INSP - VA Garland September 2025.pdf
PDF 631 KB Posted
- Attached to
- NTX Elevator Inspection
- Solicitation number
- 36C25727Q0031-0001
About this file
This document is a semi-annual elevator inspection report for VA Garland Medical Center, located at 2300 Marie Curie, Garland, TX 75216, dated September 17, 2025. The inspection was conducted by Eugene M. Kissinger (QEI C-5598), an elevator inspector with Reliant Elevator Inspections & Consulting, LLC, in accordance with A17.1 and A17.2 elevator code standards. The facility contains 13 elevators with the following characteristics: one Alpha AEC-H passenger elevator (installed 1997, altered 2024), ten KONE Resolve-100 elevators (installed 1995, altered 2014-2015), one TKE TAC-50 service elevator (installed 2004), and one BAXCO BMHC-20 hydraulic lift (installed 1992). All units are hydraulic-driven and all passed the semi-annual inspection testing.
The inspection identified 19 violations across the units requiring corrective repairs, including items such as missing Site Documentation/Maintenance Control Program information, missing repair emergency phone contact, audio signal deficiencies in car operating panels for Fire Phase I operations, broken hoistway door spirators, deficient emergency lighting and alarm systems, water or oil accumulation in pits, and restricted car door opening mechanisms. The next five-year safety test is due in 2027 for all units except P1, which is due in 2025. Building contact is Ken Ballard (214-742-8387), with the mailing address at 4500 S Lancaster, Dallas, TX 75215. All inspection forms were signed and certified as true and accurate reports.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA ELEVATOR INSPECTION
4602 Deepdale Drive Corpus Christi, Texas 78413 832-734-9977
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
correct.
1 of 14 Garland
VA Garland Medical Center P1 Alpha
2300 Marie Curie Garland TX 75216 AEC - H
240401-01-H-C1
X
1997 2024 2
125 4500 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
9/17/2025
4500 S Lancaster
X
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
3 of 14 Garland
VA Garland Medical Center P3 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20215624 X
X 1995 2014 5
350 4500 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Repair Fire Phase I (No audio signal in COP)
9/17/2025
4500 S Lancaster
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
4 of 14 Garland
VA Garland Medical Center P4 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20215629 X
X 1995 2014 5
350 4500 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.13 2016
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Hoist-way doors shall be self closing (lobby door has broken spirator)
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
ct.
5 of 14 Garland
VA Garland Medical Center P5 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20215608 X
X 1995 2014 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Repair Fire Phase I (no audio indicator in COP)
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
6 of 14 Garland
VA Garland Medical Center P6 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20215619 X
X 1995 2014 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.27.3 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Repair Fire Phase I (no audio indicator in COP)
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
rrect.
7 of 14 Garland
VA Garland Medical Center P7 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20215571 X
X 1995 2015 5
350 4000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
8 of 14 Garland
VA Garland Medical Center P8 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20216887 X
X 1995 2015 5
350 4000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.14.7.1.3 2016
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Repair emergency lighting and alarm.
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
correct.
9 of 14 Garland
VA Garland Medical Center P9 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20216893 X
X 1995 2015 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
10 of 14 Garland
VA Garland Medical Center P10 KONE
2300 Marie Curie Garland TX 75216 Resolve - 100
20216882 X
X 1995 2015 5
350 3000 1
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
rrect.
11 of 14 Garland
VA Garland Medical Center P11 TKE
2300 Marie Curie Garland TX 75216 TAC - 50
CR - 2279
X
X 2004 5
350 5200 2
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.14.7.1.3 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Repair emergency lighting and alarm.
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
12 of 14 Garland
VA Garland Medical Center P12 TKE
2300 Marie Curie Garland TX 75216 TAC - 50
CR - 2280
X
X 2004 5
350 5200 2
A17.1 8.6.1.4.1 2016 YES
A17.1 3.27.1 2016 YES
A17.1 2.14.5.7 2016 YES
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Restricted opening of car doors (repair or replace door restrictor)
9/17/2025
INSPECTION DATA - TO BE COMPLETED BY INSPECTOR
1. Unit # 2.Site Name: 3. Contract #: 4. Removed from Service Date: N/A
5. Building Name: Building Designation: 6.Manufacturer:
Building Physical Address: 7. Model Type:
Number, Street, Suite No., Apt. No. City State Zip
8. Serial Number:
9. Type of Unit: (Check one) Pass Esc. M.W Frt W.L. LULA Other (specify) :
10.Drive Machine: (check one) 11. Year Installed 12. Year Altered 13. # of Floors
Electric Hydraulic
14. Speed 15. Capacity 16. # of Car Openings
Other (specify)
17. Due Date for Next 5 year Safety Test: 19. Type of Inspection (check all that apply)
Annual New Installation Alteration Re-Inspection
18. Test Data Tag in Place:
Yes No Accident 5 Year Test OTHER Semi-Annual Item # Rule Code Year Violations (Use page ELE2a if additional pages are necessary) Check box if page 2 attached Repeat
21. Comments:
Semi-Annual inspection and testing per A17.1 and A17.2 elevator code. Testing was performed by Eugene M Kissinger - QEI C-5598, elevator inspector for Reliant Elevator Inspections & Consulting, LLC. Elevator test performed correctly and passed with the violations noted above.
22. INSPECTOR SIGNATURE IS REQUIRED FOR CERTIFICATE PROCESSING
I certify that this is a true report of my inspection. I further certify that the information on this report is correct.
C-5598 Eug QEI INSP LIC# Inspector Name Printed Date Inspection Completed
CONTACT INFORMATION - TO BE COMPLETED BY OWNER OR OWNER AGENT
24. Building Contact Name: Contact Phone Number:
Area Code Phone Number
Building Contact Business/Public Email Address: Building Contact Mailing Address:
(Ex. johndoe@yourcompanyemail.com) Number, Street, Suite No., Apt. No. City State Zip
See instruction sheet for disclosure information
25. Elevator Mechanic Name: Elevator Company:
13 of 14 Garland
VA Garland Medical Center P13 BAXCO
2300 Marie Curie Garland TX 75216 BMHC-20
871002-B X
X 1992 4
125 1500 1
A17.1 8.6.1.4.1 2016
A17.1 3.27.1 2016
A17.1 2.14.5.7 2016
A17.2 5.1.1e 2016
Ken Ballard 214 742-8387
Dallas Texas 75215
MCP's - Site Documentation (need Maintenance Control Program information)
Repair Emergency phone
Restricted opening of car doors (repair or replace door restrictor)
No water or oil shall be allowed to accumulate in pit.
9/17/2025
| Garland - P1.pdf |
| Garland - P2.pdf |
| Garland - P3.pdf |
| Garland - P4.pdf |
| Garland - P5.pdf |
| Garland - P6.pdf |
| Garland - P7.pdf |
| Garland - P8.pdf |
| Garland - P9.pdf |
| Garland - P10.pdf |
| Garland - P11.pdf |
| Garland - P12.pdf |
| Garland - P13.pdf |
| Garland - P14.pdf |
File details come from the government source that posted it. Updated .