Amendment_No_5_-_Juarez_Lincoln_Asbestos_Survey_Bldg_3.pdf

PDF 2 MB Posted

Attached to
New Construction and Tenant Improvements, Laredo 1 and 2 Ports of Entry
Solicitation number
GS-07P-14-HH-C-0016-Stage2
Issued by

About this file

J L Asbestos Survey Bldg 3

View the file

Other files

File Type Posted
Industry_Outreach_-_San_Antonio_8-6-2015_(1).pdf PDF
Industry_Outreach_-_Laredo_8-5-2015_(1).pdf PDF
Amendment_No_9_-_GS-07P-14-HH-C-0016.pdf PDF
Amendment_No_8_-_Renderings.zip ZIP file
Amendment_No_8_-_GS-07P-14-HH-C-0016.pdf PDF
Amendment_No_8_-_Revised_Drawings.pdf PDF
Amendment_No_8_-_Civil_drawing.DWG DWG drawing
Amendment_No_8_-_Convent_Existing_HVAC.pdf PDF
Amendment_No_8_-_Existing_Canopy_drawings_for_J L.pdf PDF
Amendment_No_7_-_GS-07P-14-HH-C-0016.pdf PDF
Amendment_No_6_-_GS-07P-14-HH-C-0016.pdf PDF
Amendment_No_5_-_Convent_Asbestos_Survey_1995.pdf PDF
Amendment_No_5_-_Sign_in_sheet_for_Site_Visit_-_7-15-14.pdf PDF
Amendment_No_5_-_Convent_Asbestos_Survey_2007.pdf PDF
Amendment_No_5_-_Juarez_Lincoln_Revised_Drawings.zip ZIP file
Amendment_No_5_-_Juarez_Lincoln_Asbestos_Survey_Building_2 _Combined.pdf PDF
Amendment_No_5_-_Juarez_Lincoln_Asbestos_Survey_Bldg_4.pdf PDF
Amendment_No_5_-_Convent_Revised_Specifications.pdf PDF
Amendment_No_5_-_GS-07P-14-HH-C-0016.pdf PDF
Amendment_No_5_-_Convent_Revised_Drawings.pdf PDF
Geotech_Report_-_Juarez-Lincoln.pdf PDF
Amendment_No_4_-_GS-07P-14-HH-C-0016.pdf PDF
Amendment_No_3_-_GS-07P-14-HH-C-0016.pdf PDF
SITE_VISIT.pdf PDF
Amendment_No._2_-_J L_-_NXT00009_-_Div_01_Specifications.pdf PDF
Amendment_No._2_-_Consolidated_Div_01_Specifications.pdf PDF
Amendment_No._2_-_Convent_-NTX00007_-_Div_01_Specifications.pdf PDF
Amendment_No_2_-_GS-07P-14-HH-C-0016.pdf PDF
Laredo_1_ _2_Pre-proposal_meeting_sign_in_sheet_6-16-14.pdf PDF
Amendment_No_1_-_GS-07P-14-HH-C-0016.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF HEALTH & HUMAN SERVICES Federal Occupational Health

Division of Environmental Health Services 1301 Young Street, Suite 772 Dallas, Texas 75202

ASBESTOS SURVEY REPORT

Conducted for:

GENERAL SERVICES ADMINISTRATION

REGION 7 SAFETY AND ENVIRONMENTAL TEAM

819 TAYLOR STREET

FORT WORTH, TEXAS 76102 (TARRANT COUNTY)

Conducted at:

UNITED STATES BORDER STATION (USBS)

BUILDING 3

J&L SECONDARY

TERMINATION AT I35

LAREDO, TEXAS 78040-9998

GSA Building # TX0322

Conducted on:

JANURARY 29, 2013

Prepared by:

UNITED STATES PUBLIC HEALTH SERVICE

FEDERAL OCCUPATIONAL HEALTH SERVICE

DALLAS AREA OFFICE

1301 YOUNG STREET, SUITE 772

DALLAS, TX 75202

A S B E S T

Asbestos Survey Report January 29, 2013 United States Border Station (USBS) Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

Reports and other publications issued by the Environmental Health Services (EHS) program of the Federal Occupational Health Service (FOHS) are prepared under procedures established by FOHS, which are designed to assure the technical competency of the persons or organizations under contract to the FOHS. In addition, reports and other publications are reviewed internally by one or more FOHS technical staff, and all comments are addressed to the satisfaction of the issuing office, prior to dissemination.

Mention of company name or products does not constitute endorsement by FOHS.

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

TABLE OF CONTENTS

Sections

1. EXECUTIVE SUMMARY

2. INTRODUCTION

3. BUILDING DESCRIPTION

4. FINDING SUMMARY OF ASBESTOS CONTAINING MATERIALS

5. SAMPLING PROCEDURES

5.1.SURVEY PROCEDURES

5.2.ANALYTICAL PROCEDURES

6. RECOMMENDATIONS

Appendices

Appendix A BUILDING LAYOUT / BULK SAMPLE LOCATIONS

Appendix B SUMMARY TABLES

Appendix C LABORATORY RESULTS

Appendix D HAZARD RANKING TABLE

Appendix E PHOTOGRAPHS

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

1.0 EXECUTIVE SUMMARY

On January 29, 2013, a survey for asbestos containing building materials (ACM) was conducted at the United States Border Station (USBS), Building 3 J&L Secondary Termination at Interstate 35 in Laredo, Texas 78040. The GSA building number is TX0322.

Construction of the building was completed January 1, 1982. The survey was conducted in accordance with the Memorandum of Agreement and Specifications between the General Services Administration (GSA) and the Federal Occupational Health Service (FOHS).

The objective of the investigation was to assess the presence of asbestos in the building.

The building is scheduled for demolition as part of a major project at the border station. A total of one hundred twenty-two (122) bulk samples of suspect asbestos containing building materials were collected during the survey and submitted for laboratory analysis for asbestos content. Three types of materials were assumed to be asbestos containing because they could not be sampled due to limited access or it would have been too destructive. The following materials were found to be asbestos containing or assumed to be asbestos containing:

Material Description Material Location(s) Room #

Percent Asbestos

Type

Material Condition

Estimated Quantity

Friable Non-

Friable

Hazard Ranking

FT3-Floor tile 12 x 12 cream floor tile)and associated FTM3-Floor tile Mastic black

Room 318, interview room

Floor Tile 1-2%

Chrysotile Mastic 3-6%

Chrysotile

Good 120 SF

120 SF

No 1

DM1- Duct/Pipe mastic/sealant white/cream

Janitor room, penthouse , and ceiling plenum

1-4% Chrysotile

Good 400 SF No 1

PT1- wall penetration putty/sealant

White

Janitor room 2-4% Chrysotile

Good 1 SF No 1

RS1-roof sealant silver/gray/dark brown

Roof and Canopy roof

30-60% Chrysotile

Good 1000 SF* No 1

RS2-roof sealant black Roof and Canopy roof

10-30% Chrysotile

Good 1000 SF* No 1

CK2- Caulk gray/black Exterior windows 1-10% Chrysotile

Good 300 LF No 1

CK3- Caulk brown/black Exterior windows 1-2% Chrysotile

Good 300 LF No 1

CT3- ceiling tile white Ceiling plenum space above lower ceiling tile

Assumed* Good 2000-3000

SF**

Yes 1

Brick tile and associated mortar

Cashier lobby, hallways, break room, interview rooms 313 and 313A

Assumed* Good 1500 SF** No 1

*Most likely the entire roof will need to be abated to remove asbestos containing roofing materials **Assumed materials should be tested for asbestos prior to demolition- most likely they are non-asbestos

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

2.0 INTRODUCTION

The United States Border Station (USBS), Building 3 J&L Secondary Termination at Interstate35 in Laredo, Texas (Webb County) was surveyed for asbestos containing materials (ACM) by visual inspection and bulk sampling by an accredited inspector on January 29, 2013. This survey was conducted in response to the client’s request for the FOHS to perform the survey under the Memorandum of Agreement and Specifications between the client and Federal Occupational Health Service (FOHS). Scott Fontenarosa, a certified asbestos-building inspector, performed the asbestos survey.

The purpose of the survey was to perform a building inspection according to 40 CFR Part 763 Asbestos Hazard Emergency Response Act - AHERA protocols and EPA 40 CFR Part 61 National Emissions Standard for Hazardous Air Pollutants – NESHAP protocols. A partially destructive sampling method was implemented during the survey. The survey included visual identification and representative sampling of existing and accessible suspect homogeneous building materials. In addition, an assessment of condition, friability, and estimated quantity of material was made.

Homogeneous areas were grouped building-wide and sampled using a building–wide random sampling plan. A thorough attempt was made to access all areas for visual and physical verification of suspect ACM. However, due to the partial destructive nature of this survey and because some areas of the building may have been inaccessible, FOHS does not guarantee that all ACM in the building were located and identified.

The inspection was based on state-of-the-science practices and current regulations in effect at the time of the survey.

3.0 BUILDING DESCRIPTION

The United States Border Station (USBS), Building 3 (TX0322) is a single story building in which construction was completed January 1, 1982. The building is approximately 46,129 square feet and round in shape. The building has a penthouse mechanical room where air handlers are located. The concrete structure rests on a concrete slab on grade. The roof is flat with built-up asphalt. The exterior walls are metal framed glass panels and textured plaster over concrete. The interior walls consists wallboard, plaster/concrete, cinderblock, clay block, and ceramic tile. There are columns that are plaster over concrete. Floors are finished with resilient vinyl tile, ceramic tile, stretched carpet, or brick tiles. Ceilings are suspended metal-grid with lay-in white panels, plaster, or concrete. The front entrance of the building faces north. There are administrative, facility, and detention areas.

Rooms/areas include janitorial, storage, mechanical, restrooms, holding cells, cashier area, vault, break room, interview rooms, command center, hard secondary hallways, soft secondary hallways, general office rooms, conference room, copier room, file room, and laboratory room.

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

4.0 FINDING SUMMARY OF ASBESTOS CONTAINING MATERIALS

Approximately forty (40) homogeneous areas (HA) were identified. The exact number may not be determined because some HA might be layered or associated with another HA that may not have been explicitly distinguished by themselves. For example, mixtures of different floor mastics may be given the same HA number.

Eight (8) HA contained asbestos (>1.0% asbestos), four (4) were assumed to contain asbestos, and twenty-eight (28) HA did not contain detectable asbestos (zero, ND, less than 1% or equal to 1% asbestos).

ASBESTOS CONTAINING (>1.0% ASBESTOS)

& ASSOCIATED HOMOGENEOUS AREAS

HA NUMBER & DESCRIPTION PERCENT ASBESTOS

Surfacing Material MT1 Mortar for Ceramic Brick tile gray............................................................................. Assumed

TSI (Thermal Insulation) DM1 Duct/Pipe Mastic/Sealant, (old) white/cream................................................. 1-4% Chrysotile

Miscellaneous FT3 Floor Tile, 12” x 12” cream ............................................................................ 1-2% Chrysotile FTM3 Black Mastic associated with 12” x 12” cream floor tile.................................. 3-6% Chrysotile PT1 Putty/Sealant, white wall penetration ........................................................... 2-4% Chrysotile RS1 Roof Sealant black silver/gray/dark brown ................................................ 30-50% Chrysotile RS2 Roof Sealant black .................................................................................... 10-30% Chrysotile CK2 Caulk, exterior gray/black ............................................................................ 1-10% Chrysotile CK3 Caulk, exterior brown/black ........................................................................... 1-2% Chrysotile CT3 Ceiling tile (plenum space) ........................................................................................Assumed CR1 Ceramic Brick tile, brown ..........................................................................................Assumed

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

HOMOGENEOUS AREAS NOT CONTAINING ASBESTOS

(<1% or ND)

HA NUMBER & DESCRIPTION PERCENT ASBESTOS

Surfacing Materials

JC1 Joint Compound white........................................................................................ ND TX1 Texture, wall, white ............................................................................................ ND PL1 Wall plaster/concrete.......................................................................................... ND MT2 Mortar tan/gray associated DM1with Ceramic tile 12” X 12” tan.......................... ND TX1 Wall texture, white.............................................................................................. ND GR1 Grout, brown associated with ceramic brick tiles ............................................... ND GR2 Grout, brown associated with Ceramic tile 12” X 12” tan .................................... ND PL2 Exterior plaster................................................................................................... ND

TSI (Thermal Insulation)

DM2 Duct mastic/sealant white (new)......................................................................... ND DM3 Duct mastic/sealant yellow................................................................................. ND

Miscellaneous

CT1 Ceiling Tile, 2’ x 2’ white random fissures............................................................ ND CT2 Ceiling Tile, 2’ x 2’ coarse random fissures ........................................................ ND WB1 Wallboard Panel................................................................................................. ND WV1 Wall vinyl base cove, 4’ brown/gray .................................................................. ND WVM1 Mastic, yellow-brown associated with Wall vinyl base cove, 4’ brown/gray ........ ND WV2 Wall vinyl base cove, 6’ brown/gray ................................................................... ND WVM2 Wall Vinyl, 6” black/brown and associated mastic, yellow .................................. ND CK1 Caulk, white associated with restroom sinks/toilets ............................................ ND FT1 Floor tile 12” X 12” white, gray mottled............................................................... ND FTM1 Mastic associated with associated with Floor tile 12” X 12” white, gray mottled.. ND CM1 Carpet mastic yellow-brown ............................................................................... ND FT2 Floor tile 12” X 12” tan mottled brown ................................................................ ND FTM2 Mastic tan associated with Floor tile 12” X 12” tan mottled brown ...................... ND BB1 Clay wall block, orange ...................................................................................... ND DS2 Duct sealant white.............................................................................................. ND PT1 Wall penetration putty/sealer.............................................................................. ND RT1 Roof tar black..................................................................................................... ND SC1 Sink undercoating off white ................................................................................ ND CR2 Ceramic tile 12” X 12” tan .................................................................................. ND

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

5.0 SAMPLING PROCEDURES

5.1 Survey Procedures

The asbestos survey involved an asbestos assessment comprised of the following three subtasks: Visual Inspection and Sampling, Laboratory Analysis, and Condition Assessment.

The activities performed in each task are detailed in the following paragraphs.

Visual Inspection and Sampling: The survey for asbestos-containing materials (ACM) included visual observation of the exterior, roof, interior surfaces, finishes, areas above suspended ceilings, and mechanical areas.

Laboratory Analysis: All samples were submitted to FOH’s, National Environmental Reference Laboratory, Dallas, Texas and were analyzed by progressive Polarized Light Microscopy (PLM). Polarized Light Microscopy is the EPA recommended analytical method for determining asbestos content in bulk samples.

Condition Assessment: A condition assessment was performed on all suspect asbestos building materials collected. Building materials were categorized by friability, condition, and potential for disturbance. Consideration was given to the process of demolition and renovation and the impact of the forces upon the ACM. The friability assessment was the basis for our recommendations.

The ACM was categorized as required by the National Emissions Standard for Hazardous Air Pollutants (NESHAP). The NESHAP Final Rule Revision (EPA 40 CFR Part 61) dated November 20, 1990, includes several modifications and additions. The modification, which greatly affects abatement alternatives, was the re-categorization of ACM. These are categorized as follows.

Friable: means any material that can be crumbled, pulverized, or reduced to powder by hand pressure when dry.

Category I Non-Friable ACM: means packing, gaskets, resilient floor coverings and roofing materials that contain more than one-percent asbestos.

Category II Non-Friable ACM: means any material, excluding Category I ACM that contains more than one-percent asbestos, and is not friable.

Regulated ACM (RACM): included all friable ACM; Category I ACM that will be or has been subject to sanding, grinding, cutting, or abrading; Category II ACM that has become friable;

and Category II ACM that has a high probability of becoming, or has crumbled, pulverized, or reduced to a powder by forces expected to act on the material in the course of demolition or renovation operations.

These revisions require experienced interpretation from the survey or along with input from the owner’s representative planning the renovation or demolition. This is necessary in order to determine the probability that the subsequent forces will make non-friable ACM become friable.

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Prior to conducting the ACM survey, a thorough field observation inspection was conducted to determine appropriate sampling procedures for the building, and to ensure representative assessment was made in collecting the agreed upon samples. The ACM survey consisted of identification and sampling of suspect asbestos-containing materials located in the building. An assessment of material condition and an estimation of material quantities were made at the time of sample collection.

The following protocol was used in the survey:

Materials were divided into homogeneous areas;

Representative samples of each homogeneous area of miscellaneous, surfacing, and thermal system insulation materials were collected;

A minimum of three samples of each homogeneous miscellaneous area was collected.

A minimum of three samples of each homogeneous surfacing area was collected. A minimum of three samples of each homogeneous thermal system insulation material was collected. Additional samples were collected based on square feet or different system type, such as patch material;

After collection, each sample was sealed zip-lock plastic bags and labeled. A sample log was maintained which identified sample number, sample material type, location, and area description location.

5.2 ANALYTICAL PROCEDURES

Bulk samples collected by FOHS were analyzed by the National Environmental Reference Laboratory in Denver, Colorado. Samples analyzed having identified asbestos are reported by percent asbestos range and type(s) of asbestos present. Samples analyzed having no identified asbestos are reported as “none detected” (ND). The methods used for this evaluation were in compliance with the guidelines established by EPA in its Method for the Determination of Asbestos in Bulk Building Materials (EPA-600/R-93

6.0 RECOMMENDATIONS

The recommendations can be applied to basically two classifications: 1) abatement, or 2) managing in place through an Operations and Maintenance (O&M) Program. Abatement is generally accomplished by encapsulating the material, enclosing the material, encasing the ACM, or removing the material. Managing asbestos in place includes implementing, maintaining, and adhering to an O&M Program.

Although it is generally more cost effective for the short term to manage asbestos in place, the material should be documented, maintained and periodically inspected. This alternative can be an effective alternative, but the ACM remains in the building. Prior to demolition or renovation of a building, all friable and many non-friable ACMs must be removed from the affected area.

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

Based upon the field investigation, the following hazard assessment ranking table, and analytical laboratory results of the identified suspect material, the following actions are recommendations:

Hazard Rank Abatement Priority

ACM Condition Response Actions ACM Disturbance Potential

7 1 Significantly Damaged

Evacuate or isolate the area if needed. Remove the ACBM (or enclose or encapsulate if sufficient to contain fibers).

Repair of TSI is allowed if feasible and safe. O&M Plan required.

Any

6 2 Damaged Evacuate or isolate the area if needed. Remove, enclose, encapsulate, or repair to correct damage. Take steps to reduce potential for disturbance. O&M required.

Potential for significant damage

5 3 Damaged Remove, enclose encapsulate, or repair to correct damage. O&M required.

Potential for Damage

4 4 Damaged Same as hazard rank #5. Low

3 5 Good Evacuate or isolate the area if needed. Take steps to reduce potential for disturbance. O&M required.

Potential for significant damage

2 6 Good O&M required. Potential for damage

1 7 Good O&M required. Low

0 8 Non-ACM Inventory for future use Inventory for future use

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Recommendations for Specific Homogeneous Areas

Floor Tile (FT3) Hazard Rank 1 Abatement Priority 7 This HA consists of 12” x 12” off white and tan (cream) vinyl floor tile. The tile contains 1- 2% chrysotile asbestos. This floor tile is located in interview room 318. There is approximately 120 square feet of this material. The floor tile is non-friable and in good condition. The floor tile could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing floor tile should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Floor Tile Mastic, Black (FTM3) Hazard Rank 1 Abatement Priority 7 This HA consists of black mastic and is associated with FT3. The mastic contains 3-6% chrysotile asbestos. This mastic is located in the interview room 318. There is approximately 120 square feet of this material. The mastic is non-friable and in good condition. The mastic could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing mastic should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Putty/Sealant (PT1) Hazard Rank 1 Abatement Priority 7 This HA consists of white putty/sealant found at a wall penetration. This material contains 2-4% chrysotile asbestos. This putty/sealant is found at a duct wall penetration in the janitor room. There is approximately 1 square feet of material. The putty/sealant was determined to be non-friable and in good condition. The putty/sealant could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing mastic should be placed in an Operations and Maintenance program until renovation activities or change in condition requires removal. This asbestos containing putty/sealant should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Duct/Pipe Mastic/Sealant (DM1) Hazard Rank 1 Abatement Priority 7 This HA consists of white mastic/sealant found on ducts/pipes. This material contains 1-4% chrysotile asbestos. This mastic/sealant is found on duct seams and pipe wrap seams found in the janitor room, penthouse mechanical room, and ceiling plenum space. There is approximately 400 square feet of material. The mastic/sealant was determined to be non-friable and in good condition. It should be noted that newer looking duct/pipe mastic/sealant (DM2) is similar in appearance but does not contain asbestos. For abatement purposes distinguishing the difference between DM1 and DM2 may be difficult.

Repair and installation records of new materials if available may help. The mastic/sealant could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing mastic should be placed in an Operations and Maintenance program until renovation activities or change in condition requires removal. This asbestos containing mastic/sealant should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

Roof Sealant (RS1) Hazard Rank 1 Abatement Priority 7 This HA consists of black silver/gray/dark brown roof sealant. The roof sealant contains 30-60% chrysotile asbestos. This roof sealant is found on the lower roof perimeter parapet wall, around roof pipes, ducts etc. and mixed with roof sealant RS2. There is approximately 1,000 square feet of material, however to adequately abate most of the roofing materials may have to be removed. The roof sealant was determined to be non-friable and in good condition. The roof sealant could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing roof sealant should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Roof Sealant (RS2) Hazard Rank 1 Abatement Priority 7 This HA consists of black roof sealant. The roof sealant contains 10-30% chrysotile asbestos. This roof sealant is found on the lower roof perimeter parapet wall, around roof pipes, ducts etc. and mixed with roof sealant RS1. There is approximately 1,000 square feet of material, however to adequately abate most of the roofing materials may have to be removed. The roof sealant was determined to be non-friable and in good condition. The roof sealant could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing roof sealant should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Caulk Exterior Gray/Black (CK2) Hazard Rank 1 Abatement Priority 7 This HA consists of black/gray caulk. The caulk contains 1-10% chrysotile asbestos. This caulk is found at found at the joints of exterior windows and metal frame panels and is mixed with CK3 brown/black caulk. There is approximately 300 linear feet of material. The caulk was determined to be non-friable and in good condition. The caulk could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing caulk should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Caulk Exterior Brown/Black (CK3) Hazard Rank 1 Abatement Priority 7 This HA consists of brown/black caulk. The caulk contains 1-2% chrysotile asbestos. This caulk is found at found at the joints of exterior windows and metal frame panels and is mixed with CK2 brown/black caulk. There is approximately 300 linear feet of material. The caulk was determined to be non-friable and in good condition. The caulk could present a health hazard potential to building occupants if there was a disturbance causing fiber release. This asbestos containing caulk should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal.

Ceiling Tile White (CT3) Hazard Rank 1 Abatement Priority 7 This HA consists of lay ceiling tile located in the ceiling plenum space approximately 10 feet above the lower lay-in ceiling tile CT1 and CT2. The ceiling tile was inaccessible for collecting samples for asbestos content. It was assumed to contain asbestos following AHERA protocol although most likely this ceiling tile does not contain asbestos. This assumed asbestos containing ceiling tile should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040 demolition requires removal. At this time the ceiling tile should be tested for asbestos content.

Ceramic Brick Tile Brown (CR1) Hazard Rank 1 Abatement Priority 7 This HA consists of ceramic brick tile found mainly in the entrance lobby area, hallways, and a few interview rooms. The brick tile was not sampled for asbestos content due to the highly destructive manner required to collect this sample. It was assumed to contain asbestos following AHERA protocol although most likely this tile does not contain asbestos. This assumed asbestos containing ceramic brick tile should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal. At this time the ceramic brick tile should be tested for asbestos content.

Mortar Brown (MT1) Hazard Rank 1 Abatement Priority 7 This HA consists of mortar associated with ceramic brick tile (CR1) found mainly in the entrance lobby area, hallways, and a few interview rooms. The mortar was not sampled for asbestos content due to the highly destructive manner required to collect this sample. It was assumed to contain asbestos following AHERA protocol although most likely this mortar does not contain asbestos. This assumed asbestos containing mortar should be placed in an Operations and Maintenance program until renovation activities, change in condition, or planned demolition requires removal. At this time the mortar should be tested for asbestos content.

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

APPENDIX A

BUILDING LAYOUT / BULK SAMPLE LOCATIONS

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

APPENDIX B

SUMMARY TABLES

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Table 1: Summary of Asbestos-Containing Materials

Functional Area(s) and Room Number(s)

Location of Material

Material Description Estimated Quantity

Sample Number

Analytical Results (Asbestos Type &

Percent)

Hazard Ranking and Condition of

Asbestos- Containing

Material Ceiling plenum, penthouse mechanical room, and janitor

Ducts and pipes

DM1- Duct/Pipe Mastic/Sealant, (old) white/cream

400 SF TX0322-085

TX0322-086

TX0322-087

1-4% Chrysotile 1 Good and Non-

Friable

Room 318 Interview room Floor FT3-Floor tile 12 x 12 cream floor tile associated with

FTM3- Black mastic

150 SF TX0322-076

TX0322-077

TX0322-078

3-6% Chrysotile 1 Good and Non-

Friable

Room 318 Interview room Floor FTM3- Black mastic associated with FT3-Floor tile 12 x 12 cream floor tile

150 SF TX0322-079

TX0322-080

TX0322-081

5-10% Chrysotile 1 Good and Non-

Friable

Room 317 Janitor room Wall PT1- wall penetration putty/sealant White

1 SF TX0322-091

TX03220-92

TX0322-093

2-4% Chrysotile 1 Good and Non-

Friable

Roof and canopy Roof and canopy

RS1- Roof Sealant black silver/gray/dark brown

1000 SF TX0322-094

TX0322-095

TX0322-096

30-50% Chrysotile 1 Good and Non-

Friable

Roof and canopy Roof and canopy

RS2- Roof Sealant black 1000 SF TX0322-097

TX0322-098

TX0322-099

10-30% Chrysotile 1 Good and Non-

Friable

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

Table 1: Summary of Asbestos-Containing Materials (Continued)

Functional Area(s) and Room Number(s)

Location of Material

Material Description Estimated Quantity

Sample Number

Analytical Results (Asbestos Type &

Percent)

Hazard Ranking and Condition of

Asbestos- Containing

Material Exterior Exterior window and metal frames

CK2- Caulk gray/black 300 LF TX0322-118

TX0322-119

TX0322-120

1-10% Chrysotile 1 Good and Non-

Friable

Exterior Exterior window and metal frames

CK3- Caulk brown/black 300 LF TX0322-121

TX0322-122

TX0322-123

1-2% Chrysotile 1 Good and Non-

Friable Ceiling plenum space Ceiling plenum space CT3- Ceiling tile white 1000-2000

SF

Assumed Assumed 1

Good and Non- Friable

IPT soft secondary, cashier area, soft and hard secondary hallway, break room, IPT hard secondary, Interview room 313, 313A Interview room, and 314 Interview room

Floors CR1- Brick ceramic tile brown 1500 SF Assumed Assumed 1 Good and Non-

Friable

IPT soft secondary, cashier area, soft and hard secondary hallway, break room, IPT hard secondary, Interview room 313, 313A Interview room, and 314 Interview room

Floors MT1- Brick ceramic tile brown 1500 SF Assumed Assumed 1

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Table 2: Summary of Non-Asbestos-Containing Materials

Room Number(s Location of Material

Material Description

Estimated Quantity

Sample Number

Analytical Results

Hazard Ranking and Condition of

Non-Asbestos Containing

Material IPT soft secondary, cashier area, soft secondary hallway, hard secondary hallway, break room, CPT Passenger Chief, Room 308 women restroom, men restroom, room 310 CPB laboratory, room

311, conference room/IPT Passenger Chief, room 313, room

314, Interview room, 313A Interview room, Supervisor office/Command center, Seizure processing room

Ceilings CT1-Ceiling Tile, white

2’ x 2’ random fissures

Not Applicable TX0322-001

TX0322-002

TX0322-003

None Detected 0 Good and Non-

Friable

Room 318 Interview room and file/copier room

Ceilings CT2-Ceiling Tile, white

2’ x 2’ random large fissures

Not Applicable TX0322-104

TX0322-105

TX0322-106

None Detected 0 Good and Friable

IPT soft secondary, cashier area, , break room, CPT Passenger Chief, room, room 311, conference room/IPT Passenger Chief, room

313 Interview room, 313A Interview room, room 314, Supervisor office/Command center, Seizure processing room, Room 308 women restroom, men restroom, penthouse mechanical room

Walls WB1-Wallboard Not Applicable

TX0322-006

TX0322-007

TX0322-008

TX0322-009

TX0322-010

TX0322-011

TX0322-012

None Detected

Good and Friable

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

Room Number(s Location of Material

Material Description

Estimated Quantity

Sample Number

Analytical Results

Hazard Ranking and Condition of

Non-Asbestos Containing

Material IPT soft secondary, cashier area, break room, CPT Passenger Chief, room, room 311, conference room/IPT Passenger Chief, room 313 Interview room, 313A Interview room, Supervisor office/Command center, Seizure processing room, Room 308 women restroom, men restroom, penthouse mechanical room

Walls JC1-Joint compound, white

Not Applicable TX0322-013

TX0322-014

TX0322-015

TX0322-016

TX0322-017

TX0322-018

TX0322-019

None Detected 0 Damaged and Non-

Friable

IPT soft secondary, cashier area, break room, room 311, file/copier room, Supervisor office/Command center, Seizure processing room, IPT hard secondary, CBP laboratory room 310, interview room 318

Walls WV1-Wall vinyl base cove 4”, brown

Not Applicable TX0322-020

TX0322-021

TX0322-022

None Detected 0 Good and Friable

IPT soft secondary, cashier area, break room, room 311, file/copier room, Supervisor office/Command center, Seizure processing room, IPT hard secondary, CBP laboratory room 310, interview room 318

Walls WVM1-Mastic associated with Wall vinyl base cove 4”, brown

Not Applicable TX0322-023

TX0322-024

TX0322-025

None Detected 0 Good and Friable

CPT Passenger Chief office, room, conference room/IPT Passenger

Chief, and file/copier room, Walls WV2-Wall vinyl base cove 6”, brown

Not Applicable TX0322-026

TX0322-027

TX0322-028

None Detected 0

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Room Number(s Location of Material

Material Description

Estimated Quantity

Sample Number

Analytical Results

Hazard Ranking and Condition of

Non-Asbestos Containing

Material CPT Passenger Chief, room, conference room/IPT Passenger Chief, and file/copier room, Walls WVM2-Mastic associated with WV2-Wall vinyl base cove 6”, brown

Not Applicable TX0322-029

TX0322-030

TX0322-031

None Detected 0 Good and Non-

Friable

IPT soft secondary, soft secondary hallway, hard secondary hallway, room 310 CPB laboratory, janitor room 317 interview room 318, file/copier room, detention cells 1,

2. 3, and 4

Ceilings and Walls PL1-Plasrer /Concrete

Not Applicable TX0322-032

TX0322-033

TX0322-034

TX0322-035

TX0322-036

None Detected 0 Good and Non-

Friable

Men’s and women’s restrooms Sinks and toilets CK1-Caulk white Not Applicable TX0322-040

TX0322-041

TX0322-042

None Detected 0 Good and Non-

Friable

IPT soft secondary, cashier area, soft secondary hallway, hard secondary hallway, break room, IPT hard secondary, Interview room 313, 313A Interview room, and 314 Interview room.

Floors GR1-Grout, brown associated with CR1 ceramic brick tile

Not Applicable TX0322-046

TX0322-047

TX0322-048

None Detected 0 Good and Non-

Friable

IPT soft secondary (holding cell hallway, room 311, supervisor office –Command Center, and seizure processing room

Floors FT1- Floor tile 12” x 12”, white mottled gray

Not Applicable TX0322-052

TX0322-053

TX0322-054

None Detected 0 Good and Non-

Friable

IPT soft secondary (holding cell hallway, room 311, supervisor office –Command Center, and seizure processing room

Floors FTM1- mastic associated with FT1- Floor tile

12” x 12”, white mottled gray

Not Applicable TX0322-055

TX0322-056

TX0322-057

None Detected 0

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

Room Number(s Location of Material

Material Description

Estimated Quantity

Sample Number

Analytical Results

Hazard Ranking and Condition of

Non-Asbestos Containing

Material CPT Passenger Chief office Floors CM1-Carpet mastic yellow-brown

Not Applicable TX0322-058

TX0322-059

TX0322-060

None Detected 0 Good and Non-

Friable

Men’s and women’s restrooms Floors CR2-Ceramic tile tan 12” x 12”

Not Applicable TX0322-061

TX0322-062

TX0322-063

None Detected 0 Good and Non-

Friable Men’s and women’s restrooms Floors GR2- grout, brown associated with CR2-

Ceramic tile tan 12” x 12”

Not Applicable TX0322-064

TX0322-065

TX0322-066

None Detected 0 Good and Non-

Friable

Men’s and women’s restrooms Floors MT2- Mortar, gray associated with CR2- Ceramic tile tan

12” x 12”

Not Applicable TX0322-067

TX0322-068

TX0322-069

None Detected Trace <1% Chrysotile

Good and Non-

Friable

CBP Laboratory room 310, IPT Passenger Chief office-conference room, file/copier room

Floors FT2- Floor tile vinyl, 12”x 12” tan mottled gray/brown

Not Applicable TX0322-070

TX0322-071

TX0322-072

None Detected 0 Good and Non-

Friable

CBP Laboratory room 310, IPT Passenger Chief office-conference room, file/copier room

Floors FTM2-Mastic, tan associated with FT2- Floor tile vinyl, 12”x 12” tan mottled gray/brown

Not Applicable TX0322-073

TX0322-074

TX0322-075

None Detected 0 Good and Non-

Friable

Janitor room 317 also may be where plaster walls are found.

Walls BB1-Brick block, orange

Not Applicable TX0322-082

TX0322-083

TX0322-084

None Detected 0

Building 3 J&L Secondary GSA Building # TX0322 Termination At I35 Laredo, Texas 78040

Room Number(s Location of Material

Material Description

Estimated Quantity

Sample Number

Analytical Results

Hazard Ranking and Condition of

Non-Asbestos Containing

Material Mechanical room penthouse, janitor room, ceiling plenum space

Ducts and pipes DS2- Duct/pipe sealant white

(new)

Not Applicable TX0322-088

TX0322-089

TX0322-090

None Detected 0 Good and Non-

Friable Roof and canopy roof Roof RT1-Roof tar black Not Applicable TX0322-100

TX0322-101

TX0322-102

None Detected 0 Good and Non-

Friable Exterior Windows and metal frame joints PL2-Plaster,white

/gray Not Applicable TX0322-107

TX0322-108

TX0322-109

TX0322-110

TX0322-111

None Detected 0 Good and Non-

Friable

Room 311 Walls TX1-Texture, wall, white

Not Applicable TX0322-112

TX0322-113

TX0322-114

None Detected 0 Good and Non-

Friable Break room and 310 CBP

Laboratory Sink SC1_Sink

Undercoating, white

Not Applicable TX0322-115

TX0322-116

TX0322-117

None Detected 0 Good and Non-

Friable Ceiling plenum Ducts DM3- Duct mastic yellow Not Applicable TX0322-037

TX0322-038

TX0322-039

None Detected 0

Building 3 J&L Secondary GSA Building # Tx0322 Termination At I35 Laredo, Texas 78040

APPENDIX C

LABORATORY RESULTS

DEPARTMENT OF HEALTH & HUMAN SERVICES Program Support Center

Federal Occupational Health Service PO Box 25145 Bldg 41, Ent E-1, Rm 190 Denver Federal Center Denver Co 80225-0145 Phone: 303-236-0076 x 603 Fax: 303-236-3440February 7, 2013

LGN B1381983

Scott W. Fontenarosa Federal Occupational Health 1301 Young Street, Suite 772 Dallas, TX 75202

Dear Mr. Fontenarosa:

Enclosed are the results of the analysis of 122 bulk materials from General Services Administration TX0322, Laredo TX, submitted to the Division of Federal Occupational Health (DFOH) National Environmental Reference Laboratory (NERL) Asbestos/Fine Particle Analytical Division in Denver, Colorado, for asbestos analysis. These samples were received at NERL on February 1, 2013. The methods used for this evaluation involve stereo- and polarized-light microscopy (PLM) in compliance with guidelines established by EPA in its Method For The Determination Of Asbestos In Bulk Building Materials (EPA-600/R-93-116). The DFOH laboratory services are currently accredited for bulk asbestos analysis by the National Voluntary Laboratory Accreditation Program (NVLAP) of the National Institute of Standards and Technology (NIST). This report may not be used to claim product endorsement by NVLAP or other U.S.

Government agency. This report may not be reproduced except in full, without the written approval of NERL. Our NVLAP laboratory code number is 901015-0.

The results given, which pertain only to the materials submitted for testing, are listed in Table 1. Details of this report will not be issued to any person or agency not associated with you or the GSA. The EPA method guidelines were developed for use in evaluating friable materials. Point-count reanalysis of materials is recommended to confirm trace or low-percentage PLM results. If you have questions regarding the content of this report, analytical procedures or methods, asbestos evaluation or abatement, please contact NERL directly at (303) 236-3455 ext 603.

LABORATORY COORDINATOR LABORATORY DIRECTOR

MARK A. STEINER MS CDR ROBERT A. GIBBS MS REHS

Geologist/Microscopist Senior Program Manager

TABLE 1

DIVISION OF FEDERAL OCCUPATIONAL HEALTH

NERL/AFPAD POLARIZED LIGHT MICROSCOPY (PLM) BRANCH

LGN: B1381983

PROJECT I.D.: General Services Administration TX0322, Termination at Bldg 3 USBS

Laredo, Texas REPORT DATE: February 4, 2013

NVLAP LAB CODE: 901015-0

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-01: No Ceiling Tile: off/white, None Detected Cellulose 30 0 heterogeneous, Fibrous Glass 40 friable, fibrous TX0322-02: No Ceiling Tile: off/white, None Detected Cellulose 30 0 heterogeneous, Fibrous Glass 40 friable, fibrous TX0322-03: No Ceiling Tile: off/white, None Detected Cellulose 30 0 heterogeneous, Fibrous Glass 40 friable, fibrous TX0322-04: No Ceiling Tile: off/white, None Detected Cellulose 30 0 heterogeneous, Fibrous Glass 40 friable, fibrous TX0322-05: No Ceiling Tile: off/white, None Detected Cellulose 30 0 heterogeneous, Fibrous Glass 40 friable, fibrous TX0322-06: No Wall Board: pink/tan, None Detected Cellulose 37 0 heterogeneous, Fibrous Glass 3 friable, fibrous TX0322-07: No Wall Board: pink/tan, None Detected Cellulose 27 0 heterogeneous, Fibrous Glass 3 friable, fibrous TX0322-08: No Wall Board: pink/tan, None Detected Cellulose 12 0 heterogeneous, Fibrous Glass 3 friable, fibrous

Page 02 B1381983 NVLAP Lab Code 901015-0

(CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-09: No Wall Board: white/tan, None Detected Cellulose 12 0 heterogeneous, Fibrous Glass 3 friable, fibrous TX0322-10: No Wall Board: pale pink/tan, None Detected Cellulose 17 0 heterogeneous, Fibrous Glass 3 friable, fibrous TX0322-11: No Wall Board: white/tan, None Detected Cellulose 11 0 heterogeneous, Fibrous Glass 4 friable, fibrous TX0322-12: No Wall Board: pink/tan, None Detected Cellulose 23 0 heterogeneous, Fibrous Glass 2 friable, fibrous TX0322-13: No Compound: white, None Detected None 0 homogeneous, friable, nonfibrous TX0322-14: No Compound: white, None Detected None 0 homogeneous, friable, nonfibrous TX0322-15: No Compound: white, None Detected Talc 1 0 homogeneous, friable, nonfibrous TX0322-16: No Compound: white, None Detected Talc 1 0 homogeneous, friable, nonfibrous TX0322-17: No Compound: white, None Detected Talc 1 0 homogeneous, friable, nonfibrous TX0322-18: No Compound: white, None Detected None 0 homogeneous, friable, nonfibrous

Page 03 B1381983 NVLAP Lab Code 901015-0

(CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-19: No Compound: white, None Detected Talc 1 0 homogeneous, friable, nonfibrous TX0322-20: No Base Cove: dark gray, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-22: No Base Cove: dark brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-22: No Base Cove: dark brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-23: No Mastic: brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-24: No Mastic: cream, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-25: No Mastic: brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-26: No Base Cove: black, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-27: No Base Cove: gray/brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-28: No Base Cove: gray/brown, None Detected None 0 nonfriable, nonfibrous

Page 04 B1381983 NVLAP Lab Code 901015-0

TABLE 1 (CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-29: No Mastic: tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-30: No Mastic: clear tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-31: No Mastic: clear tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-32: No Plaster: off white, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-33: No Plaster: off white, None Detected Fibrous glass 1 0 homogeneous, nonfriable, nonfibrous TX0322-34: No Plaster: off white, None Detected Fibrous glass 1 0 homogeneous, nonfriable, nonfibrous TX0322-35: No Plaster: cream, None Detected Fibrous glass 1 0 homogeneous, nonfriable, nonfibrous TX0322-36: No Plaster: cream, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-37: No Duct Mastic: cream, None Detected Wollastonite 8 0 homogeneous, nonfriable, nonfibrous TX0322-38: No Duct Mastic: cream, None Detected Wollastonite 10 0 homogeneous, nonfriable, nonfibrous TX0322-39: No Duct Mastic: cream, None Detected Wollastonite 5 0

Page 05 B1381983 NVLAP Lab Code 901015-0

(CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-40: No Caulk: white, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-41: No Caulk: white, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-42: No Caulk: white, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-43 to 45: SAMPLES NOT COLLECTED TX0322-46: No Grout: brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-47: No Grout: brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-48: No Grout: brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-49 to 51: SAMPLES NOT COLLECTED TX0322-52: No Floor Tile: white + gray, None Detected None 0 homogeneous, nonfriable, nonfibrous

Floor Tile: white, None Detected None 0 Homogeneous, nonfriable, nonfibrous TX0322-53: No Floor Tile: white + gray, None Detected None 0 homogeneous, nonfriable, nonfibrous

Floor Tile: white, None Detected None 0 Homogeneous, Page 06 B1381983 NVLAP Lab Code 901015-0

(CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-54: No Floor Tile: white + gray, None Detected None 0 homogeneous, nonfriable, nonfibrous

Floor Tile: white, None Detected None 0 Homogeneous, nonfriable, nonfibrous TX0322-55: No Mastic/Debris: black, None Detected None 0 heterogeneous, nonfriable, nonfibrous

Mastic: clear yellow, None Detected None 0 Homogeneous, nonfriable, nonfibrous TX0322-56: No Mastic: black/tan, None Detected None 0 heterogeneous, nonfriable, nonfibrous TX0322-57: No Mastic: black, None Detected None 0 heterogeneous, nonfriable, nonfibrous

Mastic: tan, None Detected None 0 Homogeneous, nonfriable, nonfibrous TX0322-58: No Mastic: light brown None Detected Synthetics 2 0 homogeneous, nonfriable, nonfibrous TX0322-59: No Mastic: light brown None Detected Synthetics 1 0 homogeneous, nonfriable, nonfibrous TX0322-60: No Mastic: light brown None Detected Synthetics 1 0 homogeneous, nonfriable, nonfibrous TX0322-61: No Ceramic Tile: brown + tan, None Detected None 0

Page 07 B1381983 NVLAP Lab Code 901015-0

(CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-62: No Ceramic Tile: brown + tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-63: No Ceramic Tile: brown + tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-64: No Grout: brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-65: No Grout Grains: brown, None Detected None 0 homogeneous, friable, nonfibrous TX0322-66: No Grout: light brown, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-67: Yes Mortar: tan + gray, Chrysotile <1 None <1 homogeneous, nonfriable, nonfibrous TX0322-68: No Mortar: tan + gray, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-69: No Mortar: tan, None Detected Synthetics 1 0 homogeneous, nonfriable, nonfibrous TX0322-70: No Floor Tile: cream + gray, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-71: No Floor Tile: cream + gray, None Detected None 0

Page 08 B1381983 NVLAP Lab Code 901015-0

(CONTINUED)

--Calibrated Visual Estimate Percentage---

SAMPLE ASBESTOS ASBESTIFORM OTHER FIBROUS TOTAL %

NUMBER PRESENT? MINERAL FIBERS CONSTITUENTS ASBESTOS

TX0322-72: No Floor Tile: cream + gray, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-73: No Mastic: tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-74: No Mastic: tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-75: No Mastic: tan, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-76: Yes Floor Tile: cream, Chrysotile 1-2 None 1-2 homogeneous, nonfriable, nonfibrous TX0322-77: Yes Floor Tile: cream, Chrysotile 1-2 None 1-2 homogeneous, nonfriable, nonfibrous TX0322-78: Yes Floor Tile: cream, Chrysotile 1-2 None 1-2 homogeneous, nonfriable, nonfibrous TX0322-79: No Mastic: amber + black, None Detected None 0 heterogeneous, nonfriable, nonfibrous TX0322-80: No Mastic: yellow, None Detected None 0 homogeneous, nonfriable, nonfibrous TX0322-81: Yes Mastic: black + yellow, Chrysotile 3-6 None 3-6 heterogeneous, Page 09 B1381983…