FCA by Building.xlsx

XLSX spreadsheet 457 KB Posted

Attached to
C1DA--518-22-111 Elevator Replacement Ph 3, A/E Federal contract opportunity
Solicitation number
36C24123Q0307
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This notice requests qualifications from SDVOSB firms for architect-engineer design services. The Bedford VA Medical Center requires design of elevator replacements at six buildings. Firms must have experience with similar medical facility projects and elevator replacements. Responses are due by March 2nd, 2023 and must include SF-330 qualifications, descriptions of relevant past projects, and evidence of SDVOSB status. The acquisition is set aside for SDVOSBs. The design contract value is estimated at $4 million. The selected firm will provide design services and may have an option for construction period services.

View the file

Other files for this federal contract opportunity

Other files attached to C1DA--518-22-111 Elevator Replacement Ph 3, A/E, newest first.
File Type Posted
Elevators Assessment per Bldg.xlsx XLSX spreadsheet
Inspection Reports Ph3.pdf PDF
Bldg 10 Site plans.pdf PDF
36C24123Q0307.docx DOCX document
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
Bldg 7 Site plans.pdf PDF
Bldg 62 Site plans.pdf PDF
Bldg 9 Site plans.pdf PDF
518-22-111 Replace Elevators Ph 3 SOW.pdf PDF
Elevator Inventory_1-19-22.xlsx XLSX spreadsheet
Bldg 6 Site plans.pdf PDF
CRG_Detailed_Customer_Procedures_Attachment_1_A-E_Procurements.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

rptFCAFacilityCondition_new

FCA - Basic FCA Report
Report Parameters: Program = VHA, District = 1, VISN = 1, Station = 518
518 - BedfordDistrict VHA - North Atlantic, VISN 1
Bldg #FunctionSF AreaHeating SystemAC SystemBoilerVentilationLighting
1Administration11,727
10Library21,183
12Offices15,311
13Housekeeping Qtrs8,174
14Housekeeping Qtrs5,549
15Housekeeping Qtrs9,267
16Housekeeping Qtrs3,841
17Research20,015
18GRECC17,556
18TQuonsett Hut Storage1,212
19Laundry Storage18,135
19TVacant Quonsett1,313
10SCrescent Bldg41,013
2Patient Care92,307
206 Bay Garage4,002
20TQuonsett Hut Storage1,220
22Boiler Plant8,685
22AHazmat Storage128
23Guard House210
27Elec Swgear389
28Storage391
28ASalt Storage1,536
28TGreenhouse2,000
29Research Storage458
3Dietetics/ Kitchen39,400
30Pumphouse293
325 Bay Garage3,054
33Fiscal4,941
39Vacant Bathrooms ??960
4Nursing Home122,175
49Barn3,600
5Research/ Vacant49,582
52Golf Course Shed202
55Recreation (Golf Course Clubhouse)1,600
6Patient Care60,659
60Elec Swgear320
61Administration65,017
62Patient Care62,122
63Storage (Garages)2,829
69Storage1,704
7Patient Care/ Domicillary68,896
70HSR &D ??49,664
71Pumphouse220
76Pumphouse600
77Pumphouse600
78Patient Care133,199
78ACanteen/ Theatre14,080
79Elec Bldg301
8CMOP/DSS51,166
80CWT/ SMS/ A&MM22,955
81Chapel7,037
82Gym/ Pool25,024
9Administration35,835
92Emergency Generator Bldg380
93Emergency Generator Bldg380
94Emergency Generator Bldg380
95Emergency Generator Bldg380
98Water Tower0
CCConnecting Corridors16,296
Site Utilities
Total SF AREA1,131,473
Bldg Total Correction$17,695,446.22Bldg Total Replacement$38,472,777 Bldg Ratio: 0.46
Bldg Total Pending$0.00
Station 518 Total Correction$213,661,070Station Total Replacement$717,182,884 Station Ratio: 0.30
Station Total Pending$0
Report TotalsCorrectionReplacement
$213,661,070$717,182,884
Pending
$0

&"Microsoft Sans Serif,Regular"&8 09-27-2016 &"Arial,Bold Italic"&11 VA Capital Asset Inventory &"Microsoft Sans Serif,Regular"&8Page &P of &N

B#1

BuildingYear BuiltLast RenovFloors
FCA GSFCurrent FunctionAdministration
119280311,727Proposed FunctionAdministration
Details
ArchitecturalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Accessibility125211C**$0-Building is accessible through connecting corridor.

-An accessible water cooler is provided.

Pending Totals:
Accessibility2994022D**$381,879-Accessible restrooms (104) are not provided in the building.

-Lever style door hardware is not provided.

-Required knee clearance at lavatories is not provided -Lavatory traps in most accessible restrooms on most floors are not insulated.

-Provide an 3 stop elevator for accessibility to all floors. (Accessibility to the Executive Director's offices and HR suite on the 2nd floor is required)

Pending Totals:
Exterior Walls125221C10015$0-Exterior wall is in fair condition.
Pending Totals:
Exterior Walls1078302D100exceeds$146,756-2007 FCA listed masonry repair project. Work still to be performed.
Pending Totals:
Exterior Walls1334764D15exceeds$99,584-Re-seal all penetrations and caulk joints (all windows and expansion joints).
Pending Totals:
Exterior Walls1334775D15exceeds$67,052-Scrape and paint wood cornice/eave (5,160l.f.).
Pending Totals:
Exterior Walls1334786D15exceeds$403,578-Rake and point joints in pre cast stone bands (2 @ 5,160 l.f.).
Pending Totals:
Exterior Walls2994037D10015$324,959-Abate the PCB's in the brick mortar when performing the exterior brick racking and repointing.
Pending Totals:
Interior Finish/Door1078312D10exceeds$64,765-Provide new carpet throughout on 1st floor.
Pending Totals:
Interior Finish/Door1326263D10exceeds$49,678-Provide suspended ceiling throughout and remove the 1x1 ceiling tile. (Facilities notes asbestos to be abated above the 1x1 ceiling tile. Costs to include the abatement are located in "Hazmat".)
Pending Totals:
Interior Finish/Door125241C10exceeds$0-Interior finishes in fair condition.
Pending Totals:
Interior Finish/Door2994044C10exceeds$0-The interior finishes are in fair condition including wall paint, doors and frames.
Pending Totals:
Life Safety2994054D**$86,050-Wood framed rafters in the attic is not sprinkled. Sprinkle the attic.
Pending Totals:
Life Safety125251D**$258,151-Not sprinkled. Provide a fire suppression system for this public business occupancy.

-Required fire extinguishers are not available.

-Required exit signs are not available.

-Exit fire stair handrails are older and do not meet the current life.

Pending Totals:
Life Safety1078343B**$0-Required exits are available.
Pending Totals:
Roof2994062D20exceeds$30,903-Prep, repaint and reflash the roof dormers and dormer windows.
Pending Totals:
Roof125261B3020$0-Newer asphalt shingle roof in good condition.
Pending Totals:
Signage / Wayfindg125271B109$0-Signage/Wayfinding has been upgraded and is in good condition.
Pending Totals:
Windows125281C30exceeds$0-Aluminum single glaze, double pane, double hung windows with bronze finish in fair condition.
Pending Totals:
System Total Correction$1,913,354System Replacement Cost$2,264,570 Ratio: 0.84
System Total Pending
ElectricalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Elec/Tele Closets125291D15exceeds$64,002Provide proper ventilation for Data closets.

Data closet in basement is located in an open area.

Electrical panelboards are wall mounted.

Pending Totals:
Emerg Elec Sys.125301D25exceeds$12,084Replace Russellectric Models RTM, 100A-3p, 208Y/120v, 3 phase transfer switch.

Fed from building no 92 engine/generator. Powers egress and exit lighting.

Pending Totals:
Fire Alarm1081362N/An/an/a$0n/a
Pending Totals:
Fire Alarm125311F15exceeds$52,869Provide new Fire Alarm System. Locate detectors, horns and strobes and synchronize strobe lights to meet NFPA 72 or ADA. Existing EST Model CM2N fire alarm control panel and system, poor condition.
Pending Totals:
Lighting & Power125321C-25exceeds$0All lighting fixtures are T-8 lamps with T-8 energy efficient electronic ballasts. Existing exit lights are LED type exit lights.
Pending Totals:
Lightning Protect125331N/A20n/a$6,401Perform risk analysis per NFPA 780 to determine need.
Pending Totals:
Nurse Call/Int/TV116341N/A15n/a$0n/a
Pending Totals:
Secondary Dist.116351D30exceeds$58,911Replace Federal Pacific Electric panelboards and main circuit breaker that is 250A, 208Y/120V,3 phase, obsolete, the firm has not been in business. Replace (2) Kelek 125AMB panels. Replacement parts are not available.
Pending Totals:
Secondary Dist.1081372F30exceeds$80,059Correct Electric (Deficiencies from Electrical Study Report, D.O.C. Feb-2005). Replace breakers as recommended in study. ($27000)
Pending Totals:
Transformer116371F30exceeds$54,379Replace old open type 225 KVA, 13.8kV-208Y/120V, 3 phase, padmounted transformer. Poor condition.
Pending Totals:
System Total Correction$328,705System Replacement Cost$870,988 Ratio: 0.38
System Total Pending
HazmatRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Asbestos2360991D**$15,105-Recommend analysis to determine extent of asbestos abatement required above ACT ceilings.
Pending Totals:
System Total Correction$15,105System Replacement Cost
System Total Pending
MechanicalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Air Handling Equip116381D20*$1,507,751Provide required ventilation with air handling units. Building is cooled with window units only. Window units get replaced when they break down. Building does not have proper ventilation. Code violation.
Pending Totals:
Ducts & Water Dist116391D30*$0None installed. See air handling equipment.
Pending Totals:
Engr. Control syst.116401D20*$145,237Provide controls system.

Minimal controls for radiators, outdated.

Pending Totals:
Heating System116411A3027$0Receiver and pumps were replaced in 2010.
Pending Totals:
Heating System1081382D30exceeds$302,781Replace original steam radiators and piping, poor condition.
Pending Totals:
Room Air Dist/Term116421D30*$0None installed. See air handling equipment.
Pending Totals:
Ventil (O.A. & Exh)116431D30*$0Poor ventilation. It requires proper ventilation per ASHRAE.

**Correction Costs: See Air Handl. Equip.**

Pending Totals:
System Total Correction$1,955,769System Replacement Cost$1,016,154 Ratio: 1.92
System Total Pending
PlumbingRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Fire Sprinkler / Pump116441n/a50*$0No fire service, no sprinklers.
Pending Totals:
Fixtures / Piping1081392D50exceeds$369,245Provide a 3" reduced pressure backflow preventer to the water sevice. Replace original hot, cold and sanitary piping systems.
Pending Totals:
Fixtures / Piping1091571C50exceeds$0The fixtures are old but HC fixtures have been added. Fair condition.
Pending Totals:
Hot Water Heater116461B2518$0Replaced in 2006 with instantaneous water heater.
Pending Totals:
Medical Gases2988531N/A30*$0n/a
Pending Totals:
System Total Correction$369,245System Replacement Cost$435,494 Ratio: 0.85
System Total Pending
StructuralRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Floor Systems116471C10015$0-One way concrete joists supported by concrete beams in fair condition.
Pending Totals:
Foundations116481C10015$0-Spread footing in fair condition.
Pending Totals:
Seismic / Wind Load116491n/a**$0Wind load governs.
Pending Totals:
Vertical Members116501C10015$0-Concrete columns in fair condition.
Pending Totals:
System Total Correction$0System Replacement Cost$987,120 Ratio: 0.00
System Total Pending
Information TechnologyRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Inside Cable Plant (ICP)116361C1510+$0The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed.
Pending Totals:
Telecommunications Rooms3027701C1510+$0The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies.
Pending Totals:
Telecommunications Rooms3027712D15$2,201Telecommunincations Room 2B1 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security.
Pending Totals:
Telecommunications Rooms3027723D15$3,564Telecommunincations Room B1 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. 5) have bare concrete floors, paint floors or apply appropriate flooring to reduce dust & static
Pending Totals:
Telecommunications Rooms3027734D$34,485Telecommunications rooms 2B1 and B1 are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84.
Pending Totals:
System Total Correction$40,251System Replacement Cost
System Total Pending
Bldg Total Correction$4,622,429.26Bldg Total Replacement$5,806,295 Bldg Ratio: 0.80
Bldg Total Pending

B#10

BuildingYear BuiltLast RenovFloors
FCA GSFCurrent FunctionLibrary
1019280421,183Proposed FunctionLibrary
Details
ArchitecturalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Accessibility116511B**$0-Building is accessible at grade and through connecting corridor and has an elevator.
Pending Totals:
Accessibility1079542D**$64,727-Upgrade men's and women's toilet room (106 and 107) and provide accessible water fountain.
Pending Totals:
Accessibility2994263D**$23,507-Lever style door hardware is not provided. (25-30 doors)
Pending Totals:
Exterior Walls2994279D10015$44,289-Repair, prep and repaint 25 l.f. of rusting metal railings at the front entry steps.

-Repair the pre cast monumental sign at the front entry.

-Repoint the two brick chimneys.

Pending Totals:
Exterior Walls1079552D100exceeds$73,378-Re-seal all penetrations and lock joints.
Pending Totals:
Exterior Walls1326593D100exceeds$35,392-Repair approx. 25% of wood cornices and eaves; scrape and paint 50%.
Pending Totals:
Exterior Walls1326604B10015$0-The four wood columns have been repaired, painted and are in good condition.
Pending Totals:
Exterior Walls1326615D10015$28,093-Repair approximately 8 s.f. of concrete slab at steps at the front entry.
Pending Totals:
Exterior Walls1326626D100exceeds$11,871-Repair concrete stairs and platform (17R x 8' W).
Pending Totals:
Exterior Walls1326637D100exceeds$22,013-Rake and point cast stone band at first floor level.
Pending Totals:
Exterior Walls1326648D100exceeds$31,448-Point brick and arched stair (approximately 200 s.f.).
Pending Totals:
Exterior Walls116521C10015$0-Exterior brick veneer walls are in fair condition.
Pending Totals:
Fixed Equipment116531C15exceeds$0-Fixed equipment is in fair condition.

-Book shelving is in fair condition.

-SPD equipment is located in the basement of the library is in fair condition.

Pending Totals:
Interior Finish/Door1079562D10exceeds$5,907-Repair approximately 500 SF of water damage at first floor
Pending Totals:
Interior Finish/Door1326653D10exceeds$15,435-Replace metal ceiling in basement corridor
Pending Totals:
Interior Finish/Door1326664D10exceeds$17,467-Remove steam trench and grate and replace VCT throughout in basement corridor. Includes project specific asbestos abatement.

-Facilities reports the steam tunnel is abandoned and can be concrete filled. Replace the existing damaged VCT during the project.

Pending Totals:
Interior Finish/Door2994305D10exceeds$52,035-Abate the mold and repair the damaged areas at the elevator machine room and the hoistway wall.

-Prep and repaint the window sills in the library.

Pending Totals:$0
Interior Finish/Door116541C10exceeds$0-Most interior finishes are in fair condition.

-The carpet is in fair condition.

Pending Totals:
Life Safety116551D**$47,758-Partially sprinkled. Complete the sprinkler installation at the basement and attic.

-Exit fire stair handrails are older and do not meet the current life safety code.

Pending Totals:
Life Safety2994312C**$0-Required fire extinguishers are available.

-Required exit signs are available.

-Quick action egress door hardware is provided at all exit / egress doors and fire egress stairways.

Pending Totals:
Roof2172602D20exceeds$5,874-Water infiltration at flat roof. Recommend study to determine corrective actions to be taken. Study is pending completion by a VA contractor
Pending Totals:
Roof116561C205$0-Asphalt shingle roof is in fair condition.

-Prefinished sheet metal gutters and downspouts are in fair condition.

Pending Totals:
Signage / Wayfindg116571D10exceeds$8,124-Interior signage is in poor condition and due to be upgraded.
Pending Totals:
Windows143231D30exceeds$89,940-Most wood windows are single pane and in poor condition.
Pending Totals:
Windows2994323$0FCA record added by Contractor - see detail/pending
Pending Totals:
Windows1079572D30exceeds$171,327-Replace (47) single glazed wood windows in basement.
Pending Totals:
System Total Correction$748,586System Replacement Cost$3,985,706 Ratio: 0.19
System Total Pending$0
ElectricalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Elec/Tele Closets143241D15exceeds$32,001Provide proper ventilation and space requirements for data closets.

Electrical closets meet the requirements of NEC.

Pending Totals:
Emerg Elec Sys.143251D25exceeds$32,001Replace Russellectric models RTM160A, 208Y/120V, 3 phase. Fed from building 95 and replaces Zenith ATS. Power egress and exit lighting. Poor condition.
Pending Totals:
Fire Alarm1079582F15exceeds$62,403Provide new Fire Alarm System. Locate detectors, horns and strobes and synchronize strobe lights to meet NFPA 72 or ADA. Existing fire alarm control panel and system, poor condition.
Pending Totals:
Lighting & Power143271C256$0All lighting fixtures are T-8 lamps with energy efficient electronic ballasts. Existing exit lights are LED type exit lights.
Pending Totals:
Lightning Protect143281N/A20n/a$6,401Perform risk analysis per NFPA 780 to determine need.
Pending Totals:
Nurse Call/Int/TV143291B1510$0New Cable TV system.
Pending Totals:
Secondary Dist.2972612A3030$0Eaton 1600AMB 208/120V, 3PH, 4W switchboard.
Pending Totals:
Secondary Dist.143301D30exceeds$4,800Replace Square D Fused panel at 125A, 208Y/120V,3 phase. Poor condition.
Pending Totals:
Transformer143321A3030$01000kVA Transformer,13.8kV- 208Y/120V, 3PH.
Pending Totals:
System Total Correction$137,605System Replacement Cost$1,678,192 Ratio: 0.08
System Total Pending
MechanicalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Air Handling Equip2989212A2020$0SPD unit installed in 2013; RTU for SPD administration;excellent condition.
Pending Totals:
Air Handling Equip143331D20exceeds$1,910,227Replaced with a proper HVAC system.

Heating and ventilating unit is old in attic, insulation was falling, rust spots. Poor condition. This should be replaced with a proper heating and air conditioning unit. Unit serves library.

Pending Totals:
Ducts & Water Dist143341N/A30*$0Ductwork serving library unit, which was visible, was in poor condition.

**Correction Costs: See Air Handl. Equip.**

Pending Totals:
Ducts & Water Dist2989222A3030$0Ductwork for new SPD unit; excellent condition.
Pending Totals:
Engr. Control syst.2989232A2020$0Controls for new SPD system; excellent condition.
Pending Totals:
Engr. Control syst.143351D20exceeds$185,853Replace controls system with updated controls system.

Minimal controls serving library, outdated.

Pending Totals:
Heating System143361D30exceeds$386,477Replace old steam radiators, steam and condensate piping, and steam PRV.

Old steam radiators, steam and condensate piping, and steam PRV, poor condition.

Pending Totals:
Heating System2989242A3030$0Steam/hot water convertor and pumping installed in 2013; excellent condition.
Pending Totals:
Refrigeration Equip2989271A2323$0Air cooled chiller for SPD installed in 2013; excellent condition.
Pending Totals:
Room Air Dist/Term143371N/A30*$0Poor condition for library area.

**Correction Costs: See Air Handl. Equip.**

Pending Totals:
Room Air Dist/Term2989252A3030$0Systems installed for SPD in 2013; excellent condition.
Pending Totals:
Ventil (O.A. & Exh)143381N/A30*$0Poor ventilation library area.

**Correction Costs: See Air Handl. Equip.**

Pending Totals:
Exhaust Fans2989261A2525$0Five (5) exhaust fans installed with SPD in 2013; excellent condition.
Pending Totals:
System Total Correction$2,482,558System Replacement Cost$1,783,079 Ratio: 1.39
System Total Pending
PlumbingRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Fire Sprinkler / Pump1079592D50*$70,157Provide complete sprinkler system for the second floor.
Pending Totals:
Fire Sprinkler / Pump143391C5028$0The first floor and basement are sprinklered, with a 4" fire service.
Pending Totals:
Fixtures / Piping143401C-50exceeds$0Some of the fixtures are original, but in servicable condition. Upper floor piping is servicable
Pending Totals:
Fixtures / Piping1079602A5050$0Backflow preventor installed in 2012.

Piping upgraded with SPD renovation in 2013.

Pending Totals:
Hot Water Heater143411A2525$0Aerdo steam instantaneous heater installed in 2013; excellent condition.
Pending Totals:
Medical Gases2989281N/A30*$0n/a
Pending Totals:
System Total Correction$70,157System Replacement Cost$629,322 Ratio: 0.11
System Total Pending
StructuralRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Floor Systems143421C10015$0-Concrete joists supported by concrete beams and masonry walls (2 story) in fair condition.
Pending Totals:
Foundations143431C10015$0-Spread footing and continuous wall footing in fair condition.
Pending Totals:
Seismic / Wind Load143441n/a**$0Wind load governs.
Pending Totals:
Vertical Members1079612B4035$0-Wood columns have been repaired and are in good condition
Pending Totals:
Vertical Members143451C10015$0-Concrete columns & masonry bearing walls in fair condition.
Pending Totals:
System Total Correction$0System Replacement Cost$2,097,739 Ratio: 0.00
System Total Pending
TransportRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Elevators143461F20exceeds$314,476P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 65 fpm., 3 stops (B-G-1). The ground floor is a rear entrance. Controls are Elevator Systems relay type installed in 1976. The over all maintenance is below average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013.
Pending Totals:
System Total Correction$314,476System Replacement Cost$314,661 Ratio: 1.00
System Total Pending
Information TechnologyRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Inside Cable Plant (ICP)143311C1510+$0The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed.
Pending Totals:
Telecommunications Rooms3028051C1510+$0The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies.
Pending Totals:
Telecommunications Rooms3028062D15$2,516Telecommunincations Room 112A 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security. 5) have bare concrete floors, paint floors or apply appropriate flooring to reduce dust & static
Pending Totals:
Telecommunications Rooms3028073D15$17,243Telecommunications room 112A are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84.
Pending Totals:
System Total Correction$19,759System Replacement Cost
System Total Pending
Bldg Total Correction$3,773,140.48Bldg Total Replacement$10,488,698 Bldg Ratio: 0.36
Bldg Total Pending$0.00

B#12

BuildingYear BuiltLast RenovFloors
FCA GSFCurrent FunctionOffice Bldg.
1219280315,311Proposed FunctionOffice Bldg.
Details
ArchitecturalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Accessibility143471D**$140,642-Building is not accessible.

-Provide ramp and accessible entrance at first floor.

-Upgrade public toilet facilities at first floor and basement.

Pending Totals:
Accessibility2994332D**$491,631-An Elevator is needed to provide accessibility to all floors.

-Required knee clearance at the sink in kitchen B06 is not provided.

-An accessible water cooler is not provided.

-Lever style door hardware is not provided.

-Required knee clearance at lavatories is not provided on the 1st and 2nd floor.

-Lavatory traps in most accessible restrooms on most floors are not insulated.

Pending Totals:
Accessibility2994343B**$0-Accessible restrooms (B07 and B08) are provided in the basement building including accessible showers

-Lever style door hardware is provided.

Pending Totals:
Exterior Walls1079622D100exceeds$83,860-Re-seal all penetrations and lock joints.
Pending Totals:
Exterior Walls143481C10015$0-Exterior brick veneer walls are in fair condition.
Pending Totals:
Exterior Walls1326673D100exceeds$70,036-Repair approximately 50% of wood cornices and eaves.
Pending Totals:
Exterior Walls1326684D100exceeds$21,441-Replace wood columns at front entrance.
Pending Totals:
Exterior Walls1326695D100exceeds$25,761-Repair masonry and concrete steps at front entrance.
Pending Totals:
Exterior Walls1326706D100exceeds$32,496-Rake and point cast stone band (watertable) at first floor level.
Pending Totals:
Exterior Walls1326717D100exceeds$11,056-Rake and point masonry wall (approximately 200 s.f.).
Pending Totals:
Fixed Equipment143491C15exceeds$0-Wood cabinets and countertops in the staff kitchen are in fair condition.

-Exercise room (B09) equipment is in fair condition.

Pending Totals:
Interior Finish/Door1079632D10exceeds$35,160-Upgrade finishes to two toilet rooms on the second floor.
Pending Totals:
Interior Finish/Door143501C10exceeds$0-Most finishes are in fair condition.
Pending Totals:
Interior Finish/Door2994353C10exceeds$0-The interior finishes are in fair condition including the ACT and grid, VCT, office carpet, vinyl base, wall paint, doors and frames.
Pending Totals:
Interior Finish/Door2994364D10exceeds$25,682-Locate and repair the water infiltration into the basement. Verify there are foundation drains and they are functioning correctly.
Pending Totals:$0
Life Safety143511D*exceeds$143,988-Not sprinkled. Sprinkle this business occupancy.

-Exit fire stair handrails are older and do not meet the current life safety code.

-Repair the attic access door.

Pending Totals:$0
Life Safety1079642D**$3,387-Repair hold opens at corridor single doors. 2 pairs on first floor.
Pending Totals:
Life Safety2994393B**$0-Required exits are available.

-Required fire extinguishers are available.

-Required exit signs are available.

-Quick action egress door hardware is provided at all exit / egress doors and fire egress stairways.

Pending Totals:
Roof143521D20exceeds$116,689-Replace old asphalt shingle roof in poor condition, including structural repairs.
Pending Totals:
Roof2369612D20exceeds$25,736-Replace 10 external roof drain conductors and downspouts.
Pending Totals:
Roof2994403D20exceeds$21,463--Prep, repaint and reflash the roof dormers. (7)
Pending Totals:
Signage / Wayfindg143531C10exceeds$0Signage/Wayfinding is in fair condition
Pending Totals:
Windows143541D30exceeds$351,566-Replace original single glazed units with new double glazed aluminum window units (64).
Pending Totals:
System Total Correction$1,600,594System Replacement Cost$2,956,666 Ratio: 0.54
System Total Pending$0
ElectricalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Elec/Tele Closets143551D15exceeds$32,001Provide proper ventilation for data closets.

Data closets do not meet space requirements and require appropriate ventilation.

Electrical panelboards are wall mounted.

Pending Totals:
Emerg Elec Sys.143561D2525$14,770Centralized battery powered exit and egress lighting systems.
Pending Totals:
Fire Alarm1079652F15exceeds$59,202Provide new Fire Alarm System. Locate detectors, horns and strobes and synchronize strobe lights to meet NFPA 72 or ADA. Existing fire alarm control panel and system, poor condition.
Pending Totals:
Lighting & Power143581C256$0All lighting fixtures are T-8 lamps with energy efficient electronic ballasts.

Existing exit lights are LED type exit lights.

Pending Totals:
Lightning Protect143591N/A20n/a$6,401Perform risk analysis per NFPA 780 to determine need.
Pending Totals:
Nurse Call/Int/TV143601C-152$010 year old Telphone System based Intercom.
Pending Totals:
Secondary Dist.143611F30exceeds$78,772Replace Federal Pacific Electric panelboards obsolete, replacement parts not available and replace 1977 dated 400A 208Y/120V equipment.
Pending Totals:
Transformer143631F30exceeds$41,847Replace 75 KVA13.8kV-208/120V, 3PH padmount transformer in fair condition.
Pending Totals:
System Total Correction$232,993System Replacement Cost$1,137,179 Ratio: 0.20
System Total Pending
MechanicalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Air Handling Equip2989292B2014$0Air handling unit for basement; good condition
Pending Totals:
Air Handling Equip143641F20*$1,832,686Provide proper air ventilation system to meet code reuirements.

Floors 1 & 2 window units for air conditioning. No proper ventilation is provided in the building, per ASHRAE. Code violation.

Pending Totals:
Ducts & Water Dist143651n/a30*$0None installed. See air handling equipment.
Pending Totals:
Ducts & Water Dist2989322C3010$0System for basement fan coil units; fair condition.
Pending Totals:
Engr. Control syst.143661D20exceeds$177,238Replace controls system with updated controls system.

Minimal controls, outdated.

Pending Totals:
Heating System143671D30exceeds$369,245Replace original steam radiators, piping and condensate pumps and a receiver.

Steam/hot water convertor and pumps poor condition.

Pending Totals:
Refrigeration Equip2989351A2014$0McQuay Packaged Chiller outdoors at grade installed in 2007; excellent condition.
Pending Totals:
Room Air Dist/Term143681A3024$0Five fan coils in basement; excellent condition.
Pending Totals:
Ventil (O.A. & Exh)143691n/a30*$0Poor ventilation.

**Correction Costs: See Air Handl. Equip.**

Pending Totals:
Exhaust Fans2989361D25exceeds$12,317Replace original exhaust fans.
Pending Totals:$0
System Total Correction$2,391,485System Replacement Cost$1,326,709 Ratio: 1.80
System Total Pending$0
PlumbingRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Fire Sprinkler / Pump143701n/a50*$0No fire service or sprinklers.
Pending Totals:
Fixtures / Piping143711C50exceeds$0Some of the fixtures are original, but in fair condition.
Pending Totals:
Fixtures / Piping1079662D50exceeds$246,164Provide a 3" reduced pressure backflow preventer to the water sevice. Replace original hot, cold and sanitary piping systems.
Pending Totals:
Hot Water Heater143721B2522$080 gallon electric water heater installed in 2010.
Pending Totals:
System Total Correction$246,164System Replacement Cost$568,590 Ratio: 0.43
System Total Pending
StructuralRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Floor Systems143731C10015$0-Concrete joists supported by concrete beams (3 story) in fair condition.
Pending Totals:
Foundations143741C10015$0-Perimeter concrete footings and interior concrete spread footings are in good condition.
Pending Totals:
Seismic / Wind Load143751n/a**$0Wind load governs.
Pending Totals:
Vertical Members143761C10015$0-Exterior masonry walls and concrete columns supporting wood framed roof rafters in fair condition.
Pending Totals:
System Total Correction$0System Replacement Cost$1,288,804 Ratio: 0.00
System Total Pending
Information TechnologyRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Inside Cable Plant (ICP)143621C1510+$0The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed.
Pending Totals:
Telecommunications Rooms3028081C1510+$0The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies.
Pending Totals:
Telecommunications Rooms3028092D15$6,604Telecommunincations Rooms 1, 2 and B07A 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security.
Pending Totals:
Telecommunications Rooms3028103D15$51,728Telecommunications rooms 1, 2 and B07A are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84.
Pending Totals:
System Total Correction$58,332System Replacement Cost
System Total Pending
Bldg Total Correction$4,529,568.57Bldg Total Replacement$7,581,195 Bldg Ratio: 0.60
Bldg Total Pending$0.00

B#13

BuildingYear BuiltLast RenovFloors
FCA GSFCurrent FunctionHousekeeping Quarters
131928038,174Proposed FunctionApartments
Details
ArchitecturalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Accessibility1326811C**$0-Building is not accessible from grade. Acceptable for a residence.

-An elevator is not provided for accessibility to all floors. Acceptable for a residence.

-Accessible restrooms (101, 201 and 217) are not provided in the building. Acceptable for a residence.

-An accessible water cooler is not provided. Acceptable for a residence.

-Lever style door hardware is not provided. Acceptable for a residence.

-Required knee clearance at lavatories is not provided Acceptable for a residence.

-Lavatory traps in most accessible restrooms on most floors are not insulated. Acceptable for a residence.

Pending Totals:
Exterior Walls2993775D10015$83,127-Prep and repaint the enclosed porches at either end of the building.

-Retuck and repoint the brick at the base of the enclosed porches.

-Repair and repaint the rotten wood areas on the building.

-Remove the ivy off of the existing exterior brick.

Pending Totals:
Exterior Walls1326821C10015$0-Exterior walls are in fair condition.
Pending Totals:
Exterior Walls1326832D100exceeds$136,273-Rake and point face brick (1,000 s.f.).
Pending Totals:
Exterior Walls1326843D100exceeds$52,413-Rake and repoint cast stone banding (water table) at first floor and cast stone banding at upper floor level.
Pending Totals:
Exterior Walls1326854D100exceeds$104,825-Re-seal all penetrations and caulk joints.
Pending Totals:
Fixed Equipment1341531C153$0-Wood cabinets and countertops in the kitchen are in fair condition.
Pending Totals:
Interior Finish/Door1326861B109$11,077-The interior finishes were renovated in 2013 and are in good condition including the ACT and grid, kitchen VCT, wood base, wall paint, doors and frames.
Pending Totals:
Life Safety1326871C**$0-Not sprinkled. Acceptable for a residence.

-Required exits are available.

-Required fire extinguishers are available.

-Required exit signs are not available. Acceptable for a residence.

-Quick action egress door hardware is not provided at all exit / egress doors. Acceptable for a residence..

Pending Totals:
Roof1326881B2018$0-Asphalt shingled roofs were replaced in 2012 and are in good condition.

-Copper gutters and downspouts are in good condition.

Pending Totals:
Roof1326892D20exceeds$13,821-Replace 600 s.f. EPDM roofs at the side porches at either end of the building.
Pending Totals:
Signage / Wayfindg1326901C10exceeds$0-Exterior building identification signage is in fair condition.

-Interior signage is not provided and not required.

Pending Totals:
Windows2993782B3027$0-New fixed aluminum double pane windows were installed in 2013 and are in good condition.
Pending Totals:
Windows1326911C301$0-Aluminum double pane casement windows are in fair condition.
Pending Totals:
System Total Correction$401,536System Replacement Cost$1,685,922 Ratio: 0.24
System Total Pending
ElectricalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Elec/Tele Closets1318211N/An/an/a$0n/a
Pending Totals:
Emerg Elec Sys.2972621A2521$0LED exit and emergency battery heads.
Pending Totals:
Fire Alarm2165741A1511$0EST3 fire alarm system; integrate with proposed campus wide fire alarm system upgrade.
Pending Totals:
Lighting & Power2972631A2521$0T-8 and CFL fixtures.
Pending Totals:
Lightning Protect2972641N/A20n/a$6,401Perform risk analysis per NFPA 780 to determine needs.
Pending Totals:
Nurse Call/Int/TV2972651N/A15n/a$0n/a
Pending Totals:
Secondary Dist.2972661A3026$0GE 400A 208/120V, 3PH, 4W panel with (8) 2P125A CBs to feed panels in buildings 13-16. GE 225A 208/120V, 3PH, 4W and 125A 208/120V, 1PH, 3W panels.
Pending Totals:
Transformer2972671A3026$0Exterior pad mounted 225kVA 13.8kV-208/120V, 3PH feeds MDP.
Pending Totals:
System Total Correction$6,401System Replacement Cost$613,063 Ratio: 0.01
System Total Pending
MechanicalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Engr. Control syst.1325801D20*$28,309Replace steam radiator controls with updated controls system.
Pending Totals:
Heating & Ventil.1318191C15exceeds$0Window A/C units.
Pending Totals:
Heating System2989371D20exceeds$72,671Replace steam radiators and piping.
Pending Totals:
Heating System2989382B3025$0Condensate pump replaced in 2008.

Orifice traps replaced.

Pending Totals:
Exhaust Fans2989391N/A25*$0n/a no fans in place
Pending Totals:
System Total Correction$100,980System Replacement Cost$536,430 Ratio: 0.19
System Total Pending
PlumbingRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Fire Sprinkler / Pump1318201n/a50*$0None
Pending Totals:
Fixtures / Piping1318231D50exceeds$24,616Replace original hot, cold and sanitary piping systems.
Pending Totals:
Hot Water Heater2989422D25*$6,132Remove old horizontal hot water storage tank.

Estimator note: Tank removal, minor piping

Pending Totals:
Hot Water Heater2989401B2522$0120 gallon electric heater installed in 2010; good condition.
Pending Totals:
Medical Gases2989411N/A50*$0n/a
Pending Totals:
System Total Correction$30,748System Replacement Cost$306,532 Ratio: 0.10
System Total Pending
StructuralRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Floor Systems2993791B10015$0-Building wood frame construction with wood floor joists on steel beams is in good condition.
Pending Totals:
Foundations2993801B10015$0-Perimeter concrete footings and interior concrete spread footings are in good condition.
Pending Totals:
Seismic / Wind Load2993811C**$0-Wind load governs
Pending Totals:
Vertical Members2993821B10015$0-Exterior masonry construction walls supporting wood frame construction and wood roof rafters are in good condition.
Pending Totals:
System Total Correction$0System Replacement Cost$689,695 Ratio: 0.00
System Total Pending
Information TechnologyRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Inside Cable Plant (ICP)3028111C1510+$0The cables in this building were installed during the last 10 years.cables are being installed on a daily basis and category 5e or category 6 cables are being used. The cables are being installed by contracted labor. The cables are being terminated to modular patch panels when needed. The cables are concealed in the intersital space above the drop ceilings. The cables are supported by cable tray and j-hooks as needed.
Pending Totals:
Telecommunications Rooms3028121C1510+$0The telecomm rooms in this building are in satisfactory conditions, however, most rooms have insufficient grounding infrastructure as well as size deficiencies. See detailed records for deficiencies.
Pending Totals:
Telecommunications Rooms3028132D15$2,201Telecommunincations Room 222 1) have no emergency power; install outlets with emergency power access. 2) have no grounding from IT equipment to building ground, install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded to building ground. 3) have abandoned cabling; remove abandoned cabling to comply with code. 4) have no signature logs, provide signature log sheets (VA Form 4793 Visitor Register) to comply with security.
Pending Totals:
Telecommunications Rooms3028143D$17,243Telecommunications room 222 are too small, expand rooms or relocate to locations that conform to requirements outlined in VA Space Planning Criteria Chapter 232 and OIT Design Guide Section 4 - 84.
Pending Totals:
System Total Correction$19,444System Replacement Cost
System Total Pending
Bldg Total Correction$559,109.74Bldg Total Replacement$3,831,643 Bldg Ratio: 0.15
Bldg Total Pending

B#14

BuildingYear BuiltLast RenovFloors
FCA GSFCurrent FunctionHousekeeping Quarters
141930035,549Proposed Function
Details
ArchitecturalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Accessibility1326921C**$0-Building is not accessible from grade. Acceptable for a residence.

-Building is not accessible by ramp. Acceptable for a residence.

-Accessible restrooms are not provided in the building. Acceptable for a residence.

-An accessible water cooler is not provided. Acceptable for a residence.

-Lever style door hardware is not provided. Acceptable for a residence.

-Required knee clearance at lavatories is not provided. Acceptable for a residence.

-Lavatory traps in most accessible restrooms on most floors are not insulated. Acceptable for a residence.

Pending Totals:
Exterior Walls1326931C10017$0-Exterior walls are in fair condition.
Pending Totals:
Exterior Walls1326942D100exceeds$29,351-Reseal all penetrations and caulk joints.
Pending Totals:
Exterior Walls1326953D100exceeds$78,619-Rake and point face brick (500 s.f.).
Pending Totals:
Exterior Walls1326964D100exceeds$22,013-Rake and repoint cast stone band at basement level.
Pending Totals:
Exterior Walls1326975D100exceeds$24,187-Repair brick entrance steps (6R x 8' W) at 2 entrances.
Pending Totals:
Fixed Equipment1326981C15exceeds$0-Wood cabinets and countertops in the kitchen are in fair condition.
Pending Totals:
Interior Finish/Door1326991D10exceeds$378,090-Interior Finishes are at the end of their life cycle and are in poor condition. Renovate the interior.
Pending Totals:
Life Safety1327001B**$0-The building is sprinkled.

-Required exits are available for a residence.

-Required fire extinguishers are available.

-Required exit signs are available.

-Quick action egress door hardware is not provided at all exit / egress doors and is not required for a residence.

Pending Totals:
Roof1327011D20exceeds$38,032-Replace asphalt shingle roof in poor condition.
Pending Totals:
Roof1327022B2018$14,176-The EPDM roofs over the side porches were replaced in 2011 and are in good condition.
Pending Totals:
Signage / Wayfindg1327031D10exceeds$4,979-Exterior building identification signage is not provided.

-Interior signage is not provided and is not required for a residence.

Pending Totals:
Windows1327041C301$0-Aluminum double glazed double hung windows are in fair condition.
Pending Totals:
System Total Correction$589,447System Replacement Cost$1,144,505 Ratio: 0.52
System Total Pending
ElectricalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Elec/Tele Closets1326771N/An/an/a$0n/a
Pending Totals:
Emerg Elec Sys.2972681A2525$0LED exit and emergency battery heads.
Pending Totals:
Fire Alarm2165751A1515$0EST3 fire alarm system; integrate with proposed campus wide fire alarm system upgrade.
Pending Totals:
Lighting & Power2972691A2525$0T-8 and CFL fixtures.
Pending Totals:
Lightning Protect2972701N/A20n/a$6,401Perform risk analysis per NFPA 780 to determine needs.
Pending Totals:
Nurse Call/Int/TV2972711N/A15n/a$0n/a
Pending Totals:
Secondary Dist.2972721A3030$0(2) GE 125A 208/120V, 1PH, 3W panels.
Pending Totals:
Transformer2972731A3030$0Service is fed from building 13.
Pending Totals:
System Total Correction$6,401System Replacement Cost$416,183 Ratio: 0.02
System Total Pending
MechanicalRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Heating System1326781C30exceeds$0Heat is through old steam radiators.
Pending Totals:
Exhaust Fans2989501N/A25*$0n/a No fans in place.
Pending Totals:
System Total Correction$0System Replacement Cost$364,161 Ratio: 0.00
System Total Pending
PlumbingRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Fire Sprinkler / Pump1326791D50exceeds$20,441Fully Sprinklered.

Replace or test heads over 50 years old per NFPA 25.

Pending Totals:
Fixtures / Piping1326801D50exceeds$20,309Replace original hot, cold and sanitary piping systems in poor condition.
Pending Totals:
Hot Water Heater2989471C30exceeds$0100 gallon eletric water heater and steam instantaneous heater in fair condition.
Pending Totals:
Hot Water Heater2989482B2523$080 gallon electric; good condition.
Pending Totals:
Medical Gases2989491N/A30*$0n/a
Pending Totals:
System Total Correction$40,750System Replacement Cost$208,092 Ratio: 0.20
System Total Pending
StructuralRec NoSeq NoConditionUseful LifeFCA RiskRemain LifeCorrection $Description
Floor Systems2991541C10017$0-Building wood frame construction with wood studs supporting wood roof rafters is in fair condition.
Pending Totals:
Foundations2991551C10017$0-Perimeter concrete footings and interior concrete spread footings are in fair condition.
Pending Totals:
Seismic / Wind Load2991561C**$0-Wind load governs
Pending Totals:
Vertical Members2991571C10017$0-Exterior masonry construction walls supporting wood frame construction and wood roof rafters is in fair condition.
Pending Totals: