This document contains an HVAC output summary schedule and information on a related federal contract opportunity for renovation work. The HVAC output summary schedule provides room-by-room details on area, height, cooling and heating loads, required airflows, and other technical specifications for an HVAC system serving various rooms including conference rooms, offices, storage areas, and workstations. The related solicitation is for renovations to the Houston VA Regional Office under Solicitation Number 36C10D23R0008_1 issued by the Department of Veterans Affairs. The opportunity type is listed as a solicitation and appears to relate to the HVAC work summarized.

View the file

Other files

File Type Posted
09 65 19 Resilient Tile Flooring.pdf PDF
03 01 30 Maintenance of Cast-In-Place Concrete.pdf PDF
00 00 10 Table of Contents.pdf PDF
08 80 00 Glazing.pdf PDF
36C10D23R0008 0001.docx DOCX document
36C10D23R0008 Q-A.pdf PDF
P07 Wage Rates - OIG.pdf PDF
36C10D23R0008.docx DOCX document
ALA129I-DL2700-LR.pdf PDF
single duct units (002).pdf PDF
6AR_led (002).pdf PDF
1805.04 Bid Specs.pdf PDF
Wage Rates - OIG.pdf PDF
Trane Trace HVAC Room Checksums (002).pdf PDF
Bid Doc Design Binder_Combined.pdf PDF
Digital Finish Board.pdf PDF
Bid Doc Designs (mod).pdf PDF
36C10D23R0008_1.docx--.docx-.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOM

EQUIP

AREA HEIGHT LOAD SUPPLY AIR RETURN AIR EXHAUST AIR OUTSIDE AIR

SF FT BTUH MBH MBH MBH CFM ACH CFM ACH OA CFM OA ACH (+) / (++) / (-) / (- -) / (o) CFM CFM CFM CFM

169 Conference Room Conference Room 222.62 9 500 10.5 6.1 -0.9 224 6.71 200 6.00 67 2.00 Return (o) 250 250 0 70

1073G Evidence Medical Records 115.72 9 0 1.4 1.4 -0.2 54 3.11 104 6.00 35 2.00 Return (o) 130 130 0 40

1073C Interview Conference Room 95.4 9 0 1.4 3.9 -0.5 45 3.14 86 6.00 29 2.00 Return (o) 130 130 0 40

1073E Office Offices 110.74 9 1388 1.6 2.6 -0.7 51 3.07 100 6.00 33 2.00 Return (o) 130 130 0 40

1073H Office Offices 141.03 9 1526 1.6 3.2 -1.2 66 3.12 127 6.00 42 2.00 Return (o) 130 130 0 50

170 Office Offices 126.61 9 1460 1.8 2.7 -0.8 59 3.11 114 6.00 38 2.00 Return (o) 130 130 0 45

174 Office Offices 116 9 1415 1.4 2.5 -0.7 54 3.10 104 6.00 35 2.00 Return (o) 130 130 0 45

176 Open Workstations/Corridor/Break Offices 689 9 2352 8.8 14.9 -10.7 322 3.12 620 6.00 207 2.00 Return (o) 625 625 0 220

1073F Storage Medical Records 97 9 400 0.4 1.1 -0.2 13 0.89 87 6.00 29 2.00 Return (o) 130 130 0 35

173 Storage Medical Records 109 9 400 0.4 1.3 -0.4 18 1.10 98 6.00 33 2.00 Return (o) 130 130 0 35

171 Team Space Conference Room 110 9 200 2.5 6.6 -1.7 112 6.79 99 6.00 33 2.00 Return (o) 130 130 0 60

1073 B-K Workstations Offices 754 9 1272 31.3 38.5 -11.3 1725 15.25 679 6.00 226 2.00 Return (o) 2,000 2,000 0 400

NOTES:

ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE

AHU NO

PEAK

HEATING

LOAD

CACULATED ROOM

AIRLFOW

PEAK COOLING LOAD

ROOM NO ROOM NAME

ROOM SIZE

SENSIBLE TOTAL

TRACE700 USER INPUTS TRACE700 OUTPUTS

ROOM AIR BALANCE

VA DESIGN REQUIREMENT INPUTS USER DEFINED DESIGN VALUES

ROOM DATA SHEET

THIS SCHEDULE IS REQUIRED FOR DESIGN SUBMISSION.

USE MINIMUM AIRFLOW (CFM [L/S]) FOR AIR CHANGE CALCULATIONS. IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE.

PROVIDE 11"x17" SPREADSHEETS TO VA FOR DESIGN SUBMISSIONS.

REQUIRED ROOM AIRFLOW - AIR

CHANGE METHOD

DESIGN AIRFLOWS

ROOM AIR

RETURN (R)

EXHAUST (G)

EXHAUST (S)