Renovate IFR to Training and Fitness Room, U. S. Border Patrol Houlton Sector Headquarters, Hodgdon, Maine
Solicitation number
GS-01P-15-BZ-C-0004
Issued by

About this file

Drawings

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

96 CALAIS RD, HODGDON, ME

PROPERTY OF THE UNITED STATES GOVERNMENT.

COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE

DRAWINGS AND/OR DOCUMENTS WITHOUT THE EXPLICIT

PERMISSION OF THE U.S. GENERAL SERVICES

ADMINISTRATION IS PROHIBITED. DISTRIBUTION TO THOSE

WITH OTHER THAN A NEED TO KNOW IS STRICTLY FORBIDDEN.

INTERNATIONAL BUILDING CODE SUMMARY

303 ASSEMBLY GROUP A

303.1.1 SMALL BUILDINGS AND TENANT SPACES

A BUILDING OR TENANT SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT

LOAD OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.

(EXERCISE ROOM)

303.4 ASSEMBLY (A-3) W/O FIXED SEATS TRAINING ROOM (SIMILAR TO LECTURE HALLS)

304 BUSINESS GROUP B

304.1 BUSINESS AREAS (TRAINING AND SKILL DEVELOPMENT NOT WITHIN A SCHOOL

OR ACADEMIC PROGRAM)

307.1(1)MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS

POSING A PHYSICAL HAZARD

MATERIAL - COMBUSTIBLE LIQUID

CLASS - IIIB

STORAGE - LIQUID GALLONS - 13,200 (ACTUAL 506 GALLONS)

311 STORAGE GROUP S-1

311.2 MODERATE-HAZARD STORAGE, GROUP S-1. BUILDINGS OCCUPIED FOR STORAGE

USES THAT ARE NOT CLASSIFIED AS GROUP S-2.

MOTOR VEHICLE REPAIR GARAGES COMPLYING WITH THE MAXIMUM ALLOWABLE

QUANTITIES OF HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1)

-MOTOR OIL STORAGE (NEW AND USED) ~506 GALLONS

406 MOTOR-VEHICLE-RELATED OCCUPANCIES

406.8 REPAIR GARAGES (EXISTING ADJACENCY)

406.8.1 MIXED USES. MIXED USES SHALL BE ALLOWED IN THE SAME BUILDING AS A

REPAIR GARAGE SUBJECT TO THE PROVISIONS OF SECTION 508.1

508 MIXED USE AND OCCUPANCY

TABLE 508.4 REQUIRED SEPARATION OF OCCUPANCIES (HOURS)

OCCUPANCY A,B AND S-1 2 HOURS ASSEMBLIES (BUILDINGS NOT EQUIPPED

THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM)

508.4.4 SEPARATION. INDIVIDUAL OCCUPANCIES SHALL BE SEPARATED FROM ADJACENT

OCCUPANCIES IN ACCORDANCE WITH TABLE 508.4.

602 CONSTRUCTION CLASSIFICATION N/A FOOTPRINT AND HEIGHT TO REMAIN THE SAME

708 FIRE PARTITIONS

708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE FLOOR

ASSEMBLY TO THE UNDERSIDE OF THE ROOF DECK ABOVE, AND SHALL BE SECURELY

ATTACHED THERETO.

1004 OCCUPANT LOAD

TRAINING ROOM ASSEMBLY (A-3) W/O FIXED SEATS 57 OCCUPANTS

TRAINING OFFICE (B) 2 OCCUPANTS

EXERCISE ROOM (B) 6 OCCUPANTS

1018 CORRIDORS

1018.1 CONSTRUCTION. CORRIDORS SHALL BE FIRE-RESISTANCE RATED IN

ACCORDANCE WITH TABLE 1018.1. THE CORRIDOR WALLS REQUIRED TO BE FIRE

RESISTANCE RATED SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS.

TABLE 1018.1 CORRIDOR FIRE-RESISTANCE RATING

OCCUPANCIES A, B & S - OCCUPANT LOAD SERVED BY CORRIDOR GREATER THAN 30 -

REQUIRED FIRE-RESISTANCE RATING (HOURS) 1 WITHOUT SPRINKLER SYSTEM.

NOTES:

1. ALL WORK SHALL BE IN STRICT CONFORMANCE WITH THE REQUIREMENTS OF THE

FOLLOWING STANDARDS:

1.1. GSA P-100

1.2. NTERNATIONAL BUILDING CODE, 2012 EDITION

1.3. NFPA 101 - LIFE SAFETY CODE, 2012 EDITION

NFPA 101: LIFE SAFETY CODE SUMMARY

13.2.6.2 EXITS SHALL BE ARRANGED SO THAT THE TOTAL LENGTH OF TRAVEL FROM ANY POINT

TO REACH AN EXIT SHALL NOT EXCEED 200 FT IN ANY ASSEMBLY OCCUPANCY

TABLE A.7.6 ASSEMBLY

TABLE A.7.6 BUSINESS

EGRESS TRAVEL CRITERIA MAXIMUM ALLOWABLE ACTUAL

COMMON PATH (FT) 20' 3'-8"

DEAD END (FT) 20' n/a

TRAVEL DISTANCE (FT) 200' 160'

8.3.3 FIRE DOORS AND WINDOWS.

8.3.3.1 OPENINGS REQUIRED TO HAVE A FIRE PORTECTION RATING BY TABLE 8.3.4.2

SHALL BE PROTECTED BY APPROVED,LISTED, LABELED FIRE DOOR ASSEMBLIES AND

FIRE WINDOW ASSEMBLIES AND THEIR ACCOMPANYING HARDWARE.

8.3.5 PENETRATIONS

8.3.5.1 FIRESTOP SYSTEMS AND DEVICES REQUIRED. PENETRATIONS FOR CABLES,

CABLE TRAYS, CONDUITS, PIPES, TUBES, COMBUSTION VENTS AND EXHAUST VENTS,

WIRES AND SIMILAR ITEMS TO ACCOMMODATE ELECTRICAL, MECHANICAL, PLUMBING

AND COMMUNICATION SYSTEMS THAT PASS THROUGH A WALL, FLOOR, OR FLOOR/

CEILING ASSEMBLY CONSTRUCTED AS A FIRE BARRIER SHALL BE PROTECTED BY A

FIRESTOP DEVICE. THE FIRESTOP SYSTEM OR DEVICE SHALL BE TESTED IN

ACCORDANCE WITH ASTM E 814, OR ANSI/UL 1479.

12.2.3.8 MINIMUM CORRIDOR WIDTH

THE WIDTH OF ANY EXIT ACCESS CORRIDOR SERVING 50 OR MORE PERSONS SHALL

BE NOT LESS THAN 44"

GSA PBS-P100 SUMMARY

1.2.1 REPAIRS & ALTERATION

ALL NEW WORK IS REQUIRED TO MEET THE APPLICABLE NATIONAL CODES AND

STANDARDS ADOPTED BY GSA. IF A MAJOR PORTION OF THE BUILDING IS BEING

RENOVATED, THE SPECIFIC CODES MUST BE EVALUATED TO DETERMINE IF THE ENTIRE

BUILDING MUST BE BROUGHT INTO COMPLIANCE WITH THE CODE.

1.4.3 NFPA LIFE SAFETY CODE

GSA HAS ADOPTED THE TECHNICAL EGRESS REQUIREMENTS OF THE NATIONAL FIRE

PROTECTION ASSOCIATION (NFPA), LIFE SAFTY CODE (NFPA 101) IN LIEU OF THE

TECHNICAL EGRESS REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE (IBC).

3.6.3.5 FIRE PERFORMANCE AND SMOKE DEVELOPMENT

INTERIOR WALL AND CEILING FINISH MATERIALS SHALL COMPLY WITH THE APPLICABLE

REQUIREMENTS IN THE INTERNATIONAL BUILDING CODE (IBC) FOR FIRE PERFORMANCE

AND SMOKE DEVELOPMENT.

7.4 MEANS OF EGRESS

THE MEANS OF EGRESS REQUIREMENTS FOR THE BUILDING MUST MEET THE

REQUIREMENTS IN NFPA 101. THE TECHNICAL EGRESS REQUIREMENTS IN NFPA 101 MUST

BE USED IN PLACE OF THE TECHNICAL REQUIREMENTS IN THE IBC.

7.5 INTERIOR FINISHES

THE INTERIOR FINISH REQUIREMENTS FOR WALLS, CEILINGS, FLOORS, DRAPERIES,

CURTAINS, AND MOVABLE PARTITIONS MUST MEET THE REQUIREMENTS IN THE IBC.

7.6 FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEMS

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEMS MUST BE INSTALLED IN

ACCORDANCE WITH THE REQUIREMENTS IN NFPA 72, THE IBC, AND THE APPROPRIATE

GSA FIRE ALARM SYSTEM SPECIFICATION.

7.6.3 SMOKE DETECTORS

SMOKE DETECTORS MUST BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS IN

NFPA 72 AND THE IBC

7.9.5 PORTABLE FIRE EXTINGUISHERS AND CABINETS

PORTABLE FIRE EXTINGUISHERS AND CABINETS MUST BE INSTALLED IN ACCORDANCE

WITH THE REQUIREMENTS IN THE IBC.

EGRESS TRAVEL CRITERIA MAXIMUM ALLOWABLE ACTUAL

COMMON PATH (FT) 75' 49'

DEAD END (FT) 50' n/a

TRAVEL DISTANCE (FT) 200' 101'

PISTOL AREA

128B

SHOOTING

AREA

128A

STORAGE /

GARAGE

GENERATOR

WEIGHT

ROOM

ORDNANCE

BOILER

JAN

LAN ROOM

ENFORCEMENT

LUNCH ROOM

MENS

OFFICE

ELECTRONICS

SHOP

GARAGE OFFICE

129A

GARAGE /

PARKING AREA

CORR

TRAP ACCESS

AREA

128C

PISTOL AREA

128B

SHOOTING AREA

128A

STORAGE /

GARAGE

GENERATOR

WEIGHT

ROOM

ORDNANCE

BOILER

SUPPLY

ENFORCEMENT

LUNCH ROOM

MENS

OFFICE

ELECTRONICS

SHOP

GARAGE OFFICE

129A

GARAGE /

PARKING AREA

CORR

TRAP ACCESS

AREA

128C

JAN

EXERCISE ROOM

TRAINING

OFFICE

TRAINING ROOM

CORRIDOR

STORAGE SPACE

129B

STORAGE /

GARAGE

GENERATOR

WEIGHT

ROOM

ORDNANCE

BOILER

JAN

LAN ROOM

ENFORCEMENT

CONF ROOM

OFFICE

GSA OFFICE

LUNCH ROOM

MENS

OFFICE

ELECTRONICS

SHOP

GARAGE OFFICE

129A

GARAGE /

PARKING AREA

LOBBY

VEST

CORR

EXERCISE

ROOM

TRAINING

OFFICE

TRAINING ROOM

CORRIDOR

STORAGE

SPACE

129B

STORAGE /

GARAGE

GENERATOR

WEIGHT

ROOM

ORDNANCE

BOILER

JAN

LAN ROOM

ENFORCEMENT

LUNCH ROOM

MENS

OFFICE

ELECTRONICS

SHOP

GARAGE OFFICE

129A

GARAGE /

PARKING AREA

CORR

TYPE DESCRIPTION VOLT MANUFACTURER (OR EQUAL) LAMPS MOUNTING CONTROL NOTES

A 2x2 RECESSED LED 120 FINELITE

HPR SERIES LED GRID OCCUPANCY SENSOR PROVIDE WITH DIMMABLE DRIVER;

PROVIDE IC-RATED FIXTURE

B 1x4 LINEAR LED 120 FINELITE

LCR SERIES LED CABLE/

PENDANT OCCUPANCY SENSOR MOUNT APPROXIMATELY 10'-0" ABOVE

FINISHED FLOOR

LED EXIT SIGN PROVIDED WITH

MAINTENANCE FREE NICKEL-CADMIUM

BATTERY AND SELF-DIAGNOSITC

ELECTRONICS.

120 DUAL-LITE

EVE SERIES LED WALL/

CEILING N/A CONNECT TO UNSWITCHED LEG OF LOCAL

LIGHTING CIRCUIT

DUAL HEAD EMERGENCY FIXTURE PROVIDED

WITH MAINTENANCE-FREE BATTERY,

SELF-DIAGNOSTIC ELECTRONICS, AND WIRE

GUARD

120 DUAL-LITE

EVR SERIES LED WALL N/A

PROVIDE MODEL WITH CAPACITY TO

SUPPLY REMOTE HEAD

CONNECT TO UNSWITCHED LEG OF LOCAL

LIGHTING CIRCUIT

EMERGENCY REMOTE LIGHTING HEADS,

WET LOCATION LISTED 6 DUAL-LITE

EVO SERIES LED WALL N/A

SHALL BE COMPATIBLE WITH AND

POWERED FROM LOCAL EMERGENCY

FIXTURE

OCCUPANCY SENSOR, DUAL TECHNOLOGY -

PASSIVE INFRARED (PIR)/ULTRASONIC 120 HUBBELL

BUILDING AUTOMATION SYSTEMS N/A CEILING PIR/ULTRASONIC

PROVIDE WITH ALL NECESSARY POWER

PACKS AND RELAYS FOR COMPLETE

SYSTEM OPERATION

PANELBOARD NO: DP1 SC RATING: 42 KAIC

PANELBOARD TYPE: BRANCH CIRCUITS MOUNTING: SURFACE 150 AMP MCB

PANEL LOCATION: GENERATOR ROOM VOLTAGE:

120/240V, 1-PHASE

AMP BUS (COPPER)

SUPPLIED FROM: PANEL DP

CKT

NO.

TRIP

AMPS

NO.

POLES

WIRE /

CONDUIT

GND.

WIRE

LOAD SERVED

LOAD

VA

φ

LOAD

VA

LOAD SERVED

WIRE /

CONDUIT

GND.

WIRE

NO.

POLES

TRIP

AMPS

CKT

NO.

1 20 1 2#12 / 3/4" #12 LIGHTING - TRAINING ROOM 133

LIGHTING - ROOMS 129B, 130, 131, & 132

2#12 / 3/4" #12 1 20 2

3 20 1 2#12 / 3/4" #12 RECEPTACLES - TRAINING OFFICE 132 QUAD RECEPTACLE - EXERCISE ROOM 131 2#12 / 3/4" #12 1 20 4

5 20 1 2#12 / 3/4" #12 QUAD RECEPTACLE - EXERCISE ROOM 131 QUAD RECEPTACLE - EXERCISE ROOM 131 2#12 / 3/4" #12 1 20 6

7 20 1 2#12 / 3/4" #12 QUAD RECEPTACLE - EXERCISE ROOM 131 RECEPTACLES - ROOMS 130 & 131 2#12 / 3/4" #12 1 20 8

9 20 1 SPARE RECEPTACLES - TRAINING ROOM 133 2#12 / 3/4" #12 1 20 10

11 20 1 2#12 / 3/4" #12 RECEPTACLES - TRAINING ROOM 133 RECEPTACLES - TRAINING ROOM 133 2#12 / 3/4" #12 1 20 12

13 20 1 2#12 / 3/4" #12 RECEPTACLES - TRAINING ROOM 133 RECEPTACLES - STORAGE SPACE 129B 2#12 / 3/4" #12 1 20 14

15 20 1 2#12 / 3/4" #12

RECEPTACLE - TIRE BALANCER (ROOM 129B) RECEPTACLE - WHEEL/RIM UNIT (ROOM 129B)

2#12 / 3/4" #12 1 20 16

17 20 1 2#12 / 3/4" #12 QUAD RECEPTACLE - EXERCISE ROOM 131 QUAD RECEPTACLE - EXERCISE ROOM 131 2#12 / 3/4" #12 1 20 18

19 20 1 2#12 / 3/4" #12 QUAD RECEPTACLE - EXERCISE ROOM 131 QUAD RECEPTACLE - EXERCISE ROOM 131 2#12 / 3/4" #12 1 20 20

21 20 1 2#12 / 3/4" #12 QUAD RECEPTACLE - TRAINING ROOM 133 QUAD RECEPTACLE - TRAINING ROOM 133 2#12 / 3/4" #12 1 20 22

23 20 1 2#12 / 3/4" #12 QUAD RECEPTACLE - TRAINING ROOM 133 SPACE 24

25 20 1 SPARE SPARE 1 20 26

27 20 1 SPARE SPARE 1 20 28

29 20 1 SPARE SPARE 1 20 30

40 2 2#8 / 3/4" #8

CU-1 (NOTE 1)

UH-1 & CUH-1, 2, 3, 4, & 5 (NOTE 1)

2#12 / 3/4" #12 1 20 32

HRV-1, 2, & 3 AND COND. PUMP (NOTE 1)

2#12 / 3/4" #12 1 20 34

30 2 2#10 / 3/4" #10

CU-3 / AC-5 (NOTE 1) CU-2 / AC-4 (NOTE 1)

2#10 / 3/4" #10 2 30

37 38

20 2 2#12 / 3/4" #12

BRANCH BOX & AC-1,2,3 (NOTE 1)

SPACE 40

41 SPACE 42

TOTAL PHASE A LOAD = 0 kVA NOTES:

TOTAL PHASE B LOAD = 0 kVA 1 PROVIDE HACR-RATED BREAKER

TOTAL PHASE C LOAD = 0 kVA

TOTAL CONNECTED LOAD = 0 kVA