12

SEE DTL 6/M-9

LPD TYP. OF 10

SEE DTL 2/M-5

LPD

TRV

TRV

AAV

TRV

TRVAAV

LPD

TRV

RELOCATED JET A

SUMP COLLECTOR

SPRING LOADED

BALL VALVE

LPD

JET A

ELEVATED

PUMP PAD

AVGAS

ELEVATED

PUMP PAD

AAV

AAV

TRV AND PUMP AAV

DISCHARGE INTO

JET A AST FILL

LPD

HPV

LPD

HPV

STRAINER

STRAINER

AVGAS DRAIN W/

BALL VALVE TYP OF 5

JET A DRAIN W/ BALL

VALVE, TYP OF 5

AST

VAPOR

RECOVERY

AST

FILL

HPV

TRV

AAV

HPV

TRV

AAV

AST

SUCTION

HPV

LPD

TRV

AAV

FSP, TYP. OF 4

SEE DTL 7/M-9

HPV

AST

SUCTION

HPV, TYP. OF 5

SEE DTL 1/M-5 AST

FILL

AAV, TYP OF 5

SEE DTL 8/M-9

TRV, TYP OF 5

SEE DTL 6/M-9

AAV

TRV

AVGAS SELF SERVICE

DISPENSER

LPD

LPD, TYP OF 5

SEE DTL 2/M-5

FSP

FSP

1-1/2" BALL VALVE

LPD ON FUEL PIPE

SEE DTL 4/M-6

LPD ON FUEL PIPE

SEE DTL 4/M-6

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L

IS

O M

E T

R

IC

M-7

A static electric spark can occur when filling portable containers sitting on truck bed liners, or on any vehicle's carpeting or matting.

This spark will explosively ignite a fuel vapor fire and cause SERIOUS INJURY or DEATH.

NEVER fill portable containers that are in or on vehicle.

STATIC ELECTRIC SPARK

EXPLOSION HAZARD

ALWAYS place containers on ground.

Keep nozzle in contact with container while filling.

STATIC ELECTRICITY

WARNING

SCALE: NTS

M-8

NOTE:

PLACE ONE ON EACH SIDE OF EACH FUEL

DISPENSER (PLACE IN A CONSPICUOUS AREA)

COLOR "BLACK"

(UNLESS LABELED OTHERWISE)

COLOR "RED"

COLOR "ORANGE"

COLOR "ORANGE"

INDUSTRY STANDARD STICKER

JET A

FUEL

AVGAS

100 LL

AVGAS AST & EQUIPMENT

LABEL

SCALE: NTS

M-8

JET A AST & EQUIPMENT

LABEL

SCALE: NTS

M-8

COLOR "WHITE"

3"

6"

COLOR "BLACK"

1/8"

COLOR "WHITE"

3"

6"

COLOR "RED"

1/8"

HELVETICA BLACK FONTHELVETICA RED FONT

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L D

E T

A

IL

M-8

THERMAL RELIEF VALVE (TRV)

DETAIL

SCALE: NTS

M-9

NEW 3/4" RELIEF VALVE

W/FLANGED ENDS

(SET AT 150-PSI)

NEW 1" CS

RELIEF PIPING

NEW 3/4" BLIND FLANGE

NEW 3/4" SOCKET WELD TEE (TYP)

NEW 3/4" SOCKET WELD FLANGE

NEW 3/4" BALL VALVE (NORMALLY

OPEN) W/LOCKABLE HANDLE.

ROTATE AS REQUIRED FOR

HANDLE TO CLEAR TEE AND PIPE.

