This document is an Addendum (#3) for Invitation for Bid (IFB) 24/25-23 issued by the City of Sanford's Finance Department and Purchasing Division for the Groveview Pump Station #3 Improvements project. The addendum, dated June 4, 2025, provides clarifications and answers to bidder questions while maintaining the original solicitation response due date of Thursday, June 12, 2025, at 2:00 P.M. Local Time. The key technical clarification involves the Remote Terminal Unit (RTU) and communication system, with the city indicating that contractors need to supply an RTU and Antenna System compatible with their existing infrastructure, specifically noting Revere Control (who purchased Curry Controls) and Rocha Controls as potential RTU suppliers.
The addendum addresses several specific bidder inquiries, including confirming that the city will not provide line items for a complete bid schedule of values and declining use of an adjacent power line easement as a lay down area. The document includes electrical site plans, grounding and bonding diagrams, and detailed electrical one-line diagrams that provide technical specifications for the pump station improvements. The electrical plans specify requirements for equipment such as service disconnects, surge protective devices, generator inlet receptacles, and communication infrastructure, with explicit details about mounting, grounding, and compatibility with the city's existing systems.
View the file
Other files for this state and local contract opportunity
Show all 50
Groveview Pump Station Improvements has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
City of Sanford | Finance Department | Purchasing Division 300 N. Park Avenue Suite 236, Sanford, Florida 32771
Phone: 407-688-5028 or 5030 | Fax: 407-688-5021 | Email: purchasing@sanfordfl.gov ADDENDUM
#3 IFB 24/25-23 GROVEVIEW PUMP STATION
IMPROVEMENTS|
DATE: June 4, 2025
TO: All Bidders/Proposers
FROM: Maria A. Green, Purchasing Coordinator City of Sanford Purchasing Division
SUBJECT: IFB 24/25-23 GROVEVIEW PUMP STATION IMPROVEMENTS|
ADDENDUM #3
This addendum is issued to provide additional information, clarification, corrections, additions, deletions and/or answers to questions concerning the above referenced solicitation. All information provided in this addendum is incorporated into the solicitation document as set forth therein. All other parts of the solicitation have been maintained as originally distributed. This addendum supersedes any verbal and/or other instructions given to any bidder/proposer qualified to respond pursuant to the requirements set forth in the solicitation document.
I. DUE DATE
This Addendum does not change the solicitation due date. As such, the solicitation response is due no later than Thursday, June 12, 2025, at 2:00 P.M. Local Time.
II. QUESTIONS AND ANSWERS (Q&A)
The City has received the following question(s) concerning the solicitation:
1.) Please clarify who the required RTU supplier is and whether it should be a cellular system which would negate the antenna and antenna tower.
Answer: The City has not started the conversion to a cellular communication system yet.
Therefore, the contractor needs to supply a RTU and Antenna System that is standardized and compatible with our existing system. Revere Control, who purchased Curry Controls is the main RTU supplier. However, Rocha Controls has done work for the City and is currently the RTU supplier for another lift station project, so they may be able to supply it also.
2.) Do we need to register with PCCLB prior to bid? See on website it states "Effective June 24, 2024, state certified contractors DO NOT have to register or renew their registrations with PCCLB to work in Pinellas County."
Answer: I do not know who put this in there, but as the PCCLB is the Pinellas County Construction Licensing Borad, I do not see how it is relevant to us.
3.) Will the City be providing line items for a complete bid schedule of values?
Provided with previous addendum answers
Answser: No.
4.) Are we able to use the adjacent power line easement as a lay down area?
Answer: No, it is not the City’s easement.
mailto:purchasing@sanfordfl.gov
City of Sanford | Finance Department | Purchasing Division 300 N. Park Avenue Suite 236, Sanford, Florida 32771
Phone: 407-688-5028 or 5030 | Fax: 407-688-5021 | Email: purchasing@sanfordfl.gov ADDENDUM
#3 IFB 24/25-23 GROVEVIEW PUMP STATION
IMPROVEMENTS|
III. CHANGES, ADDITIONS AND/OR CLARIFICATIONS
Electrical Plan Revision
IV. SIGN-IN SHEET
N/A
V. ATTACHMENTS
Electrical Plan Revision
Respondents must acknowledge receipt of this Addendum by signing this form below and returning it to the Procurement Division prior to the hour and date specified for receipt of bids/proposals or by including this Addendum with your submittal. Failure to comply may result in disqualification of your response.
Acknowledgment is hereby made of Addendum #3 to IFB 24/25-23 Groveview Pump Station Improvements|
Name of Firm/Company Contact Email
Street Address City, State, Zip Code
Telephone Number Fax Number
Authorized Person Printed Name Authorized Person Title
Authorized Person Signature Date of Signature mailto:purchasing@sanfordfl.gov
M
30'10'
MH: 20
Graphic Scale in Feet
10 10 20
N
E-1ELECTRICAL SITE PLAN
CIRCUIT BELOW GRADE
PB
LEGEND
CIRCUIT ABOVE GRADE
KEY NOTES
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 07-2024
A. ZVONARYOV
G. TAYLOR
J. VITAL
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
GREGORY D. TAYLOR, P.E.
FL P.E. No. 77811
B
ID
D O
C U
M E
N T
S
EXISTING LIFT STATION
T.E = 47.71
NW INV.=40.24 (10" CLAY)
NE INV. = 34.71 (10" CLAY)
BOT. = 33.79
CONDUIT UP FROM BELOW GRADE
NEW PUMP STATION
SITE BENCHMARK #535+
TOP OF MAG NAIL AND DISK
WITH "BM" LB #7143
EL. 47.72 NAVD88
N.1608609.12 E.557974.72
EXISTING PAD-MOUNT
TRANSFORMER
PB4 #3/0, 3"C
13"X24", 18" DEEP PULL BOX WITH
TIER 15 COVER, LOGO "ELECTRIC",
QUAZITE PG1324BA18 BOX W/
PG1324HA0017 COVER OR EQUAL
CONTROL PANEL
ABBREVIATIONS
AMP
CP
A
DISCONNECT SWITCH
DOUBLE-POLE DOUBLE-THROW
D/S
DPDT
GROUND FAULT CIRCUIT INTERRUPTERGFI
RECEPTACLE
POLE
RCPTL
P
REMOTE TERMINAL UNITRTU
SURGE PROTECTIVE DEVICE
SUPERVISORY CONTROL AND DATA ACQUISITION
SPD
SCADA
STAINLESS STEELSS
WEATHERPROOF
VOLT
WP
V
SHEET INDEX
E-1 ELECTRICAL SITE PLAN
E-2A ELECTRICAL DIAGRAMS 1 OF 2
E-2B ELECTRICAL DIAGRAMS 2 OF 2
E-3 CALCULATIONS AND DETAILS
1. OBTAIN AVAILABLE FAULT CURRENT FROM FPL.
2. PROVIDE 3"C STUB-OUT FOR CONNECTION TO TRANSFORMER BY
UTILITY. COORDINATE WITH FPL FOR SERVICE LATERAL
REQUIREMENTS.
3. REMOVE ELECTRIC METER. COORDINATE WITH FPL FOR REUSE
OF METER.
4. REMOVE ANTENNA AND TOWER. COORDINATE WITH OWNER ON
REUSE.
5. 13"X24", 18" DEEP PULL BOX WITH TIER 15 COVER, LOGO
"ELECTRIC", QUAZITE PG1324VA18 BOX W/ PG1324HA0017 COVER
OR EQUAL.
