This is a Geotechnical and Geophysical Investigation Data reference document prepared by Schnabel Engineering, LLC for the Beaver Creek Raw Water Pump Station, Intake and Transmission Main project in Albemarle County, Virginia, dated February 27, 2026. The document serves as supporting technical data for Invitation for Bids (IFB) #439 issued by the Rivanna Water & Sewer Authority (RWSA). The investigation encompasses subsurface exploration, seismic refraction testing, electrical resistivity imaging, and rock laboratory analysis at the proposed pump station and raw water line locations within the Beaver Creek Reservoir vicinity. The reference document includes site vicinity maps, test location plans showing boring locations (PS-1 through PS-4, B-1 through B-5, RW-1 through RW-3, and additional borings along the raw water line designated B-101 through B-110), seismic refraction traverse results (SR-1 through SR-9), electrical resistivity imaging results (L1 and L2), and comprehensive subsurface exploration logs documenting soil and rock conditions at specific drilling locations.

The investigation data provides critical geotechnical information for bid evaluation and construction planning, including Standard Penetration Test (SPT) results, rock core recovery percentages, Rock Quality Designation (RQD) values, pocket penetrometer readings, and in-situ packer test data presented in four appendices covering subsurface exploration data, soil laboratory test results, rock laboratory test data, and packer test data. The document notes that boring elevations were obtained from site topographic plans, with water-based borings from a barge referenced to a normal pool elevation of 539 feet. The geophysical data and boring logs document variations in soil and rock conditions across the site, including disintegrated rock zones and bedrock depths, with explicit limitations noted that geophysical data represents broad estimates of subsurface conditions and that unexpected variations may be encountered during actual construction activities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

February 27, 2026 Schnabel Engineering, LLC Project 21C43036 ©2026 All Rights Reserved

FIGURES

Figure 1: Site Vicinity Map Figure 2: Test Location Plan – Pump Station Figure 2A: Test Location Plan – Raw Water Line Figure 2B: Site Vicinity Geologic Map Figure 3: Seismic Refraction Results – SR-1, SR-2, SR-3, SR-4, SR-5, & SR-6 Figure 3A: Seismic Refraction Results – SR-7, SR-8, & SR-9 Figure 4: ERI Results – L1 & L2

Geotechnical and Geophysical Investigation Data for Beaver Creek Pump Station and Intake Project

Appendix C: Rock Laboratory Test Data

Appendix A: Subsurface Exploration Data Appendix B: Soil Laboratory Test Data

Appendix D: In-Situ Packer Test Data

³ 1/

5/

T hi s

M ap w as

C re at ed

In S ch na be l E ng in ee rin gs S ite V ic in ity M ap A pp lic at io n

NOT TO SCALE

ar cg is

RWSA INTAKE AND PUMP STATION

PROJECT NO. 21C43036

SITE VICINITY

MAP

FIGURE 1

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

Sources: Esri, HERE, Garmin, USGS, Intermap, INCREMENT P, NRCan, Esri Japan, METI, Esri China (Hong Kong), Esri Korea, Esri (Thailand), NGCC, (c) OpenStreetMap contributors, and the GIS User Community Esri, HERE, Garmin, (c) OpenStreetMap contributors Source: Esri, Maxar, Earthstar Geographics, and the GIS User Community Projection: WGS 1984 Web Mercator Auxiliary Sphere

© Schnabel Engineering, 2026. All Rights Reserved.

58559

52052

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LOD

LOD

LOD

LODLODLOD

LOD

LO

D

LO

D

LO

D

LO

D

LOD

LOD

LODLOD

LOD

LOD

LOD

LO

D

LO

D

LO

D

LOD

LOD

LOD

LOD

LOD LOD

LOD

LOD

LOD

LO

D

LOD

LOD

LOD

LOD

LOD

LO

D

LOD LOD

LOD

LO

D

LOD

LOD

LOD

LO

D

LOD

L1

L2

SR-5

SR-6SR

-7

SR-9

SR-4

SR-8

SR-2

SR-3

B-2

RW-2

RW-1

B-4

B-3

B-5

BR-2 AS-3

AS-2

RW-3

AS-1

PS-1

PS-2

B-1

PS-4

SR

-1

BR-1

PS-3

LEGEND

APPROXIMATE BORING LOCATION

APPROXIMATE SEISMIC REFRACTION TRAVERSES

APPROXIMATE ELECTRICAL RESISTIVITY TRAVERSES

N

00 75' 150'

SCALE: 1"=75' RWSA INTAKE AND PUMP STATION

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

Base Plan Provided by Hazen and Sawyer on November 11, 2025.

21C43036

C. IRIZARRY

N. SILMAN JAN 2026

Figure Name:

Project Number:

Done:

Reviewed:

Figure Number:

Date:

© Schnabel Engineering, 2026. All Rights Reserved.

Proposed Retaining Walls

Proposed Pump Station

Proposed Bridge

Proposed Access Road

Proposed Retaining Walls

Proposed Retaining Walls

R t 6

(B ro w ns G ap T ur np ik e)

TEST LOCATION PLAN - PUMP STATION

Note: Offset Borings PS-3A and RW-1A not shown for clarity.

58559 0595 54

52052

595600

585590595600

550555

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LOD

LO

D

LO

DLOD

LOD

LOD

LOD

LOD

LOD

LODLOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LODLOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LO

D

LOD

LOD

LOD LOD

LOD

LOD

LOD

LO

D

LOD LOD

LOD

LOD

LOD

LOD LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD

LOD LOD

LOD

LOD

LOD

LOD

LOD

LOD

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LO

D

LODLODLOD

LO

D

LO

D

LOD

LODLOD

LOD

LO

D

LOD

LOD

LOD LOD

LOD

LOD

LOD

LOD

LOD LOD

LOD LOD

LO

D

B-110

B-109

B-108

B-107

B-106

B-105

B-104

B-103

B-102 B-101

2A

00 150' 300'

SCALE: 1"=150' RWSA INTAKE AND PUMP STATION

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

Base Plan Provided by Hazen and Sawyer on November 11, 2025.

21C43036

C. IRIZARRY

N. SILMAN JAN 2026

Figure Name:

Project Number:

Done:

Reviewed:

Figure Number:

Date:

© Schnabel Engineering, 2026. All Rights Reserved.

TEST LOCATION PLAN - RAW WATER LINE

Proposed Alignment of Raw Water Line

Footprint of Proposed Pump Station and

Access Road

Old Three Notch'd Road

R t 6

(B ro w ns G ap T ur np ik e)

LEGEND

APPROXIMATE BORING LOCATION

APPROXIMATE CPT LOCATION

APPROXIMATE ELECTRICAL RESISTIVITY TRAVERSES

N

Note: Borings for Pump Station not shown for clarity. See Figure 2 for locations.

© Schnabel Engineering 2026 All Rights Reserved

GEOLOGIC MAP

RWSA INTAKE AND PUMP STATION

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

PROJECT NO. 21C43036

BEAVER CREEK DAM

Source: Southworth, Scott, et al. “Geologic Map of the Shenandoah National Park Region, Virginia .” U.S. Geologic Survey , 2009.

FIGURE 2B

ROCKFISH VALLEY HIGH-STRAIN

ZONE (PALEOZOIC)

SEISMIC REFRACTION RESULTS -

SR-1, SR-2, SR-3, SR-4,

SR- 5 & SR-6

FIGURE 3

RWSA INTAKE AND PUMP STATION

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

PROJECT NO. 21C43036.00

© Schnabel Engineering 2026 All Rights Reserved

Limitations: Geophysical data depicts a broad estimate of actual subsurface conditions. Correlation of this data with intrusive method data will indicate some variance due to the nature of measured geophysical properties. The resolution of the geophysical methods may be such as to not detect potentially significant small features such as individual boulders, which may appear significant in drilling results or excavations at a particular location. As such, some amount of variation in the actual field conditions should be expected.

Annotations on the results represent our interpretation of the data. We based the analyses and recommendations submitted in this report on the information revealed by our exploration. We attempted to provide for normal contingencies, but the possibility remains that unexpected conditions may be encountered during construction.

020406080100

Distance (ft)

El ev at io n (ft

4000 6000

020406080100 Distance (ft)

El ev at io n (ft

1000 1000 2000

4000 60006000800010000

1000 1000 2000

020406080100 Distance (ft)

El ev at io n (ft

200020002000 400040004000

60006000

10000 10000

20002000 400040004000 6000

1000010000

020406080100120140160180200220240260280

Distance (ft)

El ev at io n (ft

20004000

020406080100 Distance (ft)

El ev at io n (ft

Seismic Refraction Generalized Interpretation

0 1000

10000

12000 P-Wave Velocity (ft/s)

SR-1

SR-2SR-3

SR-4

SR-5

SR-6

SR-7

SR-8

SR-9

S N

W E

W E

NW SE

SW NE

SR-1

SR-2

SR-3

SR-4

SR-5

020406080100 Distance (ft)

El ev at io n (ft

SR-6

SW NE

Soil

Legend B-01

13 ft S Boring I.D

Offset from Traverse

Ground Surface

DR

Cored Rock

Interpreted Top of Rock

Auger Refusal

SR-2 AS-3

9 ft E SR-2

Line Intersection

SR-4 BR-2

5 ft NBR-1

10 ft N

AS-3

5 ft NSR-1

SR-3

SR-4

AS-2

13 ft NW

SR-3 BR-1

11 ft NE

SR-5

SR-8SR-6 AS-2

4 ft SW

AS-1

8 ft SWRW-2 6 ft SW

SR-4

SR-8

AS-1

7 ft NW

0 30 60

Scale 1 inch = 30 feet

Soil and Fill Disintegrated Rock (DR) Bedrock

SEISMIC REFRACTION RESULTS -

SR-7, SR-8, & SR-9

FIGURE 3A

RWSA INTAKE AND PUMP STATION

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

PROJECT NO. 21C43036.00

© Schnabel Engineering 2026 All Rights Reserved

Limitations: Geophysical data depicts a broad estimate of actual subsurface conditions. Correlation of this data with intrusive method data will indicate some variance due to the nature of measured geophysical properties. The resolution of the geophysical methods may be such as to not detect potentially significant small features such as individual boulders, which may appear significant in drilling results or excavations at a particular location. As such, some amount of variation in the actual field conditions should be expected.

Annotations on the results represent our interpretation of the data. We based the analyses and recommendations submitted in this report on the information revealed by our exploration. We attempted to provide for normal contingencies, but the possibility remains that unexpected conditions may be encountered during construction.

020406080100120

Distance (ft)

El ev at io n (ft

6000 6000

8000 8000

10000 10000 10000

0 20 40 60 80 100 120 140 160 180 200 220 Distance (ft)

El ev at io n (ft

6000 60002000 2000

8000 8000

10000

0 20 40 60 80 100 120 140 160 180 200 220

Distance (ft)

El ev at io n (ft

Soil and Fill

Seismic Refraction Generalized Interpretation Disintegrated

Rock (DR) Bedrock

0 1000

10000

12000 P-Wave Velocity (ft/s)

SR-1

SR-2SR-3

SR-4

SR-5

SR-6

SR-7

SR-8

SR-9

SR-8

SR-9

SR-7

NESW

NW SE

NW SE

Soil

Legend B-01

13 ft S Boring I.D

Offset from Traverse

Ground Surface

DR

Cored Rock

Interpreted Top of Rock

Auger Refusal

Line Intersection

SR-8 RW-2

14 ft E

SR-6 SR-4

RW-2

8 ft NSR-7

PS-3

8 ft N

PS-2

PS-1

4 ft NE

RW-3

6 ft NE

0 30 60

Scale 1 inch = 30 feet

AS-1

2 ft S

ERI RESULTS - L1 & L2

FIGURE 4

RWSA INTAKE AND PUMP STATION

BEAVER CREEK RESERVOIR

ALBEMARLE COUNTY, VIRGINIA

PROJECT NO. 21C43036.00

© Schnabel Engineering 2026 All Rights Reserved

Ground Surface

Legend

Wetter and/or more clayey soils

Rock

Limitations: Geophysical data depicts a broad estimate of actual subsurface conditions. Correlation of this data with intrusive method data will indicate some variance due to the nature of measured geophysical properties. The resolution of the geophysical methods may be such as to not detect potentially significant small features such as individual boulders, which may appear significant in drilling results or excavations at a particular location. As such, some amount of variation in the actual field conditions should be expected.

Annotations on the results represent our interpretation of the data. We based the analyses and recommendations submitted in this report on the information revealed by our exploration. We attempted to provide for normal contingencies, but the possibility remains that unexpected conditions may be encountered during construction.

Approximate Pump Station Extents (not at corresponding elevation) Approximate Tunnel Alignment Provided by Hazen & Sawyer (ACAD-C1-Model_Cl.dwg)

20002000

2000 2000

0 50 100 150 200 250 300 350 400 450 500 Distance (ft)

El ev at io n (ft

500 500

0 50 100 150 200 250 300 350 400 450 500 Distance (ft)

El ev at io n (ft

L1

L2

NE SW

N S

0 50 100

Scale 1 inch = 50 feet

10 30 130

20000

Resistivity (ohm-m)

Resistivity Generalized Interpretation Beaver Creek Reservoir

1+00 0+000+501+50

L2

Option 2 - Approximate Tunnel Stations (ft)

1+00 0+000+501+50 Option 1 - Approximate Tunnel Stations (ft)

2+00

L1

Line Intersection

L1

L2

Drier and/or more sandy soils

Disintegrated rock

Water

B-2 8 ft NW

B-1 8 ft NW

PS-3

14 ft SE

PS-2

8 ft W

PS-4

5 ft E

B-1 4 ft W

RW-3

9 ft E

SR-8

SR-9

SR-8

SR-9 Soil

B-01 13 ft S

Boring I.D Offset from Traverse

DR

Cored Rock Auger Refusal

Mud

Beaver Creek Reservoir

B-5 8 ft NW

B-4 8 ft NW

B-3 8 ft NW

APPENDIX A

SUBSURFACE EXPLORATION DATA

Subsurface Exploration Procedures General Notes for Subsurface Exploration Logs Identification of Soil Descriptive Criteria for Rock Core Logging Supplemental Rock Descriptive Terms Boring Logs – AS-1 to AS-3, B-1 to B-5, BR-1 and BR-2, PS-1 to PS-4, RW-1 to RW-3, and B-101 to B-110 Rock Core Photographic Logs

SUBSURFACE EXPLORATION PROCEDURES

Test Borings – Hollow Stem Augers

The borings are advanced by turning an auger with a center opening of 2¼ or 3¼ inches. A plug device blocks off the center opening while the augers are advanced. Cuttings are brought to the surface by the auger flights. Sampling is performed through the center opening in the hollow stem auger, by standard methods, after removal of the plug. Usually, no water is introduced into the boring using this procedure.

Standard Penetration Test Results

The numbers in the Sampling Data column of the boring logs represent Standard Penetration Test (SPT) results. Each number represents the blows needed to drive a 2-inch O.D., 1⅜-inch I.D. split-spoon sampler 6 inches, using a 140-pound hammer falling 30 inches. The sampler is typically driven a total of 18 or 24 inches. The first 6 inches are considered a seating interval. The total of the number of blows for the second and third 6-inch intervals is the SPT “N value.” The Standard Penetration Test is conducted according to ASTM D1586.

The SPT samples taken at the pump station site were obtained using an automatic trip hammer (ATH) rather than the standard safety hammer. The energy applied to the split-spoon sampler using the ATH is about 33 percent greater than that applied using the standard safety hammer. The hammer blows shown on the boring logs are uncorrected for the higher energy. However, we correct SPT N values for the higher energy when using N values in our analyses.

Soil Classification Criteria

The group symbols on the logs represent the Unified Soil Classification System Group Symbols (ASTM D2487) based on visual observation and limited laboratory testing of the samples. Criteria for visual identification of soil samples are included in this appendix. Some variation can be expected between samples visually classified and samples classified in the laboratory.

Disintegrated rock is defined as residual material with SPT N values between 60 blows per foot and refusal. Refusal is defined as an N value of 50 blows for a penetration of one inch or less.

Pocket Penetrometer Results

The values following “PP=” in the sampling data column of the logs represent pocket penetrometer readings. Pocket penetrometer readings provide an estimate of the unconfined compressive strength of fine-grained soils.

Rock Core Drilling

The drillers core drilled rock using special core bits set with carbide steel or diamond, depending upon the rock texture. The bit was fitted onto a double-tube, swivel-type core barrel in which an exterior tube and bit rotate, and an interior barrel remains stationary to receive the rock core. Drillers circulated water between the barrels and across the bit face to provide cooling and to flush away cuttings. The size of bits is indicated on individual boring logs.

The length of rock core recovered expressed as a percentage of the total length cored is shown on the logs. Rock Quality Designation (RQD) is also given for rock core drilled with NQ-size core drilling equipment. RQD is defined as the total length of NQ-size rock fragments recovered which are greater than 4 inches in length, discounting drilling breaks, expressed as a percentage of the total length cored.

RQD is preferred to core recovery as a measure of engineering characteristics of rock.

Water Observation Well

A temporary water observation well was installed in Boring B-1 by inserting a hand-slotted, 1¼-inch PVC pipe. The pipe was capped and the area surrounding the pipe was backfilled with cuttings from the boring.

Boring Locations and Elevations

Borings were located using sub-meter GPS equipment. Approximate boring locations are shown on Figures 2 and 2A. Ground surface elevations at the boring locations were obtained from the site topographic plan and are indicated on the boring logs. Where benches were created to gain equipment access, ground surface elevations for those borings were adjusted for the approximate cut/fill depths of the bench. Water based borings performed from a barge were based on a normal pool elevation of 539

ft. Locations and elevations should be considered no more accurate than the methods used to determine them.

GENERAL NOTES FOR

SUBSURFACE EXPLORATION LOGS

1. Numbers in sampling data column next to Standard Penetration Test (SPT) symbols indicate blows required to drive a 2-inch O.D., 1⅜-inch I.D. sampling spoon 6 inches using a 140 pound hammer falling 30 inches. The Standard Penetration Test (SPT) N value is the number of blows required to drive the sampler 12 inches, after a 6 inch seating interval. The Standard Penetration Test is performed in general accordance with ASTM D1586.

2. Visual classification of soil is in accordance with terminology set forth in “Identification of Soil.” The ASTM D2487 group symbols (e.g., CL) shown in the classification column are based on visual observations.

3. Estimated water levels indicated on the logs are only estimates from available data and may vary with precipitation, porosity of the soil, site topography, and other factors.

4. Refusal at the surface of rock, boulder, or other obstruction is defined as an SPT resistance of 50 blows for 1 inch or less of penetration.

5. The logs and related information depict subsurface conditions only at the specific locations and at the particular time when drilled or excavated. Soil conditions at other locations may differ from conditions occurring at these locations. Also, the passage of time may result in a change in the subsurface soil and water level conditions at the subsurface exploration location.

6. The stratification lines represent the approximate boundary between soil and rock types as obtained from the subsurface exploration. Some variation may also be expected vertically between samples taken. The soil profile, water level observations and penetration resistances presented on these logs have been made with reasonable care and accuracy and must be considered only an approximate representation of subsurface conditions to be encountered at the particular location.

7. Key to symbols and abbreviations:

S-01, SPT Sample No., Standard Penetration Test 5+10+10 Number of blows in each 6-inch increment

RUN 1, CORE Core No., Rock Core Run = 5.0 ft Run length in feet REC = 60", 100% Recovery in inches, Percent Recovery RQD = 60", 100% RQD in inches, Percent RQD

MC Moisture Content PP Pocket Penetrometer Reading (tsf) LL Liquid Limit PL Plastic Limit

%Passing#200 Percent by weight passing a No. 200 Sieve UCS Unconfined Compressive Strength (psi)

IDENTIFICATION OF SOIL

I. DEFINITION OF SOIL GROUP NAMES (ASTM D2487) SYMBOL GROUP NAME

Coarse-Grained Soils More than 50% retained on No. 200 sieve

Gravels – More than 50% of coarse fraction retained on No. 4 sieve Coarse, ¾” to 3” Fine, No. 4 to ¾”

Clean Gravels Less than 5% fines

GW WELL GRADED

GRAVEL

GP POORLY GRADED

GRAVEL

Gravels with fines More than 12% fines

GM SILTY GRAVEL

GC CLAYEY GRAVEL

Sands – 50% or more of coarse Fraction passes No. 4 sieve Coarse, No. 10 to No. 4 Medium, No. 40 to No. 10 Fine, No. 200 to No. 40

Clean Sands Less than 5% fines

SW WELL GRADED

SAND

SP POORLY GRADED

SAND

Sands with fines More than 12% fines

SM SILTY SAND

SC CLAYEY SAND

Fine-Grained Soils 50% or more passes the No. 200 sieve

Silts and Clays – Liquid Limit less than 50 Low to medium plasticity

Inorganic CL LEAN CLAY

ML SILT

Organic OL ORGANIC CLAY

ORGANIC SILT

Silts and Clays – Liquid Limit 50 or more Medium to high plasticity

Inorganic CH FAT CLAY

MH ELASTIC SILT

Organic OH ORGANIC CLAY

ORGANIC SILT

Highly Organic Soils Primarily organic matter, dark in color and organic odor PT PEAT

II. DEFINITION OF SOIL COMPONENT PROPORTIONS (ASTM D2487)

Examples

Adjective Form

GRAVELLY

SANDY

>30% to <50% coarse grained component in a fine-grained soil

GRAVELLY LEAN CLAY

CLAYEY

SILTY

>12% to <50% fine grained component in a coarse-grained soil

SILTY SAND

“With” WITH GRAVEL

WITH SAND

>15% to <30% coarse grained component in a fine-grained soil

FAT CLAY WITH GRAVEL

WITH GRAVEL

WITH SAND

>15% to <50% coarse grained component in a coarse-grained soil

POORLY GRADED GRAVEL WITH SAND

WITH SILT

WITH CLAY

>5% to <12% fine grained component in a coarse-grained soil

POORLY GRADED SAND WITH SILT

III. GLOSSARY OF MISCELLANEOUS TERMS

SYMBOLS .......................... Unified Soil Classification Symbols are shown above as group symbols. A dual symbol “-“ indicates the soil belongs to two groups. A borderline symbol “/” indicates the soil belongs to two possible groups.

FILL ....................................... Man-made deposit containing soil, rock and often foreign matter.

DISINTEGRATED ROCK

(DR)

Residual materials with a standard penetration resistance (SPT) between 60 blows per foot and refusal. Refusal is defined as an SPT of 50 blows for 1" or less penetration.

BOULDERS & COBBLES ..... Boulders are considered rounded pieces of rock larger than 12 inches, while cobbles range from 3 to 12-inch size.

LENSES ................................. 0 to ½-inch seam within a material in a test pit.

LAYERS ................................ ½ to 12-inch seam within a material in a test pit.

POCKET ................................ Discontinuous body within a material in a test pit.

MOISTURE CONDITIONS ..... Wet, moist or dry to indicate visual appearance of specimen.

COLOR .................................. Overall color, with modifiers such as light to dark or variation in coloration.

DESCRIPTIVE CRITERIA FOR ROCK CORE LOGGING

Rock is defined as natural subsurface material yielding SPT blow counts of N ≥ 100/2 inches (Martin, 1977). Rock descriptions may include the following descriptive elements, as applicable, generally in the order indicated. Supplemental descriptors may also be used, depending on project performance objectives and available information.

ROCK TYPE, strength, weathering, fracturing, color, recovery, RQD

Rock Type General terms are used following the NRCS (2001) rock type classification chart based on visual identification.

Some of the NRCS rock types common to our geographic area of practice are listed below. Mineralogical modifiers may be added where they help define distinct units (e.g., Garnet-Muscovite Schist).

Sedimentary: Conglomerate, Sandstone, Mudstone, Siltstone, Claystone, Shale, Limestone, Dolomite, Coal, Chert Igneous: Pegmatite, Granite, Diorite, Gabbro, Diabase, Rhyolite, Monzonite, Andesite, Basalt Metamorphic: Gneiss, Schist, Phyllite, Slate, Quartzite, Marble, Amphibolite, Hornfels

Strength (modified from Hoek, 2001) The estimated Uniaxial Compressive Strength associated with each rock strength term is based on the field strength index test for intact rock samples as follows.

• Extremely Strong >36,000 psi Specimen can only be chipped with a geological hammer.

• Very Strong 15,000 - 36,000 psi Specimen requires many blows of a geological hammer to fracture it.

• Strong 7,500 - 15,000 psi Specimen requires more than one blow of a geological hammer to fracture it.

• Medium Strong 3,500 - 7,500 psi Specimen cannot be peeled with a pocket knife; can be fractured with one blow from a geological hammer.

• Weak 700 - 3,500 psi Specimen can be peeled with a pocket knife with difficulty; shallow indentation made by firm blow with point of a geological hammer.

• Very Weak 150 - 700 psi Material crumbles under firm blows with point of a geological hammer;

can be peeled with a pocket knife.

Weathering (modified from ACOE, 1994; and USBR, 2001)

• Fresh Mineral crystals appear bright and show no discoloration. Fractures show little or no staining on their surfaces. Discoloration does not extend into intact rock.

• Slightly Weathered Rock is generally fresh except along fractures. Some fractures are stained and discoloration may extend up to 0.5 inches into rock.

• Moderately Weathered Significant portions of rock appear dull and discolored. Rock may be significantly weaker than in its fresh state near fractures. Soil zones of limited extent may occur along some fractures.

• Highly Weathered Rock appears dull and discolored throughout. Majority of rock mass is significantly weaker than in its fresh state. Isolated zones of stronger rock and/or soil may occur throughout.

• Severely Weathered Significant portions of rock mass essentially weathered to soil. Rock fabric may still be discernible (i.e., saprolite). Isolated zones of stronger rock may occur locally. Quartz may be present as hard, fractured dikes or veins.

Fracturing (from ACOE, 1994) Very Slightly Fractured > 6.5 ft Slightly Fractured 2 ft - 6.5 ft Moderately Fractured 8 in - 2 ft Highly Fractured 2.5 in - 8 in Intensely Fractured < 2.5 in

Color (from Munsell Color System; and GSA, 1995) Color descriptions include a primary color and up to two shade or secondary color modifiers, and may also include a color pattern term to define the relationship between multiple colors.

Shade: Light, Dark Secondary: Blackish, Brownish, Grayish, Greenish, Reddish, Yellowish, Orangeish Primary: Black, Brown, Gray, Green, Red, Yellow, Orange, White Pattern: and, to, with mottles of, with speckles of, with streaks of, with bands of

• Recovery is defined as the total length of recovered core in a core run divided by the total length of the core run, times 100 percent. A core run may be any depth interval of concern. Only natural fractures are considered for determining the length of core pieces. Mechanical breaks formed during or after coring do not count against the length determination. The length of recovered core pieces is measured along the core axis, between fracture midpoints.

• RQD (ASTM D6032, Deere & Deere, 1988, 1989) is defined as the total length of core pieces at least four inches long recovered from a core run divided by the total length of the core run, times 100 percent. A core run may be any depth interval of concern. Only natural fractures are considered for determining the length of core pieces. Mechanical breaks formed during or after coring do not count against the length determination. The length of recovered core pieces should be measured along the core axis, between fracture midpoints. Core pieces that are highly to severely weathered, very weak, or contain numerous pores should not count toward RQD.

SUPPLEMENTAL ROCK DESCRIPTIVE TERMS

In addition to the basic rock descriptive elements provided on the preceding Descriptive Criteria for Rock Core Logging sheet, rock descriptions may include the following supplemental descriptive elements depending on project performance objectives and available information.

Bedding Thickness & Inclination Bedding is defined as the layered arrangement of sediment deposits in sedimentary rock.

Bedding thickness is the average perpendicular distance between bedding surfaces. Bedding thickness intervals follow Bieniawski (1989). Inclination is measured in degrees from a plane perpendicular to the core axis (see Inclination Measurement Figure shown below).

Very Thickly Bedded > 6.5 ft Thickly Bedded 2 ft - 6.5 ft Medium Bedded 8 in - 2 ft Thinly Bedded 2.5 in - 8 in Very Thinly Bedded < 2.5 in

Foliation Character & Inclination Foliation is defined as the planar arrangement of textural features in metamorphic rock. Inclination is measured in degrees from a plane perpendicular to the core axis (see Inclination Measurement Figure).

Strongly Foliated Foliation is easily discernible throughout.

Moderately Foliated Foliation is discernible with some difficulty.

Poorly Foliated Foliation is generally not discernible.

Fracture Set Data Individual fractures or fracture sets may be characterized by the following descriptive elements, when applicable and discernible: fracture type, inclination (as per Inclination Measurement Figure above), average spacing, roughness and infilling condition. An example fracture set data description for an individual stratum is: 4 joints at 80-90°, moderately spaced, slightly rough, with spotty iron staining and partially filled with pyrite. If fractures are rare, they can be described individually by listing the depth, followed by the descriptive terms in this section.

FRACTURE TYPE

Fracture Any natural break in rock; ‘Fracture’ is the general term used for individual breaks that do not fall into any of the following fracture-type categories

Joint A relatively planar fracture without shear displacement; occurs with other similarly oriented joints generally at regularly spaced intervals

Shear A fracture along which differential movement has taken place parallel to the surface (i.e., shear displacement) sufficient to produce slickensides or polishing

Fault A major fracture along which there has been appreciable shear displacement accompanied by gouge and/or a severely fractured zone

Bedding Fracture A fracture along a bedding plane Foliation Fracture A fracture along a foliation plane Vein Fracture A fracture along the contact of an intrusive vein

Average Spacing (NRCS, 2001)

Very Widely Spaced > 6.5 ft Widely Spaced 2 ft - 6.5 ft Moderately Spaced 8 in - 2 ft Closely Spaced 2.5 in - 8 in Very Closely Spaced < 2.5 in

Roughness (Bieniawski, 1989) Very Rough Rough Slightly rough Smooth Slickensided

Infilling Condition Coverage Type Spotty Filling of (≤ 50% coverage) Calcite Partially Filled with (50 to 100% coverage) Chlorite Filled with (100% coverage) Clay Gypsum Iron Staining Manganese Mica Pyrite Quartz Talc

Inclination Measurement Figure

Fracture Spacing

Inclination

- Most surface asperities extend > 2 mm from the average planar surface.

- Most surface asperities extend 0.5 to 2 mm from the average planar surface.

- Most surface asperities extend < 0.5 mm from the average planar surface.

- Generally smooth to touch with few surface asperities.

- Infilling material contains slickensides.

ML

SM

DR

566.0

562.0

554.0

3.0

7.0

15.0

S-01, SPT

2+3+3+5

REC=20", 83%

S-02, SPT

2+4+9+33

REC=22", 92%

S-03, SPT

11+22+21+21

REC=24", 100%

S-04, SPT

6+15+21+40

REC=23", 96%

S-05, SPT

10+22+27+37

REC=24", 100%

S-06, SPT

15+30+37+50

REC=22", 92%

RESIDUUM

About 0.7 ft of cut performed for boring access.

5 inches of topsoil prior to cut.

C

D

MC = 29.3%

PP = 2.75 tsf

MC = 11.6%

Bottom of Boring at 15.0 ft.

Boring terminated at selected depth.

Boring backfilled with cuttings and borehole plug upon completion.

SANDY SILT; moist, olive- brown, contains mica

SILTY SAND, fine to coarse grained sand; moist, light brown, contains mica

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, light brown, contains mica

Encountered

Completion

Casing Pulled

3/18

3/18

3/18

Dry

Dry

Dry

9.0'

Schnabel Representative: C. Irizarry

Total Depth: 15.0 ft

Method: 3-1/4" I.D. Hollow Stem Auger

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 569± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/18/22 Finished: 3/18/22

Latitude: 38.07048 Longitude: -78.65295

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 1

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

AS-1

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

D T

8/

DR

564.0

562.5

555.1

5.0

6.5

13.9

S-01, SPT

1+1+2+2

REC=24", 100%

S-02, SPT

1+3+5+12

REC=22", 92%

S-03, SPT

2+5+14+14

REC=19", 79%

S-04, SPT

25+43+50/5"

REC=16", 94%

S-05, SPT

20+24+32+50/5"

REC=23", 100%

S-06, SPT

32+50/5"

REC=11", 100%

RESIDUUM

About 1 ft of cut performed for boring access.

4 inches of topsoil prior to cut.

Augers grinding/scraping.

C

D

LL = 46

PL = 29

MC = 13.0%

% Passing #200 = 48.3

Bottom of Boring at 13.9 ft.

Boring terminated at selected depth.

Boring backfilled with cuttings and borehole plug upon completion.

SILTY SAND, fine to coarse grained sand; moist, brown, contains root fragments Change: olive- brown

SILTY SAND WITH GRAVEL, fine to coarse grained sand; moist, light brown, contains rock fragments

DISINTEGRATED ROCK, sampled as silty sand with gravel, fine to coarse grained sand; moist, brown, contains mica, and rock fragments Change: gray

Encountered

Completion

Casing Pulled

3/16

3/16

3/16

Dry

Dry

Dry

10.5'

Schnabel Representative: C. Irizarry

Total Depth: 13.9 ft

Method: 3-1/4" I.D. Hollow Stem Auger

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 569± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/16/22 Finished: 3/16/22

Latitude: 38.07027 Longitude: -78.65274

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 1

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

AS-2

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

DR

566.5

557.2

4.5

13.8

S-01, SPT

2+3+8+8

REC=13", 54%

S-02, SPT

3+10+28+36

REC=24", 100%

S-03, SPT

5+32+50/4"

REC=16", 100%

S-04, SPT

50/4"

REC=4", 100%

S-05, SPT

19+50/3"

REC=9", 100%

S-06, SPT

17+50/3"

REC=9", 100%

RESIDUUM

About 0.3 ft of cut performed for boring access.

6 inches of topsoil prior to cut.

Augers grinding/scraping.

C

D

LL = 33

PL = 27

MC = 8.1%

% Passing #200 = 51.1 PP = 2.50 tsf

Bottom of Boring at 13.8 ft.

Boring terminated at selected depth.

Boring backfilled with cuttings upon completion.

SANDY SILT; moist, brown, contains mica

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, brown, contains mica Change: contains rock fragments

Encountered

Completion

Casing Pulled

3/15

3/15

3/15

Dry

Dry

Dry

8.0'

Schnabel Representative: C. Irizarry

Total Depth: 13.8 ft

Method: 3-1/4" I.D. Hollow Stem Auger

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 571± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/15/22 Finished: 3/15/22

Latitude: 38.07016 Longitude: -78.65210

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 1

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

AS-3

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

MH

DR

SM

DR

566.5

563.0

560.0

555.5

550.5

0.5

4.0

7.0

11.5

16.5

S-01, SPT

1+3+2+5

REC=18", 75%

S-02, SPT

3+3+6+9

REC=24", 100%

S-03, SPT

4+11+12+17

REC=23", 96%

S-04, SPT

7+22+38+42

REC=24", 100%

S-05, SPT

13+34+36+33

REC=23", 96%

S-06, SPT

3+7+10+23

REC=22", 92%

S-07, SPT

45+50/3"

REC=9", 100%

S-08, SPT

50/2"

REC=2", 100%

S-09, SPT

50/3"

REC=3", 100%

S-10, SPT

50/2"

REC=1", 50%

RESIDUUM

Augers grinding/scraping.

Augers grinding/scraping.

Augers

C

D

C

D

LL = 51

PL = 30

MC = 26.5%

% Passing #200 = 56.2 PP = 1.50 tsf PP = 2.00 tsf

MC = 8.3%

MC = 6.4%

Topsoil; 6 inches

SANDY ELASTIC SILT; moist, brown, contains mica, and root fragments

SILTY SAND, fine to coarse grained sand; moist, brown

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, light brown

SILTY SAND, fine to coarse grained sand; moist, brown with streaks of white

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, light brown, contains rock fragments

Change: brown

Encountered

After Drilling

After Drilling

Temporary Well

Temporary Well

3/24

3/24

3/25

5/5

8/16

37.0'

31.4'

12.3'

27.8'

29.9'

Schnabel Representative: C. Irizarry

Total Depth: 85.0 ft

Method: 3-1/4" I.D. Hollow Stem Auger, NQ Double Barrel

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 567± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/24/22 Finished: 3/28/22

Latitude: 38.07065 Longitude: -78.65334

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 3

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-1

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

(continued)

520.5

506.5

497.0

46.5

60.5

70.0

S-11, SPT

50/5"

REC=5", 100%

S-12, SPT

50/3"

REC=1", 33%

RUN 1, CORE

Run = 3.5 ft

REC=38", 90%

RQD=19", 45%

RUN 2, CORE

Run = 5.0 ft

REC=60", 100%

RQD=44", 73%

RUN 3, CORE

Run = 5.0 ft

REC=60", 100%

RQD=47", 78%

RUN 4, CORE

Run = 5.0 ft

REC=60", 100%

RQD=55", 92%

RUN 5, CORE

Run = 5.0 ft

REC=60", 100%

RQD=60", 100%

RUN 6, CORE

Run = 5.0 ft

REC=60", 100%

RQD=60", 100%

RUN 7, CORE

Run = 5.0 ft

REC=60", 100%

RQD=57", 95%

RUN 8, CORE

Run = 5.0 ft

REC=60", 100%

RQD=60", 100%

grinding/scraping.

RESIDUUM

Auger cuttings wet.

BLUE RIDGE

BASEMENT

COMPLEX

Water added.

No return water.

Gray return water.

Drilling penetration rate slower.

D

E

UCS = 12587

psi

UCS = 4250 psi

UCS = 16692

psi

UCS = 19713

psi

UCS = 14124

psi

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, light brown, contains rock fragments (continued) Change: wet

AUGEN GNEISS, medium strong, highly weathered, highly fractured (2.5

- 8 in), dark gray and light gray, strongly foliated, contains quartz augens Change: moderately weathered to slightly weathered, highly fractured (2.5

- 8 in) to moderately fractured (8 in - 2 ft)

MYLONITE, strong, slightly weathered, moderately fractured (8 in - 2 ft), gray and light gray, strongly foliated

AUGEN GNEISS, strong, slightly weathered, moderately fractured (8 in - 2 ft), gray and light gray, strongly foliated, contains quartz augens

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 2 of 3

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-1

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

482.085.0

BLUE RIDGE

BASEMENT

COMPLEXE

Bottom of Boring at 85.0 ft.

Boring terminated at selected depth.

Temporary well installed upon completion.

AUGEN GNEISS, strong, slightly weathered, moderately fractured (8 in - 2 ft), gray and light gray, strongly foliated, contains quartz augens (continued)

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 3 of 3

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-1

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

DR

SM

DR

552.6

547.0

544.5

541.5

536.5

528.0

0.4

6.0

8.5

11.5

16.5

25.0

S-01, SPT

2+2+3+4

REC=17", 71%

S-02, SPT

4+4+6+8

REC=22", 92%

S-03, SPT

2+3+4+5

REC=21", 88%

S-04, SPT

3+8+19+23

REC=22", 92%

S-05, SPT

19+36+43+37

REC=21", 88%

S-06, SPT

19+23+22+28

REC=24", 100%

S-07, SPT

50/6"

REC=6", 100%

S-08, SPT

50/4"

REC=4", 100%

RUN 1, CORE

Run = 3.5 ft

REC=42", 100%

RQD=15", 36%

RUN 2, CORE

Run = 5.0 ft

REC=60", 100%

RQD=51", 85%

RUN 3, CORE

Run = 5.0 ft

RESIDUUM

Augers grinding/scraping.

Auger cuttings wet.

BLUE RIDGE

BASEMENT

COMPLEX

Water added.

Brown return water.

Gray return water.

C

D

C

D

E

MC = 26.0%

PP = 1.25 tsf

PP = 1.50 tsf

LL = 43

PL = 35

MC = 19.2%

% Passing #200 = 58.3

MC = 10.7%

UCS = 6369 psi

Topsoil; 5 inches

SANDY SILT; moist, dark brown, contains mica, and root fragments Change: olive- brown

SILTY SAND, fine to coarse grained sand; moist, brown

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, light brown, contains mica, and rock fragments

SILTY SAND, fine to coarse grained sand; moist, olive- brown, contains mica

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, brown, contains mica, and rock fragments Change: wet

AUGEN GNEISS, medium strong, highly weathered to moderately weathered, intensely fractured (< 2.5

in) to highly fractured (2.5 - 8 in), gray and grayish brown, strongly foliated, contains quartz augens.

Encountered

After Drilling

Completion

3/22

3/22

3/23

18.0'

17.0'

16.5'

Schnabel Representative: C. Irizarry

Total Depth: 60.0 ft

Method: 3-1/4" I.D. Hollow Stem Auger, NQ Double Barrel

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 553± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/22/22 Finished: 3/24/22

Latitude: 38.07074 Longitude: -78.65312

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-2

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

499.5

493.0

53.5

60.0

REC=60", 100%

RQD=30", 50%

RUN 4, CORE

Run = 5.0 ft

REC=60", 100%

RQD=42", 70%

RUN 5, CORE

Run = 5.0 ft

REC=60", 100%

RQD=40", 67%

RUN 6, CORE

Run = 5.0 ft

REC=56", 93%

RQD=36", 60%

RUN 7, CORE

Run = 5.0 ft

REC=60", 100%

RQD=60", 100%

RUN 8, CORE

Run = 1.5 ft

REC=18", 100%

RQD=18", 100%

BLUE RIDGE

BASEMENT

COMPLEX

No return water.

Drilling penetration rate slower.

Drilling penetration rate slower.

Drilling penetration rate faster.

E

UCS = 7288 psi

UCS = 20512

psi

Bottom of Boring at 60.0 ft.

Boring terminated at selected depth.

Boring backfilled with cement/bentonite grout through tremie pipe upon completion.

AUGEN GNEISS, medium strong, highly weathered to moderately weathered, intensely fractured (< 2.5

in) to highly fractured (2.5 - 8 in), gray and grayish brown, strongly foliated, contains quartz augens. (continued)

Change: strong, moderately weathered, highly fractured (2.5 - 8 in)

AMPHIBOLITE, strong, slightly weathered, moderately fractured (8 in - 2 ft), gray, contains quartz augens.

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 2 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-2

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

CL

DR

521.5

519.0

515.5

507.0

17.5

20.0

23.5

32.0

S-01, SPT

2+2+12+45

REC=19", 79%

S-02, SPT

19+17+31+50/3"

REC=16", 76%

S-03, SPT

50/3"

REC=3", 100%

S-04, SPT

22+50

REC=11", 92%

S-05, SPT

50/2"

REC=0", 0%

S-06, SPT

50/3"

REC=3", 100%

RUN 1, CORE

Run = 5.0 ft

REC=60", 100%

RQD=18", 30%

ALLUVIUM

RESIDUUM

No recovery due to sand falling out of sampler.

BLUE RIDGE

BASEMENT

COMPLEX

B

C

D

E

MC = 14.1%

MC = 15.6%

Water

MUDLINE, visually classified as LEAN CLAY with sand; wet, gray, contains mica

SILTY SAND, fine to coarse grained sand; wet, brown, contains mica

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

wet, brown, contains mica

Encountered 3/8 --- 0.0' --- --- Schnabel Representative: C. Irizarry

Total Depth: 55.0 ft

Method: 3-1/4" I.D. Hollow Stem Auger, NQ Double Barrel

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 539± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/8/22 Finished: 3/8/22

Latitude: 38.07086 Longitude: -78.65285

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-3

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

490.3

489.0

484.0

48.7

50.0

55.0

RUN 2, CORE

Run = 5.0 ft

REC=60", 100%

RQD=16", 27%

RUN 3, CORE

Run = 5.0 ft

REC=60", 100%

RQD=35", 58%

RUN 4, CORE

Run = 5.0 ft

REC=60", 100%

RQD=44", 73%

RUN 5, CORE

Run = 3.0 ft

REC=36", 100%

RQD=36", 100%

BLUE RIDGE

BASEMENT

COMPLEX

Water added.

Brown return water.

Gray return water.

Partial loss of return water.

No return water.

E

Bottom of Boring at 55.0 ft.

Boring terminated at selected depth.

Boring backfilled with cement/bentonite grout through tremie pipe upon completion.

AUGEN GNEISS, medium strong, highly weathered to moderately weathered, highly fractured (2.5 - 8 in), gray and grayish brown, strongly foliated, contains quartz and feldspar augens (continued)

Change: moderately fractured (8 in - 2 ft) Change: highly fractured (2.5 - 8 in) Change: intensely fractured (< 2.5 in)

GNEISS, strong, moderately weathered, moderately fractured (8 in - 2 ft), dark gray and light gray, strongly foliated Change: contains quartz vein

MYLONITIC GNEISS, strong, slightly weathered, moderately fractured (8 in - 2 ft), dark gray and light gray, strongly foliated, contains quartz augens

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 2 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-3

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

SC

508.5

506.0

30.5

33.0

ALLUVIUM

RESIDUUM

B

C

Water

MUDLINE, visually classified as LEAN CLAY with sand; wet, gray, contains mica

CLAYEY SAND, fine to coarse grained sand; wet, gray, contains mica

Encountered 3/11 --- 0.0' --- --- Schnabel Representative: C. Irizarry

Total Depth: 68.8 ft

Method: 3-1/4" I.D. Hollow Stem Auger, NQ Double Barrel

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 539± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/11/22 Finished: 3/14/22

Latitude: 38.07095 Longitude: -78.65273

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-4

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

SC

DR

499.0

497.0

495.2

483.7

480.5

474.2

470.2

40.0

42.0

43.8

55.3

58.5

64.8

68.8

S-01, SPT

5+5+7+7

REC=16", 67%

S-02, SPT

2+5+9+13

REC=24", 100%

S-03, SPT

2+5+9+25

REC=24", 100%

S-04, SPT

12+36+50/3"

REC=15", 100%

S-05, SPT

50/3"

REC=3", 100%

RUN 1, CORE

Run = 5.0 ft

REC=60", 100%

RQD=19", 32%

RUN 2, CORE

Run = 5.0 ft

REC=60", 100%

RQD=31", 52%

RUN 3, CORE

Run = 5.0 ft

REC=60", 100%

RQD=36", 60%

RUN 4, CORE

Run = 5.0 ft

REC=60", 100%

RQD=58", 97%

RUN 5, CORE

Run = 5.0 ft

REC=60", 100%

RQD=58", 97%

RESIDUUM

BLUE RIDGE

BASEMENT

COMPLEX

Water added.

Brown return water.

Gray return water.

C

D

E

MC = 22.3%

MC = 15.3%

Bottom of Boring at 68.8 ft.

Boring terminated at selected depth.

Boring backfilled with cement/bentonite grout through tremie pipe upon completion.

CLAYEY SAND, fine to coarse grained sand; wet, gray, contains mica (continued)

SILTY SAND, fine to coarse grained sand; wet, brown, contains mica, and rock fragments

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

wet, brown, contains rock fragments

AUGEN GNEISS, weak, highly weathered, intensely fractured (< 2.5 in), gray and grayish brown, strongly foliated, Contains quartz and feldspar augens.

Change: highly fractured (2.5 - 8 in) to intensely fractured (< 2.5 in) Change: medium strong, highly weathered to moderately weathered, highly fractured (2.5 - 8 in)

Change: intensely fractured (< 2.5 in), Vertical fracture

GNEISS, strong, moderately weathered, highly fractured (2.5 - 8 in), brownish gray, strongly foliated Change: moderately fractured (8 in - 2 ft)

MYLONITE, strong, slightly weathered, moderately fractured (8 in - 2 ft), gray, strongly foliated, Contains quartz and feldspar augens

AUGEN GNEISS, strong, slightly weathered, moderately fractured (8 in - 2 ft), gray, strongly foliated, Contains quartz augens and pyrite

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 2 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-4

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

CL 504.534.5 B

Water

Encountered 3/10 --- 0.0' --- --- Schnabel Representative: C. Irizarry

Total Depth: 73.5 ft

Method: 3-1/4" I.D. Hollow Stem Auger, NQ Double Barrel

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 539± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/10/22 Finished: 3/11/22

Latitude: 38.07099 Longitude: -78.65263

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-5

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

SC-SM

DR

502.0

495.5

493.5

490.5

465.5

37.0

43.5

45.5

48.5

73.5

S-01, SPT

3+4+7+16

REC=23", 96%

S-02, SPT

6+11+16+35

REC=24", 100%

S-03, SPT

2+WOH+1+2

REC=24", 100%

S-04, SPT

16+50/4"

REC=10", 100%

S-05, SPT

50/4"

REC=4", 100%

RUN 1, CORE

Run = 5.0 ft

REC=17", 28%

RQD=0", 0%

RUN 2, CORE

Run = 5.0 ft

REC=60", 100%

RQD=5", 8%

RUN 3, CORE

Run = 5.0 ft

REC=60", 100%

RQD=38", 63%

RUN 4, CORE

Run = 5.0 ft

REC=60", 100%

RQD=52", 87%

RUN 5, CORE

Run = 5.0 ft

REC=60", 100%

RQD=60", 100%

ALLUVIUM

RESIDUUM

BLUE RIDGE

BASEMENT

COMPLEX

Water added.

Brown return water.

Drilling penetration rate slower.

Gray return water.

B

D

E

MC = 12.7%

LL = 26

PL = 20

MC = 22.9%

% Passing #200 = 18.5

MC = 21.7%

Bottom of Boring at 73.5 ft.

Boring terminated at selected depth.

Boring backfilled with cement/bentonite grout through tremie pipe upon completion.

MUDLINE, visually classified as LEAN CLAY with sand; wet, gray, contains mica (continued)

SILTY SAND, fine to coarse grained sand; wet, brown and gray, contains mica, and rock fragments

SILTY, CLAYEY SAND, fine to coarse grained sand; wet, brown and gray, contains mica, and rock fragments

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

wet, brown

AUGEN GNEISS, weak, severely weathered, intensely fractured (< 2.5 in), grayish brown, strongly foliated

Change: highly weathered, gray and brown

Change: medium strong, moderately weathered, highly fractured (2.5 - 8 in), gray, contains pyrite Change: intensely fractured (< 2.5 in) Change: strong, slightly weathered, moderately fractured (8 in - 2 ft)

Change: highly fractured (2.5 - 8 in)

Change: moderately fractured (8 in - 2 ft)

Change: calcite healed fractures

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 2 of 2

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

Boring Number:

DATA

B-5

REMARKS

Project:

STRA

TUM TESTSMATERIAL DESCRIPTION

T E

S T

B O

R

IN

G L

O G

C

LO

G

S _C

I_

.0 8.

.G

P J

S C

H N

A B

E L

D A

T A

T E

M P

LA

T

E

8_

_0

.G

FILL

FILL

ML

SM

DR

559.0

557.0

555.0 554.7 554.0

549.5

546.5

536.5

2.0

4.0

6.0 6.3 7.0

11.5

14.5

24.5

S-01, SPT

2+1+2+1

REC=8", 33%

S-02, SPT

13+7+5+3

REC=7", 29%

S-03, SPT

2+3+3+4

REC=10", 42%

S-04, SPT

2+3+8+9

REC=18", 75%

S-05, SPT

3+4+7+27

REC=18", 75%

S-06, SPT

50/3"

REC=1", 33%

RUN 1, CORE

Run = 5.0 ft

REC=48", 80%

RQD=22", 37%

RUN 2, CORE

Run = 5.0 ft

REC=60", 100%

RQD=18", 30%

FILL

6 ft of fill placed for boring access.

RESIDUUM

Augers grinding/scraping.

BLUE RIDGE

BASEMENT

COMPLEX

Water added.

Gray return water.

No return water.

Regained return water.

A

C

D

E

MC = 14.7%

LL = 30

PL = 22

MC = 18.4%

% Passing #200 = 57.0 PP = 2.75 tsf

Bottom of Boring at 24.5 ft.

Boring terminated at selected depth.

Boring backfilled with cuttings and borehole plug upon completion.

Groundwater observations affected by core water.

FILL, sampled as silty sand, fine to coarse grained sand; moist, dark brown, contains rock fragments

FILL, sampled as silty sand with gravel, fine to coarse grained sand;

moist, gray

FILL, sampled as sandy lean clay;

moist, dark brown

Topsoil; 4 inches

SANDY SILT; moist, brown

SILTY SAND WITH GRAVEL, fine to coarse grained sand; moist, dark brown, contains mica

DISINTEGRATED ROCK, sampled as silty sand, fine to coarse grained sand;

moist, brown

MYLONITE, medium strong, highly weathered, highly fractured (2.5 - 8 in), brownish gray, strongly foliated, Contains feldspar and quartz augens

Encountered

Completion

Casing Pulled

3/16

3/16

3/16

Dry

13.5'

9.0'

10.5'

Schnabel Representative: C. Irizarry

Total Depth: 24.5 ft

Method: 3-1/4" I.D. Hollow Stem Auger, NQ Double Barrel

Equipment: Diedrich D-50 (ATV)

Ground Surface Elevation: 561± (ft)

Contractor: Shenandoah Drilling Services, LLC Winchester, Virginia

Contractor Foreman: H. Roberts

Hammer Type: Auto Hammer (140 lb)

Dates Started: 3/16/22 Finished: 3/16/22

Latitude: 38.07010 Longitude: -78.65252

Date CavedDepthTime Casing Groundwater Observations

RWSA Intake and Pump Station Beaver Creek Reservoir Albemarle County, Virginia

SYMBOL

Contract Number: 21C43036 Sheet: 1 of 1

SAMPLING

DEPTH

DEPTH

(ft)

ELEV

(ft)

TEST

BORING

LOG

This is the start of the file's text. The full file is on GovTribe.