This is an Addendum to the District-Wide Access Control System project issued by Commtech Design for Hazel Park Schools located at 1620 E. Elza, Hazel Park, Michigan. The addendum, dated November 27, 2019, modifies the original contract documents and specifications for a system-wide access control installation across multiple school facilities. The project scope includes removal of a badge printer, badge printer laptop, camera, and tripod from the original bid, as well as elimination of a dedicated server for the S2 system in favor of utilizing existing virtual server infrastructure. The bid due date was revised to December 6, 2019, at 1:00 PM. A pre-bid meeting was held with attendees including Bret Emerson from Commtech Design, Jason Zirnis from Hazel Park Schools, James Metcalf from ROK Systems, and Diane Giovannini from Sonitrol. The project encompasses access control modifications across nine school buildings: Hazel Park High School, Hoover Elementary, United Oaks Elementary, Hazel Park Junior High, Grace (formerly Longfellow), Roosevelt Alternative High School, Jardon-Webb, and Webster Elementary.
The addendum details specific modifications to technical specifications including changes to door control devices, removal of electronic strikes and card readers from certain locations per owner direction, and comprehensive rekeying and door hardware installation requirements. Installation tasks include rekeying Best core cylinders at 43 locations throughout the district, installing blank cylinders at 81 locations, integrating existing door operators and intercoms with the new S2 access control panel, and providing HES electric strikes (models 1500C, 9600, and 9700) and card readers as specified for individual doors. No pricing information, contract award date, or contract term details are provided in this addendum document. The addendum addresses 16 pre-bid questions regarding raceway painting, existing security system integration, keypad specifications, electric strike installation responsibility, and other clarifications relevant to project execution.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hazel Park Access Control Addendum-1 1
PROJECT ADDENDUM #01
To All Bidders Date: November 27, 2019
From: Bret Emerson Company Commtech Design
Project Name:
District-Wide Access Control System
Client: Hazel Park Schools 1620 E. Elza Hazel Park, MI 48030
The Following Changes, revisions, modifications, etc. shall be incorporated into the contract documents, specifications and plans
Pre – Bid Attendees:
Bret Emerson – Commtech Design Jason Zirnis – Hazel Park Schools James Metcalf – ROK Systems Diane Giovannini – Sonitrol
Bid Due Date
1. The Due Date for the bid is changed to December 6th at 1 PM.
Attachments;
1. TC503
2. TC601C
3. TC604D
4. TC604E
5. TC604F
6. TC606C
7. TC609
8. TC610A
9. TC611A
10. Door Hardware and Re-Keying Document
11. Hazel Park Schools Door Re-Keying and Door hardware Floorplans
Drawings reissued
1. TC503
a. Remove from the scope of work the Badge Printer, Badge Printer Laptop, Camera and Tripod. The owner has an existing badge printer that can be utilized.
Hazel Park Access Control Addendum-1 2
b. Remove from the scope of work the Server for the S2 System. This server is a virtual server that was just installed to server the Edison building. Add software and licenses as required to the existing server
2. TC601C
a. Change door AD3 to an existing LR device not an ES as shown. Wire this device the new access control system.
3. TC604D -High School Area D
a. Issued for general knowledge. No work required other than what is shown on the rekeying drawings.
4. TC604E -High School Area E
a. Change control of the front entry doors as noted. Add one ES and re-wire the existing Latch retraction device to the new security panel.
5. TC604F -High School Area F
a. Issued for general knowledge. No work required other than what is shown on the rekeying drawings.
6. TC606C -Oaks Elementary Area C
a. Issued for general knowledge. No work required other than what is shown on the rekeying drawings.
7. TC609
a. Remove the ES and CR from the bid. The owner does not want to electronically control this door.
8. TC610A
a. Add a Card reader and Electric Strike to door PJ10.
9. TC611A
a. See door WE1. This is an existing Latch Retraction device. Wire to the new
Access Control system.
10. Hazel Park Schools Door Re-Keying and Door hardware Floorplans
Hazel Park Access Control Addendum-1 3
a. Contractor shall rekey doors as noted on the floorplans. Provide a new core tha meets the owners standard keys. The goal is to remove the master exterior key from users and only allow access with a proximity card.
b. “RK” note on these drawings directs the contractor to Rekey the core to a new core.
c. “B” on these drawings indicates that the contractor shall remove the key cord and install a blank.
Specifications reissued;
1. Door Hardware and Re-Keying Document
a. Provide all door hardware listed at each door to ensure electronic control of the door in coordination with the access control system.
b. Provide re-keying and blanking of doors as noted and as shown on the accompanying floorplans
Manufacturers Equals;
1. None
Clarifications;
1. None
Questions;
1. Is it a requirement to paint the new raceways installed as part of this project?
Answer. No. the owner will paint them.
2. Are we replacing the existing security systems?
Answer. Existing intercoms are to be replaced. Other system are to be replaced as per the notes on the drawings
3. If so, are we using the existing security devices? Did not see any security devices on the drawings besides the keypads.
Answer. The intrusion detections system is stand alone. Those shall remain in place and in use.
4. If not, what type of security systems are in place so we can order the correct keypad?
Answer. Match keypad to the existing system.
5. Is the extent of the integration between the S2 system and the security systems to disarm the system upon entering?
Hazel Park Access Control Addendum-1 4
Answer. There is no requirement for integration between the S2 system and the existing intrusion detection systems.
6. Bid call for badge printer and workstation. These were installed for the Edison max Project. Is this a second print station?
Answer. We will be removing this from the bid scope as the badge printer, laptop and camera are existing.
7. Sections missing from school drawings, JR High section C, H.S., section D & F.
Answer. There is no work for security on these. See attached.
8. Electric Strikes: do we (security vendor) need to include electric strikes on doors or is that going to be done by others.
Answer. See attached door hardware specifications. These are to be provided and installed by the contractor
9. We do not see door contacts on the perimeter doors. Should there be?
Answer.
10. Can you please provide an “As-Built” report from the current S2 system?
Answer.
11. Can you please provide the “About Page” from the current S2 system?
Answer.
12. Would a virtual controller from S2 be accepted in the base bid?
Answer.
13. What color cable is required?
Answer.
14. Please confirm the total number of badge printing PCs/stations that are required.
Answer.
15. Aside from batteries placed within power supplies and S2 nodes, are any rack or wall-mounted UPS’s required in the base bid?
Answer.
16. Who is installing the painted plywood in closets?
Answer.
17. In Section 28, 1.02, A, 3 and also in 28, 2.07, C, 4: Please confirm that the security system contractor is to provide hardwired power from the existing circuit/wall receptacle in lieu of plug-in power supplies and S2 nodes. If outlets can be provided by others, will plug-in power supplies and S2 nodes be accepted?
Answer.
18. For raceways, please confirm the security system contractor is to paint the metal raceways or if this will be completed by others.
Answer.
Hazel Park Access Control Addendum-1 5
19. Please clarify if the door hardware provider or the security contractor is installing the latch retractors (LR).
Answer.
20. Please clarify if the door hardware provider or the security contractor is installing the electric latches and electric strikes (EL & ES).
Answer.
Sincerely, Bret Emerson
Hazel Park Schools
Door Hardware and Re-Keying
Hazel Park Schools
Hardware Comments
District Administrative Offices
AD1 None
Existing electric strike. Re-wire to new S2 access control panel
AD2 HES 9700 Electric Strike US32D Yale SquareBolt exit device
AD3 None Existing electric latch retraction
AD4 HES 9600 Electric Strike US32D Sargent 80 Series exit device
RK 5 locations Rekey Best core
B 12 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
Hoover Elementary School
H01 None
Existing electric strike. Re-wire to new S2 access control panel
H02 HES 9600 Electric Strike US32D
H03 HES 9600 Electric Strike US32D
H04 HES 9600 Electric Strike US32D
RK 4 locations Rekey Best core
B 2 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
Hazel Park High School
HS1 HES 9700 Electric Strike US32D Yale SquareBolt exit device
HS2 None Staff will dog exit devices if and when required
HS3 None Staff will dog exit devices if and when required
HS4 None Staff will dog exit devices if and when required
HS5 HES 9700 Electric Strike US32D Yale SquareBolt exit device
HS6 HES 9600 Electric Strike US32D
HS7 HES 9600 Electric Strike US32D
HS8 HES 9600 Electric Strike US32D
HS9 HES 9600 Electric Strike US32D
RK 11 locations Rekey Best core
B 14 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
United Oaks Elementary
OA1 None
Existing electric strike.. Re-wire to new S2 access control panel
OA2 HES 1500C US32D Electric Strike Existing Sargent 8200 mortise lock
OA3 *
Field verify existing Von Duprin strike is operational, or replace
OA4 HES 9600 Electric Strike US32D
OA5 HES 9600 Electric Strike US32D
RK 6 locations Rekey Best core
B 2 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
Hazel Park Junior High School
JH1 None
Existing electric strike. Re-wire to new S2 access control panel
JH2 HES 9600 Electric Strike US32D
RK 4 locations Rekey Best core
B 5 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
Grace (Formerly Longfellow)
LF1 None
Existing electric strike. Re-wire to new S2 access control panel
LF2 HES 1500C US32D Electric Strike
LF3 HES 9600 Electric Strike US32D
LF4 (1) Rim Exit Sargent 70 43 8804 US10BE
Remove existing damaged rim exit devices. Reuse trim
(1) Rim Exit Sargent 43 8810 US10BE
HES 9600 Electric Strike 613E
RK 4 locations Rekey Best core
B 7 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
Roosevelt Alternative High School
RO1 None
Existing electric strike. Re-wire to new S2 access control panel
RO2 (1) Rim Exit Sargent 70 43 8804 US10BE Reuse trim
HES 9600 Electric Strike 613E
RO3 None No access control per Principal
RO4 None No access control per Principal
RK 3 locations Rekey Best core
B 10 locations
Jardon-Webb
PJ1 None
Existing electric strike; integrate with existing door operator. Existing electric strike. Re-wire to new S2 access control panel
PJ2 None
Existing electric strike. Re-wire to new S2 access control panel
PJ3 HES 9600 Electric Strike US32D Integrate with existing door operator
PJ4 HES 9600 Electric Strike US32D
PJ5 None
Existing electric strike.. Re-wire to new S2 access control panel
PJ6 HES 9600 Electric Strike US32D Integrate with existing door operator
PJ7 HES 1500C US32D Electric Strike
Existing Schlage mortise lock.. Re-wire to new S2 access control panel
PJ8 HES 9600 Electric Strike US32D
PJ9 HES 9600 Electric Strike US32D
PJ10 HES 9600 Electric Strike US32D Integrate with existing door operator
RK 7 locations Rekey Best core
B 26 locations
Remove keyed cylinder and replace with blank
(mortise or rim)
Webster Elementary
WE1 None
Existing electric latch retraction. Re-wire to new S2 access control panel
WE2 HES 9600 Electric Strike US32D
WE3 HES 9700 Electric Strike US32D
Yale SquareBolt exit device; integrate with existing door operator
WE4 HES 9700 Electric Strike US32D Yale SquareBolt exit device
WE5 HES 9600 Electric Strike US32D
WE6 HES 9600 Electric Strike US32D
RK 4 locations Rekey Best core
B 4 locations
TC604D
HAZEL PARK HIGH SCHOOL FIRST FLOOR
SECURITY PLAN AREA D
N
TC604D
HAZEL PARK HIGH
SCHOOL FIRST FLOOR
SECURITY PLAN AREA D
H
AZ
EL
P
AR
K, M
IC
H
IG
AN
H A
Z E
L
P
A R
K
P
U B
L I C
S
C H
O O
L S
DI
ST
RI
CT
W
ID
E
AC
CE
SS
C
ON
TR
OL
S
YS
TE
M
C o m m t e c h
KEYPLAN
A
B
C
D
E
F
G
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box
RK
Julie Chicklon Text Box Existing electric strike
Julie Chicklon Text Box Existing electric strike
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Line
Julie Chicklon Arc
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box Greenhouse
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box
RK
Julie Chicklon Text Box
RK
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Text Box
RK
Julie Chicklon Text Box
RK
Julie Chicklon Text Box B
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Text Box Existing Door Operator Add 9600 electric strike Add card reader
Julie Chicklon Text Box
RK
Julie Chicklon Ellipse
Julie Chicklon Circle
CR
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Text Box Existing exit only, no cylinder
Julie Chicklon Text Box Existing exit only, no cylinder
Julie Chicklon Arrow
Julie Chicklon Arrow
Julie Chicklon Text Box Existing exit only, no cylinder
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Text Box
RK
Julie Chicklon Text Box Existing electric strike
Julie Chicklon Text Box Add HES 1500C electric strike
Julie Chicklon Text Box
PJ10
Ellipse
Image
Julie Chicklon Line
Julie Chicklon Line
Julie Chicklon Line
Julie Chicklon Line
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Text Box Add 9700 Electric Strike
Julie Chicklon Text Box
RK
Julie Chicklon Text Box B
Julie Chicklon Text Box B
Julie Chicklon Text Box Add 9700 Electric Strike
Julie Chicklon Text Box Existing exit only, no cylinder
Julie Chicklon Text Box
RK
Julie Chicklon Text Box
RK
Julie Chicklon Text Box
RK
Julie Chicklon Text Box Add 9600 Electric Strike
Julie Chicklon Line
Julie Chicklon Text Box Existing electric latch retraction
Julie Chicklon Text Box Add 9600 Electric Strike
| Sheets and Views |
| TC604D-Security-Add 01 |
| Sheets and Views |
| TC604F-Security-Add 01 |
| Sheets and Views |
| TC606C-Security-Add 01 |
File details come from the government source that posted it. Updated .