This is a set of architectural, mechanical, and electrical drawings for an HVAC replacement project at Building #2410 at Joint Base Cape Cod in Sandwich, MA. The drawings detail the removal of an existing 5-ton rooftop unit (RTU-1) and installation of a new Bryant Legacy Line RTU or equivalent with 2000 CFM airflow, 5-ton cooling capacity, and 110 MBH heating input.
The drawings include detailed specifications for the new RTU, including requirements for marine environment-suitable coatings, perfect humidity control dehumidification system, factory-mounted non-fused disconnect switch, MERV 13 filters, and supply air smoke detector with horn/strobe annunciator. The electrical drawings show power connections from Panel-RP to the new unit, requiring removal and replacement of existing conductors and 30A breaker. The mechanical drawings detail the control system requirements, including a smart thermostat/humidistat capable of controlling dehumidification and multiple heating stages. The project requires coordination with an existing fire alarm control panel and maintaining the integrity of the building's EPDM roof system, which is under a 15-year warranty that began in August 2021.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF TRANSPORTATION
HVAC REPLACEMENT PROJECT
BUILDING #2410
JOINT BASE CAPE COD
SOUTH INNER ROAD
SANDWICH, MA 02542
December 5, 2024
OWNER/LESSOR:
Commonwealth of Massachusetts
Executive Office of Public Safety & Security
Military Division
2 Randolph Road
Hanscom AFB Bedford, MA 01731
PROJECT LOCATION
REGIONAL MAP SITE MAP
I SHEET DRAWING NUMBER SHEET NAME
GENERAL
SHEET 01 RTU-1 G-000 COVER SHEET
SHEET02 RTU-1 G-001 ARCH GENERAL NOTES, SYMBOLS, & ABBREVIATIONS
SHEET 03 RTU-1 G-002 DEMOLITION, ELECTRICAL, MECHANICAL GENERAL NOTES, SYMBOLS, & ABBREVIATIONS
ARCHITECTURAL
I SHEET 04 RTU-1 A-101 I ROOF PLAN AND PHOTOS
MECHANICAL
I
SHEET 05 RTU-1 M-101
ELECTRICAL
SHEET 06 RTU-1 E-101
SHEET 07 RTU-1 E-201
I
HVAC FLOOR PLAN
ELECTRICAL FLOOR PLAN
POWER PANEL SCHEDULES
SHEET 01 RTU-1 G-000
ARCHITECTURAL ABBREVIATIONS LIST:
A A F F
ACT ACOUSTIC CEILING TILE FA FIRE ALARM
ADA AMERICANS WITH DISABILITIES ACT FDN FOUNDATION
ADJ ADJUSTABLE FE FIRE EXTINGUISHER
AFF ABOVE FINISH FLOOR FEC FIRE EXTINGUISHER CABINET
AL ALUMINUM FF FINISH FLOOR
ALT ALTERNATE FHC FIRE HOSE CABINET
AP ACCESS PANEL FIN FINISHED
ARCH ARCHITECTURAL FLASH FLASHING
AUTO AUTOMATIC FLEX FLEXIBLE
FLR FLOOR
1! B FLOUR FLUORESCENT
BD BOARD FP FIRE PROOFING
BIT BITUMINOUS FRZ FREEZER
BLDG BUILDING FT FEET,FOOT
BL BLOCKING FURR FURRING
BM BEAM
BR BRICK G G
BSMT BASEMENT GALV GALVANIZED
BTW BETWEEN GB GRAB BAR
GC GENERAL CONTRACTOR
g C GL GLASS
CAB CABINET GRND GROUND
CPT CARPET GWB GYPSUM WALLBOARD
GER CERAMIC GYP GYPSUM
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFOI CONTRACTOR FURNISHED OWNER INSTALLED H H
CG CORNER GUARD HC HANDICAP
CJ CONTROL JOINT HCWD HOLLOW CORE WOOD
CLO CLOSET HDWD HARDWOOD
CLR CLEAR HDWR HARDWARE
CMU CONCRETE MASONRY UNIT HDR HEADER
COL COLUMN HM HOLLOW METAL
COMB COMBUSTIBLE HORZ HORIZONTAL
CON CONDITION HR HOUR
CONG CONCRETE HT HEIGHT
COND CONDUIT HTR HEATER
CONF CONFERENCE HVAC HEATING, VENTILATION, AIR CONDITIONING
CONN CONNECTION HW HOT WATER
CONT CONTINUOUS
CONST CONSTRUCTION I I
GOOD COORDINATE IBC INTERNATIONAL BUILDING CODE
CORR CORRIDOR ID INSIDE DIAMETER
cw COLD WATER IN INCH
INCD INCANDESCENT
D D INCL INCLUDED
DBL DOUBLE INFO INFORMATION
DEG DEGREE INSUL INSULATION
DEMO DEMOLISH INT INTERIOR
DEPT DEPARTMENT
DET DETAIL J J
DF DRINKING FOUNTAIN JAN JANITOR
DIA DIAMETER
DIAG DIAGONAL JS K
DIFF DIFFUSER KD KNOCK DOWN
DIM DIMENSION KO KNOCK OUT
DIR DIRECTOR KP KICK PLATE
DN DOWN
DR DOOR L L
DS DOWNSPOUT LAB LABORATORY
DTFPEPE DESIGN TEAM FIRE PROTECTION ENGINEER LAUN LAUNDRY
PROFESSIONAL ENGINEER LAV LAVATORY
DW DISH WASHER LF LINEAR FEET
DWG DRAWING LIN LINEAR
LT LIGHT
£ E
EA EACH M M
EJ EXPANSION JOINT MAS MASONRY
EL ELEVATION MAT MATERIAL
ELEC ELECTRIC MAX MAXIMUM
ELEV ELEVATOR MDF MEDIUM DENSITY FIBERBOARD
EMG EMERGENCY MDO MEDIUM DENSITY OVERLAY
EMP EMERGENCY POWER MDX MEDIUM DENSITY OVERLAY EXTERIOR GRADE
ENCL ENCLOSED MECH MECHANICAL
EOAE EQUIVALENT OR APPROVED EQUAL
ES EACH SIDE
ETR EXISTING TO REMAIN
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EX EXISTING
EXT EXTERIOR
M M
MFR MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MLDG MOULDING
MLWK MILLWORK
MO MASONRY OPENING
MOD MODULAR
MT MOUNT
MTD MOUNTED
MTL METAL
MUL MULLION
� N
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
Q Q
QA OVERALL
OAE OR APPROVED EQUAL
oc ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED OWNER INSTALLED
OH OPPOSITE HAND
OPP OPPOSITE
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PED PEDESTAL
PERF PERFORATED
PER PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PG PLATE GLASS
PH PHASE
PL PLATE
P-LAM PLASTIC LAMINATE
PLWD PLYWOOD
PNL PANEL
POL POLISHED
PORT PORTABLE
PRNT PRINTER
PROJ PROJECT
PROP PROPERTIES
PT PRESSURE TREATED
PTD PAINTED
PTW PRESSURE TREATED WOOD
PAV PAVEMENT
PWR POWER
Q Q
QT QUARRY TILE
QTR QUARTER
QUAN QUANTITY
R R
R RADIUS
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RECP RECEPTION
RECT RECTANGULAR
RECV RECEIVING
REQ REQUIRED
RES RESILIENT
RET RETURN
REV REVISION
RFPE REGIONAL FIRE PROTECTION ENGINEER
RM ROOM
RND ROUND
RO ROUGH OPENING
RTU ROOF TOP UNIT
s
SAN
SB
SC
SCHED
SD
SDT
SECT
SF
SGPL
SHEA
SHT
SI
SIM
SPEC
SPK
SPC
SQ
ss
STD
STL
STOR
STR
STRUC
SUP
SURF
sv
SYM
SYN
T i'1 T2
TF
TBD
TEL
TEMP
T&G
TO
TOIL
TOL
TRD
TWS
TYP
u
UBC
LION
U.S.
V
VP
VAR
VB
VCT
VERT
VEST
VIF
w
WI
W/O
WD
WDC
W/D
WIN
WG
WH
WK
s
SANITARY
BACKPAINTED SPANDREL INSULATING GLASS
SOLID CORE
SCHEDULE
SOAP DISPENSER
STATIC DISSIPATIVE TILE
SECTION
SQUARE FEET
STRUCTURAL GRADE PLASTIC LUMBER
SHEATHING
SHEET
SPANDREL INSULATING GLASS
SIMILAR
SPECIFICATION
SPEAKER
SPECIAL
SQUARE
STAINLESS STEEL
STANDARD
STEEL
STORAGE
STRAIGHT
STRUCTURAL
SUPPORT
SURFACE
SHEET VINYL
SYMMETRICAL
SYNTHETIC
T
TEMPERED GLASS
TEMPERED INSULATING GLASS
TEMPERED INSULATING W/ APPLIED FILM
TO BE DETERMINED
TELEPHONE
TEMPORARY
TONGUE AND GROOVE
TOP OF
TOILET
TOLERANCE
TREAD
TEACHER WORK STATION
TYPICAL
u
UNIFORM BUILDING CODE
UNLESS OTHERWISE NOTED
UNDERSIDE OF STRUCTURE
V
VAPOR
VARIABLE
VINYL BASE
VINYL COMPOSITE TILE
VERTICAL
VESTIBULE
VERIFY IN FIELD
w
WITH
WITHOUT
WOOD
WOOD WI COPPER CLADDING
WASHER/DRYER
WINDOW
WIRE GLASS
WATER HEATER
WORK
SYMBOL LEGEND
X'-X"
X'-X"
1 � l X--X"
OFFICE
1214 I
XXSF
it 0-
M\ SYMBOLS LEGEND
'-V 1/8" = 1'-0"
LIFE SAFETY CODE SUMMARY:
DIMENSION LINE
ROOM DESIGNATION
ROOM NUMBER
SQUARE FOOTAGE (IF USED)
DOOR AND DOOR
TAG
PARTITION TAG
BREAK MARK
NORTH ARROW
I STORAGE MECHANICAL RM
I
�--�v1
ELECTRICAL RM
I 6 I
17\ LIFE SAFETY PLAN
� 1/8" = 1'-0"
II
EQUIPMENT RM
45•· 73' =� L
- - - -' ....L._ - ""I b-
I I
, , , , SHOWER ROOM �
I 4 I �
I I I I I I
L------------..JI
I I I
OFFICE
r- ... � I
--------------- ______ _J
BATHROOM
X X X X X X X a.. - -JX X X X X X X X X X X X ; X X X X X X X X X X X X
LIFE SAFETY PLAN LEGEND:
ILLUMINATED CEILING MOUNTED EXIT SIGN
► - ► PATH OF EGRESS
2018 IBC - ICC INTERNATIONAL CODE
(CONSTRUCTION TYPE - 28)
ADAAG - ADA ACCESSIBILITY GUIDELINES
NFPA 101, 2015, NFPA 72 - 2015, NFPA 13 -2015
BUILDING OCCUPANCY PER IBC
SCOPE OF WORK FLOOR AREA
BUSINESS
REQUIRED RATING
OCCUPANT LOAD FACTOR
BUSINESS
OCCUPANT LOAD
BUSINESS
EXITS REQUIRED
BUSINESS
MAX. ALLOWABLE TRAVEL DISTANCE SHALL
NOT EXCEED 200' (WITHOUT SPRINKLER SYSTEM)
MAXIMUM ALLOWABLE DEAD END
MAXIMUM ALLOWABLE COMMON
PATH OF TRAVEL
MAXIMUM ALLOWABLE TRAVEL DISTANCE
BUSINESS GROUP B
2,730 SF
100 SF/PERSON
FLOOR AREA
100 GROSS =
MINIMUM
50'
MAXIMUM
100'
250'
OCCUPANT
ACTUAL
ACTUAL
33'
84' f 1 PLAN DETAIL TAG l j---
SECTION CUT TAG
X:E:
ELEVATION/DETAIL
TITLE REFERENCE
X
ELEVATION DESIGNATION
COLUMN DESIGNATION
GRID LINE
GENERAL NOTES:
AS USED IN THESE CONTRACT DOCUMENTS:
"FURNISH" MEANS TO PURCHASE AND DELIVER
TO THE PROJECT SITE COMPLETE WITH
NECESSARY APPURTENANCE,
"INSTALL" MEANS TO UNLOAD AT THE DELIVERY
POINT AT THE SITE AND PERFORM EVERY
OPERATION NECESSARY TO ESTABLISH SECURE
MOUNTING AND CORRECT OPERATION AT THE
PROPER LOCATION IN THE PROJECT.
"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."
USDOTNOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
AREAS
No. Description Date
DOT REDESIGN OF
BUILDING #2410
JOINT BASE CAPE COD
SANDWICH, MA
ARCH GENERAL
NOTES, SYMBOLS, &
ABBRV.
SHEET 02
Submission
Project number
Date
100% WORKING DOCUMENTS
December 5, 2024 Drawn by
Checked by
RTU-1 G-001
Scale As indicated
I
GENERAL DEMOLITION NOTES:
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ADHERE TO THE FOLLOWING:
1. DO NOT CLOSE OR OBSTRUCT THE PATH OF EGRESS, CORRIDORS, OR OTHER OCCUPIED OR USED SPACES OR FACILITIES WITHOUT THE WRITTEN PERMISSION OF THE OWNER IF NECESSARY PROVIDE TEMPORARY UTILITIES. PRIOR TO OBSTRUCTION OF EGRESS PATHS OR IMPAIRMENT OF FIRE/LIFE SAFETY COMPONENTS, THE NFPA 241 AND IMPAIRMENTS PLANS MUST BE SUBMITTED FOR APPROVAL BY DESIGN TEAM FIRE PROTECTION ENGINEER WHO IS LICENSED PROFESSIONAL ENGINEER (IN FIRE
PROTECTION ENGINEERING) (DTFPEPE).
2. CEASE OPERATION IF PUBLIC SAFETY OR REMAINING STRUCTURES ARE ENDANGERED. PERFORM TEMPORARY CORRECTIVE MEASURES UNTIL OPERATIONS CAN BE
CONTINUED PROPERLY.
3. IN COMPANY OF THE ARCHITECT AND OWNER, THE CONTRACTOR WILL VISIT THE SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE DEMOLITION REQUIRED PRIOR TO STARTING THE WORK. CAREFULLY IDENTIFY THE LIMITS OF SELECTIVE DEMOLITION. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE THE WORKMEN TO ALSO IDENTIFY THE ITEMS TO BE REMOVED AND STORED, AS WELL AS THE ITEMS TO BE LEFT IN PLACE INTACT.
4. USE MEANS NECESSARY TO PREVENT DUST FROM BECOMING A NUISANCE TO THE PUBLIC, NEIGHBORING BUILDINGS, AND TO ANY OTHER WORK BEING PERFORMED.
5. EXECUTE DEMOLITION WORK TO ENSURE THE SAFETY OF PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE BY DEBRIS. CONTRACTOR WILL TAKE PROTECTIVE
MEASURES TO PREVENT DUST FROM GETTING INTO DUCTS.
6. IN THE EVENT OF DEMOLITION OF ITEMS NOT SCHEDULED TO BE DEMOLISHED, PROMPTLY REPLACE SUCH ITEMS TO THE APPROVAL OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO EXISTING FEATURES AS A RESULT OF THIS WORK.
DAMAGED ITEMS SHALL BE REPLACED IN KIND AND AT NO ADDITIONAL COST TO THE OWNER.
7. SHORE, BRACE AND SUPPORT EXISTING CONDITIONS AS REQUIRED FOR REMOVAL OF EXISTING CONSTRUCTION OR INSTALLATION OF THE NEW WORK.
8. COORDINATE THE REMOVAL, RELOCATION, REPLACEMENT, RE-USE, SHUT-OFF, STUB-OFF, CAPPING-OFF OR UPGRADING OF ALL EXISTING PLUMBING, HVAC, ELECTRICAL SYSTEMS, AND TELECOM SYSTEMS EQUIPMENT, AND APPURTENANCES - INCLUDING, BUT NOT LIMITED TO , UTILITY LINES, DUCTS, CONNECTIONS, PANELS, VENTS, FANS, ELECTRICAL BASEBOARD HEAT, PIPING, DEVICES, CONTROLS, SWITCHES, OUTLETS, AND CONDUIT DURING THE CONSTRUCTION AS REQUIRED, AS SCHEDULED OR AS
SPECIFIED IN ACCORDANCE WITH ALL LOCAL, MUNICIPAL, STATE CODES.
9. THE CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF ANY HAZARDOUS MATERIALS AND IN DOING SO SHALL COMPLY WITH ALL APPLICABLE OSHA REGULATIONS AND ALL OTHER FEDERAL, STATE AND LOCAL GUIDELINES REGARDING ASBESTOS-CONTAINING MATERIAL REMOVAL AND DISPOSAL.
10. OWNER AND ARCHITECT SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES FOR SAFETY PRECAUTIONS OR FOR THE CONTRACTORS FAILURE TO CARRY OUT THE WORK IN STRICT ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. OWNER SHALL NOT BE RESPONSIBLE FOR ERRORS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR THEIR AGENTS OR EMPLOYEES OR ANY OTHER PERSONS PERFORMING ANY OF
THE WORK.
11. THE CONTRACTOR SHALL COORDINATE ALL ABOVE CEILING MEP AND STRUCTURAL ELEMENTS PRIOR TO DEMOLITION OF WALLS AND/OR CEILING. CONTRACTOR IS ULTIMATELY RESPONSIBLE FOR FIRE SAFETY DURING PROJECT BEING IN COMPLIANCE WITH IBC, IFC AND NFPA 241.
12. COORDINATE, TERMINATE, AND RELOCATE ALL WALL & CEILING ELECTRICAL (TELECOM/POWER OUTLETS, SWITCHING, THERMOSTAT, ETC.) DEVICES THAT ARE LOCATED ON WALLS & CEILINGS SCHEDULED FOR REMOVAL. GC TO V.I.F. PRIOR TO THE COMMENCEMENT OF WORK. DISCONNECT AND MAKE SAFE EXISTING ELECTRICAL
COMPONENTS TO BE REMOVED.
13. REPAIR, AND LEVEL FLOORING TO MEET MANUFACTURER'S REQUIREMENTS OF THE NEW FLOORING AND WALL MATERIALS AS SPECIFIED. IT IS THE RESPONSIBILITY OF THE GC TO FINISH ALL UNEVEN SURFACES OR PATCH ALL CONCAVE FLOORING TO A LEVEL SURFACE REGARDLESS OF FLOORING UNEVENNESS.
14. PATCH ALL EXISTING WALLS ADJACENT TO ALL WALLS SCHEDULED FOR REMOVAL. PATCHWORK WILL BE CONSISTENT WITH THE WALL RATING.
15. SUBMIT DEMOLITION SCHEDULE FOR APPROVAL INCLUDING SCHEDULE AND METHODS OF CAPPING AND CONTINUING UTILITY SERVICE.
16. THE CONTRACTOR SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS AND 29 CFR 1910.34, COVERAGE AND DEFINITIONS, 29 CFR 1910-35, COMPLIANCE WITH NFPA 101, LIFE SAFETY CODE, 29 CFR 1910-36, DESIGN AND CONSTRUCTION REQUIREMENTS FOR EXIT ROUTES, 29 CFR 1910-37, MAINTENANCE, SAFEGUARDS, AND OPERATIONAL FEATURES FOR EXIT ROUTES.
18. ALL FIRE ALARM NOTIFICATION DEVICES, EXIT SIGNAGE, HEAT DETECTORS, AND EMERGENCY LIGHTING TO REMAIN OPERATIONAL DURING DEMOLITION AND CONSTRUCTION UNTIL WHICH POINT THAT NEW FIRE ALARM SPEAKER STROBE DEVICES ARE READY TO BE INSTALLED AND ACTIVATED.
19. PROTECT ALL EXISTING BUILDING FINISHES AS WORK IS ONGOING.
GENERAL DUST CONTROL
PROVISIONS:
THE GC SHALL PROVIDE DAILY REMOVAL OF ALL DEMOLITION DEBRIS. DO NOT STORE ANY DEMOLITION DEBRIS ON THE FLOOR
OVERNIGHT.
THE GC SHALL MAINTAIN A CLEAN AND SAFE WORK AREA THROUGHOUT THE PERIOD OF DEMOLITION. THE GC SHALL, AT THE END OF EACH WORK DAY, REMOVE ALL DEMOLITION DEBRIS AND HAZARDOUS AND POTENTIALLY DANGEROUS MATERIALS USED IN THE
WORK.
THE GC SHALL CLEAN THE EXTERIOR AREAS IMPACTED BY CONSTRUCTION DUST, DIRT AND DEBRIS ON A DAILY BASIS. THE GC SHALL
BE RESPONSIBLE FOR ALL FEES, PERMITS, ETC., REQUIRED FOR WASTE DISPOSAL.
GENERAL NOTES:
AS USED IN THESE CONTRACT DOCUMENTS:
"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY APPURTENANCE, "INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT
OPERATION AT THE PROPER LOCATION IN THE PROJECT.
"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."
MECHANICAL GRAPHIC SYMBOLS
® EQUIPMENT DESIGNATION
SECTION REFERENCES
◊ KEYED NOTE SYMBOL
EB INDICATES POINT OF CONNECTION
BETWEEN NEW AND EXISTING
� AIR DEVICE TAG550 (SEE SCHEDULE)
CFM
@) THERMOSTAT/HUMIDISTAT I
NOTE: NOT ALL SYMBOLS ARE
USED IN THIS PROJECT
[><I SUPPLY DUCT
l�I RETURN OR OUTSIDE AIR DUCT l�I EXHAUST DUCT
� f CEILING AIR DEVICE f SIDEWALL AIR DEVICE I I I
I f
DUCTWORK �IRST FIGURE IS SIDE SHOWN)
I [ I
MANUAL VOLUME DAMPER 12X6 (RECTA GULAR DUCTWORK)
12X6 12"0 (ROUND DUCTWORK) (BD = BACKDRAFT DAMPER)
I
I I DUCT DIMENSIONS ARE INSIDE CLEAR
m
FLEXIBLE DUCTWORK
f f f I
MOTORIZED DAMPER
11111 FLEXIBLE DUCT CONNECTION I
f I I I
♦ so
FD FIRE DAMPER
SD SMOKE DAMPER
I I FS COMBINATION FIRE & SMOKE DAMPER
ELECTRICAL GENERAL NOTES:
1. IN GENERAL, CONDUIT ROUTING SHOWN ON THE DRAWINGS IS DIAGRAMMATIC. ACTUAL CONDUIT ROUTING
SHALL BE DETERMINED IN THE FIELD.
2. PENETRATIONS OF CONDUITS, RACEWAYS AND WIRING THROUGH FIRE RATED WALLS AND CEILING SHALL BE FIRE STOPPED USING A FIRE STOPPING U.L. LISTED ASSEMBLY BY A CERTIFIED INSTALLER SO AS TO MAINTAIN THE
UL RATING OF THE ASSEMBLY.
AS USED IN THESE CONTRACT DOCUMENTS:
"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY
APPURTENANCE,
3. AS USED IN THESE CONTRACT DOCUMENTS:
"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY
APPURTENANCE,
"INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT.
"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."
GFI
8=
[j 30/3
15AF
cp
[I]
POWER
DUPLEX RECEPTACLE - 15" TO CENTER AFF UNLESS OTHERWISE NOTED
GFI = GROUND FAULT CIRCUIT INTERRUPTING
D = DEDICATED CIRCUIT
EWC = GFI FOR ELECTRIC WATER COOLER
1V = TELEVISION, 80" TO CENTER AFF
COUNTERTOP DUPLEX RECEPTACLE - OR MOUNTED AT 44" AFF WHERE NO
COUNTER EXISTS
DOUBLE DUPLEX RECEPTACLE - 15" AFF UNLESS OTHERWISE NOTED
SPECIAL PURPOSE OUTLET - 18" AFF UNLESS OTHERWISE NOTED
MOTOR
DISCONNECT SWITCH - 30/3 = SWITCH AMPS/POLES,
15AF = 15 AMP FUSE
JUNCTION BOX - # INDICATES CIRCUIT
BRANCH CIRCUIT PANELBOARD
DISTRIBUTION PANELBOARD
FUSIBLE COMBINATION FVNR MOTOR STARTER
GROUND BAR WITH INSULATED SPACERS. GROUND BAR SHALL BE 1/4"X2"X12''
COPPER MINIMUM WITH NEMA TWO HOLE LUG SPACING. INSTALL AT 24" ABOVE
FLOOR. SEE DETAIL ON SHEET E-501.
SINGLE RECEPTACLE UNDER SINK FOR GARBAGE DISPOSAL
DRY TYPE TRANSFORMER
CONDUIT
� CONDUIT AND WIRING HOMERUN.
� SHORT STROKE INDICATES PHASE CONDUCTOR.
� LONG STROKE INDICATES NEUTRAL CONDUCTOR.
LONG STROKE WITH DOT INDICATES EQUIPMENT GROUND CONDUCTOR.
MISCELLANEOUS
�1u '\J7 EQUIPMENT DESIGNATION
0--. KEYED NOTE
OFFICE ---- ROOM
DI]...______ROOM
NAME
NUMBER
AFF
FMCP
FVNR
1V
ABBREVIATIONS
ABOVE FINISHED FLOOR
FIRE ALARM MASS NOTIFICATION CONTROL PANEL
FULL VOLTAGE NON-REVERSING
TELEVISION
No.
USDOTNOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
Description Date
DOT REDESIGN OF
BUILDING #2410
JOINT BASE CAPE COD
SANDWICH, MA
DEMOLITION,
ELECTRICAL, &
MECHANICAL NOTES,
SYMBOLS, & ABBREV
SHEET 03
Submission 100% WORKING DOCUMENTS Project number
Date December 5, 2024 Drawn by
Checked by
RTU-1 G-002
Scale 1/8" = 1 '-0"
I�
0 z
IF NECESSARY, REMOVE & REPLACE
SURROUNDING WALKPADS TO
ACCOMODATE RTU-1 INSTALLATION
REMOVE EXISTING 5-TON ROOFTOP UNIT (RTU-1)
IF NECESSARY, PROVIDE NEW CURB ADAPTOR TO ACCOMMODATE NEW RTU-1 DIMENSIONS.
FIELD VERIFY ALL DUCTWORK RISER DIMENSIONS AND PROVIDE DUCTWORK EXTENSIONS TO
ACCOMODATE NEW RTU1.
�--- (SEE NOTE 1)
0 ���� .. �
��N - DEMOLITION PLAN
LEGEND
0 EXISTING VENT PIPE
I 6 I EXISITING GAS SUPPLY LINE
EXISTING ROOF WALKWAY
PROTECTION PAD/MEMBRANE
36" WIDE
I I I I I I I
EXISTING STEEL
ROOF ACCESS STAIRWAY
NOTES:
w0..
..J
1) THE EXISTING ROOF IS AN ETHYLENE PROPYLENE DIENE MEMBRANE (EPDM) ROOF.
15YR MANUF WARRANTY: FIRESTONE BUILDING PRODUCTS
WARRANTY START DATE: 08/03/2021
INSTALLER: TECH ROOFING, INC. CHICOPEE, MA
2) AS USED IN THESE CONTRACT DOCUMENTS:
"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY APPURTENANCE, "INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT.
"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."
0���STING CURB EXPOSED DURING ROOF INSTALL
PROVIDE NEW RTU-1
IF THE ROOF CURB NEEDS TO BE REPLACED TO ACCOMODATE NEW RTU1 INSTALLATION,
PROVIDE MANUFACTURER'S ROOF CURB INSTALLED WITH FIRESTONE (EPDM) ROOFING BY A
FIRESTONE FACTORY CERTIFIED INSTALLER. ANY ROOFING REPAIR DUE TO RTU1 INSTALLATION
SHALL BE CERTIFIED BY A FIRESTONE BUILDING PRODUCTS REPRESENTATIVE ON SITE
INSPECTION. REFERENCE THE FIRESTONE 15YR WARRANTY.
I I I I I I I
� . :=-:,..,1:;-
. �·ii]iiti t:f :���,.-
No.
USDOTNOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
Description
DOT REDESIGN OF
B
Date
BUILDING #2410
JOINT BASE CAPE COD
SANDWICH, MA
ROOF PLAN &
PHOTOS
SHEET 04
Submission 100% WORKING DOCUMENTS
Project number 147001.00
Date December 5, 2024
Drawn by
Checked by
RTU-1 A-101
Scale
I� z
STORAGE
�---v1
II
J
ELECTRICAL RM
I 6
MECHANICAL RM
3 DATA CABLING FROM THE FACP HAS BEEN
INSTALLED BY OTHERS AND EXCESS
CABLING IS AVAILABLE AT EXISTING J-BOX
TO BE PULLED TO RTU1.
I < b-
SHOWER ROOM
:-;;s:_75:.....���
!:I
_..--- PROVIDE NEW SMART
THERMOSTAT/HUMIDISTAT BY
ECOBBEE, OR EQUAL.
PROVIDE CONDUIT FROM THE EXISTING JBOX TO RTU1 CONTROL UNIT. ROUTE THE EXISTING EXCESS FACP CABLING
THROUGH THE NEW CONDUIT.
A) PROVIDE TERMINATIONS OF THE FACP DATA CABLES ONTO RTU-1 CONTROL MODULE "SMOKE" TERMINAL TO
RECEIVE "GENERAL" ALARM SIGNAL TO INITIATE RTU-1 SHUTDOWN.
B) PROVIDE TERMINATIONS OF THE FACP DATA CABLES ONTO RTU1 CONTROL MODULE "ALARM" TERMINAL TO SEND A SIGNAL TO THE FACP THAT THE FACTORY FURNISH RTU1 SMOKE DETECTOR IS IN ALARM. THIS WILL INITIATE
THE FACP TO NOTIFY THE FIRE DEPT.
EQUIPMENT RM
PROVIDE RTU-1 CONTROL MODULE AND
,,,------CONNECT TO FACP CABLES. (TERMINATIONS
IN FACP SHALL BE MADE BY OTHERS)
HVAC
ZONE 1
XX XX XX X 3L-;;uJQQGGK::K::IS.S�Z::::Z::::Z::::X:::::::==xxxxx:x::x::x::x:::z:::z:::z=:i;;
BATHROOM
LOCATION OF EXISTING
FIRE ALARM CONTROL PANEL (FACP)
& FIRE ALARM RADIO BOX
CD CONTROL SYSTEM: NEW HVAC THERMOSTAT & HVAC ZONE PLAN
1/8" = 1'-0"
/ II
PROVIDE FACTORY FURNISHED RTU1 SUPPLY AIR
SMOKE DETECTOR
OFFICE
© EXISTING DUCTWORK - FACING NORTH
NTS
® EXISTING DUCTWORK - FACING SOUTH
5 NTS
GENERAL NOTES:
1. THE HVAC SYSTEM IS A ROOF TOP UNIT. THE UNIT IS A DX SYSTEM WITH GAS HEAT (RTU-1) ON A FACTORY CURB.
2. THE RTU CONTROL UNIT SHALL POLL ONE (1) THERMOSTATIHUMIDISTATS ON THE SYSTEM AND OPERATE THE HVAC SYSTEM IN THE
APPROPRIATE MODE OF OPERATION (SEE SEQUENCE OF OPERATION)
3. THE HVAC CONTROL SYSTEM SHALL BE CAPABLE OF AUTOMATIC SYSTEM STARTUP BASED ON OPTIMAL START, NIGHT SETUP, TIME
SCHEDULE, RESTART FOLLOWING A FIRE ALARM, OR RESTART FOLLOWING A POWER FAILURE.
OCCUPIED MODE (0500 TO 1700 HOURS-WEEKDAYS)
1. OCCUPIED ROOM COOLING SET POINT FOR SUMMER MONTHS SHALL BE 75'F (ADJ), HEATING SET POINT SHALL BE 68'F (ADJ).
2. IN OCCUPIED MODE, THE RTU-1 SHALL OPERATE CONTINUOUSLY TO SATISFY THE THERMOSTAT/HUMIDISTAT SETPOINT.
3. UPON START-UP, THE CONTROL SYSTEM WILL OPEN THE OUTSIDE AIR DAMPER TO ALLOW THE REQUIRED OUTSIDE AIR FLOW
INTO THE SPACE.
II
K [> C> C>
EXISTING VOLUME CONTROL DAMPERS (TYP OF 6)
BALANCE THE SYSTEM TO CFM.
FIELD VERIFY ALL DUCTWORK RISER DIMENSIONS AND PROVIDE VERTICAL DUCTWORK
EXTENSIONS TO ACCOMODATE NEW RTU-1 AS NEEDED.
4. WHEN THE SPACE TEMPERATURE GOES ABOVE 75'F (ADJ), THE SYSTEM SHALL CYCLE TO COOLING.
5. IN COOLING MODE, THE SYSTEM SHALL OPERATE TO MAINTAIN THE HUMIDITY LEVEL AT OR BELOW 50%. IF SPACE TEMPERATURE
IS SATISFIED BUT HUMIDITY IS ABOVE 50%, THE PERFECT HUMIDITY ™ CONTROL SHALL ENERGIZE TO PROVIDE DEHUMIDIFICATION FUNCTION. THE PERFECT HUMIDITY'" CONTROL SHALL REMAIN ENERGIZED UNTIL THE SPACE HUMIDITY IS AT 50% OR BELOW.R
K K
R K K K K K K
R K V
® EXISTING MECHANICAL FLOOR PLAN
1/8" = 1'-0"
I
I
,,.,,,. RSruR MR"' '" ro ,ru
)",; ; -'0"x13" ,UPPL, AIR Rli ER FRCM RTU I/ I i---k k K k k K k
X X
P<==-� I
�/ cS<==
UNOCCUPIED MODE
1. UNOCCUPIED HEATING SET POINT SHALL BE 55'F (ADJ).
2. UNOCCUPIED COOLING SET POINT SHALL BE 85'F (ADJ).
3. IN UNOCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED.
4. IN UNOCCUPIED MODE, THE SYSTEM SHALL RUN INTERMITTENTLY TO SATISFY THE THERMOSTAT SET POINTS FOR THE BUILDING.
ALARMS AND SAFETIES
1. THE FACTORY SUPPLIED CONTROLS SHALL HAVE INTEGRATED OUTPUT ALARMS.
2. THE CONTROL SYSTEM SHALL ALARM ON HIGH SPACE TEMPERATURE 90"F (ADJ); LOW SPACE TEMPERATURE 40°F (ADJ); AND
HIGH SPACE HUMIDITY 65% (ADJ); RESPECTIVELY.
1-----------------------------------------------------------------------------------------------------------------------------------------------------------------------
3. THE CONTROL SYSTEM SHALL INITIATE AN ALARM ON HIGH FILTER DIFFERENTIAL PRESSURE.
4. UPON INITIATION OF THE SUPPLY AIR SMOKE DETECTOR, THE HVAC SYSTEM SHALL DEENERGIZE AND THE RTU1 HORN/STROBE
ANNUNCIATOR ACTIVATED.
5. UPON INITIATION OF THE SUPPLY AIR SMOKE DETECTOR, THE OUTSIDE AIR DAMPER SHALL CLOSE.
6. UPON INITIATION OF THE SUPPLY AIR SMOKE DETECTOR RTU1 CONTROL BOARD SHALL SEND A SIGNAL TO THE FACP. THE FACP
WILL INITIATE A GENERAL ALARM AND NOTIFY THE FIRE DEPT.
TO RTU-1
CONTROL PANEL ill C, STATUS/FAILURE ALARM
RTU-1 FACTORY SUPPLIED
CONTROL MODULE
COOLING COIL
n
L - - - - --•--.
FAN
DRIVE
STATUS/FAILURE
ALARM
GAS HEAT
T
SUPPLY
AIR TEMP
TEMP/HUMIDITY INPUT FROM ZONE 1 SMART SENSOR.
NOTIFICATION OF ROOM LOW TEMP & HIGH HUMIDITY
SHALL BE TRANSMITTED TO CELL PHONES
M"\ NOTIONAL CONTROL SYSTEM SCHEMATIC (RTU-1)
'-VNTS
EXISTING DUCT SMOKE
DETECTOR (SENSOR 3-1)
BY OTHERS
="""""'�""9
ALARM RADIO BOX IN-DUCT SMOKE
(terminal #6 is available DETECTOR for use to broadcast INDICATOR low temp alarm to Fire PANEL Dept)
EXISTING FIRE ALARM
CONTROL PANEL (FACP)
(to signal RTU-1 of alarm condition)
GENERAL NOTES:
AS USED IN THESE CONTRACT DOCUMENTS:
"FURNISH"' MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY APPURTENANCE, "INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT
OPERATION AT THE PROPER LOCATION IN THE PROJECT.
"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."
LEGEND:
REGISTER, GRILL, AND DIFFUSER SCHEDULE
SUPPLY DIFFUSERS
1 ,-.IR DEVICE TAG 550
(SEE SCHEDULE) PLAN/
MARK MANUF/ MODEL NECK SIZE (IN) FACE SIZE MOUNT MATERIAL ACCESSORIES FINISH TYPE
CFM S-2 TITUS/S300FL 6" (HEIGHT) DUCT AL VC BWE NOTE 1
@ THERMOSTAT/HUMIDISTAT
MOUNTING
DUCT - DUCT MOUNTED
MATERIAL
AL - ALUMINUM
.E!!:!!filj
BWE - BAKED WHITE ENAMEL
TYPE
ACCESSORIES
VC - VOLUME CONTROL DAMPER
NOTE 1: PROVIDE WITH OPTIONAL AIR SCOOP DAMPER
ROOF TOP UNIT SCHEDULE
GAS PRESSURE ELECTRICAL
TAG MAKE MODEL AIRFLOW
(CFM)
COOLING
CAPACITY
(TONS)
HEATING
input
(MBH)
REFRIG. MOTOR GAS (IN WC)
INLET 1--�--+----�-�--�-�----l(HP) (IN)
BASIS
OF
DESIGN
EXISTING
TO BE
REPLACED
NOTES
RTU-1 BRYANT
RTU-1 BRYANT
LEGACY LINE
582LP06B111Q2A5MA
580FPV060115GA
2000 5 110 R-454B
2000 5 115 R-410A
0.75 1/2
0.75 1/2
MIN MAX
4 13
4 13
VOLTAGE
208/230
208/230
PH AMPS
3 50
3 30
MCA
1. BASIS OF DESIGN IS BRYANT LEGACY LINE (OR EQUAL). PROVIDE WITH ALL ACCESSORIES AND APPURTENANCES TO ENSURE A FULLY OPERATIONAL SYSTEM.
2. GAS HEATING SECTION SHALL BE STAINLESS STEEL HEAT EXCHANGER.
3. UNIT SHALL BE DOWNFLOW, VERTICAL SUPPLYNERTICAL RETURN. STANDARD/MEDIUM STATIC PRESSURE.
4. PROVIDE WITH FACTORY CONTROL BOARD.
5. PROVIDE "SMARl PHONE" CONTROLABLE THERMOSTAT/HUMIDITY SENSOR CAPABLE OF ENERGIZING CONTROL BOARD TERMINALS FOR DEHUMIDIFICATION, 1 STAGE OF COOLING, 2 DIFFERENT STAGES OF HEATING. PROVIDE DATA CABLING
TO/FROM THE WALL SENSOR & RTU-1 CONTROL BOARD.
6. PROVIDE WITH THROUGH BASE ELECTRICAL WITH FACTORY NON-FUSED DISCONNECT SWITCH. EXISTING 1" GAS SUPPLY PIPING IS EXTERIOR ON THE ROOF.
7. PROVIDE CONTROL BOARD CAPABILITY TO RECEIVE ALARM SIGNAL FROM THE EXISTING FIRE ALARM CONTROL PANEL (FACP). PROVIDE CONTROL BOARD CAPABILITY TO SEND A SMOKE ALARM SIGNAL TO FACP.
1. PROVIDE OUTDOOR & INDOOR Al/Cu COIL E-COAT Tw SUITABLE FOR OPERATION IN MARINE (SALT/AIR) ENVIRONMENT. PROVIDE CONDENSER COIL LOUVERED HAIL GUARD.
2. PROVIDE WITH ONE-STAGE COOLING AND PERFECT HUMIDITY ™ CONTROL DEHUMIDIFICATION SYSTEM.
3. PROVIDE WITH UNIT MOUNTED NON FUSED DISCONNECT SWITCH. PROVIDE WITH POWERED CONVENIENCE RECEPTACLE.
4. PROVIDE WITH FAN FILTER STATUS SWITCH & MAINTENANCE INDICATOR. PROVIDE WITH TWO 2" MERV 13 THROWAWAY TYPE FILTERS.
5. PROVIDE WITH MANUAL OUTSIDE AIR DAMPER (0 to 25%).
6. PROVIDE WITH SUPPLY AIR SMOKE DETECTOR. PROVIDE WITH HORN/STROBE ANNUNCIATOR.
MOP
EER
11.0
11.0
SEER FILTER WEIGHT
(LBS)
14.0 2" 600
10.0 2" 505
NOTES
Including Notes & Accessories listed below
USDOTNOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
���1//�,0� w_),; � AREA B
No. Description Date
DOT REDESIGN OF
BUILDING #2410
JOINT BASE CAPE COD
SANDWICH, MA
HVAC FLOOR PLAN
SHEET 05
Submission 100% WORKING DOCUMENTS Project number
Date December 5, 2024 Drawn by
Checked by
RTU-1 M-101 -
Scale As indicated
ACCESSORIES:
PANEL -MDP
/ 71
/ II
PANEL-RP _ _,,,
J
RE-USE EXISTING 2" C AND 6X6X6 J-BOX
FOR HOMERUN FROM PNL -RP TO RTU-1
J /
I I
I 111 /\ JI I
t.J ./ '-- [J
REMOVE EXISTING 1" C FROM 6X6X4 J-BOX TO 4½ X 4½ X 2 J-BOX
FOR HOMERUN FROM PNL -RP TO RTU-1.
PROVIDE 1 ½"C TO REPLACE THIS CONDUIT SECTION.
GENERAL NOTES:
1. SEE THE MECHANICAL SHEETS FOR EXACT EQUIPMENT LOCATIONS
GENERAL NOTES:
AS USED IN THESE CONTRACT DOCUMENTS:
REMOVE ALL EXISTING RTU-1 DISC SWITCHES AND ELECTRICAL APPUTERENANCES.
REMOVE & REPLACE EXISTING RTU-1 HOMERUN CONDUCTORS AND 30A BREAKER FROM PNL-RP CRKT 38-40-42 PROVIDE NEW CONDUCTORS AND 3-POLE BREAKER SIZED ACCORDINGLY. PNL-RP SPACE 7-9-11 IS RESERVED FOR
THE NEW RTU-1 POWER FEED.
(NOTE: MOST OF THE EXISTING CONDUIT AND J-BOXES CAN BE RE-USED)
PROVIDE DISC. SW
FROM MANUF
INTEGRAL WITH RTU-1
PROVIDE NEW 1½" C
FROM EXISTING J-BOX
TO NEW RTU-1
J
PROVIDE GFCI RECEPTACLE
FROM MANUF
INTEGRAL WITH RTU-1.
