GPD HVAC - Bid Plans.pdf
PDF 2 MB Posted
- Solicitation number
- 2138066
- Issued by
- Westchester County, New York
About this file
File Summary:
This is a Bid Plans document for the Town of Greenburgh Department of Public Works in Westchester County, New York, detailing HVAC improvements to the Greenburgh Police Department located at 188 Tarrytown Road, White Plains, NY. The project involves the installation of a new packaged gas-fired heating and direct expansion cooling unit with hot gas reheat (RTU-Detective Office) serving the Police Detective Office Suite, along with associated ductwork, piping, and control systems. The scope includes demolition of existing rooftop unit RTU-6, removal of existing ductwork connections, and installation of new supply and return ductwork, natural gas piping, and a 7-day programmable thermo-humidistat. A non-mandatory pre-bid conference is scheduled for 10:00 a.m. on Wednesday, August 26, 2026, at the police department's main entrance. Sealed bids must be submitted to the Town Clerk no later than 3:00 p.m. on Wednesday, September 9, 2026, marked "Greenburgh Police Department HVAC Improvements - Single Prime Bid." Technical questions are due by September 2, 2026, directed to John R. Longo at BBS Architects or CJ Geraldo of the Town of Greenburgh Bureau of Engineering. The project operates under a single-prime contractor model in which the general contractor serves as the prime and engages mechanical, plumbing, and electrical contractors as sub-contractors.
The bid documents specify that all mechanical work, including equipment installation, ductwork fabrication per SMACNA standards, system testing and balancing, firestopping, and commissioning, shall be performed by the mechanical contractor. The electrical contractor is responsible for power supply installation, temporary construction power and lighting, and coordination of fire/smoke damper controls. The mechanical contractor must provide complete operations and maintenance manuals, spare parts (including filters and motors), and ensure all new equipment is properly installed on reinforced concrete housekeeping pads. Testing and balancing reports must be submitted with independent verification of 25% of measurements; rejection criteria include deviations exceeding 10% or 2dB variance, which would require complete re-testing at the contractor's expense. No incumbent information is provided, and pricing terms are not detailed in the plans document itself; all work must comply with New York State Uniform Fire Prevention and Building Code and the state's Energy Conservation Construction Code.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| GPD HVAC - Project Manual.pdf | ||
| Greenburgh PD HVAC - Bid Addendum 1.pdf | ||
| GPD-HVAC Notice to Bidders.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TOWN OF GREENBURGH
DEPARTMENT OF PUBLIC WORKS
BUREAU OF ENGINEERING
177 HILLSDALE AVENUE, WHITE PLAINS NY 10607
GREENBURGH POLICE DEPARTMENT
HVAC IMPROVEMENTS - SINGLE PRIME BID
AUGUST 12, 2026
T0.01
BBS FILE NO. 26-129
BID PICK-UP: AUGUST 12, 2026
ENGINEER'S CERTIFICATION
THE UNDERSIGNED CERTIFIES THAT TO THE BEST OF HIS KNOWLEDGE, INFORMATION,
AND BELIEF, THE PLANS AND SPECIFICATIONS ARE IN ACCORDANCE WITH APPLICABLE
REQUIREMENTS OF THE NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING
CODE, THE NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, AND
THE CONSTRUCTION STANDARDS OF THE EDUCATION DEPARTMENT.
244 EAST MAIN STREET l PATCHOGUE l NEW YORK 11772 l T. 631.475.0349 l F. 631.475.0361 187 WOLF ROAD, SUITE 205 l ALBANY l NEW YORK 12205 l T. 518.621.7650 l F. 518.621.7655 www.BBSARCHITECTURE.COM bbs ARCHITECTS
LANDSCAPE ARCHITECTS
ENGINEERS
FREDERICK W. SEEBA, P.E. LIC. No. 068018
JULY 30, 2026
GREENBURGH POLICE DEPARTMENT
188 TARRYTOWN ROAD, WHITE PLAINS, NY
LIST OF DRAWINGS
T0.01 COVER SHEET
M0.01 MECHANICAL SYMBOLS, ABBREVIATIONS, GENERAL NOTES
M1.01 MECHANICAL DEMOLITION PLAN
M2.01 MECHANICAL NEW WORK PLAN
M6.01 MECHANICAL SCHEDULES AND DETAILS
E0.01 ELECTRICAL GENERAL NOTES AND LEGENDS
E1.01 ELECTRICAL FLOOR PLANS
SITE LOCATION MAP
SINGLE-PRIME CONTRACTOR BID NOTES:
1. THIS PROJECT SHALL BE A "SINGLE-PRIME" CONTRACTOR BID. THE PRIME
CONTRACTOR SHALL BE THE GENERAL CONTRACTOR (GC). THE GC SHALL BE
SUB-CONTRACTORS THAT INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOWING, MECHANICAL CONTRACTOR (MC), PLUMBING CONTRACTOR (PC),
ELECTRICAL CONTRACTOR (EC), ETC. THE MC, PC, & EC SHALL ALL BE
SUB-CONTRACTORS FOR THE PRIME CONTRACTOR WHICH SHALL BE THE GC.
2. ALL REFERENCES SHOWN ON PLANS FOR "MC" AND "EC" SHALL BE THE
RESPONSIBILITY OF THE SINGLE-PRIME CONTRACTOR (GC) WHO SHALL BE
THE CONTRACTOR OF RECORD.
EXP. 3-31-28
A.F.F.
B.D.
FSD
D.
GPM
H.C.
HWR
ABOVE FINISHED FLOOR
BACKDRAFT DAMPER
FIRE DAMPER - DUCT MOUNTED
DEEP / DEPTH
HANDICAPPED
HEATING SYSTEM HOT WATER RETURN
MAX.
RPM
S.P.
O.D.
ABBREVIATIONS
MAXIMUM
REVOLUTIONS PER MINUTE
STATIC PRESSURE
OUTSIDE DIAMETER
LWT LEAVING WATER TEMPERATURE
R.A. RETURN AIR
PREFAB PREFABRICATED
S.A. SUPPLY AIR
SCH. SCHEDULE
GALLONS PER MINUTE
CFM CUBIC FEET OF AIR PER MINUTE
F&T FLOAT & THERMOSTATIC
FPM FEET PER MINUTE
FO FLAT OVAL DUCTWORK
GPH GALLONS PER HOUR
HWS HEATING SYSTEM HOT WATER SUPPLY
KW KILOWATT
L. LONG
M.H. MANHOLE
MISC. MISCELLANEOUS
MTD. MOUNTED
N.I.C. NOT IN CONTRACT
No. / # NUMBER
NOM. NOMINAL
N.T.S. NOT TO SCALE
O.A. OUTSIDE AIR
O.C. ON CENTER
O.S. & Y OUTSIDE SCREW & YOKE
PSI POUNDS PER SQUARE INCH
STD. STANDARD
T TEMPERATURE
TXV THERMAL EXPANSION VALVE
TYP. TYPICAL
CWS COLD WATER SUPPLY
DIA./~ DIAMETER
FLEX FLEXIBLE
GAL. GALLONS
H. HIGH
HP HORSEPOWER
I.D. INSIDE DIAMETER
LAT LEAVING AIR TEMPERATURE
MIN. MINIMUM
MBH BTU x 1,000
MFR. MANUFACTURER
G NATURAL GAS
PE PNEUMATIC / ELECTRIC
PRV PRESSURE REDUCING VALVE
REQ'D REQUIRED
PIPING SYMBOL LEGEND
PIPING TO RISE UP
DESCRIPTIONSYMBOL
O.C. ON CENTER
G
P.A.
EG
HWS
HWR
MECHANICAL SYMBOL LEGEND
RECTANGULAR GALVANIZED DUCTWORK - DIMENSIONS 'W' x 'H'
DESCRIPTIONSYMBOL
24x12 / 20"~
42x18 FO
NEW SUPPLY DUCTWORK TO RISE UP
NEW SUPPLY DUCTWORK TO DROP DOWN
NEW RETURN DUCTWORK TO RISE UP
NEW RETURN DUCTWORK TO DROP DOWN
TRANSITION IN DUCTWORK
FIRE DAMPER INSTALLED IN DUCTWORK
VOLUME DAMPER IN DUCT (w/ LOCKING QUADRANT HANDLE)
ROUND DUCT WORK TO RISE UP
ROUND DUCTWORK TO DROP DOWN
FLAT OVAL DUCT WORK
ELBOW IN DUCTWORK (RADIUS + 1.5 x D)
45 DEG. TAKEOFF FITTING
90 DEG. TAKEOFF w/ BELLMOUTH FITTING
RECTANGULAR TO ROUND DUCT TRANSITION
ELBOW IN DUCTWORK w/ TURNING VANES
FLEXIBLE DUCTWORK TO DIFFUSER (4 FT. MAX. RUN)
4-WAY PATTERN CEILING DIFFUSER
3-WAY PATTERN CEILING DIFFUSER
2-WAY PATTERN CILING DIFFUSER (90 DEG. / OPPOSING PATTERN)
CEILING RETURN AIR REGISTER
DUCT FIRE DAMPER WITH ACCESS DOOR
DUCT COMBINATION FIRE/SMOKE DAMPER WITH ACCESS DOOR
1. PROVIDE ALL NEW DUCTWORK AS SHOWN AND SPECIFIED UNDER
SPECIFICATION SECTION 015891, AND IN CONFORMANCE WITH
'SMACNA' SPECIFICATIONS.
2. IF A DUCT ELBOW IS SHOWN TO BE RADIUSED, THEN RADIUSED
ELBOWS SHALL BE INSTALLED. SQUARE ELBOWS MAY NOT BE
SUBSTITUTED WHERE RADIUSED ELBOWS ARE SHOWN. WHERE
SQUARE ELBOWS ARE SHOWN, TURNING VANES SHALL BE
INSTALLED UPON APPROVAL BY THE ENGINEER.
3. PROVIDE DUCT LINING IN ALL DUCTWORK THAT IS CONVEYING
BELOW AMBIENT TEMPERATURE AIR & IS NOT INSULATED.
PROVIDE LINING IN SUPPLY & RETURN & EXHAUST AIR DUCTWORK
FROM AIR HANDLING EQUIPMENT FOR THE ENTIRE DUCTWORK
RUNS/LENGTHS FOR ALL DUCTWORK. IN ADDITION, INCLUDE
LINING IN ANY OTHER DUCT SPECIFICALLY SHOWN OR SPECIFIED
TO BE EQUIPPED WITH LINING. REFER TO SPECIFICATION
SECTION 15891 & 15290 FOR FURTHER INFORMATION.
4. WHERE FLEXIBLE DUCTWORK IS USED, LENGTHS MAY NOT
EXCEED 4 FEET TOTAL IN ANY ONE RUN OF FLEXIBLE DUCTWORK.
FLEXIBLE DUCTWORK SHALL BE RATED IN ACCORDANCE WITH UL
181, CLASS 1. REFER TO SPECIFICATION SECTION 15891 FOR
FURTHER INFORMATION.
5. MECHANICAL CONTRACTOR SHALL PROVIDE A BUTTERFLY TYPE
VOLUME DAMPER WITH LOCKING QUADRANT HANDLE PRIOR TO
EACH AIR OUTLET SHOWN. INSTALL DAMPER AT LEAST 5 FEET
AWAY FROM AIR OUTLET WHEREVER POSSIBLE.
