GPO Facility Management Suite Renovation Final Submission DRAWINGS 2025-05-02.pdf

PDF 46 MB Posted

Attached to
Government Publishing Office FM Modernization / Construction
Solicitation number
040ADV-26-R-0013
Issued by

About this file

This file is a set of architectural and engineering drawings for the Government Publishing Office (GPO) Facility Management Modernization project located at 732 North Capitol Street NW, Washington, DC 20401. The drawings document a comprehensive renovation of approximately 15,300 square feet on the second floor of Building A, classified as a Level 2 alteration involving facility management, HVAC, office, and restroom modernization.

The project scope encompasses architectural modifications including demolition and new partition construction with sound attenuation, interior finishes (gypsum board ceilings at 9'-6" AFF, luxury vinyl tile and carpet tile flooring, porcelain tile in toilet areas, paint finishes in specified colors), millwork and built-in cabinetry, ADA-compliant door and window modifications, and signage. Mechanical systems include three new air handling units (AHU-1, AHU-2, AHU-3 ranging from 3,690 to 6,845 CFM), variable air volume (VAV) boxes for zone control, heating and cooling coil modifications with steam and chilled water piping, and ductwork distribution. Plumbing work involves installation of new water closets, lavatories, service sinks, and drinking fountains with associated supply and waste piping. Electrical systems include new panelboards (RP-1, RP-2, RP-1A at 208/120V, 400A MCB ratings), lighting with occupancy sensors and dimming controls, receptacle circuits with controlled loads, and data/telecommunications infrastructure. Fire protection systems include modifications to the existing wet pipe sprinkler system, fire alarm devices (smoke detectors, manual pull stations, audio/visual appliances), and duct smoke detectors for HVAC units. The drawings are dated April 2, 2025 (Final Submission) and prepared by EBL Engineers, LLC and Gannett Fleming Transystems, with professional engineering certification required for Maryland licensure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G-001

DRAWING LIST

DRAWING #: SHEET DESCRIPTION:

410-668-8000 FAX 410-668-8001

BALTIMORE, MARYLAND 21234-5701

8005 HARFORD ROAD

EBL ENGINEERS, LLC

COVER SHEET

LOCATION MAP NVICINITY MAP

NO SCALE

N

NO SCALE

FINAL SUBMISSION

APRIL 2, 2025

FM HVAC/OFFICE/RESTROOM MODERNIZATION

US GOVERNMENT PUBLISHING OFFICE

PROJECT LOCATION

PROJECT LOCATION

410-512-4500

BALTIMORE, MARYLAND 21286

300 E. JOPPA ROAD SUITE 200

GANNETT FLEMING TRANSYSTEMS

A-001 A-002 A-003

AD-101

AD-102

AD-201

AD-202

A-100 A-101 A-102 A-201 A-202 A-300 A-310 A-311 A-312 A-401 A-402 A-403 A-500 A-501 A-502 A-503 A-504 A-601 A-602

GENERAL NOTES AND CONDITIONS, ABBREVIATIONS AND SYMBOLS

TYPICAL ADA CLEARANCES AND MOUNTING HEIGHTS

CODE ANALYSIS AND LIFE SAFETY

DEMOLITION - PARTIAL FLOOR PLAN

DEMOLITION - PARTIAL FLOOR PLAN

DEMOLITION - PARTIAL REFLECTED CEILING PLAN

DEMOLITION - PARTIAL REFLECTED CEILING PLAN

NEW WORK - OVERALL FLOOR PLAN

NEW WORK - PARTIAL FLOOR PLAN

NEW WORK - PARTIAL FLOOR PLAN

NEW WORK - PARTIAL REFLECTED CEILING PLAN

NEW WORK - PARTIAL REFLECTED CEILING PLAN

INTERIOR ELEVATIONS

TOILET ROOM ENLARGED PLANS AND ELEVATIONS

TOILET ROOM ENLARGED PLANS AND ELEVATIONS

MILLWORK ENLARGED PLANS AND INTERIOR ELEVATIONS

MILLWORK DETAILS

CEILING AND THRESHOLD DETAILS

SIGNAGE PLANS AND SCHEDULE

PARTITION SCHEDULE

DOOR SCHEDULE AND DETAILS

INTERIOR STOREFRONT SCHEDULE AND DETAILS

INTERIOR STOREFRONT SCHEDULE

FINISH SCHEDULE

NEW WORK - PARTIAL FINISH PLAN

NEW WORK - PARTIAL FINISH PLAN

M-001 M-002 M-101 M-102 M-201 M-202 M-203 M-204 M-401 M-601 M-602

P-401 P-402 P-601

E-001 E-101 E-102 E-103 E-104 E-105 E-201 E-202 E-203 E-204 E-205 E-206 E-401 E-501 E-601

MECHANICAL LEGENDS

MECHANICAL GENERAL NOTES AND ABBREVIATIONS

SECOND FLOOR PART PLAN - MECHANICAL DEMOLITION

SECOND FLOOR PART PLAN - MECHANICAL DEMOLITION

SECOND FLOOR PART PLAN - MECHANICAL

SECOND FLOOR PART PLAN - MECHANICAL

SECOND FLOOR PART PLAN - MECHANICAL PIPING

SECOND FLOOR PART PLAN - MECHANICAL PIPING

MECHANICAL PART PLANS

MECHANICAL SCHEDULES AND DETAILS

MECHANICAL CONTROLS

PLUMBING PART PLANS - DEMOLITION

PLUMBING PART PLANS

PLUMBING SCHEDULES, RISERS AND DETAILS

ELECTRICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES

SECOND FLOOR PART PLAN - ELECTRICAL LIGHTING - DEMOLITION

SECOND FLOOR PART PLAN - ELECTRICAL LIGHTING - DEMOLITION

SECOND FLOOR PART PLAN - ELECTRICAL POWER - DEMOLITION

SECOND FLOOR PART PLAN - ELECTRICAL POWER - DEMOLITION

FIRST FLOOR PART PLAN - ELECTRICAL POWER - DEMOLITION

SECOND FLOOR PART PLAN - ELECTRICAL LIGHTING - WORK

SECOND FLOOR PART PLAN - ELECTRICAL LIGHTING - WORK

SECOND FLOOR PART PLAN - ELECTRICAL POWER - WORK

SECOND FLOOR PART PLAN - ELECTRICAL POWER - WORK

SECOND FLOOR PART PLAN - ELECTRICAL LIGHTING - CALCULATIONS

SECOND FLOOR PART PLAN - ELECTRICAL LIGHTING - CALCULATIONS

ELECTRICAL PART PLANS

ELECTRICAL DETAILS

ELECTRICAL SCHEDULES

732 NORTH CAPITOL ST NW

WASHINGTON, DC 20401

FA-001

FA-101

FA-102

FA-201

FA-202

FP-001

FP-101

FP-102

FP-201

FP-202

FIRE ALARM GENERAL NOTES, LEGEND AND ABBREVIATIONS

SECOND FLOOR PART PLAN - FIRE ALARM DEMOLITION

SECOND FLOOR PART PLAN - FIRE ALARM DEMOLITION

SECOND FLOOR PART PLAN - FIRE ALARM

SECOND FLOOR PART PLAN - FIRE ALARM

FIRE PROTECTION GENERAL NOTES, LEGEND AND ABBREVIATIONS

SECOND FLOOR PART PLAN - FIRE PROTECTION DEMOLITION

SECOND FLOOR PART PLAN - FIRE PROTECTION DEMOLITION

SECOND FLOOR PART PLAN - FIRE PROTECTION

SECOND FLOOR PART PLAN - FIRE PROTECTION

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road Baltimore, Maryland 21234-5701

Tel: (410) 668-8000 E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

GANNETT FLEMING TRANSYSTEMS

300 East Joppa Road Suite 200

Baltimore, MD 21286

410.512.4500 www.transystems.com

MODERNIZATION

G-001

AJK

MPS

COVER SHEET

23408

08/25/2026

G:

\p ro je ct s\

\2

.0

\c ad d\

Bi d

Su bm iss io n\

3.

G-

1.

dw g, /1 1/

1:

:3

AM

, P H

O

LT

H

AU

A-001

GENERAL NOTES AND

CONDITIONS,

ABBREVIATIONS AND

SYMBOLS

GENERAL NOTES & CONDITIONS

1. GENERAL NOTES FOUND ON THIS SHEET APPLY TO ALL DRAWINGS

2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL STATE, COUNTY AND LOCAL

CODES, REGULATIONS AND ORDINANCES. MATERIAL EQUIPMENT, INSTALLATION, AND

PROCEDURES SHALL BE IN STRICT ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF

THE LATEST CURRENT EDITION OF THE REFERENCED DOCUMENTATION.

3. THE INTENT OF THESE DRAWINGS IS FOR THE CONTRACTOR TO PROVIDE ALL LABOR,

MATERIAL, FINISHES, EQUIPMENT, INSTALLATION AND SERVICES NECESSARY FOR AND

INCIDENTAL WITH THE WORK, TO PROVIDE THE OWNER WITH A COMPLETE PROJECT

INCLUSIVE OF ALL SYSTEMS.

4. ACTUAL FIELD CONDITIONS MAY VARY FROM THOSE INDICATED. SHOULD ACTUAL CONDITIONS

DIFFER FROM THOSE ORDINARILY ENCOUNTERED AND GENERALLY RECOGNIZED AS

INHERENT IN WORK OF THE CONTRACTOR PROVIDED FOR IN THE CONTRACT, THE

CONTRACTOR SHALL PROMPTLY, BEFORE CONDITIONS ARE DISTURBED, NOTIFY THE OWNER'S

MANAGER. FAILURE TO DO SO MAY MAY WAIVE THE CONTRACTORS RIGHT TO RECEIVE

ADDITIONAL TIME OR CONSIDERATION DUE TO SUCH CONDITIONS.

5. PRIOR TO INITIATING ANY PORTION OF THE WORK, THE CONTRACTOR SHALL VERIFY ALL

DIMENSIONS AND COORDINATE ALL PORTIONS OF THE CONTRACT DOCUMENTS RELATING TO

THAT PORTION OF THE WORK AND AFFECTING ADJOINING PORTIONS. IF DISCREPANCIES

EXIST, THEY SHALL BE REPORTED TO THE ENGINEER AND OWNER FOR CLARIFICATION

AND/OR RESOLUTION BEFORE COMMENCING SUCH WORK.

6. BY SUBMITTING A BID PROPOSAL, THE CONTRACTOR CERTIFIES THAT THEY HAVE VISITED THE

SITES AND UNDERSTAND THE COMPLETE SCOPE OF WORK, WHICH IS INCLUDED IN THE

PROPOSAL.

7. DEFINITIONS: "PROVIDE" MEANS "FURNISH AND INSTALL". "VERIFY" MEANS "VERIFY IN THE

FIELD AND COORDINATE DIMENSIONS AND DISCREPANCIES."

8. THESE NOTES AND OTHER NOTES ON THE DRAWINGS ARE DIRECTIONS FOR THE

CONTRACTOR'S PERFORMANCE , UNLESS NOTED OTHERWISE (U.N.O). FOR EXAMPLE, THE

VERB "INSTALL" MEANS "CONTRACTOR SHALL INSTALL", "RELOCATE" MEANS "CONTRACTOR

SHALL RELOCATE", ETC.

9. UNLESS NOTED OTHERWISE, NUMBERED DIMENSIONS SHOWN ON DRAWINGS TAKE

PRECEDENCE OVER SCALED DRAWINGS. ALL DIMENSIONS TO BE FIELD VERIFIED.

10. DIMENSIONS OF OPENINGS SHALL BE COORDINATED BY CONTRACTOR WITH EQUIPMENT

REQUIRED. SHOP DRAWINGS SHALL INCLUDE A SCHEDULE OF ACTUAL OPENING DIMENSIONS

AS VERIFIED IN FIELD.

11. DURING THE WORK, ANY CONDITION UNCOVERED THAT CAUSES CONFLICT WITH THE

INTENDED DESIGN MUST BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT.

12. CONTRACTOR SHALL STAGE WORK IN SUCH A WAY AS TO ENSURE SAFE EMERGENCY EGRESS

AT ALL TIMES.

13. BEFORE COMMENCING ANY DEMOLITION, THE CONTRACTOR MUST COORDINATE DEMOLITION

WITH THE PROPOSED WORK AND OTHER DISCIPLINES.

14. THE ARCHITECT SHALL HAVE NO RESPONSIBILITY FOR THE DISCOVERY, PRESENCE,

HANDLING, REMOVAL OR DISPOSAL OF, OR EXPOSURE OF PERSONS TO HAZARDOUS

MATERIALS IN ANY FORM AT THE PROJECT SITE, INCLUDING BUT NOT LIMITED TO ASBESTOS, ASBESTOS PRODUCTS, POLYCHLORINATED BIPHENYL (PCB) OR OTHER TOXIC SUBSTANCES.

CONTRACTOR TO CONTACT ARCHITECT AND OWNER IF THESE ITEMS ARE APPARENT OR

SUSPECTED.

15. OPERATIONS WILL NOT START PRIOR TO 7AM AND END BY 5PM. MON-FRI. WEEKENDS TO BE

AUTHORIZED IN WRITING

16. GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL TRADES.

17. CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY AND FAMILIARIZE THEMSELVES WITH

ACTUAL FIELD CONDITIONS ASSOCIATED WITH WORK UNDER THIS CONTRACT PRIOR TO

SUBMITTING THEIR BID.

18. IT IS THE INTENT THAT ALL WORK SHALL BE COMPLETE IN EVERY RESPECT AND THAT

MATERIAL OR WORK SPECIFICALLY NOT INDICATED ON THE DRAWINGS, BUT NECESSARY TO

COMPLETE THE WORK, SHALL BE PROVIDED.

19. PROVIDE ALL NECESSARY COMPONENTS FOR U.L. LISTED THROUGH PENETRATION SYSTEM

AT RATED FLOORS, CEILINGS AND WALL PENETRATIONS IN ORDER TO MAINTAIN THE THE

REQUIRED ASSEMBLY RATING. RATED WALLS AND OPENINGS NOTED ON PLANS.

20. UNLESS OTHERWISE INDICATED ALL PIPING, CONDUIT, DUCTWORK AND SIMILAR SERVICES

SHALL BE CONCEALED. ALL EXPOSED ELECTRICAL CONDUIT, PIPING, WIRING AND HVAC

EQUIPMENT SHALL BE LOCATED TO MINIMIZE VISIBILITY IN AREAS EXPOSED TO STRUCTURE.

WHERE CONDUIT CANNOT BE CONCEALED IN WALLS, FLOORS, ETC, RUN CONDUIT, PIPE AND

WIRING ADJACENT TO COLUMNS VERTICALLY AND BEAMS HORIZONTALLY. MINIMIZE

EXPOSURE TO THE GREATEST EXTENT POSSIBLE. PAINT ALL EXPOSED MATERIALS TO MATCH

SUBSTRATE FOR ALL EXPOSED CONDUIT ALONG WALLS RUN IN DIRECTION TO MINIMIZE

EXPOSURE.

21. CONSTRUCTION NOTES SPECIFICALLY REFER TO ITEMS NOTED WITH NUMBER OR LETTER

DESIGNATIONS ON THE RESPECTIVE DRAWINGS WHERE THE DESIGNATIONS ARE SHOWN.

22. MOISTURE RESISTANT GYPSUM BOARD AT ALL TOILET ROOM, JANITOR'S CLOSETS, KITCHENS

AND LOCATIONS WHERE MILLWORK IS SHOWN WITH SINK, TYPICAL.

23. SEALANT AND BACKER ROD AT ALL EXPANSION JOINTS LOCATED IN STONE VENEER, REFER

TO BUILDING ELEVATIONS FOR JOINT LOCATIONS.

24. SEALANT AND BACKER ROD ALL CONTROL JOINTS ARE LOCATED IN CONCRETE UNIT MASONRY

(CMU) KNEE WALLS, REFER LOCATIONS ON SHEET X. FOR EXPANSION JOINT LOCATIONS NOT

SHOWN ON THE FLOOR PLAN REFER TO PLAN DETAIL SHEETS XX.

25. PROVIDE SEMI RECESSED EXTINGUISHER CABINETS AND EXTINGUISHER AS REQUIRED BY

NFPA 10. REFER TO LIFE SAFETY PLAN FOR DETAILS.

26. ALL TOILET SIZES VARY BASED UPON ADA REQUIREMENTS REFER TO SHEET A401 FOR

ENLARGED PLANS AND INTERIOR ELEVATIONS.

27. ALL PARTITIONS NOT DESIGNATED, TO BE CONSIDERED WALL TYPE "A".

28. ALL DIMENSIONS, NOTES, FINISHES AND FIXTURES SHOWN ON TYPICAL FLOOR PLANS,

SECTIONS, OR DETAILS SHALL APPLY TO ALL SIMILAR, SYMMETRICAL OR OPPOSITE HAND

PLANS, SECTIONS OR DETAILS.

29. ALL DOOR JAMBS SHALL BE LOCATED 4" FROM INTERSECTING WALL, UNLESS NOTED

OTHERWISE.

30. CONTRACTOR TO PROVIDE AND INSTALL EXIT SIGNS AND EMERGENCY LIGHTING AS REQUIRED

BY APPLICABLE CODES. REFER TO DRAWINGS HEREIN FOR LOCATIONS AND DETAILS.

31. GC TO COORDINATE FLOOR DRAIN LOCATION WITH PLUMBING DRAWINGS, CONCRETE TO BE

SLOPED TO FLOOR DRAINS, TYP.

32. INTERIOR DIMENSIONS SHOWN ARE TO FINISH FACE OF WALL, UNLESS NOTED OTHERWISE.

33. SPRINKLER SYSTEM: THE SPRINKLER SYSTEM SHALL BE DESIGNED TO MINIMIZE EXPOSURE IN

GRILLE AND BANQUET ROOMS. SPRINKLER HEADS IN CEILINGS SHALL BE CENTERED IN TILES

OR SYMMETRICALLY LOCATED IN GYPSUM CEILINGS. IN EXPOSED WOOD CEILINGS SPRINKLER

PIPING IS TO BE PAINTED TO MATCH CEILING. SPRINKLER LAYOUT DRAWINGS TO BE

SUBMITTED TO ARCHITECT AND ENGINEER FOR REVIEW.

34. GENERAL CONTRACTOR TO VERIFY ALL EXISTING UTILITIES

35. GAS SERVICE

36. DOMESTIC WATER

37. SERVICE SANITARY

38. SEWER SERVICE

39. ELECTRIC POWER SOURCE

A/C AIR CONDITION

ACC ACCESSIBLE

ACOUS INSUL ACOUSTICAL INSULATION

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADH ADHESIVE

ADJ ADJACENT, ADJOING, ADJUSTABLE

AFF ABOVE FINISHED FLOOR

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZE

APC ACOUSTICAL PANEL CEILING

ARCH ARCHITECT

AV AUDIO VISUAL

BATT BATTEN

BLDG BUILDING

BLKHD BULKHEAD

BOT BOTTOM

CB CERAMIC BASE

CER CERAMIC

CG CORNER GUARD

CJ CONSTRUCTION JOINT, CONTROL JOINT

CL CENTER LINE

CLR CLEAR, COLOR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CONT CONTINUE

COORD COORDINATE

CORR CORRIDOR

CPT CARPET

CT CERAMIC TILE

CTR CENTER

CYL CYLINDER

D DEEP, DEPTH

DEMO DEMOLITION

DF DRINKING FOUNTAIN

DIA DIAMETER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DIST DISTANCE

DIV DIVIDE, DIVISION

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

E EAST

EA EACH

EL ELEVATION

ELEC ELECTRIC

ELEV ELEVATION

EQ EQUAL

EQUIP EQUIPMENT

EQUIV EQUIVALENT

EW EACH WAY

EXIST EXISTING

EXT EXTERIOR, EXTERNAL

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND EQUIPMENT

FIN FINISH

FIXT FIXTURE

FLR FLOOR

FLR FIN FLOOR FINISH

FLUOR FLUORESCENT

FO FINISHED OPENING

FRP FIBERGLASS REINFORCED PLASTIC

FRZ FREEZER

FT FEET, FIRE TREATED, FOOT

FURN FURNISH, FURNITURE

GA GAGE

GALV GALVANIC, GALVANIZED

GC GENERAL CONTRACTOR

GL GLASS

GLZ GLAZING

GYP GYPSUM

HC HANDICAP

HDPE HIGH DENSITY POLYETHYLENE

HDW HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HT HEIGHT

HVAC

HEATING, VENTILATING, AND AIR

CONDITIONING

INSTL INSTALL

INSUL INSULATION

INT INTERIOR

JAN JANITOR

L ANGLE, LITER

LAM LAMINATE

LAV LAVATORY

LBS POUND

LED LIGHT EMITTING DIODE

LH LEFT HAND

LIN LINEAR

MAINT MAINTENANCE

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEL MELAMINE

MFR MANUFACTURER

MID MIDDLE

MIN MINIMUM, MINUTE

MIRR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTL METAL

N NORTH

NA NOT APPLICABLE

NAR NARROW

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE

OC ON CENTER

OCC OCCUPY

OD OUTSIDE DIAMETER

OF/CI

OWNER FURNISHED/CONTRACTOR

INSTALLED

OFF OFFICE

OF/OI OWNER FURNISHED/OWNER INSTALLED

OH OVERHANG

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

PLAM PLASTIC LAMINATE

PLAS PLASTIC

PLYWD PLYWOOD

PREFAB PREFABRICATE

PREFIN PREFINISH

PREP PREPARATION

PT PAINT, PRESSURE TREATED

QRY QUARRY

QT QUARRY TILE

R RADIUS, RISER

RB RUBBER BASE

RD ROAD, ROOF DRAIN

RECT RECTANGLE

REF REFERENCE, REFRIGERATOR

REINF REINFORCE

REQD REQUIRED

REV REVISION

RFI REQUEST FOR INFORMATION

RH RIGHT HAND

RM ROOM

RO ROUGH OPENING

RT RIGHT

S SOUTH

SC SOLID CORE

SCHED SCHEDULE

SCWD SOLID CORE WOOD DOOR

SF SQUARE FOOT (FEET)

SHT SHEET

SIM SIMILAR

SPEC SPECIFICATION

SQ SQUARE

STC SOUND TRANSMISSION CLASS

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPEND

SYM SYMBOL

T TREAD

TEL TELEPHONE

TEMP TEMPORARY

THK THICKNESS

THRES THRESHOLD

THRU THROUGH

TK BD TACKBOARD

TMPD GL TEMPERED GLASS

TV TELEVISION

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

VAR VARIATION, VARIES

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VIF VERIFY IN FIELD

W WEST, WIDE

W/ WITH

W/O WITHOUT

WB WOOD BASE

WC WALL COVERING, WATER CLOSET

WD WOOD

WH WATER HEATER

WLD WELDED

WM WIRE MESH

WT WEIGHT

ABBREVIATIONS

A501A101

(TYP)

A201A101

(TYP)

A302A101

(TYP)

SCALE: 0" = 0"

SECTION

A101A101

A301A101

A501A101

(TYP)

4 1 A401A101

(TYP)

FLOOR LEVEL

ELEV. 00.00

ROOM NAME

X

W#

P-##

A

DETAIL DRAWING NUMBER

SHEET NUMBER WHERE

SECTION IS DRAWN

SHEET NUMBER WHERE

SECTION IS TAKEN

ADDITIONAL INSTRUCTION

DETAIL SYMBOL

ELEVATION SYMBOL

INTERIOR ELEVATION

SYMBOL WITH

MULTIPLE VIEWS

WALL SECTION SYMBOL

BUILDING SECTION SYMBOL

ENLARGED DETAIL SYMBOL

DRAWING TITLE SYMBOL

PLAN NORTH SYMBOL

FLOOR LEVEL SYMBOL

ROOM NAME & NUMBER

TAG SYMBOL

DOOR TAG SYMBOL

WINDOW TAG SYMBOL

KEYNOTE TAG SYMBOL

EQUIPMENT & FINISH

TAG SYMBOL

WALL TYPE TAG SYMBOL

REVISION TAG &

CLOUD SYMBOL

COLUMN BUBBLE &

COLUMN GRID SYMBOL

INDICATES DIRECTION OF

VIEWING PLANE

INDICATES DIRECTION OF

CUTTING PLANE

INDICATES DIRECTION OF

CUTTING PLANE

MATCH LINE

SEE XX/X-XXX

MATCH LINE &

DRAWING REFERENCE

BREAK LINE SYMBOL

DETAIL SYMBOLS

FLOOR ELEVATION TAG

TO INDICATE FINISHED

FLOOR LEVEL

A201

(TYP)

A302

(TYP)

A401

(TYP)

A

C

BDINTERIOR ELEVATION

SYMBOL

DETAIL ELEVATION

SYMBOL

DETAIL SECTION

SYMBOL

SMALL SECTION

DETAIL SYMBOL

N

PROJECT

NORTH

INDICATION OF

PROJECT NORTH

INDICATION OF

TRUE NORTH

A301

MATERIALS

CMU, CONCRETE

MASONRY UNIT

BRICK

CAST STONE OR

PRECAST CONCRETE

CONCRETE

SAND OR GROUT

RIGID INSULATION

ALUMINUM

STEEL

ENGINEERED WOOD

PLYWOOD

PLYWOOD

(SMALL SCALE)

FINISHED

HARDWOOD

CRUSHED GRAVEL

STONE

COMPACT

FILL EARTH

NATURAL

CUT STONE

WOOD, BLOCKING

& SHIMS

WOOD, FRAMING

& FURRING

BATT INSULATION

METAL DECKING

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

15613

11/26/2026

11" MIN

M

I N

8" MIN

9" MIN

(A)

ELEVATION

(B)

PLAN

M

I N

25" MAX17"-25"

9"

6" MAX

M

I N

(A)

ELEVATION

(B)

PLAN

(A)

HINGED DOOR

32" MIN

90°

42" MIN

M

I N

(E)

HINGE APPROACH,

PULL SIDE

36" MIN

M

I N

(D)

HINGE APPROACH,

PULL SIDE

M

I N

12" MIN

(C)

FRONT APPROACH, PUSH

SIDE, DOOR PROVIDED WITH

BOTH CLOSER AND LATCH

M

I N

(B)

FRONT APPROACH,

PUSH SIDE

M

I N

18" MIN

(A)

FRONT APPROACH,

PULL SIDE

M

I N

22" MIN

(F)

HINGE APPROACH,

PUSH SIDE

(G)

HINGE APPROACH, PUSH

SIDE, DOOR PROVIDED WITH

BOTH CLOSER AND LATCH

M

I N

22" MIN

M

I N

(B)

PUSH SIDE

X > 8"

M

I N

18" MIN

X > 8"

(A)

PULL SIDE

M

I N

12" MIN

(C)

PUSH SIDE, DOOR PROVIDED WITH

BOTH CLOSER AND LATCH

X > 8"

12" MIN 12" MIN

48" MIN

48" MIN

(A) (B)

48" MIN

(C)

(A)

STAIRS

(B)

RAMPS

(C)

WALKING SURFACES

1 1/2" MIN

1 1 /2"

M

IN

12" MIN

12" MIN

12" MIN

X

X

NOTE: X = TREAD DEPTH

AREA OF

REFUGE

3/8" MIN

3/8" MIN

AREA OF

REFUGE

M

I N

M

A X

18" MIN

18" MIN

45°

LIBRARY

24" MIN

M

I N

(H)

LATCH APPROACH,

PULL SIDE

(I)

LATCH APPROACH, PULL

SIDE, DOOR PROVIDED

WITH CLOSER

M

I

N 24" MIN

24" MIN

M

I N

(J)

LATCH APPROACH,

PUSH SIDE

(K)

LATCH APPROACH, PUSH

SIDE, DOOR PROVIDED

WITH CLOSER

24" MIN

M

I N

" M

AX

" M

AX

>20"-25" MAX20" MAX

(A) (B)

10" MAX

" M

AX

" M

IN

10" MAX

" M

AX

" M

AX

" M

AX

" M

AX

> 10"-24" MAX

(A) (B)

" M

IN

" M

AX

FIGURE 404.2.4.1 MANEUVERING CLEARANCES

AT MANUAL SWINGING DOORS AND GATES

FIGURE 404.2.3 CLEAR

WIDTH OF DOORWAY

(B)

SIDE APPROACH

M

I N

FIGURE 404.2.4.2 MANEUVERING CLEARANCE

AT DOORWAYS WITHOUT DOOR

FIGURE 404.2.4.3 MANEUVERING CLEARANCES

AT RECESSED DOORS AND GATES

FIGURE 404.2.6 DOORS IN SERIES

AND GATES IN SERIES

X < 4"

FIGURE 405.9.1 EXTENDED

FLOOR OR GROUND SURFACE

EDGE PROTECTION

FIGURE 405.9.2 CURB OR

BARRIER EDGE PROTECTION

FIGURE 505.4 HANDRAIL HEIGHT

FIGURE 505.5 HANDRAIL

CLEARANCE

FIGURE 505.6 HORIZONTAL

PROJECTIONS BELOW

GRIPPING SURFACE

FIGURE 505.10.1 TOP AND BOTTOM

HANDRAIL EXTENSION AT RAMPS

FIGURE 505.10.2 TOP HANDRAIL

EXTENSION AT STAIRS

FIGURE 505.10.3 BOTTOM

HANDRAIL EXTENSION AT STAIRS

FIGURE 306.3 KNEE CLEARANCEFIGURE 306.2 TOE CLEARANCE

FIGURE 308.2.1

UNOBSTRUCTED FORWARD

REACH

FIGURE 308.2.2

UNOBSTRUCTED HIGH

FORWARD REACH

FIGURE 308.3.1

UNOBSTRUCTED SIDE REACH FIGURE 308.3.2 OBSTRUCTED

HIGH SIDE REACH

FIGURE 703.2.5 HEIGHT OF

RAISED CHARACTERS

FIGURE 703.3.2 POSITION OF

BRAILLE

FIGURE 703.4.1 HEIGHT OF

TACTILE CHARACTERS ABOVE

FINISHED FLOOR OR GROUND

FIGURE 703.4.2 LOCATION OF

TACTILE SIGNS AT DOORS

AREA OF

REFUGE

CL

CENTERED ON

TACTILE

CHARACTERS

M

I N

ROOM SIGNAGE

H E

A D

C

L E

A R

A N

C E

R E

A C

H

R

A N

G E

C O

N T

R O

L S

C O

N T

R O

L S

CABINETS AND FIRE EXTINGUISHERS OUTLETS AND SWITCHES ELEVATOR CONTROLS AND SIGNALS

R E

A C

H

R

A N

G E

M

I N

V I S

I B

E

S

I G

N A

L S

*THIS DIAGRAM ILLUSTRATES TYPICAL ACCESSORIES, FOR REFERENCE ONLY. REFER TO

MANUFACTURER SPECIFICATIONS AND RECOMMENDATIONS FOR SPECIFIC MOUNTING

HEIGHTS. VISIBLE SIGNALS

CALL CONTROLS

M

A X

M

A X

M

A X

MIRROR ABOVE

SINK AND SINK MIRROR SOAP HAND DRYER SURFACE MOUNTED

MULTI-ROLL TOILET

TISSUE DISPENSER

SANITARY NAPKIN

DISPENSER

TOILET SEAT COVER

DISPENSER

SURFACE MOUNTED

SANITARY NAPKIN

DISPOSAL

M

A X

MOP RACK

M

A X

URINAL STANDARD

M

A X

A D

A

HOOK DRINKING FOUNTAIN URINAL ADA

T

O

T

O

M

A X

T

O

T

O

T O

P

O

R

B

A R

1' - 0" 3' - 6"

MAX

39" TO 41

BRACKETS, TYP.

3/4" FIRE RATED

PLYWOOD IN-WALL

BLOCKING

ADJUSTABLE

WIRE SHELVING

GENERAL MOUNTING HEIGHTS - SHELVING

DUPLEX

OUTLET

GENERAL MOUNTING HEIGHTS - CONTROLS AND

RECEPTACLES

TELECOM

OUTLET

SPECIAL

PURPOSE

JUNCTION

BOX

MANUAL

FIRE ALARM

PULL STATION

CARD READER,

LOCAL ALARM, OR

ARMING STATION

DUPLEX OUTLET

@ COUNTER W/

BACKSPLASH

RACEWAY DUPLEX

OUTLET

THERMOSTAT WALL

MOUNTED

PHONE OUTLET

LIGHT SWITCH

& DIMMER

CLOCK OR

CLOCK OUTLET

AUDIBLE

AND/OR

FIRE ALARM

SECURITY

STROBE LIGHT

TV

DUPLEX

OUTLETOUTLET VISUAL

GRAB BAR BLOCKING MOUNTING HEIGHTS

REINFORCING AT

TOILET SIDE WALL

REINFORCING BEHIND TOILET

WITH A SIDE WALL

REINFORCING BEHIND TOILET

WITHOUT A SIDE WALL

3' - 6" MIN

5' - 0"

6' MAX

T

O

T O

P

O

R

B

A R

3' - 0" MIN

T O

O

B

L O

C K

I N

G

8"3' - 0"

2' - 2" 1' - 2"

1' - 6"

M I N

A

F

F

O

O

B

L O

C K

I N

G

SIDE ELEVATION FRONT ELEVATION

1' - 6" 1' - 6"

TYPICAL MOUNTING HEIGHTS

VERTICAL CLEARANCE LESS THAN 80"

GUARDRAIL OR OTHER BARRIERPROTRUDING OBJECTS

4" MAX

M

A X

M

I N

V E

R T

I C

E

A R

A N

C E

S

M

I N

V E

R T

I C

E

A R

A N

C E

S

24" MAX 24" MAX48" MIN

M

I N

M

I N

M

A X

LEGEND

DESCRIPTIONCONVENTION

DIMENSION SHOWING ENGLISH UNITS IN

INCHES UNLESS OTHERWISE SPECIFIED,

ABOVE THE LINE.

36"

DIMENSION FOR SMALL MEASUREMENTS

6"

DIMENSION SHOWING A RANGE WITH

MINIMUM - MAXIMUM

33"-36"

MINIMUMMIN.

MAXIMUMMAX.

GREATER THAN

GREATER THAN OR EQUAL TO

LESS THAN

LESS THAN OR EQUAL TO

BOUNDARY OF CLEAR FLOOR SPACE OR

MANEUVERING CLEARANCE

CENTERLINE

A PERMITTED ELEMENT OR ITS EXTENSION

CL

DIRECTION OF TRAVEL OR APPROACH

A WALL, FLOOR, CEILING OR OTHER

ELEMENT CUT IN SECTION OR PLAN

A HIGHLIGHTED ELEMENT IN ELEVATION

OR PLAN

LOCATION ZONE OF ELEMENT CONTROL

OR FEATURE

GENERAL NOTE

1. ALL FIGURES ARE TAKEN FROM THE 2010 ADA STANDARDS

FOR ACCESSIBLE DESIGN.

1. ALL FIGURES SHOWN DEPICT COMMON DESIGN EXAMPLES

AND SOME FIGURES MAY NOT NECESSARY APPLY TO THE

SUBMITTED DRAWINGS.

A-002

TYPICAL ADA CLEARANCES

& MOUNTING HEIGHTS

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

K L 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 45

A

B

C

D

3 2 1

4 3

A216 A222 A215

A220 A2

A

A2

A224

A245E

EL 1

J.C.U.

EL 2

A245AA245B

A245D

A245C

A245 CONF.A2

A

A228

CAPITOL

POLICE

WL WL

LEASED

CARPENTERY

LOCKSMITH

CARPENTRY

PAINT

DIGITAL PRE-PRESSA233

A237

PIPE SHAFT

OFFICES

OFFICE

5 192'147'

123'

130'

FE

FE

FE

FE

FE

FE

FE

FE

FACILITIES/PBM/SIG STAFF

N105 INTER-AGENCY

CONFERENCE CENTER

N100

OPERTION CHIEFS

N101

FACILITIES

DIV CHIEF

N102

PRINT ROOM

& STORAGE

N106

PLANNING &

SCHEDULING

N107

FACILITIES

DEPT. HEAD

N108

BREAK ROOM

N109

PBM

N111

CONFERENCE ROOM

N113

SIG CHIEF

N112

ENGINEERING & AUTOMATION STAFF

N120

AUTO. DIVISION

N116

ENG. DIVISION

N117

BREAK ROOM

N118ENG. & AUTO. DEPT. HEAD

N119

MEETING ROOM

N103

PRINT AREA

N115

INDUS.

CLEANING

A247

UNION AFGE

A246

MEETING ROOM

N104

IT/SERVER

A246B

STORAGE

N114D

STORAGE

N114C

STORAGE

N114B

STORAGE

N114A

CHIEF OF FACILITIES

MANAGEMENT

N110

CONFERENCE STORAGE

N100A

FACILITIES/PBM/SIG STAFF

N105

MECHANICAL

A218A

TOILETS

N123-1 TO N123-12

CORRIDOR C

C-3

CORRIDOR T

123-3

A-003

CODE ANALYSIS & LIFE

SAFETY

SCALE: 1/16" = 1'-0"

LIFE SAFETY PLAN

A003A100

CODE ANALYSIS

Bea

PROJECT ADDRESS:

GOVERNMENT PUBLISHING OFFICE

732 NORTH CAPITOL ST NW

WASHINGTON DC 20401

APPLICABLE CODES

2017 DC CONSTRUCTION CODES WITH LOCAL AMENDMENTS

2021 INTERNATIONAL BUILDING CODE (IBC)

CODE EVALUATION BASED UPON 2018 INTERNATIONAL BUILDING CODE (IBC)

2021 INTERNATIONAL EXISTING BUILDING CODE

2021 NATIONAL ELECTRICAL CODE

2021 INTERNATIONAL FUEL GAS CODE

2021 INTERNATIONAL MECHANICAL CODE

2021 INTERNATIONAL PLUMBING CODE

2021 INTERNATIONAL FIRE CODE

EXISTING BUILDING STATISTICS:

EXISTING BUILDING AREA = LEVEL 2 FACILITIES MANAGEMENT RENOVATION AREA: 15,300 SF

USE GROUP:

B BUSINESS 15,300 S.F. 100%

PROJECT DOES NOT INVOLVE A CHANGE IN OCCUPANCY. PROJECT INVOLVES AN INTERIOR RENOVATION OF A PORTION OF THE BUILDING AREA AND IS THEREFORE CLASSIFIED AS A LEVEL 2 ALTERATION IN THE 2021 INTERNATIONAL EXISTING BUILDING CODE.

INTERNATIONAL BUILDING CODE 2018 REVIEW

CHAPTER 3 OCCUPANCY CLASSIFICATION AND USE, NO CHANGE IN OCCUPANCY FROM EXISTING.

SECTION 304 BUSINESS GROUP B

CHAPTER 5 GENERAL BUILDING HEIGHTS AND AREAS

SECTION 503 GENERAL BUILDING HEIGHT AND AREA UNITS

TYPE IB CONSTRUCTION

TABLE 504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE

GROUP B, SPRINKLERED:, TYPE IB CONSTRUCTION ALLOWABLE HT = 180'

EXISTING HEIGHT > 75'

TABLE 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE

GROUP B, SPRINKLERED, TYPE IB CONSTRUCTION = 12 STORIES ALLOWED; EXISTING = 8 STORIES

SECTION 505.3.2 SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW EQUIPMENT PLATFORM.

SECTION 506 BUILDING AREA

TABLE 506.2 ALLOWABLE AREA FACTOR

B, S, UNLIMITED = UNLIMITED SF; EXISTING BUILDING AREA = 15,300

CHAPTER 6 TYPES OF CONSTRUCTION IB

SECTION 602.3 TYPE I CONSTRUCTION IS FIRE-RESISTANT CONSTRUCTION MADE OF NON-COMBUSTIBLE MATERIALS. TYPE I

BUILDINGS ARE TYPICALLY HIGH-RISE OR MULTI-STORY

TABLE 601 FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS

TYPE IB CONSTRUCTION SPRINKLERED

PRIMARY STRUCTURAL FRAME 2 HR FIRE RATING

BEARING WALLS EXTERIOR 2 HR FIRE RATING

BEARING WALLS INTERIOR 2 HR FIRE RATING

NON-BEARING WALLS EXTERIOR SEE TABLE 602

NON-BEARING WALLS INTERIOR 0 HR FIRE RATING

FLOOR CONSTRUCTION 2 HR FIRE RATING

ROOF CONSTRUCTION 1 HR FIRE RATING

TABLE 602 FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE.

X ≥ 30', 0 HR RATING REQUIRED

CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES

TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF

OPENING PROTECTION

TABLE 705.8 30 OR GREATER, UNPROTECTED, NONSPRINKLERED, NO LIMIT; COMPLIES

CHAPTER 8 INTERIOR FINISHES

TABLE 803.13 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY

OCCUPANCY GROUP B NON SPRINKLERED

INTERIOR EXIT STAIRWAYS, INTERIOR EXIT RAMPS

AND EXIT PASSAGEWAYS CLASS A

CODE ANALYSIS

CORRIDORS AND ENCLOSURE FOR EXIT ACCESS

STAIRWAYS AND EXIT ACCESS RAMPS CLASS B

ROOMS AND ENCLOSED SPACES CLASS C

SECTION 803.1.3 INTERIOR WALL AND CEILING FINISH

MATERIALS TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723

CLASS A = FLAME SPREAD INDEX:

0-25 SMOKE DEVELOPED INDEX: 0 - 450

CLASS B = FLAME SPREAD INDEX:

26 - 75 SMOKE DEVELOPED INDEX: 0 - 450

CLASS C = FLAME SPREAD INDEX:

76 - 200 SMOKE DEVELOPED INDEX: 0 - 450

SECTION 806 DECORATIVE MATERIALS AND TRIM

SECTION 806.1 GENERAL

1. EXPLOSIVE OR HIGHLY FLAMMABLE MATERIALS SHALL NOT BE USED

2. FURNISHINGS SHALL NOT OBSTRUCT EXITS

SECTION 808 ACOUSTICAL CEILING SYSTEMS

SECTION 808.1.1.1 SUSPENDED ACOUSTICAL CEILINGS

INSTALL FOR ASTM C 635 AND ASTM C 636

ASTM C 635 FOR INTERMEDIATE - DUTY SYSTEM

CHAPTER 10 MEANS OF EGRESS

TABLE 1004.5 REFER TO OCCUPANCY SUMMARY TABLE

SECTION 1005.3.2

THE CAPACITY, IN INCHES, OF MEANS OF EGRESS COMPONENTS OTHER THAN STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF

EGRESS CAPACITY OF 0.2 INCH PER OCCUPANT.

EXIT DISCHARGE SERVING SECOND FLOOR OCCUPANTS: 48 OCCUPANTS X 0.2 = 9.6 INCHES

1 EXIT DISCHARGE DOOR = 32" = 32" EGRESS WIDTH; COMPLIES WITH REQUIREMENT

EXIT DISCHARGE SERVING FIRST FLOOR OCCUPANTS: 25 OCCUPANTS X 0.2 = 5 INCHES

1 EXIT DISCHARGE DOOR = 32" = 32" EGRESS WITH, COMPLIES WITH REQUIREMENT

TABLE 1006.3.3 STORIES WITH ONE EXIT

MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE = 65 FEET, COMPLIES

SECTION 1009.3.3 AREA OF REFUGE

STAIRWAYS SHALL EITHER INCORPORATE AN AREA OF REFUGE WITH AN ENLARGED FLOOR-LEVEL LANDING

OR SHALL BE ACCESSED FROM AN AREA OF REFUGE COMPLYING WITH SECTION 1009.6.

AREA OF REFUGE IS INCLUDED

SECTION 1009.6 AREAS OF REFUGE

EVERY REQUIRED AREA OF REFUGE SHALL BE ACCESSIBLE FROM THE SPACE IT SERVES BY AN ACCESSIBLE

MEANS OF EGRESS.

SECTION 1009.6.1 TRAVEL DISTANCE

THE MAX TRAVEL DISTANCE FROM ANY ACCESSIBLE SPACE TO AN AREA OF REFUGE SHALL NOT EXCEED THE EXIT ACCESS TRAVEL DISTANCE PERMITTED FOR THE OCCUPANCY IN ACCORDANCE WITH SECTION 1017.1

SECTION 1010.1.1 SIZE OF DOORS

DOORS SHALL BE 36" WIDE TYPICAL PROVIDING 32" CLEAR WIDTH

SECTION 1010.1.3 DOOR OPENING FORCE 5LB MAXIMUM (PULL AND PUSH SIDES)

SECTION 1010.1.9.1 HARDWARE

SECTION 1010.1.9.4 LOCKS AND LATCHES

ALLOWED FOR GROUP A OCCUPANT LOAD < 300, ALLOWED

SECTION 1010.1.10 PANIC AND FIRE EXIT HARDWARE

GROUP A>50; PANIC DEVICES REQUIRED

EXCEPTION 1: MAIN EXIT MAY HAVE LOADING LOCKING DEVICES

SECTION 1014.8 PROJECTIONS

PROJECTIONS INTO THE REQUIRED WIDTH OF AISLES, STAIRWAYS AND RAMPS AT EACH SIDE SHALL NOT

EXCEED 4 1/2 INCHES.

SECTION 1017 EXIT ACCESS TRAVEL DISTANCE

TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE

OCCUPANCY B WITH SPRINKLER = 300'

TRAVEL DISTANCE FROM MOST REMOTE LOCATION = 70'±; COMPLIES

TABLE 1020.1 CORRIDOR FIRE-RESISTANCE RATING

OCCUPANCY B WITH SPRINKLER SYSTEM = 0HR RATING, COMPLIES

TABLE 1020.2 MAXIMUM CORRIDOR WIDTH

OCCUPANT LOAD > 50 = 44", 72" WIDTH PROVIDED; COMPLIES

SECTION 1020.4 DEAD ENDS

20' MAXIMUM; COMPLIES

CODE ANALYSIS

CHAPTER 11 ACCESSIBILITY

GENERAL: TOILET ROOMS AND DOORS HAVE BEEN SIZED TO COMPLY WITH REQUIRED CLEARANCES, TURNING RADII, REACH CLEARANCES AND ACCESSIBILITY

PER 2010 ADA STANDARD REFER TO DRAWINGS FOR STANDARD DESIGN DETAILS

CHAPTER 12 INTERIOR ENVIRONMENT

SECTION 1202 VENTILATION

PER INTERNATIONAL MECHANICAL CODE, REFER TO MECHANICAL DRAWINGS FOR CODE COMPLIANCE

INTERNATIONAL INTERNATIONAL EXISTING BUILDING CODE

CHAPTER 8 CLASSIFICATION OF WORK

ALTERATION - LEVEL 2

INCLUDES THE RECONFIGURATION OF A SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL

EQUIPMENT.

SECTION 801.2 COMPLIANCE

IN ADDITION TO THE REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY WITH REQUIREMENTS OF

CHAPTER 7.

SECTION 801.3 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACE SHALL COMPLY WITH THE

REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE.

SECTION 803 FIRE PROTECTION

SECTION 803.1

THE REQUIREMENTS OF THIS SECTION SHALL BE LIMITED TO WORK AREAS IN WHICH LEVEL 2 ALTERATIONS ARE BEING PERFORMED, AND WHERE SPECIFIED THEY SHALL APPLY THROUGHOUT THE FLOOR ON WHICH

THE WORK AREAS ARE LOCATED OR OTHERWISE BEYOND THE WORK AREA.

SECTION 803.2

AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS 803.2.1 THROUGH 803.2.4 . INSTALLATION REQUIREMENTS SHALL BE IN ACCORDANCE WITH THE

INTERNATIONAL BUILDING CODE.

SECTIONS 803.2.1 &

803.2.2

IN HIGH RISE BUILDINGS AND BUILDINGS WITH OCCUPANCY GROUP B, WORK AREAS THAT HAVE EXITS AND CORRIDORS SHARED BY MORE THAN ONE TENANT OR THAT HAVE EXITS OR CORRIDORS SERVING AN OCCUPANT LOAD GREATER THAN 30 SHALL BE PROVIDED WITH AUTOMATIC SPRINKLER PROTECTION IN THE ENTIRE WORK AREA WHERE THE WORK AREA IS LOCATED ON A FLOOR THAT HAS SUFFICIENT SPRINKLER WATER SUPPLY SYSTEM FROM AN EXISTING STANDPIPE OR A SPRINKLER RISER SERVING THAT FLOOR.

SECTION 803.4

FIRE ALARM AND DETECTION. AN APPROVED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS 803.4.1 THROUGH 803.4.3. WHERE AUTOMATIC SPRINKLER PROTECTION IS PROVIDED IN ACCORDANCE WITH SECTION 803.2 AND IS CONNECTED TO THE BUILDING FIRE SYSTEM, AUTOMATIC HEAT DETECTION SHALL NOT BE REQUIRED. AN APPROVED AUTOMATIC FIRE DETECTION SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE AND NFPA 72. DEVICES, COMBINATIONS OF DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE APPROVED. THE AUTOMATIC FIRE DETECTORS SHALL BE SMOKE DETECTORS, EXCEPT THAT AN APPROVED ALTERNATE TYPE OF DETECTOR SHALL BE INSTALLED IN SPACES SUCH AS BOILER ROOMS, WHERE PRODUCTS OF COMBUSTION ARE PRESENT DURING NORMAL

OPERATION IN SUFFICIENT QUANTITY TO ACTUATE A SMOKE DETECTOR.

SECTION 805 MEANS OF EGRESS

SECTION 805.1

THE REQUIREMENTS OF THIS SECTION SHALL BE LIMITED TO WORK AREAS THAT INCLUDE EXITS OR

CORRIDORS SHARED BY MORE THAN ONE TENANT WITHIN THE WORK AREA IN WHICH LEVEL 2

ALTERNATIONS ARE BEING PERFORMED, AND WHERE SPECIFIED THEY SHALL APPLY THROUGHOUT THE

FLOOR ON WHICH THE WORK AREAS ARE LOCATED OR OTHERWISE BEYOND THE WORK AREA.

SECTION 805.2 MEANS OF EGRESS LIGHTING

MEANS OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE FLOOR OF EXIT DISCHARGE SHALL BE PROVIDED WITH ARTIFICIAL LIGHTING WITHIN THE EXIT ENCLOSURE IN ACCORDANCE W/ REQUIREMENTS OF

THE IBC, COMPLIES.

SECTION 805.3 EXIT SIGNS; COMPLIES.

INTERNATIONAL PLUMBING CODE 2018 REVIEW

TABLE 403.1 REFER TO PLUMBING FIXTURE COUNTS TABLE

1 HOUR RATED FIRE SEPARATION -

REFER TO FLOOR PLANS AND WALL

TYPES FOR SPECIFIC UL ASSEMBLIES

45 MINUTE FIRE LABELED DOOR

FE

RECESSED WALL MOUNTED FIRE

EXTINGUISHER

PATH OF TRAVEL TO EXIT

TRAVEL DISTANCE TO EXIT

OCCUPANCY SUMMARY

FUNCTION OF SPACE AREA OCCUPANCY CALCULATION

SF/OCC NSF/GSF CODE OCCUPANCY LOAD NOTES

BUSINESS AREAS

BUSINESS AREAS (ASSEMBLY USE)

13,623 SF

1,353 SF

14,976 SF

150 SF

15 SF

GROSS

NET

PLUMBING FIXTURE COUNTS

TABLE 402.1 2018 INTERNATIONAL PLUMBING CODE

*PLUMBING COUNT FIXTURE COUNT IS FOR THE ENTIRETY OF LEVEL 2 AND INCLUDES EXISTING PLUMBING FIXTURES.

AREA OF LEVEL 2: 140,968 SF

BUSINESS OCCUPANCY COUNT OF LEVEL 2: 940 OCCUPANTS

OCCUPANCY CLASSIFICATION

AND USE GROUP

WATER CLOSETS LAVATORIES DRINKING FOUNTAINS OTHER

BUSINESS OCCUPANCY

(INCLUDES

CONFERENCE ROOMS)

940 OCCUPANTS

1 PER 25 FOR THE FIRST 50 AND 1 PER

50 FOR THE REMAINDER EXCEEDING 50

1 PER 40 FOR THE FIRST 80 AND 1 PER

80 FOR THE REMAINDER EXCEEDING 80 1 PER 100 1 SERVICE SINK

REQUIRED

EXISTING

NEW

TOTAL PROVIDED

9 1 1

12.75

9.4

N 4 48

1/16" = 1'-0" 8 12 18 24 32

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALE.

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

15613

11/26/2026

ALL-GENDERALL-GENDER

19.8

BUILDING AUTOMATION

A270

K L 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19

B208

CARPENTER SHOP

D.W.

B206

B210

CARPENTER SHOP

B232 ST 21

EL.

EL.

MEN

W

B228

INVENTORY

SH 21 A234

BALING ROOM

6 5

A231 A267

REPRODUCIBLE STORAGE

EL.5 A239

A257

A250 A218

A217

B235

MEZZANINE ABOVE

B233

B233A

B202

B202A

B212 T222

T221 #10

B226

B234A

ENGINEERING

VAULT

A218A

PLATESETTER

MANAGEMENT

CARPENTERY

STORAGE

OF

FI

CE

S

OFFICE

PIPE STORAGE

STORAGE

PRE-PRESS

PRODUCTION

SUPV.

PIPE

PIPE

B201

EL.6

EL.7

STAIR 4A270B A270A A272B A272A

FACILITIES

A272C

A274A

FACILITIES FRONT OFFICE

A274

CONFERENCE

A268

A269

A266A265PHONE ROOM

A273

A271

A264A263

A262

A251

IT

2B-A

A253A

SUPV.

A253B

D-1

D-1

D-1

D-1

D-3D-3D-3

D-4

D-4 D-4

D-9

D-8 D-6

D-7

PARTIALLY

DEMO'D

SPACE

D-1 D-1 D-1 D-1

D-1

D-10D-1D-10D-1 D-1

AD101

DEMOLITION - PARTIAL

FLOOR PLAN

SCALE: 1/8" = 1'-0"

DEMOLITION FLOOR PLAN

AD101AD101

EXISTING CONSTRUCTION TO BE REMOVED.

EXISTING CONSTRUCTION TO REMAIN.

EXISTING DOORS & FRAMES TO REMAIN

EXISTING DOORS & FRAMES TO BE REMOVED.

1.

2.

3.

4.

5.

7.

6.

EXISTING SPRINKLER HEADS TO REMAIN, BE ROTATED TO NEW

LOCATION, REMOVED OR ADDED

EXISTING SUPPLY REGISTER

EXISTING RETURN OR LOUVER REGISTER

EXISTING 2' X 2' LIGHT FIXTURE

EXISTING 2' X 4' LIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING RECESSED DOWNLIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING EXIT SIGN

EXISTING EMERGENCY LIGHT

DEMOLITION LEGENDGENERAL DEMOLITION NOTES

REFER TO EXISTING MECHANICAL/ELECTRICAL DRAWINGS FOR

COORDINATION OF EXISTING LIGHTING AND MECHANICAL EQUIPMENT.

REMOVE ALL ADHESIVES FROM CONCRETE FLOOR SLAB TO OBTAIN

LEVEL SURFACE.

VERIFY OVERALL DIMENSIONS PRIOR TO DEMOLITION & NOTIFY ARCHITECT

OF ANY DISCREPANCIES OR UNKNOWN CONDITIONS.

REFER TO EXISTING MECHANICAL & ELECTRICAL DRAWINGS TO FOR DEMOLITION,

RELOCATION & CONNECTIONS TO EXISTING HVAC DUCT SYSTEMS, POWER

DISTRIBUTION SYSTEMS, LIGHTING, & PLUMBING SYSTEMS TO BE REMOVED &

CAPPED.

USE CARE DURING DEMOLITION WORK TO PREVENT DAMAGE TO

EXISTING BUILDING COMPONENTS TO REMAIN.

CAP OFF ALL EXISTING PLUMBING DRAINS & PIPES FLUSH TO FLOOR & WALL.

ALL DEMOLITION WORK SHALL COMPLY WITH IBC 2018

REQUIREMENTS.

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALES.

1/8"=1'-0" 2416128640

N

KEY PLAN

D-1

D-2

D-3

D-4

D-5

D-7

D-6

DEMOLITION KEYNOTES

EXISTING SHAFTWALLS TO BE REMOVED AND INTERSECTING WALLS TO BE PATCHED

UP AND REPAIRED. EXISTING SHAFT TO BE FILLED IN AT LEVEL 2.

REMOVE EXISTING RESTROOM STALLS.

REMOVE EXISTING WATERCLOSETS AND URINALS.

REMOVE EXISTING CASEWORK, COUNTERTOPS, AND LAVATORIES.

REMOVE EXISTING FLOORING, TYPICAL

REMOVE EXISTING ACOUSTICAL PANEL CEILING AND LIGHTING.

PATCH AND REPAIR DAMAGED WALL OR COLUMN ONCE

INTERSECTING WALL IS REMOVED, TYPICAL THROUGHOUT.

D-8 REMOVE EXISTING RESTROOM ACCESSORIES AND PATCH UP & REPAIR WALLS/

D-9 REMOVE EXISTING PLINTH. REFER TO PLUMBING DRAWINGS FOR PLUMBING

DEMOLITION.

REMOVE EXISTING WOOD PANEL & REPAIR SUBSTRATE FOR NEW FINISH, TYPICAL AT

EXTERIOR WALLS.

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

15613

D-10

22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 45

B

C

D

3 2 1

A267

REPRODUCIBLE STORAGE

EL.5 A239

A257A A257

4 3

A257B

A250 A218

A217

A212

EL

FLOOR ROOF

A208 EL 1

ST

AI

R

J.C.U.

EL 2A202

A203A

A200 A225

A2

A2

EL.3

EL.4

ST

AI

R

EL

T121

T122

A210 A2

A214A

A206A205 A214

A204 A204A A204B

A204C

A201

CONF.

A227A213C

CAPITOL POLICE LEASED

A204D

CAPITOL

POLICE

CAPITOL

POLICE

FOP

A221B

LEASED

LEASED

GPO POLICE

GPO POLICE

UN

IO

N

OPEN TO 1st

A244

UN

IO

N

A218A

PLATESETTER

PRE-PRESS

PRODUCTION

PRE-PRESS

STORAGE STORAGE

OFFICES

OFFICEA239B

STAIR 4

A253A

SUPV.

A253B

A253C A255C A255B A255A

FACILITIES MANAGEMENT

A255

A254 A261

POWER BR. MECHANICAL ROOM

A258 A259

A239A

D-1

D-4 D-5

D-9

D-8 D-6

D-1

D-1

D-3

D-3

D-4

D-4

D-4

D-5

D-5

D-6

D-6

D-8

D-8

D-1 D3

D3

D-1 D-1

D-10

AD102

DEMOLITION - PARTIAL

FLOOR PLAN

SCALE: 1/8" = 1'-0"

DEMOLITION FLOOR PLAN

AD102AD102

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALES.

1/8"=1'-0" 2416128640

EXISTING CONSTRUCTION TO BE REMOVED.

EXISTING CONSTRUCTION TO REMAIN.

EXISTING DOORS & FRAMES TO REMAIN

EXISTING DOORS & FRAMES TO BE REMOVED.

1.

2.

3.

4.

5.

7.

6.

EXISTING SPRINKLER HEADS TO REMAIN, BE ROTATED TO NEW

LOCATION, REMOVED OR ADDED

EXISTING SUPPLY REGISTER

EXISTING RETURN OR LOUVER REGISTER

EXISTING 2' X 2' LIGHT FIXTURE

EXISTING 2' X 4' LIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING RECESSED DOWNLIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING EXIT SIGN

EXISTING EMERGENCY LIGHT

DEMOLITION LEGENDGENERAL DEMOLITION NOTES

REFER TO EXISTING MECHANICAL/ELECTRICAL DRAWINGS FOR

COORDINATION OF EXISTING LIGHTING AND MECHANICAL EQUIPMENT.

REMOVE ALL ADHESIVES FROM CONCRETE FLOOR SLAB TO OBTAIN

LEVEL SURFACE.

VERIFY OVERALL DIMENSIONS PRIOR TO DEMOLITION & NOTIFY ARCHITECT

OF ANY DISCREPANCIES OR UNKNOWN CONDITIONS.

REFER TO EXISTING MECHANICAL & ELECTRICAL DRAWINGS TO FOR DEMOLITION,

RELOCATION & CONNECTIONS TO EXISTING HVAC DUCT SYSTEMS, POWER

DISTRIBUTION SYSTEMS, LIGHTING, & PLUMBING SYSTEMS TO BE REMOVED &

CAPPED.

USE CARE DURING DEMOLITION WORK TO PREVENT DAMAGE TO

EXISTING BUILDING COMPONENTS TO REMAIN.

CAP OFF ALL EXISTING PLUMBING DRAINS & PIPES FLUSH TO FLOOR & WALL.

ALL DEMOLITION WORK SHALL COMPLY WITH IBC 2018

REQUIREMENTS.

KEY PLAN

N

D-1

D-2

D-3

D-4

D-5

D-7

D-6

DEMOLITION KEYNOTES

EXISTING SHAFTWALLS TO BE REMOVED AND INTERSECTING WALLS TO BE PATCHED

UP AND REPAIRED. EXISTING SHAFT TO BE FILLED IN AT LEVEL 2.

REMOVE EXISTING RESTROOM STALLS.

REMOVE EXISTING WATERCLOSETS AND URINALS.

REMOVE EXISTING CASEWORK, COUNTERTOPS, AND LAVATORIES.

REMOVE EXISTING FLOORING, TYPICAL

REMOVE EXISTING ACOUSTICAL PANEL CEILING AND LIGHTING.

PATCH AND REPAIR DAMAGED WALL OR COLUMN ONCE

INTERSECTING WALL IS REMOVED, TYPICAL THROUGHOUT.

D-8 REMOVE EXISTING RESTROOM ACCESSORIES AND PATCH UP & REPAIR WALLS/

D-9 REMOVE EXISTING PLINTH. REFER TO PLUMBING DRAWINGS FOR PLUMBING

DEMOLITION.

REMOVE PORTION OF EXISTING CHASE WALLD-10

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

BUILDING AUTOMATION

A270

A270B A270A A272B A272A

FACILITIES

A272C

A274A

FACILITIES FRONT OFFICE

A274

CONFERENCE

A268

A269

A266A265PHONE ROOM

A273

A271

A264A263

A262

A251

IT

2B-A

A253A

SUPV.

A253B

K L 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19

PARTIALLY

DEMO'D

SPACE

D-3

D-3

D-3

AD201

DEMOLITION - PARTIAL

REFLECTED CEILING PLAN

SCALE: 1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN

AD201AD201

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALES.

1/8"=1'-0" 2416128640

EXISTING CONSTRUCTION TO BE REMOVED.

EXISTING CONSTRUCTION TO REMAIN.

EXISTING DOORS & FRAMES TO REMAIN

EXISTING DOORS & FRAMES TO BE REMOVED.

1.

2.

3.

4.

5.

7.

6.

EXISTING SPRINKLER HEADS TO REMAIN, BE ROTATED TO NEW

LOCATION, REMOVED OR ADDED

EXISTING SUPPLY REGISTER

EXISTING RETURN OR LOUVER REGISTER

EXISTING 2' X 2' LIGHT FIXTURE

EXISTING 2' X 4' LIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING RECESSED DOWNLIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING EXIT SIGN

EXISTING EMERGENCY LIGHT

DEMOLITION LEGENDGENERAL DEMOLITION NOTES

REFER TO EXISTING MECHANICAL/ELECTRICAL DRAWINGS FOR

COORDINATION OF EXISTING LIGHTING AND MECHANICAL EQUIPMENT.

REMOVE ALL ADHESIVES FROM CONCRETE FLOOR SLAB TO OBTAIN

LEVEL SURFACE.

VERIFY OVERALL DIMENSIONS PRIOR TO DEMOLITION & NOTIFY ARCHITECT

OF ANY DISCREPANCIES OR UNKNOWN CONDITIONS.

REFER TO EXISTING MECHANICAL & ELECTRICAL DRAWINGS TO FOR DEMOLITION,

RELOCATION & CONNECTIONS TO EXISTING HVAC DUCT SYSTEMS, POWER

DISTRIBUTION SYSTEMS, LIGHTING, & PLUMBING SYSTEMS TO BE REMOVED &

CAPPED.

USE CARE DURING DEMOLITION WORK TO PREVENT DAMAGE TO

EXISTING BUILDING COMPONENTS TO REMAIN.

CAP OFF ALL EXISTING PLUMBING DRAINS & PIPES FLUSH TO FLOOR & WALL.

ALL DEMOLITION WORK SHALL COMPLY WITH IBC 2018

REQUIREMENTS.

KEY PLAN

N

D-1

D-2

D-3

D-4

D-5

D-7

D-6

DEMOLITION KEYNOTES

EXISTING SHAFTWALLS TO BE REMOVED AND INTERSECTING WALLS TO BE PATCHED

UP AND REPAIRED. EXISTING SHAFT TO BE FILLED IN AT LEVEL 2.

REMOVE EXISTING RESTROOM STALLS.

REMOVE EXISTING WATERCLOSETS AND URINALS.

REMOVE EXISTING CASEWORK, COUNTERTOPS, AND LAVATORIES.

REMOVE EXISTING FLOORING, TYPICAL

REMOVE EXISTING ACOUSTICAL PANEL CEILING AND LIGHTING.

PATCH AND REPAIR DAMAGED WALL OR COLUMN ONCE

INTERSECTING WALL IS REMOVED, TYPICAL THROUGHOUT.

D-8 REMOVE EXISTING RESTROOM ACCESSORIES AND PATCH UP & REPAIR WALLS/

D-9 REMOVE EXISTING PLINTH. REFER TO PLUMBING DRAWINGS FOR PLUMBING

DEMOLITION.

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

A253A

SUPV.

A253B

A253C A255C A255B A255A

FACILITIES MANAGEMENT

A255

A254 A261

POWER BR. MECHANICAL ROOM

A258 A259

A239A

22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 45

A

B

C

D

3 2 1

OPEN TO

ABOVE

OPEN TO

ABOVE

D-2

D-2

D-2

D-2

AD202

DEMOLITION - PARTIAL

REFLECTED CEILING PLAN

SCALE: 1/8" = 1'-0"

DEMOLITION - PARTIAL REFLECTED CEILING PLAN

AD102AD102

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALES.

1/8"=1'-0" 2416128640

EXISTING CONSTRUCTION TO BE REMOVED.

EXISTING CONSTRUCTION TO REMAIN.

EXISTING DOORS & FRAMES TO REMAIN

EXISTING DOORS & FRAMES TO BE REMOVED.

1.

2.

3.

4.

5.

7.

6.

EXISTING SPRINKLER HEADS TO REMAIN, BE ROTATED TO NEW

LOCATION, REMOVED OR ADDED

EXISTING SUPPLY REGISTER

EXISTING RETURN OR LOUVER REGISTER

EXISTING 2' X 2' LIGHT FIXTURE

EXISTING 2' X 4' LIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING RECESSED DOWNLIGHT FIXTURE, DEMOLISHED LIGHTS TO BE

SALVAGED, STORED ON SITE FOR REUSE IN CONSTRUCTION PHASE.

EXISTING EXIT SIGN

EXISTING EMERGENCY LIGHT

DEMOLITION LEGENDGENERAL DEMOLITION NOTES

REFER TO EXISTING MECHANICAL/ELECTRICAL DRAWINGS FOR

COORDINATION OF EXISTING LIGHTING AND MECHANICAL EQUIPMENT.

REMOVE ALL ADHESIVES FROM CONCRETE FLOOR SLAB TO OBTAIN

LEVEL SURFACE.

VERIFY OVERALL DIMENSIONS PRIOR TO DEMOLITION & NOTIFY ARCHITECT

OF ANY DISCREPANCIES OR UNKNOWN CONDITIONS.

REFER TO EXISTING MECHANICAL & ELECTRICAL DRAWINGS TO FOR DEMOLITION,

RELOCATION & CONNECTIONS TO EXISTING HVAC DUCT SYSTEMS, POWER

DISTRIBUTION SYSTEMS, LIGHTING, & PLUMBING SYSTEMS TO BE REMOVED &

CAPPED.

USE CARE DURING DEMOLITION WORK TO PREVENT DAMAGE TO

EXISTING BUILDING COMPONENTS TO REMAIN.

CAP OFF ALL EXISTING PLUMBING DRAINS & PIPES FLUSH TO FLOOR & WALL.

ALL DEMOLITION WORK SHALL COMPLY WITH IBC 2018

REQUIREMENTS.

KEY PLAN

N

D-1

D-2

D-3

D-4

D-5

D-7

D-6

DEMOLITION KEYNOTES

EXISTING SHAFTWALLS TO BE REMOVED AND INTERSECTING WALLS TO BE PATCHED

UP AND REPAIRED. EXISTING SHAFT TO BE FILLED IN AT LEVEL 2.

REMOVE EXISTING RESTROOM STALLS.

REMOVE EXISTING WATERCLOSETS AND URINALS.

REMOVE EXISTING CASEWORK, COUNTERTOPS, AND LAVATORIES.

REMOVE EXISTING FLOORING, TYPICAL

REMOVE EXISTING ACOUSTICAL PANEL CEILING AND LIGHTING.

PATCH AND REPAIR DAMAGED WALL OR COLUMN ONCE

INTERSECTING WALL IS REMOVED, TYPICAL THROUGHOUT.

D-8 REMOVE EXISTING RESTROOM ACCESSORIES AND PATCH UP & REPAIR WALLS/

D-9 REMOVE EXISTING PLINTH. REFER TO PLUMBING DRAWINGS FOR PLUMBING

DEMOLITION.

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

K L 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 45

A

B

C

D

3 2 1

4 3

A216 A222 A215

A220 A2

A

A249

A2

A224

A245E

EL 1

J.C.U.

EL 2

A245AA245B

A245D

A245C

A245 CONF.A2

A

A228

CAPITOL

POLICE

WL WL

LEASED

CARPENTERY

LOCKSMITH

CARPENTRY

PAINT

DIGITAL PRE-PRESSA233

A237

PIPE SHAFT

OFFICES

OFFICE

A-100

NEW WORK - OVERALL

FLOOR PLAN

SCALE: 1/16" = 1'-0"

LEVEL 2 OVERALL FLOOR PLAN

A100A100

EXISTING PARTITION TO REMAIN.

EXISTING WINDOW AND FRAME TO REMAIN.

EXISTING DOOR AND FRAME TO REMAIN.

NEW PARTITION TO BE CONSTRUCTED.

NEW WINDOW AND FRAME TO BE

CONSTRUCTED.

NEW DOOR AND FRAME TO BE CONSTRUCTED.

N 4 48

1/16" = 1'-0" 8 12 18 24 32

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALE.

NOTE: SHADED AREA INDICATES "NOT IN THIS CONTRACT".

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

15613

REFER TO PARTIAL FLOOR PLAN 1/A-101 REFER TO PARTIAL FLOOR PLAN 1/A-102

PBM

N111

CONFERENCE ROOM

N113

SIG CHIEF

N112

ENGINEERING & AUTOMATION STAFF

N120

AUTO. DIVISION

N116

ENG. DIVISION

N117BREAK ROOM

N118

ENG. & AUTO. DEPT. HEAD

N119

PRINT AREA

N115

STORAGE

N114D

STORAGE

N114C

STORAGE

N114B

STORAGE

N114A

CHIEF OF FACILITIES MANAGEMENT

N110

A502

A502

A502 4

A502

A-312

A312

A300

A502

3 A502

A502

A312

D

A

A

B C C

C

A

B

A

A

A

AA

A

A

A A

A

A

A

A

D

D

B

CC

C

A

6'-0" 14'-5" 6'-0"

9'-1"3'-4"1'-2"

2'-4" 13'-2"

13'-3" 11'-11" 8'-11"

5'-0" 3'-6"

6'-0" 26'-0"

5'-0"

13'-4" 12'-8"

'-6

'-3

5'-

4 1 /2"

'-8

3/ 4" 3'-3"

8'- 4"

9'-

4'-

0"

'-0

8'- 5"

20'-4 5/8"23'-0"85'-3"

7'-6" 4'-8" 7'-4" 4'-9 5/8"

A

B

D D D

B C

B

C

C B B

B

C B B

B

119-1

120-2

117-1 116-1

114D-1 114C-1

114B-1 114A-1

120-1

112-1 111-1

110-1113-1

113-2

CORRIDOR A

C-1

CORRIDOR B

C-2

CORRIDOR B

C-2

CORRIDOR A

C-1

BREAK ROOM

N109

2'- 4"

A

B

B

2'- 4"

2'- 4"

6'-0"

5'- 5"

2'- 5"

6'- 5"

8'-1"10'-8 1/2"

K L 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19

A310

A-401

FE

FE

F-2TYPICALF-1TYPICAL F-1

TYPICAL

F-1TYPICAL

F-2

TYPICAL

AA A

F-3

TYPICAL

F-3

TYPICAL

F-3

TYPICAL

F-3

TYPICAL

ALIGN

C

EXISTING WALL EXISTING WALL

EXISTING WALL

6'- 0" 5'-

9"

A-101

NEW WORK - PARTIAL

FLOOR PLAN1

SCALE: 1/8" = 1'-0"

LEVEL 2 PARTIAL FLOOR PLAN

A101A100

EXISTING PARTITION TO REMAIN.

EXISTING WINDOW AND FRAME TO REMAIN.

EXISTING DOOR AND FRAME TO REMAIN.

NEW PARTITION TO BE CONSTRUCTED.

NEW WINDOW AND FRAME TO BE

CONSTRUCTED.

NEW DOOR AND FRAME TO BE CONSTRUCTED.

FIRE EXTINGUISHER/ CABINET

CAUTION:

IF THIS DRAWING IS A REDUCTION,

USE THE GRAPHIC SCALES.

1/8"=1'-0" 2416128640

N

NOTE: SHADED AREA INDICATES "NOT IN THIS CONTRACT".

OFFICE/

RESTROOM

FM HVAC/

U.S. GOVERNMENT

PUBLISHING OFFICE

732 NORTH CAPITOL ST, NW

APRIL 2, 2025

22903.001

FINAL SUBMISSION

CONSULTANTS:

PROJECT:

DESCRIPTION

ISSUE:

CHECKED BY:

PROJECT NO:

DATE:

DRAWN BY:

MARK DATE

SHEET TITLE

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND,

LICENSE NO: _______________________

EXPIRATION DATE: _______________________

PROFESSIONAL CERTIFICATION:

ENGINEERS

ESTABLISHED 1972

Mechanical - Electrical - Fire Protection

8005 Harford Road

Baltimore, Maryland 21234-5701

Tel: (410) 668-8000

E-mail: ebl@eblengineers.com

WASHINGTON, DC 20401

MODERNIZATION

LM/ PRM

BF

15613

11/26/2026

FE

F-1

F-2

FLOOR PLAN KEYNOTES

REPAIR/ INSTALL DRYWALL AT ALL WINDOW OPENINGS ALONG THE

EXTTERIOR WALL PERIMETER FOR NEW PAINT FINISH, TYPICAL

PAINT EXTERIOR WINDOW FRAMES & MULLIONS (INTERIOR)- COLOR

P-1,…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .