INSP - VA Garland September 2025.pdf

PDF 631 KB Posted

Attached to
NTX Elevator Inspection
Solicitation number
36C25727Q0031-0001
Issued by

About this file

This document is a semi-annual elevator inspection report for VA Garland Medical Center, located at 2300 Marie Curie, Garland, TX 75216, dated September 17, 2025. The inspection was conducted by Eugene M. Kissinger (QEI C-5598), an elevator inspector with Reliant Elevator Inspections & Consulting, LLC, in accordance with A17.1 and A17.2 elevator code standards. The facility contains 13 elevators with the following characteristics: one Alpha AEC-H passenger elevator (installed 1997, altered 2024), ten KONE Resolve-100 elevators (installed 1995, altered 2014-2015), one TKE TAC-50 service elevator (installed 2004), and one BAXCO BMHC-20 hydraulic lift (installed 1992). All units are hydraulic-driven and all passed the semi-annual inspection testing.

The inspection identified 19 violations across the units requiring corrective repairs, including items such as missing Site Documentation/Maintenance Control Program information, missing repair emergency phone contact, audio signal deficiencies in car operating panels for Fire Phase I operations, broken hoistway door spirators, deficient emergency lighting and alarm systems, water or oil accumulation in pits, and restricted car door opening mechanisms. The next five-year safety test is due in 2027 for all units except P1, which is due in 2025. Building contact is Ken Ballard (214-742-8387), with the mailing address at 4500 S Lancaster, Dallas, TX 75215. All inspection forms were signed and certified as true and accurate reports.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA ELEVATOR INSPECTION

4602 Deepdale Drive Corpus Christi, Texas 78413 832-734-9977

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

correct.

1 of 14 Garland

VA Garland Medical Center P1 Alpha

2300 Marie Curie Garland TX 75216 AEC - H

240401-01-H-C1

X

1997 2024 2

125 4500 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

9/17/2025

4500 S Lancaster

X

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

3 of 14 Garland

VA Garland Medical Center P3 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20215624 X

X 1995 2014 5

350 4500 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Repair Fire Phase I (No audio signal in COP)

9/17/2025

4500 S Lancaster

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

4 of 14 Garland

VA Garland Medical Center P4 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20215629 X

X 1995 2014 5

350 4500 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.13 2016

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Hoist-way doors shall be self closing (lobby door has broken spirator)

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

ct.

5 of 14 Garland

VA Garland Medical Center P5 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20215608 X

X 1995 2014 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Repair Fire Phase I (no audio indicator in COP)

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

6 of 14 Garland

VA Garland Medical Center P6 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20215619 X

X 1995 2014 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.27.3 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Repair Fire Phase I (no audio indicator in COP)

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

rrect.

7 of 14 Garland

VA Garland Medical Center P7 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20215571 X

X 1995 2015 5

350 4000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

8 of 14 Garland

VA Garland Medical Center P8 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20216887 X

X 1995 2015 5

350 4000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.14.7.1.3 2016

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Repair emergency lighting and alarm.

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

correct.

9 of 14 Garland

VA Garland Medical Center P9 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20216893 X

X 1995 2015 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

10 of 14 Garland

VA Garland Medical Center P10 KONE

2300 Marie Curie Garland TX 75216 Resolve - 100

20216882 X

X 1995 2015 5

350 3000 1

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

rrect.

11 of 14 Garland

VA Garland Medical Center P11 TKE

2300 Marie Curie Garland TX 75216 TAC - 50

CR - 2279

X

X 2004 5

350 5200 2

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.14.7.1.3 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Repair emergency lighting and alarm.

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

12 of 14 Garland

VA Garland Medical Center P12 TKE

2300 Marie Curie Garland TX 75216 TAC - 50

CR - 2280

X

X 2004 5

350 5200 2

A17.1 8.6.1.4.1 2016 YES

A17.1 3.27.1 2016 YES

A17.1 2.14.5.7 2016 YES

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Restricted opening of car doors (repair or replace door restrictor)

9/17/2025

INSPECTION DATA - TO BE COMPLETED BY INSPECTOR

1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A

5. Building Name: Building Designation: 6.Manufacturer:

Building Physical Address: 7. Model Type:

Number, Street, Suite No., Apt. No. City State Zip

8. Serial Number:

9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :

10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors

Electric Hydraulic

14. Speed 15. Capacity 16. # of Car Openings

Other (specify)

17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)

Annual New Installation Alteration Re-Inspection

18. Test Data Tag in Place:

Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat

21. Comments:

Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.

22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING

I certify that this is a true report of my inspection. I further certify that the information on this report is correct.

C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed

CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT

24. Building Contact Name: Contact Phone Number:

Area Code Phone Number

Building Contact Business/Public Email Address: Building Contact Mailing Address:

(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip

See instruction sheet for disclosure information

25. Elevator Mechanic Name: Elevator Company:

13 of 14 Garland

VA Garland Medical Center P13 BAXCO

2300 Marie Curie Garland TX 75216 BMHC-20

871002-B X

X 1992 4

125 1500 1

A17.1 8.6.1.4.1 2016

A17.1 3.27.1 2016

A17.1 2.14.5.7 2016

A17.2 5.1.1e 2016

Ken Ballard 214 742-8387

Dallas Texas 75215

MCP's - Site Documentation (need Maintenance Control Program information)

Repair Emergency phone

Restricted opening of car doors (repair or replace door restrictor)

No water or oil shall be allowed to accumulate in pit.

9/17/2025

Garland - P1.pdf
Garland - P2.pdf
Garland - P3.pdf
Garland - P4.pdf
Garland - P5.pdf
Garland - P6.pdf
Garland - P7.pdf
Garland - P8.pdf
Garland - P9.pdf
Garland - P10.pdf
Garland - P11.pdf
Garland - P12.pdf
Garland - P13.pdf
Garland - P14.pdf

File details come from the government source that posted it. Updated .