Elevators Assessment per Bldg.xlsx
XLSX spreadsheet 14 KB Posted
- Attached to
- C1DA--518-22-111 Elevator Replacement Ph 3, A/E Federal contract opportunity
- Solicitation number
- 36C24123Q0307
About this file
This document outlines a federal contract opportunity for architect and engineering services. The Department of Veterans Affairs is seeking qualified Service-Disabled Veteran-Owned Small Businesses to provide design services for the replacement of six elevators at the Bedford VA Medical Center in Bedford, Massachusetts. Interested firms must submit SF-330 qualification statements by March 2, 2023 demonstrating experience with similar elevator replacement or medical facility projects. Qualifications in areas such as cost control, schedule compliance, and staff competency will be evaluated. The selected firm will then be invited to submit a price proposal to provide drawings, specifications, and construction period services for the $4 million elevator replacement project. The opportunity is set aside exclusively for SDVOSBs, and the selected firm must perform over 50% of the work.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FCA by Building.xlsx | XLSX spreadsheet | |
| Inspection Reports Ph3.pdf | ||
| Bldg 10 Site plans.pdf | ||
| 36C24123Q0307.docx | DOCX document | |
| Elevator Inventory_1-19-22.xlsx | XLSX spreadsheet | |
| Bldg 6 Site plans.pdf | ||
| CRG_Detailed_Customer_Procedures_Attachment_1_A-E_Procurements.docx | DOCX document | |
| VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx | DOCX document | |
| Bldg 7 Site plans.pdf | ||
| Bldg 62 Site plans.pdf | ||
| Bldg 9 Site plans.pdf | ||
| 518-22-111 Replace Elevators Ph 3 SOW.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Building | Transport | Rec No | Seq No | Condition | Useful Life | FCA Risk | Remain Life | Correction $ | Description |
| 1 | Elevators | No elevator. Required | |||||||
| 2 | Elevators | 14652 | 1 | D | 20 | 1 | $649,918 | P1 and P2 are in average condition. Duplex geared overhead traction with a capacity of 4000 lb., and operates at 200 fpm., 5 stops (B-1-2-3-4). Controls are MCE VVMC-1000-SCR installed in 1994. The over all maintenance is below average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 3 | Elevators | 14889 | 1 | D | 20 | exceeds | $314,476 | P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 100 fpm., 2 stops (B-1). Controls are Elevator systems Programmable I/O installed in 1990. The over all maintenance is below average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 3 | Elevators | 107903 | 2 | A | 20 | 17 | $0 | S1 is in good condition. Simplex overhead geared traction with a capacity of 2000 lb. and operates at 100 fpm., 2 stops (B-1) The basement is a rear entrance and the first floor has both front and rear entrances. Controls are Elevator Controls type V900 installed in 2010. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 4 | Elevators | 14951 | 1 | D | 20 | exceeds | $314,476 | P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 100 fpm., 3 stops (B-1-2). Controls are Elevator systems Programmable I/O installed in 1989. The elevator is equipped with a wanderguard system on the second floor. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 4 | Elevators | 217193 | 2 | D | 20 | exceeds | $314,476 | P2 is in in average condition. Simplex gearless overhead traction with a capacity of 3000 lb., and operates at 200 fpm., 3 stops (B-1-2) Controls are GAL Relay type 6SRM installed in 1989. The elevator is equipped with a wanderguard system on the first and second floors. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 5 | Elevators | 217194 | 2 | D | 20 | exceeds | $314,476 | P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 100 fpm., 3 stops (B-1-2). Controls are Elevator systems Programmable I/O installed in 1990. The elevator is currently programmed to only serve the basement and first floors. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 5 | Elevators | 217195 | 3 | D | 20 | exceeds | $314,476 | P2 is in in average condition. Simplex gearless overhead traction with a capacity of 4000 lb., and operates at 200 fpm., 3 stops (B-1-2) Controls are GAL Relay type 6SRM installed in 1989. The elevator is currently programmed to only serve the first and second floors. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. | |
| 5 | Elevators | 217196 | 4 | D | 20 | exceeds | $3,145 | WL1 is in average condition. National Wheel-O-Vator screw drive type platform lift, with a capacity of 750 lb., and operates at 9 fpm. The installation date is unknown. The travel is 41 inches. The unit is currently under power but not used. It is recommended that if the unit is no longer needed it should be removed. | |
| 6 | Elevators | 15015 | 1 | A | 20 | 17 | $0 | P1 is in average condition. Simplex overhead geared traction with a capacity of 3000 lb. and operates at 150 fpm., 3 stops (B-1-2). Controls are Elevator Controls installed in 2010. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 7 | Elevators | 14791 | 1 | D | 20 | 17 | $393,096 | P1 is in below average condition. Simplex overhead geared traction with a capacity of 3000 lb. and operates at 75 fpm., 3 stops (B-1-2). Controls are Elevator Controls installed in 2010. The over all maintenance is below average. The GAL rope gripper was installed incorrectly as well as several other Code deficiencies that should have been corrected during the recent renovation. It is recommended the elevator be evaluated for all deficiencies and corrective action taken. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 8 | Elevators | 15223 | 1 | C | 20 | 3 | $0 | P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 150 fpm., 4 stops (B-G-1-2). The ground floor is a rear entrance. Controls are MCE HMC-1000 installed in 1996. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 9 | Elevators | 15318 | 1 | F | 20 | exceeds | $314,476 | P1 is in average condition. Single automatic push button holed hydraulic with a capacity of 1800 lb. and operates at 100 fpm., 4 stops (B-G-1-2). The ground floor is a rear entrance. Controls are ESCO installed in 1967. The over all maintenance is average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 10 | Elevators | 14346 | 1 | F | 20 | exceeds | $314,476 | P1 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 65 fpm., 3 stops (B-G-1). The ground floor is a rear entrance. Controls are Elevator Systems relay type installed in 1976. The over all maintenance is below average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 12 | Elevators | No elevator. Required | ||||||
| 13 | Elevators | No elevator. Not required. | ||||||
| 14 | Elevators | No elevator. Not required. | ||||||
| 15 | Elevators | No elevator. Not required. | ||||||
| 16 | Elevators | No elevator. Not required. | ||||||
| 17 | Elevators | No elevator. Required | ||||||
| 18 | Elevators | No elevator. Required | ||||||
| 18T | Elevators | No elevator. Not required. | ||||||
| 19 | Elevators | No elevator. Not required. | ||||||
| 19T | Elevators | No elevator. Not required. | ||||||
| 20 | Elevators | No elevator. Not required. | ||||||
| 20T | Elevators | 14684 | 1 | F | 20 | exceeds | $314,476 | F1 is in average condition. Two stop basement winding drum with a capacity of 2000 lb., and operates at 25 fpm., 2 stops (B-1). Controls are FS Payne. The unit was installed in 1928. The overall maintenance is average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 22 | Elevators | No elevator. Not required. | ||||||
| 22A | Elevators | No elevator. Not required. | ||||||
| 23 | Elevators | No elevator. Not required. | ||||||
| 27 | Elevators | No elevator. Not required. | ||||||
| 28 | Elevators | No elevator. Not required. | ||||||
| 28A | Elevators | No elevator. Not required. | ||||||
| 28T | Elevators | No elevator. Not required. | ||||||
| 29 | Elevators | No elevator. Not required. | ||||||
| 30 | Elevators | No elevator. Not required. | ||||||
| 32 | Elevators | No elevator. Not required. | ||||||
| 33 | Elevators | No elevator. Required | ||||||
| 49 | Elevators | No elevator. Not required. | ||||||
| 52 | Elevators | No elevator. Not required. | ||||||
| 55 | Elevators | No elevator. Not required. | ||||||
| 60 | Elevators | No elevator. Not required. | ||||||
| 61 | Elevators | 15052 | 1 | F | 20 | exceeds | $314,476 | P1 is in average condition. Simplex overhead geared traction with a capacity of 3500 lb. and operates at 100 fpm., 3 stops (B-1-2). Controls are Serge relay type installed in 1983. The over all maintenance is average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 62 | Elevators | 15083 | 1 | D | 20 | exceeds | $314,476 | P2 is in average condition. Simplex holed hydraulic with a capacity of 4000 lb. and operates at 100 fpm., 3 stops (B-1-2). Controls are Elevator systems Programmable I/O installed in 1990. The over all maintenance is below average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 62 | Elevators | 108023 | 2 | A | 20 | 17 | $0 | P1 is in good condition. Simplex overhead geared traction with a capacity of 3000 lb. and operates at 100 fpm., 3 stops (B-1-2) Controls are Elevator Controls type V900 installed in 2010. The over all maintenance is average. The current operation and signaling fixtures do meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 63 | Elevators | No elevator. Not required. | ||||||
| 70 | Elevators | 15123 | 1 | D | 20 | exceeds | $314,476 | P1 is in average condition. Simplex overhead geared traction with a capacity of 4000 lb. and operates at 100 fpm., 3 stops (B-1-2) Controls are Beckwith relay type installed in 1967. The over all maintenance is average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 71 | Elevators | No elevator. Not required. | ||||||
| 78 | Elevators | 15160 | 1 | D | 20 | 2 | $649,918 | P1 and P2 are in below average condition. Duplex geared overhead traction with a capacity of 4000 lb., and operates at 250 fpm., 5 stops (G-1-2-3-4). Controls are MCE VVMC-1000-SCR installed in 1995. The over all maintenance is average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 78 | Elevators | 217242 | 2 | D | 20 | 2 | $324,959 | S3 is in below average condition. Simplex geared overhead traction with a capacity of 5000 lb., and operates at 200 fpm., 5 stops (G-1-2-3-4). Controls are MCE VVMC-1000-SCR installed in 1995. The over all maintenance is below average. The current operation and signaling fixtures do not meet ADA or VA Standard requirements. The annual testing was completed in August 2013. |
| 78A | Elevators | No elevator. Not required. | ||||||
| 79 | Elevators | No elevator. Not required. | ||||||
| 80 | Elevators | No elevator. Required | ||||||
| 81 | Elevators | No elevator. Not required. | ||||||
| 82 | Elevators | No elevator. Not required. | ||||||
| 92 | Elevators | No elevator. Not required. | ||||||
| 93 | Elevators | No elevator. Not required. | ||||||
| 94 | Elevators | No elevator. Not required. | ||||||
| 95 | Elevators | No elevator. Not required. |