AVGAS FILTER OR JET A FILTER

SEPARATOR, RELAXATION VESSEL, OR

FUEL PIPE DEAD END FLOW

FUEL PIPE

OPEN FLOW

TO AST

ISOLATION VALVE OMITTED FOR

GRAPHIC CLARITY

3/4" SOCKET WELDING

BRANCH CONN. (TYP)

AUTOMATIC AIR VENT (AAV)

DETAIL

SCALE: NTS

M-9

SOCKET WELD

BRANCH CONNECTION

AND PIPE NIPPLE

NIPPLE AND CAP

SOCKET WELD

BALL VALVE

MANUAL VENT

AAV

3/4" AAV CHECK VALVE

DISCHARGE OPEN

FLOW PIPING

SEE DWGS M-3 & M-7

GUARD POST DETAIL

SCALE: NTS

M-9

NO SMOKING AND DANGER

SIGN

SCALE: NTS

M-9

FIRE EXTINGUISHER SIGN

SCALE: NTS

M-9

EFSO SIGN POST DETAIL

SCALE: NTS

M-9

OTHER SIGNAGE

SCALE: NTS

M-9

4'-0"

5'-0"

3"

18"

CONCRETE DOME

6"Ø SCHEDULE 40 STEEL

PIPE. FILL W/ CONCRETE

PAINT YELLOW

FINISH GRADE

CONCRETE BASE

9" 3"

18"

7'- 6"

A

BO

VE

F

IN

IS

H

GR

AD

E

PIPE CAP GALVANIZED

(WELD ALL AROUND)

TYPICAL FOR ALL SIGNAGE.

SIGN MOUNTING HOLES

(TYP)

2" HIGH RED LETTERS W/

WHITE BACKGROUND

EFSO SIGN. 18"Lx9"W

EFSO PULL TYPE OR BREAK

GLASS STATION. (SEE

ELECTRICAL DRAWINGS &

SPECIFICATIONS)

2" GALVANIZED PIPE OR

STRUCTURAL STEEL TUBE

INSTALL 5 FEET INTO GRADE

W/ CONCRETE BASE SIMILAR

TO GUARD POST DETAIL.NOTE:

COORDINATE LOCATION W/ ELECTRICAL DRAWINGS.

9"

18"

4' MIN FROM

FINISHED FLOOR

NOTE:

SECURE TO 2" GALVANIZED PIPE POST.

RED

BACKGROUND

WHITE

LETTERING

WHITE

BACKGROUND

2" HEIGHT

BLACK LETTERS

9"

18" TYP

WHITE

BACKGROUND

RED LETTERS

2" HIGH MIN

TYP OF ALL

SIGNAGE

SECURE TO

2"Ø GALVANIZED

POST TO

HAND RAIL

PROVIDE FIRE

EXTINGUISHER W/

BRACKET (AT

LOCATIONS NOTED

ON PLANS)

NOTE:

1. SECURE SIGN TO 2"Ø GALVANIZED PIPE POST.

2. ALL SIGNS SHALL BE 18"Lx9"W FIBERGLASS.

3. THESE SIGNS SHALL HAVE A WHITE BACKGROUND WITH 2"

BLACK LETTERS.

4. CONTRACTOR SHALL CONTACT OPERATOR FOR

PROCEDURES AND EMERGENCY INFORMATION FOR SIGNS.

5. TERMINATE 4'Lx2"Ø GALVANIZED POST WITH FLANGE. BOLT

TO EQUIPMENT PAD SUPPORT PLATE.

6. TERMINATE 9'Lx2"Ø GALVANIZED POST 5 FEET INTO GRADE

WITH CONCRETE BASE SIMILAR TO GUARD POST DETAIL.

7. SECURE SIGNS TO PIPE WITH STRAP.

22 23 24

19 20 21

FUEL SAMPLING POINT

CONNECTION DETAIL

SCALE: NTS

M-9

1/2 D

D FUEL PIPECL

1/4" S.S. QUICK DISCONNECT

COUPLER, MNPT END.

3/4"x1/4" REDUCING BUSHING

3/4" BRANCH CONNECTION

1/4" S.S. SAMPLE PROBE.

45° CUT IN DIRECTION OF FLOW

1/4" BALL VALVE

FNPT ENDS.

WELD

NOTES:

1. REFER TO FLOW DIAGRAM FOR QTY. AND LOCATION OF HIGH POINT VENTS, LOW

POINT DRAINS, AND FUEL SAMPLING PROBES.