ABANDONED 2" CONDUIT
RE-USE EXISTING 4½ X 4½ X 4½ J-BOX
FOR HOMERUN FROM PNL -RP TO RTU-1
�-tit--------; J
J
"FURNISH" MEANS TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH NECESSARY APPURTENANCE, "INSTALL" MEANS TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT
OPERATION AT THE PROPER LOCATION IN THE PROJECT.
"PROVIDE" MEANS TO "FURNISH" AND "INSTALL."
Q)
No.
USDOTNOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
Description
DOT REDESIGN OF
BUILDING #2410
B
Date
JOINT BASE CAPE COD
SANDWICH, MA
ELECTRICAL FLOOR
PLAN
SHEET 06
Submission
Project number
Date
100% WORKING DOCUMENTS
147001.00
December 5, 2024
Drawn by
Checked by
RTU-1 E-101
Scale
PANELBOARD - MDP VOLTAGE 208 / 120 AMP BUS 400 SPECIAL FEATURES - EXISTING
MOUNTING - SURFACE PHASE 3 AMP MCB ------
A.I.C. RATING - 10,000 WIRE 4 AMP MLO 400
LOAD DESCRIPTION
LOAD (VA) BREAKER
CIRCUIT
3 PH.
CIRCUIT
BREAKER LOAD (VA)
LOAD DESCRIPTION
LIGHT RECEP. HVAC MISC. AMP POLES A B C POLES AMP LIGHT RECEP. HVAC MISC.
1 2
3 100
3 4
(future) STORAGE RM, CLOSET RM RECPTS
5 6 7 8 9 10 11 12
13 14
PANELBOARD - RP9373
15 16 17 18
NOTES:
1) REFER TO CLIN 0600 LIGHTING PLAN FOR POINT OF CONNECTION LOCATIONS TO EXISTING CIRCUITS #1, #3, #5, #7.
Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors
Total Demand Loads By Type (VA)
Total Phase A 20,379 Lighting 1,970 Lighting 1.00 Lighting 1,970 Total Phase B 18,611 Receptacles 4,800 Receptacles 0.50 Receptacles 7,400 Total Phase C 16,607 HVAC 48,327 HVAC 0.85 HVAC 41,078
Miscellaneous 500 Miscellaneous 0.65 Miscellaneous 325 Total
55,597
Subtotal
50,773
Spare Capacity 25% Spare 12,693
Total Demand Load
63,466
Total Demand Amps
PANELBOARD - RP VOLTAGE 208 / 120 AMP BUS 200 SPECIAL FEATURES -
MOUNTING - SURFACE PHASE 3 AMP MCB ------
A.I.C. RATING - 22,000 WIRE 4 AMP MLO 200
LOAD DESCRIPTION
LOAD (VA) BREAKER
CIRCUIT
3 PH.
CIRCUIT
BREAKER LOAD (VA)
LOAD DESCRIPTION
LIGHT RECEP. HVAC MISC. AMP POLES A B C POLES AMP LIGHT RECEP. HVAC MISC.
(future) BATHROOM EXHAUST FANS 1224 20 1 1 2 1 20 TANKLESS WATER HEATER RM 2, RECEPT RM 2
(future) ELECTRICAL RM UH-1
20 2 3 4 1 20 (future) RECEPTACLES BATHROOM RM 5
1650 5 6 1 20 (future) RECEPTACLES SHOWER RM 6
(future new) RTU-1 3 7 8 1 20 RECEPTACLES RM 1 Northeast 9 10 1 20 RECEPTACLES RM 1 Southeast 11 12 1 20 SEPTIC TANK FULL ALARM, (future) RECEPTACLES RM 1 Northwest 13 14 1 20 (future) RECEPTACLES RM 1 Southwest 15 16 17 18
SPARE 20 1 19 20
21 22 23 24 25 26 27 28
DRILL PRESS (relocated??) 20 3
29 30 1 SPARE
31 32 1 FIRE ALARM CONTROL PANEL (FACP)
SPARE
33 34 1 SPARE
35 36 1 SPARE
37 38
SPARE 3 39 40 3 existing RTU-1 41 42
NOTES: REFER TO CLIN 0200 ELECTRICAL PLAN FOR POINT OF CONNECTION LOCATIONS TO EXISTING CIRCUITS #1, #2, #4, #6, $8, #10, #12, #14, #16, #18, #20.
Connected Loads By Phase (VA) Total Connected Loads By Type (VA) Demand Factors
Total Demand Loads By Type (VA)
Total Phase A 9,747 Lighting 0 Lighting 1.00 Lighting 0 Total Phase B 9,373 Receptacles 7,320 Receptacles 1.00 Receptacles 7,320 Total Phase C 8,693 HVAC 19,493 HVAC 0.85 HVAC 16,569
Miscellaneous 1,000 Miscellaneous 0.65 Miscellaneous 650 Total
27,813
Subtotal
24,539
Spare Capacity 25% Spare 6,135
Total Demand Load
30,674
Total Demand Amps
Scale
Project number
Date
Drawn by
Checked by
A B
Submission
147001.00 December 5, 2024
DOT REDESIGN OF
BUILDING #2410
JOINT BASE CAPE COD
SANDWICH, MA
USDOT/VOLPE
CENTER
55 BROADWAY CENTER
CAMBRIDGE, MA 02142-1001
No. Description Date
100% SUBMISSION
20 1
3 200
CONSTANT CURRENT REGULATOR
3 20 spare WW FIELD (overhead lines to Field) 60 2
1 20 (future) RECEPTACLES OFFICE West
UPS for DAS
2 30
PANELBOARD
SCHEDULES
SHEET 07
1 20
20 1EQUIPMT RM LTS (SOUTH)
OFFICE LTS. and future DOOR #4 EXIT SIGN
STORAGE, MECH, WORKSHOP, BATHRMS LTS
EQUIPMT RM LTS (NORTH) and future DOOR#1 EXIT SIGN 1 20 1 20 1
OUTDOOR LTS (future) 20 1 spare 20 1
RTU-1_E-201
1 20
SPACE
existing RTU-1
SPARE 20 1
SPARE 20 1
SPARE 20 1
SPARE 20 1
SPARE 20 1
Convenience Recpt at PNL-RP (removed ??) 20 2
SPARE 20 1
30 2
RECEPTACLES OFFICE East 1 20
SPARE
Convenience Recpt at PNL-RP
1 30
SPARE