IFB_24-25-23_Groveview_Pump_Station_Improvements_-_Plans.pdf
PDF 8 MB Posted
- Attached to
- Groveview Pump Station Improvements State and local contract opportunity
- Solicitation number
- IFB 24/25-23
- Issued by
- Seminole County, Florida
About this file
These bid documents are for the Groveview Pump Station Improvements project (IFB 24/25-23) by the City of Sanford, Florida, prepared by CPH, LLC. The project involves completely demolishing an existing above-ground lift station and constructing a new submersible pump station, including a new 8-foot diameter wet well, junction manhole, force and gravity mains, electrical controls, and an emergency diesel by-pass pump. The comprehensive plan includes installing approximately 39 linear feet of 12-inch PVC sanitary sewer, 20 linear feet of 6-inch PVC forcemain, and constructing a new concrete driveway and site infrastructure. The project will utilize fiber mesh-reinforced concrete, include extensive electrical and grounding systems, and requires careful utility coordination and environmental compliance.
The bid documents indicate a complex municipal infrastructure project with detailed technical specifications for utility construction, electrical systems, and site preparation. The project emphasizes precise engineering requirements, including specific material specifications, utility separation standards, and comprehensive grounding and bonding protocols. While no specific budget is mentioned, the extensive technical details suggest a significant capital investment. The project will require advanced coordination with Florida Power and Light, adherence to Florida Department of Environmental Protection regulations, and integration of sophisticated SCADA-capable electrical systems. Bidders must demonstrate professional engineering expertise, licensing, and the ability to execute a technically demanding municipal infrastructure upgrade within an approximately 270-calendar-day contract period.
View the file
Other files for this state and local contract opportunity
Show all 50
Groveview Pump Station Improvements has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J:
\S
2.
\C iv il\ D
W G
C ur re nt _P la n_
Se t\W or ki ng \1
C ov er
.d w g A pr
7,
- 3 :4
5p m z aa da d
Know what's below.
before you dig.Call
R
C I T Y O F S A N F O R D
INDEX OF SHEETS
GROVEVIEW PUMP
STATION IMPROVEMENTS
DEMOLITION PLAN
GENERAL NOTES
5.
7.
COVER SHEET1.
3.
2.
4.
6.
SITE PLAN
LIFT STATION PLAN VIEW
N
Graphic Scale in Feet
200 200 400VICINITY MAP
1" = 200'
CITY OFFICIALS
MAYOR
ART WOODRUFF
COMMISSIONERS
DISTRICT 1: SHEENA BRITTON
DISTRICT 2: KERRY S. WIGGINS, SR.
DISTRICT 3: PATRICK AUSTIN
DISTRICT 4: PATTY MAHANY
UTILITY PLANTS MANAGER
RICHARD CASELLA, UMC
BRYNT JOHNSON
PUBLIC WORKS/
UTILITIES DIRECTOR
NEW LIFT STATION SITE LOCATION
BY-PASS PUMP DETAILS AND NOTES
LIFT STATION SECTION
E-1. ELECTRICAL SITE PLAN
E-2A, E-2B ELECTRICAL DIAGRAMS
E-3. CALCULATIONS AND DETAILS
c 2024 FL P.E. No. 64727
ROCCO R. NASSO II, P.E.
*NOTICE*
THIS SET OF PLANS IS NOT VALID FOR CONSTRUCTION PURPOSES WITHOUT BEING STAMPED
"APPROVED FOR CONSTRUCTION BY CPH INC." PLANS WITHOUT THIS STAMP ARE GIVEN FOR
INFORMATIONAL PURPOSES ONLY.
JOB# S06222
DATE: AUGUST 2024
CITY MANAGER
NORTON N BONAPARTE JR
IFB 24/25-23
DETAILS
www.cphcorp.com A Full Service
A & E Firm
Plans Prepared by:
CPH, LLC
500 West Fulton Street
Sanford, FL 32771 Ph: 407.322.6841
BID DOCUMENTS
2GENERAL NOTES
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
GENERAL PROVISIONS
1. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL MAKE A PRE-CONSTRUCTION VIDEO
(.MP4, .MPG, .WMV, .MOV OR APPROVED EQUAL) AT THE EXISTING LIFT STATION AND THE
NEW LIFT STATION SITE IN ACCORDANCE WITH THE SPECIFICATIONS. THE FILES SHALL BE
SAVED IN DIGITAL FORMAT ON A PORTABLE USB HARD/FLASH DRIVE OR APPROVED EQUAL,
AND SHALL BE ABLE TO BE PLAYED BACK ON ANY WINDOWS COMPATIBLE COMPUTER. IN
PARTICULAR, THE VIDEO SHALL DOCUMENT THE CONDITION OF EXISTING BUILDINGS,
STRUCTURES, SIGNS, FENCES, AND LANDSCAPING ALONG PROPOSED CONSTRUCTION
AREAS.
2. THE CONTRACTOR SHALL RECOGNIZE AND ABIDE BY ALL OSHA EXCAVATION SAFETY
STANDARDS, INCLUDING THE FLORIDA TRENCH SAFETY ACT (FS 553.60-553.64). ANY
MATERIAL, CONSTRUCTION METHODS, OR MATERIAL COST TO COMPLY WITH THESE LAWS
SHALL BE INCIDENTAL TO THE CONTRACT.
3. THE CONTRACTOR SHALL OBTAIN FROM THE OWNER COPIES OF ALL AVAILABLE
REGULATORY AGENCY PERMITS AND LOCAL AGENCY PERMITS.
4. THE SIZE OF THIS PROJECT IS LESS THAN 1.0 ACRE; THEREFORE, THE CONSTRUCTION IS
NOT REQUIRED TO COMPLY WITH THE REQUIREMENTS OF THE NATIONAL POLLUTANT
DISCHARGE ELIMINATION SYSTEM (NPDES) GENERAL PERMIT FOR STORMWATER
DISCHARGE FROM SMALL AND LARGE CONSTRUCTION ACTIVITIES. HOWEVER, THE
CONTRACTOR IS STILL RESPONSIBLE FOR IMPLEMENTING AND MAINTAINING EROSION AND
SEDIMENT CONTROL MEASURES PRIOR TO AND DURING CONSTRUCTION IN ACCORDANCE
WITH THE DRAWINGS AND SPECIFICATIONS.
5. THE EROSION AND SEDIMENT CONTROL MEASURES SHOWN ON THE PLANS REPRESENT A
MINIMUM REQUIREMENT. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING
ADDITIONAL EROSION AND SEDIMENT CONTROL MEASURES NEEDED IN ORDER TO PREVENT
THE TRANSFER OF SEDIMENT FROM THE PROJECT AREA AND PREVENT THE EROSION OF
SURFACES DURING CONSTRUCTION, AS NEEDED TO PROTECT ADJACENT PROPERTIES AND
WATER BODIES.
6. IN THE EVENT THAT WATER IS ENCOUNTERED DURING CONSTRUCTION, DEWATERING
SHALL BE CONDUCTED. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN,
INSTALLATION, OPERATION, AND SUBSEQUENT REMOVAL OF DEWATERING SYSTEMS AND
THEIR SAFETY AND CONFORMITY WITH LOCAL CODES AND REGULATIONS. IF DEWATERING
EQUIPMENT NEEDED EXCEEDS ANY OF THE FOLLOWING: 1) 6" PUMP VOLUTE; 2) 100,000 GPD
TOTAL 24 HOUR (1 DAY) DEWATERING, AND; 3) 1,000,000 GPD PUMP CAPACITY, THE
CONTRACTOR SHALL BE REQUIRED TO PERMIT THE DEWATERING SYSTEM WITH THE ST.
JOHNS RIVER WATER MANAGEMENT DISTRICT (SJRWMD). THE ENGINEER AND/OR OWNER
SHALL BE NOTIFIED IMMEDIATELY IF ANY OF THE ABOVE THRESHOLDS ARE EXCEEDED.
7. DEWATERING DISCHARGE FROM THE SITE SHALL COMPLY WITH ALL NPDES GENERAL
PERMIT REQUIREMENTS AND STATE WATER QUALITY STANDARDS. PROVIDE ALL TESTING
AND PERMITTING REQUIRED AND COMPLY WITH ALL TREATMENT OR DISPOSAL METHODS
REQUIRED TO MEET ALL LOCAL, STATE AND FEDERAL REQUIREMENTS.
8. UNLESS OTHERWISE DIRECTED BY THE OWNER OR ENGINEER, THE CONTRACTOR IS
EXPECTED TO CONTAIN ALL CONSTRUCTION ACTIVITIES WITHIN THE PROPERTY BOUNDARY,
RIGHT-OF-WAY AND EASEMENTS, AND OTHER AREAS SPECIFICALLY DESIGNATED FOR
CONSTRUCTION. AT NO TIME SHALL THE CONTRACTOR DISTURB SURROUNDING
PROPERTIES OR TRAVEL ON SURROUNDING PROPERTIES WITHOUT WRITTEN CONSENT
FROM THE PROPERTY OWNER. ANY REPAIR OR RECONSTRUCTION OF DAMAGED AREAS IN
SURROUNDING PROPERTIES SHALL BE REPAIRED BY THE CONTRACTOR ON AN IMMEDIATE
BASIS. ALL COSTS FOR REPAIRS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND
NO EXTRA COMPENSATION SHALL BE PROVIDED.
9. UNLESS OTHERWISE NOTED ON THE PLANS, THE CONTRACTOR SHALL USE THE
GEOMETRY PROVIDED ON THE CONSTRUCTION PLANS. BENCHMARK INFORMATION SHALL
BE PROVIDED TO THE CONTRACTOR BY THE OWNER OR OWNER'S SURVEYOR. ANY
DISCREPANCIES BETWEEN FIELD MEASUREMENTS AND CONSTRUCTION PLAN INFORMATION
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IMMEDIATELY.
10. BASE SURVEY INFORMATION INCLUDING BUT NOT LIMITED TO ELEVATIONS, EASEMENTS,
RIGHTS OF WAY, AND OTHER TOPOGRAPHIC INFORMATION HAS BEEN PREPARED BY OTHER
PROFESSIONALS. CPH, LLC ASSUMES NO RESPONSIBILITY FOR THE ACCURACY OF THIS
INFORMATION.
