Inspection Reports Ph3.pdf
PDF 410 KB Posted
- Attached to
- C1DA--518-22-111 Elevator Replacement Ph 3, A/E Federal contract opportunity
- Solicitation number
- 36C24123Q0307
About this file
This solicitation is seeking qualifications from Service-Disabled Veteran-Owned Small Businesses to provide Architect/Engineer design services for an elevator replacement project at the Bedford VA Medical Center in Bedford, Massachusetts. The scope of work includes evaluating six elevators and developing design plans and specifications to replace them within a $4 million construction budget. Interested SDVOSBs must submit SF-330 qualification statements by March 2nd, 2023 demonstrating experience with similar elevator replacement or medical facility projects, past performance references, and staff qualifications in engineering design. Submissions must also provide evidence that the SDVOSB will perform over 50% of the work. The selection process will evaluate qualifications and then request a price proposal from the most qualified firm.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx | DOCX document | |
| Bldg 7 Site plans.pdf | ||
| Bldg 62 Site plans.pdf | ||
| Bldg 9 Site plans.pdf | ||
| 518-22-111 Replace Elevators Ph 3 SOW.pdf | ||
| FCA by Building.xlsx | XLSX spreadsheet | |
| Elevators Assessment per Bldg.xlsx | XLSX spreadsheet | |
| Bldg 10 Site plans.pdf | ||
| 36C24123Q0307.docx | DOCX document | |
| Elevator Inventory_1-19-22.xlsx | XLSX spreadsheet | |
| Bldg 6 Site plans.pdf | ||
| CRG_Detailed_Customer_Procedures_Attachment_1_A-E_Procurements.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPORT OF INSPECTION OF ELEVATORS DATE OF INSPECTION
03 Mar 2021
TO
Director Field Operations Region No._________(138) Veterans Administration Central office Washington, D.C. 20420
Name and Location of Station
VAMC Bedford MA
Building Name and Number
Building 06 No. of stops
No. of Openings
Elevator number and type
P - 1 GEARED TRACTION PASSENGER V3F
Rated Capacity
LBS: 3000 PERSONS 20
Manufacturer Serial No. and year installed
ELEVATOR CONTROLS CORP SER:18988 2010
Rated Speed (fpm)
Actual Speed (fpm-tach)
1. CONDITION OF EQUIPMENT (Check)
ITEM GOOD FAIR POOR ITEM GOOD FAIR POOR
MACHINE
X
ELECTRONIC TUBES & TRANSISTORS
WORM AND GEAR
RESISTANCES
WORM AND GEAR THRUST BEARING
RECTIFIERS
SHEAVE SHAFT BEARINGS
CONTACT INSULATORS
WORM SHAFT PACKING AND SEALS
CONTACT HOLDERS
BEDPLATE
CONTACT SPRINGS
MAIN MOTOR
BRAIDED & WIRE CONNECTORS
MOTOR FIELDS, BRUSHES & HOLDERS
N/A
MACHINE ROOM VENTILATION
COMMUTATOR AND SLIP RINGS
ELECTRIC WIRING
MOTOR GENERATOR
LIGHTING IN MACHINE ROOM
EXCITER
HEATING IN MACHINE ROOM
X
MOTOR GENERATORS FIELD,
BRUSHES AND HOLDERS
N/A CLEARANCE AROUND MACHINE ROOM
EQUIPMENT
BRAKE, PINS, LINING, DRUM
MAIN LINE SWITCH LOCATION
GOVERNOR AND RELEASING CARRIER
CONDITION OF MACHING ROOM FLOOR
SELECTOR, CABLE, SWITCH AND TAPE
GUARDING OF EXPOSED EQUIPMENT
CONTROLLER
PROJECTIONS, RECESSES
RELAY PANELS
HOISTWAY VENTING
RELAYS AND CONTACTS
PIT LADDER
OVERLOADS
GROUNDING OF EQUIPMENT
FUSES AND FUSE LINKS
ELECTRICAL PROTECTIVE DEVICES
MAGNET COILS
CYLINDER AND PLUNGER
CAPACITORS
PUMPS, VALVES, PIPING AND TANKS
N/A
VAFORM 10-6166 SUPERSEDES VA FORM 10-6166, MAY 1972, WHICH WILL NOT BE USED.