COPPER
ALUMINUM
CU
AL
POLE-MOUNTED LIGHT FIXTURE
UNLESS OTHERWISE NOTEDUON
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.7'
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.6'
AutoCAD SHX Text
LOT 19
AutoCAD SHX Text
LOT 18
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text 05/27/25
AutoCAD SHX Text
REVISED SITE LAYOUT
AutoCAD SHX Text
JAV
AutoCAD SHX Text CPH, LLC A Full Service A & E Firm
AutoCAD SHX Text
AutoCAD SHX Text
PROPOSED SANITARY
MANHOLE
8' DIA. WET WELL
BYPASS PUMP
CHAIN LINK FENCE
ALUMINUM ACCESS HATCH WITH
LOCKSET AND RELEASE HANDLE
PUMP # 1PUMP # 2
60" X 48" ALUMINUM ACCESS HATCH
(HALLIDAY PRODUCT H2R4860 OR EQUAL)
6" 45° BEND (MJ)
WATER SERVICE
METER SUPPLIED
BY CITY
HOSE BIB W/ RPZ
AND METER
2 -6' SWING GATE
2" ARV
6" CHECK VALVE
SPD &
RCPTL
D/S
METER
CPANTENNA
TOWER
CADWELD #4 STRANDED
TINNED COPPER TO GEC
CADWELD #4 STRANDED TINNED
COPPER TO EQUIPMENT RACK
CADWELD #4 STRANDED TINNED
COPPER TO 20' X 3/4"
COPPER-CLAD GROUND ROD
(TYP, EACH CORNER)
COUNTERPOISE (GROUND
RING) - #2/0 STRANDED
TINNED COPPER MIN 30"
BELOW GRADE
CADWELD #4 STRANDED TINNED
COPPER TO ACCESS COVER AND
FRAME
CADWELD #4 STRANDED TINNED
COPPER TO ACCESS COVER AND
FRAME
CADWELD #4 STRANDED
TINNED COPPER TO FLANGE
CADWELD #4
STRANDED TINNED
COPPER TO FRAME
CADWELD #4
STRANDED TINNED
COPPER FROM FENCE
TO SWING GATE (TYP,
BOTH SWING GATES)
CADWELD #4 STRANDED
TINNED COPPER TO FENCE -
MINIMUM 2 LOCATIONS
GROUND TEST WELL
GROUNDING AND BONDING DIAGRAM
6" PVC FM
M
RTU
4" MAG
METER
2" ARV
TIMER
SWITCH
MH: 20ENCLOSED
BREAKER
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 07-2024
A. ZVONARYOV
G. TAYLOR
J. VITAL
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
GREGORY D. TAYLOR, P.E.
FL P.E. No. 77811
B
ID
D O
C U
M E
N T
S
E-2AELECTRICAL DIAGRAMS
Graphic Scale in Feet
2 2 4
N
AutoCAD SHX Text S
AutoCAD SHX Text CPH, LLC A Full Service A & E Firm
AutoCAD SHX Text 05/27/25
AutoCAD SHX Text
REVISED SITE LAYOUT
JAV
SERVICE
DISCONNECT
FPL
METERRTU CONTROL
PANEL
PUMP #1
PUMP #2
CONTROL
TO
WET
WELL
2" C WITH PULL
STRING TO
ANTENNACONCRETE BASE
3/4" x 20'
COPPER-CLAD
GROUND ROD
10'
MIN.
ANTENNA TOWER
2'-4" 2'-4"
WP/GFCI SERVICE
RECEPTACLE
1'-0"
ALARM BELL/HORN
PIPE MOUNTED
ALARM LIGHT
BEHIND PANEL
2'
MAX.
ANTENNA
4'-0"
MIN.
EQUIPMENT
RACK
(NOTE 1)
18.5' MIN
2'-4"
FROM UTILITY
TRANSFORMER
SPD
STRUT CHANNEL
1-1/2" MIN. (TYP)
GENERATOR
INLET RECEPTACLE
ALUMINUM CONDUIT
SEAL (TYP, 3 PL.)
MAG
METER
XMTR
6" x 6" x 12'
CONCRETE POST
(TYP. 4 PL.)
TO MAG METER
- SEE E-2A
TIMER
SWITCH
3/4"C. WITH PULL
STRING TO LIGHT
POLE
ENCL.
CKT.
BKR
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 07-2024
A. ZVONARYOV
G. TAYLOR
J. VITAL
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
GREGORY D. TAYLOR, P.E.
FL P.E. No. 77811
B
ID
D O
C U
M E
N T
S
E-2BELECTRICAL DIAGRAMS
RISER DIAGRAM
ELECTRICAL ONE-LINE DIAGRAM
GENERAL NOTES:
1. THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED WIND LOAD CALCULATIONS FROM A STATE OF FLORIDA LICENSED
PROFESSIONAL ENGINEER FOR THE EQUIPMENT RACK, FOUNDATIONS, TOWER, ANTENNA AND ACCESSORIES. THE CALCULATIONS SHALL DOCUMENT THE POSTS, BRACKETS, MOUNTING HARDWARE, CONCRETE BASES AND FOUNDATIONS INCLUDING EMBEDMENT DEPTH, REINFORCEMENT, AND REQUIRED DIMENSIONS. THE CALCULATIONS SHALL USE THE
REQUIRED WIND SPEED OF 139 MPH (RISK CATEGORY II).
2. ALL MOUNTING HARDWARE SHALL BE STAINLESS STEEL UNLESS OTHERWISE NOTED.
3. EQUIPMENT RACK MOUNTING BRACKETS SHALL LINE UP WITH ALL EQUIPMENT ENCLOSURE'S FACTORY SET MOUNTING
HOLES. NO DRILLING OF PANELS IS ALLOWED.
4. EQUIPMENT RACK POSTS SHALL BE EITHER STAINLESS STEEL OR CONCRETE.
5. ALL CONDUIT SHALL BE ALUMINUM RIGID METAL CONDUIT (AL RMC) ABOVE GRADE TO 6" BELOW GRADE OR THROUGH SLAB, WHICHEVER IS GREATER, WHERE IT SHALL TRANSITION TO PVC UNLESS OTHERWISE NOTED. ALUMINUM CONDUIT IN CONTACT W/ EARTH OR CONCRETE SHALL HAVE SUPPLEMENTARY CORROSION PROTECTION PER NEC 300.6.
6. PROVIDE PULL WIRE IN EMPTY CONDUITS.
2"C TO WET WELL. CABLES FURNISHED WITH PUMPS AND FLOAT SWITCHES.
INSTALLED AND WIRED UNDER THIS CONTRACT.
METER
SPD
PUMP CONTROL PANEL
4 #3/0, 3"C
FROM UTILITY
TRANSFORMER
200A/3P/200AF SERVICE
ENTRANCE RATED
#6 BARE CU
4-#3/0, 3"C
4-#3/0, 1-#6 GROUND, 3"C
KEY NOTES:
1. SERVICE DISCONNECT: 200A, 240V, 3P SINGLE-THROW, 4W, FUSED, NEMA 4X, 316 SS (EATON DH324NWK316 OR EQUAL)
NOTE: BASIS OF DESIGN IS TO PROVIDE CONTROL PANEL WITH INTEGRAL POWER SOURCE TRANSFER MECHANISM;
OTHERWISE PROVIDE DPDT INSTEAD OF SPST SERVICE DISCONNECT (EATON DT324NWK316 OR EQUAL) AND INSTALL GENERATOR INLET RECEPTACLE ON DISCONNECT SWITCH OR ON RACK-MOUNTED BACK BOX INSTEAD OF ON CONTROL
PANEL.
2. SURGE PROTECTIVE DEVICE: TYPE 1, 240/120V, 3-PHASE, 4-WIRE + GROUND, 240KA PEAK SURGE CURRENT/PHASE, NEMA
4X SS (SQUARE D SSP03EMA24S1 OR EQUAL)
3. GEN INLET RCPTL: 200A, 600VAC/250VDC, 3P, 4W PIN & SLEEVE RECEPTACLE (HUBBELL HBL4200RS2W OR EQUAL)
4. GEC IN 3/4 IN AL RMC - BOND AT EACH END. CONNECT GEC, EQUIPMENT RACK, AND ANTENNA TOWER STRUCTURAL STEEL
TO GROUND RING.