6. MECHANICAL CONTRACTOR SHALL PROVIDE FLEXIBLE DUCT
CONNECTIONS WHERE DUCT SYSTEMS CONNECT TO EQUIPMENT.
REFER TO SPECIFICATION SECTION 15891 FOR FURTHER
INFORMATION.
DUCTWORK NOTES
1. MECHANICAL CONTRACTOR WILL BE REQUIRED TO PERFORM ALL
EQUIPMENT & SYSTEM TESTING / BALANCING REQUIRED UNDER THIS
CONTRACT. PROVIDE A FULL REPORT DETAILING ALL DESIGN & ACTUAL
CONDITIONS FOR ALL AIR & HYDRONIC SYSTEMS SHOWN ON THE
DRAWINGS. REFER TO SPECIFICATION SECTIONS 15990 & 15997 FOR
FURTHER DETAILS.
2. UPON NOTICE OF COMPLETION OF WORK BY THE CONTRACTOR, OWNER
WILL OBTAIN THE SERVICES OF AN INDEPENDENT TESTING & BALANCING
CONTRACTOR TO VERIFY THE RESULTS OF THE TESTING & BALANCING
REPORT SUBMISSION. INDEPENDENT TESTING AGENCY SHALL SELECT A
RANDOM NUMBER OF MEASUREMENTS TO BE CHECKED. MEASUREMENTS
WILL BE CHECKED IN THE SAME MANNER AS ORIGINALLY MEASURED.
NUMBER OF VERIFICATION MEASUREMENTS SHALL BE APPROXIMATELY
25% OF THE TOTAL MEASUREMENTS FOR THE PROJECT.
3. IF MORE THAN 10% OF THE VERIFICATION TESTING SHOWS DEVIATIONS OF
10% OR MORE / SOUND LEVEL OF 2dB DIFFERENT THAN THAT ORIGINALLY
MEASURED, THE ORIGINAL REPORT WILL BE REJECTED. ALL SYSTEMS WILL
THEN BE REQUIRED TO BE COMPLETELY RE-TESTED, WITH A SECOND
REPORT SUBMITTED. IN THE EVENT THAT THE ORIGINAL REPORT IS
REJECTED, ALL SYSTEMS SHALL BE READJUSTED & TESTED, NEW
CERTIFIED REPORTS SUBMITTED, AND NEW VERIFICATION TESTS MADE, AT
NO ADDITIONAL COST TO THE OWNER. THE CONTRACTOR WILL BE
RESPONSIBLE FOR ALL COSTS INVOLVED WITH THE VERIFICATION TESTS.
TESTING and BALANCING NOTES
1. MECHANICAL CONTRACTOR WILL BE RESPONSIBLE FOR THE PROPER VENTING OF ALL NEWLY INSTALLED HYDRONIC PIPING SYSTEMS. AUTOMATIC AIR VENTS SHALL BE INSTALLED AT EVERY HIGH POINT IN THE PIPING SYSTEM WHERE AIR CAN COLLECT. PROVIDE COCK IN RISER PRIOR TO AUTOMATIC AIR VENT.
NEW AIR VENTS SHALL BE "TACO" #HY-VENT OR EQUIVALENT.
2. MECHANICAL CONTRACTOR SHALL PROVIDE & INSTALL NEW AUTOMATIC AIR VENT FOR EACH AIR HANDLING UNIT COIL OR DUCT MOUNTED COIL. INSTALL SHUT-OFF COCK PRIOR TO VENT TIE-IN.
3. MECHANICAL CONTRACTOR SHALL PROVIDE NEW MANUAL AIR VENTS FOR ALL UNIT VENTILATOR COILS, CONVECTORS, FAN COIL UNITS, FIN TUBE RADIATORS, ETC. MANUAL VENTS SHALL BE "TACO" #417 COIN VENT OR EQUIVALENT. PROVIDE SHUT-OFF COCK PRIOR TO VENT. AIM COIN VENT DISCHARGE IN AN APPROPRIATE MANNER AS TO FACILITATE THE CAPTURE OF BLEED WATER WHILE PERFORMING SYSTEM
BLEEDING OPERATIONS.
PIPING SYSTEMS and EQUIPMENT VENTING NOTES
1. AT A MINIMUM, PROVIDE THERMOMETERS / WELLS AT THE FOLLOWING LOCATIONS:
· AT INLETS & OUTLET OF EACH THREE WAY VALVE (UNIT VENTILATORS / CABINET UNIT HEATER
INSTALLATIONS EXCEPTED).
· AT INLET & OUTLET OF EACH HYDRONIC BOILER, CHILLER OR COOLING TOWER.
· AT INLET & OUTLET OF EACH HYDRONIC COIL IN AIR HANDLING UNITS & BUILT-UP CENTRAL SYSTEMS.
2. AT A MINIMUM, PROVIDE LIQUID FILLED PRESSURE GAUGES / WELLS AT THE FOLLOWING LOCATIONS:
· AT SUCTION & DISCHARGE OF EACH PUMP.
· FOR EACH MAKEUP WATER LINE.
· BEFORE & AFTER ALL PRESSURE REDUCING VALVES.
· AT ACCESSIBLE HIGH POINT OF ALL HYDRONIC PIPING SYSTEMS.
· AT ALL EXPANSION / COMPRESSION TANKS.
GENERAL INSTRUMENTATION NOTES
1. ALL PENETRATIONS RELATED TO MECHANICAL WORK THROUGH FIRE RATED WALLS, FLOORS OR OTHER STRUCTURES SHALL BE FIRE STOPPED AS REQUIRED TO MAINTAIN THE RATING OF THE WALL BY MECHANICAL CONTRACTOR. IT IS ASSUMED THAT ALL WALLS IN THE CONSTRUCTION CARRY A MINIMUM FIRE RATING OF 1 HR. IT SHOULD BE ASSUMED THAT ALL MACHINE ROOM WALLS / BOILER ROOM WALLS / ELECTRIC ROOM WALLS CARRY A RATING OF 2 HR. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR A COMPLETE REVIEW OF THE ARCHITECTURAL DRAWINGS IN ORDER TO DETERMINE FIRE RATINGS OF
ALL WALLS / PARTITIONS RELATED TO WORK UNDER THIS CONTRACT.
2. MECHANICAL CONTRACTOR SHALL REVIEW THE COMPLETE ARCHITECTURAL SET OF DRAWINGS IN ORDER TO DETERMINE WHERE DUCT PENETRATIONS THROUGH RATED BARRIERS. DUCTS PENETRATING SAID RATED BARRIERS SHALL BE EQUIPPED WITH A UL LISTED FUSIBLE LINK TYPE FIRE DAMPER, RATED FOR SERVICE FOR WHICH IT IS BEING USED. FIRE DAMPERS SHALL BE PROVIDED & INSTALLED BY THE MECHANICAL CONTRACTOR, COMPLETE W/ DUCT ACCESS DOORS DIRECTLY ADJACENT TO THE DAMPER, POSITIONED FOR EASY REPLACEMENT OF THE LINK.
3. MECHANICAL CONTRACTOR SHALL REVIEW THE COMPLETE ARCHITECTURAL SET OF DRAWINGS IN ORDER TO DETERMINE WHERE DUCT PENETRATIONS THROUGH RATED BARRIERS OCCUR BETWEEN SEPARATE SMOKE ZONES. DUCTS PENETRATING SAID FIRE / SMOKE BARRIERS SHALL BE EQUIPPED WITH A UL LISTED COMBINATION FIRE / SMOKE DAMPER, RATED FOR SERVICE FOR WHICH IT IS BEING USED. FIRE / SMOKE DAMPERS SHALL BE PROVIDED & INSTALLED BY THE MECHANICAL CONTRACTOR, COMPLETE W/ DUCT ACCESS DOORS DIRECTLY ADJACENT TO THE DAMPER. DAMPER ACTUATOR & RELATED WIRING
SHALL BE PROVIDED & INSTALLED BY THE ELECTRICAL CONTRACTOR. COORDINATE DAMPER
INSTALLATIONS W/ E.C. TO VERIFY PROPER CLEARANCES TO ASSURE PROPER DAMPER OPERATION.
4. MECHANICAL CONTRACTOR SHALL PROVIDE A FULL SET OF AS-BUILT DRAWINGS, SHOWING EACH DAMPER
LOCATION, TYPE OF DAMPER, ACCESS DOOR LOCATIONS, ETC.
5. CONTRACTOR SHALL REFER TO SPECIFICATION SECTION 230680 FOR FURTHER DETAILS REGARDING FIRE
STOPPING MATERIALS & METHODS.
6. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF PRODUCTS TO BE USED. FIRESTOP MATERIALS OTHER THAN THE PRODUCTS SPECIFIED SHALL INCLUDE FULL TECHNICAL DATA WITH SHOP DRAWINGS TO
DEMONSTRATE EQUALITY WITH THE SPECIFIED FIRESTOPPING MATERIALS.
FIRESTOPPING NOTES
1. MECHANICAL CONTRACTOR SHALL PROVIDE ALL STARTERS & DISCONNECT SWITCHES REQUIRED FOR ALL NEW MECHANICAL EQUIPMENT. STARTER / DISCONNECT SWITCH INSTALLATION TO BE PERFORMED UNDER THE ELECTRICAL CONTRACT. COORDINATE WORK W/ ELECTRICAL CONTRACTOR PRIOR TO START
OF WORK.
2. POWER WIRING REQUIRED FOR CONTROLS SHALL BE PERFORMED UNDER THE MECHANICAL CONTRACT UNLESS SPECIFICALLY NOTED OTHERWISE ON THE ELECTRICAL DRAWINGS. MECHANICAL CONTRACTOR SHALL OBTAIN THE SERVICES OF A LICENSED ELECTRICIAN (PER NEC REQUIREMENTS) TO PERFORM ALL
ELECTRICAL WORK.
ELECTRICAL WORK UNDER MECHANICAL CONTRACT
1. REMOVAL & RELOCATION OF CERTAIN EXISTING WORK SHALL BE NECESSARY FOR THE PERFORMANCE OF THE NEW WORK SHOWN HEREIN. ALL EXISTING CONDITIONS ARE NOT COMPLETELY DETAILED ON THE DRAWINGS. THE CONTRACTOR SHALL SURVEY THE SITE & MAKE ALL NECESSARY CHANGES BASED ON EXISTING CONDITIONS AS REQUIRED FOR PROPER DEMOLITION OF EXISTING WORK & SHALL INCLUDE ALL MATERIALS & LABOR FOR SAME IN HIS BID PRICE. NO ALLOWANCE WILL BE MADE FOR FAILURE TO DO SO.
2. PRIOR TO SUBMITTING A BID, THE CONTRACTOR SHALL VISIT THE PREMISES OF THE PROPOSED WORK & SHALL CAREFULLY EXAMINE THE ENGINEERING DRAWINGS, EXISTING CONDITIONS & LIMITATIONS THEREOF. VERIFY ACTUAL LOCATIONS WHERE THE NEW PIPING WILL BE ROUTED, COORDINATE WITH NEW & EXISTING WORK & PROVIDE CLEARANCE W/ BUILDING STRUCTURE, OTHER SERVICES, ETC.. THE
CONTRACTOR SHALL INCLUDE ALL COSTS WHATSOEVER WHICH ARE INCURRED AS A RESULT OF
LIMITATIONS OF THE EXISTING & NEW CONDITIONS. LATER CLAIMS FOR EXTRA LABOR, EQUIPMENT, MATERIALS, ETC. REQUIRED DUE TO DIFFICULTIES WHICH COULD HAVE BEEN FORESEEN WILL NOT BE
CONSIDERED AS EXTRA WORK.
3. INSTALL WORK SO AS TO BE READILY ACCESSIBLE FOR OPERATING, MAINTENANCE & REPAIR. MINOR DEVIATIONS FROM DRAWINGS MAY BE MADE TO ACCOMPLISH THIS, BUT CHANGES OF MAGNITUDE WHICH
INVOLVE EXTRA COST SHALL NOT BE MADE WITHOUT APPROVAL.
4. INVESTIGATE EACH SPACE THROUGH WHICH EQUIPMENT MUST BE MOVED. WHEN NECESSARY,
EQUIPMENT SHALL BE SHIPPED FROM MANUFACTURER IN CRATED SECTIONS OF SIZE SUITABLE FOR MOVING THROUGH AREAS AVAILABLE. ASCERTAIN FROM BUILDING OWNER AT WHAT TIMES OF DAY
EQUIPMENT MAY BE MOVED THROUGH THE BUILDING.
5. COORDINATE THE EXACT SIZE & LOCATION OF NEW OPENINGS WITH EXISTING STRUCTURE. PATCH / INSULATE AS REQUIRED. CONTRACTOR SHALL FIRESTOP ALL PENETRATIONS FROM NEW PIPING, CONDUIT, DUCTWORK, ETC. THROUGH EXISTING OR NEW FIRE/ SMOKE BARRIERS. REFER TO
SPECIFICATION SECTION 15511 FOR FURTHER DETAILS.
6. IT IS THE INTENT OF THIS CONTRACT FOR REMAINING SYSTEMS TO BE LEFT IN GOOD WORKING ORDER, READY FOR OPERATION. COORDINATE ANY REQUIRED SYSTEM SHUTDOWNS WITH OWNER 48 HOURS IN ADVANCE. EXISTING SYSTEM SHUTDOWNS WILL NOT BE PERMITTED IF THEY INTERFERE WITH THE DAILY OPERATIONS OF THE BUILDING. CONTRACTOR WILL BE REQUIRED TO TAKE PROPER PRECAUTIONS AGAINST DAMAGING OR DISRUPTING BUILDING SYSTEMS, WIRING, PIPING OR CONTROL TUBING. ANY DAMAGE TO THESE ITEMS SHALL BE REPAIRED AT THE CONTRACTOR'S COST AS A PART OF THIS
CONTRACT.
7. THE CONTRACTOR SHALL REPAIR / RESTORE TO ORIGINAL CONDITION ANY EXISTING EQUIPMENT OR MATERIALS DAMAGED IN THE PROCESS OF INSTALLATION, OR DEMOLITION TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE. CONTRACTOR SHALL MAKE REPAIRS USING THE SAME OR EQUIVALENT
MATERIALS. WORK WILL BE PERFORMED AT THE CONTRACTOR'S COST.
8. CONTRACTOR SHALL INCUR ANY COSTS OR BURDENS ASSOCIATED WITH LOST OR STOLEN EQUIPMENT /
MATERIALS.
9. DURING THE LIFE OF THE CONTRACT PERIOD, CONTRACTOR SHALL REMOVE ALL RUBBISH / EXCESS MATERIAL ACCUMULATED AS A RESULT OF HIS OPERATIONS ON A DAILY BASIS. ALL AREAS / EQUIPMENT AFFECTED UNDER THIS CONTRACT SHALL BE KEPT CLEAN OF DUST / DEBRIS. ALL AREAS SHALL RECEIVE
A FINAL CLEANING PRIOR TO FINAL ACCEPTANCE BY THE OWNER.
10. PROVIDE FOR LEGAL REMOVAL / DISPOSAL OF ALL RUBBISH / DEBRIS FROM THE BUILDING & SITE.
PROTECT ALL WORK NOT SLATED FOR DEMOLITION.
11. THIS CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES PRIOR TO SCHEDULING THE WORK. WORK SHALL BE PERFORMED IN PROPER SEQUENCE, AS AGREED TO BY ALL TRADES. ANY COSTS INCURRED BY THE OWNER DUE TO IMPROPER SEQUENCING OF WORK WILL BE PAID FOR BY THIS
CONTRACTOR.
12. CONTRACTOR SHALL FILE AND OBTAIN ALL TOWN PERMITS, PAY ALL PERMIT FEES, CONNECTION
CHARGES, ETC. ASSOCIATED WITH THE WORK UNDER THEIR CONTRACT.
13. PAINT / TOUCH UP ALL SURFACES MARRED AS A RESULT OF THE PERFORMANCE OF THE CONTRACT
WORK.
14. THE MECHANICAL CONTRACTOR SHALL REFER TO / REVIEW ALL OTHER TRADE DRAWINGS IN THE BID PACKAGE & SHALL BE RESPONSIBLE FOR / PERFORM ALL WORK INDICATED AS (M.C.) MECHANICAL WORK
AS A PART OF THE BASE BID UNLESS SPECIFICALLY NOTED OTHERWISE.
15. SUBSTITUTED EQUIPMENT OF GREATER OR LARGER POWER, DIMENSIONS, CAPACITIES & RATINGS MAY BE FURNISHED PROVIDED THAT SAID EQUIPMENT IS APPROVED IN WRITING PRIOR TO ORDER. ANY CONNECTING MECHANICAL SERVICES, ELECTRICAL SERVICES, BASES, STRUCTURAL APPURTENANCES, ETC. REQUIRED TO BE INCREASED DUE TO THE USE OF SAID EQUIPMENT WILL BE PAID FOR IN FULL BY
THE MECHANICAL CONTRACTOR, INCLUDING ANY ADDITIONAL REQUIRED ENGINEERING FEES.
16. EACH PIECE OF EQUIPMENT SHALL BE PROVIDED WITH A PERMANENT TYPE LAMINATED, BLACK FINISH, WHITE CORE, PHENOLIC NAMEPLATE. NAMEPLATES SHOULD INDICATE THE NAME & NUMBER OF THE UNIT, UNIT VOLTAGE, & ANY INTERLOCK REFERENCE. STARTERS / DISCONNECT SWITCHES SHOULD ALSO BE
EQUIPPED WITH AN IDENTICAL NAMEPLATE WITH THE SAME INFORMATION.
17. "ATTIC STOCK" - UPON COMPLETION OF THE PROJECT, MECHANICAL CONTRACTOR SHALL COMPLETELY REMOVE / DISPOSE OF FILTERS USED DURING CONSTRUCTION & START-UP PROCEDURES. INSTALL NEW FILTERS IN ALL EQUIPMENT, MERV-8 OR BETTER UPON TURN OVER OF THE PROJECT TO THE OWNER. IN ADDITION, PROVIDE (2) COMPLETE SETS OF FILTERS FOR EACH PEICE OF EQUIPMENT & TURN OVER TO
OWNER.
18. MECHANICAL CONTRACTOR SHALL PROVIDE (1) SPARE MOTOR FOR EACH SIZE MOTOR USED ON THE
PROJECT. IN INSTANCES WHERE MORE THAN TEN OF THE SAME MOTOR ARE USED, MECHANICAL
CONTRACTOR SHALL PROVIDE (1) SPARE MOTOR FOR EVERY TEN MOTORS OF A GIVEN SIZE USED ON THE
PROJECT.
19. MAINTENANCE MANUAL: UPON COMPLETION OF THE PROJECT, THE MECHANICAL CONTRACTOR SHALL PROVIDE A BINDER CONTAINING THE OPERATIONS & MAINTENANCE MANUALS FOR EACH NEW PEICE OF EQUIPMENT INSTALLED UNDER THIS PROJECT. THE FIRST SECTION OF THE MAINTENANCE MANUAL SHALL CONTAIN A LIST OF EACH PEICE OF EQUIPMENT, COMPLETE WITH INFORMATION SHOWING APPROPRIATE REPLACEMENT FILTER SIZES / TYPES, APPROPRIATE REPLACEMENT BELT SPECIFICATIONS, REPLACEMENT MOTOR SPECIFICATIONS, REPLACEMENT BEARING SPECIFICATIONS, VOLTAGES OF UNIT, ETC. THIS SHALL SERVE AS A WRITTEN DATABASE DESCRIBING ALL MAINTENANCE INFORMATION FOR EACH NEW PEICE OF
EQUIPMENT USED.
GENERAL NOTES
1. THE DRAWINGS SHOW THE GENERAL ARRANGEMENT OF ALL PIPING &
EQUIPMENT, & INDICATE THE REQUIRED SIZE / POINTS OF TERMINATION OF THE
PIPING & SUGGEST PROPER ROUTING OF SAME. IT IS NOT THE INTENTION OF
THE DRAWINGS TO SHOW ALL NECESSARY OFFSETS, RISES, DROPS,
OBSTRUCTIONS OR STRUCTURAL CONDITIONS. IT SHALL BE THE
RESPONSIBILITY OF THIS CONTRACTOR TO INSTALL HIS WORK IN SUCH A
MANNER THAT IT WILL CONFORM TO THE STRUCTURE, AVOID OBSTRUCTIONS,
PRESERVE HEADROOM & KEEP OPENINGS / PASSAGEWAYS CLEAR WITHOUT
FURTHER CONSTRUCTION OR COST.
2. ALL FLOOR MOUNTED BOILER ROOM EQUIPMENT SHALL BE INSTALLED ON A
LEVEL, REINFORCED CONCRETE HOUSEKEEPING PAD, 4" THICK MIN. UNLESS
OTHERWISE NOTED. ALL HOUSEKEEPING PADS SHALL BE INSTALLED BY THE
MECHANICAL CONTRACTOR. PADS SHALL BE REINFORCED W/ WELDED WIRE
MESH & SHALL BE POURED USING 3,000 PSI CONCRETE.
3. MECHANICAL CONTRACTOR SHALL PROVIDE & INSTALL ALL REQUIRED
STRUCTURAL SUPPORTS FOR ALL PIPING SYSTEMS & EQUIPMENT AS
REQUIRED. PIPING SYSTEMS SHALL BE EQUIPPED WITH EXPANSION
COMPENSATORS AT THE INTERVALS REQUIRED. PROVIDE PIPING GUIDES /
ANCHORS AS REQUIRED.
4. MECHANICAL CONTRACTOR SHALL PROPERLY INSULATE ALL NEW PIPING
SYSTEMS & EQUIPMENT. REFER TO SPECIFICATION SECTION 15250 FOR
FURTHER DETAILS REGARDING INSULATION REQUIREMENTS. UPON
COMPLETION OF INSULATION WORK, MECHANICAL CONTRACTOR SHALL
PROPERLY LABEL EACH PIPING RUN SHOWING THE TYPE OF FLUID CARRIED &
DIRECTION OF FLOW. PIPE IDENTIFICATION MARKERS SHALL BE INSTALLED
EVERY 20 FEET IN THE PIPING RUNS.
5. ALL VALVES WITHIN PIPING SYSTEMS SHALL BE TAGGED USING A 1-1/2" DIA.
BRASS TAG. PROVIDE A LEGEND LISTING VALVE #, TYPE OF VALVE, SERVICE
TYPE, & LOCATION OF VALVE. KEY VALVE #'S TO AS-BUILT DRAWINGS UPON
COMPLETION OF PROJECT.
6. MECHANICAL CONTRACTOR SHALL SUBMIT (3) SETS OF OPERATING MANUALS
FOR EACH PIECE / TYPE OF MECHANICAL EQUIPMENT.
7. MECHANICAL CONTRACTOR SHALL PROVIDE & INSTALL ALL WIRING & DEVICES
AS REQUIRED TO CONTROL THE BOILER ROOM EQUIPMENT AS DESCRIBED IN
THE SEQUENCE OF OPERATIONS LISTED IN THE PROJECT MANUAL. REFER TO
SPECIFICATION SECTIONS FOR FURTHER DETAILS.
BOILER ROOM and PIPING NOTES
PIPING TO DROP DOWN
PIPING ANCHOR
PIPING GUIDE
COLD WATER SUPPLY PIPING
HEATING SYSTEM SUPPLY PIPING
HEATING SYSTEM RETURN PIPING
LOW PRESSURE NATURAL GAS PIPING
ELEVATED PRESSURE NATURAL GAS PIPING
GAS COCK
DIRT LEG IN PIPING
VOL.
V.D.
VEL.
VOLUME
VFD
VOLUME DAMPER
W.
VELOCITY
W/
VARIABLE FREQUENCY DRIVE
W/O WITHOUT
WB WET BULB TEMPERATURE
WTD WATER TEMPERATURE DROP
WTR WATER TEMPERATURE RISE
WPD WATER PRESSURE DROP
WITH
WIDE
VENTILATION SCHEDULE
CONNECTION POINT OF NEW WORK TO BE DONE
CONNECTION POINT OF DEMOLITION WORK TO BE DONE
LINEAR SLOT DIFFUSER
ROOF MOUNTED EXHAUST FAN
FD/AD
FSD/AD
NOTICE
THESE DRAWINGS ARE BASED ON CONSTRUCTION DRAWINGS NOT
PREPARED BY BBS ARCHITECTS, LANDSCAPE ARCHITECTS AND
ENGINEERS, PC. AND, THEREFORE, MAY NOT REPRESENT THE
CONDITIONS AS CONSTRUCTED AT THE TIME. ALL EXISTING
CONDITIONS SHOWN ARE REPRESENTED AS SUGGESTIVE
INFORMATION AS THEY MAY NOT HAVE BEEN BUILT AND DETAILED
PER THE ORIGINAL DOCUMENTS OR PER THE OWNER'S INFORMATION.
ME
CH
AN
IC
AL
ME
CH
AN
IC
AL
_S
YM
BO
LS
-A
BB
RE
V.
-G
EN
ER
AL
-N
OT
ES
U.F.
U.F.
AS-NOTED
MECHANICAL-SYMBOLS
ABBREV.,AND_GENERAL-NOTES
M0.01
244 EAST MAIN STREET
PATCHOGUE
NEW YORK 11772
T. 631.475.0349 F. 631.475.0361
187 WOLF ROAD, STE. 205
ALBANY
NEW YORK 12205
T. 518.621.7650 F. 518.621.7655 bbs
ARCHITECTS
LANDSCAPE ARCHITECTS
ENGINEERS
www.BBSARCHITECTURE.com
DATE
PR
OJ
EC
T
DW
G
TI
TL
E
DRAWING BY:
CHECK BY:
REV. ITEM
NOTICE
THIS DRAWING, PREPARED FOR THE SPECIFIC PROJECT INDICATED IS
AN INSTRUMENT OF SERVICE AND THE PROPERTY OF BBS
ARCHITECTS, LANDSCAPE ARCHITECTS AND ENGINEERS, PC.
INFRINGEMENT OR ANY USE OF THIS DRAWING FOR ANY OTHER
PROJECT IS PROHIBITED. ANY ALTERATION OR REPRODUCTION OF
THIS DOCUMENT IS ALSO PROHIBITED WITHOUT THE WRITTEN
CONSENT OF THE ARCHITECT OR ENGINEER.
FILE No:
BID PICK-UP:
DATE:
SCALE:
OWNER
PROJECT
DWG TITLE
BUILDING No.
ALTERATION OF THIS DOCUMENT, UNLESS
UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, IS A
VIOLATION OF SECTION 7209 OF ARTICLE
145 OF THE NYS EDUCATION LAW
CD CONDENSATE DRAINAGE PIPING
KEY PLAN
NOT TO SCALE
TO
W
N
OF
G
RE
EN
BU
RG
H
DE
PA
RT
ME
NT
O
F
PU
BL
IC
W
OR
KS
PO
LIC
E
DE
PA
RT
ME
NT
H
VA
C
IM
PR
OV
EM
EN
TS
TO
W
N
OF
G
RE
EN
BU
RG
H
/ W
ES
TC
HE
ST
ER
C
OU
NT
Y
/ N
EW
Y
OR
K
TOWN OF GREENBURGH
DEPT. OF PUBLIC WORKS
POLICE DEPARTMENT
HVAC IMPROVEMENTS
JULY 31, 2026
AUGUST 12, 2026
26-129
SINGLE-PRIME CONTRACTOR BID NOTES:
1. THIS PROJECT SHALL BE A "SINGLE-PRIME" CONTRACTOR BID. THE PRIME
CONTRACTOR SHALL BE THE GENERAL CONTRACTOR (GC). THE GC SHALL BE
SUB-CONTRACTORS THAT INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOWING, MECHANICAL CONTRACTOR (MC), PLUMBING CONTRACTOR (PC),
ELECTRICAL CONTRACTOR (EC), ETC. THE MC, PC, & EC SHALL ALL BE
SUB-CONTRACTORS FOR THE PRIME CONTRACTOR WHICH SHALL BE THE GC.
2. ALL REFERENCES SHOWN ON PLANS FOR "MC" AND "EC" SHALL BE THE
RESPONSIBILITY OF THE SINGLE-PRIME CONTRACTOR (GC) WHO SHALL BE
NOTICE
THESE DRAWINGS ARE BASED ON CONSTRUCTION DRAWINGS NOT
PREPARED BY BBS ARCHITECTS, LANDSCAPE ARCHITECTS AND
ENGINEERS, PC. AND, THEREFORE, MAY NOT REPRESENT THE
CONDITIONS AS CONSTRUCTED AT THE TIME. ALL EXISTING
CONDITIONS SHOWN ARE REPRESENTED AS SUGGESTIVE
INFORMATION AS THEY MAY NOT HAVE BEEN BUILT AND DETAILED
PER THE ORIGINAL DOCUMENTS OR PER THE OWNER'S INFORMATION.
ME
CH
AN
IC
AL
DE
MO
LIT
IO
N_
PL
AN
U.F.
U.F.
AS-NOTED
MECHANICAL_DEMOLITION
PLAN
M1.01
244 EAST MAIN STREET
PATCHOGUE
NEW YORK 11772
T. 631.475.0349 F. 631.475.0361
187 WOLF ROAD, STE. 205
ALBANY
NEW YORK 12205
T. 518.621.7650 F. 518.621.7655 bbs
ARCHITECTS
LANDSCAPE ARCHITECTS
ENGINEERS
www.BBSARCHITECTURE.com
DATE
PR
OJ
EC
T
DW
G
TI
TL
E
DRAWING BY:
CHECK BY:
REV. ITEM
NOTICE
THIS DRAWING, PREPARED FOR THE SPECIFIC PROJECT INDICATED IS
AN INSTRUMENT OF SERVICE AND THE PROPERTY OF BBS
ARCHITECTS, LANDSCAPE ARCHITECTS AND ENGINEERS, PC.
INFRINGEMENT OR ANY USE OF THIS DRAWING FOR ANY OTHER
PROJECT IS PROHIBITED. ANY ALTERATION OR REPRODUCTION OF
THIS DOCUMENT IS ALSO PROHIBITED WITHOUT THE WRITTEN
CONSENT OF THE ARCHITECT OR ENGINEER.
FILE No:
BID PICK-UP:
DATE:
SCALE:
OWNER
PROJECT
DWG TITLE
BUILDING No.
ALTERATION OF THIS DOCUMENT, UNLESS
UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, IS A
VIOLATION OF SECTION 7209 OF ARTICLE
145 OF THE NYS EDUCATION LAW
KEY PLAN
NOT TO SCALE
TO
W
N
OF
G
RE
EN
BU
RG
H
DE
PA
RT
ME
NT
O
F
PU
BL
IC
W
OR
KS
PO
LIC
E
DE
PA
RT
ME
NT
H
VA
C
IM
PR
OV
EM
EN
TS
TO
W
N
OF
G
RE
EN
BU
RG
H
/ W
ES
TC
HE
ST
ER
C
OU
NT
Y
/ N
EW
Y
OR
K
TOWN OF GREENBURGH
DEPT. OF PUBLIC WORKS
POLICE DEPARTMENT
HVAC IMPROVEMENTS
JULY 31, 2026
THIRD FLOOR ROOF LEVEL-TOWN
OF GREENBURG - POLICE
DEPARTMENT-OVERALL KEY PLAN
SCALE: 1/64" = 1'-0"
POLICE DETECTIVE
OFFICE SUITE ROOF
- AREA OF WORK
MECHANICAL - ROOF LEVEL- DETECTIVE OFFICE SUITE ROOF - MECHANICAL DEMOLITION WORK - PARTIAL PLAN
TOWN OF GREENBURG-POLICE DEPARTMENT SCALE: 1/4" = 1'-0"
THIRD FLOOR -TOWN OF GREENBURG -
POLICE DEPARTMENT-OVERALL KEY PLAN
SCALE: 1/64" = 1'-0"
POLICE DETECTIVE
OFFICE SUITE - AREA
OF WORK
MECHANICAL - THIRD FLOOR- DETECTIVE OFFICE SUITE - MECHANICAL DEMOLITION WORK - PARTIAL RCP PLAN
TOWN OF GREENBURG-POLICE DEPARTMENT SCALE: 1/4" = 1'-0"
x x x x xx x x xx x x x x xx x x x x x x x x x x
X1
2( E)
23X12(E)
23X12(E)
23X14(E)
27X18(E)
34X18(E)34X18(E)
MECHANICAL - ROOF LEVEL - DETECTIVE OFFICE SUITE ROOF -MECHANICAL DEMOLITION
WORK- PARTIAL PLAN - KEY PLAN NOTES:
1 EXISTING ROOFTOP SUPPLY DUCTWORK TO REMAIN & BE RE-USED. EXISTING
DUCTWORK SIZES NOTED ON PLANS.
2 EXISTING ROOFTOP RETURN DUCTWORK TO REMAIN & BE RE-USED. EXISTING
DUCTWORK SIZES NOTED ON PLANS.
3 EXISTING ROOFTOP UNIT (RTU-5) SERVING POLICE CAPTAIN'S OFFICE SUITE TO
REMAIN IN PLACE & IS SHOWN FOR COORDINATION PURPOSES ONLY.
4 EXISTING ROOFTOP SUPPLY DUCTWORK FOR EXISTING RTU-5 TO REMAIN & BE
RE-USED. EXISTING DUCTWORK SIZES NOTED ON PLANS.
5 EXISTING ROOFTOP RETURN DUCTWORK FOR EXISTING RTU-5 TO REMAIN & BE
RE-USED. EXISTING DUCTWORK SIZES NOTED ON PLANS.
1-1/2"Ø(E) 1-1/2"Ø(E)
1-1/4"Ø(E)
1"Ø(E)
1-1/4"Ø(E)
6 EXISTING 16X16 SUPPLY DUCT PENETRATION INTO ROOF FOR EXISTING RTU-5 TO
REMAIN & BE RE-USED.
27X18(E)
27X18(E)
27X18(E) TO
23X14(E) DUCT
TRANSITION
EXISTING 23X14(E)
DUCT OFFSET
EPT
GENERAL DEMOLITION NOTES:
1. MC SHALL FIELD VERIFY ALL EXISTING DIMENSIONS, ALL DUCTWORK SIZES,
ALL EQUIPMENT DIMENSIONS & NOTE ALL ITEMS REQUIRED TO REMAIN IN A
SUBMITTED DUCTWORK SHOP DRAWING FOR REVIEW/APPROVAL PROCESS
BY ARCHITECT/ENGINEER OF RECORD.
MECHANICAL - THIRD FLOOR - DETECTIVE OFFICE
SUITE -MECHANICAL DEMOLITION WORK-
PARTIAL PLAN - KEY PLAN NOTES:
1 EXISTING CEILING PLENUM SPACE HAS 12" DEEP BAR JOISTS SPACED 28" ON
CENTER. THERE IS APPROXIMATELY 4" OF SPACE BELOW BAR JOIST TO TOP OF
EXISTING DROP CEILING. MC SHALL FIELD VERIFY THE EXACT STRUCTURAL DETAILS
PRIOR TO START OF ANY WORK.
8 EXISTING 1-1/2"Ø NATURAL GAS PIPING MAIN TO REMAIN & BE RE-USED.
REFER TO NEW WORK PLANS FOR FURTHER DETAILS.
X1
6( E)
14X24(E)
MC TO HIRE A LICENSED PLUMBING CONTRACTOR (PC) TO PERFORM
DEMOLITION WORK FOR EXISTING NATURAL GAS PIPING SHOWN. MC SHALL
HAVE PC CUT BACK EXISTING 1-1/4"Ø NATURAL GAS PIPING AS SHOWN BACK
TO EXISTING GAS COCK SHOWN.
9 EXISTING 1-1/4"Ø NATURAL GAS PIPING SERVING EXISTING ROOFTOP UNIT
(RTU-5) SHALL REMAIN & BE RE-USED & IS SHOWN FOR COORDINATION
PURPOSES.
10 EXISTING 1-1/2"Ø NATURAL GAS PIPING SERVING EXISTING ROOFTOP UNIT
(RTU-6) SHALL BE RE-USED FOR NEW ROOFTOP UNIT RTU-6. REFER TO NEW
WORK PLANS FOR SCOPE OF WORK FOR PLUMBING CONTRACTOR (PC).
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING LADDER
TO HIGHER ROOF
LOWER ROOF
LOWER ROOF
HIGHER ROOF
HIGHER ROOF
LOWER ENTRYWAY
COVER
LOWER ENTRYWAY
COVER
LOWER ROOF
xxx x x x x x x
11 EXISTING 32X32 RETURN DUCTWORK UP THROUGH ROOF TO REMAIN & BE
REUSED.
12 MC TO DEMOLISH & REMOVE EXISTING 17X34 EXTERIOR RETURN DUCT
CONNECTION TO UNIT & TO DEMOLISH & REMOVE EXISTING SECTION OF
34X18 EXTERIOR RETURN DUCTWORK SHOWN.
14 MC TO DEMOLISH & REMOVE EXISTING 24X24 TO 27X18 EXTERIOR SUPPLY
DUCT CONNECTION TO UNIT AS SHOWN.
15 MC TO HAVE EC DISCONNECT POWER TO EXISTING UNIT RTU-6 PRIOR TO
START OF ANY DEMOLITION WORK. MC TO THEN DEMOLISH & REMOVE
EXISTING ROOFTOP UNIT RTU-6 & LEGALLY DISPOSE OF UNIT.
16 MC TO HIRE CERTIFIED ROOFING/GENERAL CONTRACTOR (GC) TO DEMOLISH
& REMOVE EXISTING ROOFTOP UNIT RTU-6 THY CURB SUPPORTS & PATCH
EXISTING ROOF SECTIONS.
17 MC TO RE-USED EXISTING 16X16 ROOF SUPPLY OPENINGS (TYPICAL OF 5
TOTAL).
2 EXISTING DROP CEILING GRID IS 24X24 TILES/GRID AS SHOWN & SHALL BE RE-USED.
3 EXISTING 24X24 LAY-IN TYPE SUPPLY DIFFUSERS TO REMAIN & BE RE-USED (TYPICAL
OF 5 TOTAL).
4 EXISTING 24X24 LAY-IN TYPE RETURN GRILLE TO REMAIN & BE RE-USED (TYPICAL OF
ONE TOTAL).
5 MC SHALL HAVE EC DISCONNECT POWER TO EXISTING PROGRAMMABLE WALL
MOUNTED THERMOSTAT. MC TO THEN REMOVE THERMOSTAT. REFER TO NEW
WORK PLANS FOR FURTHER DETAILS OF NEW WORK.
GENERAL DEMOLITION NOTES:
1. MC SHALL FIELD VERIFY ALL EXISTING DIMENSIONS, ALL DUCTWORK SIZES,
ALL EQUIPMENT DIMENSIONS & NOTE ALL ITEMS REQUIRED TO REMAIN IN A
SUBMITTED DUCTWORK SHOP DRAWING FOR REVIEW/APPROVAL PROCESS
BY ARCHITECT/ENGINEER OF RECORD.
2. MC SHALL BE ENTIRELY RESPONSIBLE FOR REMOVAL OF ANY REQUIRED
EXISTING DROP CEILING TILES/GRID TO ANY DEMOLITION/NEW WORK
REQUIRED. UPON COMPLETION OF ALL WORK, MC SHALL RE-INSTALL
EXISTING CEILING TILES/GRID. ANY GRID/TILES DAMAGED BY MC SHALL BE
REPLACED WITH AN EQUAL AT THE MC'S OWN EXPENSE.
6 EXISTING ROOF LEADER DRAIN RUNNING IN ROOF & IS SHOWN FOR COORDINATION
PURPOSES.
SINGLE-PRIME CONTRACTOR BID NOTES:
1. THIS PROJECT SHALL BE A "SINGLE-PRIME" CONTRACTOR BID. THE PRIME
CONTRACTOR SHALL BE THE GENERAL CONTRACTOR (GC). THE GC SHALL BE
SUB-CONTRACTORS THAT INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOWING, MECHANICAL CONTRACTOR (MC), PLUMBING CONTRACTOR (PC),
ELECTRICAL CONTRACTOR (EC), ETC. THE MC, PC, & EC SHALL ALL BE
SUB-CONTRACTORS FOR THE PRIME CONTRACTOR WHICH SHALL BE THE GC.
2. ALL REFERENCES SHOWN ON PLANS FOR "MC" AND "EC" SHALL BE THE
RESPONSIBILITY OF THE SINGLE-PRIME CONTRACTOR (GC) WHO SHALL BE
PREPARED BY BBS ARCHITECTS, LANDSCAPE ARCHITECTS AND
ENGINEERS, PC. AND, THEREFORE, MAY NOT REPRESENT THE
CONDITIONS AS CONSTRUCTED AT THE TIME. ALL EXISTING
CONDITIONS SHOWN ARE REPRESENTED AS SUGGESTIVE
INFORMATION AS THEY MAY NOT HAVE BEEN BUILT AND DETAILED
PER THE ORIGINAL DOCUMENTS OR PER THE OWNER'S INFORMATION.
ME
CH
AN
IC
AL
NE
W _W
OR
K_
PL
AN
U.F.
U.F.
AS-NOTED
MECHANICAL_NEW
WORK_PLAN
M2.01
244 EAST MAIN STREET
PATCHOGUE
NEW YORK 11772
T. 631.475.0349 F. 631.475.0361
187 WOLF ROAD, STE. 205
ALBANY
NEW YORK 12205
T. 518.621.7650 F. 518.621.7655 bbs
ARCHITECTS
LANDSCAPE ARCHITECTS
ENGINEERS
www.BBSARCHITECTURE.com
DATE
PR
OJ
EC
T
DW
G
TI
TL
E
DRAWING BY:
CHECK BY:
REV. ITEM
NOTICE
THIS DRAWING, PREPARED FOR THE SPECIFIC PROJECT INDICATED IS
AN INSTRUMENT OF SERVICE AND THE PROPERTY OF BBS
ARCHITECTS, LANDSCAPE ARCHITECTS AND ENGINEERS, PC.
INFRINGEMENT OR ANY USE OF THIS DRAWING FOR ANY OTHER
PROJECT IS PROHIBITED. ANY ALTERATION OR REPRODUCTION OF
THIS DOCUMENT IS ALSO PROHIBITED WITHOUT THE WRITTEN
CONSENT OF THE ARCHITECT OR ENGINEER.
FILE No:
BID PICK-UP:
DATE:
SCALE:
OWNER
PROJECT
DWG TITLE
BUILDING No.
ALTERATION OF THIS DOCUMENT, UNLESS
UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, IS A
VIOLATION OF SECTION 7209 OF ARTICLE
145 OF THE NYS EDUCATION LAW
KEY PLAN
NOT TO SCALE
TO
W
N
OF
G
RE
EN
BU
RG
H
DE
PA
RT
ME
NT
O
F
PU
BL
IC
W
OR
KS
PO
LIC
E
DE
PA
RT
ME
NT
H
VA
C
IM
PR
OV
EM
EN
TS
TO
W
N
OF
G
RE
EN
BU
RG
H
/ W
ES
TC
HE
ST
ER
C
OU
NT
Y
/ N
EW
Y
OR
K
TOWN OF GREENBURGH
DEPT. OF PUBLIC WORKS
POLICE DEPARTMENT
HVAC IMPROVEMENTS
JULY 31, 2026
THIRD FLOOR ROOF LEVEL-TOWN
OF GREENBURG - POLICE
DEPARTMENT-OVERALL KEY PLAN
SCALE: 1/64" = 1'-0"
POLICE DETECTIVE
OFFICE SUITE ROOF
- AREA OF WORK
MECHANICAL - ROOF LEVEL- DETECTIVE OFFICE SUITE ROOF - MECHANICAL NEW WORK - PARTIAL PLAN
TOWN OF GREENBURG-POLICE DEPARTMENT SCALE: 1/4" = 1'-0"
THIRD FLOOR -TOWN OF GREENBURG -
POLICE DEPARTMENT-OVERALL KEY PLAN
SCALE: 1/64" = 1'-0"
POLICE DETECTIVE
OFFICE SUITE - AREA
OF WORK
MECHANICAL - THIRD FLOOR- DETECTIVE OFFICE SUITE - MECHANICAL NEW WORK - PARTIAL RCP PLAN
TOWN OF GREENBURG-POLICE DEPARTMENT SCALE: 1/4" = 1'-0"
MECHANICAL - ROOF LEVEL - DETECTIVE OFFICE SUITE ROOF -MECHANICAL NEW WORK-
PARTIAL PLAN - KEY PLAN NOTES:
PT
GENERAL NEW WORK NOTES:
1. MC SHALL FIELD VERIFY ALL EXISTING DIMENSIONS, ALL DUCTWORK SIZES,
ALL EQUIPMENT DIMENSIONS & NOTE ALL ITEMS REQUIRED TO REMAIN IN A
SUBMITTED DUCTWORK SHOP DRAWING FOR REVIEW/APPROVAL PROCESS
BY ARCHITECT/ENGINEER OF RECORD.
2. MC SHALL HAVE GC FURNISH & INSTALL NEW ROOF RAIL FOR RIGHT
SIDE/SECTION OF NEW ROOFTOP UNIT (RTU-DETECTIVE OFFICE) SHOWN.
3. MC SHALL HAVE APPROVED ROOFTOP UNIT MANUFACTURER PROVIDE
STARTERS & DISCONNECTS FOR NEW ROOFTOP UNIT. MC SHALL PROVIDE
STARTER AND DISCONNECT FOR UNIT TO EC FOR EC TO INSTALL & FLASH
WITH MC PRESENT.
MECHANICAL - THIRD FLOOR - DETECTIVE OFFICE
SUITE -MECHANICAL NEW WORK- PARTIAL PLAN -
KEY PLAN NOTES:
1 MC SHALL FURNISH & INSTALL NEW 7-DAY PROGRAMMABLE THERMO-HUMIDI-STAT
ON WALL. REFER TO SCHEDULES PLANS FOR POWER REQUIREMENT DETAILS.
LOWER ROOF
GENERAL NEW WORK NOTES:
1. MC SHALL FIELD VERIFY ALL EXISTING DIMENSIONS, ALL DUCTWORK SIZES,
ALL EQUIPMENT DIMENSIONS & NOTE ALL ITEMS REQUIRED TO REMAIN IN A
SUBMITTED DUCTWORK SHOP DRAWING FOR REVIEW/APPROVAL PROCESS
BY ARCHITECT/ENGINEER OF RECORD.
2. MC SHALL BE ENTIRELY RESPONSIBLE FOR REMOVAL OF ANY REQUIRED
EXISTING DROP CEILING TILES/GRID TO ANY DEMOLITION/NEW WORK
REQUIRED. UPON COMPLETION OF ALL WORK, MC SHALL RE-INSTALL
EXISTING CEILING TILES/GRID. ANY GRID/TILES DAMAGED BY MC SHALL BE
REPLACED WITH AN EQUAL AT THE MC'S OWN EXPENSE.
X1
2( E)
23X12(E)
23X12(E)
23X14(E)
27X18(E)
34X18(E)
1-1/2"Ø(E) 1-1/2"Ø(E)
1-1/4"Ø(E)
1"Ø(E)
1-1/4"Ø(E)
27X18(E)
27X18(E)
27X18(E) TO
23X14(E) DUCT
TRANSITION
EXISTING 23X14(E)
DUCT OFFSET
X1
6( E)
14X24(E)
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING ROOF
EDGE
EXISTING LADDER
TO HIGHER ROOF
LOWER ROOF
LOWER ROOF
HIGHER ROOF
LOWER ENTRYWAY
COVER
LOWER ENTRYWAY
COVER
1 MC SHALL FURNISH & INSTALL 18X15 FLEXIBLE SUPPLY DUCTWORK CONNECTION &
MC SHALL THEN INSTALL NEW 18X15 EXTERIOR SUPPLY DUCTWORK AS SHOWN &
RUN A NEW SIX-INCH LENGTH 18X15 EXTERIOR SUPPLY DUCTWORK PIECE THEN MC
SHALL DO AN ECCENTRIC DUCT TRANSITION TO 27X18 SIZE & CONNECT TO EXISTING
27X18 EXTERIOR SUPPLY DUCTWORK.
2 MC SHALL FURNISH & INSTALL 14X24 FLEXIBLE RETURN DUCTWORK CONNECTION &
MC SHALL THEN INSTALL NEW 14X24 EXTERIOR SUPPLY DUCTWORK AS SHOWN & DO
AN ECCENTRIC DUCT TRANSITION FROM 24X24 FACE/SIZE TO A 27X18 FACE/SIZE &
CONNECT TO EXISTING 27X18 EXTERIOR RETURN DUCTWORK.
3 MC SHALL FURNISH & INSTALL NEW PACKAGED GAS-FIRED HEATING / DIRECT
EXPANSION (DX) COOLING WITH HOT GAS REHEAT UNIT (RTU-DETECTIVE OFFICE) AS
SHOWN. PROVIDE SIDE SUPPLY & RETURN DUCTWORK CONNECTIONS FOR NEW
UNIT. APPROVED ROOFTOP UNIT MANUFACTURER SHALL PROVIDE NEW THY CURB
SUPPORTS FOR UNIT.
4 MC SHALL PROVIDE 72" NEW THY CURB SUPPORTS FOR NEW ROOFTOP UNIT TO GC
FOR GC TO INSTALL & FLASH WITH MC PRESENT. MC SHALL THEN FURNISH &
INSTALL NEW ROOFTOP UNIT ON NEW SUPPORTS. MC SHALL PROVIDE TIE DOWN
CLIPS TO UNIT TO FASTEN UNIT AS PER THE REQUIREMENTS OF THE APPROVED
ROOFTOP UNIT MANUFACTURER.
5 MC SHALL HAVE PC INSTALL NEW 1-1/4"Ø NEW NATURAL GAS PIPING FOR NEW
ROOFTOP UNIT & RUN AS SHOWN & PROVIDE A NEW GAS SHUT OFF COCK & THEN
PROVIDE A DIRT LEG POCKET BEFORE CONNECTING PIPING TO NEW ROOFTOP UNIT.
PC SHALL PROVIDE GAS PIPING SUPPORTS FOR NEW GAS PIPING WHICH ARE
MIRO-INDUSTRIES OR EQUIVALENT. REFER TO DETAILS SECTION FOR ADDITIONAL
INFORMATION.
EXISTING
RTU-5
RTU-DETECTIVE
OFFICE
1-1/4"Ø
1-1/4"Ø
6 MC TO HAVE GC FURNISH & INSTALL NEW KEE-RAIL BALLASTED ROOF EDGE
GUARDRAIL SYSTEM.
SINGLE-PRIME CONTRACTOR BID NOTES:
1. THIS PROJECT SHALL BE A "SINGLE-PRIME" CONTRACTOR BID. THE PRIME
CONTRACTOR SHALL BE THE GENERAL CONTRACTOR (GC). THE GC SHALL BE
SUB-CONTRACTORS THAT INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOWING, MECHANICAL CONTRACTOR (MC), PLUMBING CONTRACTOR (PC),
ELECTRICAL CONTRACTOR (EC), ETC. THE MC, PC, & EC SHALL ALL BE
SUB-CONTRACTORS FOR THE PRIME CONTRACTOR WHICH SHALL BE THE GC.
2. ALL REFERENCES SHOWN ON PLANS FOR "MC" AND "EC" SHALL BE THE
RESPONSIBILITY OF THE SINGLE-PRIME CONTRACTOR (GC) WHO SHALL BE
PREPARED BY BBS ARCHITECTS, LANDSCAPE ARCHITECTS AND
ENGINEERS, PC. AND, THEREFORE, MAY NOT REPRESENT THE
CONDITIONS AS CONSTRUCTED AT THE TIME. ALL EXISTING
CONDITIONS SHOWN ARE REPRESENTED AS SUGGESTIVE
INFORMATION AS THEY MAY NOT HAVE BEEN BUILT AND DETAILED
PER THE ORIGINAL DOCUMENTS OR PER THE OWNER'S INFORMATION.
ME
CH
AN
IC
AL
SC
HE
DU
LE
S
U.F.
U.F.
AS-NOTED
MECHANICAL
SCHEDULES
M6.01
244 EAST MAIN STREET
PATCHOGUE
NEW YORK 11772
T. 631.475.0349 F. 631.475.0361
187 WOLF ROAD, STE. 205
ALBANY
NEW YORK 12205
T. 518.621.7650 F. 518.621.7655 bbs
ARCHITECTS
LANDSCAPE ARCHITECTS
ENGINEERS
www.BBSARCHITECTURE.com
DATE
PR
OJ
EC
T
DW
G
TI
TL
E
DRAWING BY:
CHECK BY:
REV. ITEM
NOTICE
THIS DRAWING, PREPARED FOR THE SPECIFIC PROJECT INDICATED IS
AN INSTRUMENT OF SERVICE AND THE PROPERTY OF BBS
ARCHITECTS, LANDSCAPE ARCHITECTS AND ENGINEERS, PC.
INFRINGEMENT OR ANY USE OF THIS DRAWING FOR ANY OTHER
PROJECT IS PROHIBITED. ANY ALTERATION OR REPRODUCTION OF
THIS DOCUMENT IS ALSO PROHIBITED WITHOUT THE WRITTEN
CONSENT OF THE ARCHITECT OR ENGINEER.
FILE No:
BID PICK-UP:
DATE:
SCALE:
OWNER
PROJECT
DWG TITLE
BUILDING No.
ALTERATION OF THIS DOCUMENT, UNLESS
UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, IS A
VIOLATION OF SECTION 7209 OF ARTICLE
145 OF THE NYS EDUCATION LAW
KEY PLAN
NOT TO SCALE
TO
W
N
OF
G
RE
EN
BU
RG
H
DE
PA
RT
ME
NT
O
F
PU
BL
IC
W
OR
KS
PO
LIC
E
DE
PA
RT
ME
NT
H
VA
C
IM
PR
OV
EM
EN
TS
TO
W
N
OF
G
RE
EN
BU
RG
H
/ W
ES
TC
HE
ST
ER
C
OU
NT
Y
/ N
EW
Y
OR
K
TOWN OF GREENBURGH
DEPT. OF PUBLIC WORKS
POLICE DEPARTMENT
HVAC IMPROVEMENTS
JULY 31, 2026
SCHEDULE NOTES:
1. PROVIDE ROOF THY CURB SUPPORTS FOR PROPOSED ROOFTOP UNIT. MC SHALL HAVE APPROVED ROOFTOP
FACTORY-AUTHORIZED MANUFACTURER VISIT JOB SITE AND TAKE MEASUREMENTS OF EXISTING ROOF CURB & EXISTING SUPPLY & RETURN DUCT DROPS WITHIN ROOF PRIOR TO FURNISHING A DETAILED SUBMITTAL
FOR REVIEW & APPROVAL PROCESS.
2. PROVIDE ECONOMIZER HOOD.
3. PROVIDE RELIEF/BAROMETRIC DAMPER HOOD.
4. PROVIDE HOT GAS REHEAT COIL.
5. PROVIDE GAS FURNACE.
6. PROVIDE FACTORY ASSEMBLED DISCONNECT SWITCH WITHIN UNIT CASING.
7. PROVIDE VFD (VARIABLE FREQUENCY DRIVE) FOR FAN MOTOR WITHIN UNIT CASING. FOR EXTERNAL VFD, ENCLOSURE SHALL BE NEMA 4X RATED.
8. PROVIDE 7-DAY PROGRAMMABLE THERMO/HUMIDISTAT FOR UNIT. MC RESPONSIBLE TO PROVIDE POWER FOR
NEW THERMO/HUMIDISTAT.
9. PROVIDE OUTDOOR AIR ENTHALPY BASED ECONOMIZER.
10. PROVIDE FACTORY-AUTHORIZED MANUFACTURER'S REPRESENTATIVE TO BE PRESENT FOR START-UP, COMMISSIONING, & TRAINING OF NEW EQUIPMENT TO OWNER'S DESIGNATED PERSONNEL.
11. PROVIDE POWER CONVENIENCE OUTLET WITH NEW ROOFTOP UNIT.
12. PROVIDE MICRO-PROCESSOR CONTROLLER FOR UNIT.
13. PROVIDE FACTORY-CONTROLS FOR UNIT.
14. UNIT SHALL BE CONSTANT VOLUME APPLICATION FOR DESIGN AIRFLOW TO SPACE SERVED BY IT.
15. PROVIDE P-TRAP FOR UNIT.
16. PROVIDE TIE DOWN CLAMPS FOR EQUIPMENT ON TO SUPPORTS/RAILS.
17. PROVIDE HIGH-STATIC FOR NEW UNIT.
ROOF MOUNTED GAS PIPING SUPPORT DETAIL
SCALE: N.T.S.
ROOF
GALVANIZED
SHEETMETAL
DUCTWORK
EMBOSSED WHITE, MULTI-LAYERED REINFORCED
LAMINATE SELF-ADHERING INSULATION JACKETING
TAPE. MFM BUILDING PRODUCTS, CORP.,
FLEXCLAD-250, 36" - 52836, 25 MILS THICK OR EQUAL.
MINIMUM 6" JOINT SEAM OVERLAP. FOLLOW
MANUFACTURED INSTALLATION INSTRUCTIONS.
2" THICK EXTRUDED POLYSTYRENE RIGID FOAM
INSULATION BOARD. OWENS-CORNING
FORMULAR-250 OR EQUAL. TYPICAL ALL FOUR (4)
SIDES. INSULATION TO BE GLUED & STUD
WELDED & CLIPPED TO DUCT.
COMPRESSIVE STRENGTH - FOAMULAR-250 =
25PSI.
ENCLOSED POLYCARBONATE PIPE STANDS AS
MANUFACTURED BY MIRO INDUSTRIES MODEL
10-DS WITH SWIVEL BASES & RUBBER SUPPORT
PADS WITH ETERNABOND DOUBLESTICK
MICROSEALANT PUTTY TAPE OR APPROVED
EQUAL.
1/2" - 1-1/2" TAPERED PANEL SIZE EXTRUDED
POLYSTYRENE RIGID FOAM INSULATION BOARD,
OWENS CORNING TAPERED FOAMULAR
THERMAPINK 25 OR EQUAL. BUILD-UP & TAPER
AT 1/2" PER FOOT SLOPE MINIMUM.
COMPRESSIVE STRENGTH -
FOAMULAR-THERMAPINK 25 = 25PSI
DUCTWORK DIMENSIONS SHOWN ON DRAWINGS
ARE "CLEAR" INSIDE DIMENSIONS.
PROVIDE ALUMINUM EDGE/CORNER/ CLOSE-OFF
ANGLES & ADHERED WITH MEMBRANE TAPE
EXTERIOR DUCTWORK INSULATION WITH SUPPORTS
SCALE: N.T.S.
RE
V.
1-
NEW UNIT GAS CONNECTION DETAIL
NOTE: DIRT LEG TO BE
INSTALLED WITH ROOM
FOR MAINTENANCE
NOT TO SCALE
ROOF ROOF
NEW UNIT
GAS LINE IN
PLUG
2" LOCK SHIELD GAS COCK
DIRT LEG
LOCK SHIELD GAS COCK
"UL" LISTED FLEX CONNECTOR
NEW PACKAGED GAS-FIRED ROOFTOP WITH DX COOLING & HOT
GAS REHEAT (RTU-DETECTIVE OFFICE) SCHEDULE (BASIS: TRANE)
NEW TREATED WOOD BLOCKING BY
EQUIPMENT RAIL MANUFACTURER
NEW GALVANIZED COUNTER FLASHING
BY EQUIPMENT RAIL MANUFACTURER
NEW EQUIPMENT RAIL SYSTEM WITH INTEGRAL BASE
PLATE BY 'THYBAR CORP.' MODEL TEMS-3, 18" HIGH
OR ARCHITECT APPROVED EQUAL
" R
AI
L
G.C. TO REMOVE AND INSTALL NEW
ROOF SYSTEM COMPONENTS TO
MATCH EXISTING AS REQUIRED TO
INSTALL NEW PIPE PORTAL (TYP.)
EXISTING ROOF SYSTEM TO REMAIN.
G.C. TO MAINTAIN THE EXISTING ROOF
WARRANTY. G.C. TO PROCURE A ROOF
SYSTEM MANUFACTURERS CERTIFIED
ROOFER TO CUT OPENINGS IN ROOFING
AND ROOF DECK FOR THE M.C.
G.C. TO INSTALL AND FLASH NEW PIPE
PENETRATION ASSEMBLY SUPPLIED BY THE
M.C., G.C. SHALL COORDINATE WITH M.C.
EQUIPMENT RAIL DETAIL (BY GC)
NOTE: EXISTING ROOF
INSTALLATION
SCALE: N.T.S.
EXISTING ROOF DECK
TO REMAIN, V.I.F. (TYP.)
NEW LIQUID APPLIED SP FLASHING SYSTEM,
COMPATIBLE WITH EXIST'G ROOF SYSTEM (TYP.)
SINGLE-PRIME CONTRACTOR BID NOTES:
1. THIS PROJECT SHALL BE A "SINGLE-PRIME" CONTRACTOR BID. THE PRIME
CONTRACTOR SHALL BE THE GENERAL CONTRACTOR (GC). THE GC SHALL BE
SUB-CONTRACTORS THAT INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOWING, MECHANICAL CONTRACTOR (MC), PLUMBING CONTRACTOR (PC),
ELECTRICAL CONTRACTOR (EC), ETC. THE MC, PC, & EC SHALL ALL BE
SUB-CONTRACTORS FOR THE PRIME CONTRACTOR WHICH SHALL BE THE GC.
2. ALL REFERENCES SHOWN ON PLANS FOR "MC" AND "EC" SHALL BE THE
RESPONSIBILITY OF THE SINGLE-PRIME CONTRACTOR (GC) WHO SHALL BE
THE CONTRACTOR OF RECORD.
6" TYP.
6" OVERLAP
TYP.
VE
RI
FY
IN
F
IE
LD
PREPARED BY BBS ARCHITECTS, LANDSCAPE ARCHITECTS AND
ENGINEERS, PC. AND, THEREFORE, MAY NOT REPRESENT THE
CONDITIONS AS CONSTRUCTED AT THE TIME. ALL EXISTING
CONDITIONS SHOWN ARE REPRESENTED AS SUGGESTIVE
INFORMATION AS THEY MAY NOT HAVE BEEN BUILT AND DETAILED
PER THE ORIGINAL DOCUMENTS OR PER THE OWNER'S INFORMATION.
EL
EC
TR
IC
AL
GE
NE
RA
L_
NO
TE
S_
AN
D_
LE
GE
ND
S
M.C.
M.C.
AS-NOTED
ELECTRICAL_GENERAL_NOTES
AND_LEGENDS
E0.01
244 EAST MAIN STREET
PATCHOGUE
NEW YORK 11772
T. 631.475.0349 F. 631.475.0361
187 WOLF ROAD, STE. 205
ALBANY
NEW YORK 12205
T. 518.621.7650 F. 518.621.7655 bbs
ARCHITECTS
LANDSCAPE ARCHITECTS
ENGINEERS
www.BBSARCHITECTURE.com
DATE
PR
OJ
EC
T
DW
G
TI
TL
E
DRAWING BY:
CHECK BY:
REV. ITEM
NOTICE
THIS DRAWING, PREPARED FOR THE SPECIFIC PROJECT INDICATED IS
AN INSTRUMENT OF SERVICE AND THE PROPERTY OF BBS
ARCHITECTS, LANDSCAPE ARCHITECTS AND ENGINEERS, PC.
INFRINGEMENT OR ANY USE OF THIS DRAWING FOR ANY OTHER
PROJECT IS PROHIBITED. ANY ALTERATION OR REPRODUCTION OF
THIS DOCUMENT IS ALSO PROHIBITED WITHOUT THE WRITTEN
CONSENT OF THE ARCHITECT OR ENGINEER.
FILE No:
BID PICK-UP:
DATE:
SCALE:
OWNER
PROJECT
DWG TITLE
BUILDING No.
ALTERATION OF THIS DOCUMENT, UNLESS
UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER, IS A
VIOLATION OF SECTION 7209 OF ARTICLE
145 OF THE NYS EDUCATION LAW
KEY PLAN
NOT TO SCALE
TO
W
N
OF
G
RE
EN
BU
RG
H
DE
PA
RT
ME
NT
O
F
PU
BL
IC
W
OR
KS
PO
LIC
E
DE
PA
RT
ME
NT
H
VA
C
IM
PR
OV
EM
EN
TS
TO
W
N
OF
G
RE
EN
BU
RG
H
/ W
ES
TC
HE
ST
ER
C
OU
NT
Y
/ N
EW
Y
OR
K
TOWN OF GREENBURGH
DEPT. OF PUBLIC WORKS
POLICE DEPARTMENT
HVAC IMPROVEMENTS
JULY 31, 2026
1. THE ITEMS SPECIFICALLY SHOWN ON THE DEMOLITION DRAWINGS ARE TO BE ADDRESSED BY THE ELECTRICAL CONTRACTOR. THE ITEMS ARE TO BE TREATED AS NOTED AND RANGE FROM DIRECT
REMOVAL AND DISPOSAL TO REMOVAL, STORAGE AND REINSTALLATION
2. MANY OTHER ELECTRIC ITEMS EXIST THAT ARE NOT SHOWN INCLUDING, BUT ARE NOT LIMITED TO, SWITCHES, RECEPTACLES, FLOOR OUTLETS, LOW VOLTAGE JACKS, LOW VOLTAGE DEVICES AND WIRING, TELEPHONE PUNCH DOWN BLOCKS, AND OUT OF SERVICE ITEMS. ALL SUCH ITEMS SHALL BE
PERMANENTLY DE-ENERGIZED, DISCONNECTED, AND OTHERWISE MADE SAFE FOR DEMOLITION BY NON-ELECTRICAL CONTRACTORS. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ASSURING THAT ALL ELECTRIC DEVICES SCHEDULED FOR DEMOLITION, OF ANY VOLTAGE OR FUNCTION, ARE SAFE AND
ADVISE THE OTHER CONTRACTORS.
3. AFTER THE ELECTRICAL CONTRACTOR HAS DISCONNECTED ELECTRIC SUPPLIES TO ITEMS TO BE DEMOLISHED, HE SHALL ADVISE THE GENERAL CONTRACTOR OF ANY ELECTRIC ITEMS TO BE RETAINED FOR FUTURE USE AND THEREFORE NOT TO BE DEMOLISHED. THE GENERAL CONTRACTOR SHALL THEN PERFORM ALL WORK ZONE DEMOLITION. THIS MATTER APPLIES TO ALL ELECTRIC ITEMS, OF ANY VOLTAGE
OR PURPOSE.
4. THE SPECIAL/SPECIFIC ITEMS SHOWN ON THE DRAWING FOR ELECTRICAL CONTRACTOR TO ACT ON WERE FOUND BY SURVEY. NUMEROUS LOCATIONS WERE BLOCKED BY FURNITURE, ETC. AND ADDITIONAL EQUAL TYPE ITEMS MAY BE PRESENT. THE ELECTRICAL CONTRACTOR SHALL ALLOW FOR THIS IN HIS BID PRICE
AND ATTEND TO THOSE EQUAL OR SIMILAR DEVICES AS MAY BE DISCOVERED.
5. REMOVAL ITEMS THAT ARE LISTED AS TO BE TURNED OVER TO OWNER'S INVENTORY SHALL BE DISCUSSED WITH THE OWNERS BUILDINGS AND GROUNDS MANAGER. THOSE ITEMS THAT THE OWNER DECLINES SHALL THEN BE DISPOSED OF BY THE CONTRACTOR IN THE MANNER OF OTHER PERMANENT REMOVALS.
ANY PCB BEARING FLUORESCENT FIXTURES SHALL BE DISPOSED OF PER REGULATIONS.
6. THE ELECTRICAL CONTRACTOR SHALL COVER ALL BACK BOXES IN THE WALL THAT BECOME EXPOSED DUE TO DEVICE REMOVALS. THIS INSTRUCTION ALSO APPLIES TO EXPOSED ELECTRICAL BACK BOXES AS MAY EXIST AT THE SITE PRIOR TO THIS PROJECT. THE COVER SHALL BE BRUSHED ALUMINUM WITH CHAMFERED EDGES AND COVER THE HOLE COMPLETELY WITH AT LEAST 3/4" EXTRA MARGIN ON ALL SIDES. MOUNT THE
COVER WITH SCREWS TO MATCH THE ORIGINAL PATTERN.
7. IT IS EXPECTED THAT STRUCTURAL DEMOLITION BY THE GENERAL CONTRACTOR WILL CAUSE VARIOUS ELECTRIC SUPPLIES, OF VARIOUS VOLTAGES AND PURPOSES, TO BE CUT AND RENDER SOME DEVICES TEMPORARILY INACTIVE. IT IS THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO RECONSTRUCT AND
RECONNECT SUCH ELECTRIC SOURCES WHEN THE NEW STRUCTURE IS BUILT. NOTE THAT MOST
REINSTALLED ITEMS WILL BE IN DIFFERENT LOCATIONS FROM THE REMOVAL LOCATION. THE ELECTRICAL CONTRACTOR SHALL MAKE ALL REQUIRED CIRCUIT EXTENSIONS OR MODIFICATIONS TO PROVIDE SERVICE TO A REINSTALLED ITEM AS RELOCATED. PROVIDE ALL REQUIRED CIRCUIT EXTENSIONS AS REQUIRED TO RESTORE SERVICE TO DEVICES. NOTE THAT THIS REQUIREMENT ALSO APPLIES TO THE ROOMS AND ELECTRICAL ITEMS WITHIN THAT ARE NOMINALLY NOT IN CONTRACT. SUCH RESTORATION OF SERVICE, IF
NEEDED, IS SPECIFICALLY IN THE ELECTRICAL CONTRACTOR'S CONTRACT.
8. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO PROTECT ALL ELECTRICAL DEVICES, FROM DAMAGES DURING CONSTRUCTION, WHICH ARE EITHER INDICATED TO REMAIN, AND/OR TO BE REMOVED AND REINSTALLED THROUGHOUT ALL CONSTRUCTION AREAS. DEVICES SHALL INCLUDE BUT WILL NOT BE LIMITED TO: SMOKE DETECTORS, EMERGENCY LIGHTS, EXIT SIGNS, OCCUPANCY SENSORS, SPEAKERS, LIGHT FIXTURES, SWITCHES, RECEPTACLE, ETC. IN THE EVENT OF DAMAGES INCURRED DUE TO CONSTRUCTION ACTIVITIES, THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REPLACE ANY
DAMAGED DEVICES AT NO ADDITIONAL COST TO THE OWNER.
9. ALL SYSTEMS ASSOCIATED WITH THE DEVICES SCHEDULED TO BE REMOVED, STORED AND PROTECTED SHALL BE TESTED BY THE MANUFACTURER'S CERTIFIED TESTING VENDOR PRIOR TO ANY DEMOLITION ACTIVITY. ANY DEVICE WHICH FAILS THE TEST SHALL BE REPLACED WITH A FORM, FIT AND FUNCTION COMPONENT PER UNIT PRICES, AND SUCH DEVICES ARE NOT INCLUDED IN THIS RESPONSIBILITY STATEMENT, BUT ALSO SUCH INSTALLATION SHALL BE IN THE ELECTRICAL CONTRACTOR'S BASE BID. THE
ELECTRICAL CONTRACTOR SHALL RE-TEST ALL SUCH SYSTEM COMPONENTS BY A MANUFACTURER
CERTIFIED TESTING VENDOR OF SUCH SYSTEM OF ALL PREVIOUSLY TESTED SYSTEM COMPONENTS AFTER ALL WORK BY ALL TRADES HAS BEEN COMPLETED, AND ALL SYSTEM COMPONENTS HAVE BEEN INSTALLED.
ANY COMPONENT WHICH FAILS SHALL BE REPLACED, AND PROGRAMMED IF NECESSARY BY THE
ELECTRICAL CONTRACTOR. ALL SUCH REPLACEMENT AND PROGRAMMING COSTS SHALL BE ELECTRICAL CONTRACTOR'S RESPONSIBILITY. ALL COSTS ASSOCIATED WITH THE TESTING OF AFFECTED SYSTEM SUCH AS BUT NOT LIMITED TO FIRE ALARM, PUBLIC ADDRESS, INTERCOM, TELEPHONE, AND SECURITY SYSTEMS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. ALL EQUIPMENT, DEVICES, WIRING AND THEIR ASSOCIATED MATERIAL SPECIFIED TO REMAIN, WHICH IS NOT STORED AND PROTECTED, SHALL BE PROTECTED DURING THE DEMOLITION ACTIVITIES, AND ALL TRADES SHALL BE INFORMED OF SUCH COMPONENTS. ANY OF SUCH COMPONENTS WHICH BECOME DAMAGED DURING DEMOLITION SHALL
BE REPLACED FORM, FIT AND FUNCTION BY THE ELECTRICAL CONTRACTOR AT HIS EXPENSE.
DEMOLITION NOTES
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTING IN THE CONSTRUCTION
AREAS OF THE PROJECT.
2. ALL TEMPORARY POWER PANELS AND FUSED SWITCHES OUTDOORS SHALL BE NEMA 3R CONSTRUCTION
AND LOCKABLE. ALL OUTDOOR RECEPTACLES SHALL BE WATERPROOF AND HAVE A COVER THAT
ENCLOSES THE PLUGGED IN CORDS WHILE IN SERVICE AS 'INTERMATIC WP1020C'. NON-WATERPROOF
GEAR IN A HOUSING IS NOT ACCEPTABLE.
3. ALL RECEPTACLES SHALL BE GFCI PROTECTED AND MOUNTED 3'-0" ABOVE FINISHED FLOOR. PROVIDE WORK BLOCKING AS REQUIRED. ALL RECEPTACLES OUTLETS SHALL BE 2 GANG DOUBLE DUPLEX.
4. TEMPORARY LIGHTING SHALL BE CONSTRUCTED OF SINGLE AND DOUBLE 100 WATT CLEAR INCANDESCENT
LAMPS, OR EQUIVALENT, AND WATERPROOF RUBBER SOCKETS, SPLICED WITH WATERPROOF
CONNECTORS ON FESTOONED ROMEX-TYPE WIRE. ADEQUACY OF ALL TEMPORARY LIGHTING
CONFIGURATIONS SHALL BE AS DETERMINED BY THE CONSTRUCTION MANAGER. PRE ASSEMBLED
TEMPORARY LIGHTING IS DISALLOWED. TAPS AND SPLICES SHALL BE MADE WITH SCOTCH LOCK CONNECTORS, RUBBER TAPE, AND THEN PVC COATED. THE CONNECTORS SHALL BE FILLED WITH PENETROX. A PLASTIC SHAPE ON CAGE/GUARD SHALL PROTECT EACH SOCKET AND LAMP. NOMINAL SPACING BETWEEN LAMP CLUSTER IS 16 FEET. MOUNT LIGHTS EIGHT FEET ABOVE FINISHED FLOOR IN TYPICAL LOCATIONS AND 10 FEET ABOVE FINISHED FLOOR IN CORRIDOR. PROVIDE NIGHT LIGHTING CIRCUIT, WHICH SHALL OPERATE CONTINUOUSLY. ALL LAMPS SHALL BE 130 VOLT, ROUGH SERVICE RATED.
TEMPORARY LIGHTS SHALL BE TO OSHA STANDARDS. ALTERNATE FIXTURES SHALL BE 400W
CONSTRUCTION SITE STYLE
5. WIRING SHALL BE 1#12+1#12(N)+1#12(G) ROMEX STYLE. CIRCUITS SHALL BE OPERATED A MAXIMUM OF 15 AMPS OR 1800 WATTS (18 100 WATT LAMPS), SWITCHING SHALL BE DONE VIA THE SWITCH RATED 20A, 10 CIRCUIT BREAKERS. SEGREGATE THE NIGHT LIGHTS AND RECEPTACLES IN THE LOWER PART OF THE POWER PANELS AND LABEL THESE "DO NOT TURN OFF" . CIRCUIT HOME RUNS CONDUCTORS SHALL INCREASE ONE WIRE SIZE EVERY 100 FEET I.E. #10 CONDUCTORS. WIRING WITHIN THE ROOM AREA SHALL
BE MADE WITH #12 CONDUCTORS.
6. THE ELECTRICAL CONTRACTOR SHALL PREPARE EACH PANEL SCHEDULE.
7. A LENGTH OF GREENFIELD FLEX CONDUIT AT PINCH POINTS SHALL PROTECT ALL WIRE, SUCH AS WHERE WIRING PASSES THROUGH A DOORWAY. WIRING SHALL BE SUPPORTED FROM ANCHORS INSTALLED BY THE ELECTRICAL CONTRACTOR FOR THE PURPOSE OF THIS PROJECT. ALL ELECTRICAL HARDWARE SHALL BE
NEW FOR THIS PROJECT.
8. ALL WIRING SHALL BE INSTALLED SO AS NOT TO CAUSE TRIPPING HAZARD OR SIMILAR OBSTRUCTION.
9. POWER PANELS SHALL BE EQUIPPED WITH 42 1P, 20A CIRCUIT BREAKERS AND ALL CIRCUIT BREAKERS NOT IN SERVICE SHALL BE LABELED SPARE. AT THE OWNERS OPTION PANEL AND CIRCUIT BREAKERS SHALL BE TURNED OVER TO OWNERS INVENTORY AT CONCLUSION OF THE PROJECT. ALL ELECTRICAL HARDWARE
SHALL BE NEW FOR THIS PROJECT.
10. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MAINTENANCE OF TEMPORARY LIGHTING AND POWER SYSTEMS DURING,…