2. INSTALL IN ACCORDANCE TO MANUFACTURER RECOMMENDATION.

PROVIDE ADDITIONAL SIGN

INSIDE OPS BLDG COORD /W

OPERATOR

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 4-29-2024

This document originally issued by TECS LLC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

B R

U C

E M

. K E

L L

Y , P

.E

M

EM

O R

IA

L

H W

Y

SU

IT

E

TA

M

PA

, F L

(8

) 3

-7

BID SET

THIS ITEM HAS BEEN DIGITALLY SIGNED AND

SEALED BY BRUCE M. KELLEY, PE ON THE DATE

ADJACENT TO THE SEAL. PRINTED COPIES OF

THIS DOCUMENT ARE NOT CONSIDERED SIGNED

AND SEALED AND THE SIGNATURE MUST BE

VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

M E

C H

A N

IC

A

L

SI

G N

A G

E

M-9

EL

EC

TR

IC

AL

LE

AD

-IN

S

HE

ET

E-1

A V

IA

T

IO

N

FU

E

L F

A R

M R

E

PL

A C

E M

E N

T

PR

O

JE

C T

2-

Dwg. No.

DATE: 04-29-2024

This document originally issued by PHOENIX ENGINEERING GROUP, INC.

This document should not be considered a certified document unless embossed and signed by a licensed engineer. SCALE: AS SHOWN

100% SUBMITTAL

Su ite w w w .p ho en ix en g.

us t.8

.9

.0 f.8

.3

.0

En gi ne er in g

Li ce ns e

N o.

N

. D al e M ab ry

Ta m pa , F

L

8PH

O

EN

IX

EN

G

IN

EE

RI

N G

G

RO

UP

M ec ha ni ca l

El ec tri

Pl um bi ng

F ire

P ro te ct io n

Pr oc es s on st ru ct io n Ad m in is tra tio n

T M

L I C EN S E

THIS ITEM HAS BEEN DIGITALLY SIGNED AND SEALED BY RHETT R.

JACKSON, PE ON THE DATE ADJACENT TO THE SEAL. PRINTED COPIES

OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND

THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

W . I

D

LE

W

IL

D A

V E, SU

IT

E

TA

M

PA

, F L

(8

) 3

-2

C

ER

T.

O

F A

U

TH

Z.

N

O .3

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text No. 53250

AutoCAD SHX Text

STATE OF

AutoCAD SHX Text

%%UABBREVIATIONS

AutoCAD SHX Text

TERMINAL CABINET- SURFACE MTD.

AutoCAD SHX Text

PULL BOX

AutoCAD SHX Text

REVISION NUMBER

AutoCAD SHX Text

SHEET NOTE INDICATOR

AutoCAD SHX Text

INDICATES SECTION NUMBER SECTION REFERENCE TAG

AutoCAD SHX Text

INDICATES DRAWING IN WHICH SECTION APPEARS

AutoCAD SHX Text

CONNECTION POINT OF NEW TO EXISTING

AutoCAD SHX Text BRANCH CIRCUIT HOMERUN TO PANELBOARD PNL-1 IS PANEL DESIGNATION 10 IS CIRCUIT DESIGNATION EACH CIRCUIT CONSISTS OF (2)#12, (1)#12 EG, 3/4"C UNO

AutoCAD SHX Text UNLESS NOTED ON PLAN REFER TO STANDARD MOUNTING HEIGHTS BELOW. UNLESS OTHERWISE NOTED MOUNTING HEIGHTS ARE TO CENTERLINE OF BOX. UNLESS OTHERWISE NOTED, MOUNTING HEIGHTS FOR LIGHT FIXTURES ARE TO BOTTOM ON FIXTURE.

AutoCAD SHX Text

%%UMOUNTING HEIGHTS

AutoCAD SHX Text USE OF SYMBOLS AND ABBREVIATIONS: 1. NOT ALL SYMBOLS, ABBREVIATIONS AND EQUIPMENT ABBREVIATIONS INDICATED APPEAR ON THESE CONTRACT DRAWINGS. INDIVIDUAL DRAWINGS MAY HAVE SHEET LEGENDS OR SYMBOL DESCRIPTIONS FOR UNIQUE SYMBOLS AND/OR FOR CONVENIENCE. COMMISSIONING 1. COMMISSION ELECTRICAL SYSTEMS IN THE OWNER'S PRESENCE ACCORDING TO NECA 90 COMMISSION ELECTRICAL SYSTEMS IN THE OWNER'S PRESENCE ACCORDING TO NECA 90 STANDARDS/RECOMMENDATIONS. 2. VERY PHASE ROTATION FOR ALL THREE-PHASE OUTLETS AND DISCONNECTS PRIOR TO ENERGIZING VERY PHASE ROTATION FOR ALL THREE-PHASE OUTLETS AND DISCONNECTS PRIOR TO ENERGIZING EQUIPMENT. OWNER SHALL FURNISH TEST EQUIPMENT FOR SAID TESTING.

AutoCAD SHX Text

MOTOR RATED SWITCH SIZE (A)/POLES/ENCLOSURE RATING

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text X/X/X

AutoCAD SHX Text

MATCH EXISTING

AutoCAD SHX Text

EXISTING TO BE RELOCATED - NEW LOCATION

AutoCAD SHX Text

EXISTING TO BE RELOCATED - EXISTING LOCATION

AutoCAD SHX Text

EXISTING TO BE DEMOLISHED

AutoCAD SHX Text

EXISTING TO REMAIN

AutoCAD SHX Text

TERMINATION POINT OF DEMOLITION

AutoCAD SHX Text

(ME)

AutoCAD SHX Text

(ERN)

AutoCAD SHX Text

(ERE)

AutoCAD SHX Text

(ED)

AutoCAD SHX Text

(EX)

AutoCAD SHX Text

INDICATES DRAWING IN WHICH DETAIL APPEARS

AutoCAD SHX Text

INDICATES DETAIL NUMBER DETAIL REFERENCE TAG

AutoCAD SHX Text

EQUIPMENT IDENTITY TAG

AutoCAD SHX Text

FUTURE ITEM

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

PNL-1/10

AutoCAD SHX Text

%%UREFERENCE

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

CONDUIT/WIRE UNDERSLAB OR UNDERGROUND

AutoCAD SHX Text LIGHT SWITCH FOR INDUSTRIAL APPLICATIONS SS COVER PLATE. WP=WATERPROOF INCL SS HINGED COVER, DP=DUSTPROOF WITH CLEAR RUBBER BOOT SHIELDING TOGGLE.

AutoCAD SHX Text

VOLTAGE TRANSFORMER WITH CONCRETE PAD

AutoCAD SHX Text

BRANCH CIRCUIT PANELBOARD-FLUSH MTD

AutoCAD SHX Text

POWER PANEL SURFACE MOUNTED

AutoCAD SHX Text

LIGHTING CONTACTOR

AutoCAD SHX Text

FOUR-WAY SWITCH 20 AMP, 125/277 VOLT

AutoCAD SHX Text

TWO-POLE SWITCH 20 AMP, 125/277 VOLT

AutoCAD SHX Text

SPECIAL PURPOSE LOCKING RECEPTACLE, IN FLOOR BOX NEMA CONFIGURATION AS INDICATED

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R SINGLE, IN FLOOR BOX

AutoCAD SHX Text RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R QUADRUPLEX, PEDESTAL OR LAB BENCHTOP MOUNTED

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX - SPLIT WIRED

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R SINGLE

AutoCAD SHX Text

PIS=PIN IN SLEEVE

AutoCAD SHX Text

TL=TWIST LOCK

AutoCAD SHX Text RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX, PEDESTAL OR LAB BENCHTOP MOUNTED

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UTILITY METER

AutoCAD SHX Text

MOTOR #=MOTOR HORSEPOWER

AutoCAD SHX Text

CONTROL PANEL

AutoCAD SHX Text

TERMINAL CABINET- RECESSED MTD.

AutoCAD SHX Text

ENCLOSED CIRCUIT BREAKER, SIZE/POLES/ENCLOSURE TYPE

AutoCAD SHX Text

VARIABLE FREQUENCY DRIVE CONTROLLER

AutoCAD SHX Text

JUNCTION BOX HP=MOTOR HORSEPOWER

AutoCAD SHX Text

MANUAL MOTOR STARTER WITH OVERLOAD AND PILOT LIGHT

AutoCAD SHX Text MOTOR STARTER/CONTROLLER, WITH LOCAL DISCONNECT, U.O.N. TYPE/NEMA STARTER SIZE/POLES/ENCLOSURE TYPE. DISCONNECTING MEANS: CB=CIRCUIT BREAKER F=FUSED SWITCH

AutoCAD SHX Text J

AutoCAD SHX Text

VFD

AutoCAD SHX Text

PB

AutoCAD SHX Text J

AutoCAD SHX Text X/X/X/X

AutoCAD SHX Text X/X/X

AutoCAD SHX Text

TC

AutoCAD SHX Text

TC

AutoCAD SHX Text

AutoCAD SHX Text

CP

AutoCAD SHX Text DISCONNECT SWITCH RATING/FUSING/POLES/ENCLOSURE TYPE. WHERE "F" IS SHOWN FOR FUSING RATING/FUSING/POLES/ENCLOSURE TYPE. WHERE "F" IS SHOWN FOR FUSING SIZE FUSE PER EQUIPMENT NAMEPLATE DATA. NF=NON-FUSED

AutoCAD SHX Text X/X/X/X

AutoCAD SHX Text

%%UPOWER

AutoCAD SHX Text

THREE-WAY SWITCH 20 AMP, 125/277 VOLT

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING EQUIPMENT OR FEEDER TO BE REMOVED

AutoCAD SHX Text

EXISTING EQUIPMENT OR FEEDER TO REMAIN

AutoCAD SHX Text

VOLTAGE TRANSFORMER

AutoCAD SHX Text

BRANCH CIRCUIT PANELBOARD-SURFACE MTD

AutoCAD SHX Text

DISTRIBUTION PANELBOARD SURFACE MOUNTED

AutoCAD SHX Text

DIMMER SWITCH, SEE PLANS FOR WATTAGE RATING, VOLTAGE TO MATCH APPLICATION.

AutoCAD SHX Text T

AutoCAD SHX Text

TIME CLOCK

AutoCAD SHX Text

TC

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text

%%UWIRING

AutoCAD SHX Text T

AutoCAD SHX Text

%%UPOWER DISTRIBUTION

AutoCAD SHX Text

WP

AutoCAD SHX Text S

AutoCAD SHX Text X

AutoCAD SHX Text

LC

AutoCAD SHX Text

SINGLE POLE SWITCH 20 AMP, 125/277 VOLT

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R QUADRUPLEX, IN FLOOR BOX

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX, IN FLOOR BOX

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text

%%ULIGHTING

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text SPECIAL PURPOSE RECEPTACLE, 480V, NEMA TYPE CONFIGURATION OR ELECTRICAL REQUIREMENTS WITH CONFIGURATION TO MATCH APPLICATION.

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DOUBLE DUPLEX-QUADRUPLEX

AutoCAD SHX Text

RECEPTACLE - 20 AMP, 125 VOLT NEMA 5-20R DUPLEX

AutoCAD SHX Text

WP=WATER/WEATHER PROOF

AutoCAD SHX Text

#=NUMBER INDICATES CIRCUIT NUMBER

AutoCAD SHX Text

GFI=GROUND FAULT CIRCUIT INTERRUPTER

AutoCAD SHX Text

AutoCAD SHX Text L6-30

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

30A/3P/TL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

%%URECEPTACLES

AutoCAD SHX Text

RECEPTACLE NOMENCLATURE:

AutoCAD SHX Text

CONDUIT CONCEALED IN WALL OR CEILING

AutoCAD SHX Text

EXPOSED CONDUIT

AutoCAD SHX Text

PANEL BOARDS - LIGHTING AND RECEPTACLE

AutoCAD SHX Text

NEW

AutoCAD SHX Text (N)

AutoCAD SHX Text

OCCUPANCY SENSOR LIGHTING CONTROLLER, WALL MOUNT

AutoCAD SHX Text S

AutoCAD SHX Text

OS

AutoCAD SHX Text

80" A.F.F. TO BOTTOM OF STROBE OR 6" BELOW CLG WHICHEVER IS LOWER

AutoCAD SHX Text 18" A.F.F.

AutoCAD SHX Text 48" A.F.F.

AutoCAD SHX Text

72" AFF TO TOP OF PANEL

AutoCAD SHX Text 48" A.F.F.

AutoCAD SHX Text

RECEPTACLE AND WALL COMM. JACKS - GENERAL

AutoCAD SHX Text

LIGHT SWITCHES - GENERAL

AutoCAD SHX Text

FIRE ALARM STROBE, HORN/STROBE

AutoCAD SHX Text

FIRE ALARM PULL STATION

AutoCAD SHX Text S

AutoCAD SHX Text

OS

AutoCAD SHX Text

AutoCAD SHX Text OCCUPANCY SENSOR LIGHTING CONTROLLER, CEILING MOUNT. NUMBER INDICATES ANGLE OF COVERAGE

AutoCAD SHX Text SPECIAL PURPOSE RECEPTACLE, 208V OR 240V, NEMA TYPE CONFIGURATION OR ELECTRICAL REQUIREMENTS WITH CONFIGURATION TO MATCH APPLICATION.

AutoCAD SHX Text AC ABOVE COUNTER ABOVE COUNTER AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFC ABOVE FINISHED GRADE ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIR HANDLING UNIT AIC AMPERE INTERRUPT CAPACITY AMPERE INTERRUPT CAPACITY AM AMMETER AMMETER ANN ANNUNCIATOR ANNUNCIATOR AS AMMETER SWITCH AMMETER SWITCH AT AMPERE(S) TRIP AMPERE(S) TRIP ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH AUX AUXILIARY AUXILIARY AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BAS BUILDING AUTOMATION SYSTEM BUILDING AUTOMATION SYSTEM BC BELOW COUNTER BELOW COUNTER BFC BELOW FINISHED CEILING BELOW FINISHED CEILING BFE BASE FLOOD ELEVATION BASE FLOOD ELEVATION BFG BELOW FINISHED GRADE BELOW FINISHED GRADE BKR BREAKER BREAKER C CONDUIT CONDUIT CAT CATEGORY CATEGORY CB CIRCUIT BREAKER CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CLOSED CIRCUIT TELEVISION CKT CIRCUIT CIRCUIT CL CURRENT LIMITING CURRENT LIMITING CMP COMMUNICATIONS CABLE PLENUM RATED COMMUNICATIONS CABLE PLENUM RATED CMR COMMUNICATIONS CABLE RISER RATED COMMUNICATIONS CABLE RISER RATED COMM COMMUNICATIONS COMMUNICATIONS CT CURRENT TRANSFORMER CURRENT TRANSFORMER DE DUAL ELEMENT DUAL ELEMENT DN DOWN DOWN DSW DISCONNECT SWITCH DISCONNECT SWITCH DT DOUBLE THROW DOUBLE THROW DWG DRAWING DRAWING EM EMERGENCY EMERGENCY EC ELECTRICAL CONTRACTOR ELECTRICAL CONTRACTOR EF EXHAUST FAN EXHAUST FAN EFSO EMERGENCY FUEL SHUTOFF EMERGENCY FUEL SHUTOFF EG ELECTRICAL GROUND ELECTRICAL GROUND EMT ELECTRIC METALLIC TUBING ELECTRIC METALLIC TUBING EOL END OF LINE (RESISTOR) END OF LINE (RESISTOR) ES END SWITCH END SWITCH EVH ELECTRIC UNIT HEATER ELECTRIC UNIT HEATER EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER ELECTRIC WATER HEATER F FUSE, FUSED FUSE, FUSED FA FIRE ALARM FIRE ALARM FACP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL FARA FIRE ALARM REMOTE ANNUNCIATOR FIRE ALARM REMOTE ANNUNCIATOR FCU FAN COIL UNIT FAN COIL UNIT FLUOR FLUORESCENT FLUORESCENT FO FIBER OPTIC FIBER OPTIC FVNR FULL VOLTAGE NON-REVERSING FULL VOLTAGE NON-REVERSING FWE FURNISHED WITH EQUIPMENT FURNISHED WITH EQUIPMENT GA GAUGE GAUGE GFI GROUND FAULT (CIRCUIT) INTERRUPTER GROUND FAULT (CIRCUIT) INTERRUPTER GFP GROUND FAULT PROTECTION GROUND FAULT PROTECTION GND,GRD GROUND GROUND GRS GALVANIZED RIGID STEEL GALVANIZED RIGID STEEL HH HAND HOLE HAND HOLE HID HIGH INTENSITY DISCHARGE HIGH INTENSITY DISCHARGE HDA HAND-OFF-AUTO HAND-OFF-AUTO HP HORSEPOWER HORSEPOWER HT HEAT TRACE HEAT TRACE HTT HIGH TEMPERATURE HEAT TRACE HIGH TEMPERATURE HEAT TRACE HV HIGH VOLTAGE HIGH VOLTAGE HZ HERTZ HERTZ IAW IN ACCORDANCE WITH IN ACCORDANCE WITH IMC INTERMEDIATE METAL CONDUIT INTERMEDIATE METAL CONDUIT INC INCANDESCENT INCANDESCENT JB JUNCTION BOX JUNCTION BOX KV KILOVOLTS KILOVOLTS KVA KILOVOLTS-AMPERE KILOVOLTS-AMPERE KVAR KILOVAR KILOVAR KW KILOWATTS KILOWATTS KWH KILOWATT-HOUR KILOWATT-HOUR LC LIGHTING CONTACTOR LIGHTING CONTACTOR LTS LIGHT(S) LIGHT(S) mA MILLIAMPERE MILLIAMPERE MAX MAXIMUM MAXIMUM MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MOTOR CIRCUIT PROTECTOR MH MANHOLE MANHOLE MIN MINIMUM MINIMUM MLO MAIN LUG ONLY MAIN LUG ONLY MOA MULTI-OUTLET ASSEMBLY MULTI-OUTLET ASSEMBLY MTD MOUNT, MOUNTED MOUNT, MOUNTED MTS MANUAL TRANSFER SWITCH MANUAL TRANSFER SWITCH N NEUTRAL NEUTRAL N1 NEMA-1 NEMA-1 N3R NEMA-3R NEMA-3R N4X NEMA-4X NEMA-4X N4X SS NEMA-4X STAINLESS STEEL NEMA-4X STAINLESS STEEL N12 NEMA-12 NEMA-12 N.C. NORMALLY CLOSED NORMALLY CLOSED NAC NOTIFICATION APPLIANCE CIRCUIT NOTIFICATION APPLIANCE CIRCUIT NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NF NON-FUSED NON-FUSED NIC NOT IN CONTRACT NOT IN CONTRACT N.O. NORMALLY OPEN NORMALLY OPEN No. NUMBER NUMBER NTS NOT TO SCALE NOT TO SCALE OC ON CENTER ON CENTER OFNP OPTICAL FIBER NONCONDUCTIVE PLENUM OPTICAL FIBER NONCONDUCTIVE PLENUM OFNR OPTICAL FIBER NONCONDUCTIVE RISER OPTICAL FIBER NONCONDUCTIVE RISER OH OVERHEAD OVERHEAD OL OVERLOAD OVERLOAD P POLE POLE PA/E PROJECT ARCHITECT/ENGINEER PROJECT ARCHITECT/ENGINEER PB PULL BOX PULL BOX PH PHASE PHASE PNL PANEL/PANELBOARD PANEL/PANELBOARD PRI PRIMARY PRIMARY PT POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE POLYVINYL CHLORIDE RE REFERENCE REFERENCE RCP RECEPTACLE(S) RECEPTACLE(S) RGSC RIGID GALVANIZED STEEL CONDUIT RIGID GALVANIZED STEEL CONDUIT RMS ROOT MEAN SQUARE ROOT MEAN SQUARE RR REMOVE AND REPLACE REMOVE AND REPLACE SBJ SERVICE BONDING JUMPER SERVICE BONDING JUMPER SD SMOKE DETECTOR SMOKE DETECTOR SEC SECONDARY SECONDARY SF SUPPLY FAN SUPPLY FAN SLC SIGNAL LINE CIRCUIT SIGNAL LINE CIRCUIT SQFT SQUARE FOOT SQUARE FOOT SS STAINLESS STEEL STAINLESS STEEL STP SHIELDED TWISTED PAIR SHIELDED TWISTED PAIR ST SINGLE THROW SINGLE THROW SW SWITCH SWITCH SWBD SWITCHBOARD SWITCHBOARD SWGR SWITCHGEAR SWITCHGEAR TEL TELEPHONE TELEPHONE TL TWIST LOCK TWIST LOCK TS TIME SWITCH TIME SWITCH TTB TELEPHONE TERMINAL BOARD TELEPHONE TERMINAL BOARD TYP TYPICAL TYPICAL uM MICRON MICRON UNO UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE UON UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED UTP UNSHIELDED TWISTED PAIR UNSHIELDED TWISTED PAIR V VOLTS VOLTS VFD VARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE VIF VERIFY IN FIELD VERIFY IN FIELD W WATTS WATTS W/ WITH WITH WP WEATHERPROOF/WATER PROOF WEATHERPROOF/WATER PROOF XFMR TRANSFORMER TRANSFORMER 1P ONE POLE ONE POLE 2P TWO POLE TWO POLE 3P THREE POLE THREE POLE PHASE

AutoCAD SHX Text

XP=NEC CLASSIFIED UON: CLASS 1, DIV 1 GROUPS A,B,C,D,

AutoCAD SHX Text

GROUND

AutoCAD SHX Text GENERAL 1. THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE "CONTRACTOR" SHALL PROVIDE THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE "CONTRACTOR" SHALL PROVIDE COMPLETE AND PROPERLY FUNCTIONING ELECTRICAL SYSTEMS AS INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. 2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND INSPECTIONS REQUIRED TO CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND INSPECTIONS REQUIRED TO COMMENCE AND COMPLETE ELECTRICAL WORK. 3. CONTRACTOR SHALL CONDUCT A THOROUGH SITE INSPECTION TO FAMILIARIZE HIMSELF WITH CONTRACTOR SHALL CONDUCT A THOROUGH SITE INSPECTION TO FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS AND ALL ASPECTS OF HIS SCOPE OF WORK. SUCH AN INSPECTION SHALL BE CONDUCTED PRIOR TO BIDDING. 4. THIS CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO THIS CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PROCEEDING WITH ANY WORK. IF DISCREPANCIES OCCUR BETWEEN THESE DOCUMENTS AND EXISTING, THE CONTRACTOR SHALL REPORT SAID DISCREPANCY TO THE OWNER AND/OR ENGINEER FOR EXPEDITING AND RESOLUTION. CONTINUATION OF WORK BEFORE RESOLUTION IS GIVEN SHALL BE AT THE CONTRACTORS RISK. 5. THE CONTRACTOR SHALL PROVIDE DROP CLOTHS, RUBBER MATS AND, PLYWOOD COVERS TO THE CONTRACTOR SHALL PROVIDE DROP CLOTHS, RUBBER MATS AND, PLYWOOD COVERS TO PROTECT OWNER'S EQUIPMENT FROM DAMAGE DURING CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S REPRESENTATIVE. 6. ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE OWNER. SCHEDULE ALL ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE OWNER. SCHEDULE ALL WORK WITH THE OWNER'S REPRESENTATIVE BEFORE PROCEEDING. 7. ALL ACTIVITIES ASSOCIATED WITH CONSTRUCTION OF THIS FACILITY SHALL COMPLY WITH OSHA ALL ACTIVITIES ASSOCIATED WITH CONSTRUCTION OF THIS FACILITY SHALL COMPLY WITH OSHA GUIDELINES. 8.