5. CONTROL PANEL: PROVIDE CITY STANDARD CONTROL PANEL WITH POWER AND CONTROLS AS REQUIRED FOR BYPASS
PUMP.
6 RTU: PROVIDE CITY STANDARD RTU WITH ADDITIONAL SCADA CAPABILITIES TO MONITOR AND CONTROL BYPASS PUMP.
7. RTU ANTENNA: HEAVY DUTY, ALL-WELDED, DIRECTIONAL YAGI ANTENNA AS MANUFACTURED BY LAIRD,KATHREIN USA, OR L-COM, IMPEDANCE 50 OHMS, N FEMAILE CONNECTOR, AND SHALL MEET THE CITY'S REQUIRED FREQUENCY RANGE. THE BOOM AND ELEMENTS SHALL BE ANODIZED ALUMINUM AND THE HARDWARE AND FASTENINGS SHALL BE STAINLESS STEEL.
THE INTERNAL ELEMENTS SHALL BE SEALED IN A FOAM POTTING SYSTEM TO PREVENT MOISTURE PENETRATION. THE
ANTENNA SHALL BE ABLE TO WITHSTAND A WIND SPEED OF 139 MPH.
8. ANTENNA TOWER: ROHN 25G STEEL TOWER OR 6 INCH SQUARE TAPERED PRECAST CONCRETE POST.
9. PROVIDE METER SOCKET AND NEW METER OR CONSULT FPL ABOUT REUSE OF EXISTING METER REMOVED FROM PUMP
HOUSE.
10. SENSOR CABLE (PROVIDED WITH MAG METER) IN 1"C.
11. REMOTE TRANSMITTER, 17W @120V POWER FROM CONTROL PANEL , 4-20mA OUTPUT, NEMA 4X IP67 (SIEMENS MAG 5000W)INCLUDED WITH MAG METER. INSTALL ON RACK MOUNTING BRACKET (SIEMENS FDK085U1053) WITH SUNSHIELD (SIEMENS A5E01209496). PROVIDE #22 STP IN 1/2" CONDUIT FOR 4-20mA SIGNAL FROM TRANSMITTER TO CONTROL PANEL.
12. ELECTROMAGNETIC FLOW SENSOR ("MAG METER"), 70-2800.9 GPM (SIEMENS 7ME6520-4HJ13-2ZA2-Z+K52+N03 - MAG 5100W) WITH GROUNDING RINGS (SIEMENS A5E01002955) AND TERMINAL BOX POTTING (SIEMENS FDK:085U0220).
13. TWO 1/2"C - 120V AND 4-20mA IN SEPARATE CONDUITS.
14. PROVIDE SPRING WOUND COUNTDOWN TIMER 12 HOUR MAX WITHOUT HOLD (INTERMATIC FF412H). MOUNT TIMER WITHIN A WEATHER PROOF BOX WITH IN USE COVER. PROVIDE 2#10,1#10 CU. GND. IN 3/4" SCH. 80 PVC CONDUIT TO LIGHT POLE.
15. ENCLOSED CIRCUIT BREAKER, 20A/1P/250V NEMA 3R ENCL. VERIFY LOAD -SIDE LUG OF CIRCUIT BREAKER ACCEPTS 2#10 OR
SPLICE WIRE TO FEED TIMECLOCK AND RECEPTACLE.
TO
WET WELL
TO
WET WELL
RTU
DIESEL
PUMP
1"C 1"C FOR
12VDC WIRING
1"C FOR ENGINE
ALARM WIRING
1"C FOR PRESTART
ALARM WIRING
1"C FOR
FLOAT CABLES
MAG
METER
WP
GFI
AREA LIGHT
2-#10, #10G, 1/2"C
10' MAX
AutoCAD SHX Text CPH, LLC A Full Service A & E Firm
AutoCAD SHX Text 05/27/25
AutoCAD SHX Text
REVISED SITE LAYOUT
AutoCAD SHX Text
JAV
AutoCAD SHX Text
AutoCAD SHX Text
NOTES:
1. INSTALL SCH. 80 PVC CONDUIT EXTENDING FROM HATCH TO GROUND RING.
INSTALL GAS TIGHT SEAL AT WET WALL.
2. INSTALL GROUND WIRE IN WET WELL AT THE EDGE NEAR THE FRAME AWAY FROM
THE HATCH OPENING SO IT DOES NOT INTERFERE WITH PUMP REMOVAL AND
MAINTENANCE ACTIVITIES.
2"
#4 AWG TINNED
COPPER GROUNDING
CONDUCTOR,
GROUND
TEST WELL
LIFTING HOLE
MECHANICAL CONNECTION
FINISHED
GRADE
STAINLESS STEEL
GROUND CLAMP,
BOLT TO FRAME
METAL ACCESS COVER
1/8" THICK X 1" WIDE
MULTI-STRAND TINNED
COPPER BRAID
(LENGTH AS REQUIRED)
STAINLESS STEEL GROUND CLAMP,
BOLT TO COVER
#2/0 AWG, 34 " PVC
TO GROUND RING
10" X 17" PULL BOX,
H20 LOAD RATED,
CHRISTY B1017 OR
EQUAL
GROUND TEST WELL
WET WELL HATCH GROUNDING
#2/0 AWG BOND
TO GROUND RING
DRILL & TAP
BOLT TO
COVER
SLEEVES SIZED FOR
4 " CONDUIT
REINFORCED
CONCRETE W/
STEEL FRAME
(LOOP 36" EXTRA IN
BOX)
12" THICK CRUSHED
STONE (EXTEND 6" MIN
BELOW BOTTOM OF BOX)
GROUND ROD
4" X 20'
BOLT DOWN STEEL COVER
(LOCKABLE w/ GASKET)
LETTERS ON LID
E-3
E-3
CONCRETE-POLYMER
PULLBOX AND COVER
FINISHED
GRADE
12" THICK CRUSHED
STONE (EXTEND 6" MIN
BELOW BOTTOM OF BOX)
CONCRETE
APRON
6"
1'
GROUND ROD
3/4" X 20'
APPROVED GROUND
CONNECTION
PULLBOX DETAIIL1
E-3
FIXTURE:
RSX2-P4-30K-R4-MVOLT-IS-EGS-DBLXD
EPA LOAD=0.69
20' CONCRETE POLE DETAIL4
E-3
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com
THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 07-2024
A. ZVONARYOV
G. TAYLOR
J. VITAL
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
GREGORY D. TAYLOR, P.E.
FL P.E. No. 77811
B
ID
D O
C U
M E
N T
S
E-3CALCULATIONS AND DETAILS
AutoCAD SHX Text
HANDHOLE
AutoCAD SHX Text
CONDUIT ACCESS
AutoCAD SHX Text
COPPER GROUND TO 10FT GROUND ROD.
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text 20'-0"
AutoCAD SHX Text 24"
AutoCAD SHX Text NOTE: POLE IS TO MEET LOCAL WIND LOADS. INSTALLATION MAY REQUIRE STRUCTURAL ENGINEER APPROVAL.
AutoCAD SHX Text
ROUND CONCRETE POLE SEMINOLE POLE INC. SP2720TII EPA CAPACITY @ 140 MPH = 8
AutoCAD SHX Text
3/4" SCH.80 CONDUIT
AutoCAD SHX Text CPH, LLC A Full Service A & E Firm
AutoCAD SHX Text
AutoCAD SHX Text 05/27/25
AutoCAD SHX Text
REVISED SITE LAYOUT
JAV
| IFB 24-25-23 Groveview Pump Station Improvements - Addendum 3- Electrical Plan Revision.pdf |
| Sheets and Views |
| E-1 - Electrical Site Plan-E-1 |
| E-2A - Electrical Diagrams 1 of 2-E-2A |
| E-2B - Electrical Diagrams 2 of 2-E-2B |
| E-3 - Electrical Calculations and Details-E-3 |
File details come from the government source that posted it. Updated .