11. THIS SET OF PLANS MAY CONTAIN DRAWINGS PREPARED BY OTHER PROFESSIONALS,
WHICH CONTAIN THE NAME, ADDRESS, AND LOGO OF THE PROFESSIONAL. CPH, LLC IS NOT
RESPONSIBLE FOR DRAWINGS PREPARED BY OTHER PROFESSIONALS.
12. THE ENTIRE PROJECT SITE SHALL BE THOROUGHLY CLEANED AT THE COMPLETION OF
THE WORK. CLEAN ALL INSTALLED PIPELINES, STRUCTURES, SIDEWALKS, PAVED AREAS,
ACCUMULATED SILT IN PONDS, PLUS ALL ADJACENT AREAS AFFECTED BY CONSTRUCTION,
AS DIRECTED BY THE OWNER OR JURISDICTIONAL AGENCY. EQUIPMENT TO CLEAN THESE
SURFACES SHALL BE SUBJECT TO APPROVAL BY THE OWNER.
EXISTING UTILITIES
1. THE UTILITY DATA SHOWN ON THESE PLANS WAS LOCATED BY THE RESPECTIVE UTILITY,
OR IS BASED ON UTILITY DRAWINGS, MAPS, OR FIELD RECONNAISSANCE.
2. THE LOCATION, MATERIAL TYPE, AND SIZE OF ALL EXISTING UTILITIES SHOWN ON THE
PLANS HAVE BEEN DETERMINED FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN
FOR THE CONVENIENCE OF THE CONTRACTOR. THE OWNER ASSUMES NO RESPONSIBILITY
FOR THEIR ACCURACY. PRIOR TO THE START OF ANY CONSTRUCTION ACTIVITY, THE
CONTRACTOR SHALL CONDUCT ALL INVESTIGATIONS NEEDED TO DETERMINE THE
HORIZONTAL AND VERTICAL ELEVATIONS OF EXISTING UTILITIES THAT WILL BE CONNECTED
TO, CROSSED, OR OTHERWISE BE LOCATED IN THE VICINITY OF THE PROPOSED
CONSTRUCTION. AT PROPOSED CONNECTIONS, INVESTIGATIONS SHALL EXTEND BEYOND
THE POINT OF CONNECTION AS NEEDED TO ADJUST PROPOSED CONNECTION POINTS DUE
TO UTILITY CONFLICTS. IN THE EVENT STRUCTURES ARE IMPACTED IN ORDER TO CONDUCT
THESE INVESTIGATIONS, THE COST OF TRAFFIC CONTROL AND RESTORATION IS
INCIDENTAL TO THE CONTRACT. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY ALL UTILITIES OF THE CONSTRUCTION AND TO MAKE THE NECESSARY
ARRANGEMENTS TO PROTECT ALL EXISTING UTILITIES. ANY UTILITIES THAT INTERFERE
WITH THE PROPOSED CONSTRUCTION SHALL BE CLOSELY COORDINATED WITH THE OWNER
AND THE RESPECTIVE UTILITY COMPANY FOR RELOCATION OR PROPER INSTRUCTION.
3. A SINGLE POINT UTILITY IDENTIFICATION SERVICE HAS BEEN SET UP FOR EXISTING
UTILITIES. THE CONTRACTOR IS TO CONTACT THE SUNSHINE STATE ONE CALL CENTER BY
DIALING “811” AT LEAST TWO (2) AND NO MORE THAN FIVE (5) WORKING DAYS PRIOR TO THE
SPECIFIC CONSTRUCTION ACTIVITY FOR FIELD LOCATION. NOTE THAT NOT ALL UTILITIES
PARTICIPATE IN THIS PROGRAM. THE CONTRACTOR SHOULD CONTACT ALL
NON-PARTICIPATING UTILITIES SEPARATELY FOR FIELD LOCATION OF THEIR FACILITIES AT
LEAST TWO (2) WORKING DAYS PRIOR TO CONSTRUCTION.
4. THE FOLLOWING UTILITIES HAVE PREVIOUSLY INDICATED THAT THEY MAY HAVE
FACILITIES IN THE VICINITY OF THE CONSTRUCTION AREA:
AT&T DISTRIBUTION
ATTN: DINO FARRUGGIO
E-MAIL: G27896@ATT.COM
CHARTER COMMUNICATIONS (SPECTRUM)
ATTN: JOHN SMITH
407-532-8520
CROWN CASTLE
800-654-3110
FLORIDA POWER & LIGHT
ATTN: JAMIE PURNELL
386-586-6403
E-MAIL: JAMIE.PURNELL@FPL.COM
FLORIDA PUBLIC UTILITIES
ATTN: COLIN DUNN
352-636-7057 E-MAIL: CDUNN@CHPK.COM
CITY OF LAKE MARY
ATTN: DANIELLE KOURY
407-585-1452
E-MAIL: DKOURY@LAKEMARYFL.COM
CITY OF SANFORD
ATTN: RICHARD BLAKE
407-688-5101
E-MAIL: RICHARD.BLAKE@SANFORDFL.GOV
SEMINOLE COUNTY ENVIRONMENTAL SERVICES DEPT.
ATTN: PAUL ZIMMERMAN
407-665-2040
E-MAIL: PZIMMERMAN@SEMINOLECOUNTYFL.GOV
THE CONTRACTOR SHALL KEEP LOCATE TICKETS UP TO DATE AT ALL TIMES.
5. THE CONTRACTOR IS RESPONSIBLE FOR ALL COORDINATION WITH EACH UTILITY AND ALL
COSTS ASSOCIATED WITH THE PROTECTION OF EXISTING FACILITIES DURING
CONSTRUCTION. THE CONTRACTOR SHALL ALSO COORDINATE NECESSARY RELOCATIONS
OR OTHER CONSTRUCTION RELATED MATTERS WITH EACH UTILITY.
6. IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO MAINTAIN IN SERVICE ALL EXISTING
PIPING ENCOUNTERED DURING CONSTRUCTION UNLESS OTHERWISE INDICATED IN THE
DRAWINGS. ANY PIPING WHICH CAN BE REMOVED DURING CONSTRUCTION WITHOUT UNDUE
INTERRUPTION OF SERVICE MAY BE REMOVED AND REPLACED BY THE CONTRACTOR WITH
THE PERMISSION OF THE OWNER AND THE ENGINEER.
7. THE CONTRACTOR SHALL FIELD LOCATE ALL WATER AND SEWER SERVICES AND
LATERALS WITHIN THE PROPOSED CONSTRUCTION AREA PRIOR TO CONSTRUCTION AND
ADJUST THE PROPOSED CONSTRUCTION AS NEEDED TO ACCOMMODATE THESE EXISTING
LINES.
8. TYPICAL DETAILS AND PROPOSED CONSTRUCTION AS SHOWN ILLUSTRATE THE
ENGINEER’S INTENT AND ARE NOT PRESENTED AS A SOLUTION TO ALL CONSTRUCTION
PROBLEMS ENCOUNTERED IN THE FIELD. THE CONTRACTOR MAY ALTER THE PROPOSED
CONSTRUCTION TO SUIT FIELD CONDITIONS, PROVIDED IT COMPLIES WITH THE PROJECT
SPECIFICATIONS AND APPROVAL IS RECEIVED FROM THE ENGINEER. WHERE SUCH
PROPOSED REVISIONS DEVIATE FROM THE FDEP CONSTRUCTION PERMIT, THEN SUCH
REVISIONS WILL ALSO REQUIRE APPROVAL FROM FDEP.
9. FOR EACH RESPECTIVE PIPELINE CONSTRUCTION REQUIRED, THE CONTRACTOR SHALL
FIELD VERIFY THE LOCATION, DEPTH, SIZE, MATERIAL TYPE, AND ALIGNMENT OF ALL
EXISTING PIPES, CABLES, ETC. TO BE CROSSED OR CONNECTED TO. IF THE CONTRACTOR
DEEMS NECESSARY (A) A CHANGE IN ALIGNMENT OR DEPTH, OR THE NEED FOR ADDITIONAL
FITTINGS, BENDS, OR COUPLINGS, WHICH REPRESENT A DEPARTURE FROM THE CONTRACT
DRAWING, OR (B) A NEED FOR RELOCATION OF EXISTING UTILITIES, THEN DETAILS OF SUCH
DEPARTURES, RELOCATIONS, OR ADDITIONAL FITTINGS, INCLUDING CHANGES IN RELATED
PORTIONS OF THE PROJECT AND THE REASONS THEREFORE, SHALL BE SUBMITTED WITH
SHOP DRAWINGS. APPROVED DEPARTURES FOR THE CONTRACTOR’S CONVENIENCE SHALL
BE MADE AT NO ADDITIONAL COST TO THE OWNER
TRAFFIC CONTROL
1. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A TEMPORARY TRAFFIC
CONTROL PLAN (TTCP) PRIOR TO CONSTRUCTION. THE TTCP (ALSO CALLED A
MAINTENANCE OF TRAFFIC (MOT) PLAN) SHALL SHOW ALL PROPOSED TRAFFIC
CONTROL SIGNS, PAVEMENT MARKINGS, AND BARRICADES, AND SHALL DETAIL
ALL PROPOSED CONSTRUCTION SEQUENCING. THE TTCP PLAN AND INSTALLED
TRAFFIC CONTROL MEASURES SHALL BE APPROVED BY THE ENGINEER, OWNER,
AND ROADWAY JURISDICTIONAL AGENCY. IN GENERAL, ROADWAY LANE
CLOSURES AND DRIVEWAY CLOSURES ARE PROHIBITED DURING CONSTRUCTION
UNLESS SPECIFICALLY DETAILED ON THESE PLANS. IN THE EVENT IT IS
DETERMINED THAT ROADWAY AND DRIVEWAY CLOSURES WILL BE ALLOWED, THE
CLOSURES SHALL BE RESTRICTED TO THE HOURS BETWEEN 9:00 A.M. AND 3:00
P.M. UNLESS OTHERWISE AUTHORIZED IN THE APPROVED TTCP PLAN.
2. ALL TRAFFIC CONTROL MEASURES SHALL BE IN ACCORDANCE WITH FDOT
STANDARD PLANS FOR ROAD CONSTRUCTION, INDEX NO. 102-600 AND THE
MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD). ALL TRAFFIC
CONTROL MEASURES SHALL BE INSTALLED PRIOR TO CONSTRUCTION AND
MAINTAINED DURING CONSTRUCTION.
3. INSPECT TRAFFIC CONTROL DEVICES ON A DAILY BASIS TO ENSURE
PLACEMENT OF BARRICADES AND FUNCTION OF LIGHTS IS MAINTAINED
THROUGHOUT CONSTRUCTION.
4. CONTACT PROPERTY OWNERS AFFECTED BY CONSTRUCTION. COORDINATE
TEMPORARY DRIVEWAY CLOSURES AND SEQUENCING. MAINTAIN ACCESS FOR
ALL PROPERTY OWNERS DURING CONSTRUCTION.
5. WET UNSTABILIZED AREAS AS NECESSARY TO CONTROL DUST.
6. ADJUST TRAFFIC CONTROL DEVICES AS REQUIRED UNDER EMERGENCY
CONDITIONS.
7. THE CONTRACTOR IS EXPECTED TO COORDINATE ITS ACTIVITIES WITH OTHER
CONTRACTORS WHO MAY BE WORKING IN THE IMMEDIATE VICINITY.
8. WHEN WORK OCCURS ALONG TWO LANE, TWO WAY ROADS AND IS WITHIN 15-FT
OF ACTIVE ROAD TRAVEL WAY BUT NO CLOSER THAN 2-FT FROM THE TRAVEL
WAY, SIGNAGE AND WARNING DEVICES ARE TO BE INSTALLED IN ACCORDANCE
WITH FDOT INDEX NO. 102-600 AND 102-602. WHEN WORK OCCURS ALONG TWO
LANE, TWO WAY ROADS BETWEEN THE ROAD CENTERLINE AND A LINE 2-FT
OUTSIDE THE EDGE OF THE TRAVEL WAY, SIGNAGE AND WARNING DEVICES ARE
TO BE INSTALLED IN ACCORDANCE WITH FDOT INDEX NO. 102-600 AND 102-603.
9. TYPE I OR TYPE II BARRICADES AT 20-FT CENTERS SHALL BE PLACED AND
MAINTAINED ALONG THE EDGE OF THE ROAD WHEREVER HAZARDS EXIST AND
TO BLOCK ENTRANCE INTO COMPLETED OR PARTIALLY COMPLETED
PAVEMENTS UNTIL SUCH PAVEMENTS ARE OPEN TO PUBLIC USE.
10. WHERE A DROP-OFF CONDITION IN THE WORK ZONE OCCURS, IT SHALL BE
MITIGATED IN ACCORDANCE WITH FDOT INDEX 102-600. REFER TO FDOT INDEX
NO. 102-600 FOR THE DEFINITION OF A DROP-OFF.
1. THE LOCATIONS OF ALL EXISTING UTILITIES SHOWN ON THIS PLAN HAVE BEEN
DETERMINED FROM THE BEST INFORMATION AVAILABLE AND ARE GIVEN FOR THE
CONVENIENCE OF THE CONTRACTOR. THE ENGINEER ASSUMES NO RESPONSIBILITY
FOR THEIR ACCURACY. PRIOR TO THE START OF ANY DEMOLITION ACTIVITY, THE
CONTRACTOR SHALL NOTIFY THE UTILITY COMPANIES FOR ON SITE LOCATIONS OF
EXISTING UTILITIES.
2. CHAPTER 553.851 OF THE FLORIDA STATUTES REQUIRES THAT AN EXCAVATOR NOTIFY
ALL GAS UTILITIES A MINIMUM OF TWO (2) WORKING DAYS PRIOR TO EXCAVATING.
3. THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR, SUPERVISION, AND
EQUIPMENT REQUIRED FOR THE ORDERLY DEMOLITION AND REMOVAL OF EXISTING
STRUCTURES, PAVEMENT AND UTILITIES AS SHOWN ON THE DRAWINGS AND DESCRIBED
HEREIN.
4. THE CONTRACTOR IS REQUIRED TO FAMILIARIZE HIMSELF WITH THE STRUCTURES TO BE
DEMOLISHED. THE CONTRACTOR IS TO BE RESPONSIBLE FOR ALL ASSOCIATED
FACILITIES IN THE DEMOLITION AREAS. THE CONTRACTOR IS TO COORDINATE ALL
DEMOLITION ACTIVITES WITH THE PLANT OWNER/OPERATOR PRIOR TO ANY
CONSTRUCTION ACTIVITY.
5. ALL SITE UNDERGROUND STRUCTURES AND PIPING TO BE DEMOLISHED MUST BE
COMPLETELY REMOVED AND OVER EXCAVATED BY A MINIMUM OF 12" BENEATH THE
STRUCTURES. CONTRACTOR SHALL USE APPROVED FILLING MATERIAL FOR FILLING
THESE AREAS. FILL SHALL BE OF CLEAN, FINE SAND AASHTO CLASS A-3 AND SHALL BE
PLACED IN LOOSE LIFTS NOT EXCEEDING 8" IN THICKNESS AND COMPACTED TO AT
LEAST 98% OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY (ASTM D-1557).
6. ALL EXISTING STRUCTURES, PAVEMENTS, SLABS, FOUNDATIONS, STEPS, AND OTHER
EXISTING FEATURES INDICATED ON THE DRAWINGS TO BE REMOVED SHALL BE
DEMOLISHED AND REMOVED BY THE CONTRACTOR.
7. ALL EXISTING SEWERS, PIPING AND UTILITIES SHOWN ARE NOT TO BE INTERPRETED AS
THE EXACT LOCATION, OR AS THE ONLY OBSTACLES THAT MAY OCCUR ON THE SITE.
VERIFY EXISTING CONDITIONS AND PROCEED WITH CAUTION AROUND ANY ANTICIPATED
FEATURES. GIVE NOTICE TO ALL UTILITY COMPANIES REGARDING DESTRUCTION AND
REMOVAL OF ALL SERVICE LINES AND CAP ALL LINES BEFORE PROCEEDING WITH THE
WORK.
8. ELECTRICAL, TELEPHONE, CABLE AND/OR GAS LINES NEEDING TO BE REMOVED OR
RELOCATED SHALL BE COORDINATED WITH THE AFFECTED UTILITY COMPANY PRIOR TO
COMMENCEMENT OF CONSTRUCTION. ADEQUATE TIME SHALL BE PROVIDED FOR
RELOCATION AND CLOSE COORDINATION WITH THE UTILITY COMPANY IS A NECESSITY
TO PROVIDE A SMOOTH TRANSITION IN UTILITY SERVICE.
9. PROVIDE ADEQUATE PROTECTION FOR PERSONS AND PROPERTY AT ALL TIMES.
EXECUTE THE WORK IN A MANNER TO AVOID HAZARDS TO PERSONS AND PROPERTY
AND PREVENT INTERFERENCE WITH THE USE OF AND ACCESS TO ADJACENT BUILDINGS.
DRIVEWAYS AND SIDEWALKS SHALL NOT BE BLOCKED BY DEBRIS AND EQUIPMENT.
10. CONTRACTOR MUST STOP OPERATION AND NOTIFY THE OWNER FOR PROPER
DIRECTION IF ANY ENVIRONMENTAL OR HEALTH RELATED CONTAMINATE IS
ENCOUNTERED DURING THE DEMOLITION / EXCAVATION PROCESS.
11. DISPOSAL
a. REMOVE AND LEGALLY DISPOSE OF ALL OTHER DEMOLISHED, RUBBLE, AND DEBRIS.
COMPLY WITH ALL APPLICABLE LAWS AND REGULATIONS GOVERNING DISPOSAL OF
WASTES AND DEBRIS.
12. PAVEMENT REMOVAL
a. WHERE EXISTING PAVEMENT IS TO BE REMOVED, SAW-CUT THE SURFACE LEAVING
A UNIFORM AND STRAIGHT EDGE WITH MINIMUM DISTURBANCE TO THE REMAINING
ADJACENT SURFACE. IF CONSTRUCTION RESULTS IN RAVELING OF THE SAW-CUT
SURFACE, RECUT BACK FROM THE RAVELED EDGE PRIOR TO RESTORATION.
b. WHERE EXISTING PAVEMENT, CURB, CURB AND GUTTER, SIDEWALK, DRIVEWAY, OR
VALLEY GUTTER IS REMOVED FOR THE PURPOSE OF CONSTRUCTING OR REMOVING
BOX CULVERTS, PIPE, INLETS. MANHOLES, APPURTENANCES, FACILITIES OR
STRUCTURES OR FOR RECONSTRUCTION PURPOSES SAID PAVEMENT, ETC., SHALL
BE REPLACED AND RESTORED IN EQUAL OR BETTER CONDITION THAN THE
ORIGINAL, CONTRACTOR SHALL PROVIDE ALL NECESSARY LABOR, MATERIALS,
EQUIPMENT, TOOLS, SUPPLIES, AND OTHER EQUIPMENT AS REQUIRED.
13. CONTINUOUS ACCESS SHALL BE MAINTAINED FOR THE SURROUNDING PROPERTIES AT
ALL TIMES DURING DEMOLITION OF THE EXISTING FACILITIES.
14. PERMITTING: IT IS THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN ANY REQUIRED
PERMITTING FOR DEMOLITION FROM RESPONSIBLE REGULATIONS AND FULLY
ACKNOWLEDGE AND COMPLY WITH ALL REQUIREMENTS PRIOR TO COMMENCING
DEMOLITION WORK.
15. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE THE EXTENT OF THIS
PROJECT. THE CONTRACTOR SHALL CONDUCT SITE VISITS AND SHALL CHECK FOR
DISCREPANCIES AND/OR OMISSIONS THAT SHALL BE BROUGHT TO THE ATTENTION OF
THE ENGINEER PRIOR TO BID SUBMITTAL.
16. PRIOR TO DEMOLITION OCCURRING, ALL EROSION CONTROL DEVICES ARE TO BE
INSTALLED.
17. THE CONTRACTOR SHALL COORDINATE WITH OWNER PRIOR TO COMMENCEMENT OF
ANY WORK. ACTUAL REMOVAL AND/OR RELOCATION OF ALL EXISTING PLANTS IS TO BE
CONDUCTED BY THE LANDSCAPE CONTRACTOR. IT IS THE RESPONSIBILITY OF THE SITE
WORK CONTRACTOR TO COORDINATE DEMOLITION ACTIVITIES WITH THE LANDSCAPE
CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR REMOVING AND PRESERVING
TREES.
18. CONTRACTOR SHALL LIMIT ALL DEMOLITION ACTIVITY TO THAT AREA DELINEATED IN
THE DRAWING. ALL EXISTING UTILITIES INCLUDING: STORM DRAINAGE, GAS, ELECTRIC,
TELEPHONE, WATER AND SEWER SHALL BE PRESERVED AND PROTECTED, UNLESS
OTHERWISE NOTED.
GENERAL DEMOLITION NOTES
AutoCAD SHX Text CPH, LLC A Full Service A & E Firm
S
Graphic Scale in Feet
5 5 10
N
3DEMOLITION PLAN
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
EXISTING LIFT STATION
T.E = 47.71
NW INV.=40.24 (10" CLAY)
NE INV. = 34.71 (10" CLAY)
BOT. = 33.79
DEMOLISH EXISTING
PUMP HOUSE
CONTRACTOR TO
COORDINATE REMOVAL
REMOVE EXISTING
ANTENNA
REMOVE EXISTING
ELECTRIC METER
EXISTING SANITARY MANHOLE TO REMAIN
T.E = 47.69
SW INV.=35.40 (10" CLAY)
E INV. = 35.51 (10" CLAY)
SE INV. = 42.50 (10" CLAY)
REMOVE EXISTING
WATER METER
EXISTING 6' CHAIN
LINK FENCE (CLF)
TO REMAIN
EXISTING 4' HOG
WIRE FENCE TO
REMAIN
EXISTING
ELEC TRANS.
DEMOLITION NOTES:
1. DEMOLITION OF THE EXISTING LIFT STATION CANNOT BEGIN UNTIL AFTER THE NEW
LIFT STATION HAS BEEN CONSTRUCTED, AND APPROVED BY THE FLORIDA DEPT. OF
ENVIRONMENTAL PROTECTION (FDEP) AND THE CITY OF SANFORD TO BE PLACED
INTO SERVICE.
2. COORDINATE WITH FLORIDA POWER AND LIGHT (FPL) AS NEEDED IN ORDER TO HAVE
THE EXISTING ELECTRICAL SERVICE AND METER CAN TAKEN OUT OF SERVICE.
REMOVE ALL OF THE ELECTRICAL SERVICE RELATED ITEMS NOT REMOVED BY FPL.
3. PER SECTION 02220 OF THE PROJECT MANUAL, THE FOLLOWING ITEMS ARE TO BE
SALVAGED AND DELIVERED TO THE CITY OF SANFORD: CONTROL PANEL, WATER
METER, METER BOX, AND RTU.
4. DEMOLISH THE BUILDING COMPLETELY INCLUDING ALL INTERIOR ITEMS AND
EXTERIOR ATTACHMENTS TO THE BUILDING AND REMOVE FROM THE SITE USING
METHODS AS REQUIRED TO COMPLETE WORK WITHIN THE LIMITATIONS OF
GOVERNING REGULATIONS. SMALL STRUCTURES MAY BE REMOVED INTACT WHEN
ACCEPTABLE TO THE CITY AND AUTHORITIES HAVING JURISDICTION.
5. REMOVE SLABS-ON-GRADE AND WALLS BELOW GRADE TO A DEPTH OF 4 FEET
BELOW GRADE. SLABS AND WALLS LEFT MORE THAN 4 FEET BELOW GRADE ARE TO
HAVE HOLES PUNCHED THROUGH THE SLABS (MINIMUM HOLE SIZE OF4-INCHES).
6. COMPLETELY FILL BELOW GRADE AREAS AND VOIDS RESULTING FROM DEMOLITION
OR REMOVAL OF STRUCTURES ETC. USING ACCEPTABLE MATERIAL AS DEFINED IN
SECTION 02315 OF THE PROJECT MANUAL. CONCRETE RUBBLE FROM DEMOLITION
ACTIVITIES CAN ALSO BE USED AS BACKFILL PROVIDED IT IS NOT PAINTED OR
COATED, IS FREE OF STEEL REINFORCEMENT, AND IS BROKEN INTO PIECES THAT
MEASURE NO LARGER THAN 8-INCHES IN ANY DIRECTION.
EXISTING
PROPERTY LINE
SITE BENCHMARK #535+
TOP OF MAG NAIL AND DISK
WITH "BM" LB #7143
EL. 47.72 NAVD88
N.1608609.12 E.557974.72
DEMOLISH
LEGEND
DEMO TOP SLAB AND
PIPING. WET WELL TO
REMAIN IN PLACE
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.7'
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.6'
M
28'
TOP OF MAG NAIL & DISK
WITH "BM" LB #7143
ELEV = 47.72 (NAVD '88)
N:-16.38 E:49.82
SITE BENCHMARK #535
Graphic Scale in Feet
20 20 40
N
4SITE PLAN
EXISTING FORCE MAIN TO REMAIN
PROPOSED SILT FENCE
PROPOSED CONTOUR GRADE LINE
PROPOSED FORCE MAIN
XX
PROPOSED CONCRETE
PAD (8" THICK)
LEGEND
PROPOSED 6' HIGH CHAIN LINK FENCE
XX.X PROPOSED ELEV.
R/W LINE
NEW LIFT STATION AND CONCRETE DRIVEWAY GENERAL NOTES
1. THE NEW CONCRETE DRIVEWAY SHALL CONSIST OF 6" THICK FIBER MESH REINFORCED CONCRETE, MINIMUM 3000 P.S.I. THE NEW LIFT STATION SITE CONCRETE SHALL CONSIST OF 8" THICK CONCRETE, REINFORCED WITH NO. 4 REBAR AT 12 INCHES ON CENTER EACH WAY.
2. PRIOR TO INSTALLATION, COMPACT EXISTING SUBGRADE TO A DEPTH OF 6" AND INSTALL VAPOR BARRIER PRIOR TO CONCRETE PLACEMENT. ADD STABILIZING MATERIAL AS
NEEDED TO ACHIEVE MIN. 98% MAXIMUM DENSITY PER AASHTO T-180.
4. CONCRETE CONTRACTION JOINTS ARE TO CONSIST OF 2" DEEP SAW CUT JOINTS, SAW CUT WITHIN 24 HOURS OF CONCRETE INSTALLATION. INSTALL CONTRACTION JOINTS ALONG THE DRIVEWAY AND SITE CONCRETE PAD IN EACH DIRECTION, WITH A MAXIMUM ALLOWABLE SPACING OF 12.5'.
5. FINISH THE CONCRETE SURFACE WITH A LIGHT BROOM FINISH.
6. THE NEW DRIVEWAY AND SITE CONCRETE SHALL CURE A MINIMUM OF 7 DAYS BEFORE THEY CAN BE USED. INSTALL BARRICADES AND TEMPORARY FENCING AS NEEDED TO
PROTECT THE COMPLETED DRIVEWAY AND SITE CONCRETE FROM VEHICLES AND PEDESTRIANS
3. CONCRETE EXPANSION JOINTS SHALL CONSIST OF 3/8" X 6" PREMOLDED EXPANSION MATERIAL. INSTALL EXPANSION JOINTS BETWEEN THE DRIVEWAY AND LIFT STATION SITE CONCRETE, BETWEEN THE DRIVEWAY AND THE DROP CURB AT THE STREET, AND AROUND THE NEW WET WELL, VALVE VAULT. AND GENERATOR PAD. IN ADDITION, INSTALL
ONE EXPANSION JOINT ACROSS THE SITE CONCRETE PAD AS SHOWN.
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
EXISTING 6" CIP
FORCEMAIN TO
REMAIN
MANHOLE TO REDIRECT TO NEW STATION
EXISTING LIFT STATION
T.E = 47.71
NW INV.=40.24 (10" CLAY)
NE INV. = 34.71 (10" CLAY)
BOT. = 33.79
S-1
EXISTING SANITARY MANHOLE TO REMAIN
T.E = 47.69
SW INV.=35.40 (10" CLAY)
E INV. = 35.51 (10" CLAY)
SE INV. = 35.30 (8" PVC) (CORE)
PROPOSED 39 LF OF 12"
PVC SANITARY SEWER @
0.40%
PROPOSED JUNCTION MH
T.E = 45.87
NW INV.=35.22 (8" PVC)
S INV. = 35.12 (8" PVC)
PROPOSED 20 LF 6" PVC
FORCEMAIN
PROPOSED SAN SEWER
EXISTING 6" CIP
FORCEMAIN TO BE
REMOVED
EXISTING FORCE MAIN TO BE REMOVED
PROPOSED 2- 6" FM
45°BENDS
CUT AND CONNECT
45° BEND
PROPOSED 6" FM 45°BEND
EXISTING SAN SEWER TO REMAIN
PROPOSED 6"X 6" FM TEE
TREE LINE SHOWN
APPROXIMATE THIS AREA
TREE LINE SHOWN
APPROXIMATE THIS AREA
GROUT FILL AND
ABANDON EXISTING
SANITARY SEWER
SEGMENT
PROPOSED 53 LF
OF 1" WATER SERVICE
PROPOSED WATER MAIN SERVICE
PROPOSED 9 LF OF 10" PVC
SANITARY SEWER @ 0.28%
PROPOSED 30 LF OF 10" PVC
SANITARY SEWER @ 0.4%
NEW LIFT STATION TOP LID
EL. 45.87
PROPOSED 9 LF OF 10" PVC
SANITARY SEWER @ 0.28%
PROPOSED LINE
STOP
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.7'
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.6'
AutoCAD SHX Text
LOT 19
AutoCAD SHX Text
RECREATION AREA GROVEVIEW VILLAGE PB 19, PGS 4-6
AutoCAD SHX Text
LOT 18
AutoCAD SHX Text S
AutoCAD SHX Text S
10'
30.5'
24'
Graphic Scale in Feet
10 10 20
N
4SITE PLAN
EXISTING FORCE MAIN TO REMAIN
PROPOSED CONTOUR GRADE LINE
PROPOSED FORCE MAIN
XX
PROPOSED CONCRETE
PAD (8" THICK)
LEGEND
PROPOSED 6' HIGH CHAIN LINK FENCE
XX.X PROPOSED ELEV.