MAY 1974
1. CONDITION OF EQUIPMENT (CONTINUED)
CROSSHEAD, SHOES, CARTOP
CAR ENCLOSURE
X
CAR DOORS, OPERATOR & RESTRICTOR
X
CAR OPERATING PANEL
X
GUIDE RAILS AND SUPPORTS
X
CAR CANOPY
X
OVERHEAD BEAMS
X
CAR EMERGENCY EXIT CONTACTS
X
SHEAVES AND BEARINGS
X
CAR FLOORING
X
HANGERS AND DOOR GIBS
X
CAR EMERGENCY LIGHTING
X
INTERLOCKS AND CLOSERS
X
CAR VENTILATIONS
X
LEVELING SWITCHES AND VANES
X
CAR CAPACTIY PLATE
X
TOP CAR OPERATING DEVICE
X
CAR TELEPHONE BOX
X
TRAVELING CABLE
X
CAR CERTIFICATE FRAME
N/A
LIMIT SWITCHES
X
HOISTWAY DOOR PANELS AND FRAMES
X
CWT, TIE RODS, AND COTTER PINS
X
HANGER COVERS
X
BUFFERS (CAR AND CWT)
X
FASCIA PLATES
X
GUARD FOR CONTERWIGHT
X
TOE GUARDS
X
GOVERNOR TENSION SHEAVE & GAURD
X
HEADERS
X
GOVERNOR TENSION SHEAVE WEIGHT
X
HOISTWAY SILLS
X
SAFETY
X
FIREPROOFING UNDER PLATFORM
X
PIT ACCESS DOOR
N/A
NUMERAL ON EQUIPMENT
X
CAR PHOTO-ELECTRIC RAYS
X
HALL LANTERNS
X
CAR DOORS CONTACTS
X
HALL PUSH BUTTONS
X
CAR SAFETY EDGE
X
DISPATCHING PANEL
N/A
FACEPLATES AT STATIONS
X
HOISTWAY ACCESS SWITCH
X
CAR POSITION INDICATOR
X
PAINTING OF EQUIPMENT
X
HALL POSITION INDICATOR
X
EMERGENCY ELECTRIC POWER EQUIPMENT
X
ARE MANUAL AND PARTS LIST AVAILABLE?
[ X ] Yes [ ] No
ARE TOOLS AVAILABLE?
[ ]Yes [ ] No
2. CONDITION OF ROPES
LOCATION MATERIALS NUMBER SIZE AND
CONSRUCTION
USED LIFE
(in months)
EST. ADD. LIFE
(in months)
NO. OF BROKEN WIRES (Per Rope Lay)
HOISTING T.S. 4 5/8 – 8x19
DRUM COUNTERWEIGHT
CAR COUNTERWEIGHT
GOVERNOR – CAR T.S 1 3/8 – 8x19
GOVERNOR – CWT
COMPENSATING
SAFETY
CONTRACT NO.
36C24121P0254
NAME OF CONTRACT COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY That the contractor has complied with all requirements of the contract and specifications.
DATE SIGNATURE OF ENGINEER OFFICER SIGNATURE OF DIRECTOR
Use blank sheet for any remarks and/or recommendations and attach to this report.
REPORT OF TEST OF ELEVATOR GOVERNOR AND
SAFETY DEVICE
DATE OF TEST
Regional Medical Director Region No._________(138) Veterans Administration Central Office
NAME AND LOCATION OF STATION
TEST (Check)
[ X ] ANNUAL
[ ] FIVE YEARS (See contract specifications) [ ] THREE YEARS (HYDRAULIC) (See contract specifications)
BUILDING NAME AND NO.
Building 06
ELEVATOR NUMBER AND TYPE
P-1 GEARED TRACTION
RATED CAPACITY
LBS: 3000 PERSONS: 20
MAUFACTURER SERIAL NO. AND YEAR INSTALLED
ELEVATOR CONTROLS CORP SER:18988 2010
RATED SPEED (FPM)
ACTUAL SPEED (FPM-TACH.)
SAFETY (See rule 205.5 code A17/1-1971 and below) OTHER
[ ] TYPE A [ X ] TYPE B [ ] TYPE C [ ] BROKEN ROPE [ ] (SPECIFY)
IS SAFETY VALVE PROPERLY SET?
[ ] YES [ ] NO
DISTANCE CAR SLIDES AFTER
SAFETY IS APPLIED TO RAIL
FT IN.
MARK ON RAIL
LEFT RIGHT
[X ] RAIL [X ] RAIL FT IN
DISTANCE GOVERNOR ROPE
SLIDES THROUGH JAWS.
0 FT 0 IN
CONDITION OF GOVERNOR JAWS
[X ] GOOD [ ] FAIR [ ] POOR
ROPE FROM DRUM IN TEST
FT IN
NO. OF TURNS REMAINING ON
DRUM
WAS PLATFORM OUT OF LEVEL
AFTER TEST?
[ ] YES [ X ] NO (If “Yes,” how much)
WAS CAR FRAME SPRUNG AFTER
TEST? (If “Yes,” specify whether left or right)
[ ] YES [X ]NO
DAMAGE RESULTING FROM TEST
DID DAMAGE OCCUR TO THE FOLLOWING?
CAR GUIDES ROPES RAILS CLAMPS BRACKETS SAFETY
[ ] YES [ X ] NO [ ] YES [X ] NO [ ] YES [ ] NO [ ] YES [X ] NO [ ] YES [ X] NO [ ] YES [X] NO
ANY LOSS OF BUFFER OIL IN TYPE C SAFETIES?
[ ] YES [X] NO
WAS RELEASING CARRIER PROPERLY ADJUSTED?
[X ]YES [ ] NO
ARE GUIDES FIRMLY SECURED TO CAR
FRAMES?
