Additional Questions and Answers Posted to Feb Biz Ops Feb 8, 2012.
1. On sheet 5 of the plans that are attached to the solicitation, it appears that there is insufficient vertical cable management shown on the racks, are we only to supply what is shown? No, the Contractor shall supply and install additional vertical cable management as needed to meet the requirements of Section 271100 - 1.1.H......All cable shall be placed so that there is cable guides in both the horizontal and vertical position.
2. Are all firestops shown on the list in Section 078413 - 3.2? During installation if it becomes apparent a firestop has been missed, or a wall is mislabeled and requires a firestop, it will be paid as a change order.