R/W LINE
GENERAL NOTES
1. THE NEW CONCRETE DRIVEWAY SHALL CONSIST OF 6" THICK FIBER MESH REINFORCED CONCRETE, MINIMUM 3000 P.S.I. THE NEW LIFT STATION SITE CONCRETE SHALL CONSIST OF 8" THICK CONCRETE, REINFORCED WITH NO. 4 REBAR AT 12 INCHES ON CENTER EACH WAY.
2. PRIOR TO INSTALLATION, COMPACT EXISTING SUBGRADE TO A DEPTH OF 6" AND INSTALL VAPOR BARRIER PRIOR TO CONCRETE PLACEMENT. ADD STABILIZING MATERIAL AS
NEEDED TO ACHIEVE MIN. 98% MAXIMUM DENSITY PER AASHTO T-180.
4. CONCRETE CONTRACTION JOINTS ARE TO CONSIST OF 2" DEEP SAW CUT JOINTS, SAW CUT WITHIN 24 HOURS OF CONCRETE INSTALLATION. INSTALL CONTRACTION JOINTS ALONG THE DRIVEWAY AND SITE CONCRETE PAD IN EACH DIRECTION, WITH A MAXIMUM ALLOWABLE SPACING OF 12.5'.
5. FINISH THE CONCRETE SURFACE WITH A LIGHT BROOM FINISH.
6. THE NEW DRIVEWAY AND SITE CONCRETE SHALL CURE A MINIMUM OF 7 DAYS BEFORE THEY CAN BE USED. INSTALL BARRICADES AND TEMPORARY FENCING AS NEEDED TO
PROTECT THE COMPLETED DRIVEWAY AND SITE CONCRETE FROM VEHICLES AND PEDESTRIANS
3. CONCRETE EXPANSION JOINTS SHALL CONSIST OF 3/8" X 6" PREMOLDED EXPANSION MATERIAL. INSTALL EXPANSION JOINTS BETWEEN THE DRIVEWAY AND LIFT STATION SITE CONCRETE, BETWEEN THE DRIVEWAY AND THE DROP CURB AT THE STREET, AND AROUND THE NEW WET WELL, VALVE VAULT. AND GENERATOR PAD. IN ADDITION, INSTALL
ONE EXPANSION JOINT ACROSS THE SITE CONCRETE PAD AS SHOWN.
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
EXISTING 6" CIP
FORCEMAIN TO
REMAIN
EXISTING LIFT STATION
T.E = 47.71
NW INV.=40.24 (10" CLAY)
NE INV. = 34.71 (10" CLAY)
BOT. = 33.79
S-1
EXISTING SANITARY MANHOLE TO REMAIN
T.E = 47.69
SW INV.=35.40 (10" CLAY)
E INV. = 35.51 (10" CLAY)
SE INV ELEV (6" PVC) = 42.50
PROPOSED 39 LF OF 12"
PVC SANITARY SEWER @
0.40%
PROPOSED JUNCTION MH
T.E = 46.91
NW INV =35.25 (12" PVC)
S INV = 35.15 (12" PVC)
PROPOSED 12 LF 6" PVC
FORCEMAIN
PROPOSED SAN SEWER
EXISTING 6" CIP
FORCEMAIN TO BE
REMOVED
EXISTING FORCE MAIN TO BE REMOVED
PROPOSED 6" FM
45°BEND
CUT AND CONNECT
45° BEND
PROPOSED 6" FM 45°BEND
EXISTING SAN SEWER TO REMAIN
PROPOSED 6"X 4" FM TEE
TREE LINE SHOWN
APPROXIMATE THIS AREA
TREE LINE SHOWN
APPROXIMATE THIS AREA
GROUT FILL AND
ABANDON EXISTING
SANITARY SEWER
SEGMENT
PROPOSED 53 LF
OF 1" WATER SERVICE
PROPOSED WATER MAIN SERVICE
PROPOSED 9 LF OF 10" PVC
SANITARY SEWER @ 0.40%
PROPOSED 15 LF OF 12" PVC
SANITARY SEWER @ 0.4%
NEW PUMP STATION TOP
LID EL. 45.94
PROPOSED LINE
STOP
PROPOSED 6" FM
45° WYE
PROPOSED GRADING
PROPOSED TOP SLAB.
REPLACEMENT WITH MANHOLE COVER
(MANHOLE TO REDIRECT TO NEW PUMP STATION)
EXISTING
WET WELL
RIM 47.71
INV. 36.48
INV. 34.71
S-1
RIM 47.69
INV. 35.41
S-2
RIM 46.91
INV. 36.44
EXISTING TO BE PLUGGED
PROPOSED 9 LF OF 10" PVC
SANITARY SEWER @ 0.40%
PROPOSED 39 LF OF 12" PVCSANITARY SEWER @ 0.4% INV. 35.25
INV. 40.24
SITE BENCHMARK #535+
TOP OF MAG NAIL AND DISK
WITH "BM" LB #7143
EL. 47.72 NAVD88
N.1608609.12 E.557974.72
100 YEAR FLOOD ELEVATION (FT) - 45.010 20 30 40 50 60 70 80 90
1" = 10' HORIZONTAL
1" = 2' VERTICAL
45.44 45.44
45.44 45.44
45.44 45.44
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.7'
AutoCAD SHX Text 14.0'
AutoCAD SHX Text 12.6'
AutoCAD SHX Text
LOT 19
AutoCAD SHX Text
LOT 18
AutoCAD SHX Text S
AutoCAD SHX Text S
PROPOSED SANITARY
MANHOLE
8' DIA. WET WELL
6" EMERGENCY PUMP
OUT FEMEL FLANGED
END "AGRI-LOCK" WITH
LOCK RING
6" CHECK VALVES W/
LEVER AND WEIGHT
CHAIN LINK FENCE
CONTROL PANEL
6" PLUG VALVES
ALUMINUM ACCESS HATCH WITH
LOCKSET AND RELEASE HANDLE
2" DRAIN LINE W/
SS FLAPPERVALVE
4" 316 SS VENT
WITH SS SCREEN
60" X 48" ALUMINUM ACCESS HATCH
(HALLIDAY PRODUCT H2R4860 OR EQUAL)
6" 45° BEND (MJ)
CONCRETE
EXPANSION
JOINT
WATER SERVICE
METER SUPPLIED
BY CITY
5'X6' CONCRETE
VALVE VAULT
30.5'
6" PVC FM
HOSE BIB W/ RPZ
AND METER
SUCTION LINE
2 -6' SWING GATE
2" ARV
ARV DRAIN
6" PLUG VALVE
4" CHECK
VALVE
PRESSURE GAUGE
CONNECT TO 6"
FLANGE W/ FLEX
COUPLING
ADJUSTABLE PIPE SUPPORT
W/ U-BOLT BETWEEN PLUG
VALVE AND BEND
13 LF OF
4" HDPE
(UNDER
3' OF
COVER)
(2) 6" 45° BENDS (MJ)
6" WYE (MJ)
6" X4" TEE (MJ)
4" PLUG
VALVE (MJ)
4" 90°
BENDS
(MJ)
(FLG)
6" 90°
BENDS
(MJ)
(FLG)
SECTION C-C
N.T.S.
8"
4" 6"
4"
#4 DOWELS
CONTINUOUS
8" CONCRETE SLAB (3000
PSI CONCRETE)
#4@12" O.C.
9"#4@12" O.C.E.W.
3.0'
A
3.0'
14.0'
5 LF OF 6" HDPE
(UNDER 3' OF
COVER)
24.0'
20.0'
.0
5.0' 8"8"
NEW CONCRETE FLOW
METER VAULT
B 5 6
6" ELECTROMAGNETIC
FLOW METER
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
5LIFT STATION
PLAN VIEW
Graphic Scale in Feet
2 2 4
N
C C
C C
C C
C C
AutoCAD SHX Text S
8'
12"
2" DRAIN LINE W/ SS
FLAPPER VALVE
FLOAT SWITCHES HIGH
LEVEL AND LOW LEVEL
ALARMS
10"
4"
8"
EL. 45.44'
6" EMERGENCY PUMP OUT FEMALE FLANGED
END "AGRI-LOCK" WITH LOCK RING
6" X 6" TEE
60" X 48" ALUMINUM ACCESS HATCH
(HALLIDAY PRODUCTS H2R4860 OR EQUAL)
6" PLUG VALVE
EPOXY COATING AS MANUFACTURED BY RAVEN LINING
SYSTEMS OR SEWPERCOAT CALCIUM ALUMINATE
COATING PER THE SPECIFICATIONS.
316 SS PIPE SUPPORT
6" CHECK VALVE
W/ LEVER AND
WEIGHT
EL. 25.09'
LEVEL TRANSDUCER
SLEEVES SIZED FOR
2" PVC CONDUITS
EL. 45.94
4" 316 SS VENT WITH SS SCREEN
LEVELING GROUT (1" MIN.)
60" X 60" ALUMINUM ACCESS HATCH
(HALLIDAY PRODUCTS H2R6060 OR EQUAL)
6" THICK CONCRETE W/ #4@12" O.C.E.W. (SEE DETAIL)
6" 90° BEND
6" X 4" REDUCER
6"X 6" WYE
6" D
.I.
6" D.I.
6" PVC
2 NO. 5 CONTINOUS @
PERIMETER OF WET WELL
AND VALVE VAULT (TYP.)
INSTALL 3/4" EXPANSION MATERIAL AROUND
WET WELL & VALVE VAULT (TYP.)
CONTROL PANEL SEE
ELECTRICAL PLAN FOR DETAIL
PRESSURE GAUGE AND
PET COCK VALVE
WALL SLEEVE AND COMPRESSION SEAL (TYP)
FDOT NO. 57 STONE
9"
MIN
9" M
IN
SECTION
N.T.S.
STAINLESS STEEL LIFTING
CABLE
6-45° BEND
A 5 6
3' C
O
VE
R
6-45° BEND
6-45° BEND
6" RESTRAINED
FLANGE COUPLING
ADAPTER
HDPE LINER
SEE SPECS
TOP EL. 45.44
#4 BAR @ 12" O.C.E.W. (TYP.)
