rptFCAFacilityCondition_new
| FCA - Basic FCA Report | | | | | | | | |
| Report Parameters: Program = VHA, District = 1, VISN = 1, Station = 518 | | | | | | | | |
| 518 - Bedford | | | | | | | | District VHA - North Atlantic, VISN 1 |
| Bldg # | Function | SF Area | Heating System | AC System | Boiler | Ventilation | Lighting | |
| 1 | Administration | 11,727 | | | | | | |
| 10 | Library | 21,183 | | | | | | |
| 12 | Offices | 15,311 | | | | | | |
| 13 | Housekeeping Qtrs | 8,174 | | | | | | |
| 14 | Housekeeping Qtrs | 5,549 | | | | | | |
| 15 | Housekeeping Qtrs | 9,267 | | | | | | |
| 16 | Housekeeping Qtrs | 3,841 | | | | | | |
| 17 | Research | 20,015 | | | | | | |
| 18 | GRECC | 17,556 | | | | | | |
| 18T | Quonsett Hut Storage | 1,212 | | | | | | |
| 19 | Laundry Storage | 18,135 | | | | | | |
| 19T | Vacant Quonsett | 1,313 | | | | | | |
| 10S | Crescent Bldg | 41,013 | | | | | | |
| 2 | Patient Care | 92,307 | | | | | | |
| 20 | 6 Bay Garage | 4,002 | | | | | | |
| 20T | Quonsett Hut Storage | 1,220 | | | | | | |
| 22 | Boiler Plant | 8,685 | | | | | | |
| 22A | Hazmat Storage | 128 | | | | | | |
| 23 | Guard House | 210 | | | | | | |
| 27 | Elec Swgear | 389 | | | | | | |
| 28 | Storage | 391 | | | | | | |
| 28A | Salt Storage | 1,536 | | | | | | |
| 28T | Greenhouse | 2,000 | | | | | | |
| 29 | Research Storage | 458 | | | | | | |
| 3 | Dietetics/ Kitchen | 39,400 | | | | | | |
| 30 | Pumphouse | 293 | | | | | | |
| 32 | 5 Bay Garage | 3,054 | | | | | | |
| 33 | Fiscal | 4,941 | | | | | | |
| 39 | Vacant Bathrooms ?? | 960 | | | | | | |
| 4 | Nursing Home | 122,175 | | | | | | |
| 49 | Barn | 3,600 | | | | | | |
| 5 | Research/ Vacant | 49,582 | | | | | | |
| 52 | Golf Course Shed | 202 | | | | | | |
| 55 | Recreation (Golf Course Clubhouse) | 1,600 | | | | | | |
| 6 | Patient Care | 60,659 | | | | | | |
| 60 | Elec Swgear | 320 | | | | | | |
| 61 | Administration | 65,017 | | | | | | |
| 62 | Patient Care | 62,122 | | | | | | |
| 63 | Storage (Garages) | 2,829 | | | | | | |
| 69 | Storage | 1,704 | | | | | | |
| 7 | Patient Care/ Domicillary | 68,896 | | | | | | |
| 70 | HSR &D ?? | 49,664 | | | | | | |
| 71 | Pumphouse | 220 | | | | | | |
| 76 | Pumphouse | 600 | | | | | | |
| 77 | Pumphouse | 600 | | | | | | |
| 78 | Patient Care | 133,199 | | | | | | |
| 78A | Canteen/ Theatre | 14,080 | | | | | | |
| 79 | Elec Bldg | 301 | | | | | | |
| 8 | CMOP/DSS | 51,166 | | | | | | |
| 80 | CWT/ SMS/ A&MM | 22,955 | | | | | | |
| 81 | Chapel | 7,037 | | | | | | |
| 82 | Gym/ Pool | 25,024 | | | | | | |
| 9 | Administration | 35,835 | | | | | | |
| 92 | Emergency Generator Bldg | 380 | | | | | | |
| 93 | Emergency Generator Bldg | 380 | | | | | | |
| 94 | Emergency Generator Bldg | 380 | | | | | | |
| 95 | Emergency Generator Bldg | 380 | | | | | | |
| 98 | Water Tower | 0 | | | | | | |
| CC | Connecting Corridors | 16,296 | | | | | | |
| Site Utilities | | | | | | | | |
| Total SF AREA | 1,131,473 | | | | | | |
| Bldg Total Correction | $17,695,446.22 | Bldg Total Replacement | $38,472,777 Bldg Ratio: 0.46 |
| Bldg Total Pending | $0.00 | | |
| Station 518 Total Correction | $213,661,070 | Station Total Replacement | $717,182,884 Station Ratio: 0.30 |
| Station Total Pending | $0 | | |
| Report Totals | Correction | Replacement |
| $213,661,070 | $717,182,884 |
| Pending | |
| $0 | |
&"Microsoft Sans Serif,Regular"&8 09-27-2016 &"Arial,Bold Italic"&11 VA Capital Asset Inventory &"Microsoft Sans Serif,Regular"&8Page &P of &N
B#1
| Building | Year Built | Last Renov | | Floors | | | | |
| FCA GSF | | Current Function | Administration | | | | | |
| 1 | 1928 | 0 | | 3 | 11,727 | | Proposed Function | Administration |
| Details | | | | | | | | |
| Architectural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Accessibility | 12521 | 1 | C | * | | * | $0 | -Building is accessible through connecting corridor. |
-An accessible water cooler is provided.
| Pending Totals: | | | | | | | |
| Accessibility | 299402 | 2 | D | * | * | $381,879 | -Accessible restrooms (104) are not provided in the building. |
-Lever style door hardware is not provided.
-Required knee clearance at lavatories is not provided -Lavatory traps in most accessible restrooms on most floors are not insulated.
-Provide an 3 stop elevator for accessibility to all floors. (Accessibility to the Executive Director's offices and HR suite on the 2nd floor is required)
| Pending Totals: | | | | | | | |
| Exterior Walls | 12522 | 1 | C | 100 | 15 | $0 | -Exterior wall is in fair condition. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 107830 | 2 | D | 100 | exceeds | $146,756 | -2007 FCA listed masonry repair project. Work still to be performed. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 133476 | 4 | D | 15 | exceeds | $99,584 | -Re-seal all penetrations and caulk joints (all windows and expansion joints). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 133477 | 5 | D | 15 | exceeds | $67,052 | -Scrape and paint wood cornice/eave (5,160l.f.). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 133478 | 6 | D | 15 | exceeds | $403,578 | -Rake and point joints in pre cast stone bands (2 @ 5,160 l.f.). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 299403 | 7 | D | 100 | 15 | $324,959 | -Abate the PCB's in the brick mortar when performing the exterior brick racking and repointing. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 107831 | 2 | D | 10 | exceeds | $64,765 | -Provide new carpet throughout on 1st floor. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 132626 | 3 | D | 10 | exceeds | $49,678 | -Provide suspended ceiling throughout and remove the 1x1 ceiling tile. (Facilities notes asbestos to be abated above the 1x1 ceiling tile. Costs to include the abatement are located in "Hazmat".) |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 12524 | 1 | C | 10 | exceeds | $0 | -Interior finishes in fair condition. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 299404 | 4 | C | 10 | exceeds | $0 | -The interior finishes are in fair condition including wall paint, doors and frames. |
| Pending Totals: | | | | | | | |
| Life Safety | 299405 | 4 | D | * | * | $86,050 | -Wood framed rafters in the attic is not sprinkled. Sprinkle the attic. |
| Pending Totals: | | | | | | | |
| Life Safety | 12525 | 1 | D | * | * | $258,151 | -Not sprinkled. Provide a fire suppression system for this public business occupancy. |
-Required fire extinguishers are not available.
-Required exit signs are not available.
-Exit fire stair handrails are older and do not meet the current life.
| Pending Totals: | | | | | | | |
| Life Safety | 107834 | 3 | B | * | * | $0 | -Required exits are available. |
| Pending Totals: | | | | | | | |
| Roof | 299406 | 2 | D | 20 | exceeds | $30,903 | -Prep, repaint and reflash the roof dormers and dormer windows. |
| Pending Totals: | | | | | | | |
| Roof | 12526 | 1 | B | 30 | 20 | $0 | -Newer asphalt shingle roof in good condition. |
| Pending Totals: | | | | | | | |
| Signage / Wayfindg | 12527 | 1 | B | 10 | 9 | $0 | -Signage/Wayfinding has been upgraded and is in good condition. |
| Pending Totals: | | | | | | | |
| Windows | 12528 | 1 | C | 30 | exceeds | $0 | -Aluminum single glaze, double pane, double hung windows with bronze finish in fair condition. |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $1,913,354 | | System Replacement Cost | | $2,264,570 Ratio: 0.84 |
| System Total Pending | | | | | | | |
| Electrical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Elec/Tele Closets | 12529 | 1 | D | 15 | | exceeds | $64,002 | Provide proper ventilation for Data closets. |
Data closet in basement is located in an open area.
Electrical panelboards are wall mounted.
| Pending Totals: | | | | | | | |
| Emerg Elec Sys. | 12530 | 1 | D | 25 | exceeds | $12,084 | Replace Russellectric Models RTM, 100A-3p, 208Y/120v, 3 phase transfer switch. |
Fed from building no 92 engine/generator. Powers egress and exit lighting.
| Pending Totals: | | | | | | | |
| Fire Alarm | 108136 | 2 | N/A | n/a | n/a | $0 | n/a |
| Pending Totals: | | | | | | | |
| Fire Alarm | 12531 | 1 | F | 15 | exceeds | $52,869 | Provide new Fire Alarm System. Locate detectors, horns and strobes and synchronize strobe lights to meet NFPA 72 or ADA. Existing EST Model CM2N fire alarm control panel and system, poor condition. |
| Pending Totals: | | | | | | | |
| Lighting & Power | 12532 | 1 | C- | 25 | exceeds | $0 | All lighting fixtures are T-8 lamps with T-8 energy efficient electronic ballasts. Existing exit lights are LED type exit lights. |
| Pending Totals: | | | | | | | |
| Lightning Protect | 12533 | 1 | N/A | 20 | n/a | $6,401 | Perform risk analysis per NFPA 780 to determine need. |
| Pending Totals: | | | | | | | |
| Nurse Call/Int/TV | 11634 | 1 | N/A | 15 | n/a | $0 | n/a |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 11635 | 1 | D | 30 | exceeds | $58,911 | Replace Federal Pacific Electric panelboards and main circuit breaker that is 250A, 208Y/120V,3 phase, obsolete, the firm has not been in business. Replace (2) Kelek 125AMB panels. Replacement parts are not available. |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 108137 | 2 | F | 30 | exceeds | $80,059 | Correct Electric (Deficiencies from Electrical Study Report, D.O.C. Feb-2005). Replace breakers as recommended in study. ($27000) |
| Pending Totals: | | | | | | | |
| Transformer | 11637 | 1 | F | 30 | exceeds | $54,379 | Replace old open type 225 KVA, 13.8kV-208Y/120V, 3 phase, padmounted transformer. Poor condition. |
| Pending Totals: | | | |
| System Total Correction | $328,705 | System Replacement Cost | $870,988 Ratio: 0.38 |
| System Total Pending | | | |
| Hazmat | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Asbestos | 236099 | 1 | D | * | | * | $15,105 | -Recommend analysis to determine extent of asbestos abatement required above ACT ceilings. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $15,105 | | | System Replacement Cost | | |
| System Total Pending | | | | | | | | |
| Mechanical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Air Handling Equip | 11638 | 1 | D | 20 | | * | $1,507,751 | Provide required ventilation with air handling units. Building is cooled with window units only. Window units get replaced when they break down. Building does not have proper ventilation. Code violation. |
| Pending Totals: | | | | | | | |
| Ducts & Water Dist | 11639 | 1 | D | 30 | * | $0 | None installed. See air handling equipment. |
| Pending Totals: | | | | | | | |
| Engr. Control syst. | 11640 | 1 | D | 20 | * | $145,237 | Provide controls system. |
Minimal controls for radiators, outdated.
| Pending Totals: | | | | | | | |
| Heating System | 11641 | 1 | A | 30 | 27 | $0 | Receiver and pumps were replaced in 2010. |
| Pending Totals: | | | | | | | |
| Heating System | 108138 | 2 | D | 30 | exceeds | $302,781 | Replace original steam radiators and piping, poor condition. |
| Pending Totals: | | | | | | | |
| Room Air Dist/Term | 11642 | 1 | D | 30 | * | $0 | None installed. See air handling equipment. |
| Pending Totals: | | | | | | | |
| Ventil (O.A. & Exh) | 11643 | 1 | D | 30 | * | $0 | Poor ventilation. It requires proper ventilation per ASHRAE. |
**Correction Costs: See Air Handl. Equip.**
| Pending Totals: | | | |
| System Total Correction | $1,955,769 | System Replacement Cost | $1,016,154 Ratio: 1.92 |
| System Total Pending | | | |
| Plumbing | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Fire Sprinkler / Pump | 11644 | 1 | n/a | 50 | | * | $0 | No fire service, no sprinklers. |
| Pending Totals: | | | | | | | | |
| Fixtures / Piping | 108139 | 2 | D | 50 | | exceeds | $369,245 | Provide a 3" reduced pressure backflow preventer to the water sevice. Replace original hot, cold and sanitary piping systems. |
| Pending Totals: | | | | | | | |
| Fixtures / Piping | 109157 | 1 | C | 50 | exceeds | $0 | The fixtures are old but HC fixtures have been added. Fair condition. |
| Pending Totals: | | | | | | | |
| Hot Water Heater | 11646 | 1 | B | 25 | 18 | $0 | Replaced in 2006 with instantaneous water heater. |
| Pending Totals: | | | | | | | |
| Medical Gases | 298853 | 1 | N/A | 30 | * | $0 | n/a |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $369,245 | | System Replacement Cost | | $435,494 Ratio: 0.85 |
| System Total Pending | | | | | | | |
| Structural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Floor Systems | 11647 | 1 | C | 100 | | 15 | $0 | -One way concrete joists supported by concrete beams in fair condition. |
| Pending Totals: | | | | | | | | |
| Foundations | 11648 | 1 | C | 100 | | 15 | $0 | -Spread footing in fair condition. |
| Pending Totals: | | | | | | | | |
| Seismic / Wind Load | 11649 | 1 | n/a | * | | * | $0 | Wind load governs. |
| Pending Totals: | | | | | | | | |
| Vertical Members | 11650 | 1 | C | 100 | | 15 | $0 | -Concrete columns in fair condition. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $0 | | | System Replacement Cost | | $987,120 Ratio: 0.00 |
| System Total Pending | | | | | | | | |
| Information Technology | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Inside Cable Plant (ICP) | 11636 | 1 | C | 15 | | 10+ | $0 | The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed. |
| Pending Totals: | | | | | | | |
| Telecommunications Rooms | 302770 | 1 | C | 15 | 10+ | $0 | The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies. |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302771 | 2 | D | 15 | $2,201 | Telecommunincations Room 2B1 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302772 | 3 | D | 15 | $3,564 | Telecommunincations Room B1 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. 5) have bare concrete floors, paint floors or apply appropriate flooring to reduce dust & static |
| Pending Totals: | | | | | |
| Telecommunications Rooms | 302773 | 4 | D | $34,485 | Telecommunications rooms 2B1 and B1 are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84. |
| Pending Totals: | | |
| System Total Correction | $40,251 | System Replacement Cost |
| System Total Pending | | |
| Bldg Total Correction | $4,622,429.26 | Bldg Total Replacement | $5,806,295 Bldg Ratio: 0.80 |
| Bldg Total Pending | | | |
B#10
| Building | Year Built | Last Renov | | Floors | | | | |
| FCA GSF | | Current Function | Library | | | | | |
| 10 | 1928 | 0 | | 4 | 21,183 | | Proposed Function | Library |
| Details | | | | | | | | |
| Architectural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Accessibility | 11651 | 1 | B | * | | * | $0 | -Building is accessible at grade and through connecting corridor and has an elevator. |
| Pending Totals: | | | | | | | | |
| Accessibility | 107954 | 2 | D | * | | * | $64,727 | -Upgrade men's and women's toilet room (106 and 107) and provide accessible water fountain. |
| Pending Totals: | | | | | | | | |
| Accessibility | 299426 | 3 | D | * | | * | $23,507 | -Lever style door hardware is not provided. (25-30 doors) |
| Pending Totals: | | | | | | | |
| Exterior Walls | 299427 | 9 | D | 100 | 15 | $44,289 | -Repair, prep and repaint 25 l.f. of rusting metal railings at the front entry steps. |
-Repair the pre cast monumental sign at the front entry.
-Repoint the two brick chimneys.
| Pending Totals: | | | | | | | |
| Exterior Walls | 107955 | 2 | D | 100 | exceeds | $73,378 | -Re-seal all penetrations and lock joints. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132659 | 3 | D | 100 | exceeds | $35,392 | -Repair approx. 25% of wood cornices and eaves; scrape and paint 50%. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132660 | 4 | B | 100 | 15 | $0 | -The four wood columns have been repaired, painted and are in good condition. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132661 | 5 | D | 100 | 15 | $28,093 | -Repair approximately 8 s.f. of concrete slab at steps at the front entry. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132662 | 6 | D | 100 | exceeds | $11,871 | -Repair concrete stairs and platform (17R x 8' W). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132663 | 7 | D | 100 | exceeds | $22,013 | -Rake and point cast stone band at first floor level. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132664 | 8 | D | 100 | exceeds | $31,448 | -Point brick and arched stair (approximately 200 s.f.). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 11652 | 1 | C | 100 | 15 | $0 | -Exterior brick veneer walls are in fair condition. |
| Pending Totals: | | | | | | | |
| Fixed Equipment | 11653 | 1 | C | 15 | exceeds | $0 | -Fixed equipment is in fair condition. |
-Book shelving is in fair condition.
-SPD equipment is located in the basement of the library is in fair condition.
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 107956 | 2 | D | 10 | exceeds | $5,907 | -Repair approximately 500 SF of water damage at first floor |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 132665 | 3 | D | 10 | exceeds | $15,435 | -Replace metal ceiling in basement corridor |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 132666 | 4 | D | 10 | exceeds | $17,467 | -Remove steam trench and grate and replace VCT throughout in basement corridor. Includes project specific asbestos abatement. |
-Facilities reports the steam tunnel is abandoned and can be concrete filled. Replace the existing damaged VCT during the project.
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 299430 | 5 | D | 10 | exceeds | $52,035 | -Abate the mold and repair the damaged areas at the elevator machine room and the hoistway wall. |
-Prep and repaint the window sills in the library.
| Pending Totals: | | | | | | $0 | |
| Interior Finish/Door | 11654 | 1 | C | 10 | exceeds | $0 | -Most interior finishes are in fair condition. |
-The carpet is in fair condition.
| Pending Totals: | | | | | | | |
| Life Safety | 11655 | 1 | D | * | * | $47,758 | -Partially sprinkled. Complete the sprinkler installation at the basement and attic. |
-Exit fire stair handrails are older and do not meet the current life safety code.
| Pending Totals: | | | | | | | |
| Life Safety | 299431 | 2 | C | * | * | $0 | -Required fire extinguishers are available. |
-Required exit signs are available.
-Quick action egress door hardware is provided at all exit / egress doors and fire egress stairways.
| Pending Totals: | | | | | | | |
| Roof | 217260 | 2 | D | 20 | exceeds | $5,874 | -Water infiltration at flat roof. Recommend study to determine corrective actions to be taken. Study is pending completion by a VA contractor |
| Pending Totals: | | | | | | | |
| Roof | 11656 | 1 | C | 20 | 5 | $0 | -Asphalt shingle roof is in fair condition. |
-Prefinished sheet metal gutters and downspouts are in fair condition.
| Pending Totals: | | | | | | | |
| Signage / Wayfindg | 11657 | 1 | D | 10 | exceeds | $8,124 | -Interior signage is in poor condition and due to be upgraded. |
| Pending Totals: | | | | | | | |
| Windows | 14323 | 1 | D | 30 | exceeds | $89,940 | -Most wood windows are single pane and in poor condition. |
| Pending Totals: | | | | | | | |
| Windows | 299432 | 3 | | | | $0 | FCA record added by Contractor - see detail/pending |
| Pending Totals: | | | | | | | |
| Windows | 107957 | 2 | D | 30 | exceeds | $171,327 | -Replace (47) single glazed wood windows in basement. |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $748,586 | | System Replacement Cost | | $3,985,706 Ratio: 0.19 |
| System Total Pending | | | $0 | | | | |
| Electrical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Elec/Tele Closets | 14324 | 1 | D | 15 | | exceeds | $32,001 | Provide proper ventilation and space requirements for data closets. |
Electrical closets meet the requirements of NEC.
| Pending Totals: | | | | | | | |
| Emerg Elec Sys. | 14325 | 1 | D | 25 | exceeds | $32,001 | Replace Russellectric models RTM160A, 208Y/120V, 3 phase. Fed from building 95 and replaces Zenith ATS. Power egress and exit lighting. Poor condition. |
| Pending Totals: | | | | | | | |
| Fire Alarm | 107958 | 2 | F | 15 | exceeds | $62,403 | Provide new Fire Alarm System. Locate detectors, horns and strobes and synchronize strobe lights to meet NFPA 72 or ADA. Existing fire alarm control panel and system, poor condition. |
| Pending Totals: | | | | | | | |
| Lighting & Power | 14327 | 1 | C | 25 | 6 | $0 | All lighting fixtures are T-8 lamps with energy efficient electronic ballasts. Existing exit lights are LED type exit lights. |
| Pending Totals: | | | | | | | |
| Lightning Protect | 14328 | 1 | N/A | 20 | n/a | $6,401 | Perform risk analysis per NFPA 780 to determine need. |
| Pending Totals: | | | | | | | |
| Nurse Call/Int/TV | 14329 | 1 | B | 15 | 10 | $0 | New Cable TV system. |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 297261 | 2 | A | 30 | 30 | $0 | Eaton 1600AMB 208/120V, 3PH, 4W switchboard. |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 14330 | 1 | D | 30 | exceeds | $4,800 | Replace Square D Fused panel at 125A, 208Y/120V,3 phase. Poor condition. |
| Pending Totals: | | | | | | | |
| Transformer | 14332 | 1 | A | 30 | 30 | $0 | 1000kVA Transformer,13.8kV- 208Y/120V, 3PH. |
| Pending Totals: | | | |
| System Total Correction | $137,605 | System Replacement Cost | $1,678,192 Ratio: 0.08 |
| System Total Pending | | | |
| Mechanical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Air Handling Equip | 298921 | 2 | A | 20 | | 20 | $0 | SPD unit installed in 2013; RTU for SPD administration;excellent condition. |
| Pending Totals: | | | | | | | | |
| Air Handling Equip | 14333 | 1 | D | 20 | | exceeds | $1,910,227 | Replaced with a proper HVAC system. |
Heating and ventilating unit is old in attic, insulation was falling, rust spots. Poor condition. This should be replaced with a proper heating and air conditioning unit. Unit serves library.
| Pending Totals: | | | | | | | |
| Ducts & Water Dist | 14334 | 1 | N/A | 30 | * | $0 | Ductwork serving library unit, which was visible, was in poor condition. |
**Correction Costs: See Air Handl. Equip.**
| Pending Totals: | | | | | | | |
| Ducts & Water Dist | 298922 | 2 | A | 30 | 30 | $0 | Ductwork for new SPD unit; excellent condition. |
| Pending Totals: | | | | | | | |
| Engr. Control syst. | 298923 | 2 | A | 20 | 20 | $0 | Controls for new SPD system; excellent condition. |
| Pending Totals: | | | | | | | |
| Engr. Control syst. | 14335 | 1 | D | 20 | exceeds | $185,853 | Replace controls system with updated controls system. |
Minimal controls serving library, outdated.
| Pending Totals: | | | | | | | |
| Heating System | 14336 | 1 | D | 30 | exceeds | $386,477 | Replace old steam radiators, steam and condensate piping, and steam PRV. |
Old steam radiators, steam and condensate piping, and steam PRV, poor condition.
| Pending Totals: | | | | | | | |
| Heating System | 298924 | 2 | A | 30 | 30 | $0 | Steam/hot water convertor and pumping installed in 2013; excellent condition. |
| Pending Totals: | | | | | | | |
| Refrigeration Equip | 298927 | 1 | A | 23 | 23 | $0 | Air cooled chiller for SPD installed in 2013; excellent condition. |
| Pending Totals: | | | | | | | |
| Room Air Dist/Term | 14337 | 1 | N/A | 30 | * | $0 | Poor condition for library area. |
**Correction Costs: See Air Handl. Equip.**
| Pending Totals: | | | | | | | |
| Room Air Dist/Term | 298925 | 2 | A | 30 | 30 | $0 | Systems installed for SPD in 2013; excellent condition. |
| Pending Totals: | | | | | | | |
| Ventil (O.A. & Exh) | 14338 | 1 | N/A | 30 | * | $0 | Poor ventilation library area. |
**Correction Costs: See Air Handl. Equip.**
| Pending Totals: | | | | | | | |
| Exhaust Fans | 298926 | 1 | A | 25 | 25 | $0 | Five (5) exhaust fans installed with SPD in 2013; excellent condition. |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $2,482,558 | | System Replacement Cost | | $1,783,079 Ratio: 1.39 |
| System Total Pending | | | | | | | |
| Plumbing | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Fire Sprinkler / Pump | 107959 | 2 | D | 50 | | * | $70,157 | Provide complete sprinkler system for the second floor. |
| Pending Totals: | | | | | | | |
| Fire Sprinkler / Pump | 14339 | 1 | C | 50 | 28 | $0 | The first floor and basement are sprinklered, with a 4" fire service. |
| Pending Totals: | | | | | | | |
| Fixtures / Piping | 14340 | 1 | C- | 50 | exceeds | $0 | Some of the fixtures are original, but in servicable condition. Upper floor piping is servicable |
| Pending Totals: | | | | | | | |
| Fixtures / Piping | 107960 | 2 | A | 50 | 50 | $0 | Backflow preventor installed in 2012. |
Piping upgraded with SPD renovation in 2013.
| Pending Totals: | | | | | | | |
| Hot Water Heater | 14341 | 1 | A | 25 | 25 | $0 | Aerdo steam instantaneous heater installed in 2013; excellent condition. |
| Pending Totals: | | | | | | | |
| Medical Gases | 298928 | 1 | N/A | 30 | * | $0 | n/a |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $70,157 | | System Replacement Cost | | $629,322 Ratio: 0.11 |
| System Total Pending | | | | | | | |
| Structural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Floor Systems | 14342 | 1 | C | 100 | | 15 | $0 | -Concrete joists supported by concrete beams and masonry walls (2 story) in fair condition. |
| Pending Totals: | | | | | | | | |
| Foundations | 14343 | 1 | C | 100 | | 15 | $0 | -Spread footing and continuous wall footing in fair condition. |
| Pending Totals: | | | | | | | | |
| Seismic / Wind Load | 14344 | 1 | n/a | * | | * | $0 | Wind load governs. |
| Pending Totals: | | | | | | | | |
| Vertical Members | 107961 | 2 | B | 40 | | 35 | $0 | -Wood columns have been repaired and are in good condition |
| Pending Totals: | | | | | | | | |
| Vertical Members | 14345 | 1 | C | 100 | | 15 | $0 | -Concrete columns & masonry bearing walls in fair condition. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $0 | | | System Replacement Cost | | $2,097,739 Ratio: 0.00 |
| System Total Pending | | | | | | | | |
| Transport | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Elevators | 14346 | 1 | F | 20 | | exceeds | $314,476 | P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 65 fpm., 3 stops (B-G-1). The ground floor is a rear entrance. Controls are Elevator Systems relay type installed in 1976. The over all maintenance is below average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $314,476 | | | System Replacement Cost | | $314,661 Ratio: 1.00 |
| System Total Pending | | | | | | | | |
| Information Technology | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Inside Cable Plant (ICP) | 14331 | 1 | C | 15 | | 10+ | $0 | The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed. |
| Pending Totals: | | | | | | | |
| Telecommunications Rooms | 302805 | 1 | C | 15 | 10+ | $0 | The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies. |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302806 | 2 | D | 15 | $2,516 | Telecommunincations Room 112A 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. 5) have bare concrete floors, paint floors or apply appropriate flooring to reduce dust & static |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302807 | 3 | D | 15 | $17,243 | Telecommunications room 112A are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84. |
| Pending Totals: | | |
| System Total Correction | $19,759 | System Replacement Cost |
| System Total Pending | | |
| Bldg Total Correction | $3,773,140.48 | Bldg Total Replacement | $10,488,698 Bldg Ratio: 0.36 |
| Bldg Total Pending | $0.00 | | |
B#12
| Building | Year Built | Last Renov | | Floors | | | | |
| FCA GSF | | Current Function | Office Bldg. | | | | | |
| 12 | 1928 | 0 | | 3 | 15,311 | | Proposed Function | Office Bldg. |
| Details | | | | | | | | |
| Architectural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Accessibility | 14347 | 1 | D | * | | * | $140,642 | -Building is not accessible. |
-Provide ramp and accessible entrance at first floor.
-Upgrade public toilet facilities at first floor and basement.
| Pending Totals: | | | | | | | |
| Accessibility | 299433 | 2 | D | * | * | $491,631 | -An Elevator is needed to provide accessibility to all floors. |
-Required knee clearance at the sink in kitchen B06 is not provided.
-An accessible water cooler is not provided.
-Lever style door hardware is not provided.
-Required knee clearance at lavatories is not provided on the 1st and 2nd floor.
-Lavatory traps in most accessible restrooms on most floors are not insulated.
| Pending Totals: | | | | | | | |
| Accessibility | 299434 | 3 | B | * | * | $0 | -Accessible restrooms (B07 and B08) are provided in the basement building including accessible showers |
-Lever style door hardware is provided.
| Pending Totals: | | | | | | | |
| Exterior Walls | 107962 | 2 | D | 100 | exceeds | $83,860 | -Re-seal all penetrations and lock joints. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 14348 | 1 | C | 100 | 15 | $0 | -Exterior brick veneer walls are in fair condition. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132667 | 3 | D | 100 | exceeds | $70,036 | -Repair approximately 50% of wood cornices and eaves. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132668 | 4 | D | 100 | exceeds | $21,441 | -Replace wood columns at front entrance. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132669 | 5 | D | 100 | exceeds | $25,761 | -Repair masonry and concrete steps at front entrance. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132670 | 6 | D | 100 | exceeds | $32,496 | -Rake and point cast stone band (watertable) at first floor level. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132671 | 7 | D | 100 | exceeds | $11,056 | -Rake and point masonry wall (approximately 200 s.f.). |
| Pending Totals: | | | | | | | |
| Fixed Equipment | 14349 | 1 | C | 15 | exceeds | $0 | -Wood cabinets and countertops in the staff kitchen are in fair condition. |
-Exercise room (B09) equipment is in fair condition.
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 107963 | 2 | D | 10 | exceeds | $35,160 | -Upgrade finishes to two toilet rooms on the second floor. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 14350 | 1 | C | 10 | exceeds | $0 | -Most finishes are in fair condition. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 299435 | 3 | C | 10 | exceeds | $0 | -The interior finishes are in fair condition including the ACT and grid, VCT, office carpet, vinyl base, wall paint, doors and frames. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 299436 | 4 | D | 10 | exceeds | $25,682 | -Locate and repair the water infiltration into the basement. Verify there are foundation drains and they are functioning correctly. |
| Pending Totals: | | | | | | $0 | |
| Life Safety | 14351 | 1 | D | * | exceeds | $143,988 | -Not sprinkled. Sprinkle this business occupancy. |
-Exit fire stair handrails are older and do not meet the current life safety code.
-Repair the attic access door.
| Pending Totals: | | | | | | $0 | |
| Life Safety | 107964 | 2 | D | * | * | $3,387 | -Repair hold opens at corridor single doors. 2 pairs on first floor. |
| Pending Totals: | | | | | | | |
| Life Safety | 299439 | 3 | B | * | * | $0 | -Required exits are available. |
-Required fire extinguishers are available.
-Required exit signs are available.
-Quick action egress door hardware is provided at all exit / egress doors and fire egress stairways.
| Pending Totals: | | | | | | | |
| Roof | 14352 | 1 | D | 20 | exceeds | $116,689 | -Replace old asphalt shingle roof in poor condition, including structural repairs. |
| Pending Totals: | | | | | | | |
| Roof | 236961 | 2 | D | 20 | exceeds | $25,736 | -Replace 10 external roof drain conductors and downspouts. |
| Pending Totals: | | | | | | | |
| Roof | 299440 | 3 | D | 20 | exceeds | $21,463 | --Prep, repaint and reflash the roof dormers. (7) |
| Pending Totals: | | | | | | | |
| Signage / Wayfindg | 14353 | 1 | C | 10 | exceeds | $0 | Signage/Wayfinding is in fair condition |
| Pending Totals: | | | | | | | |
| Windows | 14354 | 1 | D | 30 | exceeds | $351,566 | -Replace original single glazed units with new double glazed aluminum window units (64). |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $1,600,594 | | System Replacement Cost | | $2,956,666 Ratio: 0.54 |
| System Total Pending | | | $0 | | | | |
| Electrical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Elec/Tele Closets | 14355 | 1 | D | 15 | | exceeds | $32,001 | Provide proper ventilation for data closets. |
Data closets do not meet space requirements and require appropriate ventilation.
Electrical panelboards are wall mounted.
| Pending Totals: | | | | | | | |
| Emerg Elec Sys. | 14356 | 1 | D | 25 | 25 | $14,770 | Centralized battery powered exit and egress lighting systems. |
| Pending Totals: | | | | | | | |
| Fire Alarm | 107965 | 2 | F | 15 | exceeds | $59,202 | Provide new Fire Alarm System. Locate detectors, horns and strobes and synchronize strobe lights to meet NFPA 72 or ADA. Existing fire alarm control panel and system, poor condition. |
| Pending Totals: | | | | | | | |
| Lighting & Power | 14358 | 1 | C | 25 | 6 | $0 | All lighting fixtures are T-8 lamps with energy efficient electronic ballasts. |
Existing exit lights are LED type exit lights.
| Pending Totals: | | | | | | | |
| Lightning Protect | 14359 | 1 | N/A | 20 | n/a | $6,401 | Perform risk analysis per NFPA 780 to determine need. |
| Pending Totals: | | | | | | | |
| Nurse Call/Int/TV | 14360 | 1 | C- | 15 | 2 | $0 | 10 year old Telphone System based Intercom. |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 14361 | 1 | F | 30 | exceeds | $78,772 | Replace Federal Pacific Electric panelboards obsolete, replacement parts not available and replace 1977 dated 400A 208Y/120V equipment. |
| Pending Totals: | | | | | | | |
| Transformer | 14363 | 1 | F | 30 | exceeds | $41,847 | Replace 75 KVA13.8kV-208/120V, 3PH padmount transformer in fair condition. |
| Pending Totals: | | | |
| System Total Correction | $232,993 | System Replacement Cost | $1,137,179 Ratio: 0.20 |
| System Total Pending | | | |
| Mechanical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Air Handling Equip | 298929 | 2 | B | 20 | | 14 | $0 | Air handling unit for basement; good condition |
| Pending Totals: | | | | | | | | |
| Air Handling Equip | 14364 | 1 | F | 20 | | * | $1,832,686 | Provide proper air ventilation system to meet code reuirements. |
Floors 1 & 2 window units for air conditioning. No proper ventilation is provided in the building, per ASHRAE. Code violation.
| Pending Totals: | | | | | | | |
| Ducts & Water Dist | 14365 | 1 | n/a | 30 | * | $0 | None installed. See air handling equipment. |
| Pending Totals: | | | | | | | |
| Ducts & Water Dist | 298932 | 2 | C | 30 | 10 | $0 | System for basement fan coil units; fair condition. |
| Pending Totals: | | | | | | | |
| Engr. Control syst. | 14366 | 1 | D | 20 | exceeds | $177,238 | Replace controls system with updated controls system. |
Minimal controls, outdated.
| Pending Totals: | | | | | | | |
| Heating System | 14367 | 1 | D | 30 | exceeds | $369,245 | Replace original steam radiators, piping and condensate pumps and a receiver. |
Steam/hot water convertor and pumps poor condition.
| Pending Totals: | | | | | | | |
| Refrigeration Equip | 298935 | 1 | A | 20 | 14 | $0 | McQuay Packaged Chiller outdoors at grade installed in 2007; excellent condition. |
| Pending Totals: | | | | | | | |
| Room Air Dist/Term | 14368 | 1 | A | 30 | 24 | $0 | Five fan coils in basement; excellent condition. |
| Pending Totals: | | | | | | | |
| Ventil (O.A. & Exh) | 14369 | 1 | n/a | 30 | * | $0 | Poor ventilation. |
**Correction Costs: See Air Handl. Equip.**
| Pending Totals: | | | | | | | |
| Exhaust Fans | 298936 | 1 | D | 25 | exceeds | $12,317 | Replace original exhaust fans. |
| Pending Totals: | | | $0 | |
| System Total Correction | $2,391,485 | System Replacement Cost | | $1,326,709 Ratio: 1.80 |
| System Total Pending | $0 | | | |
| Plumbing | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Fire Sprinkler / Pump | 14370 | 1 | n/a | 50 | | * | $0 | No fire service or sprinklers. |
| Pending Totals: | | | | | | | | |
| Fixtures / Piping | 14371 | 1 | C | 50 | | exceeds | $0 | Some of the fixtures are original, but in fair condition. |
| Pending Totals: | | | | | | | | |
| Fixtures / Piping | 107966 | 2 | D | 50 | | exceeds | $246,164 | Provide a 3" reduced pressure backflow preventer to the water sevice. Replace original hot, cold and sanitary piping systems. |
| Pending Totals: | | | | | | | |
| Hot Water Heater | 14372 | 1 | B | 25 | 22 | $0 | 80 gallon electric water heater installed in 2010. |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $246,164 | | System Replacement Cost | | $568,590 Ratio: 0.43 |
| System Total Pending | | | | | | | |
| Structural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Floor Systems | 14373 | 1 | C | 100 | | 15 | $0 | -Concrete joists supported by concrete beams (3 story) in fair condition. |
| Pending Totals: | | | | | | | | |
| Foundations | 14374 | 1 | C | 100 | | 15 | $0 | -Perimeter concrete footings and interior concrete spread footings are in good condition. |
| Pending Totals: | | | | | | | | |
| Seismic / Wind Load | 14375 | 1 | n/a | * | | * | $0 | Wind load governs. |
| Pending Totals: | | | | | | | | |
| Vertical Members | 14376 | 1 | C | 100 | | 15 | $0 | -Exterior masonry walls and concrete columns supporting wood framed roof rafters in fair condition. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $0 | | | System Replacement Cost | | $1,288,804 Ratio: 0.00 |
| System Total Pending | | | | | | | | |
| Information Technology | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Inside Cable Plant (ICP) | 14362 | 1 | C | 15 | | 10+ | $0 | The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed. |
| Pending Totals: | | | | | | | |
| Telecommunications Rooms | 302808 | 1 | C | 15 | 10+ | $0 | The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies. |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302809 | 2 | D | 15 | $6,604 | Telecommunincations Rooms 1, 2 and B07A 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302810 | 3 | D | 15 | $51,728 | Telecommunications rooms 1, 2 and B07A are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84. |
| Pending Totals: | | |
| System Total Correction | $58,332 | System Replacement Cost |
| System Total Pending | | |
| Bldg Total Correction | $4,529,568.57 | Bldg Total Replacement | $7,581,195 Bldg Ratio: 0.60 |
| Bldg Total Pending | $0.00 | | |
B#13
| Building | Year Built | Last Renov | | Floors | | | | |
| FCA GSF | | Current Function | Housekeeping Quarters | | | | | |
| 13 | 1928 | 0 | | 3 | 8,174 | | Proposed Function | Apartments |
| Details | | | | | | | | |
| Architectural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Accessibility | 132681 | 1 | C | * | | * | $0 | -Building is not accessible from grade. Acceptable for a residence. |
-An elevator is not provided for accessibility to all floors. Acceptable for a residence.
-Accessible restrooms (101, 201 and 217) are not provided in the building. Acceptable for a residence.
-An accessible water cooler is not provided. Acceptable for a residence.
-Lever style door hardware is not provided. Acceptable for a residence.
-Required knee clearance at lavatories is not provided Acceptable for a residence.
-Lavatory traps in most accessible restrooms on most floors are not insulated. Acceptable for a residence.
| Pending Totals: | | | | | | | |
| Exterior Walls | 299377 | 5 | D | 100 | 15 | $83,127 | -Prep and repaint the enclosed porches at either end of the building. |
-Retuck and repoint the brick at the base of the enclosed porches.
-Repair and repaint the rotten wood areas on the building.
-Remove the ivy off of the existing exterior brick.
| Pending Totals: | | | | | | | |
| Exterior Walls | 132682 | 1 | C | 100 | 15 | $0 | -Exterior walls are in fair condition. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132683 | 2 | D | 100 | exceeds | $136,273 | -Rake and point face brick (1,000 s.f.). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132684 | 3 | D | 100 | exceeds | $52,413 | -Rake and repoint cast stone banding (water table) at first floor and cast stone banding at upper floor level. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132685 | 4 | D | 100 | exceeds | $104,825 | -Re-seal all penetrations and caulk joints. |
| Pending Totals: | | | | | | | |
| Fixed Equipment | 134153 | 1 | C | 15 | 3 | $0 | -Wood cabinets and countertops in the kitchen are in fair condition. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 132686 | 1 | B | 10 | 9 | $11,077 | -The interior finishes were renovated in 2013 and are in good condition including the ACT and grid, kitchen VCT, wood base, wall paint, doors and frames. |
| Pending Totals: | | | | | | | |
| Life Safety | 132687 | 1 | C | * | * | $0 | -Not sprinkled. Acceptable for a residence. |
-Required exits are available.
-Required fire extinguishers are available.
-Required exit signs are not available. Acceptable for a residence.
-Quick action egress door hardware is not provided at all exit / egress doors. Acceptable for a residence..
| Pending Totals: | | | | | | | |
| Roof | 132688 | 1 | B | 20 | 18 | $0 | -Asphalt shingled roofs were replaced in 2012 and are in good condition. |
-Copper gutters and downspouts are in good condition.
| Pending Totals: | | | | | | | |
| Roof | 132689 | 2 | D | 20 | exceeds | $13,821 | -Replace 600 s.f. EPDM roofs at the side porches at either end of the building. |
| Pending Totals: | | | | | | | |
| Signage / Wayfindg | 132690 | 1 | C | 10 | exceeds | $0 | -Exterior building identification signage is in fair condition. |
-Interior signage is not provided and not required.
| Pending Totals: | | | | | | | |
| Windows | 299378 | 2 | B | 30 | 27 | $0 | -New fixed aluminum double pane windows were installed in 2013 and are in good condition. |
| Pending Totals: | | | | | | | |
| Windows | 132691 | 1 | C | 30 | 1 | $0 | -Aluminum double pane casement windows are in fair condition. |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $401,536 | | System Replacement Cost | | $1,685,922 Ratio: 0.24 |
| System Total Pending | | | | | | | |
| Electrical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Elec/Tele Closets | 131821 | 1 | N/A | n/a | | n/a | $0 | n/a |
| Pending Totals: | | | | | | | | |
| Emerg Elec Sys. | 297262 | 1 | A | 25 | | 21 | $0 | LED exit and emergency battery heads. |
| Pending Totals: | | | | | | | |
| Fire Alarm | 216574 | 1 | A | 15 | 11 | $0 | EST3 fire alarm system; integrate with proposed campus wide fire alarm system upgrade. |
| Pending Totals: | | | | | | | |
| Lighting & Power | 297263 | 1 | A | 25 | 21 | $0 | T-8 and CFL fixtures. |
| Pending Totals: | | | | | | | |
| Lightning Protect | 297264 | 1 | N/A | 20 | n/a | $6,401 | Perform risk analysis per NFPA 780 to determine needs. |
| Pending Totals: | | | | | | | |
| Nurse Call/Int/TV | 297265 | 1 | N/A | 15 | n/a | $0 | n/a |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 297266 | 1 | A | 30 | 26 | $0 | GE 400A 208/120V, 3PH, 4W panel with (8) 2P125A CBs to feed panels in buildings 13-16. GE 225A 208/120V, 3PH, 4W and 125A 208/120V, 1PH, 3W panels. |
| Pending Totals: | | | | | | | |
| Transformer | 297267 | 1 | A | 30 | 26 | $0 | Exterior pad mounted 225kVA 13.8kV-208/120V, 3PH feeds MDP. |
| Pending Totals: | | | |
| System Total Correction | $6,401 | System Replacement Cost | $613,063 Ratio: 0.01 |
| System Total Pending | | | |
| Mechanical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Engr. Control syst. | 132580 | 1 | D | 20 | | * | $28,309 | Replace steam radiator controls with updated controls system. |
| Pending Totals: | | | | | | | |
| Heating & Ventil. | 131819 | 1 | C | 15 | exceeds | $0 | Window A/C units. |
| Pending Totals: | | | | | | | |
| Heating System | 298937 | 1 | D | 20 | exceeds | $72,671 | Replace steam radiators and piping. |
| Pending Totals: | | | | | | | |
| Heating System | 298938 | 2 | B | 30 | 25 | $0 | Condensate pump replaced in 2008. |
Orifice traps replaced.
| Pending Totals: | | | | | | | |
| Exhaust Fans | 298939 | 1 | N/A | 25 | * | $0 | n/a no fans in place |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $100,980 | | System Replacement Cost | | $536,430 Ratio: 0.19 |
| System Total Pending | | | | | | | |
| Plumbing | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Fire Sprinkler / Pump | 131820 | 1 | n/a | 50 | | * | $0 | None |
| Pending Totals: | | | | | | | | |
| Fixtures / Piping | 131823 | 1 | D | 50 | | exceeds | $24,616 | Replace original hot, cold and sanitary piping systems. |
| Pending Totals: | | | | | | | |
| Hot Water Heater | 298942 | 2 | D | 25 | * | $6,132 | Remove old horizontal hot water storage tank. |
Estimator note: Tank removal, minor piping
| Pending Totals: | | | | | | | |
| Hot Water Heater | 298940 | 1 | B | 25 | 22 | $0 | 120 gallon electric heater installed in 2010; good condition. |
| Pending Totals: | | | | | | | |
| Medical Gases | 298941 | 1 | N/A | 50 | * | $0 | n/a |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $30,748 | | System Replacement Cost | | $306,532 Ratio: 0.10 |
| System Total Pending | | | | | | | |
| Structural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Floor Systems | 299379 | 1 | B | 100 | | 15 | $0 | -Building wood frame construction with wood floor joists on steel beams is in good condition. |
| Pending Totals: | | | | | | | | |
| Foundations | 299380 | 1 | B | 100 | | 15 | $0 | -Perimeter concrete footings and interior concrete spread footings are in good condition. |
| Pending Totals: | | | | | | | | |
| Seismic / Wind Load | 299381 | 1 | C | * | | * | $0 | -Wind load governs |
| Pending Totals: | | | | | | | | |
| Vertical Members | 299382 | 1 | B | 100 | | 15 | $0 | -Exterior masonry construction walls supporting wood frame construction and wood roof rafters are in good condition. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $0 | | | System Replacement Cost | | $689,695 Ratio: 0.00 |
| System Total Pending | | | | | | | | |
| Information Technology | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Inside Cable Plant (ICP) | 302811 | 1 | C | 15 | | 10+ | $0 | The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed. |
| Pending Totals: | | | | | | | |
| Telecommunications Rooms | 302812 | 1 | C | 15 | 10+ | $0 | The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies. |
| Pending Totals: | | | | | | |
| Telecommunications Rooms | 302813 | 2 | D | 15 | $2,201 | Telecommunincations Room 222 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. |
| Pending Totals: | | | | | |
| Telecommunications Rooms | 302814 | 3 | D | $17,243 | Telecommunications room 222 are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84. |
| Pending Totals: | | |
| System Total Correction | $19,444 | System Replacement Cost |
| System Total Pending | | |
| Bldg Total Correction | $559,109.74 | Bldg Total Replacement | $3,831,643 Bldg Ratio: 0.15 |
| Bldg Total Pending | | | |
B#14
| Building | Year Built | Last Renov | | Floors | | | | |
| FCA GSF | | Current Function | Housekeeping Quarters | | | | | |
| 14 | 1930 | 0 | | 3 | 5,549 | | Proposed Function | |
| Details | | | | | | | | |
| Architectural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Accessibility | 132692 | 1 | C | * | | * | $0 | -Building is not accessible from grade. Acceptable for a residence. |
-Building is not accessible by ramp. Acceptable for a residence.
-Accessible restrooms are not provided in the building. Acceptable for a residence.
-An accessible water cooler is not provided. Acceptable for a residence.
-Lever style door hardware is not provided. Acceptable for a residence.
-Required knee clearance at lavatories is not provided. Acceptable for a residence.
-Lavatory traps in most accessible restrooms on most floors are not insulated. Acceptable for a residence.
| Pending Totals: | | | | | | | |
| Exterior Walls | 132693 | 1 | C | 100 | 17 | $0 | -Exterior walls are in fair condition. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132694 | 2 | D | 100 | exceeds | $29,351 | -Reseal all penetrations and caulk joints. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132695 | 3 | D | 100 | exceeds | $78,619 | -Rake and point face brick (500 s.f.). |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132696 | 4 | D | 100 | exceeds | $22,013 | -Rake and repoint cast stone band at basement level. |
| Pending Totals: | | | | | | | |
| Exterior Walls | 132697 | 5 | D | 100 | exceeds | $24,187 | -Repair brick entrance steps (6R x 8' W) at 2 entrances. |
| Pending Totals: | | | | | | | |
| Fixed Equipment | 132698 | 1 | C | 15 | exceeds | $0 | -Wood cabinets and countertops in the kitchen are in fair condition. |
| Pending Totals: | | | | | | | |
| Interior Finish/Door | 132699 | 1 | D | 10 | exceeds | $378,090 | -Interior Finishes are at the end of their life cycle and are in poor condition. Renovate the interior. |
| Pending Totals: | | | | | | | |
| Life Safety | 132700 | 1 | B | * | * | $0 | -The building is sprinkled. |
-Required exits are available for a residence.
-Required fire extinguishers are available.
-Required exit signs are available.
-Quick action egress door hardware is not provided at all exit / egress doors and is not required for a residence.
| Pending Totals: | | | | | | | |
| Roof | 132701 | 1 | D | 20 | exceeds | $38,032 | -Replace asphalt shingle roof in poor condition. |
| Pending Totals: | | | | | | | |
| Roof | 132702 | 2 | B | 20 | 18 | $14,176 | -The EPDM roofs over the side porches were replaced in 2011 and are in good condition. |
| Pending Totals: | | | | | | | |
| Signage / Wayfindg | 132703 | 1 | D | 10 | exceeds | $4,979 | -Exterior building identification signage is not provided. |
-Interior signage is not provided and is not required for a residence.
| Pending Totals: | | | | | | | |
| Windows | 132704 | 1 | C | 30 | 1 | $0 | -Aluminum double glazed double hung windows are in fair condition. |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $589,447 | | System Replacement Cost | | $1,144,505 Ratio: 0.52 |
| System Total Pending | | | | | | | |
| Electrical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Elec/Tele Closets | 132677 | 1 | N/A | n/a | | n/a | $0 | n/a |
| Pending Totals: | | | | | | | | |
| Emerg Elec Sys. | 297268 | 1 | A | 25 | | 25 | $0 | LED exit and emergency battery heads. |
| Pending Totals: | | | | | | | |
| Fire Alarm | 216575 | 1 | A | 15 | 15 | $0 | EST3 fire alarm system; integrate with proposed campus wide fire alarm system upgrade. |
| Pending Totals: | | | | | | | |
| Lighting & Power | 297269 | 1 | A | 25 | 25 | $0 | T-8 and CFL fixtures. |
| Pending Totals: | | | | | | | |
| Lightning Protect | 297270 | 1 | N/A | 20 | n/a | $6,401 | Perform risk analysis per NFPA 780 to determine needs. |
| Pending Totals: | | | | | | | |
| Nurse Call/Int/TV | 297271 | 1 | N/A | 15 | n/a | $0 | n/a |
| Pending Totals: | | | | | | | |
| Secondary Dist. | 297272 | 1 | A | 30 | 30 | $0 | (2) GE 125A 208/120V, 1PH, 3W panels. |
| Pending Totals: | | | | | | | |
| Transformer | 297273 | 1 | A | 30 | 30 | $0 | Service is fed from building 13. |
| Pending Totals: | | | |
| System Total Correction | $6,401 | System Replacement Cost | $416,183 Ratio: 0.02 |
| System Total Pending | | | |
| Mechanical | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Heating System | 132678 | 1 | C | 30 | | exceeds | $0 | Heat is through old steam radiators. |
| Pending Totals: | | | | | | | | |
| Exhaust Fans | 298950 | 1 | N/A | 25 | | * | $0 | n/a No fans in place. |
| Pending Totals: | | | | | | | | |
| System Total Correction | | | $0 | | | System Replacement Cost | | $364,161 Ratio: 0.00 |
| System Total Pending | | | | | | | | |
| Plumbing | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Fire Sprinkler / Pump | 132679 | 1 | D | 50 | | exceeds | $20,441 | Fully Sprinklered. |
Replace or test heads over 50 years old per NFPA 25.
| Pending Totals: | | | | | | | |
| Fixtures / Piping | 132680 | 1 | D | 50 | exceeds | $20,309 | Replace original hot, cold and sanitary piping systems in poor condition. |
| Pending Totals: | | | | | | | |
| Hot Water Heater | 298947 | 1 | C | 30 | exceeds | $0 | 100 gallon eletric water heater and steam instantaneous heater in fair condition. |
| Pending Totals: | | | | | | | |
| Hot Water Heater | 298948 | 2 | B | 25 | 23 | $0 | 80 gallon electric; good condition. |
| Pending Totals: | | | | | | | |
| Medical Gases | 298949 | 1 | N/A | 30 | * | $0 | n/a |
| Pending Totals: | | | | | | | |
| System Total Correction | | | $40,750 | | System Replacement Cost | | $208,092 Ratio: 0.20 |
| System Total Pending | | | | | | | |
| Structural | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| Floor Systems | 299154 | 1 | C | 100 | | 17 | $0 | -Building wood frame construction with wood studs supporting wood roof rafters is in fair condition. |
| Pending Totals: | | | | | | | | |
| Foundations | 299155 | 1 | C | 100 | | 17 | $0 | -Perimeter concrete footings and interior concrete spread footings are in fair condition. |
| Pending Totals: | | | | | | | | |
| Seismic / Wind Load | 299156 | 1 | C | * | | * | $0 | -Wind load governs |
| Pending Totals: | | | | | | | | |
| Vertical Members | 299157 | 1 | C | 100 | | 17 | $0 | -Exterior masonry construction walls supporting wood frame construction and wood roof rafters is in fair condition. |
| Pending Totals: | | | | | | | | |