[X] YES [ ] NO
DID SAFETY PARTS ON CAR FRAME SHOW FOREIGN OBSTRUCTION? NO
[ ] RUST [ ] LACK OF ATTENTION
[ ] CORROSION [ ] DAMPNESS [ ] OTHER (other please specify)
GOVERNOR
ALL PARTS FREE FROM—
PAINT? RUST? CORROSION?
[ X ] YES [ ] NO [X ] YES [ ] NO [X] YES [ ] NO
WAS GOVERNOR PROPERLY LUBRICATED?
[X] YES [ ] NO
WAS THERE AMPLE FLY WEIGHT SPACE BETWEEN WALL AND
GOVERNOR? [X] YES [ ] NO
WERE THERE ANY SEALS ON THE GOVERONR?
[X] YES [ ] NO
WERE SPRING NUT LOCKS OR KEYS PROPERLY SECURED AND
SEALED? [X] YES [ ] NO
DID GOVERNOR JAWS DROP OF OWN WEIGHT WHEN LATCH WAS
RELEASED? [X] YES [ ] NO
DO BEARING OR GEARS SHOW EXCESSIVE WEAR?
[ ] YES [X] NO
WAS TENSION IDLER FREE IN FRAME GUIDES AND IN ITS SHAFT?
[X] YES [ ] NO
IS PROPER SIZE GOVERNOR ROPE BEING USED?
[X] YES [ ] NO
IS THE PROPER TYPE OF ROPE USED?
[X] YES [ ] NO
REMARKS
NOTE: SAFETIES SHALL BE SUBJECT TO AN ANNUAL RUNNING TES WITH NO LOAD IN THE CAR AS FOLLOWS:
APPLICABLE RULE OF ANSI.—CODE
TEST OF SAFETIES A17.1 1971
1. TUPE A, B, OR C GOVERNOR – OPERATED SAFETIES. 1001.4a1
2. WOOD GUIDE GOVERNOR – OPERATED SAFETIES 1001.4a1
3. TYPE A AND WOOD GUIDE SAFETIES WITHOUT GOVERNORS OPERATED ONLY AS A RRESULT OF THE BREAKING OR SLACKENING OF THE HOISTING ROPES 1001.4a3
CONTRACT NO.
36C24121P0254
NAME OF CONTRACTING COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY that the contractor has complied with all requirements of the contract and specifications
Use reverse for any Remarks and/or recommendations
2021030901 ©2021 enDevelopment LLC. All rights reserved. 1 enDevelopment LLC
Montgomery NY, 12549
Building 06 Car P – 1
Deficiencies
Replace burned out machine room lights and properly guard
Clean machine room from construction dust
Provide Code Data Plate
Clean hoistway and car top from construction dust
Provide spin outs
Adjust restrictor for proper operation
Adjust top access down lmit for proper distance. Top of car should stop level with top landing
Replace cover on up slowdown limit switch
Remove old lighting wires from hoistway at midpoint
Repair pit light
Properly secure pit ladder
Region No._________(138) Veterans Administration Central office
Building 07 No. of stops
No. of Openings
Elevator number and type
P - 1 GEARED TRACTION PASSENGER V3F
ELEVATOR CONTROLS CORP SER:18987 2010
Rated Speed (fpm)
HEATING IN MACHINE ROOM
X
MOTOR GENERATORS FIELD,
BRUSHES AND HOLDERS
N/A CLEARANCE AROUND MACHINE ROOM
PUMPS, VALVES, PIPING AND TANKS
N/A
VAFORM 10-6166 SUPERSEDES VA FORM 10-6166, MAY 1972, WHICH WILL NOT BE USED.
CAR ENCLOSURE
X
CAR DOORS, OPERATOR & RESTRICTOR
X
CAR OPERATING PANEL
X
GUIDE RAILS AND SUPPORTS
X
CAR CANOPY
X
OVERHEAD BEAMS
X
CAR EMERGENCY EXIT CONTACTS
X
SHEAVES AND BEARINGS
X
CAR FLOORING
X
HANGERS AND DOOR GIBS
X
CAR EMERGENCY LIGHTING
X
INTERLOCKS AND CLOSERS
X
CAR VENTILATIONS
X
LEVELING SWITCHES AND VANES
X
CAR CAPACTIY PLATE
X
TOP CAR OPERATING DEVICE
X
CAR TELEPHONE BOX
X
TRAVELING CABLE
X
CAR CERTIFICATE FRAME
N/A
LIMIT SWITCHES
X
HOISTWAY DOOR PANELS AND FRAMES
X
CWT, TIE RODS, AND COTTER PINS
X
HANGER COVERS
X
BUFFERS (CAR AND CWT)
X
FASCIA PLATES
X
GUARD FOR CONTERWIGHT
X
TOE GUARDS
X
GOVERNOR TENSION SHEAVE & GAURD
X
HEADERS
X
GOVERNOR TENSION SHEAVE WEIGHT
X
HOISTWAY SILLS
X
SAFETY
X
FIREPROOFING UNDER PLATFORM
X
PIT ACCESS DOOR
N/A
NUMERAL ON EQUIPMENT
X
CAR PHOTO-ELECTRIC RAYS
X
HALL LANTERNS
X
CAR DOORS CONTACTS
X
HALL PUSH BUTTONS
X
CAR SAFETY EDGE
X
DISPATCHING PANEL
N/A
FACEPLATES AT STATIONS
X
HOISTWAY ACCESS SWITCH
X
CAR POSITION INDICATOR
X
PAINTING OF EQUIPMENT
X
HALL POSITION INDICATOR
X
EMERGENCY ELECTRIC POWER EQUIPMENT
X
ARE MANUAL AND PARTS LIST AVAILABLE?
[ X ] Yes [ ] No
ARE TOOLS AVAILABLE?
[ ]Yes [ ] No
2. CONDITION OF ROPES
LOCATION MATERIALS NUMBER SIZE AND
CONSRUCTION
USED LIFE
(in months)
EST. ADD. LIFE
(in months)
NO. OF BROKEN WIRES (Per Rope Lay)
HOISTING T.S. 4 5/8 – 8x19 0 REPLACE ROPES
DRUM COUNTERWEIGHT
CAR COUNTERWEIGHT
GOVERNOR – CAR
GOVERNOR – CWT T.S 1 3/8 – 8x19 OK
COMPENSATING
SAFETY
CONTRACT NO.
36C24121P0254
NAME OF CONTRACT COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY That the contractor has complied with all requirements of the contract and specifications.
Veterans Administration Central Office
[ X ] ANNUAL
[ ] FIVE YEARS (See contract specifications) [ ] THREE YEARS (HYDRAULIC) (See contract specifications)
Building 07
RATED CAPACITY
LBS: 3000 PERSONS: 20
MAUFACTURER SERIAL NO. AND YEAR INSTALLED
ELEVATOR CONTROLS CORP SER:18987 2010
RATED SPEED (FPM)
SAFETY (See rule 205.5 code A17/1-1971 and below) OTHER
[ ] TYPE A [ X ] TYPE B [ ] TYPE C [ ] BROKEN ROPE [ ] (SPECIFY)
IS SAFETY VALVE PROPERLY SET?
[ ] YES [ ] NO
DISTANCE CAR SLIDES AFTER
SAFETY IS APPLIED TO RAIL
FT IN.
MARK ON RAIL
LEFT RIGHT
[X ] RAIL [X ] RAIL FT IN
DISTANCE GOVERNOR ROPE
SLIDES THROUGH JAWS.
[ ] YES [ X ] NO (If “Yes,” how much)
WAS CAR FRAME SPRUNG AFTER
TEST? (If “Yes,” specify whether left or right)
[ ] YES [X ]NO
DAMAGE RESULTING FROM TEST
DID DAMAGE OCCUR TO THE FOLLOWING?
CAR GUIDES ROPES RAILS CLAMPS BRACKETS SAFETY
[ ] YES [ X ] NO [ ] YES [X ] NO [ ] YES [ ] NO [ ] YES [X ] NO [ ] YES [ X] NO [ ] YES [X] NO
ANY LOSS OF BUFFER OIL IN TYPE C SAFETIES?
[ ] YES [X] NO
WAS RELEASING CARRIER PROPERLY ADJUSTED?
[X ]YES [ ] NO
ARE GUIDES FIRMLY SECURED TO CAR
FRAMES?
[X] YES [ ] NO
DID SAFETY PARTS ON CAR FRAME SHOW FOREIGN OBSTRUCTION? NO
[ ] RUST [ ] LACK OF ATTENTION
[ ] CORROSION [ ] DAMPNESS [ ] OTHER (other please specify)
PAINT? RUST? CORROSION?
[ X ] YES [ ] NO [X ] YES [ ] NO [X] YES [ ] NO
WAS GOVERNOR PROPERLY LUBRICATED?
[X] YES [ ] NO
WAS THERE AMPLE FLY WEIGHT SPACE BETWEEN WALL AND
GOVERNOR? [X] YES [ ] NO
WERE THERE ANY SEALS ON THE GOVERONR?
[X] YES [ ] NO
WERE SPRING NUT LOCKS OR KEYS PROPERLY SECURED AND
SEALED? [X] YES [ ] NO
DID GOVERNOR JAWS DROP OF OWN WEIGHT WHEN LATCH WAS
RELEASED? [X] YES [ ] NO
DO BEARING OR GEARS SHOW EXCESSIVE WEAR?
[ ] YES [X] NO
WAS TENSION IDLER FREE IN FRAME GUIDES AND IN ITS SHAFT?
[X] YES [ ] NO
IS PROPER SIZE GOVERNOR ROPE BEING USED?
[X] YES [ ] NO
IS THE PROPER TYPE OF ROPE USED?
TEST OF SAFETIES A17.1 1971
1. TUPE A, B, OR C GOVERNOR – OPERATED SAFETIES. 1001.4a1
2. WOOD GUIDE GOVERNOR – OPERATED SAFETIES 1001.4a1
3. TYPE A AND WOOD GUIDE SAFETIES WITHOUT GOVERNORS OPERATED ONLY AS A RRESULT OF THE BREAKING OR SLACKENING OF THE HOISTING ROPES 1001.4a3
Building 07 Car P – 1
Emergency light and bell not operational
Hoist ropes were hit with water and are rusted/rouged. Should be replaced (Gov rope OK)
Provide spin outs
Adjust top access down lmit for proper distance. Top of car should stop level with top landing
Repair bottom floor access key switch
Provide Code Data Plate
Provide pit light
02 Mar 2021
Region No._________(138) Veterans Administration Central office
Building 09 No. of stops
No. of Openings
Elevator number and type
P - 1 HYDRAULIC PASSENGER 190 WP 390 RP
LBS: 1800 PERSONS 9
ESSCO/PAYNE C8158 1967 Note: Unit has Life Jacket Rated Speed (fpm)
HEATING IN MACHINE ROOM
X
MOTOR GENERATORS FIELD,
BRUSHES AND HOLDERS
N/A CLEARANCE AROUND MACHINE ROOM
PUMPS, VALVES, PIPING AND TANKS
X
VAFORM 10-6166 SUPERSEDES VA FORM 10-6166, MAY 1972, WHICH WILL NOT BE USED.
CAR ENCLOSURE
X
CAR DOORS, OPERATOR & RESTRICTOR
X
CAR OPERATING PANEL
X
GUIDE RAILS AND SUPPORTS
X
CAR CANOPY
X
OVERHEAD BEAMS
X
CAR EMERGENCY EXIT CONTACTS
X
SHEAVES AND BEARINGS
X
CAR FLOORING
X
HANGERS AND DOOR GIBS
X
CAR EMERGENCY LIGHTING
X
INTERLOCKS AND CLOSERS
X
CAR VENTILATIONS
X
LEVELING SWITCHES AND VANES
X
CAR CAPACTIY PLATE
X
TOP CAR OPERATING DEVICE
X
CAR TELEPHONE BOX
X
TRAVELING CABLE
X
CAR CERTIFICATE FRAME
N/A
LIMIT SWITCHES
X
HOISTWAY DOOR PANELS AND FRAMES
X
CWT, TIE RODS, AND COTTER PINS
X
HANGER COVERS
X
BUFFERS (CAR AND CWT)
X
FASCIA PLATES
X
GUARD FOR CONTERWIGHT
N/A
TOE GUARDS
X
GOVERNOR TENSION SHEAVE & GAURD
N/A
HEADERS
X
GOVERNOR TENSION SHEAVE WEIGHT
N/A
HOISTWAY SILLS
X
SAFETY
N/A
FIREPROOFING UNDER PLATFORM
X
PIT ACCESS DOOR
N/A
NUMERAL ON EQUIPMENT
X
CAR PHOTO-ELECTRIC RAYS
X
HALL LANTERNS
X
CAR DOORS CONTACTS
X
HALL PUSH BUTTONS
X
CAR SAFETY EDGE
X
DISPATCHING PANEL
N/A
FACEPLATES AT STATIONS
X
HOISTWAY ACCESS SWITCH
N/A
CAR POSITION INDICATOR
X
PAINTING OF EQUIPMENT
X
HALL POSITION INDICATOR
X
EMERGENCY ELECTRIC POWER EQUIPMENT
X
ARE MANUAL AND PARTS LIST AVAILABLE?
[ X ] Yes [ ] No
ARE TOOLS AVAILABLE?
[ ]Yes [ ] No
2. CONDITION OF ROPES
LOCATION MATERIALS NUMBER SIZE AND
CONSRUCTION
USED LIFE
(in months)
EST. ADD. LIFE
(in months)
NO. OF BROKEN WIRES (Per Rope Lay)
HOISTING
DRUM COUNTERWEIGHT
CAR COUNTERWEIGHT
GOVERNOR – CAR
GOVERNOR – CWT
COMPENSATING
SAFETY
CONTRACT NO.
36C24121P0254
NAME OF CONTRACT COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY That the contractor has complied with all requirements of the contract and specifications.
Building 09 Car P – 1
Emergency light and bell not operational
Phone not operational
Provide beveled fascia above second floor door
Replace acoustic ceiling tiles in cab ceiling with translucent panels or similar
Traveling cable jakets are cracked and brittle. Been hit with water. Failure may be imminent
Region No._________(138) Veterans Administration Central office
Building 10 No. of stops
No. of Openings
Elevator number and type
P – 1 HYDRAULIC PASSENGER 160 WP 295 RP
LBS: 4000 PERSONS 26
ESI 76-097 1976 Note: Unit has Life Jacket Rated Speed (fpm)
HEATING IN MACHINE ROOM
X
MOTOR GENERATORS FIELD,
BRUSHES AND HOLDERS
N/A CLEARANCE AROUND MACHINE ROOM
PUMPS, VALVES, PIPING AND TANKS
X
VAFORM 10-6166 SUPERSEDES VA FORM 10-6166, MAY 1972, WHICH WILL NOT BE USED.
CAR ENCLOSURE
X
CAR DOORS, OPERATOR & RESTRICTOR
X
CAR OPERATING PANEL
X
GUIDE RAILS AND SUPPORTS
X
CAR CANOPY
X
OVERHEAD BEAMS
X
CAR EMERGENCY EXIT CONTACTS
X
SHEAVES AND BEARINGS
X
CAR FLOORING
X
HANGERS AND DOOR GIBS
X
CAR EMERGENCY LIGHTING
X
INTERLOCKS AND CLOSERS
X
CAR VENTILATIONS
X
LEVELING SWITCHES AND VANES
X
CAR CAPACTIY PLATE
X
TOP CAR OPERATING DEVICE
X
CAR TELEPHONE BOX
X
TRAVELING CABLE
X
CAR CERTIFICATE FRAME
N/A
LIMIT SWITCHES
X
HOISTWAY DOOR PANELS AND FRAMES
X
CWT, TIE RODS, AND COTTER PINS
X
HANGER COVERS
X
BUFFERS (CAR AND CWT)
X
FASCIA PLATES
X
GUARD FOR CONTERWIGHT
N/A
TOE GUARDS
X
GOVERNOR TENSION SHEAVE & GAURD
N/A
HEADERS
X
GOVERNOR TENSION SHEAVE WEIGHT
N/A
HOISTWAY SILLS
X
SAFETY
N/A
FIREPROOFING UNDER PLATFORM
X
PIT ACCESS DOOR
N/A
NUMERAL ON EQUIPMENT
X
CAR PHOTO-ELECTRIC RAYS
X
HALL LANTERNS
X
CAR DOORS CONTACTS
X
HALL PUSH BUTTONS
X
CAR SAFETY EDGE
X
DISPATCHING PANEL
N/A
FACEPLATES AT STATIONS
X
HOISTWAY ACCESS SWITCH
X
CAR POSITION INDICATOR
X
PAINTING OF EQUIPMENT
X
HALL POSITION INDICATOR
X
EMERGENCY ELECTRIC POWER EQUIPMENT
X
ARE MANUAL AND PARTS LIST AVAILABLE?
[ X ] Yes [ ] No
ARE TOOLS AVAILABLE?
[ ]Yes [ ] No
2. CONDITION OF ROPES
LOCATION MATERIALS NUMBER SIZE AND
CONSRUCTION
USED LIFE
(in months)
EST. ADD. LIFE
(in months)
NO. OF BROKEN WIRES (Per Rope Lay)
HOISTING
DRUM COUNTERWEIGHT
CAR COUNTERWEIGHT
GOVERNOR – CAR
GOVERNOR – CWT
COMPENSATING
SAFETY
CONTRACT NO.
36C24121P0254
NAME OF CONTRACT COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY That the contractor has complied with all requirements of the contract and specifications.
Building 10 Car P – 1
Peeling paint in machine room represents a potential health risk and should be investigated and remediated
Emergency light and bell not operational
Phone not operational
Replace missing restrictor parts and adjust
Remove plexi‐glass covering hoistway ventilation
Region No._________(138) Veterans Administration Central office
Building 62 No. of stops
No. of Openings
Elevator number and type
F – 1 HYDRAULIC FREIGHT 180 WP 460 RP
LBS: 4000 PERSONS 26
ESI 90484 1990
Rated Speed (fpm)
HEATING IN MACHINE ROOM
X
MOTOR GENERATORS FIELD,
BRUSHES AND HOLDERS
N/A CLEARANCE AROUND MACHINE ROOM
PUMPS, VALVES, PIPING AND TANKS
X
VAFORM 10-6166 SUPERSEDES VA FORM 10-6166, MAY 1972, WHICH WILL NOT BE USED.
CAR ENCLOSURE
X
CAR DOORS, OPERATOR & RESTRICTOR
X
CAR OPERATING PANEL
X
GUIDE RAILS AND SUPPORTS
X
CAR CANOPY
X
OVERHEAD BEAMS
X
CAR EMERGENCY EXIT CONTACTS
X
SHEAVES AND BEARINGS
X
CAR FLOORING
X
HANGERS AND DOOR GIBS
X
CAR EMERGENCY LIGHTING
X
INTERLOCKS AND CLOSERS
X
CAR VENTILATIONS
X
LEVELING SWITCHES AND VANES
X
CAR CAPACTIY PLATE
X
TOP CAR OPERATING DEVICE
X
CAR TELEPHONE BOX
X
TRAVELING CABLE
X
CAR CERTIFICATE FRAME
N/A
LIMIT SWITCHES
X
HOISTWAY DOOR PANELS AND FRAMES
X
CWT, TIE RODS, AND COTTER PINS
X
HANGER COVERS
X
BUFFERS (CAR AND CWT)
X
FASCIA PLATES
X
GUARD FOR CONTERWIGHT
N/A
TOE GUARDS
X
GOVERNOR TENSION SHEAVE & GAURD
N/A
HEADERS
X
GOVERNOR TENSION SHEAVE WEIGHT
N/A
HOISTWAY SILLS
X
SAFETY
N/A
FIREPROOFING UNDER PLATFORM
X
PIT ACCESS DOOR
N/A
NUMERAL ON EQUIPMENT
X
CAR PHOTO-ELECTRIC RAYS
X
HALL LANTERNS
X
CAR DOORS CONTACTS
X
HALL PUSH BUTTONS
X
CAR SAFETY EDGE
X
DISPATCHING PANEL
N/A
FACEPLATES AT STATIONS
X
HOISTWAY ACCESS SWITCH
X
CAR POSITION INDICATOR
X
PAINTING OF EQUIPMENT
X
HALL POSITION INDICATOR
X
EMERGENCY ELECTRIC POWER EQUIPMENT
X
ARE MANUAL AND PARTS LIST AVAILABLE?
[ X ] Yes [ ] No
ARE TOOLS AVAILABLE?
[ ]Yes [ ] No
2. CONDITION OF ROPES
LOCATION MATERIALS NUMBER SIZE AND
CONSRUCTION
USED LIFE
(in months)
EST. ADD. LIFE
(in months)
NO. OF BROKEN WIRES (Per Rope Lay)
HOISTING
DRUM COUNTERWEIGHT
CAR COUNTERWEIGHT
GOVERNOR – CAR
GOVERNOR – CWT
COMPENSATING
SAFETY
CONTRACT NO.
36C24121P0254
NAME OF CONTRACT COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY That the contractor has complied with all requirements of the contract and specifications.
Building 62 Car F – 1
Emergency light not operational
Top Access switch not operational
01 Mar 2021
Region No._________(138) Veterans Administration Central office
Building 62 No. of stops
No. of Openings
Elevator number and type
P – 1 GEARED TRACTION PASSENGER V3F
ELEVATOR CONTROLS CORP SER:18986 2010
Rated Speed (fpm)
HEATING IN MACHINE ROOM
X
MOTOR GENERATORS FIELD,
BRUSHES AND HOLDERS
N/A CLEARANCE AROUND MACHINE ROOM
PUMPS, VALVES, PIPING AND TANKS
N/A
VAFORM 10-6166 SUPERSEDES VA FORM 10-6166, MAY 1972, WHICH WILL NOT BE USED.
CAR ENCLOSURE
X
CAR DOORS, OPERATOR & RESTRICTOR
X
CAR OPERATING PANEL
X
GUIDE RAILS AND SUPPORTS
X
CAR CANOPY
X
OVERHEAD BEAMS
X
CAR EMERGENCY EXIT CONTACTS
X
SHEAVES AND BEARINGS
X
CAR FLOORING
X
HANGERS AND DOOR GIBS
X
CAR EMERGENCY LIGHTING
X
INTERLOCKS AND CLOSERS
X
CAR VENTILATIONS
X
LEVELING SWITCHES AND VANES
X
CAR CAPACTIY PLATE
X
TOP CAR OPERATING DEVICE
X
CAR TELEPHONE BOX
X
TRAVELING CABLE
X
CAR CERTIFICATE FRAME
N/A
LIMIT SWITCHES
X
HOISTWAY DOOR PANELS AND FRAMES
X
CWT, TIE RODS, AND COTTER PINS
X
HANGER COVERS
X
BUFFERS (CAR AND CWT)
X
FASCIA PLATES
X
GUARD FOR CONTERWIGHT
X
TOE GUARDS
X
GOVERNOR TENSION SHEAVE & GAURD
X
HEADERS
X
GOVERNOR TENSION SHEAVE WEIGHT
X
HOISTWAY SILLS
X
SAFETY
X
FIREPROOFING UNDER PLATFORM
X
PIT ACCESS DOOR
N/A
NUMERAL ON EQUIPMENT
X
CAR PHOTO-ELECTRIC RAYS
X
HALL LANTERNS
X
CAR DOORS CONTACTS
X
HALL PUSH BUTTONS
X
CAR SAFETY EDGE
X
DISPATCHING PANEL
N/A
FACEPLATES AT STATIONS
X
HOISTWAY ACCESS SWITCH
N/A
CAR POSITION INDICATOR
X
PAINTING OF EQUIPMENT
X
HALL POSITION INDICATOR
X
EMERGENCY ELECTRIC POWER EQUIPMENT
X
ARE MANUAL AND PARTS LIST AVAILABLE?
[ X ] Yes [ ] No
ARE TOOLS AVAILABLE?
[ ]Yes [ ] No
2. CONDITION OF ROPES
LOCATION MATERIALS NUMBER SIZE AND
CONSRUCTION
USED LIFE
(in months)
EST. ADD. LIFE
(in months)
NO. OF BROKEN WIRES (Per Rope Lay)
HOISTING T.S. 4 5/8 – 8x19 0 REPLACE ROPES
DRUM COUNTERWEIGHT
CAR COUNTERWEIGHT
GOVERNOR – CAR T.S 1 3/8 – 8x19 REPLACE ROPE
GOVERNOR – CWT
COMPENSATING
SAFETY
CONTRACT NO.
36C24121P0254
NAME OF CONTRACT COMPANY
enDevelopment
SIGNATURE OF INSPECTING OFFICER
WE CERTIFY That the contractor has complied with all requirements of the contract and specifications.
01 Mar 2021
Veterans Administration Central Office
[ X ] ANNUAL
[ ] FIVE YEARS (See contract specifications) [ ] THREE YEARS (HYDRAULIC) (See contract specifications)
Building 62
RATED CAPACITY
LBS: 3000 PERSONS: 20
MAUFACTURER SERIAL NO. AND YEAR INSTALLED
ELEVATOR CONTROLS CORP SER:18986 2010
RATED SPEED (FPM)
SAFETY (See rule 205.5 code A17/1-1971 and below) OTHER
[ ] TYPE A [ X ] TYPE B [ ] TYPE C [ ] BROKEN ROPE [ ] (SPECIFY)
IS SAFETY VALVE PROPERLY SET?
[ ] YES [ ] NO
DISTANCE CAR SLIDES AFTER
SAFETY IS APPLIED TO RAIL
FT IN.
MARK ON RAIL
LEFT RIGHT
[X ] RAIL [X ] RAIL FT IN
DISTANCE GOVERNOR ROPE
SLIDES THROUGH JAWS.
[ ] YES [ X ] NO (If “Yes,” how much)
WAS CAR FRAME SPRUNG AFTER
TEST? (If “Yes,” specify whether left or right)
[ ] YES [X ]NO
DAMAGE RESULTING FROM TEST
DID DAMAGE OCCUR TO THE FOLLOWING?
CAR GUIDES ROPES RAILS CLAMPS BRACKETS SAFETY
[ ] YES [ X ] NO [ ] YES [X ] NO [ ] YES [ ] NO [ ] YES [X ] NO [ ] YES [ X] NO [ ] YES [X] NO
ANY LOSS OF BUFFER OIL IN TYPE C SAFETIES?
[ ] YES [X] NO
WAS RELEASING CARRIER PROPERLY ADJUSTED?
[X ]YES [ ] NO
ARE GUIDES FIRMLY SECURED TO CAR
FRAMES?
[X] YES [ ] NO
DID SAFETY PARTS ON CAR FRAME SHOW FOREIGN OBSTRUCTION? NO
[ ] RUST [ ] LACK OF ATTENTION
[ ] CORROSION [ ] DAMPNESS [ ] OTHER (other please specify)
PAINT? RUST? CORROSION?
[ X ] YES [ ] NO [X ] YES [ ] NO [X] YES [ ] NO
WAS GOVERNOR PROPERLY LUBRICATED?
[X] YES [ ] NO
WAS THERE AMPLE FLY WEIGHT SPACE BETWEEN WALL AND
GOVERNOR? [X] YES [ ] NO
WERE THERE ANY SEALS ON THE GOVERONR?
[X] YES [ ] NO
WERE SPRING NUT LOCKS OR KEYS PROPERLY SECURED AND
SEALED? [X] YES [ ] NO
DID GOVERNOR JAWS DROP OF OWN WEIGHT WHEN LATCH WAS
RELEASED? [X] YES [ ] NO
DO BEARING OR GEARS SHOW EXCESSIVE WEAR?
[ ] YES [X] NO
WAS TENSION IDLER FREE IN FRAME GUIDES AND IN ITS SHAFT?
[X] YES [ ] NO
IS PROPER SIZE GOVERNOR ROPE BEING USED?
[X] YES [ ] NO
IS THE PROPER TYPE OF ROPE USED?
TEST OF SAFETIES A17.1 1971
1. TUPE A, B, OR C GOVERNOR – OPERATED SAFETIES. 1001.4a1
2. WOOD GUIDE GOVERNOR – OPERATED SAFETIES 1001.4a1
3. TYPE A AND WOOD GUIDE SAFETIES WITHOUT GOVERNORS OPERATED ONLY AS A RRESULT OF THE BREAKING OR SLACKENING OF THE HOISTING ROPES 1001.4a3
Building 62 Car P – 1
Adjust restrictor
Emergency light and bell not operational
Phone not operational
Hoist ropes were hit with water and are rusted/rouged. Should be replaced
Governor rope was hit with water and is rusted/rouged. Should be replaced
Provide guards on hoistway lights
Cover 4” (1900) box by bottom landing and remove hanging flex conduit
Provide Spin outs
| B06 P1 VA Bedford MA |
| B06 P1 VA Bedford MA Cno.pdf |
| B06 P1 VA Bedford MA last page.pdf |
| B07 P1 VA Bedford MA |
| B07 P1 VA Bedford MA Cno.pdf |
| B07 P1 VA Bedford MA last page.pdf |
| B09 P1 VA Bedford MA |
| B09 P1 VA Bedford MA Cno.pdf |
| B09 P1 VA Bedford MA last page.pdf |
| B10 P1 VA Bedford MA |
| B10 P1 VA Bedford MA Cno.pdf |
| B10 P1 VA Bedford MA last page.pdf |
| B62 F1 VA Bedford MA |
| B62 F1 VA Bedford MA Cno.pdf |
| B62 F1 VA Bedford MA last page.pdf |
| B62 P1 VA Bedford MA |
| B62 P1 VA Bedford MA Cno.pdf |
| B62 P1 VA Bedford MA last page.pdf |
File details come from the government source that posted it. Updated .