2 - #4 BARS (TYP.)
#4 'L' SHAPED DOWEL (TYP.)
2 - #4 BARS (TYP.)
#4 'L' SHAPED DOWEL (TYP.)
4'-0" x 4'-0" SPRING ASSIST ALUMINUM ACCESS
HATCH WITH LOCKSET AND RECESSED
HANDLE HALLIDAY PRODUCTS OR APPROVED
EQUAL. HATCH TO BE TRAFFIC RATED
4'-1"
TO DISTRIBUTION SYSTEM
CONCRETE VAULT WITH OPEN
BOTTOM 5'-0" L x 5'-0" W x 5'-0" DEEP
(INSIDE DIMENSIONS)
OPEN BOTTOM WITH # 89 GRANITE GRAVEL
6" FM PVC
FINISHED GRADE
6" FM PVC
6" FLOW
METER
8"8"
8" (TYP.)
PROTECTIVE AGRU LINER
SECTION
N.T.S.
B 5 6
6LIFT STATION SECTION
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
100 YEAR FLOOD ELEVATION (FT) - 45.0
A A C C
B B
BY-PASS PUMP DETAILS
AND NOTES
DIMENSIONS IN INCHES
PIPE DIA. A B D C E
MIN MAX
4 3/16
3 5/8
9 1/2 14 5 4 13/16 10 1/8 1 5/8 6 5 7/16 10 3/4 15 1/4 8 6 15/16 12 1/4 16 3/4
10 8 7/16 13 3/4 18 1/4 12 9 15/16 14 5/8 19 1/8 14 10 1/2
15 13/16 20 5/16 16 11 1/2 16 13/16 21 5/16
13 1/2
19 1/8 23 5/8 20 14 1/2 20 1/8 24 5/8 22 15 1/2 21 5/16 25 13/16 24 17 1/2 23 5/16 27 13/16 26 18 1/2 24 5/16 28 13/16 30 20 5/8 26 7/16 30 15/16 32 21 5/8 27 7/16 31 15/16 36 23 5/8 29 7/16 33 15/16
A
D
A
ADJUSTABLE "U-BOLT"
PIPE SUPPORT ANVIL
FIG 265 OR EQUAL
STANCHION PIPE SIZE PER
TABLE STAINLESS STEEL /
HOT DIP GALVANIZED
4 EA. 5/8" SS ADHESIVE
SET ANCHOR BOLTS (TYP)
C
E
B
D
1" H.S. NON-SHRINK
GROUT
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com THIS SHEET NOT VALID FOR CONSTRUCTION WITHOUT COMPLETE SET OF PLANS. SEE GENERAL NOTES FOR MASTER LEGEND.
8 GROVEVIEW PUMP STATION
IMPROVEMENTS
Sanford, Florida S06222 08-2024
R.NASSO
M. SANTOS-CHAVEZ
Z. AADAD
C 2025
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
ROCCO R. NASSO II, P.E.
FL P.E. No. 64727
B
ID
D O
C U
M E
N T
S
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
VIBRATION ISOLATION PAD
AutoCAD SHX Text
6" CHECK VALVE
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
DRAIN PIPE FROM PUMP & ARV
AutoCAD SHX Text
2" ARV ON SPOOL PIECE
AutoCAD SHX Text
6" MJ DI 90 BEND
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
6" MJ DI 90 BEND
AutoCAD SHX Text
6" GATE VALVE
AutoCAD SHX Text
6" MJ DI 90 BEND
AutoCAD SHX Text
6" MJ DI 90 BEND
AutoCAD SHX Text
TO WETWELL
AutoCAD SHX Text
6" MJ ADAPTER
AutoCAD SHX Text
TO FM CONNECTION
AutoCAD SHX Text
6" MJ ADAPTER
AutoCAD SHX Text 2x 304 SS NUTS
AutoCAD SHX Text
304 SS METAL WASHER
AutoCAD SHX Text
PUMP MOUNTING SKID
AutoCAD SHX Text
NOTE: NUMBER AND LOCATION PER PUMP MANUFACTURER
AutoCAD SHX Text
EPOXY OR VINYLESTER ADHESIVE ANCHORING SYSTEM
AutoCAD SHX Text
1" PAD (UNISORB VIBRATION ISOLATION PAD)
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
FINISH SURFACE SMOOTH AND LEVEL
AutoCAD SHX Text 34"x 8 " DIA. 304 SS TREAD ROD 12" DIA. 304 SS TREAD ROD
AutoCAD SHX Text
12" RUBBER WASHER (UNISORB)
AutoCAD SHX Text WWR 6x6-W2.9xW2.9 W/ MIN 2" COVER
AutoCAD SHX Text
12" EXPANSION JOINT (ALL SIDES AROUND PAD-TYP)
AutoCAD SHX Text NOTE: PAD DIMENSIONS=8'8"Lx4'4" x 8" THICK TO EXTEND BEYOND FOOTPRINT OF PUMP APPROX 2" ON EACH OF ALL FOUR SIDES.
AutoCAD SHX Text
COMPACTED SOIL
AutoCAD SHX Text #5 @ 12" E.W
AutoCAD SHX Text
2" CL
AutoCAD SHX Text 8"
AutoCAD SHX Text 2"
AutoCAD SHX Text
2" CL
AutoCAD SHX Text
AIR RELEASE VALVE STAINLESS STEEL
AutoCAD SHX Text
BALL VALVE, SS
AutoCAD SHX Text
SS TEE W/ THREADED CAP
AutoCAD SHX Text
SCH. 80 PVC TO DRAIN LINE
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
GROUT FILL
AutoCAD SHX Text
DRAIN LINE SLOPPED TO WET WELL
AutoCAD SHX Text
1 " SCHED. 80 PVC12" SCHED. 80 PVC
AutoCAD SHX Text
%%UTYPICAL ARV & PIPE DRAIN ASSEMBLY DETAIL
AutoCAD SHX Text
%%UCONCRETE PAD FOR PUMP
AutoCAD SHX Text
%%UPUMP ANCHOR DETAIL
AutoCAD SHX Text
HDPE SUCTION RISER
AutoCAD SHX Text
TO PUMP
AutoCAD SHX Text
SHOP WELD HDPE 90%%D BEND
AutoCAD SHX Text
LINK SEAL
AutoCAD SHX Text
INSTALL DRAIN PIPE FROM PUMP ARV THRU TOP OF EXIST. SLAB
AutoCAD SHX Text
WET WELL
AutoCAD SHX Text
SS WALL MOUNTED PIPE SUPPORT
AutoCAD SHX Text
STRAW TO BE CUT AT 45° ANGLE
AutoCAD SHX Text %%uTOP VIEW
AutoCAD SHX Text
%%UPIPE FASTENING BRACKET
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
1. ALL COMPONENTS AND BRACKET ASSEMBLY SHALL BE GRADE 316 STAINLESS STEEL.
AutoCAD SHX Text
2. BRACKETS SHALL BE SPACED AS INDICATED IN THE CONSTRUCTION DRAWING OR AT THE DIRECTION OF TWA.AT THE DIRECTION OF TWA.
AutoCAD SHX Text
3. PIPE SIZES AND MATERIALS SHALL BE AS INDICATED IN THE CONSTRUCTION DRAWINGS.
AutoCAD SHX Text
4. A MINIMUM OF 2 BRACKETS REQUIRED. MAX 10' SPACING.
AutoCAD SHX Text
PER PUMP MANUFACTURERS RECOMMENDATIONS
AutoCAD SHX Text %%uSECTION VIEW
AutoCAD SHX Text
WET WELL WALL
AutoCAD SHX Text
BOTTOM SLAB
AutoCAD SHX Text
WET WELL
AutoCAD SHX Text 3"x3" ANGLE TYPE 316 S.S.
AutoCAD SHX Text
S.S. "U" BOLT
AutoCAD SHX Text
5. WELD ALL CONNECTIONS EXCEPT U-BOLTS.
AutoCAD SHX Text
PIPE DIA.
AutoCAD SHX Text
S.S. FASTENER (TYP.)
AutoCAD SHX Text 3"x3" ANGLE IRON TYPE 316 S.S.
AutoCAD SHX Text 3"x3" ANGLE IRON TYPE 316 S.S.
AutoCAD SHX Text
S.S. "U" BOLT
AutoCAD SHX Text PENETRATIONS THROUGH NEW LINER PER MANUFACTURER'S INSTALLATION (TYP. ALL CONNECTION LOCATIONS)
AutoCAD SHX Text
UNBOLT AND SHORTEN SUPPORTS (TYP. OF 2)
AutoCAD SHX Text
REMOVE CROSS SUPPORT AND SHORTEN TO ACCOMMODATE NEW DIAMETER
AutoCAD SHX Text
6. MODIFY BRACKET SPACING AS NEEDED TO AVOID CONFLICT WITH EXISTING SUBMERSIBLE PUMPS AND RISERS.
AutoCAD SHX Text
CORE NEW LINER PER MANUFACTURER'S REQUIREMENTS
AutoCAD SHX Text
CONTRACTOR TO VERIFY TOTAL LENGTH OF PIPE BASED ON FUEL TANK SIZING
AutoCAD SHX Text
CONTRACTOR TO VERIFY TOTAL LENGTH OF PIPE BASED ON FUEL TANK SIZING
AutoCAD SHX Text
PIPE SUPPORT
AutoCAD SHX Text
SEAL LINER TO NEW PIPE
AutoCAD SHX Text
%%UPUMP OUT DISCHARGE
AutoCAD SHX Text
SCALE: HORIZ: N.T.S.
AutoCAD SHX Text
%%UBY-PASS SUCTION
AutoCAD SHX Text
SCALE: HORIZ: N.T.S.
AutoCAD SHX Text
%%UPUMP OUT SUCTION
AutoCAD SHX Text
SCALE: HORIZ: N.T.S.
AutoCAD SHX Text
INV EL. 49.73'
AutoCAD SHX Text
12" EXPANSION JOINT (ALL SIDES AROUND PAD-TYP)
AutoCAD SHX Text
EXISTING GRADE SLAB
AutoCAD SHX Text
SOD
AutoCAD SHX Text
SCALE: HORIZ: N.T.S.
AutoCAD SHX Text
SCALE: HORIZ: N.T.S.
AutoCAD SHX Text
(SEE DETAIL)
AutoCAD SHX Text
PIPE SUPPORT
AutoCAD SHX Text
(SEE DETAIL)
AutoCAD SHX Text
PUMP DRAIN LINE
AutoCAD SHX Text
1. THE CONTRACTOR SHALL REVIEW AND VERIFY DIMENSIONS SHOWN IN ALL PLANS AND REVIEW THE CONTRACTOR SHALL REVIEW AND VERIFY DIMENSIONS SHOWN IN ALL PLANS AND REVIEW ALL FIELD CONDITIONS THAT MAY AFFECT THE INSTALLATION OF THE DETAILS SHOWN. SHOULD DISCREPANCIES APPEAR, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING TO OBTAIN ENGINEER'S CLARIFICATION BEFORE COMMENCING WITH WORK. 2. THE CONTRACTOR SHALL TAKE ANY AND ALL NECESSARY MEASURES TO PROTECT EXISTING THE CONTRACTOR SHALL TAKE ANY AND ALL NECESSARY MEASURES TO PROTECT EXISTING STRUCTURES AND UTILITIES FROM DAMAGE WHEN WORKING IN AND AROUND EXISTING STRUCTURE. 3. ALL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE MECHANICAL, CIVIL, ALL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE MECHANICAL, CIVIL, ELECTRICAL, AND SHOP DRAWINGS, AND SPECIFICATIONS.
AutoCAD SHX Text
GENERAL CONDITIONS
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text ALL MATERIALS AND METHODS OF CONSTRUCTION SHALL BE IN ACCORDANCE WITH ACI 318 REQUIREMENTS (LATEST EDITION). ALL CONCRETE SHALL BE AIR-ENTRAINED WITH 4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS UNLESS OTHERWISE NOTED. ALL CONCRETE SURFSCES EXPOSED TO AIR, UNLESS OTHERWISE NOTED IN SPECIFICATIONS, SHALL BE TREATED WITH AN APPROPRIATE CURING COMPOUND AS SOON AS CEMENT FINISHING IS COMPLETED OR FORMS ARE REMOVED. ALL EXPOSED CORNERS SHALL HAVE A MINIMUM CHAMFER OF 3/4" UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL OBTAIN ENGINEER'S APPROVAL FOR THE LOCATION OF CONSTRUCTION JOINTS THAT ARE NOT SHOWN ON THE DRAWINGS.
AutoCAD SHX Text
GENERAL STRUCTURAL NOTES
AutoCAD SHX Text REINFORCEMENT SHALL CONFORM TO ASTM A615, GRADE 60 REQUIREMENTS. WELDED WIRE FABRIC, ASTM A185. ALL ACCESSORIES SHALL BE IN CONFORMANCE WITH ACI 315 REQUIREMENTS. REINFORCING STEEL SHALL HAVE THE FOLLOWING CLEAR COVER UNLESS OTHERWISE NOTED: CONCRETE CASE AGAINST EARTH 3" 3" FORMED SURFACES IN CONTACT 2" 2" WITH SOIL, SEWAGE, WATER OR EXPOSED TO WEATHER
AutoCAD SHX Text
REINFORCING STEEL
AutoCAD SHX Text
PRECAST CONSTRUCTION
AutoCAD SHX Text PRECAST TOP SLAB SHALL BE IN CONFORMANCE WITH THE REQUIREMENTS OF ASTM C478. COORDINATE ALL PIPE PENETRATIONS WITH PUMP MANUFACTURER AND OTHER DISCIPLINE DRAWINGS. FOR REINFORCEMENT DIFFERING FROM THE BELOW SIZES AND LAYOUT THE PRECAST SUPPLIER SHALL PROVIDE A SIGNED AND SEALED SHOP DRAWING BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE SUPERIMPOSED LOADS SHOWN. DESIGN LOADS SUPERIMPOSED LIVE LOAD - H-20 - H-20 H-20 MINIMUM REINFORCEMENT PROVIDE #5 AT 8", CENTER, W/(2) #5 AT 4" AT EACH SIDE OF THE OPENING PROVIDE #5 PROVIDE #5 AT 4" X 2'-6", CENTER, DIAGONAL REINFORCEMENT AS SHOWN
AutoCAD SHX Text
COATING SYSTEMS
AutoCAD SHX Text SURFACE PREPARATION - ALL INTERIOR SURFACES & ALL COATING SYSTEMS 1. EXISTING SUBSTRATE SHALL BE PREPARED BY REMOVING ALL DIRT, OIL, GREASE, CHEMICALS, EXISTING SUBSTRATE SHALL BE PREPARED BY REMOVING ALL DIRT, OIL, GREASE, CHEMICALS, WASTE AND OTHER SURFACE CONTAMINANTS BY WATER BLASTING OR ABRASIVE BLASTING. REMOVE ALL PREVIOUSLY APPLIED COATINGS TO ACHIEVE A SURFACE PROFILE OF SSPC SP-13/NACE No.6 OR ARE REQUIRED BY THE MANUFACTURER. ALL SURFACES SHALL BE CLEAN AND DRY PRIOR TO APPLICATION OF COATINGS. SEE MANUFACTURES'S INFORMATION FOR ANY ADDITIONAL REQUIREMENTS. 2. WHERE JOINTS OR OTHER LOCATIONS ARE LEAKING OR ALLOWING INFILTRATION OF ANY KIND, WHERE JOINTS OR OTHER LOCATIONS ARE LEAKING OR ALLOWING INFILTRATION OF ANY KIND, THE LOCATION SHALL BE REPAIRED TO ACHIEVE A MANUFACTURER'S REQUIREMENTS. 3. WHERE REINFORCEMENT IS EXPOSED DURING SURFACE PREPARATION, SIKA ARMATEC 110 WHERE REINFORCEMENT IS EXPOSED DURING SURFACE PREPARATION, SIKA ARMATEC 110 CORROSION INHIBITOR SHALL BE APPLIED TO REINFORCEMENT AFTER REINFORCEMENT HAS BEEN CLEANED TO WHITE METAL.
AutoCAD SHX Text
%%UADJUSTABLE PIPE SUPPORT W/ U-BOLT DETAIL
24"
24"
NEW OR RELOCATED WATER MAINS AND FIRE HYDRANTS WITH
UNDERGROUND DRAINS MUST BE AT LEAST 10 FEET FROM ANY EXISTING
OR PROPOSED "ON-SITE SEWAGE TREATMENT SYSTEM" (OSTADS) AS
DEFINED IN SECTION 381.0065(2), F.S., AND RULE 64E-6.002 F.A.C.
EXAMPLES OF OSTADS INCLUDE SEPTIC TANKS, DRAINFIELDS, AND
GREASE TRAPS.
OR CONCRETE ENCASEMENT AT LEAST 4" THICK FOR
THE WATER MAIN AND THE OTHER PIPELINE IF THE
OTHER PIPE LINE CONVEYS WASTEWATER OR
A. WHERE A WATER MAIN IS BEING LAID LESS THAN THE REQUIRED
MINIMUM HORIZONTAL DISTANCE AND/OR WHERE A WATER MAIN
CROSSING HAS LESS THAN THE MINIMUM REQUIRED DISTANCE
1. USE OF PRESSURE RATED PIPE CONFORMING TO
AWWA STANDARDS, FOR A GRAVITY OR VACUUM
2. USE OF WELDED, FUSED OR OTHERWISE RESTRAINED
3. USE OF WATERTIGHT CASING PIPE OR CONCRETE
ENCASEMENT AT LEAST 4" THICK FOR EITHER PIPE.
B. WHERE A WATER MAIN IS BEING LAID LESS THAN 3 FEET HORIZON-
TALLY FROM ANOTHER PIPE LINE AND/OR WHERE A WATER MAIN
IS BEING LAID WITH LESS THAN THE REQUIRED MINIMUM VERTICAL
1. USE OF PIPE OR CASING PIPE, HAVING HIGH IMPACT
STRENGTH (AT LEAST EQUAL TO 0.25" THICK D.I.P.),
MINIMUM HORIZONTAL AND VERTICAL SEPARATION REQUIREMENTS
12" BELOW
6" ABOVE
6. NO WATER PIPE SHALL PASS THROUGH OR BE CONSTRUCTED
TOUCHING ANY PART OF A SANITARY MANHOLE OR STORM SEWER
THE TOP OF THE GRAVITY SEWER.
1. THE TABLE REPRESENTS THE MINIMUM SEPARATION REQUIREMENTS
AS DESCRIBED IN F.D.E.P. RULES PER THE FLORIDA ADMINISTRATION
CODE (F.A.C.). THESE SEPARATION REQUIREMENTS SHALL APPLY
BETWEEN NEWLY PROPOSED UTILITY LINES AND EXISTING OR
2. FOR THE PURPOSE OF THIS TABLE RECLAIMED WATER SHALL MEAN
UNRESTRICTED PUBLIC ACCESS REUSE WATER AS DEFINED BY
F.A.C. 62-610. OTHER TYPES OF RECLAIMED WATER ARE CONSIDERED
RAW SEWAGE AND SEPARATION LISTED FOR SANITARY SEWER SHALL
3. ALL SEPARATION DISTANCES ARE FROM OUTSIDE OF PIPE TO OUTSIDE
4. THE MINIMUM HORIZONTAL SEPARATION BETWEEN POTABLE WATER
AND GRAVITY SANITARY SEWER MAY BE REDUCED TO 3 FEET IF THE
BOTTOM OF THE WATER MAIN IS LOCATED AT LEAST 6 INCHES ABOVE
5. AT UTILITY CROSSINGS ONE FULL LENGTH OF WATER MAIN SHALL BE
CENTERED ABOVE OR BELOW THE OTHER UTILITY PIPELINE MAXIMIZING
THE SEPARATION OF PIPELINE JOINTS. ALTERNATIVELY, WATER MAIN
A. AT LEAST 3' FROM ALL JOINTS IN VACUUM TYPE SANITARY SEWERS,
STORM SEWERS, STORMWATER FORCE MAINS, OR UNRESTRICTED
PUBLIC ACCESS RECLAIMED WATER.
B. AT LEAST 6' FROM ALL JOINTS IN GRAVITY OR PRESSURE SANITARY
SEWERS, WASTEWATER FORCE MAINS, AND ALL OTHER TYPES OF
12" BELOW
6" ABOVE
OF PIPE. MANHOLE OR INLET STRUCTURE.
RECLAIMED WATER.
JOINTS MUST BE:
PROPOSED UTILITY LINES.
APPLY.
SANITARY SEWER
VACUUM TYPE
STORM SEWER OR
W/UNDERGROUND
FIRE HYDRANT
GRAVITY MAIN
SANITARY SEWER
DRAINS
3'
6' **
RECLAIMED WATER.
SEPARATION:
BETWEEN JOINTS:
TYPE PIPE LINE.
JOINTS FOR EITHER PIPE.
-- 3'
3'
12"
6'
7.
8.
6'
POTABLE WATER
VERTICAL
PROPOSED
SANITARY SEWER
RECLAIMED
FORCE MAIN
WATER
WATER
POTABLE
UTILITY
3'
6'
HORIZONTAL HORIZONTAL
SANITARY SEWER
FORCE MAINRECLAIMED WATER
12"
12"
3'
HORIZONTAL
-- 3'
12"
3'
VERTICAL
12" 6'
SANITARY SEWER
HORIZONTAL
12"
12"
VERTICAL
12" BELOW
3'
12"
6" ABOVE
GRAVITY MAIN
6' **
VERTICAL
3'
STORM SEWER OR
6" ABOVE
12" BELOW
SANITARY SEWER
VERTICAL
VACUUM TYPE
HORIZONTAL
3'
THE FOLLOWING ARE ACCEPTABLE ALTERNATIVE CONSTRUCTION VARIANCES
WHERE IT IS NOT POSSIBLE TO MEET THE SEPARATION REQUIREMENTS, AND
ARE ONLY TO BE IMPLEMENTED UPON RECEIPT OF EXPRESSED WRITTEN
CONSENT FROM THE ENGINEER AND APPROVAL FROM FDEP ON A CASE BY
CASE BASIS. IMPLEMENTATION OF THESE MEASURES WITHOUT THE
EXPRESSED WRITTEN CONSENT OF THE ENGINEER AND APPROVAL BY FDEP
COULD RESULT IN THE REQUIREMENT THAT THE INSTALLED UNAPPROVED
MEASURES BE REMOVED AND REPLACED AT NO COST.
TYPE III SILT FENCE
N.T.S.
6' MAX. SPACING
ELEVATION
RUNOFF
GROUND
UNDISTURBED
3' -0
(M
IN
COMPACTED BACKFILL
(M
IN
4" X 4" TRENCH WITH
6' MAX. SPACING
PONDING HEIGHT
STEEL OR
WOOD POST
FILTER FABRIC ATTACH
SECURELY TO UPSTREAM
SIDE OF POST
PONDING HEIGHT
FILTER FABRIC ATTACH
SECURELY TO UPSTREAM
SIDE OF POST(M
IN
3' -0
RUNOFF
(M
IN
GROUND
UNDISTURBED
STANDARD DETAIL
ALTERNATE DETAIL
9" MAX.
(RECOMMENDED)
STORAGE HT.
8"
TRENCH WITH GRAVEL
TRENCH WITH NATIVE BACKFILL
GRAVEL
NOTE:
1. INSPECT AND REPAIR FENCE AFTER EACH STORM EVENT AND REMOVE SEDIMENT WHEN NECESSARY
2. REMOVED SEDIMENT SHALL BE DEPOSITED TO AN AREA THAT WILL NOT CONTRIBUTE SEDIMENT
OFF-SITE AND CAN BE PERMENTLY STABILIZED
3. SILT FENCE SHALL BE PLACED ON SLOPE CONTOURS TO MAXIMIZE PONDING EFFICIENCY
FINISH GRADE
FLOW
FLOW
FILTER FABRIC
3' O
R M
O R
E
VE
R
TI
C
AL
SEC. 985 FDOT SPEC.)
" M
IN
8"
ELEVATION
" T
O
8"
SECTION
SILT FLOW
6' MAX.
FILTER FABRIC (IN
CONFORMANCE WITH
20°±
20° TOWARD FLOW)
PRINCIPLE POST
POSITION (CANTED
POST (OPTIONS: 2"X4" OR
2 1/2" MIN. DIA. WOOD;
STEEL 1.33 LBS/FT. MIN.)
EXTRA STRENGTH
FILTER FABRIC
NEEDED WITHOUT
WIRE MESH
SUPPORT
COMPACTED
BACKFILL
STEEL OR
WOOD POST
PIPE RESTRAINT FOR PVC PIPE (C-900/C-905 DR 18)
MINIMUM RESTRAINED LENGTH (FT) - EACH SIDE OF FITTING
PIPE SIZE - INCHES
FITTING TYPE 4 6 8 10 12 14 16 18 20 24 30
VERT. UP OR HORIZ
11-1/4 BEND 2 2 3 3 4 4 5 5 6 7 8
22-1/2 BEND 3 4 6 7 8 9 10 11 12 13 16
45 BEND 6 9 11 14 16 18 20 22 24 28 32
90 BEND 15 22 28 33 39 44 49 53 58 67 78
VERTICAL DOWN
11-1/4 BEND 4 5 7 8 9 11 12 13 14 17 20
22-1/2 BEND 7 10 13 16 19 22 24 26 29 33 40
45 BEND 15 22 28 34 39 45 50 55 60 70 83
90 BEND 37 53 68 82 95 109 121 133 146 168 199
BRANCH OF TEE 2 15 29 42 55 73 80 92 104 126 156
DEAD END 37 53 68 82 95 109 121 133 146 168 199
REDUCERS
SIZE 6X4 8X4 8X6 10X6 10X8 12X6 12X8 12X10 14X6 14X8 16X6
RESTR. LENGTH 27 49 29 51 28 71 51 28 89 72 106
SIZE 16X8 16X12 18X8 18X12 18X16 20X12 20X16 24X12 24X16 30X20 30X24
RESTR. LENGTH 91 52 109 74 27 94 52 129 95 112 71
NOTES:
1. INCREASE RESTRAINED LENGTH WHEN TEST PRESSURES EXCEED 100 PSI.
2. RESTRAINED LENGTHS SHOWN ARE BASED ON LAYING CONDITION TYPE 3, AND MINIMUM COVER OF 3 FT.
3. RESTRAINED LENGTH BASED ON SOILS BEING CLASSIFICATION TYPE SAND-SILT, SOIL INT. FRICTION ANGLE =
30, SOIL DENSITY = 90 PCF, TRENCH LAYING CONDITION 3, TRENCH FACTOR =0.60, PIPE TO SOIL INT. FRICTION ANGLE = 0.6, RATIO OF PIPE TO SOIL COHESION = 0. ADJUST RESTRAINED LENGTHS FOR DIFFERENT SOIL TYPES.
4. IN-LINE VALVES ARE TO BE RESTRAINED ON EACH SIDE OF THE VALVE AT THE CONNECTION TO ADJOINING
PIPE.
5. FOR VERTICAL OFFSETS (CROSSINGS) USE THE EQUATION FOR THE VERTICAL DOWN BEND FOR THE UPPER
BEND AND THE EQUATION FOR THE HORIZONTAL BEND FOR THE LOWER BEND.
6. TEE RESTRAINT SHOWN IS FOR NON-REDUCING TEES. FOR REDUCING TEES, THE RESTRAINED LENGTH OF THE BRANCH SHALL BE EITHER THE LENGTH BASED ON THE DIAMETER OF THE RUN OF THE TEE OR THE LENGTH
REQUIRED FOR A REDUCER FITTING, WHICHEVER IS GREATER.
7. AT ALL TEES, THE TOTAL LENGTH BETWEEN THE FIRST JOINTS OR RESTRAINED LENGTH ON EITHER SIDE OF TEE (RUN) SHALL BE A MIN. TOTAL DISTANCE OF 30 FT. SEE THE ABOVE TABLE FOR RESTRAINT LENGTH ON TEE
BRANCH LINE.
8. THE SAFETY FACTOR UTILIZED FOR THE ABOVE TABLE IS 1.5.
CHAIN LINK FENCE DETAIL
NTS
COMPACTED
BACKFILL
Bd
( SEE NOTE 1 )
Bc
COMPACTED
SELECT
MATERIAL
CONCRETE
M
IN
Bc/2
Bc/4
(4" MIN.)
Bc/4 (6" MIN.)
PIPE BELL
CONCRETE CRADLE CONCRETE ARCH
ENCASEMENT
COMPACTED GRANULAR
BEDDING MATERIAL
UNDISTURBED
SOIL
Bc/4 (4" MIN.)
Bc/2
CONCRETE
Bc/4 (6" MIN.)
CL
BRACING
SHEETING
PIPE BELL
COMPACTED BACKFILL
OR OTHER FINISH
SCREENED FINISH
6X6-6/6 W.W.F.
AS
REQUIRED
6" MIN. 12"
MIN.
COMPACTED BACKFILL
AS SPECIFIED FOR
BEDDING TYPE.
Bc
Bd
(SEE NOTE 1)
PROTECTIVE CONCRETE SLAB SHEETED TRENCH
CL
THIS PORTION TO BE
CUT AND REMOVED
12'
MIN.
Bd
(SEE NOTE 1)
Bc
COMPACTED
BACKFILL
COMPACTED
SELECT
MATERIAL
Bc/2
SEE NOTE 2
COMPACTED GRANULAR
BEDDING MATERIAL
NORMAL TRENCH GRANULAR BEDDING
O.6 Bc (TOTAL)
PIPE BELL
UNDISTURBED
SOIL
M
IN
TR
EN
C H
W
AL
LS
AS
V
ER
TI
C
AL
AS
P
O
SS
IB
LE
VE
R
TI
C
AL
TR
EN
C
H W
AL
LS
CL
CLASS "A" BEDDING-SPECIAL CONDITIONS
SPECIAL DETAIL
CLASS "B" BEDDING-NORMAL CONDITIONS
SEM. CO. DEC 2013
BEDDING AND TRENCHING NOTES
1. Bc = PIPE O.D.
Bd = TRENCH WIDTH AT TOP OF PIPE MAX. Bd = Bc + 24" MIN. Bd = MAX. DIM.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .